Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2023-10-16 08:28:15
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1385.62 | 5963.69 | 5963.69 |
Net Site Energy | 1385.62 | 5963.69 | 5963.69 |
Total Source Energy | 2300.55 | 9901.51 | 9901.51 |
Net Source Energy | 2300.55 | 9901.51 | 9901.51 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 356.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 21.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 239.49 | 451.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 54.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 194.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 36.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 383.36 | 1002.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 356.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 20.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 21.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 10.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 220.85 | 451.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 54.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 194.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 10.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 17.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 356.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 20.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 21.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 10.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 239.49 | 451.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 54.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 194.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 36.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 137.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 324.06 | 2370.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1188.49 | 1942.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1649.96 | 4313.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 137.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 324.06 | 2370.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1188.49 | 1942.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1649.96 | 4313.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 383.358 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 383.358 | 100.00 |
Total On-Site and Utility Electric Sources | 383.358 | 100.00 |
Total Electricity End Uses | 383.358 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.33 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3570.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 4.0792 | 1.33 | 110.4804 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.6205 | 18.52 | 1009.9592 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 6.8498 | 2.48 | 560.2198 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 6.8498 | 2.48 | 560.2198 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 4.0792 | 1.33 | 110.4804 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.6205 | 18.52 | 1009.9592 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 6.8498 | 1.24 | 560.2198 | |||||||
Conditioned Total | 232.34 | 6.8498 | 1.24 | 560.2198 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 6.8498 | 2.48 | 560.2198 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-12:00 | 10-JAN-20:00 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 112802.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12884.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 989.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 11230.28 | 17393.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2918.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 10233.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1184.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 29206.02 | 140429.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 112802.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 12884.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 989.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 10639.48 | 17393.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 2918.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 10233.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 363.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 626.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 386.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 66.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 67.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 33.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 758.45 | 489.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 172.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 210.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 116.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1214.09 | 1086.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1662.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 285.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 289.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 145.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3264.36 | 2105.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 740.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 908.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 499.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5225.44 | 4676.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1662.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 285.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 289.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 145.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3264.36 | 2105.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 740.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 908.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 499.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5225.44 | 4676.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.90 |
KITCHEN DIRECT AIR | 1.21 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.90 | 1.90 | 1.90 | 1.90 | 1.90 | 1.90 | 1.00 | 1.00 | 1.90 |
PSZ-AC_2:2 | 1.21 | 1.21 | 1.21 | 1.21 | 1.21 | 1.21 | 1.00 | 1.00 | 1.21 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.90 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.21 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.90 | 2027.80 |
PSZ-AC_2:2_ADDAQ FAN | 1.21 | 1338.27 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.90 | 1.90 | 1.90 | 1.25 | 33006.58 | 61482.23 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.21 | 1.21 | 1.21 | 0.797772 | 28738.09 | 83202.95 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.90 | 0.947529 | 1.26 | 33006.58 | 16503.29 | 0.800420 | 0.800420 |
PSZ-AC_2:2 COOLING COIL | 1.21 | 0.604373 | 0.805833 | 28738.09 | 14369.05 | 0.714980 | 0.714980 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 61482.23 |
PSZ-AC_2:2 HEATING COIL | 83202.95 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 4.079 | 110.480 | 0.000 | 0.000 | 0.000 | 0.000 | 114.560 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.620 | 261.340 | 748.620 | 0.000 | 0.000 | 0.000 | 1019.580 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 473.883 | 4.079 | 5.413 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 473.883 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1117.624 | 9.620 | 178.156 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1117.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 12834.676 | 110.480 | 146.608 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3722.056 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 29769.412 | 256.254 | 4745.415 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 8633.129 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 277.500 | 2.389 | 44.235 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 313.300 | 2.697 | 49.942 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 86968.240 | 748.620 | 13863.236 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 25220.790 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.4002 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2403 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2403 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.265 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.085 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.085 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.36497932E-12 | 0.65593627E-15 | -0.12833793E-12 | 0.14057672E-15 |
34 | 6 | 0.33075537E-07 | 0.11699647E-09 | 0.75401566E-08 | -0.15914535E-12 |
35 | 5 | -0.21222498E-03 | 0.97557935E-06 | -0.10882611E-03 | 0.74384351E-08 |
36 | 4 | 0.31766798 | 0.46388355E-03 | 0.10887901 | -0.37209111E-04 |
37 | 3 | -7.7709266 | 0.14076565E-01 | -2.4887051 | 0.31484223E-01 |
38 | 2 | 42.534380 | 0.49126722E-01 | 15.877466 | -0.35186973 |
39 | 1 | -81.819330 | 0.21810079E-01 | -29.690133 | 1.1057606 |
40 | 0 | 46.824331 | 0.43177108E-03 | 16.278511 | |
41 | 7 | -0.17492660E-08 | -0.39206577E-15 | 0.56910466E-14 | -0.74880728E-16 |
42 | 6 | 0.67235958E-05 | 0.46061729E-08 | 0.31866593E-02 | -0.26732369E-04 |
43 | 5 | -0.48404724E-03 | 0.27298576E-05 | -0.22354209 | 0.19545396E-02 |
44 | 4 | 0.11137682E-01 | 0.12426572E-03 | 4.8265062 | -0.45235764E-01 |
45 | 3 | -0.97815318E-01 | 0.98833577E-03 | -38.004246 | 0.39846397 |
46 | 2 | 0.34733640 | 0.16441863E-02 | 116.45053 | -1.4174923 |
47 | 1 | -0.50133706 | 0.50116224E-03 | -143.88764 | 2.0487166 |
48 | 0 | 0.24442836 | 0.12066061E-04 | 60.838472 | |
49 | 7 | -0.17492660E-08 | -0.39206577E-15 | 0.56910466E-14 | -0.74880728E-16 |
50 | 6 | 0.67235958E-05 | 0.46061729E-08 | 0.31866593E-02 | -0.26732369E-04 |
51 | 5 | -0.48404724E-03 | 0.27298576E-05 | -0.22354209 | 0.19545396E-02 |
52 | 4 | 0.11137682E-01 | 0.12426572E-03 | 4.8265062 | -0.45235764E-01 |
53 | 3 | -0.97815318E-01 | 0.98833577E-03 | -38.004246 | 0.39846397 |
54 | 2 | 0.34733640 | 0.16441863E-02 | 116.45053 | -1.4174923 |
55 | 1 | -0.50133706 | 0.50116224E-03 | -143.88764 | 2.0487166 |
56 | 0 | 0.24442836 | 0.12066061E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.342_SHGC_SOUTH_0.379 | 38 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
2 | NONRESWINDOW_U_0.342_SHGC_NORTH_0.379 | 39 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
3 | NONRESWINDOW_U_0.342_SHGC_EAST_0.379 | 40 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
4 | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 41 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.238 | 0.3637 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 1.853E-002 | 1.595E-004 | 1.994E-004 | 0.188 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.584 | 5.025E-003 | 6.281E-003 | 5.934 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 1.853E-002 | 1.595E-004 | 1.953E-004 | 0.188 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.8190E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.1212E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.6610E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.9396E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.2883E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.2624E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.6373E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.6408E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.1665E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.0333E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 9.5828E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 9.4295E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 4.7826E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.6965E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.7751E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.7751E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.7823E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.3753E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.5101E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.0834E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.8423E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.9257E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6410E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.6373E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 18759.38602 | 22511.26323 | 1.57921 | 1.89506 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40000 | 6.30683E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 6954.55361 | 8345.46433 | 0.33861 | 0.41606 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -27.60000 | 3.41898E-004 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 14359.20853 | 17231.05024 | 1.00729 | 1.20875 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31.96000 | 6.30459E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 1242.80397 | 1491.36477 | 5.40878E-002 | 1.14133 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -27.60000 | 3.41898E-004 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 26414.73 | 1.89506 | 1.89506 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 29763.89 | 0.41606 | 0.41606 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 24881.17 | 1.20875 | 1.20875 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 81648.89 | 1.14133 | 1.14133 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.89506 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.20875 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.89506 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.89506 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.89506 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.89506 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.89506 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.89506 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.20875 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.20875 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.20875 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20875 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.20875 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.20875 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.89506 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.20875 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.89506 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.89506 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2027.80126 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.89506 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.89506 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.89506 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.25074 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.89506 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.94753 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.26337 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33006.58000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16503.29000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80042 