Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 08:28:21
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1163.05 | 5005.74 | 5005.74 |
Net Site Energy | 1163.05 | 5005.74 | 5005.74 |
Total Source Energy | 2460.28 | 10588.98 | 10588.98 |
Net Source Energy | 2460.28 | 10588.98 | 10588.98 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 203.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 21.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 239.49 | 451.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 60.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 133.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 40.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 575.87 | 587.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 203.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 21.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 10.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 220.85 | 451.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 60.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 133.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 12.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 19.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 203.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 21.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 10.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 239.49 | 451.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 60.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 133.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 40.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 137.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1136.64 | 584.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1204.43 | 1942.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2478.52 | 2527.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 137.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1136.64 | 584.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1204.43 | 1942.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2478.52 | 2527.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 575.868 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 575.868 | 100.00 |
Total On-Site and Utility Electric Sources | 575.868 | 100.00 |
Total Electricity End Uses | 575.868 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 892.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6776.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 4.0792 | 1.33 | 110.4804 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.6205 | 18.52 | 1009.9592 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 6.8498 | 2.48 | 560.2198 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 6.8498 | 2.48 | 560.2198 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 4.0792 | 1.33 | 110.4804 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.6205 | 18.52 | 1009.9592 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 6.8498 | 1.24 | 560.2198 | |||||||
Conditioned Total | 232.34 | 6.8498 | 1.24 | 560.2198 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 6.8498 | 2.48 | 560.2198 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 25-JUL-10:20 | 18-JAN-13:00 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14888.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 989.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 12932.59 | 21742.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3002.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 19809.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 3931.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 35743.36 | 41551.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14888.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 989.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 12341.79 | 21742.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 3002.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 19809.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 643.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 67.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 33.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 758.45 | 489.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 192.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 145.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 127.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1823.77 | 636.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 8.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2771.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 289.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 145.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3264.36 | 2105.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 828.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 624.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 550.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7849.49 | 2739.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 8.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2771.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 289.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 145.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3264.36 | 2105.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 828.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 624.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 550.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7849.49 | 2739.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.98 |
KITCHEN DIRECT AIR | 1.14 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.98 | 1.98 | 1.98 | 1.98 | 1.98 | 1.98 | 1.00 | 1.00 | 1.98 |
PSZ-AC_2:2 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.98 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.14 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.98 | 2119.57 |
PSZ-AC_2:2_ADDAQ FAN | 1.14 | 1263.64 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.98 | 1.98 | 1.98 | 1.31 | 49188.48 | 51462.69 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 0.753280 | 28342.03 | 43175.09 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.98 | 0.990410 | 1.32 | 49188.48 | 24594.24 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.14 | 0.570667 | 0.760887 | 28342.03 | 14171.01 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 51462.69 |
PSZ-AC_2:2 HEATING COIL | 43175.09 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 4.079 | 110.480 | 0.000 | 0.000 | 0.000 | 0.000 | 114.560 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.620 | 261.340 | 748.620 | 0.000 | 0.000 | 0.000 | 1019.580 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 473.883 | 4.079 | 5.413 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 473.883 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1117.624 | 9.620 | 178.156 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1117.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 12834.676 | 110.480 | 146.608 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3722.056 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 29769.412 | 256.254 | 4745.415 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 8633.129 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 277.500 | 2.389 | 44.235 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 313.300 | 2.697 | 49.942 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 86968.240 | 748.620 | 13863.236 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 25220.790 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.6929 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.209 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.33002231E-12 | 0.10712597E-14 | -0.10720425E-12 | 0.10137879E-15 |
34 | 6 | 0.29661659E-07 | 0.19687232E-09 | 0.67865745E-08 | -0.14052424E-12 |
35 | 5 | -0.19512200E-03 | 0.16741682E-05 | -0.10029371E-03 | 0.67057946E-08 |
36 | 4 | 0.29799499 | 0.81016957E-03 | 0.10178761 | -0.34398158E-04 |
37 | 3 | -7.3821031 | 0.24971312E-01 | -2.3732702 | 0.29576512E-01 |
38 | 2 | 41.252923 | 0.88368331E-01 | 15.405914 | -0.33759269 |
39 | 1 | -80.838295 | 0.39713828E-01 | -29.267905 | 1.0848528 |
40 | 0 | 46.824337 | 0.79570062E-03 | 16.288235 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.23 | 38 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 | ||
2 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.23 | 39 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 | ||
3 | NONRESWINDOW_U_0.503_SHGC_EAST_0.23 | 40 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 | ||
4 | NONRESWINDOW_U_0.503_SHGC_WEST_0.23 | 41 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.238 | 0.3637 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 1.853E-002 | 1.595E-004 | 1.994E-004 | 0.188 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 1.853E-002 | 1.595E-004 | 1.953E-004 | 0.188 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5132E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.1811E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.3819E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0602E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.2491E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.1898E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.0078E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0016E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.2166E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.1254E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.4843E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.3775E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.5790E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.5208E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.0845E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.0846E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.6939E-003 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.2919E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 8.1369E-003 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.1144E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.1956E-003 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0133E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0017E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0078E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 22397.39664 | 26876.87597 | 1.65068 | 1.98082 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.20000 | 1.71672E-002 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 1658.14406 | 1989.77287 | 6.98474E-002 | 0.41606 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 8.70000 | 6.99286E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 15212.80467 | 18255.36560 | 0.93185 | 1.14133 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32.59700 | 1.71661E-002 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.14133 | 00:10:00 | 8.70000 | 6.99286E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 31161.18 | 1.98082 | 1.98082 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 15738.84 | 0.41606 | 0.41606 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 28139.67 | 1.14133 | 1.14133 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 43175.09 | 1.14133 | 1.14133 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.98082 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14133 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.98082 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.98082 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.98082 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.98082 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.98082 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.98082 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14133 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14133 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14133 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14133 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14133 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14133 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.98082 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.14133 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.98082 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.98082 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2119.57119 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.98082 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.98082 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.98082 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.30734 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.98082 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.99041 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.32055 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 49188.48000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 24594.24000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 49188.48000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 51462.69464 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 51462.69464 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14133 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14133 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1263.63741 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14133 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14133 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14133 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75328 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14133 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57067 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76089 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28342.03000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14171.01500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28342.03000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 43175.08870 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 43175.08870 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 47780.6 | 12.16 | 12.10 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 27530.8 | 12.34 | 12.29 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_EAST_0.23 | N/A | 2.860 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.23 | N/A | 2.860 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_WEST_0.23 | N/A | 2.860 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 6.5510811110E-002 | 0.2297482729 | Pass | Pass | 0.1099950676 | 0.3503296698 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1828702403 | 0.6067381006 | Pass | Pass | 0.1986901599 | 1.0209913519 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4254514090 | 0.4441688392 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 597.60 | -71.6 | -191.4 | 4.16 | 1366.04 | 1704.83 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.503_SHGC_EAST_0.23 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.860 | 0.231 | 0.254 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.23 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.860 | 0.231 | 0.254 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.503_SHGC_WEST_0.23 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.860 | 0.231 | 0.254 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.860 | 0.231 | 0.254 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.860 | 0.231 | 0.254 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 4.0792 | 116.17 | 473.88 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 43.48 | 0.0000 | Y | 3.87 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.6205 | 116.17 | 1117.62 | LightsWired | LTG_SCH_KITCHEN | 86.84 | 168.00 | 82.89 | 0.0000 | Y | 17.39 |
Interior Lighting Total | 6.8498 | 232.34 | 1591.51 | 21.26 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 473.88 | 180.08 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 473.88 | 180.08 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 209.35 | AstronomicalClock | - | 48.82 | 48.82 | 1.92 | |
EXTERIOR_LIGHTS_B | 742.80 | AstronomicalClock | - | 83.82 | 62.82 | 8.76 | |
Exterior Lighting Total | 952.15 | 10.68 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 49188.48 | 34485.06 | 14703.42 | 0.70 | 3.92 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28342.03 | 19870.03 | 8472.00 | 0.70 | 3.99 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 47780.6 | 12.16 | 12.10 | ||||
PSZ-AC_2:2 COOLING COIL | 27530.8 | 12.34 | 12.29 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 51462.69 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 43175.09 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.98 | 2119.57 | 1070.05 | 1.00 | 1.32 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1263.64 | 1107.16 | 1.00 | 1.37 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.95 | 1.24 | 0.36 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 22397.40 | 26876.88 | 231.36 | 1.651 | 1.981 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.86 | 0.01213 | 33.20 | 0.01717 | 0.416 | 0.00 |
KITCHEN | 15212.80 | 18255.37 | 157.14 | 0.932 | 1.141 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.01025 | 32.60 | 0.01717 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 1658.14 | 1989.77 | 17.13 | 0.070 | 0.416 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00784 | 8.70 | 0.00699 | 0.416 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.141 | 00:10:00 | 15.56 | 26.18 | 0.00489 | 8.70 | 0.00699 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.98 | 1.98 | 0.42 | 0.42 | 1.9808 | 1.9808 | 1.9808 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.14 | 1.14 | 1.14 | 1.14 | 1.1413 | 1.1413 | 1.1413 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 49188.480 | 34485.060 | 1.980820 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24594.24 | 13498.90 | 1.320547 | 25.82 | 20.67 | 0.01318536 | 11.94 | 11.73 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 31.5064 | 23.86 | 0.01212662 | 65.3771 | 22397.40 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 51462.695 | 51462.695 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 51462.69 | 51462.69 | 1.980820 | 18.50 | 13.63 | 0.00772755 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 21.0042 | 20.95 | 0.00792290 | 51.3277 | 904.87 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28342.030 | 19870.030 | 1.141330 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14171.01 | 7062.25 | 0.760887 | 33.20 | 25.32 | 0.01716721 | 11.91 | 11.72 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 150.0005 | 26.09 | 0.01046184 | 49.5025 | 13563.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 43175.089 | 43175.089 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 43175.09 | 43175.09 | 1.141334 | 8.70 | 8.70 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 100.0000 | 26.18 | 0.00489424 | 23.2388 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 49188.480 | 34485.060 | 1.980820 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1029.3509 | 1004.8586 | 1.2027 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.980820 | 2.38240951 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 24594.24 | 13498.90 | 1.0000 | 1.58827289 | 1.320547 | 25.82 | 20.67 | 0.01318536 | 59550.0 | 11.94 | 11.73 | 0.00850000 | 33440.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24594.24 | 33.20 | 0.01716721 | 25.32 | 0.41605618 | 31.5064 | 23.85 | 0.01212662 | 23.86 | 0.01212662 | 65.3771 | 22397.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 51462.695 | 51462.695 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.980820 | 2.38240951 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 51462.69 | 51462.69 | 1.0000 | 2.38240951 | 1.980820 | 18.50 | 13.63 | 0.00772755 | 38184.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51462.69 | 8.70 | 0.00699286 | 8.70 | 0.41605618 | 21.0042 | 21.11 | 0.00792290 | 20.95 | 0.00792290 | 51.3277 | 904.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28342.030 | 19870.030 | 1.141330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1036.7530 | 1004.8586 | 1.2027 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.141334 | 1.37272629 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 14171.01 | 7062.25 | 1.0000 | 0.91514802 | 0.760887 | 33.20 | 25.32 | 0.01716721 | 77354.4 | 11.91 | 11.72 | 0.00850000 | 33416.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14171.01 | 33.20 | 0.01716721 | 25.32 | 1.14133354 | 150.0005 | 26.04 | 0.01046184 | 26.09 | 0.01046184 | 49.5025 | 13563.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 43175.089 | 43175.089 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.141334 | 1.37272629 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 43175.09 | 43175.09 | 1.0000 | 1.37272629 | 1.141334 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 43175.09 | 8.70 | 0.00699286 | 8.70 | 1.14133354 | 100.0000 | 0.00 | 0.00489424 | 26.18 | 0.00489424 | 23.2388 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 6594.00 | 5243.00 | 4794.50 |
KITCHEN | 7080.17 | 6832.17 | 6775.83 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 7080.83 | 7154.83 | 6776.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 166.67 | 0.00 | 9.00 |
KITCHEN | 0.00 | 1224.83 | 0.00 | 883.33 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 1311.83 | 0.00 | 892.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.328 | 4.121 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 9.495 | 0.011 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.171 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 7.525 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 11280652.68 | 0.00 | 11280652.68 | 10274901.40 | 21555554.08 | 13120747.55 | 1394.06 | 7361.41 | 4.54 | 562.56 |
KITCHEN | 24980312.52 | 0.00 | 24980312.52 | 43474.78 | 25023787.31 | 35993094.65 | 7223.55 | 1536.45 | 0.00 | 1068.26 |
Total Facility | 36260965.20 | 0.00 | 36260965.20 | 10318376.18 | 46579341.38 | 49113842.20 | 7237.86 | 7375.86 | 4.54 | 1135.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4161 | 0.0000 | 0.4161 | 0.3965 | 0.8126 | 0.4161 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 0.9045 | 0.0000 | 0.9045 | 0.0010 | 0.9056 | 1.1413 | 5690.12 | 1496.88 | 0.00 |
Total Facility | 1.3206 | 0.0000 | 1.3206 | 0.3975 | 1.7181 | 1.5574 | 5690.12 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 16318155.29 | 0.00 | 16318155.29 | 13120747.55 | 1318.54 | 3.38 | 7438.07 | 562.56 |