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80042 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33006.58000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 61482.22992 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 61482.22992 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.20875 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.20875 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1338.27379 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.20875 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.20875 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.20875 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.79777 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.20875 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.60437 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.80583 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28738.09000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14369.04500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71498 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71498 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28738.09000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 83202.95415 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 83202.95415 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 31624.2 | 11.13 | 11.08 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 27875.7 | 11.76 | 11.71 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.400 | 0.378 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.400 | 0.378 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.400 | 0.378 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.240 | 0.227 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.400 | 0.378 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.400 | 0.378 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.400 | 0.378 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.240 | 0.227 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 8.9512330218E-002 | 0.3658428063 | Pass | Pass | 1.1383991116 | 7.4626585229 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1658713450 | 0.6044072057 | Pass | Pass | 3.1885558382E-002 | 9.1035725443E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.3053348483 | 0.3422388763 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 472.39 | 134.84 | 1086.45 | 8.51 | 364.88 | 2067.09 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.378 | 0.400 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.378 | 0.400 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.378 | 0.400 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.231 | 0.240 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.378 | 0.400 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.378 | 0.400 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.378 | 0.400 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.231 | 0.240 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.342_SHGC_EAST_0.379 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 1.943 | 0.380 | 0.418 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.342_SHGC_SOUTH_0.379 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 1.943 | 0.380 | 0.418 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 1.943 | 0.380 | 0.418 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 1.943 | 0.380 | 0.418 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 4.0792 | 116.17 | 473.88 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 43.23 | 0.0000 | Y | 3.85 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.6205 | 116.17 | 1117.62 | LightsWired | LTG_SCH_KITCHEN | 86.84 | 168.00 | 82.89 | 0.0000 | Y | 17.39 |
Interior Lighting Total | 6.8498 | 232.34 | 1591.51 | 21.23 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 473.88 | 180.08 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 473.88 | 180.08 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 209.35 | AstronomicalClock | - | 49.11 | 49.11 | 1.93 | |
EXTERIOR_LIGHTS_B | 742.80 | AstronomicalClock | - | 83.57 | 62.84 | 8.76 | |
Exterior Lighting Total | 952.15 | 10.69 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33006.58 | 26419.13 | 6587.45 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28738.09 | 20547.16 | 8190.93 | 0.71 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 31624.2 | 11.13 | 11.08 | ||||
PSZ-AC_2:2 COOLING COIL | 27875.7 | 11.76 | 11.71 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 61482.23 | 0.84 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 83202.95 | 0.85 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.90 | 2027.80 | 1070.05 | 1.00 | 1.32 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.21 | 1338.27 | 1107.16 | 1.00 | 1.36 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.95 | 1.24 | 0.36 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 18759.39 | 22511.26 | 193.78 | 1.579 | 1.895 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.88 | 0.00774 | 33.40 | 0.00631 | 0.416 | 0.00 |
KITCHEN | 14359.21 | 17231.05 | 148.32 | 1.007 | 1.209 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.00883 | 31.96 | 0.00630 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 6954.55 | 8345.46 | 71.84 | 0.339 | 0.416 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00792 | -27.60 | 0.00034 | 0.416 | 0.00 |
KITCHEN | 1242.80 | 1491.36 | 12.84 | 0.054 | 1.141 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 18.89 | 18.89 | 0.00539 | -27.60 | 0.00034 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.90 | 1.90 | 0.42 | 0.42 | 1.8951 | 1.8951 | 1.8951 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.21 | 1.21 | 1.14 | 1.14 | 1.2087 | 1.2087 | 1.2087 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 33006.580 | 26419.127 | 1.895060 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 16503.29 | 15629.82 | 1.263373 | 25.97 | 14.80 | 0.00742850 | 11.80 | 8.99 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 32.9322 | 23.88 | 0.00774404 | 36.7611 | 18759.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 61482.230 | 61482.230 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | 61482.23 | 61482.23 | 1.895058 | 9.34 | 6.97 | 0.00612911 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 21.9548 | 15.56 | 0.00775710 | 61.7350 | 92.83 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28738.090 | 20547.160 | 1.208750 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 14369.05 | 14369.05 | 0.805833 | 33.40 | 16.37 | 0.00630683 | 11.77 | 8.24 | 0.00630683 | 33.40 | 0.00630683 | 16.37 | 141.6339 | 26.09 | 0.00903703 | 37.5290 | 12851.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 83202.954 | 83202.954 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 83202.95 | 83202.95 | 1.208746 | -25.04 | -25.04 | 0.00067709 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 94.4229 | 19.59 | 0.00635200 | 39.2967 | 809.36 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33006.580 | 26419.127 | 1.895060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.6492 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.895058 | 1.99576078 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 16503.29 | 15629.82 | 1.0000 | 1.33050884 | 1.263373 | 25.97 | 14.80 | 0.00742850 | 45034.0 | 11.80 | 8.99 | 0.00700000 | 29519.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16503.29 | 33.40 | 0.00630683 | 16.37 | 0.41605618 | 32.9322 | 23.88 | 0.00774404 | 23.88 | 0.00774404 | 36.7611 | 18759.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61482.230 | 61482.230 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.895058 | 1.99576078 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | Sensible | 61482.23 | 61482.23 | 1.0000 | 1.99576078 | 1.895058 | 9.34 | 6.97 | 0.00612911 | 24822.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61482.23 | -27.60 | 0.00034190 | -27.60 | 0.41605618 | 21.9548 | 19.73 | 0.00775710 | 15.56 | 0.00775710 | 61.7350 | 92.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28738.090 | 20547.160 | 1.208750 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1016.5641 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.208746 | 1.27297870 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 14369.05 | 14369.05 | 1.0000 | 0.84865522 | 0.805833 | 33.40 | 16.37 | 0.00630683 | 49726.3 | 11.77 | 8.24 | 0.00630683 | 27733.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14369.05 | 33.40 | 0.00630683 | 16.37 | 1.14133354 | 141.6339 | 26.04 | 0.00903703 | 26.09 | 0.00903703 | 37.5290 | 12851.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 83202.954 | 83202.954 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.208746 | 1.27297870 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | Sensible | 83202.95 | 83202.95 | 1.0000 | 1.27297870 | 1.208746 | -25.04 | -25.04 | 0.00067709 | -23504.2 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 83202.95 | -27.60 | 0.00034190 | -27.60 | 1.14133354 | 94.4229 | 18.22 | 0.00635200 | 19.59 | 0.00635200 | 39.2967 | 809.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.90 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.21 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 2697.17 | 5312.00 | 1405.83 |
KITCHEN | 4499.50 | 5975.50 | 3533.33 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4536.50 | 6891.00 | 3570.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 60.00 | 18.17 | 0.33 | 0.17 |
KITCHEN | 0.00 | 94.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 60.00 | 109.83 | 0.33 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.90 | 87.54 | 354.18 | 4.864 | 2.756 | 0.000 | 0.000 |
KITCHEN | 2.64 | 6.27 | 354.18 | 8.459 | 0.014 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.90 | 87.54 | 354.18 | 4.066 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.64 | 6.27 | 354.18 | 7.829 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.90 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.64 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.55 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 12543290.48 | 0.00 | 12543290.48 | 6968645.70 | 19511936.18 | 13120747.55 | 1437.04 | 6281.54 | 1041.42 | 367.93 |
KITCHEN | 21887138.41 | 0.00 | 21887138.41 | 61809.11 | 21948947.52 | 35993094.65 | 8757.96 | 0.26 | 1.78 | 380.64 |
Total Facility | 34430428.88 | 0.00 | 34430428.88 | 7030454.82 | 41460883.70 | 49113842.20 | 8758.80 | 6281.57 | 1042.24 | 579.10 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4734 | 0.0000 | 0.4734 | 0.2683 | 0.7417 | 0.4161 | 0.00 | 6159.24 | 1027.76 |
KITCHEN | 0.8240 | 0.0000 | 0.8240 | 0.0014 | 0.8254 | 1.1413 | 7186.77 | 0.19 | 0.04 |
Total Facility | 1.2974 | 0.0000 | 1.2974 | 0.2697 | 1.5671 | 1.5574 | 7186.77 | 6159.24 | 1027.78 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 13912230.83 | 0.00 | 13912230.83 | 13120747.55 | 1436.46 | 0.05 | 7323.49 | 367.91 |
PSZ-AC_2:2 | 24275103.51 | 0.00 | 24275103.51 | 35993094.65 | 8737.80 | 10.63 | 11.57 | 380.64 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5251 | 0.0000 | 0.5251 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 0.9139 | 0.0000 | 0.9139 | 1.1413 | 7168.46 | 9.85 | 8.68 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 843.14 | 434.47 | 6277.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 88.28 | 909.36 | 6570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.0421 | 0.7128 | 0.4616 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.9958 | 0.9143 | 0.9139 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 386 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 383.36 | 2747.52 | 11-JAN-01:20 | 29206.02 | 17-JUL-13:00 |
Electricity:Building | 268.66 | 1624.98 | 01-JAN-01:20 | 17215.91 | 02-JAN-11:10 |
Electricity:Zone:DINING | 70.38 | 280.44 | 01-JAN-01:20 | 3811.41 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 260.72 | 1488.70 | 01-JAN-01:20 | 13921.86 | 02-JAN-11:10 |
InteriorLights:Electricity | 21.23 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:DINING | 3.85 | 20.75 | 23-JUN-05:00 | 389.13 | 02-JAN-16:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 21.23 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 21.23 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 3.85 | 20.75 | 23-JUN-05:00 | 389.13 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 21.23 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-16:40 |
Electricity:Zone:KITCHEN | 198.28 | 1344.54 | 01-JAN-01:20 | 13404.50 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.39 | 25.01 | 01-JAN-01:20 | 895.88 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.39 | 25.01 | 01-JAN-01:20 | 895.88 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 239.49 | 1438.68 | 01-JAN-01:10 | 12932.59 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 66.53 | 255.43 | 01-JAN-01:10 | 3718.02 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 239.49 | 1438.68 | 01-JAN-01:10 | 12932.59 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 220.85 | 847.88 | 01-JAN-01:10 | 12341.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 66.53 | 255.43 | 01-JAN-01:10 | 3718.02 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 220.85 | 847.88 | 01-JAN-01:10 | 12341.79 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 172.95 | 1183.25 | 01-JAN-01:10 | 9214.57 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 154.32 | 592.45 | 01-JAN-01:10 | 8623.77 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 36.65 | 594.45 | 03-FEB-23:30 | 3924.37 | 07-SEP-10:20 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 28.71 | 508.67 | 20-JAN-23:10 | 1619.39 | 08-SEP-03:50 |
LowTempRefrigeration:Refrigeration:Electricity | 10.95 | 0.00 | 01-JAN-11:10 | 982.30 | 08-SEP-03:50 |
MedTempRefrigeration:Refrigeration:Electricity | 17.76 | 475.34 | 06-FEB-01:00 | 637.09 | 02-MAY-13:10 |
ElectricityPurchased:Facility | 383.36 | 2747.52 | 11-JAN-01:20 | 29206.02 | 17-JUL-13:00 |
ElectricityPurchased:Plant | 383.36 | 2747.52 | 11-JAN-01:20 | 29206.02 | 17-JUL-13:00 |
Cogeneration:ElectricityPurchased | 383.36 | 2747.52 | 11-JAN-01:20 | 29206.02 | 17-JUL-13:00 |
General:Cogeneration:ElectricityPurchased | 383.36 | 2747.52 | 11-JAN-01:20 | 29206.02 | 17-JUL-13:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 383.36 | 2747.52 | 11-JAN-01:20 | 29206.02 | 17-JUL-13:00 |
ElectricityNet:Plant | 383.36 | 2747.52 | 11-JAN-01:20 | 29206.02 | 17-JUL-13:00 |
Cogeneration:ElectricityNet | 383.36 | 2747.52 | 11-JAN-01:20 | 29206.02 | 17-JUL-13:00 |
General:Cogeneration:ElectricityNet | 383.36 | 2747.52 | 11-JAN-01:20 | 29206.02 | 17-JUL-13:00 |
Electricity:HVAC | 75.29 | 0.00 | 01-JAN-01:10 | 15802.44 | 17-JUL-13:00 |
Fans:Electricity | 54.32 | 0.00 | 01-JAN-01:10 | 3274.11 | 10-JAN-21:00 |
General:Fans:Electricity | 54.32 | 0.00 | 01-JAN-01:10 | 3274.11 | 10-JAN-21:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 20.97 | 0.00 | 01-JAN-00:10 | 12884.04 | 17-JUL-13:00 |