PSZ-AC_2:2 | 36136047.08 | 0.00 | 36136047.08 | 35993094.65 | 4437.32 | 146.25 | 4176.43 | 1068.26 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6019 | 0.0000 | 0.6019 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.3085 | 0.0000 | 1.3085 | 1.1413 | 3030.93 | 135.25 | 4020.82 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 382.50 | 0.00 | 7367.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 1423.79 | 0.00 | 1685.26 | 5146.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 0.6019 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 1.6519 | 0.0000 | 1.1203 | 1.2365 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 386 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 575.87 | 2861.55 | 04-FEB-01:20 | 35743.36 | 25-JUL-10:20 |
Electricity:Building | 268.68 | 1624.98 | 01-JAN-01:20 | 17215.91 | 02-JAN-11:10 |
Electricity:Zone:DINING | 70.40 | 280.44 | 01-JAN-01:20 | 3811.41 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 260.74 | 1488.70 | 01-JAN-01:20 | 13921.86 | 02-JAN-11:10 |
InteriorLights:Electricity | 21.26 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-17:40 |
InteriorLights:Electricity:Zone:DINING | 3.87 | 25.01 | 01-JAN-01:20 | 389.13 | 02-JAN-17:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 21.26 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity | 21.26 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 3.87 | 25.01 | 01-JAN-01:20 | 389.13 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 21.26 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-17:40 |
Electricity:Zone:KITCHEN | 198.28 | 1344.54 | 01-JAN-01:20 | 13404.50 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.39 | 25.01 | 01-JAN-01:20 | 895.88 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.39 | 25.01 | 01-JAN-01:20 | 895.88 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 239.49 | 1438.68 | 01-JAN-01:10 | 12932.59 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 66.53 | 255.43 | 01-JAN-01:10 | 3718.02 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 239.49 | 1438.68 | 01-JAN-01:10 | 12932.59 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 220.85 | 847.88 | 01-JAN-01:10 | 12341.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 66.53 | 255.43 | 01-JAN-01:10 | 3718.02 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 220.85 | 847.88 | 01-JAN-01:10 | 12341.79 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 172.95 | 1183.25 | 01-JAN-01:10 | 9214.57 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 154.32 | 592.45 | 01-JAN-01:10 | 8623.77 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 40.36 | 620.88 | 03-FEB-23:30 | 3931.14 | 02-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 32.41 | 535.10 | 03-FEB-23:30 | 1634.34 | 22-SEP-03:30 |
LowTempRefrigeration:Refrigeration:Electricity | 12.76 | 0.00 | 01-JAN-11:10 | 997.25 | 22-SEP-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 19.65 | 514.11 | 04-FEB-06:00 | 637.09 | 01-JAN-01:30 |
ElectricityPurchased:Facility | 575.87 | 2861.55 | 04-FEB-01:20 | 35743.36 | 25-JUL-10:20 |
ElectricityPurchased:Plant | 575.87 | 2861.55 | 04-FEB-01:20 | 35743.36 | 25-JUL-10:20 |
Cogeneration:ElectricityPurchased | 575.87 | 2861.55 | 04-FEB-01:20 | 35743.36 | 25-JUL-10:20 |
General:Cogeneration:ElectricityPurchased | 575.87 | 2861.55 | 04-FEB-01:20 | 35743.36 | 25-JUL-10:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 575.87 | 2861.55 | 04-FEB-01:20 | 35743.36 | 25-JUL-10:20 |
ElectricityNet:Plant | 575.87 | 2861.55 | 04-FEB-01:20 | 35743.36 | 25-JUL-10:20 |
Cogeneration:ElectricityNet | 575.87 | 2861.55 | 04-FEB-01:20 | 35743.36 | 25-JUL-10:20 |
General:Cogeneration:ElectricityNet | 575.87 | 2861.55 | 04-FEB-01:20 | 35743.36 | 25-JUL-10:20 |
Electricity:HVAC | 264.09 | 0.00 | 01-JAN-01:10 | 20656.06 | 27-JUL-17:10 |
Fans:Electricity | 60.79 | 0.00 | 01-JAN-01:10 | 3480.59 | 14-JUL-11:20 |
General:Fans:Electricity | 60.79 | 0.00 | 01-JAN-01:10 | 3480.59 | 14-JUL-11:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 203.30 | 0.00 | 01-JAN-00:10 | 17218.06 | 27-JUL-17:10 |
General:Cooling:Electricity | 203.30 | 0.00 | 01-JAN-00:10 | 17218.06 | 27-JUL-17:10 |
ExteriorLights:Electricity | 10.68 | 0.00 | 01-JAN-07:20 | 952.15 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 10.68 | 0.00 | 01-JAN-07:20 | 952.15 | 01-JAN-06:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 07-JAN-15:40 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 07-JAN-15:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 587.18 | 2351.77 | 01-JAN-01:30 | 41551.68 | 18-JAN-14:00 |
NaturalGas:Building | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
NaturalGas:HVAC | 1.91 | 0.00 | 01-JAN-00:10 | 19503.33 | 04-FEB-07:10 |
Heating:NaturalGas | 1.91 | 0.00 | 01-JAN-00:10 | 19503.33 | 04-FEB-07:10 |
General:Heating:NaturalGas | 1.91 | 0.00 | 01-JAN-00:10 | 19503.33 | 04-FEB-07:10 |
NaturalGas:Plant | 133.88 | 612.41 | 01-JAN-03:10 | 19809.62 | 18-JAN-14:00 |
WaterSystems:NaturalGas | 133.88 | 612.41 | 01-JAN-03:10 | 19809.62 | 18-JAN-14:00 |
Water Heater:WaterSystems:NaturalGas | 133.88 | 612.41 | 01-JAN-03:10 | 19809.62 | 18-JAN-14:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1592.94 | 3090.69 | 04-FEB-01:10 | 116347.36 | 22-AUG-13:00 |
EnergyTransfer:Building | 506.68 | 1545.34 | 04-FEB-01:10 | 33787.14 | 07-JUL-11:10 |
EnergyTransfer:Zone:KITCHEN | 332.97 | 1545.34 | 04-FEB-01:10 | 18842.42 | 15-DEC-05:10 |
Refrigeration:EnergyTransfer | 161.81 | 2990.34 | 03-FEB-23:30 | 7834.84 | 01-JAN-11:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 80.91 | 1495.17 | 03-FEB-23:30 | 3917.42 | 01-JAN-11:40 |
General:Refrigeration:EnergyTransfer | 80.91 | 1495.17 | 03-FEB-23:30 | 3917.42 | 01-JAN-11:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 80.91 | 1495.17 | 03-FEB-23:30 | 3917.42 | 01-JAN-11:40 |
EnergyTransfer:Plant | 181.89 | 1545.34 | 04-FEB-01:10 | 16090.71 | 19-JAN-13:50 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 13.51 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 67.39 | 1342.18 | 04-FEB-06:00 | 2238.70 | 01-JAN-01:30 |
EnergyTransfer:Zone:DINING | 173.71 | 0.00 | 01-JAN-01:10 | 18386.97 | 29-JUL-18:10 |
Heating:EnergyTransfer | 0.47 | 0.00 | 01-JAN-00:10 | 6331.64 | 04-FEB-07:10 |
Heating:EnergyTransfer:Zone:DINING | 0.45 | 0.00 | 01-JAN-00:10 | 6331.64 | 04-FEB-07:10 |
General:Heating:EnergyTransfer | 0.47 | 0.00 | 01-JAN-00:10 | 6331.64 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:DINING | 0.45 | 0.00 | 01-JAN-00:10 | 6331.64 | 04-FEB-07:10 |
Cooling:EnergyTransfer | 425.31 | 0.00 | 01-JAN-01:10 | 29869.72 | 07-JUL-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 173.25 | 0.00 | 01-JAN-01:10 | 18386.97 | 29-JUL-18:10 |
General:Cooling:EnergyTransfer | 425.31 | 0.00 | 01-JAN-01:10 | 29869.72 | 07-JUL-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 173.25 | 0.00 | 01-JAN-01:10 | 18386.97 | 29-JUL-18:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 560.12 | 10-SEP-23:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 560.12 | 10-SEP-23:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 252.06 | 0.00 | 01-JAN-01:10 | 15034.24 | 15-DEC-05:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 252.06 | 0.00 | 01-JAN-01:10 | 15034.24 | 15-DEC-05:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 100.98 | 0.00 | 01-JAN-00:10 | 13542.14 | 15-JAN-13:40 |
PlantLoopHeatingDemand:Plant | 100.98 | 0.00 | 01-JAN-00:10 | 13542.14 | 15-JAN-13:40 |
WaterSystems:PlantLoopHeatingDemand | 100.98 | 0.00 | 01-JAN-00:10 | 13542.14 | 15-JAN-13:40 |
General:WaterSystems:PlantLoopHeatingDemand | 100.98 | 0.00 | 01-JAN-00:10 | 13542.14 | 15-JAN-13:40 |
EnergyTransfer:HVAC | 904.37 | 0.00 | 01-JAN-00:10 | 75124.04 | 14-JUL-11:20 |
HeatingCoils:EnergyTransfer | 1.53 | 0.00 | 01-JAN-00:10 | 15602.67 | 04-FEB-07:10 |
CoolingCoils:EnergyTransfer | 902.84 | 0.00 | 01-JAN-00:10 | 75124.04 | 14-JUL-11:20 |
WaterSystems:EnergyTransfer | 100.98 | 0.00 | 01-JAN-00:10 | 13542.14 | 15-JAN-13:40 |
WaterUse:WaterSystems:EnergyTransfer | 100.98 | 0.00 | 01-JAN-00:10 | 13542.14 | 15-JAN-13:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 0.455 | -173.254 | 0.000 | 0.000 | 65.432 | 3.868 | 49.900 | 20.825 | 0.000 | 32.139 | 17.502 | 0.000 | -3.887 | 0.000 | -12.980 | 0.000 |
KITCHEN | 0.000 | 0.000 | 0.010 | -252.053 | 0.000 | 0.000 | 3.888 | 17.389 | 178.354 | 0.000 | 0.000 | 0.033 | 52.573 | 0.000 | 0.000 | 0.000 | -0.196 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.807 | 12.455 | 0.000 | 0.000 | 0.000 | -16.262 | -0.001 |
Total Facility | 0.000 | 0.000 | 0.465 | -425.307 | 0.000 | 0.000 | 69.321 | 21.257 | 228.254 | 20.825 | 0.000 | 35.980 | 82.529 | 0.000 | -3.887 | 0.000 | -29.438 | -0.001 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 18-OCT-02:61 | 0.00 | 0.00 | 0.00 | -28276.25 | 0.00 | 0.00 | 0.00 | 25.01 | 191.57 | 0.00 | 0.00 | 0.00 | 28269.04 | 0.00 | -205.41 | 0.00 | -3.97 | 0.00 |
KITCHEN | 15-DEC-03:01 | 0.00 | 0.00 | 0.00 | -42995.35 | 0.00 | 0.00 | 0.00 | 25.01 | 1205.28 | 0.00 | 0.00 | 0.00 | 41915.16 | 0.00 | -0.00 | 0.00 | -150.10 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-APR-02:61 | 0.00 | 0.00 | 0.00 | -52318.31 | 0.00 | 0.00 | 0.00 | 50.02 | 1396.85 | 0.00 | 0.00 | 170.00 | 51187.37 | 0.00 | -431.07 | 0.00 | -54.86 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 04-FEB-07:10 | 0.00 | 0.00 | 6333.35 | 0.00 | 0.00 | 0.00 | 3598.57 | 121.21 | 1442.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -684.82 | 0.00 | -10336.13 | -474.51 |
KITCHEN | 10-SEP-23:01 | 0.00 | 0.00 | 2835.46 | 0.00 | 0.00 | 0.00 | 18.55 | 149.31 | 1514.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4517.39 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-FEB-07:10 | -9851.03 | 9851.03 | 6333.35 | -9851.03 | 0.00 | 0.00 | 3883.16 | 419.84 | 6649.44 | 0.00 | 0.00 | 356.62 | 3255.38 | 0.00 | -684.82 | 0.00 | -10361.93 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9808 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.9808 | 0.2100 | 1.0000 | Not calculated | 0.4161 | 0.2100 | ||
PSZ-AC_2:2 | 1.1413 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.1413 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1325 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9808 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.9808 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2100 | ||
PSZ-AC_2:2 | 1.1413 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.1413 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1325 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9808 | 1.9808 | 1.9808 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1413 | 1.1413 | 1.1413 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9808 | 1.9808 | 1.9808 | 1.9808 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.1413 | 1.1413 | 1.1413 | 1.1413 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9808 | 1.9808 | 1.9808 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1413 | 1.1413 | 1.1413 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9808 | 1.9808 | 1.9808 | 1.9808 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.1413 | 1.1413 | 1.1413 | 1.1413 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 892.33 |
Number of hours not met | 892.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1.91 | 19503.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 203.30 | 17218.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 21.26 | 1285.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 10.68 | 952.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 220.85 | 12341.79 | 451.39 | 25220.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 60.79 | 3480.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 133.88 | 19809.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 12.76 | 997.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 19.65 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 279.84 | 575.87 |