General:Cooling:Electricity | 20.97 | 0.00 | 01-JAN-00:10 | 12884.04 | 17-JUL-13:00 |
ExteriorLights:Electricity | 10.69 | 0.00 | 01-JAN-08:20 | 952.15 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 10.69 | 0.00 | 01-JAN-08:20 | 952.15 | 01-JAN-06:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1002.26 | 2351.77 | 01-JAN-01:10 | 140429.86 | 10-JAN-21:00 |
NaturalGas:Building | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
NaturalGas:HVAC | 356.23 | 0.00 | 01-JAN-01:10 | 112802.99 | 10-JAN-21:00 |
Heating:NaturalGas | 356.23 | 0.00 | 01-JAN-01:10 | 112802.99 | 10-JAN-21:00 |
General:Heating:NaturalGas | 356.23 | 0.00 | 01-JAN-01:10 | 112802.99 | 10-JAN-21:00 |
NaturalGas:Plant | 194.64 | 612.41 | 01-JAN-00:20 | 24113.18 | 17-FEB-13:20 |
WaterSystems:NaturalGas | 194.64 | 612.41 | 01-JAN-00:20 | 24113.18 | 17-FEB-13:20 |
Water Heater:WaterSystems:NaturalGas | 194.64 | 612.41 | 01-JAN-00:20 | 24113.18 | 17-FEB-13:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1007.10 | 2414.89 | 11-JAN-01:10 | 143197.98 | 10-JAN-21:00 |
EnergyTransfer:Building | 402.38 | 1207.44 | 11-JAN-01:10 | 37916.82 | 11-JAN-03:20 |
EnergyTransfer:Zone:KITCHEN | 295.57 | 1207.44 | 11-JAN-01:10 | 20003.41 | 25-APR-04:10 |
Refrigeration:EnergyTransfer | 133.06 | 2414.87 | 11-JAN-01:00 | 7834.84 | 08-SEP-03:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 66.53 | 1207.44 | 11-JAN-01:00 | 3917.42 | 08-SEP-03:50 |
General:Refrigeration:EnergyTransfer | 66.53 | 1207.44 | 11-JAN-01:00 | 3917.42 | 08-SEP-03:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 66.53 | 1207.44 | 11-JAN-01:00 | 3917.42 | 08-SEP-03:50 |
EnergyTransfer:Plant | 224.12 | 1207.44 | 11-JAN-01:00 | 23909.38 | 27-FEB-13:50 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.93 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 53.60 | 1059.55 | 06-FEB-01:00 | 2238.70 | 02-MAY-13:10 |
EnergyTransfer:Zone:DINING | 106.80 | 0.00 | 01-JAN-01:10 | 36269.61 | 11-JAN-03:20 |
Heating:EnergyTransfer | 46.44 | 0.00 | 01-JAN-00:10 | 28545.62 | 10-JAN-21:00 |
Heating:EnergyTransfer:Zone:DINING | 46.42 | 0.00 | 01-JAN-00:10 | 28545.62 | 10-JAN-21:00 |
General:Heating:EnergyTransfer | 46.44 | 0.00 | 01-JAN-00:10 | 28545.62 | 10-JAN-21:00 |
General:Heating:EnergyTransfer:Zone:DINING | 46.42 | 0.00 | 01-JAN-00:10 | 28545.62 | 10-JAN-21:00 |
Cooling:EnergyTransfer | 289.41 | 0.00 | 01-JAN-01:10 | 27287.33 | 17-JUL-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 60.38 | 0.00 | 01-JAN-01:10 | 17072.11 | 11-JAN-03:10 |
General:Cooling:EnergyTransfer | 289.41 | 0.00 | 01-JAN-01:10 | 27287.33 | 17-JUL-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 60.38 | 0.00 | 01-JAN-01:10 | 17072.11 | 11-JAN-03:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 1611.11 | 29-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 1611.11 | 29-JAN-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 229.03 | 0.00 | 01-JAN-01:10 | 16255.61 | 25-APR-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 229.03 | 0.00 | 01-JAN-01:10 | 16255.61 | 25-APR-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 157.59 | 0.00 | 01-JAN-00:10 | 21511.03 | 18-FEB-13:10 |
PlantLoopHeatingDemand:Plant | 157.59 | 0.00 | 01-JAN-00:10 | 21511.03 | 18-FEB-13:10 |
WaterSystems:PlantLoopHeatingDemand | 157.59 | 0.00 | 01-JAN-00:10 | 21511.03 | 18-FEB-13:10 |
General:WaterSystems:PlantLoopHeatingDemand | 157.59 | 0.00 | 01-JAN-00:10 | 21511.03 | 18-FEB-13:10 |
EnergyTransfer:HVAC | 380.61 | 0.00 | 01-JAN-01:10 | 95317.33 | 10-JAN-21:00 |
HeatingCoils:EnergyTransfer | 300.82 | 0.00 | 01-JAN-01:10 | 95317.33 | 10-JAN-21:00 |
CoolingCoils:EnergyTransfer | 79.78 | 0.00 | 01-JAN-00:10 | 46442.87 | 17-JUL-13:00 |
WaterSystems:EnergyTransfer | 157.59 | 0.00 | 01-JAN-00:10 | 21511.03 | 18-FEB-13:10 |
WaterUse:WaterSystems:EnergyTransfer | 157.59 | 0.00 | 01-JAN-00:10 | 21511.03 | 18-FEB-13:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 46.421 | -60.383 | 0.000 | 0.000 | 72.496 | 3.845 | 49.900 | 27.617 | 0.000 | 2.899 | 0.000 | 0.000 | -14.683 | 0.000 | -107.048 | -21.064 |
KITCHEN | 0.000 | 0.000 | 0.015 | -229.021 | 0.000 | 0.000 | 5.166 | 17.389 | 178.354 | 0.000 | 0.000 | 0.006 | 29.181 | 0.000 | 0.000 | 0.000 | -1.092 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.700 | 8.359 | 0.000 | 0.000 | 0.000 | -12.059 | -0.000 |
Total Facility | 0.000 | 0.000 | 46.436 | -289.403 | 0.000 | 0.000 | 77.662 | 21.235 | 228.254 | 27.617 | 0.000 | 6.605 | 37.540 | 0.000 | -14.683 | 0.000 | -120.199 | -21.065 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 11-JAN-03:02 | 0.00 | 0.00 | 0.00 | -34396.21 | 0.00 | 0.00 | 0.00 | 25.01 | 191.57 | 0.00 | 0.00 | 0.00 | 36237.27 | 0.00 | -2025.38 | 0.00 | -32.26 | 0.00 |
KITCHEN | 28-SEP-02:61 | 0.00 | 0.00 | 0.00 | -45027.95 | 0.00 | 0.00 | 0.00 | 25.01 | 1205.28 | 0.00 | 0.00 | 0.00 | 43898.34 | 0.00 | -0.00 | 0.00 | -100.68 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-JUN-02:61 | 0.00 | 0.00 | 0.00 | -64237.70 | 0.00 | 0.00 | 0.00 | 50.02 | 1396.85 | 0.00 | 0.00 | 219.74 | 63318.80 | 0.00 | -690.35 | 0.00 | -57.35 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 31-DEC-03:51 | 0.00 | 0.00 | 43712.80 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 191.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1910.71 | 0.00 | -177.22 | -41841.45 |
KITCHEN | 08-JAN-05:02 | 0.00 | 0.00 | 14382.83 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 4277.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -53.33 | -18632.18 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 31-DEC-03:51 | 0.00 | 0.00 | 43712.80 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 1396.85 | 0.00 | 0.00 | 145.23 | 0.00 | 0.00 | -1910.71 | 0.00 | -360.36 | -43033.83 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.8951 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.8951 | 0.2195 | 1.0000 | Not calculated | 0.4161 | 0.2195 | ||
PSZ-AC_2:2 | 1.2087 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2087 | 0.1251 | 1.0000 | Not calculated | 0.1513 | 0.1251 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.8951 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.8951 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2195 | ||
PSZ-AC_2:2 | 1.2087 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2087 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1251 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8951 | 1.8951 | 1.8951 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2087 | 1.2087 | 1.2087 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.8951 | 1.8951 | 1.8951 | 1.8951 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2087 | 1.2087 | 1.2087 | 1.2087 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8951 | 1.8951 | 1.8951 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2087 | 1.2087 | 1.2087 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.8951 | 1.8951 | 1.8951 | 1.8951 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2087 | 1.2087 | 1.2087 | 1.2087 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.33 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 0.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 356.23 | 112802.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 20.97 | 12884.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 21.23 | 1285.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 10.69 | 952.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 220.85 | 12341.79 | 451.39 | 25220.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 54.32 | 3274.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 194.64 | 24113.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 10.95 | 982.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 17.76 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 276.14 | 383.36 |
Natural Gas | 451.39 | 1002.26 |
Additional | 0.00 | 0.00 |
Total | 727.53 | 1385.62 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 91.39 |
Space Heating | 0.00 |
Space Cooling | 90.25 |
Fans (All) | 233.81 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1030.74 |
Miscellaneous (All) | 1649.96 |
Subtotal | 1649.96 |
Natural Gas [MJ/m2] | |
Space Heating | 1533.23 |
Service Water Heating | 837.72 |
Miscellaneous (All) | 4313.72 |
Subtotal | 4313.72 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.53 |
Space Heating | 25.71 |
Space Cooling | 1.51 |
Fans (All) | 3.92 |
Service Water Heating | 14.05 |
Receptacle Equipment | 49.86 |
Miscellaneous | 3.42 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4528. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8483.00 | 277.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 7278.83 | 502.17 | 450.17 | 513.50 | 15.33 |
Min | 7278.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 502.17 | 450.17 | 513.50 | 15.33 |
Average | 8173.94 | 259.72 | 150.06 | 171.17 | 5.11 |
Sum | 24521.83 | 779.17 | 450.17 | 513.50 | 15.33 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16258.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 90327.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 270983.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8344.00 | 416.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 7470.83 | 670.50 | 235.83 | 198.00 | 184.83 |
Min | 7470.83 | 11.50 | 0.00 | 0.00 | 0.00 |
Max | 8748.50 | 670.50 | 235.83 | 198.00 | 184.83 |
Average | 8187.78 | 366.00 | 78.61 | 66.00 | 61.61 |
Sum | 24563.33 | 1098.00 | 235.83 | 198.00 | 184.83 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 254494.33 | 230.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15608.67 | 649.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254494.33 | 649.33 | 0.00 | 0.00 | 0.00 |
Average | 90034.33 | 293.33 | 0.00 | 0.00 | 0.00 |
Sum | 270103.00 | 880.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:15
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111295E+10 | 34403.51 | 11-JAN-03:02 | -30.7 | -30.9 | 0.436685E+10 | 3682.70 | 07-JAN-19:10 | -30.7 | -30.9 |
February | 0.138864E+10 | 24928.42 | 01-FEB-04:03 | -25.0 | -25.2 | 0.397729E+10 | 4362.50 | 27-FEB-12:00 | 17.20 | 6.49 |
March | 0.156232E+10 | 18152.45 | 05-MAR-03:53 | -21.1 | -21.7 | 0.441575E+10 | 3814.39 | 14-MAR-11:00 | 14.40 | 6.37 |
April | 0.279220E+10 | 9477.25 | 28-APR-23:01 | -4.6 | -6.2 | 0.440007E+10 | 4476.85 | 22-APR-18:10 | -4.6 | -6.2 |
May | 0.479063E+10 | 19903.91 | 20-MAY-02:61 | 14.90 | 9.98 | 0.475880E+10 | 4640.97 | 20-MAY-18:10 | 24.13 | 13.93 |
June | 0.869559E+10 | 24280.29 | 29-JUN-02:61 | 11.83 | 6.62 | 0.497156E+10 | 4640.76 | 24-JUN-18:00 | 11.83 | 6.62 |
July | 0.124701E+11 | 26103.99 | 29-JUL-02:61 | 13.53 | 8.62 | 0.524897E+10 | 4641.27 | 01-JUL-18:49 | 13.53 | 8.62 |
August | 0.115152E+11 | 26682.16 | 05-AUG-02:61 | 16.20 | 8.86 | 0.525343E+10 | 4640.86 | 26-AUG-18:00 | 20.60 | 12.09 |
September | 0.803504E+10 | 26475.79 | 03-SEP-02:61 | 16.02 | 9.04 | 0.482026E+10 | 4640.89 | 02-SEP-18:30 | 16.02 | 9.04 |
October | 0.465713E+10 | 8538.29 | 21-OCT-04:01 | -1.0 | -1.9 | 0.461257E+10 | 4363.73 | 12-OCT-11:50 | -1.0 | -1.9 |
November | 0.230251E+10 | 13617.08 | 27-NOV-00:01 | -15.1 | -15.9 | 0.427271E+10 | 4317.99 | 04-NOV-18:10 | -15.1 | -15.9 |
December | 0.106103E+10 | 26355.40 | 29-DEC-03:09 | -25.8 | -26.1 | 0.436581E+10 | 3682.63 | 30-DEC-19:10 | -15.7 | -16.3 |
Annual Sum or Average | 0.603834E+11 | 0.554641E+11 | ||||||||
Minimum of Months | 0.106103E+10 | 8538.29 | -30.7 | -30.9 | 0.397729E+10 | 3682.63 | -30.7 | -30.9 | ||
Maximum of Months | 0.124701E+11 | 34403.51 | 16.20 | 9.98 | 0.525343E+10 | 4641.27 | 24.13 | 13.93 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179714E+11 | 41117.68 | 27-JAN-05:01 | -27.8 | -28.2 | 0.727647E+10 | 4791.30 | 14-JAN-11:00 | -27.8 | -28.2 |
February | 0.166890E+11 | 38314.77 | 01-FEB-05:01 | -25.0 | -25.2 | 0.658073E+10 | 4856.70 | 27-FEB-11:00 | 16.10 | 6.08 |
March | 0.187625E+11 | 33675.03 | 05-MAR-05:01 | -20.3 | -21.0 | 0.728621E+10 | 4820.35 | 14-MAR-10:00 | 12.80 | 5.58 |
April | 0.181758E+11 | 28769.10 | 07-APR-04:01 | 11.78 | 5.16 | 0.708886E+10 | 4868.90 | 07-APR-10:00 | 18.90 | 7.88 |
May | 0.190505E+11 | 39439.13 | 31-MAY-02:61 | 8.40 | 6.20 | 0.736380E+10 | 4868.92 | 30-MAY-10:50 | 8.40 | 6.20 |
June | 0.190348E+11 | 41847.88 | 20-JUN-02:61 | 9.13 | 5.67 | 0.718854E+10 | 4868.95 | 13-JUN-10:00 | 9.13 | 5.67 |
July | 0.202477E+11 | 42853.25 | 12-JUL-02:61 | 9.27 | 5.03 | 0.744348E+10 | 4868.96 | 07-JUL-10:00 | 9.27 | 5.03 |
August | 0.202969E+11 | 41419.71 | 28-AUG-02:61 | 10.00 | 6.08 | 0.744221E+10 | 4868.93 | 23-AUG-10:00 | 10.00 | 6.08 |
September | 0.198553E+11 | 45070.85 | 28-SEP-02:61 | 7.33 | 3.71 | 0.716443E+10 | 4868.94 | 07-SEP-10:50 | 7.33 | 3.71 |
October | 0.206755E+11 | 41023.23 | 19-OCT-02:61 | 12.80 | 5.87 | 0.734727E+10 | 4868.91 | 16-OCT-10:50 | 12.80 | 5.87 |
November | 0.192938E+11 | 30804.53 | 27-NOV-05:01 | -15.4 | -16.5 | 0.706862E+10 | 4853.21 | 17-NOV-11:00 | -15.4 | -16.5 |
December | 0.189762E+11 | 39287.43 | 29-DEC-05:01 | -25.0 | -25.3 | 0.727988E+10 | 4825.42 | 06-DEC-11:00 | -25.0 | -25.3 |
Annual Sum or Average | 0.229029E+12 | 0.865305E+11 | ||||||||
Minimum of Months | 0.166890E+11 | 28769.10 | -27.8 | -28.2 | 0.658073E+10 | 4791.30 | -27.8 | -28.2 | ||
Maximum of Months | 0.206755E+11 | 45070.85 | 12.80 | 6.20 | 0.744348E+10 | 4868.96 | 18.90 | 7.88 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1.38 | -1.3 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.3 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 | -13.9 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.9 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 | -4.1 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 2.68 | 0.55 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.55 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -1.1 | -3.0 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -3.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 | 10.36 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.36 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 | 13.32 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.32 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 | 11.96 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.96 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 | 11.59 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.59 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 | 6.94 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.94 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 | 1.54 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.54 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.9 | 0.00 | 0.00 | -12.4 | -13.9 | ||
Maximum of Months | 0.00 | 0.00 | 19.45 | 13.32 | 0.00 | 0.00 | 19.45 | 13.32 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146742E+11 | 43415.83 | 08-JAN-04:41 | -26.7 |
February | 0.777988E+10 | 42986.19 | 01-FEB-04:31 | -25.0 |
March | 0.584949E+10 | 40615.64 | 05-MAR-03:01 | -20.2 |
April | 0.209541E+10 | 16666.60 | 29-APR-02:62 | -6.7 |
May | 0.113408E+10 | 14554.75 | 08-MAY-02:62 | -2.8 |
June | 48073446.55 | 6151.10 | 16-JUN-21:03 | 6.52 |
July | 2246444.60 | 5488.78 | 25-JUL-02:20 | 21.50 |
August | 1273365.62 | 4912.09 | 10-AUG-03:27 | 17.75 |
September | 0.208798E+09 | 5098.72 | 19-SEP-11:44 | 7.38 |
October | 0.923812E+09 | 7410.40 | 02-OCT-04:03 | 4.90 |
November | 0.391916E+10 | 20797.01 | 27-NOV-03:12 | -15.9 |
December | 0.978436E+10 | 43704.06 | 31-DEC-03:51 | -25.0 |
Annual Sum or Average | 0.464207E+11 | |||
Minimum of Months | 1273365.62 | 4912.09 | -26.7 | |
Maximum of Months | 0.146742E+11 | 43704.06 | 21.50 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7310053.25 | 14399.58 | 08-JAN-05:02 | -26.7 |
February | 1996939.84 | 8530.12 | 03-FEB-05:03 | -16.7 |
March | 1222611.51 | 6584.53 | 05-MAR-05:02 | -20.3 |
April | 653408.09 | 7649.51 | 29-APR-04:03 | -7.8 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 |
October | 9926.37 | 165.44 | 05-OCT-04:04 | -1.7 |
November | 917549.22 | 8317.34 | 12-NOV-05:03 | -10.6 |
December | 3213423.60 | 9185.26 | 27-DEC-05:03 | -10.0 |
Annual Sum or Average | 15323911.88 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 7310053.25 | 14399.58 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.414379E+09 | 389.13 | 02-JAN-16:40 | 0.565077E+10 | 3718.02 | 01-JAN-11:09 |
February | 0.335236E+09 | 389.13 | 01-FEB-17:19 | 0.510393E+10 | 3718.02 | 01-FEB-11:09 |
March | 0.332269E+09 | 389.13 | 01-MAR-17:00 | 0.565082E+10 | 3718.02 | 01-MAR-11:09 |
April | 0.283137E+09 | 389.13 | 01-APR-18:49 | 0.546849E+10 | 3718.02 | 01-APR-10:09 |
May | 0.265184E+09 | 389.13 | 01-MAY-19:30 | 0.565080E+10 | 3718.02 | 01-MAY-10:09 |
June | 0.232728E+09 | 389.13 | 01-JUN-20:10 | 0.546853E+10 | 3718.02 | 01-JUN-10:09 |
July | 0.259593E+09 | 389.13 | 01-JUL-20:30 | 0.565075E+10 | 3718.02 | 01-JUL-10:09 |
August | 0.274360E+09 | 389.13 | 01-AUG-19:00 | 0.565082E+10 | 3718.02 | 01-AUG-10:09 |
September | 0.301436E+09 | 389.13 | 01-SEP-18:00 | 0.546849E+10 | 3718.02 | 01-SEP-10:09 |
October | 0.347277E+09 | 389.13 | 02-OCT-17:00 | 0.565077E+10 | 3718.02 | 01-OCT-10:09 |
November | 0.383788E+09 | 389.13 | 01-NOV-16:00 | 0.546851E+10 | 3718.02 | 01-NOV-10:09 |
December | 0.415941E+09 | 389.13 | 01-DEC-16:40 | 0.565075E+10 | 3718.02 | 01-DEC-11:09 |
Annual Sum or Average | 0.384533E+10 | 0.665334E+11 | ||||
Minimum of Months | 0.232728E+09 | 389.13 | 0.510393E+10 | 3718.02 | ||
Maximum of Months | 0.415941E+09 | 389.13 | 0.565082E+10 | 3718.02 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146885E+10 | 895.88 | 02-JAN-10:09 | 0.146891E+11 | 9214.57 | 01-JAN-11:09 |
February | 0.133058E+10 | 895.88 | 01-FEB-10:09 | 0.132676E+11 | 9214.57 | 01-FEB-11:09 |
March | 0.149423E+10 | 895.88 | 01-MAR-10:09 | 0.146892E+11 | 9214.57 | 01-MAR-11:09 |
April | 0.142731E+10 | 895.88 | 01-APR-16:10 | 0.142152E+11 | 9214.57 | 01-APR-10:09 |
May | 0.148154E+10 | 895.88 | 01-MAY-09:09 | 0.146891E+11 | 9214.57 | 01-MAY-10:09 |
June | 0.144409E+10 | 895.88 | 01-JUN-09:09 | 0.142153E+11 | 9214.57 | 01-JUN-10:09 |
July | 0.146494E+10 | 895.88 | 01-JUL-16:10 | 0.146890E+11 | 9214.57 | 01-JUL-10:09 |
August | 0.149423E+10 | 895.88 | 01-AUG-09:09 | 0.146892E+11 | 9214.57 | 01-AUG-10:09 |
September | 0.142766E+10 | 895.88 | 01-SEP-09:09 | 0.142152E+11 | 9214.57 | 01-SEP-10:09 |
October | 0.146867E+10 | 895.88 | 02-OCT-09:09 | 0.146891E+11 | 9214.57 | 01-OCT-10:09 |
November | 0.142226E+10 | 895.88 | 01-NOV-09:09 | 0.142153E+11 | 9214.57 | 01-NOV-10:09 |
December | 0.146511E+10 | 895.88 | 01-DEC-10:09 | 0.146890E+11 | 9214.57 | 01-DEC-11:09 |
Annual Sum or Average | 0.173895E+11 | 0.172953E+12 | ||||
Minimum of Months | 0.133058E+10 | 895.88 | 0.132676E+11 | 9214.57 | ||
Maximum of Months | 0.149423E+10 | 895.88 | 0.146892E+11 | 9214.57 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.414379E+09 | 0.565077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199637E+11 |
February | 0.852256E+10 | 0.335236E+09 | 0.510393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136231E+11 |
March | 0.954557E+10 | 0.332269E+09 | 0.565082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127397E+11 |
April | 0.915225E+10 | 0.283137E+09 | 0.546849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817869E+10 |
May | 0.947560E+10 | 0.265184E+09 | 0.565080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43791649.28 | 0.647475E+10 |
June | 0.922788E+10 | 0.232728E+09 | 0.546853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405407E+09 | 0.307873E+10 |
July | 0.939996E+10 | 0.259593E+09 | 0.565075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120840E+10 | 0.154255E+10 |
August | 0.954557E+10 | 0.274360E+09 | 0.565082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905680E+09 | 0.225861E+10 |
September | 0.915225E+10 | 0.301436E+09 | 0.546849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333323E+09 | 0.439840E+10 |
October | 0.940563E+10 | 0.347277E+09 | 0.565077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2296645.55 | 0.759374E+10 |
November | 0.909363E+10 | 0.383788E+09 | 0.546851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109103E+11 |
December | 0.939996E+10 | 0.415941E+09 | 0.565075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162862E+11 |
Annual Sum or Average | 0.111326E+12 | 0.384533E+10 | 0.665334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289890E+10 | 0.107048E+12 |
Minimum of Months | 0.852256E+10 | 0.232728E+09 | 0.510393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154255E+10 |
Maximum of Months | 0.954557E+10 | 0.415941E+09 | 0.565082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120840E+10 | 0.199637E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.146885E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167430E+09 |
February | 0.610713E+09 | 0.133058E+10 | 0.971608E+10 | 0.103882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126253E+09 |
March | 0.684021E+09 | 0.149423E+10 | 0.107572E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112707E+09 |
April | 0.655836E+09 | 0.142731E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78623866.15 |
May | 0.679007E+09 | 0.148154E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 94509.20 | 82784419.27 |
June | 0.661256E+09 | 0.144409E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 800114.60 | 50600449.24 |
July | 0.673587E+09 | 0.146494E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 2392466.41 | 34020969.23 |
August | 0.684021E+09 | 0.149423E+10 | 0.107572E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 2166872.26 | 38915856.65 |
September | 0.655836E+09 | 0.142766E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 910068.25 | 64836408.46 |
October | 0.673993E+09 | 0.146867E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83697440.32 |
November | 0.651635E+09 | 0.142226E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115333E+09 |
December | 0.673587E+09 | 0.146511E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136803E+09 |
Annual Sum or Average | 0.797748E+10 | 0.173895E+11 | 0.126656E+12 | 0.135417E+12 | 0.00 | 0.00 | 0.00 | 6364030.73 | 0.109201E+10 |
Minimum of Months | 0.610713E+09 | 0.133058E+10 | 0.971608E+10 | 0.103882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34020969.23 |
Maximum of Months | 0.684021E+09 | 0.149423E+10 | 0.107572E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 2392466.41 | 0.167430E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393837E+09 | 0.439169E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316677E+09 | 0.585689E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335644E+09 | 0.102667E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273125E+09 | 0.118186E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206286E+09 | 0.156994E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172753E+09 | 0.170051E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237510E+09 | 0.172763E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265842E+09 | 0.144517E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284915E+09 | 0.101119E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381151E+09 | 0.686436E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404953E+09 | 0.395534E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427019E+09 | 0.288778E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369971E+10 | 0.120586E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172753E+09 | 0.288778E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427019E+09 | 0.172763E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 389.13 | 02-JAN-16:40 | 3718.02 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 31998.30 | 10-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 389.13 | 01-FEB-17:19 | 3718.02 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 26988.88 | 04-FEB-20:00 |
March | 9454.80 | 04-MAR-19:10 | 389.13 | 01-MAR-17:00 | 3718.02 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 26188.94 | 04-MAR-20:00 |
April | 9454.80 | 01-APR-18:10 | 389.13 | 01-APR-18:49 | 3718.02 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 14604.81 | 28-APR-20:00 |
May | 9454.80 | 06-MAY-18:10 | 389.13 | 01-MAY-19:30 | 3718.02 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1865.18 | 20-MAY-17:10 | 11981.63 | 22-MAY-20:00 |
June | 9454.80 | 03-JUN-18:10 | 389.13 | 01-JUN-20:10 | 3718.02 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3616.75 | 29-JUN-13:00 | 8538.74 | 16-JUN-11:02 |
July | 9454.80 | 01-JUL-18:10 | 389.13 | 01-JUL-20:30 | 3718.02 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5941.91 | 17-JUL-17:03 | 4783.80 | 07-JUL-19:52 |
August | 9454.80 | 05-AUG-18:10 | 389.13 | 01-AUG-19:00 | 3718.02 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5546.12 | 05-AUG-18:03 | 6839.29 | 17-AUG-12:00 |
September | 9454.80 | 02-SEP-18:10 | 389.13 | 01-SEP-18:00 | 3718.02 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4389.58 | 02-SEP-17:03 | 9954.35 | 18-SEP-20:00 |
October | 9454.80 | 07-OCT-18:10 | 389.13 | 02-OCT-17:00 | 3718.02 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 303.18 | 18-OCT-14:00 | 12196.64 | 31-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 389.13 | 01-NOV-16:00 | 3718.02 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 18337.50 | 26-NOV-21:00 |
December | 9454.80 | 02-DEC-19:10 | 389.13 | 01-DEC-16:40 | 3718.02 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 26279.98 | 29-DEC-19:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 389.13 | 3718.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4783.80 | |||||
Maximum of Months | 9454.80 | 389.13 | 3718.02 | 0.00 | 0.00 | 0.00 | 0.00 | 5941.91 | 31998.30 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 895.88 | 02-JAN-10:09 | 6627.44 | 01-JAN-11:09 | 7566.24 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 332.15 | 06-JAN-03:51 |
February | 677.52 | 04-FEB-19:10 | 895.88 | 01-FEB-10:09 | 6627.44 | 01-FEB-11:09 | 7566.24 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 309.67 | 17-FEB-04:10 |
March | 677.52 | 04-MAR-19:10 | 895.88 | 01-MAR-10:09 | 6627.44 | 01-MAR-11:09 | 7566.24 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 355.22 | 17-MAR-04:00 |
April | 677.52 | 01-APR-18:10 | 895.88 | 01-APR-16:10 | 6627.44 | 01-APR-10:09 | 7566.24 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 250.75 | 27-APR-02:00 |
May | 677.52 | 06-MAY-18:10 | 895.88 | 01-MAY-09:09 | 6627.44 | 01-MAY-10:09 | 7566.24 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 6.64 | 20-MAY-16:00 | 527.87 | 22-MAY-04:00 |
June | 677.52 | 03-JUN-18:10 | 895.88 | 01-JUN-09:09 | 6627.44 | 01-JUN-10:09 | 7566.24 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 15.92 | 29-JUN-15:00 | 246.71 | 14-JUN-02:00 |
July | 677.52 | 01-JUL-18:10 | 895.88 | 01-JUL-16:10 | 6627.44 | 01-JUL-10:09 | 7566.24 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 17.34 | 25-JUL-15:00 | 135.56 | 05-JUL-01:00 |
August | 677.52 | 05-AUG-18:10 | 895.88 | 01-AUG-09:09 | 6627.44 | 01-AUG-10:09 | 7566.24 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 15.86 | 11-AUG-14:00 | 175.31 | 23-AUG-03:20 |
September | 677.52 | 02-SEP-18:10 | 895.88 | 01-SEP-09:09 | 6627.44 | 01-SEP-10:09 | 7566.24 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 16.20 | 02-SEP-14:00 | 304.92 | 12-SEP-03:20 |
October | 677.52 | 07-OCT-18:10 | 895.88 | 02-OCT-09:09 | 6627.44 | 01-OCT-10:09 | 7566.24 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 210.51 | 31-OCT-03:40 |
November | 677.52 | 04-NOV-18:10 | 895.88 | 01-NOV-09:09 | 6627.44 | 01-NOV-10:09 | 7566.24 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 301.14 | 28-NOV-05:00 |
December | 677.52 | 02-DEC-19:10 | 895.88 | 01-DEC-10:09 | 6627.44 | 01-DEC-11:09 | 7566.24 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 503.27 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 895.88 | 6627.44 | 7566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 135.56 | ||||||
Maximum of Months | 677.52 | 895.88 | 6627.44 | 7566.24 | 0.00 | 0.00 | 0.00 | 17.34 | 527.87 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1173.50 | 11-JAN-08:31 | 1524.28 | 28-JAN-14:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 737.94 | 05-FEB-23:53 | 1589.06 | 05-FEB-13:40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.83 | 01-MAR-07:00 | 2020.61 | 07-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 565.66 | 11-APR-06:53 | 2232.48 | 29-APR-13:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.17 | 13-MAY-03:53 | 2551.53 | 09-MAY-12:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.87 | 20-JUN-04:55 | 2222.39 | 03-JUN-13:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.76 | 03-JUL-14:30 | 2424.39 | 05-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.91 | 07-AUG-02:52 | 2125.86 | 03-AUG-12:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 617.25 | 03-SEP-04:55 | 2035.90 | 17-SEP-13:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.01 | 27-OCT-07:05 | 1471.61 | 10-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.59 | 14-NOV-07:35 | 1165.74 | 12-NOV-13:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.81 | 29-DEC-06:00 | 1156.94 | 29-DEC-13:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.87 | 1156.94 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1173.50 | 2551.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 34403.51 | 11-JAN-03:02 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 |
February | 24928.42 | 01-FEB-04:03 | 0.00 | 250.09 | 6385.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.10 |
March | 18152.45 | 05-MAR-03:53 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.86 |
April | 9477.25 | 28-APR-23:01 | 5252.67 | 864.74 | 3846.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 |
May | 19903.91 | 20-MAY-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.68 |
June | 24280.29 | 29-JUN-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 |
July | 26103.99 | 29-JUL-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 |