Natural Gas | 451.39 | 587.18 |
Additional | 0.00 | 0.00 |
Total | 731.23 | 1163.05 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 91.49 |
Space Heating | 0.00 |
Space Cooling | 874.99 |
Fans (All) | 261.65 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1030.74 |
Miscellaneous (All) | 2478.52 |
Subtotal | 2478.52 |
Natural Gas [MJ/m2] | |
Space Heating | 8.23 |
Service Water Heating | 576.20 |
Miscellaneous (All) | 2527.21 |
Subtotal | 2527.21 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.83 |
Space Heating | 0.16 |
Space Cooling | 17.48 |
Fans (All) | 5.23 |
Service Water Heating | 11.51 |
Receptacle Equipment | 59.40 |
Miscellaneous | 4.39 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4528. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8206.33 | 553.17 | 0.50 | 0.00 | 0.00 |
KITCHEN | 6236.50 | 2175.83 | 347.67 | 0.00 | 0.00 |
ATTIC | 4753.67 | 768.50 | 872.00 | 1263.00 | 1102.83 |
Min | 4753.67 | 553.17 | 0.50 | 0.00 | 0.00 |
Max | 8206.33 | 2175.83 | 872.00 | 1263.00 | 1102.83 |
Average | 6398.83 | 1165.83 | 406.72 | 421.00 | 367.61 |
Sum | 19196.50 | 3497.50 | 1220.17 | 1263.00 | 1102.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254227.00 | 496.00 | 2.00 | 0.00 | 0.00 |
KITCHEN | 12681.50 | 3573.83 | 2.67 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254227.00 | 3573.83 | 2.67 | 0.00 | 0.00 |
Average | 88969.50 | 1356.61 | 1.56 | 0.00 | 0.00 |
Sum | 266908.50 | 4069.83 | 4.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 2677.67 | 6082.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 856.50 | 7836.83 | 66.67 | 0.00 | 0.00 |
ATTIC | 2641.33 | 3207.83 | 707.00 | 650.17 | 1553.67 |
Min | 856.50 | 3207.83 | 0.00 | 0.00 | 0.00 |
Max | 2677.67 | 7836.83 | 707.00 | 650.17 | 1553.67 |
Average | 2058.50 | 5709.00 | 257.89 | 216.72 | 517.89 |
Sum | 6175.50 | 17127.00 | 773.67 | 650.17 | 1553.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 80261.50 | 174463.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 1339.67 | 14918.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 80261.50 | 174463.50 | 0.00 | 0.00 | 0.00 |
Average | 27200.39 | 63127.28 | 0.00 | 0.00 | 0.00 |
Sum | 81601.17 | 189381.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:21
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.896135E+10 | 24593.15 | 06-JAN-03:01 | 21.78 | 19.23 | 0.516337E+10 | 4640.76 | 07-JAN-19:10 | 21.10 | 20.05 |
February | 0.950869E+10 | 24953.32 | 15-FEB-03:01 | 20.60 | 19.39 | 0.473549E+10 | 4640.76 | 11-FEB-19:10 | 20.60 | 19.39 |
March | 0.108661E+11 | 22703.79 | 12-MAR-02:61 | 21.10 | 15.64 | 0.530378E+10 | 4640.79 | 11-MAR-19:49 | 21.10 | 15.64 |
April | 0.131711E+11 | 25621.89 | 18-APR-02:61 | 20.50 | 16.24 | 0.517392E+10 | 4641.07 | 01-APR-18:00 | 20.50 | 16.24 |
May | 0.164801E+11 | 23033.97 | 03-MAY-02:61 | 24.90 | 21.03 | 0.536225E+10 | 4640.95 | 20-MAY-18:10 | 28.03 | 21.49 |
June | 0.174719E+11 | 23124.34 | 17-JUN-02:61 | 27.12 | 22.17 | 0.521517E+10 | 4641.25 | 24-JUN-18:10 | 26.20 | 23.51 |
July | 0.192570E+11 | 24369.02 | 02-JUL-02:61 | 25.00 | 21.47 | 0.533212E+10 | 4641.18 | 22-JUL-18:10 | 26.02 | 21.82 |
August | 0.189469E+11 | 20094.14 | 08-AUG-02:61 | 26.60 | 23.46 | 0.539327E+10 | 4640.98 | 19-AUG-18:30 | 29.40 | 24.39 |
September | 0.181817E+11 | 21222.48 | 17-SEP-02:61 | 24.40 | 22.49 | 0.518325E+10 | 4641.11 | 30-SEP-18:00 | 28.90 | 23.70 |
October | 0.172198E+11 | 28300.05 | 18-OCT-02:61 | 23.98 | 19.33 | 0.533347E+10 | 4641.11 | 14-OCT-18:10 | 23.98 | 19.33 |
November | 0.134205E+11 | 23785.89 | 20-NOV-03:01 | 24.40 | 20.57 | 0.512853E+10 | 4641.58 | 18-NOV-19:49 | 24.40 | 20.57 |
December | 0.976907E+10 | 24673.91 | 01-DEC-03:01 | 22.20 | 17.94 | 0.520301E+10 | 4641.63 | 09-DEC-19:40 | 25.00 | 22.52 |
Annual Sum or Average | 0.173254E+12 | 0.625276E+11 | ||||||||
Minimum of Months | 0.896135E+10 | 20094.14 | 20.50 | 15.64 | 0.473549E+10 | 4640.76 | 20.50 | 15.64 | ||
Maximum of Months | 0.192570E+11 | 28300.05 | 27.12 | 23.46 | 0.539327E+10 | 4641.63 | 29.40 | 24.39 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204696E+11 | 40951.50 | 27-JAN-03:01 | 14.40 | 7.78 | 0.744296E+10 | 4868.95 | 18-JAN-11:39 | 14.40 | 7.78 |
February | 0.185145E+11 | 42266.69 | 24-FEB-03:01 | 11.88 | 7.35 | 0.672552E+10 | 4868.94 | 06-FEB-11:39 | 11.88 | 7.35 |
March | 0.205678E+11 | 39184.55 | 15-MAR-02:11 | 12.60 | 9.15 | 0.745179E+10 | 4879.74 | 14-MAR-10:50 | 12.60 | 9.15 |
April | 0.203351E+11 | 34396.13 | 19-APR-02:61 | 15.00 | 11.82 | 0.721370E+10 | 4879.28 | 13-APR-10:00 | 15.00 | 11.82 |
May | 0.216603E+11 | 24219.76 | 08-MAY-02:11 | 23.70 | 18.75 | 0.745737E+10 | 4889.36 | 31-MAY-10:00 | 32.80 | 24.33 |
June | 0.212224E+11 | 19594.17 | 17-JUN-02:61 | 27.12 | 22.17 | 0.722875E+10 | 4905.68 | 06-JUN-10:50 | 27.12 | 22.17 |
July | 0.221578E+11 | 20521.25 | 02-JUL-02:61 | 25.00 | 21.47 | 0.747168E+10 | 4917.48 | 14-JUL-10:50 | 31.52 | 26.32 |
August | 0.221554E+11 | 18614.94 | 29-AUG-02:11 | 23.70 | 22.63 | 0.747560E+10 | 4912.86 | 04-AUG-10:50 | 23.70 | 22.63 |
September | 0.215833E+11 | 20030.14 | 05-SEP-02:11 | 23.30 | 21.69 | 0.722623E+10 | 4907.64 | 06-SEP-10:00 | 30.60 | 26.05 |
October | 0.219630E+11 | 23633.75 | 18-OCT-02:11 | 24.07 | 19.26 | 0.745839E+10 | 4912.76 | 04-OCT-10:50 | 24.07 | 19.26 |
November | 0.206614E+11 | 39755.54 | 13-NOV-03:01 | 13.22 | 8.58 | 0.721201E+10 | 4896.58 | 30-NOV-11:50 | 27.12 | 25.09 |
December | 0.207667E+11 | 43026.79 | 15-DEC-03:01 | 8.80 | 5.79 | 0.744444E+10 | 4870.38 | 07-DEC-11:50 | 8.80 | 5.79 |
Annual Sum or Average | 0.252057E+12 | 0.878085E+11 | ||||||||
Minimum of Months | 0.185145E+11 | 18614.94 | 8.80 | 5.79 | 0.672552E+10 | 4868.94 | 8.80 | 5.79 | ||
Maximum of Months | 0.221578E+11 | 43026.79 | 27.12 | 22.63 | 0.747560E+10 | 4917.48 | 32.80 | 26.32 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 | 19.26 | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 | 19.26 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 | 13.10 | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 | 13.10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 | 13.44 | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 | 13.44 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 | 18.63 | 0.00 | 0.00 | 01-APR-00:10 | 22.57 | 18.63 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 22.05 | 20.01 | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 20.01 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 | 24.42 | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 | 24.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 | 23.72 | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 | 23.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 | 25.82 | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 | 25.82 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 | 24.00 | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 | 24.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 27.93 | 23.96 | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 | 23.96 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 22.40 | 21.03 | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 | 21.03 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 24.10 | 21.22 | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 | 21.22 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 16.65 | 13.10 | 0.00 | 0.00 | 16.65 | 13.10 | ||
Maximum of Months | 0.00 | 0.00 | 28.60 | 25.82 | 0.00 | 0.00 | 28.60 | 25.82 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11161195.08 | 4165.23 | 25-JAN-08:44 | 10.92 |
February | 49597472.31 | 6331.64 | 04-FEB-07:10 | 5.28 |
March | 35223277.36 | 4203.12 | 20-MAR-07:44 | 10.92 |
April | 2523221.03 | 1223.34 | 12-APR-23:01 | 25.60 |
May | 25135943.38 | 1888.40 | 31-MAY-23:01 | 26.87 |
June | 80595401.52 | 2991.33 | 10-JUN-23:01 | 29.32 |
July | 61787935.09 | 2702.48 | 31-JUL-23:01 | 28.68 |
August | 73809550.14 | 2783.98 | 02-AUG-23:01 | 28.90 |
September | 56100415.36 | 3010.81 | 10-SEP-23:01 | 29.40 |
October | 23920497.70 | 1985.91 | 29-OCT-23:01 | 27.12 |
November | 10387732.95 | 1782.03 | 03-NOV-23:01 | 26.70 |
December | 24593851.93 | 4191.63 | 20-DEC-22:55 | 10.00 |
Annual Sum or Average | 0.454836E+09 | |||
Minimum of Months | 2523221.03 | 1223.34 | 5.28 | |
Maximum of Months | 80595401.52 | 6331.64 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 105220.41 | 627.84 | 31-MAY-23:01 | 26.87 |
June | 3207379.74 | 2782.00 | 10-JUN-23:01 | 29.32 |
July | 1884744.34 | 2117.53 | 31-JUL-23:01 | 28.68 |
August | 2568730.68 | 2372.58 | 02-AUG-23:01 | 28.90 |
September | 2445725.49 | 2833.90 | 10-SEP-23:01 | 29.40 |
October | 176090.10 | 809.79 | 29-OCT-23:01 | 27.12 |
November | 28753.26 | 479.22 | 03-NOV-23:01 | 26.70 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 24.10 |
Annual Sum or Average | 10416644.01 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 3207379.74 | 2833.90 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.366970E+09 | 389.13 | 02-JAN-17:40 | 0.565077E+10 | 3718.02 | 01-JAN-11:09 |
February | 0.316387E+09 | 389.13 | 01-FEB-18:10 | 0.510393E+10 | 3718.02 | 01-FEB-11:09 |
March | 0.324827E+09 | 389.13 | 01-MAR-18:19 | 0.565082E+10 | 3718.02 | 01-MAR-11:09 |
April | 0.300713E+09 | 389.13 | 01-APR-18:40 | 0.546849E+10 | 3718.02 | 01-APR-10:09 |
May | 0.300114E+09 | 389.13 | 01-MAY-18:49 | 0.565080E+10 | 3718.02 | 01-MAY-10:09 |
June | 0.289060E+09 | 389.13 | 01-JUN-18:30 | 0.546853E+10 | 3718.02 | 01-JUN-10:09 |
July | 0.287282E+09 | 389.13 | 01-JUL-19:19 | 0.565075E+10 | 3718.02 | 01-JUL-10:09 |
August | 0.308250E+09 | 389.13 | 01-AUG-18:00 | 0.565082E+10 | 3718.02 | 01-AUG-10:09 |
September | 0.310404E+09 | 389.13 | 01-SEP-18:40 | 0.546849E+10 | 3718.02 | 01-SEP-10:09 |
October | 0.338495E+09 | 389.13 | 02-OCT-17:00 | 0.565077E+10 | 3718.02 | 01-OCT-10:09 |
November | 0.349874E+09 | 389.13 | 01-NOV-17:40 | 0.546851E+10 | 3718.02 | 01-NOV-10:09 |
December | 0.375595E+09 | 389.13 | 01-DEC-17:30 | 0.565075E+10 | 3718.02 | 01-DEC-11:09 |
Annual Sum or Average | 0.386797E+10 | 0.665334E+11 | ||||
Minimum of Months | 0.287282E+09 | 389.13 | 0.510393E+10 | 3718.02 | ||
Maximum of Months | 0.375595E+09 | 389.13 | 0.565082E+10 | 3718.02 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146885E+10 | 895.88 | 02-JAN-10:09 | 0.146891E+11 | 9214.57 | 01-JAN-11:09 |
February | 0.133058E+10 | 895.88 | 01-FEB-10:09 | 0.132676E+11 | 9214.57 | 01-FEB-11:09 |
March | 0.149423E+10 | 895.88 | 01-MAR-10:09 | 0.146892E+11 | 9214.57 | 01-MAR-11:09 |
April | 0.142731E+10 | 895.88 | 01-APR-16:10 | 0.142152E+11 | 9214.57 | 01-APR-10:09 |
May | 0.148154E+10 | 895.88 | 01-MAY-09:09 | 0.146891E+11 | 9214.57 | 01-MAY-10:09 |
June | 0.144409E+10 | 895.88 | 01-JUN-09:09 | 0.142153E+11 | 9214.57 | 01-JUN-10:09 |
July | 0.146494E+10 | 895.88 | 01-JUL-16:10 | 0.146890E+11 | 9214.57 | 01-JUL-10:09 |
August | 0.149423E+10 | 895.88 | 01-AUG-09:09 | 0.146892E+11 | 9214.57 | 01-AUG-10:09 |
September | 0.142766E+10 | 895.88 | 01-SEP-09:09 | 0.142152E+11 | 9214.57 | 01-SEP-10:09 |
October | 0.146867E+10 | 895.88 | 02-OCT-09:09 | 0.146891E+11 | 9214.57 | 01-OCT-10:09 |
November | 0.142226E+10 | 895.88 | 01-NOV-09:09 | 0.142153E+11 | 9214.57 | 01-NOV-10:09 |