August | 26682.16 | 05-AUG-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.31 |
September | 26475.79 | 03-SEP-02:61 | 0.00 | 225.08 | 2298.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.38 |
October | 8538.29 | 21-OCT-04:01 | 0.00 | 250.09 | 15325.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.43 |
November | 13617.08 | 27-NOV-00:01 | 5252.67 | 648.56 | 3846.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.73 |
December | 26355.40 | 29-DEC-03:09 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8538.29 | 0.00 | 225.08 | 2298.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 | |
Maximum of Months | 34403.51 | 5252.67 | 864.74 | 15325.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 41117.68 | 27-JAN-05:01 | 376.40 | 250.09 | 30887.20 | 31308.57 | 0.00 | 0.00 | 0.00 | 0.00 | 49.61 |
February | 38314.77 | 01-FEB-05:01 | 376.40 | 250.09 | 30887.20 | 31308.57 | 0.00 | 0.00 | 0.00 | 0.00 | 17.94 |
March | 33675.03 | 05-MAR-05:01 | 0.00 | 225.08 | 27711.98 | 28177.71 | 0.00 | 0.00 | 0.00 | 0.00 | 18.52 |
April | 28769.10 | 07-APR-04:01 | 376.40 | 250.09 | 30887.20 | 31308.57 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 |
May | 39439.13 | 31-MAY-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.32 |
June | 41847.88 | 20-JUN-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.13 |
July | 42853.25 | 12-JUL-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.43 |
August | 41419.71 | 28-AUG-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 |
September | 45070.85 | 28-SEP-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.68 |
October | 41023.23 | 19-OCT-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.01 |
November | 30804.53 | 27-NOV-05:01 | 376.40 | 250.09 | 30887.20 | 31308.57 | 0.00 | 0.00 | 0.00 | 0.00 | 63.03 |
December | 39287.43 | 29-DEC-05:01 | 376.40 | 250.09 | 30887.20 | 31308.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 28769.10 | 0.00 | 225.08 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45070.85 | 376.40 | 250.09 | 30887.20 | 31308.57 | 0.00 | 0.00 | 0.00 | 0.00 | 100.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.88 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.99 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.60 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.99 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.97 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.32 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.37 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.04 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.07 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.51 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.49 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.49 | 38.99 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.318035E+11 | 20696.89 | 09-JAN-11:09 | 0.153764E+12 | 140429.86 | 10-JAN-20:00 |
February | 0.281964E+11 | 20405.48 | 10-FEB-11:09 | 0.107011E+12 | 110993.38 | 09-FEB-11:09 |
March | 0.308313E+11 | 20281.44 | 03-MAR-11:09 | 0.103273E+12 | 108880.57 | 04-MAR-11:20 |
April | 0.294669E+11 | 19950.90 | 27-APR-10:09 | 0.738928E+11 | 69766.02 | 28-APR-12:09 |
May | 0.312082E+11 | 22371.44 | 20-MAY-10:20 | 0.675525E+11 | 71204.38 | 08-MAY-10:09 |
June | 0.328738E+11 | 25821.15 | 23-JUN-10:20 | 0.539723E+11 | 53906.00 | 16-JUN-10:20 |
July | 0.375524E+11 | 29206.02 | 17-JUL-12:00 | 0.535325E+11 | 44525.74 | 01-JUL-10:50 |
August | 0.361643E+11 | 27101.24 | 10-AUG-10:20 | 0.535850E+11 | 47997.66 | 17-AUG-12:50 |
September | 0.326060E+11 | 25737.48 | 02-SEP-10:20 | 0.554267E+11 | 52800.74 | 12-SEP-12:20 |
October | 0.310447E+11 | 21136.45 | 18-OCT-10:20 | 0.662399E+11 | 62295.10 | 10-OCT-10:20 |
November | 0.300633E+11 | 20186.40 | 27-NOV-11:09 | 0.873124E+11 | 94374.52 | 26-NOV-11:09 |
December | 0.315468E+11 | 20543.42 | 28-DEC-11:09 | 0.126701E+12 | 120253.21 | 31-DEC-07:10 |
Annual Sum or Average | 0.383358E+12 | 0.100226E+13 | ||||
Minimum of Months | 0.281964E+11 | 19950.90 | 0.535325E+11 | 44525.74 | ||
Maximum of Months | 0.375524E+11 | 29206.02 | 0.153764E+12 | 140429.86 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.188323E+10 | 0.125467E+10 | 0.203399E+11 | 0.00 | 0.539466E+10 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166581E+10 | 0.100840E+10 | 0.183715E+11 | 0.00 | 0.447527E+10 | 0.72 | 0.00 | 2297704.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182650E+10 | 0.941605E+09 | 0.203400E+11 | 0.00 | 0.476180E+10 | 0.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171044E+10 | 0.734591E+09 | 0.196837E+11 | 0.00 | 0.430014E+10 | 0.77 | 0.00 | 85289075.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174672E+10 | 0.613757E+09 | 0.203399E+11 | 0.00 | 0.436126E+10 | 0.80 | 0.00 | 0.100219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167682E+10 | 0.532294E+09 | 0.196839E+11 | 0.00 | 0.415125E+10 | 0.77 | 0.00 | 0.363992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.172453E+10 | 0.571093E+09 | 0.203398E+11 | 0.00 | 0.438697E+10 | 0.79 | 0.00 | 0.718519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176859E+10 | 0.688523E+09 | 0.203400E+11 | 0.00 | 0.435399E+10 | 0.80 | 0.00 | 0.568017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172910E+10 | 0.833996E+09 | 0.196837E+11 | 0.00 | 0.420091E+10 | 0.77 | 0.00 | 0.301062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.181594E+10 | 0.104329E+10 | 0.203399E+11 | 0.00 | 0.436896E+10 | 0.79 | 0.00 | 0.360132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180605E+10 | 0.116934E+10 | 0.196838E+11 | 0.00 | 0.448873E+10 | 0.77 | 0.00 | 3173057.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188105E+10 | 0.129980E+10 | 0.203398E+11 | 0.00 | 0.508007E+10 | 0.79 | 0.00 | 23296.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212348E+11 | 0.106914E+11 | 0.239486E+12 | 0.00 | 0.543240E+11 | 9.37 | 0.00 | 0.209690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.166581E+10 | 0.532294E+09 | 0.183715E+11 | 0.00 | 0.415125E+10 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.188323E+10 | 0.129980E+10 | 0.203400E+11 | 0.00 | 0.539466E+10 | 0.80 | 0.00 | 0.718519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.383373E+11 | 0.00 | 0.974051E+11 | 0.00 | 0.180218E+11 | 0.00 | 0.00 |
February | 0.346273E+11 | 0.00 | 0.558639E+11 | 0.00 | 0.165197E+11 | 0.00 | 0.00 |
March | 0.383373E+11 | 0.00 | 0.467765E+11 | 0.00 | 0.181591E+11 | 0.00 | 0.00 |
April | 0.371007E+11 | 0.00 | 0.198394E+11 | 0.00 | 0.169528E+11 | 0.00 | 0.00 |
May | 0.383373E+11 | 0.00 | 0.125476E+11 | 0.00 | 0.166675E+11 | 0.00 | 0.00 |
June | 0.371007E+11 | 0.00 | 0.162746E+10 | 0.00 | 0.152442E+11 | 0.00 | 0.00 |
July | 0.383373E+11 | 0.00 | 0.176097E+09 | 0.00 | 0.150191E+11 | 0.00 | 0.00 |
August | 0.383373E+11 | 0.00 | 0.479754E+09 | 0.00 | 0.147679E+11 | 0.00 | 0.00 |
September | 0.371007E+11 | 0.00 | 0.387227E+10 | 0.00 | 0.144537E+11 | 0.00 | 0.00 |
October | 0.383373E+11 | 0.00 | 0.123250E+11 | 0.00 | 0.155776E+11 | 0.00 | 0.00 |
November | 0.371007E+11 | 0.00 | 0.342843E+11 | 0.00 | 0.159275E+11 | 0.00 | 0.00 |
December | 0.383373E+11 | 0.00 | 0.710374E+11 | 0.00 | 0.173265E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.451391E+12 | 0.00 | 0.356235E+12 | 0.00 | 0.194637E+12 | 0.00 | 0.00 |
Minimum of Months | 0.346273E+11 | 0.00 | 0.176097E+09 | 0.00 | 0.144537E+11 | 0.00 | 0.00 |
Maximum of Months | 0.383373E+11 | 0.00 | 0.974051E+11 | 0.00 | 0.181591E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1285.01 | 02-JAN-16:40 | 952.15 | 01-JAN-06:10 | 12932.59 | 01-JAN-11:09 | 0.00 | 3274.11 | 10-JAN-20:00 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 1285.01 | 01-FEB-17:19 | 952.15 | 01-FEB-06:10 | 12932.59 | 01-FEB-11:09 | 0.00 | 2899.65 | 04-FEB-19:00 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 1285.01 | 01-MAR-17:00 | 952.15 | 01-MAR-06:10 | 12932.59 | 01-MAR-11:09 | 0.00 | 2871.11 | 04-MAR-19:00 | 0.00 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 1285.01 | 01-APR-18:49 | 952.15 | 01-APR-05:10 | 12932.59 | 01-APR-10:09 | 0.00 | 2413.02 | 29-APR-06:10 | 0.00 | 01-APR-12:39 | 0.00 | 01-APR-00:10 |
May | 1285.01 | 01-MAY-19:30 | 952.15 | 01-MAY-05:10 | 12932.59 | 01-MAY-10:09 | 0.00 | 2272.79 | 08-MAY-06:10 | 0.00 | 16-MAY-08:39 | 0.00 | 01-MAY-00:10 |
June | 1285.01 | 01-JUN-20:10 | 952.15 | 01-JUN-20:10 | 12932.59 | 01-JUN-10:09 | 0.00 | 2089.09 | 29-JUN-12:00 | 0.00 | 01-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 1285.01 | 01-JUL-20:30 | 952.15 | 01-JUL-20:30 | 12932.59 | 01-JUL-10:09 | 0.00 | 2918.40 | 17-JUL-12:00 | 0.00 | 06-JUL-14:39 | 0.00 | 01-JUL-00:10 |
August | 1285.01 | 01-AUG-19:00 | 952.15 | 01-AUG-19:00 | 12932.59 | 01-AUG-10:09 | 0.00 | 2508.17 | 05-AUG-18:10 | 0.00 | 22-AUG-14:39 | 0.00 | 01-AUG-00:10 |
September | 1285.01 | 01-SEP-18:00 | 952.15 | 01-SEP-05:10 | 12932.59 | 01-SEP-10:09 | 0.00 | 2390.56 | 02-SEP-17:10 | 0.00 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 1285.01 | 02-OCT-17:00 | 952.15 | 01-OCT-05:10 | 12932.59 | 01-OCT-10:09 | 0.00 | 2339.13 | 10-OCT-06:10 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 1285.01 | 01-NOV-16:00 | 952.15 | 01-NOV-05:10 | 12932.59 | 01-NOV-10:09 | 0.00 | 2665.68 | 26-NOV-07:00 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 1285.01 | 01-DEC-16:40 | 952.15 | 01-DEC-06:10 | 12932.59 | 01-DEC-11:09 | 0.00 | 3066.51 | 31-DEC-07:10 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1285.01 | 952.15 | 12932.59 | 0.00 | 2089.09 | 0.00 | 0.00 | ||||||
Maximum of Months | 1285.01 | 952.15 | 12932.59 | 0.00 | 3274.11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 463.79 | 27-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3136.47 | 07-APR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5901.20 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8650.75 | 29-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12884.04 | 17-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10524.54 | 05-AUG-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10083.30 | 02-SEP-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4709.44 | 18-OCT-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 874.25 | 17-NOV-04:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38.83 | 08-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12884.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 20696.89 | 09-JAN-11:09 | 989.27 | 12932.59 | 0.00 | 0.00 | 2947.08 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20405.48 | 10-FEB-11:09 | 989.27 | 12932.59 | 0.00 | 0.00 | 2655.67 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20281.44 | 03-MAR-11:09 | 989.27 | 12932.59 | 0.00 | 0.00 | 2531.56 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19950.90 | 27-APR-10:09 | 989.27 | 12932.59 | 0.00 | 0.00 | 2193.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22371.44 | 20-MAY-10:20 | 879.34 | 12932.59 | 0.00 | 0.00 | 1850.07 | 0.00 | 0.00 | 2807.43 | 0.00 |
June | 25821.15 | 23-JUN-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 1850.07 | 0.00 | 0.00 | 6136.87 | 0.00 |
July | 29206.02 | 17-JUL-12:00 | 989.27 | 11230.28 | 0.00 | 0.00 | 2918.40 | 0.00 | 0.00 | 12884.04 | 0.00 |
August | 27101.24 | 10-AUG-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 1909.07 | 0.00 | 0.00 | 7361.25 | 0.00 |
September | 25737.48 | 02-SEP-10:20 | 879.34 | 12932.59 | 0.00 | 0.00 | 1850.07 | 0.00 | 0.00 | 6173.79 | 0.00 |
October | 21136.45 | 18-OCT-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 1850.07 | 0.00 | 0.00 | 1461.28 | 0.00 |
November | 20186.40 | 27-NOV-11:09 | 989.27 | 12932.59 | 0.00 | 0.00 | 2435.76 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20543.42 | 28-DEC-11:09 | 989.27 | 12932.59 | 0.00 | 0.00 | 2793.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 19950.90 | 879.34 | 11230.28 | 0.00 | 0.00 | 1850.07 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29206.02 | 989.27 | 12932.59 | 0.00 | 0.00 | 2947.08 | 0.00 | 0.00 | 12884.04 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 25220.79 | 01-JAN-11:09 | 0.00 | 112802.99 | 10-JAN-20:00 | 0.00 | 24072.82 | 31-JAN-13:20 | 0.00 |
February | 25220.79 | 01-FEB-11:09 | 0.00 | 86447.88 | 01-FEB-07:10 | 0.00 | 24113.18 | 17-FEB-13:20 | 0.00 |
March | 25220.79 | 01-MAR-11:09 | 0.00 | 82559.29 | 04-MAR-22:00 | 0.00 | 24096.62 | 01-MAR-13:30 | 0.00 |
April | 25220.79 | 01-APR-10:09 | 0.00 | 44935.05 | 29-APR-06:10 | 0.00 | 23896.81 | 01-APR-12:30 | 0.00 |
May | 25220.79 | 01-MAY-10:09 | 0.00 | 33344.02 | 08-MAY-06:10 | 0.00 | 23539.08 | 01-MAY-12:20 | 0.00 |
June | 25220.79 | 01-JUN-10:09 | 0.00 | 18263.59 | 17-JUN-05:10 | 0.00 | 22997.65 | 01-JUN-12:20 | 0.00 |
July | 25220.79 | 01-JUL-10:09 | 0.00 | 4979.84 | 08-JUL-05:10 | 0.00 | 22484.48 | 01-JUL-12:50 | 0.00 |
August | 25220.79 | 01-AUG-10:09 | 0.00 | 6345.21 | 17-AUG-22:00 | 0.00 | 22127.27 | 01-AUG-12:50 | 0.00 |
September | 25220.79 | 01-SEP-10:09 | 0.00 | 21298.20 | 17-SEP-06:10 | 0.00 | 22353.52 | 30-SEP-12:39 | 0.00 |
October | 25220.79 | 01-OCT-10:09 | 0.00 | 38758.75 | 10-OCT-06:10 | 0.00 | 22879.16 | 31-OCT-12:20 | 0.00 |
November | 25220.79 | 01-NOV-10:09 | 0.00 | 73193.13 | 12-NOV-03:09 | 0.00 | 23400.36 | 30-NOV-13:30 | 0.00 |
December | 25220.79 | 01-DEC-11:09 | 0.00 | 100243.38 | 31-DEC-07:10 | 0.00 | 23831.02 | 31-DEC-13:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 25220.79 | 0.00 | 4979.84 | 0.00 | 22127.27 | 0.00 | |||
Maximum of Months | 25220.79 | 0.00 | 112802.99 | 0.00 | 24113.18 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.00 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 |
February | 10.33 | 20.01 | 0.00 | 20.01 | 0.00 | 20.01 | 0.00 | 20.01 |
March | 10.00 | 20.12 | 0.00 | 20.12 | 0.00 | 20.12 | 0.00 | 20.12 |
April | 2.67 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
May | 2.17 | 20.42 | 0.17 | 20.42 | 0.17 | 20.69 | 0.00 | 20.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.54 | 0.00 | 24.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 24.66 | 0.00 | 24.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 24.68 | 0.17 | 24.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.67 | 0.00 | 24.67 |
October | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
November | 4.67 | 20.34 | 0.17 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
December | 12.00 | 20.04 | 0.00 | 20.04 | 0.00 | 20.04 | 0.00 | 20.04 |
Annual Sum or Average | 60.00 | 19.99 | 0.33 | 19.99 | 18.17 | 21.07 | 0.17 | 21.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.65 | 0.00 | 19.65 |
Maximum of Months | 18.00 | 20.53 | 0.17 | 20.53 | 6.83 | 24.68 | 0.17 | 24.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.91 | 0.00 | 26.91 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.68 | 0.00 | 26.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.28 | 0.00 | 27.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.62 | 0.00 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 28.30 | 0.00 | 28.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 29.07 | 0.00 | 29.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 28.96 | 0.00 | 28.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 28.58 | 0.00 | 28.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.55 | 0.00 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.17 | 0.00 | 27.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.75 | 0.00 | 26.75 |