December | 0.146511E+10 | 895.88 | 01-DEC-10:09 | 0.146890E+11 | 9214.57 | 01-DEC-11:09 |
Annual Sum or Average | 0.173895E+11 | 0.172953E+12 | ||||
Minimum of Months | 0.133058E+10 | 895.88 | 0.132676E+11 | 9214.57 | ||
Maximum of Months | 0.149423E+10 | 895.88 | 0.146892E+11 | 9214.57 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.366970E+09 | 0.565077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331722E+09 | 0.373319E+10 |
February | 0.852256E+10 | 0.316387E+09 | 0.510393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527834E+09 | 0.218053E+10 |
March | 0.954557E+10 | 0.324827E+09 | 0.565082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631042E+09 | 0.208210E+10 |
April | 0.915225E+10 | 0.300713E+09 | 0.546849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166126E+10 | 0.556210E+09 |
May | 0.947560E+10 | 0.300114E+09 | 0.565080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362922E+10 | 53059848.95 |
June | 0.922788E+10 | 0.289060E+09 | 0.546853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458109E+10 | 3315594.84 |
July | 0.939996E+10 | 0.287282E+09 | 0.565075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550297E+10 | 25914727.97 |
August | 0.954557E+10 | 0.308250E+09 | 0.565082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507805E+10 | 32971579.94 |
September | 0.915225E+10 | 0.310404E+09 | 0.546849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454892E+10 | 11156364.45 |
October | 0.940563E+10 | 0.338495E+09 | 0.565077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343854E+10 | 55082464.42 |
November | 0.909363E+10 | 0.349874E+09 | 0.546851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172587E+10 | 0.100817E+10 |
December | 0.939996E+10 | 0.375595E+09 | 0.565075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482725E+09 | 0.323849E+10 |
Annual Sum or Average | 0.111326E+12 | 0.386797E+10 | 0.665334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321392E+11 | 0.129802E+11 |
Minimum of Months | 0.852256E+10 | 0.287282E+09 | 0.510393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331722E+09 | 3315594.84 |
Maximum of Months | 0.954557E+10 | 0.375595E+09 | 0.565082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550297E+10 | 0.373319E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.146885E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 118726.17 | 26379429.52 |
February | 0.610713E+09 | 0.133058E+10 | 0.971608E+10 | 0.103882E+11 | 0.00 | 0.00 | 0.00 | 268661.94 | 35586906.06 |
March | 0.684021E+09 | 0.149423E+10 | 0.107572E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 387622.93 | 36326410.51 |
April | 0.655836E+09 | 0.142731E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 1410989.47 | 17789351.28 |
May | 0.679007E+09 | 0.148154E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 4960512.93 | 10654505.19 |
June | 0.661256E+09 | 0.144409E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 5429439.50 | 4076090.14 |
July | 0.673587E+09 | 0.146494E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 5172462.09 | 3488390.24 |
August | 0.684021E+09 | 0.149423E+10 | 0.107572E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 5854048.64 | 3199159.46 |
September | 0.655836E+09 | 0.142766E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 5388280.77 | 4103058.20 |
October | 0.673993E+09 | 0.146867E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 3282795.97 | 6722021.54 |
November | 0.651635E+09 | 0.142226E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 932847.17 | 20261252.88 |
December | 0.673587E+09 | 0.146511E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 209456.58 | 27591967.45 |
Annual Sum or Average | 0.797748E+10 | 0.173895E+11 | 0.126656E+12 | 0.135417E+12 | 0.00 | 0.00 | 0.00 | 33415844.17 | 0.196179E+09 |
Minimum of Months | 0.610713E+09 | 0.133058E+10 | 0.971608E+10 | 0.103882E+11 | 0.00 | 0.00 | 0.00 | 118726.17 | 3199159.46 |
Maximum of Months | 0.684021E+09 | 0.149423E+10 | 0.107572E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 5854048.64 | 36326410.51 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404946E+09 | 0.101844E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297548E+09 | 0.106755E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299915E+09 | 0.147655E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294678E+09 | 0.166354E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267755E+09 | 0.167343E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269319E+09 | 0.158815E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308308E+09 | 0.179800E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327043E+09 | 0.145283E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291465E+09 | 0.139974E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387391E+09 | 0.117652E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339786E+09 | 0.977760E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319339E+09 | 0.969493E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380749E+10 | 0.162620E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267755E+09 | 0.969493E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404946E+09 | 0.179800E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 389.13 | 02-JAN-17:40 | 3718.02 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3972.23 | 02-JAN-14:00 | 8394.93 | 24-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 389.13 | 01-FEB-18:10 | 3718.02 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3500.65 | 02-FEB-14:00 | 10336.13 | 04-FEB-07:10 |
March | 9454.80 | 04-MAR-19:10 | 389.13 | 01-MAR-18:19 | 3718.02 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4334.71 | 13-MAR-17:03 | 7713.01 | 16-MAR-06:10 |
April | 9454.80 | 01-APR-18:10 | 389.13 | 01-APR-18:40 | 3718.02 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6232.84 | 17-APR-17:10 | 4168.41 | 02-APR-06:10 |
May | 9454.80 | 06-MAY-18:10 | 389.13 | 01-MAY-18:49 | 3718.02 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8200.90 | 22-MAY-12:00 | 1788.25 | 07-MAY-06:10 |
June | 9454.80 | 03-JUN-18:10 | 389.13 | 01-JUN-18:30 | 3718.02 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6352.92 | 09-JUN-12:00 | 358.23 | 13-JUN-16:59 |
July | 9454.80 | 01-JUL-18:10 | 389.13 | 01-JUL-19:19 | 3718.02 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8863.45 | 29-JUL-18:02 | 988.57 | 14-JUL-19:30 |
August | 9454.80 | 05-AUG-18:10 | 389.13 | 01-AUG-18:00 | 3718.02 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.16 | 23-AUG-12:00 | 1537.04 | 28-AUG-12:00 |
September | 9454.80 | 02-SEP-18:10 | 389.13 | 01-SEP-18:40 | 3718.02 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6850.19 | 13-SEP-12:00 | 758.32 | 05-SEP-06:10 |
October | 9454.80 | 07-OCT-18:10 | 389.13 | 02-OCT-17:00 | 3718.02 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6832.23 | 03-OCT-12:00 | 1335.18 | 28-OCT-06:10 |
November | 9454.80 | 04-NOV-18:10 | 389.13 | 01-NOV-17:40 | 3718.02 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4440.39 | 17-NOV-13:00 | 5695.07 | 12-NOV-20:55 |
December | 9454.80 | 02-DEC-19:10 | 389.13 | 01-DEC-17:30 | 3718.02 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3107.75 | 08-DEC-14:00 | 9446.82 | 20-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 389.13 | 3718.02 | 0.00 | 0.00 | 0.00 | 0.00 | 3107.75 | 358.23 | |||||
Maximum of Months | 9454.80 | 389.13 | 3718.02 | 0.00 | 0.00 | 0.00 | 0.00 | 8863.45 | 10336.13 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 895.88 | 02-JAN-10:09 | 6627.44 | 01-JAN-11:09 | 7566.24 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 5.00 | 07-JAN-13:00 | 134.66 | 24-JAN-02:30 |
February | 677.52 | 04-FEB-19:10 | 895.88 | 01-FEB-10:09 | 6627.44 | 01-FEB-11:09 | 7566.24 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 6.03 | 02-FEB-14:00 | 189.76 | 04-FEB-05:00 |
March | 677.52 | 04-MAR-19:10 | 895.88 | 01-MAR-10:09 | 6627.44 | 01-MAR-11:09 | 7566.24 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 7.63 | 13-MAR-16:53 | 190.31 | 16-MAR-02:00 |
April | 677.52 | 01-APR-18:10 | 895.88 | 01-APR-16:10 | 6627.44 | 01-APR-10:09 | 7566.24 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 10.91 | 15-APR-16:53 | 83.77 | 23-APR-02:10 |
May | 677.52 | 06-MAY-18:10 | 895.88 | 01-MAY-09:09 | 6627.44 | 01-MAY-10:09 | 7566.24 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 17.74 | 22-MAY-14:41 | 66.67 | 08-MAY-00:50 |
June | 677.52 | 03-JUN-18:10 | 895.88 | 01-JUN-09:09 | 6627.44 | 01-JUN-10:09 | 7566.24 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 13.55 | 08-JUN-02:10 | 61.25 | 18-JUN-02:00 |
July | 677.52 | 01-JUL-18:10 | 895.88 | 01-JUL-16:10 | 6627.44 | 01-JUL-10:09 | 7566.24 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 12.19 | 27-JUL-15:53 | 39.40 | 04-JUL-03:20 |
August | 677.52 | 05-AUG-18:10 | 895.88 | 01-AUG-09:09 | 6627.44 | 01-AUG-10:09 | 7566.24 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 11.10 | 18-AUG-02:10 | 64.87 | 14-AUG-03:20 |
September | 677.52 | 02-SEP-18:10 | 895.88 | 01-SEP-09:09 | 6627.44 | 01-SEP-10:09 | 7566.24 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 10.70 | 19-SEP-15:00 | 42.19 | 20-SEP-00:07 |
October | 677.52 | 07-OCT-18:10 | 895.88 | 02-OCT-09:09 | 6627.44 | 01-OCT-10:09 | 7566.24 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 10.10 | 03-OCT-12:10 | 63.62 | 17-OCT-02:00 |
November | 677.52 | 04-NOV-18:10 | 895.88 | 01-NOV-09:09 | 6627.44 | 01-NOV-10:09 | 7566.24 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 4.69 | 17-NOV-14:53 | 136.59 | 12-NOV-04:20 |
December | 677.52 | 02-DEC-19:10 | 895.88 | 01-DEC-10:09 | 6627.44 | 01-DEC-11:09 | 7566.24 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 6.73 | 10-DEC-15:00 | 179.66 | 15-DEC-04:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 895.88 | 6627.44 | 7566.24 | 0.00 | 0.00 | 0.00 | 4.69 | 39.40 | ||||||
Maximum of Months | 677.52 | 895.88 | 6627.44 | 7566.24 | 0.00 | 0.00 | 0.00 | 17.74 | 190.31 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.39 | 27-JAN-03:40 | 2226.87 | 31-JAN-13:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 625.20 | 28-FEB-07:15 | 2153.25 | 25-FEB-13:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.41 | 02-MAR-04:10 | 2542.42 | 16-MAR-13:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.48 | 05-APR-05:10 | 2534.28 | 10-APR-12:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.27 | 06-MAY-05:20 | 2552.75 | 06-MAY-12:40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.76 | 10-JUN-03:00 | 2564.09 | 09-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.65 | 07-JUL-06:05 | 2554.24 | 07-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.82 | 31-AUG-03:51 | 2363.76 | 07-AUG-13:02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.43 | 12-SEP-02:20 | 2385.51 | 17-SEP-12:40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.72 | 22-OCT-04:00 | 2357.55 | 06-OCT-12:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.95 | 07-NOV-06:40 | 1905.80 | 10-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.20 | 13-DEC-06:00 | 1892.31 | 04-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.27 | 1892.31 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.39 | 2564.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24593.15 | 06-JAN-03:01 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 |
February | 24953.32 | 15-FEB-03:01 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.15 |
March | 22703.79 | 12-MAR-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 |
April | 25621.89 | 18-APR-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 |
May | 23033.97 | 03-MAY-02:61 | 0.00 | 200.07 | 2043.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 0.00 |
June | 23124.34 | 17-JUN-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 12.16 | 0.00 |
July | 24369.02 | 02-JUL-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20094.14 | 08-AUG-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21222.48 | 17-SEP-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 |
October | 28300.05 | 18-OCT-02:61 | 0.00 | 225.08 | 2298.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 |
November | 23785.89 | 20-NOV-03:01 | 0.00 | 200.07 | 2043.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
December | 24673.91 | 01-DEC-03:01 | 0.00 | 200.07 | 2043.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20094.14 | 0.00 | 200.07 | 2043.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28300.05 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 12.16 | 28.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 40951.50 | 27-JAN-03:01 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 42266.69 | 24-FEB-03:01 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 |
March | 39184.55 | 15-MAR-02:11 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 145.80 |
April | 34396.13 | 19-APR-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.11 |
May | 24219.76 | 08-MAY-02:11 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.06 |
June | 19594.17 | 17-JUN-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.96 |
July | 20521.25 | 02-JUL-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18614.94 | 29-AUG-02:11 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.78 |
September | 20030.14 | 05-SEP-02:11 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.34 |
October | 23633.75 | 18-OCT-02:11 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 |
November | 39755.54 | 13-NOV-03:01 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.14 |
December | 43026.79 | 15-DEC-03:01 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 150.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 18614.94 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43026.79 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 150.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.56 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.79 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.08 | 0.00 |
April | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.25 | 0.00 |
May | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.26 | 0.00 |
June | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.40 | 0.00 |
July | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.30 | 0.00 |
August | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.91 | 0.00 |
September | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.14 | 0.00 |
October | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.53 | 0.00 |
November | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.66 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.79 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.381405E+11 | 30311.48 | 07-JAN-11:20 | 0.510098E+11 | 41551.68 | 18-JAN-13:00 |
February | 0.362919E+11 | 31472.31 | 11-FEB-11:20 | 0.461394E+11 | 41510.27 | 02-FEB-13:20 |
March | 0.415364E+11 | 31707.85 | 14-MAR-10:20 | 0.506305E+11 | 41268.98 | 16-MAR-10:20 |
April | 0.436820E+11 | 31691.20 | 13-APR-10:20 | 0.481559E+11 | 40654.98 | 07-APR-12:20 |
May | 0.515148E+11 | 34095.87 | 31-MAY-10:20 | 0.493125E+11 | 39982.31 | 08-MAY-12:39 |
June | 0.546938E+11 | 34305.91 | 06-JUN-10:20 | 0.473827E+11 | 39421.95 | 04-JUN-12:39 |
July | 0.578933E+11 | 35743.36 | 25-JUL-10:20 | 0.487871E+11 | 39065.86 | 01-JUL-12:20 |
August | 0.580481E+11 | 35548.20 | 23-AUG-10:20 | 0.489108E+11 | 39283.02 | 25-AUG-12:30 |
September | 0.550111E+11 | 34516.65 | 21-SEP-10:20 | 0.476198E+11 | 39969.61 | 30-SEP-12:00 |
October | 0.530184E+11 | 34310.36 | 03-OCT-11:20 | 0.496568E+11 | 40599.20 | 28-OCT-12:39 |
November | 0.455828E+11 | 32861.87 | 10-NOV-11:20 | 0.485850E+11 | 41154.47 | 28-NOV-13:20 |
December | 0.404546E+11 | 31012.16 | 24-DEC-11:20 | 0.509895E+11 | 41497.32 | 31-DEC-13:00 |
Annual Sum or Average | 0.575868E+12 | 0.587180E+12 | ||||
Minimum of Months | 0.362919E+11 | 30311.48 | 0.461394E+11 | 39065.86 | ||
Maximum of Months | 0.580481E+11 | 35743.36 | 0.510098E+11 | 41551.68 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.183582E+10 | 0.106386E+10 | 0.203399E+11 | 0.00 | 0.442088E+10 | 0.79 | 0.00 | 0.710321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164696E+10 | 0.903280E+09 | 0.183715E+11 | 0.00 | 0.402514E+10 | 0.72 | 0.00 | 0.828847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181906E+10 | 0.922181E+09 | 0.203400E+11 | 0.00 | 0.453275E+10 | 0.80 | 0.00 | 0.105259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172802E+10 | 0.816286E+09 | 0.196837E+11 | 0.00 | 0.452872E+10 | 0.77 | 0.00 | 0.136183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178165E+10 | 0.774788E+09 | 0.203399E+11 | 0.00 | 0.521308E+10 | 0.80 | 0.00 | 0.199669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173315E+10 | 0.718595E+09 | 0.196839E+11 | 0.00 | 0.564877E+10 | 0.77 | 0.00 | 0.235578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175222E+10 | 0.752508E+09 | 0.203398E+11 | 0.00 | 0.600960E+10 | 0.79 | 0.00 | 0.255738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180248E+10 | 0.813065E+09 | 0.203400E+11 | 0.00 | 0.602352E+10 | 0.80 | 0.00 | 0.255964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173807E+10 | 0.860275E+09 | 0.196837E+11 | 0.00 | 0.567172E+10 | 0.77 | 0.00 | 0.237078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180716E+10 | 0.967884E+09 | 0.203399E+11 | 0.00 | 0.538517E+10 | 0.79 | 0.00 | 0.210747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177213E+10 | 0.100710E+10 | 0.196838E+11 | 0.00 | 0.477547E+10 | 0.77 | 0.00 | 0.150366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184071E+10 | 0.107871E+10 | 0.203398E+11 | 0.00 | 0.455677E+10 | 0.79 | 0.00 | 0.924883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212574E+11 | 0.106785E+11 | 0.239486E+12 | 0.00 | 0.607916E+11 | 9.37 | 0.00 | 0.203299E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.164696E+10 | 0.718595E+09 | 0.183715E+11 | 0.00 | 0.402514E+10 | 0.72 | 0.00 | 0.710321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184071E+10 | 0.107871E+10 | 0.203400E+11 | 0.00 | 0.602352E+10 | 0.80 | 0.00 | 0.255964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.383373E+11 | 0.00 | 0.396691E+09 | 0.00 | 0.122758E+11 | 0.00 | 0.00 |
February | 0.346273E+11 | 0.00 | 0.510174E+09 | 0.00 | 0.110019E+11 | 0.00 | 0.00 |
March | 0.383373E+11 | 0.00 | 0.402029E+09 | 0.00 | 0.118911E+11 | 0.00 | 0.00 |
April | 0.371007E+11 | 0.00 | 0.00 | 0.00 | 0.110552E+11 | 0.00 | 0.00 |
May | 0.383373E+11 | 0.00 | 0.00 | 0.00 | 0.109751E+11 | 0.00 | 0.00 |
June | 0.371007E+11 | 0.00 | 0.00 | 0.00 | 0.102820E+11 | 0.00 | 0.00 |
July | 0.383373E+11 | 0.00 | 0.00 | 0.00 | 0.104497E+11 | 0.00 | 0.00 |
August | 0.383373E+11 | 0.00 | 0.00 | 0.00 | 0.105734E+11 | 0.00 | 0.00 |
September | 0.371007E+11 | 0.00 | 0.00 | 0.00 | 0.105191E+11 | 0.00 | 0.00 |
October | 0.383373E+11 | 0.00 | 0.00 | 0.00 | 0.113195E+11 | 0.00 | 0.00 |
November | 0.371007E+11 | 0.00 | 74792224.95 | 0.00 | 0.114096E+11 | 0.00 | 0.00 |
December | 0.383373E+11 | 0.00 | 0.527693E+09 | 0.00 | 0.121245E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.451391E+12 | 0.00 | 0.191138E+10 | 0.00 | 0.133877E+12 | 0.00 | 0.00 |
Minimum of Months | 0.346273E+11 | 0.00 | 0.00 | 0.00 | 0.102820E+11 | 0.00 | 0.00 |
Maximum of Months | 0.383373E+11 | 0.00 | 0.527693E+09 | 0.00 | 0.122758E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1285.01 | 02-JAN-17:40 | 952.15 | 01-JAN-06:10 | 12932.59 | 01-JAN-11:09 | 0.00 | 2926.87 | 02-JAN-13:00 | 0.00 | 07-JAN-15:39 | 0.00 | 01-JAN-00:10 |
February | 1285.01 | 01-FEB-18:10 | 952.15 | 01-FEB-06:10 | 12932.59 | 01-FEB-11:09 | 0.00 | 2722.31 | 11-FEB-13:00 | 0.00 | 24-FEB-08:00 | 0.00 | 01-FEB-00:10 |
March | 1285.01 | 01-MAR-18:19 | 952.15 | 01-MAR-06:10 | 12932.59 | 01-MAR-11:09 | 0.00 | 2723.02 | 13-MAR-12:00 | 0.00 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 1285.01 | 01-APR-18:40 | 952.15 | 01-APR-05:10 | 12932.59 | 01-APR-10:09 | 0.00 | 3023.11 | 13-APR-11:00 | 0.00 | 01-APR-09:39 | 0.00 | 01-APR-00:10 |
May | 1285.01 | 01-MAY-18:49 | 952.15 | 01-MAY-05:10 | 12932.59 | 01-MAY-10:09 | 0.00 | 3235.87 | 31-MAY-12:00 | 0.00 | 10-MAY-14:39 | 0.00 | 01-MAY-00:10 |
June | 1285.01 | 01-JUN-18:30 | 952.15 | 01-JUN-05:10 | 12932.59 | 01-JUN-10:09 | 0.00 | 3278.50 | 08-JUN-17:10 | 0.00 | 13-JUN-16:40 | 0.00 | 01-JUN-00:10 |
July | 1285.01 | 01-JUL-19:19 | 952.15 | 01-JUL-05:10 | 12932.59 | 01-JUL-10:09 | 0.00 | 3480.59 | 14-JUL-11:20 | 0.00 | 01-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 1285.01 | 01-AUG-18:00 | 952.15 | 01-AUG-05:10 | 12932.59 | 01-AUG-10:09 | 0.00 | 3432.21 | 22-AUG-12:00 | 0.00 | 05-AUG-17:49 | 0.00 | 01-AUG-00:10 |
September | 1285.01 | 01-SEP-18:40 | 952.15 | 01-SEP-05:10 | 12932.59 | 01-SEP-10:09 | 0.00 | 3387.80 | 22-SEP-11:00 | 0.00 | 02-SEP-13:20 | 0.00 | 01-SEP-00:10 |
October | 1285.01 | 02-OCT-17:00 | 952.15 | 01-OCT-05:10 | 12932.59 | 01-OCT-10:09 | 0.00 | 3362.19 | 03-OCT-11:00 | 0.00 | 09-OCT-12:20 | 0.00 | 01-OCT-00:10 |
November | 1285.01 | 01-NOV-17:40 | 952.15 | 01-NOV-05:10 | 12932.59 | 01-NOV-10:09 | 0.00 | 2967.49 | 03-NOV-12:00 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 1285.01 | 01-DEC-17:30 | 952.15 | 01-DEC-06:10 | 12932.59 | 01-DEC-11:09 | 0.00 | 2646.11 | 08-DEC-12:09 | 0.00 | 25-DEC-09:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1285.01 | 952.15 | 12932.59 | 0.00 | 2646.11 | 0.00 | 0.00 | ||||||
Maximum of Months | 1285.01 | 952.15 | 12932.59 | 0.00 | 3480.59 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 13801.63 | 02-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12920.98 | 11-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12872.89 | 13-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14391.37 | 13-APR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15740.51 | 31-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15703.60 | 08-JUN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17218.06 | 27-JUL-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16926.76 | 22-AUG-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16329.87 | 22-SEP-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16316.41 | 03-OCT-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14041.40 | 03-NOV-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12492.55 | 08-DEC-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 12492.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17218.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 30311.48 | 07-JAN-11:20 | 879.34 | 12932.59 | 0.00 | 0.00 | 2337.51 | 0.00 | 0.00 | 10240.32 | 0.00 |
February | 31472.31 | 11-FEB-11:20 | 879.34 | 12932.59 | 0.00 | 0.00 | 2484.98 | 0.00 | 0.00 | 11253.67 | 0.00 |
March | 31707.85 | 14-MAR-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 2507.00 | 0.00 | 0.00 | 11347.85 | 0.00 |