Annual Sum or Average | 0.00 | 0.00 | 94.00 | 28.44 | 0.00 | 28.44 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 29.07 | 0.00 | 29.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.86 | 365.33 | 20.79 | 365.33 | 20.77 |
February | 545.00 | 20.92 | 224.50 | 20.81 | 224.50 | 20.74 |
March | 612.00 | 20.88 | 215.00 | 20.76 | 215.00 | 20.69 |
April | 554.50 | 21.16 | 97.17 | 21.00 | 97.17 | 20.87 |
May | 457.33 | 21.25 | 89.67 | 21.33 | 46.17 | 21.21 |
June | 244.83 | 21.68 | 249.33 | 22.75 | 6.83 | 22.72 |
July | 116.00 | 22.09 | 431.00 | 23.52 | 10.17 | 23.52 |
August | 150.17 | 21.76 | 362.00 | 23.27 | 0.83 | 23.26 |
September | 303.67 | 21.55 | 229.33 | 22.48 | 23.33 | 22.46 |
October | 522.67 | 21.25 | 47.67 | 21.21 | 30.33 | 21.10 |
November | 586.83 | 21.02 | 118.00 | 20.88 | 118.00 | 20.78 |
December | 609.00 | 20.87 | 268.17 | 20.77 | 268.17 | 20.72 |
Annual Sum or Average | 5312.00 | 21.12 | 2697.17 | 21.46 | 1405.83 | 21.31 |
Minimum of Months | 116.00 | 20.86 | 47.67 | 20.76 | 0.83 | 20.69 |
Maximum of Months | 612.00 | 22.09 | 431.00 | 23.52 | 365.33 | 23.52 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 18.81 | 449.00 | 18.75 | 449.00 | 18.73 |
February | 530.50 | 18.99 | 323.83 | 18.93 | 313.67 | 18.84 |
March | 607.83 | 19.06 | 301.33 | 18.90 | 300.83 | 18.81 |
April | 474.33 | 19.57 | 242.00 | 20.12 | 149.50 | 19.89 |
May | 451.83 | 21.27 | 316.17 | 22.30 | 188.33 | 22.46 |
June | 413.33 | 24.76 | 476.00 | 25.15 | 321.00 | 25.38 |
July | 482.83 | 25.92 | 580.83 | 25.83 | 466.00 | 25.91 |
August | 448.83 | 25.70 | 550.83 | 25.69 | 415.17 | 25.81 |
September | 420.17 | 23.71 | 409.17 | 24.47 | 273.50 | 24.78 |
October | 414.50 | 20.37 | 249.17 | 21.51 | 105.00 | 21.55 |
November | 514.83 | 19.33 | 239.67 | 19.46 | 189.83 | 19.27 |
December | 606.50 | 18.93 | 361.50 | 18.82 | 361.50 | 18.77 |
Annual Sum or Average | 5975.50 | 21.11 | 4499.50 | 21.74 | 3533.33 | 21.82 |
Minimum of Months | 413.33 | 18.81 | 239.67 | 18.75 | 105.00 | 18.73 |
Maximum of Months | 610.00 | 25.92 | 580.83 | 25.83 | 466.00 | 25.91 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.85755 | 14.98386 | -0.6369 | 14.61184 |
February | 551.00000 | 20.95368 | 18.44338 | -0.5327 | 12.33325 |
March | 612.00000 | 20.88076 | 20.03915 | -0.5275 | 11.91296 |
April | 590.00000 | 21.32219 | 25.65080 | -0.3588 | 9.61710 |
May | 611.00000 | 21.90798 | 29.68067 | -1.2256 | 39.53981 |
June | 592.00000 | 22.95503 | 36.99007 | -0.7313 | 20.04183 |
July | 609.00000 | 23.53209 | 39.04011 | -0.4656 | 11.49086 |
August | 612.00000 | 23.35302 | 35.21049 | -0.5547 | 14.22398 |
September | 590.00000 | 22.65174 | 36.83816 | -0.8134 | 23.87327 |
October | 610.00000 | 21.62178 | 28.33325 | -0.1848 | 7.68826 |
November | 591.00000 | 21.04395 | 21.85977 | -0.4284 | 10.03856 |
December | 609.00000 | 20.86539 | 17.44484 | -0.5758 | 12.95751 |
Annual Sum or Average | 7187.00000 | 21.83439 | 27.07924 | -0.5869 | 15.72273 |
Minimum of Months | 551.00000 | 20.85755 | 14.98386 | -1.2256 | 7.68826 |
Maximum of Months | 612.00000 | 23.53209 | 39.04011 | -0.1848 | 39.53981 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.81181 | 22.76244 | -0.7392 | 17.43525 |
February | 551.00000 | 19.18917 | 26.85352 | -0.6150 | 15.31215 |
March | 612.00000 | 19.08874 | 29.05971 | -0.6190 | 14.64176 |
April | 590.00000 | 20.56220 | 33.61515 | -0.2488 | 12.56353 |
May | 611.00000 | 22.06195 | 35.94634 | -0.8336 | 35.17397 |
June | 592.00000 | 24.57235 | 38.96560 | 0.05633 | 14.93004 |
July | 609.00000 | 25.55298 | 39.59162 | 0.41854 | 12.29922 |
August | 612.00000 | 25.25971 | 36.59564 | 0.29736 | 12.23595 |
September | 590.00000 | 23.77195 | 39.31528 | -0.1804 | 20.81119 |
October | 610.00000 | 21.55636 | 34.33451 | 0.04528 | 12.46952 |
November | 591.00000 | 19.91172 | 29.22403 | -0.3919 | 12.50260 |
December | 609.00000 | 18.94395 | 25.37461 | -0.6665 | 15.58750 |
Annual Sum or Average | 7187.00000 | 21.62089 | 32.65648 | -0.2881 | 16.35189 |
Minimum of Months | 551.00000 | 18.81181 | 22.76244 | -0.8336 | 12.23595 |
Maximum of Months | 612.00000 | 25.55298 | 39.59162 | 0.41854 | 35.17397 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 96983595.48 | 28766642.87 | 14.17 | 96983595.48 | -0.0 | 0.00 | 0.34 | 07-APR-13:57 | 0.00 | 01-APR-00:01 | 4651.28 | 07-APR-13:57 | 4651.28 | 07-APR-13:57 | 0.00 | 06-APR-16:10 | 1334.15 | 07-APR-13:57 | 0.00 | 01-APR-00:01 |
May | 0.139321E+10 | 0.386986E+09 | 82.51 | 0.135399E+10 | 39220835.24 | 0.00 | 1.00 | 20-MAY-02:61 | 0.00 | 01-MAY-00:01 | 16262.60 | 20-MAY-02:61 | 12923.35 | 20-MAY-02:61 | 3339.25 | 20-MAY-02:61 | 3901.98 | 20-MAY-02:61 | 0.00 | 01-MAY-00:01 |
June | 0.597827E+10 | 0.158581E+10 | 226.46 | 0.550284E+10 | 0.475437E+09 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 | 32562.55 | 21-JUN-02:61 | 28369.94 | 21-JUN-02:61 | 10151.92 | 22-JUN-02:62 | 7806.84 | 21-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.123277E+11 | 0.326047E+10 | 381.03 | 0.116697E+11 | 0.658036E+09 | 0.00 | 1.00 | 01-JUL-02:62 | 0.00 | 01-JUL-00:01 | 32562.55 | 19-JUL-02:41 | 32562.55 | 26-JUL-02:61 | 13126.27 | 01-JUL-02:62 | 7806.84 | 01-JUL-02:62 | 0.00 | 01-JUL-00:01 |
August | 0.959356E+10 | 0.254432E+10 | 325.83 | 0.938087E+10 | 0.212697E+09 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 | 32562.55 | 16-AUG-02:61 | 32562.55 | 07-AUG-03:21 | 10411.74 | 16-AUG-02:61 | 7806.84 | 05-AUG-02:61 | 0.00 | 01-AUG-00:01 |
September | 0.476342E+10 | 0.126329E+10 | 184.59 | 0.440682E+10 | 0.356598E+09 | 0.00 | 1.00 | 01-SEP-02:62 | 0.00 | 01-SEP-00:01 | 32562.55 | 04-SEP-02:13 | 31621.87 | 10-SEP-02:61 | 12760.82 | 06-SEP-02:61 | 7806.84 | 01-SEP-02:62 | 0.00 | 01-SEP-00:01 |
October | 0.474160E+09 | 0.136138E+09 | 40.58 | 0.474108E+09 | 51296.64 | 0.00 | 0.62 | 18-OCT-13:00 | 0.00 | 01-OCT-00:01 | 9114.41 | 18-OCT-13:00 | 9114.41 | 18-OCT-13:00 | 153.73 | 19-OCT-02:46 | 2431.63 | 18-OCT-13:00 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.346273E+11 | 0.920578E+10 | 1255.15 | 0.328853E+11 | 0.174204E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.123277E+11 | 0.326047E+10 | 381.03 | 0.116697E+11 | 0.658036E+09 | 0.00 | 1.00 | 0.00 | 32562.55 | 32562.55 | 13126.27 | 7806.84 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 7567698.42 | 2297704.62 | 1.99 | 7419859.86 | 147838.56 | 0.00 | 0.19 | 28-FEB-04:10 | 0.00 | 01-FEB-00:01 | 2110.73 | 28-FEB-04:10 | 1541.28 | 27-FEB-14:55 | 591.34 | 28-FEB-04:10 | 629.01 | 28-FEB-04:10 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.194689E+09 | 56522432.80 | 28.11 | 0.188403E+09 | 6285235.57 | 0.00 | 1.00 | 07-APR-03:21 | 0.00 | 01-APR-00:01 | 28351.47 | 07-APR-03:21 | 24670.57 | 07-APR-03:21 | 3680.90 | 07-APR-03:21 | 6797.24 | 07-APR-03:21 | 0.00 | 01-APR-00:01 |
May | 0.225713E+10 | 0.615205E+09 | 134.17 | 0.203765E+10 | 0.219480E+09 | 0.00 | 1.00 | 14-MAY-02:61 | 0.00 | 01-MAY-00:01 | 28351.47 | 19-MAY-03:21 | 24421.46 | 29-MAY-02:42 | 11475.90 | 19-MAY-03:21 | 6797.24 | 19-MAY-03:21 | 0.00 | 01-MAY-00:01 |
June | 0.791603E+10 | 0.205410E+10 | 307.35 | 0.687597E+10 | 0.104006E+10 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 | 28351.47 | 23-JUN-04:00 | 22637.60 | 25-JUN-02:61 | 14562.10 | 13-JUN-03:31 | 6797.24 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.152079E+11 | 0.392472E+10 | 446.49 | 0.138287E+11 | 0.137920E+10 | 0.00 | 1.00 | 01-JUL-02:11 | 0.00 | 01-JUL-00:01 | 28351.47 | 14-JUL-02:52 | 25686.14 | 17-JUL-14:00 | 15411.64 | 01-JUL-02:52 | 7225.24 | 17-JUL-14:00 | 0.00 | 01-JUL-00:01 |
August | 0.120343E+11 | 0.313584E+10 | 398.85 | 0.112431E+11 | 0.791211E+09 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 | 28351.47 | 09-AUG-02:52 | 27516.58 | 11-AUG-02:11 | 11928.85 | 01-AUG-02:61 | 6797.24 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 |
September | 0.672745E+10 | 0.174734E+10 | 247.42 | 0.576743E+10 | 0.960019E+09 | 0.00 | 1.00 | 01-SEP-02:11 | 0.00 | 01-SEP-00:01 | 28351.47 | 04-SEP-02:24 | 24259.24 | 10-SEP-02:42 | 16182.93 | 08-SEP-03:41 | 6797.24 | 01-SEP-02:11 | 0.00 | 01-SEP-00:01 |
October | 0.797665E+09 | 0.223994E+09 | 66.78 | 0.757688E+09 | 39976976.89 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:01 | 28351.47 | 01-OCT-02:61 | 24669.24 | 19-OCT-03:22 | 12619.75 | 01-OCT-02:61 | 6797.24 | 01-OCT-02:61 | 0.00 | 01-OCT-00:01 |
November | 11464580.12 | 3173057.79 | 3.09 | 9101097.79 | 2363482.34 | 0.00 | 1.00 | 05-NOV-02:61 | 0.00 | 01-NOV-00:01 | 14159.48 | 05-NOV-02:61 | 11570.58 | 05-NOV-02:61 | 3713.52 | 17-NOV-04:42 | 3397.37 | 05-NOV-02:61 | 0.00 | 01-NOV-00:01 |
December | 75450.78 | 23296.01 | 0.06 | 59885.96 | 15564.82 | 0.00 | 0.03 | 08-DEC-05:00 | 0.00 | 01-DEC-00:01 | 377.25 | 08-DEC-05:00 | 299.43 | 08-DEC-05:00 | 77.82 | 08-DEC-05:00 | 116.48 | 08-DEC-05:00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.451542E+11 | 0.117632E+11 | 1634.30 | 0.407155E+11 | 0.443876E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.152079E+11 | 0.392472E+10 | 446.49 | 0.138287E+11 | 0.137920E+10 | 0.00 | 1.00 | 0.00 | 28351.47 | 27516.58 | 16182.93 | 7225.24 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.32 | 33.16 | 39.17 | 39.94 | 252.65 | 0.00 | 0.00 | 0.00 |
February | 113.12 | 56.16 | 56.96 | 89.70 | 183.87 | 0.00 | 0.00 | 0.00 |
March | 152.10 | 62.93 | 89.16 | 134.17 | 146.39 | 0.00 | 0.00 | 0.00 |
April | 194.06 | 96.18 | 97.89 | 203.00 | 100.38 | 0.00 | 0.00 | 0.00 |
May | 214.37 | 95.38 | 118.99 | 239.29 | 79.04 | 0.00 | 0.00 | 0.00 |
June | 277.47 | 142.79 | 134.68 | 349.99 | 52.00 | 0.00 | 0.00 | 0.00 |
July | 291.21 | 164.63 | 126.58 | 392.44 | 43.68 | 0.00 | 0.00 | 0.00 |
August | 253.08 | 141.01 | 112.07 | 332.53 | 49.72 | 0.00 | 0.00 | 0.00 |
September | 179.03 | 92.41 | 86.61 | 215.16 | 72.23 | 0.00 | 0.00 | 0.00 |
October | 128.44 | 65.22 | 63.22 | 129.39 | 107.64 | 0.00 | 0.00 | 0.00 |
November | 81.40 | 38.01 | 43.40 | 60.15 | 153.25 | 0.00 | 0.00 | 0.00 |
December | 60.04 | 25.79 | 34.25 | 31.36 | 216.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 168.34 | 84.62 | 83.72 | 185.30 | 121.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.04 | 25.79 | 34.25 | 31.36 | 43.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 291.21 | 164.63 | 134.68 | 392.44 | 252.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 444.03 | 317.14 | 126.90 | 434.63 | 465.58 | 0.00 | 0.00 | 0.00 |
February | 565.47 | 406.71 | 158.76 | 612.21 | 341.95 | 0.00 | 0.00 | 0.00 |
March | 505.46 | 283.84 | 221.62 | 550.49 | 296.16 | 0.00 | 0.00 | 0.00 |
April | 406.30 | 194.34 | 211.97 | 463.01 | 211.44 | 0.00 | 0.00 | 0.00 |
May | 360.99 | 119.89 | 241.10 | 419.40 | 167.59 | 0.00 | 0.00 | 0.00 |
June | 358.68 | 104.61 | 254.07 | 467.74 | 114.90 | 0.00 | 0.00 | 0.00 |
July | 386.69 | 142.84 | 243.85 | 557.03 | 93.80 | 0.00 | 0.00 | 0.00 |
August | 459.56 | 231.70 | 227.86 | 640.29 | 105.84 | 0.00 | 0.00 | 0.00 |
September | 509.71 | 312.31 | 197.39 | 661.39 | 150.07 | 0.00 | 0.00 | 0.00 |
October | 532.87 | 368.47 | 164.40 | 637.43 | 214.38 | 0.00 | 0.00 | 0.00 |
November | 485.82 | 351.91 | 133.91 | 532.20 | 285.64 | 0.00 | 0.00 | 0.00 |
December | 422.25 | 304.91 | 117.34 | 424.02 | 396.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.37 | 260.59 | 191.78 | 532.70 | 236.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 358.68 | 104.61 | 117.34 | 419.40 | 93.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 565.47 | 406.71 | 254.07 | 661.39 | 465.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.51 | 26.40 | 39.11 | 34.49 | 262.66 | 0.00 | 0.00 | 0.00 |
February | 111.81 | 54.96 | 56.85 | 89.71 | 187.87 | 0.00 | 0.00 | 0.00 |
March | 143.09 | 52.43 | 90.66 | 123.08 | 152.06 | 0.00 | 0.00 | 0.00 |
April | 186.81 | 82.77 | 104.04 | 195.69 | 104.89 | 0.00 | 0.00 | 0.00 |
May | 231.07 | 105.38 | 125.69 | 263.76 | 82.05 | 0.00 | 0.00 | 0.00 |
June | 251.40 | 115.48 | 135.92 | 316.14 | 55.81 | 0.00 | 0.00 | 0.00 |
July | 257.53 | 130.13 | 127.40 | 348.54 | 46.97 | 0.00 | 0.00 | 0.00 |
August | 218.68 | 107.32 | 111.35 | 287.41 | 52.30 | 0.00 | 0.00 | 0.00 |
September | 175.91 | 88.93 | 86.98 | 212.72 | 75.61 | 0.00 | 0.00 | 0.00 |
October | 125.73 | 62.47 | 63.26 | 128.07 | 112.06 | 0.00 | 0.00 | 0.00 |
November | 89.00 | 44.15 | 44.85 | 73.48 | 158.62 | 0.00 | 0.00 | 0.00 |
December | 59.83 | 25.25 | 34.58 | 33.46 | 222.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.91 | 74.71 | 85.20 | 175.99 | 125.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 59.83 | 25.25 | 34.58 | 33.46 | 46.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 257.53 | 130.13 | 135.92 | 348.54 | 262.66 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.193709E+09 | 88807442.74 | 0.104901E+09 | 0.106965E+09 | 0.676694E+09 |
February | 0.273657E+09 | 0.135864E+09 | 0.137793E+09 | 0.217005E+09 | 0.444824E+09 |
March | 0.407381E+09 | 0.168563E+09 | 0.238818E+09 | 0.359369E+09 | 0.392081E+09 |
April | 0.503011E+09 | 0.249288E+09 | 0.253723E+09 | 0.526174E+09 | 0.260196E+09 |
May | 0.574163E+09 | 0.255466E+09 | 0.318697E+09 | 0.640907E+09 | 0.211707E+09 |
June | 0.719205E+09 | 0.370102E+09 | 0.349103E+09 | 0.907169E+09 | 0.134776E+09 |
July | 0.779987E+09 | 0.440947E+09 | 0.339040E+09 | 0.105111E+10 | 0.116984E+09 |
August | 0.677844E+09 | 0.377673E+09 | 0.300171E+09 | 0.890661E+09 | 0.133174E+09 |
September | 0.464040E+09 | 0.239535E+09 | 0.224505E+09 | 0.557695E+09 | 0.187220E+09 |
October | 0.344022E+09 | 0.174689E+09 | 0.169333E+09 | 0.346570E+09 | 0.288298E+09 |
November | 0.211001E+09 | 98509551.93 | 0.112491E+09 | 0.155913E+09 | 0.397221E+09 |
December | 0.160813E+09 | 69069419.66 | 91743518.08 | 83986316.33 | 0.579761E+09 |
Annual Sum or Average | 0.530883E+10 | 0.266851E+10 | 0.264032E+10 | 0.584352E+10 | 0.382294E+10 |
Minimum of Months | 0.160813E+09 | 69069419.66 | 91743518.08 | 83986316.33 | 0.116984E+09 |
Maximum of Months | 0.779987E+09 | 0.440947E+09 | 0.349103E+09 | 0.105111E+10 | 0.676694E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118930E+10 | 0.849424E+09 | 0.339880E+09 | 0.116411E+10 | 0.124702E+10 |
February | 0.136799E+10 | 0.983909E+09 | 0.384081E+09 | 0.148107E+10 | 0.827247E+09 |
March | 0.135382E+10 | 0.760242E+09 | 0.593578E+09 | 0.147444E+10 | 0.793236E+09 |
April | 0.105314E+10 | 0.503723E+09 | 0.549417E+09 | 0.120011E+10 | 0.548062E+09 |
May | 0.966879E+09 | 0.321126E+09 | 0.645752E+09 | 0.112332E+10 | 0.448871E+09 |
June | 0.929701E+09 | 0.271145E+09 | 0.658557E+09 | 0.121238E+10 | 0.297834E+09 |
July | 0.103572E+10 | 0.382591E+09 | 0.653130E+09 | 0.149194E+10 | 0.251240E+09 |
August | 0.123089E+10 | 0.620590E+09 | 0.610297E+09 | 0.171495E+10 | 0.283491E+09 |
September | 0.132116E+10 | 0.809517E+09 | 0.511644E+09 | 0.171432E+10 | 0.388988E+09 |
October | 0.142724E+10 | 0.986920E+09 | 0.440323E+09 | 0.170729E+10 | 0.574194E+09 |
November | 0.125925E+10 | 0.912148E+09 | 0.347100E+09 | 0.137947E+10 | 0.740391E+09 |
December | 0.113096E+10 | 0.816668E+09 | 0.314293E+09 | 0.113571E+10 | 0.106280E+10 |
Annual Sum or Average | 0.142661E+11 | 0.821800E+10 | 0.604805E+10 | 0.167991E+11 | 0.746337E+10 |
Minimum of Months | 0.929701E+09 | 0.271145E+09 | 0.314293E+09 | 0.112332E+10 | 0.251240E+09 |
Maximum of Months | 0.142724E+10 | 0.986920E+09 | 0.658557E+09 | 0.171495E+10 | 0.124702E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175459E+09 | 70711150.82 | 0.104748E+09 | 92370308.25 | 0.703495E+09 |
February | 0.270500E+09 | 0.132964E+09 | 0.137536E+09 | 0.217033E+09 | 0.454493E+09 |
March | 0.383264E+09 | 0.140434E+09 | 0.242831E+09 | 0.329646E+09 | 0.407275E+09 |
April | 0.484213E+09 | 0.214528E+09 | 0.269685E+09 | 0.507217E+09 | 0.271871E+09 |
May | 0.618901E+09 | 0.282252E+09 | 0.336650E+09 | 0.706451E+09 | 0.219749E+09 |
June | 0.651620E+09 | 0.299313E+09 | 0.352307E+09 | 0.819436E+09 | 0.144665E+09 |
July | 0.689763E+09 | 0.348547E+09 | 0.341216E+09 | 0.933539E+09 | 0.125814E+09 |
August | 0.585702E+09 | 0.287449E+09 | 0.298252E+09 | 0.769808E+09 | 0.140083E+09 |
September | 0.455962E+09 | 0.230515E+09 | 0.225446E+09 | 0.551361E+09 | 0.195975E+09 |
October | 0.336750E+09 | 0.167313E+09 | 0.169437E+09 | 0.343028E+09 | 0.300152E+09 |
November | 0.230697E+09 | 0.114445E+09 | 0.116252E+09 | 0.190454E+09 | 0.411154E+09 |
December | 0.160240E+09 | 67632520.93 | 92607102.11 | 89613417.08 | 0.597182E+09 |
Annual Sum or Average | 0.504307E+10 | 0.235610E+10 | 0.268697E+10 | 0.554995E+10 | 0.397191E+10 |
Minimum of Months | 0.160240E+09 | 67632520.93 | 92607102.11 | 89613417.08 | 0.125814E+09 |
Maximum of Months | 0.689763E+09 | 0.348547E+09 | 0.352307E+09 | 0.933539E+09 | 0.703495E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 470.26 | 942.10 | 581.87 | 376.70 | 205.17 | 0.00 | 0.00 |
February | 764.30 | 686.36 | 790.40 | 517.83 | 272.57 | 0.00 | 0.00 |
March | 795.22 | 582.09 | 800.65 | 399.21 | 401.44 | 0.00 | 0.00 |
April | 843.38 | 398.41 | 787.18 | 373.28 | 413.90 | 0.00 | 0.00 |
May | 906.79 | 313.02 | 806.43 | 320.66 | 485.77 | 0.00 | 0.00 |
June | 1120.29 | 209.13 | 887.55 | 362.87 | 524.68 | 0.00 | 0.00 |
July | 1289.52 | 175.97 | 935.44 | 437.61 | 497.83 | 0.00 | 0.00 |
August | 1252.03 | 199.65 | 931.31 | 480.03 | 451.28 | 0.00 | 0.00 |
September | 1080.22 | 288.86 | 864.65 | 493.66 | 370.99 | 0.00 | 0.00 |
October | 884.96 | 424.15 | 787.04 | 496.16 | 290.88 | 0.00 | 0.00 |
November | 641.53 | 573.21 | 656.23 | 434.07 | 222.16 | 0.00 | 0.00 |
December | 455.31 | 802.70 | 542.12 | 355.95 | 186.17 | 0.00 | 0.00 |
Annual Sum or Average | 875.73 | 465.58 | 780.63 | 419.92 | 360.71 | 0.00 | 0.00 |
Minimum of Months | 455.31 | 175.97 | 542.12 | 320.66 | 186.17 | 0.00 | 0.00 |
Maximum of Months | 1289.52 | 942.10 | 935.44 | 517.83 | 524.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.125954E+10 | 0.252331E+10 | 0.155847E+10 | 0.100894E+10 | 0.549529E+09 | 0.00 | 0.00 |
February | 0.184898E+10 | 0.166045E+10 | 0.191215E+10 | 0.125274E+10 | 0.659410E+09 | 0.00 | 0.00 |
March | 0.212993E+10 | 0.155906E+10 | 0.214446E+10 | 0.106924E+10 | 0.107523E+10 | 0.00 | 0.00 |
April | 0.218605E+10 | 0.103268E+10 | 0.204036E+10 | 0.967540E+09 | 0.107282E+10 | 0.00 | 0.00 |
May | 0.242875E+10 | 0.838400E+09 | 0.215994E+10 | 0.858844E+09 | 0.130110E+10 | 0.00 | 0.00 |
June | 0.290378E+10 | 0.542070E+09 | 0.230053E+10 | 0.940560E+09 | 0.135997E+10 | 0.00 | 0.00 |
July | 0.345386E+10 | 0.471311E+09 | 0.250547E+10 | 0.117208E+10 | 0.133339E+10 | 0.00 | 0.00 |
August | 0.335343E+10 | 0.534753E+09 | 0.249443E+10 | 0.128571E+10 | 0.120872E+10 | 0.00 | 0.00 |
September | 0.279992E+10 | 0.748730E+09 | 0.224116E+10 | 0.127957E+10 | 0.961595E+09 | 0.00 | 0.00 |
October | 0.237029E+10 | 0.113604E+10 | 0.210801E+10 | 0.132892E+10 | 0.779094E+09 | 0.00 | 0.00 |
November | 0.166284E+10 | 0.148577E+10 | 0.170095E+10 | 0.112510E+10 | 0.575843E+09 | 0.00 | 0.00 |
December | 0.121950E+10 | 0.214994E+10 | 0.145201E+10 | 0.953369E+09 | 0.498644E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.276169E+11 | 0.146825E+11 | 0.246180E+11 | 0.132426E+11 | 0.113753E+11 | 0.00 | 0.00 |
Minimum of Months | 0.121950E+10 | 0.471311E+09 | 0.145201E+10 | 0.858844E+09 | 0.498644E+09 | 0.00 | 0.00 |
Maximum of Months | 0.345386E+10 | 0.252331E+10 | 0.250547E+10 | 0.132892E+10 | 0.135997E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.155625E+11 | -0.147611E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -801378411.8 | 58.99 | 0.00 | 0.00 |
February | 0.142850E+11 | -0.135683E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -716628105.4 | 58.99 | 0.00 | 0.00 |
March | 0.156911E+11 | -0.148964E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -794722955.7 | 58.99 | 0.00 | 0.00 |
April | 0.145937E+11 | -0.138526E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -741088936.7 | 58.99 | 0.00 | 0.00 |
May | 0.142749E+11 | -0.135383E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -736661331.6 | 58.99 | 0.00 | 0.00 |
June | 0.129713E+11 | -0.123051E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -666175457.4 | 58.99 | 0.00 | 0.00 |
July | 0.127078E+11 | -0.120383E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -669532933.0 | 58.98 | 0.00 | 0.00 |
August | 0.124689E+11 | -0.117944E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -674504012.0 | 58.99 | 0.00 | 0.00 |
September | 0.122236E+11 | -0.115436E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -679914168.8 | 58.99 | 0.00 | 0.00 |
October | 0.132360E+11 | -0.124914E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -744632983.0 | 58.99 | 0.00 | 0.00 |
November | 0.136233E+11 | -0.128715E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -751889415.9 | 58.99 | 0.00 | 0.00 |
December | 0.149005E+11 | -0.141034E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -797165653.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.166539E+12 | -0.157764E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.877429E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.122236E+11 | -0.148964E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -801378411.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.156911E+11 | -0.115436E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -666175457.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.28 | 0.24 | 01-JAN-08:50 | 3880.72 | 29.85 | 142.50 | 228.50 | 3838.04 | 29.55 | 141.00 | 227.17 |
February | 275.00 | 0.26 | 0.24 | 01-FEB-08:09 | 6615.11 | 35.10 | 241.67 | 257.67 | 5872.89 | 31.63 | 189.33 | 258.17 |
March | 304.00 | 0.25 | 0.24 | 01-MAR-07:40 | 2307.58 | 22.07 | 117.83 | 326.67 | 2375.27 | 22.08 | 120.83 | 328.83 |
April | 325.17 | 0.25 | 0.24 | 01-APR-08:39 | 2359.08 | 21.07 | 75.50 | 358.17 | 1751.95 | 19.26 | 45.33 | 360.17 |
May | 385.83 | 0.26 | 0.24 | 01-MAY-05:49 | 2064.59 | 18.96 | 22.67 | 408.33 | 2012.53 | 19.08 | 30.83 | 410.33 |
June | 434.17 | 0.26 | 0.24 | 01-JUN-13:39 | 1982.40 | 18.49 | 4.17 | 433.17 | 2318.14 | 18.48 | 15.83 | 431.00 |
July | 417.33 | 0.25 | 0.24 | 01-JUL-06:40 | 2311.98 | 18.87 | 8.00 | 418.50 | 2453.93 | 18.81 | 22.00 | 424.83 |
August | 421.33 | 0.26 | 0.24 | 01-AUG-05:40 | 1758.25 | 18.67 | 32.50 | 402.50 | 1932.09 | 18.59 | 38.17 | 402.83 |
September | 352.17 | 0.27 | 0.24 | 01-SEP-06:40 | 2091.57 | 20.94 | 95.17 | 335.83 | 2369.06 | 21.00 | 94.50 | 338.83 |
October | 317.67 | 0.26 | 0.24 | 01-OCT-07:40 | 2450.42 | 25.73 | 148.67 | 302.67 | 2792.37 | 25.94 | 150.67 | 305.00 |
November | 269.50 | 0.27 | 0.24 | 01-NOV-07:49 | 4423.57 | 32.14 | 195.17 | 247.00 | 4538.38 | 32.40 | 196.00 | 247.50 |
December | 236.83 | 0.28 | 0.24 | 01-DEC-08:39 | 3022.26 | 29.77 | 141.00 | 229.00 | 3019.36 | 29.69 | 141.17 | 227.83 |
Annual Sum or Average | 3965.83 | 0.26 | 2762.07 | 23.28 | 1224.83 | 3948.00 | 2788.33 | 22.91 | 1185.67 | 3962.50 | ||
Minimum of Months | 226.83 | 0.25 | 0.24 | 1758.25 | 18.49 | 4.17 | 228.50 | 1751.95 | 18.48 | 15.83 | 227.17 | |
Maximum of Months | 434.17 | 0.28 | 0.24 | 6615.11 | 35.10 | 241.67 | 433.17 | 5872.89 | 32.40 | 196.00 | 431.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.425088E+11 | 61482.23 | 06-JAN-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.260618E+11 | 61482.23 | 01-FEB-03:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.229468E+11 | 61482.23 | 01-MAR-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111498E+11 | 29219.79 | 29-APR-02:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.721311E+10 | 25010.81 | 08-MAY-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120791E+10 | 12083.35 | 16-JUN-21:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147922E+09 | 5498.48 | 09-JUL-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.402904E+09 | 5329.98 | 17-AUG-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.269133E+10 | 11121.28 | 17-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.749907E+10 | 21943.88 | 10-OCT-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174122E+11 | 61482.23 | 12-NOV-03:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.330796E+11 | 61482.23 | 13-DEC-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172321E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.147922E+09 | 5329.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.425088E+11 | 61482.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.398028E+11 | 71432.31 | 29-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.211247E+11 | 47429.11 | 10-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165498E+11 | 48724.32 | 05-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.558422E+10 | 34132.95 | 29-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.336848E+10 | 17277.46 | 08-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161145E+09 | 9808.35 | 17-JUN-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 90080.74 | 150.13 | 17-AUG-22:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568399E+09 | 13927.72 | 17-SEP-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288957E+10 | 19210.70 | 10-OCT-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115289E+11 | 39577.61 | 27-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.269242E+11 | 50457.61 | 29-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128502E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.398028E+11 | 71432.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 96983595.48 | 96983595.48 | 4651.28 | 07-APR-13:57 | 4651.28 | 0.00 |
May | 0.00 | 0.00 | 0.139321E+10 | 0.135399E+10 | 16262.60 | 20-MAY-02:61 | 12923.35 | 0.00 |
June | 0.00 | 0.00 | 0.597827E+10 | 0.550284E+10 | 32562.55 | 21-JUN-02:61 | 28369.94 | 0.00 |
July | 0.00 | 0.00 | 0.123277E+11 | 0.116697E+11 | 32562.55 | 19-JUL-02:41 | 20679.15 | 0.00 |
August | 0.00 | 0.00 | 0.959356E+10 | 0.938087E+10 | 32562.55 | 16-AUG-02:61 | 22150.80 | 0.00 |
September | 0.00 | 0.00 | 0.476342E+10 | 0.440682E+10 | 32562.55 | 04-SEP-02:13 | 30218.06 | 0.00 |
October | 0.00 | 0.00 | 0.474160E+09 | 0.474108E+09 | 9114.41 | 18-OCT-13:00 | 9114.41 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.346273E+11 | 0.328853E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.123277E+11 | 0.116697E+11 | 32562.55 | 30218.06 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 7567698.42 | 7419859.86 | 2110.73 | 28-FEB-04:10 | 1519.39 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.194689E+09 | 0.188403E+09 | 28351.47 | 07-APR-03:21 | 24670.57 | 0.00 |
May | 0.00 | 0.00 | 0.225713E+10 | 0.203765E+10 | 28351.47 | 19-MAY-03:21 | 16875.58 | 0.00 |
June | 0.00 | 0.00 | 0.791603E+10 | 0.687597E+10 | 28351.47 | 23-JUN-04:00 | 21199.53 | 0.00 |
July | 0.00 | 0.00 | 0.152079E+11 | 0.138287E+11 | 28351.47 | 14-JUL-02:52 | 19207.58 | 0.00 |
August | 0.00 | 0.00 | 0.120343E+11 | 0.112431E+11 | 28351.47 | 09-AUG-02:52 | 20802.96 | 0.00 |
September | 0.00 | 0.00 | 0.672745E+10 | 0.576743E+10 | 28351.47 | 04-SEP-02:24 | 23630.57 | 0.00 |
October | 0.00 | 0.00 | 0.797665E+09 | 0.757688E+09 | 28351.47 | 01-OCT-02:61 | 15731.72 | 0.00 |
November | 0.00 | 0.00 | 11464580.12 | 9101097.79 | 14159.48 | 05-NOV-02:61 | 11570.58 | 0.00 |
December | 0.00 | 0.00 | 75450.78 | 59885.96 | 377.25 | 08-DEC-05:00 | 299.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.451542E+11 | 0.407155E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.152079E+11 | 0.138287E+11 | 28351.47 | 24670.57 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5805.25 | 21844.80 | 31-JAN-13:15 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 5903.17 | 21964.95 | 18-FEB-13:15 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5857.80 | 21924.15 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5637.18 | 21375.32 | 01-APR-12:40 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5347.97 | 20360.18 | 01-MAY-12:35 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5040.55 | 19102.35 | 01-JUN-12:40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4784.83 | 18008.68 | 01-JUL-12:40 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4697.00 | 17310.81 | 01-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 4744.84 | 17755.44 | 30-SEP-12:40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4955.52 | 18794.01 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 5259.13 | 20009.69 | 30-NOV-14:00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5557.69 | 21145.45 | 31-DEC-13:20 |
Annual Sum or Average | 0.00 | 5295.69 | ||||
Minimum of Months | 0.00 | 0.00 | 4697.00 | 17310.81 | ||
Maximum of Months | 0.00 | 0.00 | 5903.17 | 21964.95 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112472E+10 | 0.25 | 503.64 | 01-JAN-00:01 | 0.30 |
February | 0.101737E+10 | 0.25 | 503.64 | 01-FEB-00:01 | 0.30 |
March | 0.112411E+10 | 0.25 | 503.64 | 01-MAR-00:01 | 0.30 |
April | 0.111074E+10 | 0.26 | 503.64 | 01-APR-04:01 | 0.30 |
May | 0.116937E+10 | 0.26 | 503.64 | 01-MAY-04:01 | 0.30 |
June | 0.117956E+10 | 0.27 | 503.64 | 01-JUN-02:61 | 0.30 |
July | 0.124658E+10 | 0.28 | 503.64 | 01-JUL-00:55 | 0.30 |
August | 0.124298E+10 | 0.28 | 503.64 | 01-AUG-00:30 | 0.30 |
September | 0.117871E+10 | 0.27 | 503.64 | 01-SEP-00:55 | 0.30 |
October | 0.117760E+10 | 0.26 | 503.64 | 01-OCT-02:61 | 0.30 |
November | 0.110932E+10 | 0.26 | 503.64 | 01-NOV-04:01 | 0.30 |
December | 0.112502E+10 | 0.25 | 503.64 | 01-DEC-00:01 | 0.30 |
Annual Sum or Average | 0.138061E+11 | 0.26 | |||
Minimum of Months | 0.101737E+10 | 0.25 | 503.64 | 0.30 | |
Maximum of Months | 0.124658E+10 | 0.28 | 503.64 | 0.30 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.269096E+10 | 0.67 | 2027.80 | 06-JAN-03:01 | 1.01 |
February | 0.217468E+10 | 0.63 | 2027.80 | 01-FEB-03:06 | 1.01 |
March | 0.228316E+10 | 0.62 | 2027.80 | 01-MAR-04:30 | 1.01 |
April | 0.197665E+10 | 0.57 | 1233.68 | 29-APR-04:01 | 0.79 |
May | 0.195527E+10 | 0.54 | 1219.47 | 07-MAY-04:06 | 0.78 |