April | 31691.20 | 13-APR-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 2465.65 | 0.00 | 0.00 | 11372.54 | 0.00 |
May | 34095.87 | 31-MAY-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 2764.56 | 0.00 | 0.00 | 13478.31 | 0.00 |
June | 34305.91 | 06-JUN-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 2839.65 | 0.00 | 0.00 | 13613.27 | 0.00 |
July | 35743.36 | 25-JUL-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 3002.33 | 0.00 | 0.00 | 14888.02 | 0.00 |
August | 35548.20 | 23-AUG-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 3005.55 | 0.00 | 0.00 | 14689.65 | 0.00 |
September | 34516.65 | 21-SEP-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 2863.27 | 0.00 | 0.00 | 13800.39 | 0.00 |
October | 34310.36 | 03-OCT-11:20 | 989.27 | 12081.43 | 0.00 | 0.00 | 3341.78 | 0.00 | 0.00 | 16141.37 | 0.00 |
November | 32861.87 | 10-NOV-11:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 2616.93 | 0.00 | 0.00 | 12391.94 | 0.00 |
December | 31012.16 | 24-DEC-11:20 | 769.42 | 12932.59 | 0.00 | 0.00 | 2521.07 | 0.00 | 0.00 | 10876.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 30311.48 | 769.42 | 12081.43 | 0.00 | 0.00 | 2337.51 | 0.00 | 0.00 | 10240.32 | 0.00 | |
Maximum of Months | 35743.36 | 989.27 | 12932.59 | 0.00 | 0.00 | 3341.78 | 0.00 | 0.00 | 16141.37 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 25220.79 | 01-JAN-11:09 | 0.00 | 8533.04 | 25-JAN-07:10 | 0.00 | 19809.62 | 18-JAN-13:00 | 0.00 |
February | 25220.79 | 01-FEB-11:09 | 0.00 | 19503.33 | 04-FEB-07:10 | 0.00 | 19768.21 | 02-FEB-13:20 | 0.00 |
March | 25220.79 | 01-MAR-11:09 | 0.00 | 12425.34 | 16-MAR-06:10 | 0.00 | 19510.60 | 03-MAR-13:39 | 0.00 |
April | 25220.79 | 01-APR-10:09 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 18912.92 | 07-APR-12:20 | 0.00 |
May | 25220.79 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 18240.25 | 08-MAY-12:39 | 0.00 |
June | 25220.79 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 17679.89 | 04-JUN-12:39 | 0.00 |
July | 25220.79 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 17323.80 | 01-JUL-12:20 | 0.00 |
August | 25220.79 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 17540.96 | 25-AUG-12:30 | 0.00 |
September | 25220.79 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 18227.55 | 30-SEP-12:00 | 0.00 |
October | 25220.79 | 01-OCT-10:09 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 18857.14 | 28-OCT-12:39 | 0.00 |
November | 25220.79 | 01-NOV-10:09 | 0.00 | 6143.59 | 27-NOV-07:10 | 0.00 | 19412.41 | 28-NOV-13:20 | 0.00 |
December | 25220.79 | 01-DEC-11:09 | 0.00 | 10135.50 | 15-DEC-07:10 | 0.00 | 19755.26 | 31-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 25220.79 | 0.00 | 0.00 | 0.00 | 17323.80 | 0.00 | |||
Maximum of Months | 25220.79 | 0.00 | 19503.33 | 0.00 | 19809.62 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 24.61 | 0.33 | 24.60 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 24.62 | 0.17 | 24.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 24.63 | 1.00 | 24.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 24.65 | 0.50 | 24.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 24.77 | 1.83 | 24.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 24.94 | 0.50 | 24.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 24.99 | 0.00 | 24.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 25.04 | 0.17 | 25.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 25.02 | 0.67 | 25.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 24.94 | 1.17 | 24.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 24.78 | 1.83 | 24.75 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 24.68 | 0.83 | 24.68 |
Annual Sum or Average | 0.00 | 0.00 | 166.67 | 24.83 | 9.00 | 24.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 24.61 | 0.00 | 24.60 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 25.04 | 1.83 | 25.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 29.10 | 0.50 | 29.05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 29.09 | 0.83 | 28.99 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 29.41 | 0.33 | 29.37 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 29.68 | 0.83 | 29.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 57.00 | 28.54 | 26.67 | 28.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 174.33 | 27.69 | 139.17 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 276.17 | 27.63 | 240.00 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 256.83 | 27.65 | 219.83 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 186.33 | 27.66 | 152.00 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 107.83 | 27.96 | 75.67 | 27.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 52.67 | 28.36 | 26.67 | 27.92 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 29.29 | 0.83 | 29.20 |
Annual Sum or Average | 0.00 | 0.00 | 1224.83 | 27.91 | 883.33 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.63 | 0.33 | 27.46 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 276.17 | 29.68 | 240.00 | 29.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 326.67 | 22.94 | 424.83 | 23.47 | 180.50 | 23.56 |
February | 264.83 | 23.27 | 438.67 | 23.66 | 181.17 | 23.72 |
March | 315.00 | 23.39 | 498.33 | 23.72 | 232.33 | 23.78 |
April | 255.50 | 23.95 | 574.00 | 23.96 | 247.50 | 23.97 |
May | 463.67 | 24.03 | 611.00 | 24.02 | 463.67 | 24.02 |
June | 579.00 | 24.04 | 592.00 | 24.04 | 579.00 | 24.04 |
July | 593.67 | 24.04 | 609.00 | 24.03 | 593.67 | 24.04 |
August | 604.50 | 24.04 | 612.00 | 24.04 | 604.50 | 24.04 |
September | 580.17 | 24.03 | 590.00 | 24.03 | 580.17 | 24.03 |
October | 479.83 | 24.03 | 610.00 | 24.02 | 479.83 | 24.02 |
November | 408.83 | 23.83 | 548.50 | 23.91 | 379.67 | 23.94 |
December | 371.33 | 23.30 | 485.67 | 23.63 | 272.50 | 23.70 |
Annual Sum or Average | 5243.00 | 23.82 | 6594.00 | 23.91 | 4794.50 | 23.94 |
Minimum of Months | 255.50 | 22.94 | 424.83 | 23.47 | 180.50 | 23.56 |
Maximum of Months | 604.50 | 24.04 | 612.00 | 24.04 | 604.50 | 24.04 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.33 | 25.98 | 588.33 | 25.84 | 481.83 | 25.92 |
February | 481.17 | 25.96 | 526.50 | 25.95 | 467.00 | 26.00 |
March | 545.17 | 26.05 | 587.00 | 26.01 | 534.67 | 26.06 |
April | 582.00 | 26.18 | 590.00 | 26.17 | 582.00 | 26.18 |
May | 611.00 | 26.29 | 611.00 | 26.29 | 611.00 | 26.29 |
June | 592.00 | 26.59 | 592.00 | 26.59 | 592.00 | 26.59 |
July | 609.00 | 26.79 | 609.00 | 26.79 | 609.00 | 26.79 |
August | 612.00 | 26.76 | 612.00 | 26.76 | 612.00 | 26.76 |
September | 590.00 | 26.60 | 590.00 | 26.60 | 590.00 | 26.60 |
October | 610.00 | 26.39 | 610.00 | 26.39 | 610.00 | 26.39 |
November | 566.33 | 26.22 | 583.33 | 26.20 | 563.67 | 26.21 |
December | 540.17 | 25.93 | 581.00 | 25.91 | 522.67 | 25.97 |
Annual Sum or Average | 6832.17 | 26.33 | 7080.17 | 26.31 | 6775.83 | 26.33 |
Minimum of Months | 481.17 | 25.93 | 526.50 | 25.84 | 467.00 | 25.92 |
Maximum of Months | 612.00 | 26.79 | 612.00 | 26.79 | 612.00 | 26.79 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.32852 | 56.75041 | 0.46327 | 11.32316 |
February | 551.00000 | 23.56539 | 56.51760 | 0.52051 | 12.18527 |
March | 612.00000 | 23.61603 | 58.84314 | 0.54800 | 12.85688 |
April | 590.00000 | 23.93586 | 62.36697 | 0.65763 | 14.37146 |
May | 611.00000 | 24.00396 | 69.39690 | -0.0951 | 5.49371 |
June | 592.00000 | 24.04139 | 73.50819 | -0.0399 | 5.51079 |
July | 609.00000 | 24.03307 | 73.10212 | -0.0222 | 5.45334 |
August | 612.00000 | 24.04149 | 73.92163 | -0.0143 | 5.49833 |
September | 590.00000 | 24.03250 | 72.83438 | -0.0129 | 5.50446 |
October | 610.00000 | 24.00978 | 69.82012 | 0.76861 | 17.65145 |
November | 591.00000 | 23.84424 | 65.96805 | 0.67984 | 15.61914 |
December | 609.00000 | 23.48938 | 61.50246 | 0.53994 | 12.81368 |
Annual Sum or Average | 7187.00000 | 23.82923 | 66.26544 | 0.33124 | 10.34136 |
Minimum of Months | 551.00000 | 23.32852 | 56.51760 | -0.0951 | 5.45334 |
Maximum of Months | 612.00000 | 24.04149 | 73.92163 | 0.76861 | 17.65145 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 25.58612 | 52.42660 | 1.15540 | 34.89389 |
February | 551.00000 | 25.73564 | 52.38840 | 1.19390 | 36.73777 |
March | 612.00000 | 25.80899 | 53.98758 | 1.22619 | 38.13276 |
April | 590.00000 | 26.15915 | 57.15135 | 1.34670 | 42.87009 |
May | 611.00000 | 26.29429 | 62.71946 | 0.89453 | 22.45822 |
June | 592.00000 | 26.58960 | 66.24970 | 1.03198 | 28.48969 |
July | 609.00000 | 26.79400 | 66.61405 | 1.11969 | 32.65894 |
August | 612.00000 | 26.75747 | 66.75728 | 1.10281 | 31.86574 |
September | 590.00000 | 26.59612 | 65.81081 | 1.04575 | 29.10031 |
October | 610.00000 | 26.39410 | 63.00750 | 1.47334 | 49.48761 |
November | 591.00000 | 26.11979 | 59.22027 | 1.36137 | 44.10261 |
December | 609.00000 | 25.69621 | 55.86861 | 1.21601 | 37.75779 |
Annual Sum or Average | 7187.00000 | 26.21327 | 60.22775 | 1.18029 | 35.69684 |
Minimum of Months | 551.00000 | 25.58612 | 52.38840 | 0.89453 | 22.45822 |
Maximum of Months | 612.00000 | 26.79400 | 66.75728 | 1.47334 | 49.48761 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.124170E+11 | 0.315842E+10 | 407.77 | 0.720370E+10 | 0.521326E+10 | 0.00 | 1.00 | 01-JAN-03:01 | 0.00 | 01-JAN-00:10 | 53916.42 | 14-JAN-03:01 | 28418.53 | 06-JAN-03:01 | 30322.64 | 07-JAN-03:01 | 11633.12 | 07-JAN-03:01 | 0.00 | 01-JAN-00:10 |
February | 0.152225E+11 | 0.386549E+10 | 442.76 | 0.933833E+10 | 0.588414E+10 | 0.00 | 1.00 | 02-FEB-03:02 | 0.00 | 01-FEB-00:10 | 53400.44 | 11-FEB-03:01 | 28384.82 | 15-FEB-03:01 | 29045.26 | 11-FEB-03:01 | 11521.87 | 11-FEB-03:01 | 0.00 | 01-FEB-00:10 |
March | 0.196149E+11 | 0.489604E+10 | 516.33 | 0.111337E+11 | 0.848119E+10 | 0.00 | 1.00 | 04-MAR-03:01 | 0.00 | 01-MAR-00:10 | 53916.42 | 10-MAR-03:01 | 25991.29 | 13-MAR-02:61 | 31090.39 | 14-MAR-02:61 | 11633.12 | 10-MAR-03:01 | 0.00 | 01-MAR-00:10 |
April | 0.265668E+11 | 0.653064E+10 | 594.35 | 0.156301E+11 | 0.109368E+11 | 0.00 | 1.00 | 01-APR-02:61 | 0.00 | 01-APR-00:02 | 53916.42 | 12-APR-02:61 | 28766.97 | 05-APR-02:61 | 31275.81 | 13-APR-02:61 | 11633.12 | 12-APR-02:61 | 0.00 | 01-APR-00:02 |
May | 0.406416E+11 | 0.950111E+10 | 631.04 | 0.216520E+11 | 0.189895E+11 | 0.00 | 1.00 | 01-MAY-02:62 | 0.00 | 01-MAY-00:02 | 53916.42 | 25-MAY-02:61 | 29270.77 | 03-MAY-02:61 | 35553.13 | 29-MAY-02:61 | 11633.12 | 04-MAY-02:61 | 0.00 | 01-MAY-00:02 |
June | 0.487571E+11 | 0.110583E+11 | 611.41 | 0.238859E+11 | 0.248712E+11 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:03 | 53916.42 | 10-JUN-02:61 | 29267.66 | 17-JUN-02:61 | 35246.77 | 07-JUN-02:02 | 11633.12 | 01-JUN-02:61 | 0.00 | 01-JUN-00:03 |
July | 0.535022E+11 | 0.122006E+11 | 631.82 | 0.267099E+11 | 0.267923E+11 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:03 | 53916.42 | 05-JUL-02:61 | 29778.17 | 02-JUL-02:61 | 33409.11 | 12-JUL-02:02 | 11633.12 | 01-JUL-02:61 | 0.00 | 01-JUL-00:03 |
August | 0.534482E+11 | 0.121082E+11 | 631.81 | 0.260721E+11 | 0.273761E+11 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:03 | 53916.42 | 01-AUG-02:61 | 25439.74 | 08-AUG-02:61 | 34279.09 | 28-AUG-02:61 | 11633.12 | 01-AUG-02:61 | 0.00 | 01-AUG-00:03 |
September | 0.493406E+11 | 0.112242E+11 | 611.51 | 0.245290E+11 | 0.248116E+11 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:03 | 53916.42 | 19-SEP-02:02 | 26416.06 | 30-SEP-02:61 | 33117.53 | 28-SEP-02:61 | 11633.12 | 01-SEP-02:61 | 0.00 | 01-SEP-00:03 |