June | 0.178142E+10 | 0.52 | 1050.24 | 16-JUN-21:03 | 0.71 |
July | 0.185106E+10 | 0.53 | 1398.06 | 20-JUL-02:61 | 0.83 |
August | 0.183945E+10 | 0.53 | 1294.89 | 09-AUG-02:61 | 0.80 |
September | 0.181509E+10 | 0.53 | 1415.66 | 05-SEP-02:61 | 0.84 |
October | 0.195951E+10 | 0.54 | 1148.79 | 10-OCT-06:10 | 0.76 |
November | 0.210938E+10 | 0.59 | 2027.80 | 12-NOV-03:05 | 1.01 |
December | 0.250035E+10 | 0.65 | 2027.80 | 13-DEC-03:02 | 1.01 |
Annual Sum or Average | 0.249370E+11 | 0.58 | |||
Minimum of Months | 0.178142E+10 | 0.52 | 1050.24 | 0.71 | |
Maximum of Months | 0.269096E+10 | 0.67 | 2027.80 | 1.01 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157898E+10 | 0.62 | 1224.68 | 29-JAN-05:02 | 1.01 |
February | 0.128322E+10 | 0.59 | 993.03 | 10-FEB-05:03 | 0.91 |
March | 0.135453E+10 | 0.57 | 1005.53 | 05-MAR-05:02 | 0.91 |
April | 0.121275E+10 | 0.55 | 864.72 | 29-APR-04:03 | 0.84 |
May | 0.123663E+10 | 0.55 | 1338.27 | 20-MAY-02:61 | 1.04 |
June | 0.119027E+10 | 0.56 | 1338.27 | 01-JUN-02:61 | 1.04 |
July | 0.128932E+10 | 0.58 | 1338.27 | 01-JUL-02:11 | 1.03 |
August | 0.127156E+10 | 0.58 | 1338.27 | 01-AUG-02:61 | 1.04 |
September | 0.120711E+10 | 0.57 | 1338.27 | 01-SEP-02:11 | 1.04 |
October | 0.123185E+10 | 0.55 | 1338.27 | 01-OCT-02:61 | 1.04 |
November | 0.127003E+10 | 0.57 | 917.26 | 27-NOV-05:03 | 0.87 |
December | 0.145471E+10 | 0.59 | 1022.26 | 29-DEC-05:03 | 0.92 |
Annual Sum or Average | 0.155809E+11 | 0.57 | |||
Minimum of Months | 0.119027E+10 | 0.55 | 864.72 | 0.84 | |
Maximum of Months | 0.157898E+10 | 0.62 | 1338.27 | 1.04 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 49.41 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 50.67 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 50.68 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 50.86 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 50.01 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 52.00 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:10 | 0.00 | 0.00 | 52.43 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 52.24 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 52.18 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:02 | 0.00 | 0.00 | 46.31 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 51.76 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 51.33 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 46.31 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 52.43 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 36.42 | 36.42 | 5805.25 | 21844.80 | 31-JAN-13:15 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 51.10 | 51.10 | 5903.17 | 21964.95 | 18-FEB-13:15 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 51.07 | 51.07 | 5857.80 | 21924.15 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.00 | 51.00 | 5637.18 | 21375.32 | 01-APR-12:40 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 37.23 | 37.23 | 5347.97 | 20360.18 | 01-MAY-12:35 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 51.79 | 51.79 | 5040.55 | 19102.35 | 01-JUN-12:40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 51.95 | 51.95 | 4784.83 | 18008.68 | 01-JUL-12:40 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.00 | 52.00 | 4697.00 | 17310.81 | 01-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.40 | 52.40 | 4744.84 | 17755.44 | 30-SEP-12:40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 40.09 | 40.09 | 4955.52 | 18794.01 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.16 | 52.16 | 5259.13 | 20009.69 | 30-NOV-14:00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 51.81 | 51.81 | 5557.69 | 21145.45 | 31-DEC-13:20 |
Annual Sum or Average | 0.00 | 5295.69 | ||||||
Minimum of Months | 0.00 | 0.00 | 36.42 | 36.42 | 4697.00 | 17310.81 | ||
Maximum of Months | 0.00 | 0.00 | 52.40 | 52.40 | 5903.17 | 21964.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.269096E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.217468E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.228316E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.200542E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.234225E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.336723E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.511154E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.438377E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.307837E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.209565E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.210938E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.250035E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.341428E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.200542E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.511154E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.157898E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.128551E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.135453E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.126927E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.185183E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.324437E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.521404E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.440740E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.295445E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.145585E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.127320E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.145473E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.273442E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.126927E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.521404E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.269096E+10 | 0.00 | 0.425088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217468E+10 | 0.00 | 0.260618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.228316E+10 | 0.00 | 0.229468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197665E+10 | 96983595.48 | 0.111498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195527E+10 | 0.139321E+10 | 0.721311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.178142E+10 | 0.597245E+10 | 0.120791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.185106E+10 | 0.123020E+11 | 0.147922E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.183945E+10 | 0.957788E+10 | 0.402904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.181509E+10 | 0.475056E+10 | 0.269133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195951E+10 | 0.474160E+09 | 0.749907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210938E+10 | 0.00 | 0.174122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250035E+10 | 0.00 | 0.330796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.249370E+11 | 0.345672E+11 | 0.172321E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.178142E+10 | 0.00 | 0.147922E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.269096E+10 | 0.123020E+11 | 0.425088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157898E+10 | 0.00 | 0.398028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128322E+10 | 7567698.42 | 0.211247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135453E+10 | 0.00 | 0.165498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121275E+10 | 0.193862E+09 | 0.558422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123663E+10 | 0.225418E+10 | 0.336848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119027E+10 | 0.789396E+10 | 0.161145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.128932E+10 | 0.151490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127156E+10 | 0.119973E+11 | 90080.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120711E+10 | 0.669681E+10 | 0.568399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123185E+10 | 0.791803E+09 | 0.288957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127003E+10 | 11464580.12 | 0.115289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145471E+10 | 75450.78 | 0.269242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155809E+11 | 0.449960E+11 | 0.128502E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157898E+10 | 0.151490E+11 | 0.398028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.269096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.228316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197665E+10 | 0.00 | 0.00 | 0.00 | 28766642.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195527E+10 | 0.00 | 0.00 | 0.00 | 0.386986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.178142E+10 | 0.00 | 0.00 | 0.00 | 0.158581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.185106E+10 | 0.00 | 0.00 | 0.00 | 0.326047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.183945E+10 | 0.00 | 0.00 | 0.00 | 0.254432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.181509E+10 | 0.00 | 0.00 | 0.00 | 0.126329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195951E+10 | 0.00 | 0.00 | 0.00 | 0.136138E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.249370E+11 | 0.00 | 0.00 | 0.00 | 0.920578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.178142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.269096E+10 | 0.00 | 0.00 | 0.00 | 0.326047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.157898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128322E+10 | 0.00 | 0.00 | 0.00 | 2297704.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121275E+10 | 0.00 | 0.00 | 0.00 | 56522432.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123663E+10 | 0.00 | 0.00 | 0.00 | 0.615205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119027E+10 | 0.00 | 0.00 | 0.00 | 0.205410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.128932E+10 | 0.00 | 0.00 | 0.00 | 0.392472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127156E+10 | 0.00 | 0.00 | 0.00 | 0.313584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120711E+10 | 0.00 | 0.00 | 0.00 | 0.174734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123185E+10 | 0.00 | 0.00 | 0.00 | 0.223994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127003E+10 | 0.00 | 0.00 | 0.00 | 3173057.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145471E+10 | 0.00 | 0.00 | 0.00 | 23296.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155809E+11 | 0.00 | 0.00 | 0.00 | 0.117632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157898E+10 | 0.00 | 0.00 | 0.00 | 0.392472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.292142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312511E+11 | 0.00 | 0.00 | 3.61 |
February | 0.384954E+10 | 0.00 | 0.00 | 243999.94 | 0.00 | 0.201150E+11 | 0.200699E+09 | 0.00 | 3.60 |
March | 0.497374E+10 | 0.00 | 0.00 | 1365.49 | 0.00 | 0.185319E+11 | 17503294.21 | 0.00 | 3.61 |
April | 0.622604E+10 | 0.00 | 0.00 | 2675219.34 | 0.00 | 0.903276E+10 | 0.112825E+10 | 0.00 | 3.77 |
May | 0.642229E+10 | 11976982.41 | 0.00 | 11290326.27 | 0.00 | 0.537392E+10 | 0.265864E+10 | 0.00 | 4.22 |
June | 0.462791E+10 | 0.219306E+09 | 0.00 | 23524670.73 | 0.00 | 0.395010E+09 | 0.426680E+10 | 0.00 | 4.71 |
July | 0.236886E+10 | 0.764006E+09 | 0.00 | 35660993.92 | 0.00 | 231462.63 | 0.415291E+10 | 0.00 | 4.86 |
August | 0.313064E+10 | 0.506584E+09 | 0.00 | 32584098.51 | 0.00 | 11992902.77 | 0.504344E+10 | 0.00 | 4.96 |
September | 0.541370E+10 | 0.254171E+09 | 0.00 | 19326775.20 | 0.00 | 0.146809E+10 | 0.417687E+10 | 0.00 | 4.58 |
October | 0.866737E+10 | 0.00 | 0.00 | 5141154.82 | 0.00 | 0.493788E+10 | 0.196349E+10 | 0.00 | 3.92 |
November | 0.650063E+10 | 0.00 | 0.00 | 175896.42 | 0.00 | 0.136835E+11 | 0.236986E+09 | 0.00 | 3.56 |
December | 0.371288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256779E+11 | 0.00 | 0.00 | 3.61 |
Annual Sum or Average | 0.588150E+11 | 0.175604E+10 | 0.00 | 0.130625E+09 | 0.00 | 0.130479E+12 | 0.238456E+11 | 0.00 | 4.09 |
Minimum of Months | 0.236886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 231462.63 | 0.00 | 0.00 | 3.56 |
Maximum of Months | 0.866737E+10 | 0.764006E+09 | 0.00 | 35660993.92 | 0.00 | 0.312511E+11 | 0.504344E+10 | 0.00 | 4.96 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.692385E+11 | 0.00 | 0.00 | 21535.56 | 0.00 | 65343563.54 | 8901245.81 | 0.00 | 7.49 |
February | 0.474860E+11 | 0.00 | 0.00 | 459414.96 | 0.00 | 17695599.46 | 0.806167E+09 | 0.00 | 7.18 |
March | 0.467390E+11 | 0.00 | 0.00 | 86210.72 | 0.00 | 13922026.50 | 0.287262E+09 | 0.00 | 7.10 |
April | 0.309335E+11 | 0.00 | 0.00 | 5760227.83 | 0.00 | 5684934.13 | 0.429266E+10 | 0.00 | 6.92 |
May | 0.238728E+11 | 0.00 | 0.00 | 25163035.08 | 0.00 | 0.00 | 0.887677E+10 | 0.00 | 6.96 |
June | 0.919819E+10 | 16428342.95 | 0.00 | 55613067.31 | 0.00 | 0.00 | 0.143970E+11 | 0.00 | 7.09 |
July | 0.410560E+10 | 0.255053E+09 | 0.00 | 83062554.69 | 0.00 | 0.00 | 0.141421E+11 | 0.00 | 7.25 |
August | 0.546866E+10 | 0.149756E+09 | 0.00 | 72354238.31 | 0.00 | 0.00 | 0.157348E+11 | 0.00 | 7.22 |
September | 0.121659E+11 | 65484369.25 | 0.00 | 44085693.98 | 0.00 | 0.00 | 0.131909E+11 | 0.00 | 7.11 |
October | 0.255658E+11 | 0.00 | 0.00 | 12919191.61 | 0.00 | 0.00 | 0.880272E+10 | 0.00 | 6.93 |
November | 0.387518E+11 | 0.00 | 0.00 | 1893996.28 | 0.00 | 8953834.56 | 0.304116E+10 | 0.00 | 6.99 |
December | 0.568894E+11 | 0.00 | 0.00 | 74910.55 | 0.00 | 27636350.25 | 0.253329E+09 | 0.00 | 7.29 |
Annual Sum or Average | 0.370415E+12 | 0.486722E+09 | 0.00 | 0.301494E+09 | 0.00 | 0.139236E+09 | 0.838337E+11 | 0.00 | 7.13 |
Minimum of Months | 0.410560E+10 | 0.00 | 0.00 | 21535.56 | 0.00 | 0.00 | 8901245.81 | 0.00 | 6.92 |
Maximum of Months | 0.692385E+11 | 0.255053E+09 | 0.00 | 83062554.69 | 0.00 | 65343563.54 | 0.157348E+11 | 0.00 | 7.49 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:15
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.120044E+11 | 0.220709E+11 | 0.153393E+12 | 0.00 | 0.284156E+11 |
February | 0.216962E+11 | 0.157136E+11 | 0.112172E+12 | 32817051.26 | 0.215770E+11 |
March | 0.405563E+11 | 0.154293E+11 | 0.111969E+12 | 0.00 | 0.227803E+11 |
April | 0.464720E+11 | 0.109540E+11 | 0.872668E+11 | 0.333843E+09 | 0.205001E+11 |
May | 0.636959E+11 | 0.968341E+10 | 0.810079E+11 | 0.103271E+10 | 0.265447E+11 |
June | 0.714249E+11 | 0.586182E+10 | 0.591464E+11 | 0.154480E+10 | 0.399208E+11 |
July | 0.718005E+11 | 0.349056E+10 | 0.451005E+11 | 0.156769E+10 | 0.600806E+11 |
August | 0.591009E+11 | 0.434843E+10 | 0.526110E+11 | 0.190074E+10 | 0.504512E+11 |
September | 0.428607E+11 | 0.648778E+10 | 0.639389E+11 | 0.147888E+10 | 0.341438E+11 |
October | 0.254351E+11 | 0.981531E+10 | 0.863905E+11 | 0.612179E+09 | 0.195986E+11 |
November | 0.109165E+11 | 0.128401E+11 | 0.101413E+12 | 7193150.16 | 0.176802E+11 |
December | 0.643031E+10 | 0.181479E+11 | 0.132045E+12 | 0.00 | 0.231889E+11 |
Annual Sum or Average | 0.472394E+12 | 0.134843E+12 | 0.108645E+13 | 0.851086E+10 | 0.364882E+12 |
Minimum of Months | 0.643031E+10 | 0.349056E+10 | 0.451005E+11 | 0.00 | 0.176802E+11 |
Maximum of Months | 0.718005E+11 | 0.220709E+11 | 0.153393E+12 | 0.190074E+10 | 0.600806E+11 |