October | 0.433046E+11 | 0.100111E+11 | 631.33 | 0.223293E+11 | 0.209753E+11 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:02 | 53916.42 | 02-OCT-02:61 | 34470.49 | 18-OCT-02:61 | 34997.32 | 03-OCT-02:02 | 11633.12 | 01-OCT-02:61 | 0.00 | 01-OCT-00:02 |
November | 0.298500E+11 | 0.704726E+10 | 560.82 | 0.154704E+11 | 0.143796E+11 | 0.00 | 1.00 | 01-NOV-02:61 | 0.00 | 01-NOV-00:02 | 53916.42 | 03-NOV-02:61 | 29920.36 | 20-NOV-03:01 | 33498.02 | 05-NOV-02:61 | 11633.12 | 03-NOV-02:61 | 0.00 | 01-NOV-00:02 |
December | 0.166141E+11 | 0.410739E+10 | 464.76 | 0.887151E+10 | 0.774262E+10 | 0.00 | 1.00 | 01-DEC-03:01 | 0.00 | 01-DEC-00:01 | 53916.42 | 11-DEC-03:01 | 29854.96 | 01-DEC-03:01 | 33003.71 | 26-DEC-03:01 | 11633.12 | 07-DEC-03:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.409280E+12 | 0.957087E+11 | 6735.69 | 0.212826E+12 | 0.196454E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.124170E+11 | 0.315842E+10 | 407.77 | 0.720370E+10 | 0.521326E+10 | 0.00 | 1.00 | 0.00 | 53400.44 | 25439.74 | 29045.26 | 11521.87 | 0.00 | |||||||
Maximum of Months | 0.535022E+11 | 0.122006E+11 | 631.82 | 0.267099E+11 | 0.273761E+11 | 0.00 | 1.00 | 0.00 | 53916.42 | 34470.49 | 35553.13 | 11633.12 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.171282E+11 | 0.394479E+10 | 490.54 | 0.938500E+10 | 0.774317E+10 | 0.00 | 1.00 | 01-JAN-03:01 | 0.00 | 01-JAN-00:10 | 31066.25 | 02-JAN-14:20 | 24603.42 | 27-JAN-03:01 | 20339.17 | 07-JAN-03:52 | 6585.42 | 02-JAN-13:50 | 0.00 | 01-JAN-00:10 |
February | 0.193381E+11 | 0.442297E+10 | 493.23 | 0.112036E+11 | 0.813449E+10 | 0.00 | 1.00 | 01-FEB-03:01 | 0.00 | 01-FEB-00:10 | 31066.25 | 11-FEB-11:43 | 22760.12 | 03-FEB-03:01 | 18804.70 | 11-FEB-04:32 | 6614.63 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.250165E+11 | 0.562984E+10 | 581.49 | 0.134413E+11 | 0.115752E+11 | 0.00 | 1.00 | 01-MAR-03:01 | 0.00 | 01-MAR-00:10 | 31066.25 | 05-MAR-11:31 | 21720.54 | 17-MAR-04:01 | 20253.57 | 06-MAR-03:11 | 6585.42 | 04-MAR-11:43 | 0.00 | 01-MAR-00:10 |
April | 0.318246E+11 | 0.708769E+10 | 639.22 | 0.182416E+11 | 0.135830E+11 | 0.00 | 1.00 | 01-APR-02:11 | 0.00 | 01-APR-00:02 | 31066.25 | 25-APR-13:35 | 21913.05 | 20-APR-02:61 | 20166.25 | 01-APR-02:11 | 6709.47 | 14-APR-13:13 | 0.00 | 01-APR-00:02 |
May | 0.485387E+11 | 0.104658E+11 | 677.58 | 0.251993E+11 | 0.233394E+11 | 0.00 | 1.00 | 01-MAY-02:11 | 0.00 | 01-MAY-00:02 | 31066.25 | 27-MAY-02:61 | 24934.96 | 22-MAY-13:00 | 21702.01 | 29-MAY-02:42 | 7077.21 | 22-MAY-13:00 | 0.00 | 01-MAY-00:02 |
June | 0.583213E+11 | 0.124995E+11 | 668.22 | 0.276641E+11 | 0.306573E+11 | 0.00 | 1.00 | 01-JUN-01:23 | 0.00 | 01-JUN-00:03 | 31066.25 | 02-JUN-21:00 | 20976.62 | 11-JUN-12:55 | 21320.86 | 06-JUN-19:55 | 6852.19 | 11-JUN-12:55 | 0.00 | 01-JUN-00:03 |
July | 0.617596E+11 | 0.133732E+11 | 687.41 | 0.303298E+11 | 0.314299E+11 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:03 | 31066.25 | 06-JUL-03:22 | 24456.01 | 29-JUL-15:53 | 21117.70 | 03-JUL-03:22 | 7213.16 | 29-JUL-15:53 | 0.00 | 01-JUL-00:03 |
August | 0.626716E+11 | 0.134882E+11 | 690.97 | 0.295612E+11 | 0.331104E+11 | 0.00 | 1.00 | 01-AUG-00:08 | 0.00 | 01-AUG-00:03 | 31066.25 | 25-AUG-10:52 | 22323.24 | 23-AUG-11:55 | 21385.52 | 12-AUG-14:00 | 7023.25 | 23-AUG-13:00 | 0.00 | 01-AUG-00:03 |
September | 0.580421E+11 | 0.124836E+11 | 667.56 | 0.278528E+11 | 0.301893E+11 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:03 | 31066.25 | 09-SEP-08:62 | 21336.44 | 08-SEP-15:35 | 21458.21 | 06-SEP-02:42 | 6852.19 | 13-SEP-12:55 | 0.00 | 01-SEP-00:03 |
October | 0.514105E+11 | 0.110637E+11 | 677.72 | 0.251519E+11 | 0.262586E+11 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:02 | 31066.25 | 04-OCT-05:40 | 21488.95 | 23-OCT-11:10 | 22188.67 | 04-OCT-04:02 | 6852.19 | 09-OCT-10:53 | 0.00 | 01-OCT-00:02 |
November | 0.366604E+11 | 0.798937E+10 | 611.14 | 0.177068E+11 | 0.189536E+11 | 0.00 | 1.00 | 01-NOV-02:11 | 0.00 | 01-NOV-00:02 | 31066.25 | 03-NOV-19:40 | 22077.47 | 12-NOV-03:01 | 21027.77 | 04-NOV-03:22 | 6614.63 | 03-NOV-13:00 | 0.00 | 01-NOV-00:02 |
December | 0.228478E+11 | 0.514145E+10 | 538.74 | 0.112425E+11 | 0.116052E+11 | 0.00 | 1.00 | 01-DEC-03:11 | 0.00 | 01-DEC-00:01 | 31066.25 | 24-DEC-13:35 | 19951.47 | 15-DEC-03:01 | 21228.95 | 24-DEC-03:11 | 6585.42 | 07-DEC-11:35 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.493559E+12 | 0.107590E+12 | 7423.81 | 0.246980E+12 | 0.246579E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.171282E+11 | 0.394479E+10 | 490.54 | 0.938500E+10 | 0.774317E+10 | 0.00 | 1.00 | 0.00 | 31066.25 | 19951.47 | 18804.70 | 6585.42 | 0.00 | |||||||
Maximum of Months | 0.626716E+11 | 0.134882E+11 | 690.97 | 0.303298E+11 | 0.331104E+11 | 0.00 | 1.00 | 0.00 | 31066.25 | 24934.96 | 22188.67 | 7213.16 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.55 | 33.32 | 36.23 | 102.89 | 69.66 | 0.00 | 0.00 | 0.00 |
February | 80.30 | 37.17 | 43.13 | 128.63 | 57.62 | 0.00 | 0.00 | 0.00 |
March | 98.04 | 46.35 | 51.69 | 159.07 | 46.36 | 0.00 | 0.00 | 0.00 |
April | 106.40 | 47.48 | 58.93 | 193.31 | 31.70 | 0.00 | 0.00 | 0.00 |
May | 100.66 | 40.09 | 60.58 | 201.17 | 15.01 | 0.00 | 0.00 | 0.00 |
June | 99.35 | 38.16 | 61.19 | 209.49 | 6.74 | 0.00 | 0.00 | 0.00 |
July | 102.09 | 36.81 | 65.27 | 222.78 | 10.07 | 0.00 | 0.00 | 0.00 |
August | 93.35 | 31.21 | 62.14 | 195.87 | 7.49 | 0.00 | 0.00 | 0.00 |
September | 90.00 | 32.53 | 57.46 | 192.03 | 12.10 | 0.00 | 0.00 | 0.00 |
October | 82.84 | 35.67 | 47.16 | 162.93 | 19.51 | 0.00 | 0.00 | 0.00 |
November | 67.23 | 26.81 | 40.43 | 117.41 | 36.20 | 0.00 | 0.00 | 0.00 |
December | 54.31 | 19.17 | 35.14 | 81.16 | 61.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.03 | 35.37 | 51.65 | 164.03 | 31.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.31 | 19.17 | 35.14 | 81.16 | 6.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.40 | 47.48 | 65.27 | 222.78 | 69.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.51 | 176.39 | 95.12 | 450.36 | 136.42 | 0.00 | 0.00 | 0.00 |
February | 245.62 | 142.12 | 103.50 | 429.82 | 114.96 | 0.00 | 0.00 | 0.00 |
March | 188.58 | 79.73 | 108.85 | 334.79 | 95.39 | 0.00 | 0.00 | 0.00 |
April | 128.23 | 22.49 | 105.75 | 250.00 | 65.18 | 0.00 | 0.00 | 0.00 |
May | 102.76 | 2.22 | 100.53 | 220.48 | 30.98 | 0.00 | 0.00 | 0.00 |
June | 97.97 | 0.18 | 97.79 | 227.13 | 14.33 | 0.00 | 0.00 | 0.00 |
July | 104.90 | 0.97 | 103.93 | 255.26 | 20.49 | 0.00 | 0.00 | 0.00 |
August | 119.06 | 10.05 | 109.01 | 272.82 | 15.59 | 0.00 | 0.00 | 0.00 |
September | 152.41 | 37.35 | 115.06 | 349.77 | 24.89 | 0.00 | 0.00 | 0.00 |
October | 209.59 | 98.33 | 111.26 | 425.34 | 40.08 | 0.00 | 0.00 | 0.00 |
November | 238.47 | 133.09 | 105.38 | 434.25 | 72.93 | 0.00 | 0.00 | 0.00 |
December | 261.66 | 165.04 | 96.62 | 443.37 | 119.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 176.41 | 72.02 | 104.39 | 340.67 | 62.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.97 | 0.18 | 95.12 | 220.48 | 14.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 271.51 | 176.39 | 115.06 | 450.36 | 136.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.48 | 26.93 | 35.54 | 91.47 | 72.68 | 0.00 | 0.00 | 0.00 |
February | 78.12 | 35.36 | 42.77 | 128.38 | 60.45 | 0.00 | 0.00 | 0.00 |
March | 97.29 | 44.43 | 52.86 | 162.00 | 49.29 | 0.00 | 0.00 | 0.00 |
April | 107.09 | 49.58 | 57.50 | 196.10 | 32.21 | 0.00 | 0.00 | 0.00 |
May | 97.62 | 37.58 | 60.04 | 197.11 | 15.85 | 0.00 | 0.00 | 0.00 |
June | 82.72 | 23.20 | 59.51 | 178.63 | 7.30 | 0.00 | 0.00 | 0.00 |
July | 92.44 | 28.60 | 63.85 | 204.69 | 10.09 | 0.00 | 0.00 | 0.00 |
August | 92.23 | 30.06 | 62.18 | 193.90 | 7.86 | 0.00 | 0.00 | 0.00 |
September | 78.68 | 23.20 | 55.48 | 170.91 | 12.31 | 0.00 | 0.00 | 0.00 |
October | 78.27 | 30.51 | 47.76 | 155.10 | 20.24 | 0.00 | 0.00 | 0.00 |
November | 64.57 | 23.68 | 40.88 | 114.85 | 38.44 | 0.00 | 0.00 | 0.00 |
December | 64.68 | 28.92 | 35.76 | 101.42 | 62.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 31.83 | 51.22 | 158.04 | 32.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.48 | 23.20 | 35.54 | 91.47 | 7.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.09 | 49.58 | 63.85 | 204.69 | 72.68 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186274E+09 | 89236778.67 | 97037547.90 | 0.275569E+09 | 0.186573E+09 |
February | 0.194271E+09 | 89928048.50 | 0.104342E+09 | 0.311174E+09 | 0.139393E+09 |
March | 0.262603E+09 | 0.124147E+09 | 0.138456E+09 | 0.426062E+09 | 0.124172E+09 |
April | 0.275797E+09 | 0.123059E+09 | 0.152738E+09 | 0.501047E+09 | 82159091.89 |
May | 0.269612E+09 | 0.107366E+09 | 0.162247E+09 | 0.538810E+09 | 40207868.50 |
June | 0.257527E+09 | 98914328.81 | 0.158613E+09 | 0.542986E+09 | 17457661.15 |
July | 0.273432E+09 | 98605159.65 | 0.174827E+09 | 0.596686E+09 | 26976152.41 |
August | 0.250030E+09 | 83604612.69 | 0.166426E+09 | 0.524627E+09 | 20070922.74 |
September | 0.233270E+09 | 84327711.19 | 0.148942E+09 | 0.497731E+09 | 31352401.86 |
October | 0.221872E+09 | 95551600.38 | 0.126321E+09 | 0.436380E+09 | 52247550.65 |
November | 0.174270E+09 | 69487909.69 | 0.104782E+09 | 0.304330E+09 | 93832194.95 |
December | 0.145464E+09 | 51355836.69 | 94108437.05 | 0.217381E+09 | 0.163942E+09 |
Annual Sum or Average | 0.274442E+10 | 0.111558E+10 | 0.162884E+10 | 0.517279E+10 | 0.978384E+09 |
Minimum of Months | 0.145464E+09 | 51355836.69 | 94108437.05 | 0.217381E+09 | 17457661.15 |
Maximum of Months | 0.275797E+09 | 0.124147E+09 | 0.174827E+09 | 0.596686E+09 | 0.186573E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.727216E+09 | 0.472455E+09 | 0.254760E+09 | 0.120624E+10 | 0.365389E+09 |
February | 0.594208E+09 | 0.343822E+09 | 0.250386E+09 | 0.103981E+10 | 0.278120E+09 |
March | 0.505098E+09 | 0.213551E+09 | 0.291547E+09 | 0.896698E+09 | 0.255493E+09 |
April | 0.332378E+09 | 58286166.70 | 0.274092E+09 | 0.647995E+09 | 0.168955E+09 |
May | 0.275226E+09 | 5954427.09 | 0.269272E+09 | 0.590534E+09 | 82967300.67 |
June | 0.253939E+09 | 479224.57 | 0.253460E+09 | 0.588721E+09 | 37150432.38 |
July | 0.280964E+09 | 2604277.42 | 0.278359E+09 | 0.683680E+09 | 54891756.08 |
August | 0.318885E+09 | 26909133.90 | 0.291975E+09 | 0.730722E+09 | 41745496.88 |
September | 0.395046E+09 | 96806670.67 | 0.298239E+09 | 0.906608E+09 | 64503795.07 |
October | 0.561376E+09 | 0.263380E+09 | 0.297996E+09 | 0.113922E+10 | 0.107344E+09 |
November | 0.618118E+09 | 0.344978E+09 | 0.273140E+09 | 0.112557E+10 | 0.189025E+09 |
December | 0.700832E+09 | 0.442045E+09 | 0.258787E+09 | 0.118752E+10 | 0.320201E+09 |
Annual Sum or Average | 0.556329E+10 | 0.227127E+10 | 0.329201E+10 | 0.107433E+11 | 0.196579E+10 |
Minimum of Months | 0.253939E+09 | 479224.57 | 0.250386E+09 | 0.588721E+09 | 37150432.38 |
Maximum of Months | 0.727216E+09 | 0.472455E+09 | 0.298239E+09 | 0.120624E+10 | 0.365389E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167337E+09 | 72141064.99 | 95195525.66 | 0.245005E+09 | 0.194662E+09 |
February | 0.189000E+09 | 85533114.92 | 0.103467E+09 | 0.310569E+09 | 0.146244E+09 |
March | 0.260580E+09 | 0.118994E+09 | 0.141586E+09 | 0.433890E+09 | 0.132031E+09 |
April | 0.277571E+09 | 0.128524E+09 | 0.149047E+09 | 0.508291E+09 | 83483539.79 |
May | 0.261476E+09 | 0.100656E+09 | 0.160820E+09 | 0.527948E+09 | 42463357.92 |
June | 0.214404E+09 | 60142129.75 | 0.154262E+09 | 0.463011E+09 | 18928819.22 |
July | 0.247603E+09 | 76600471.73 | 0.171003E+09 | 0.548247E+09 | 27038359.08 |
August | 0.247040E+09 | 80509729.17 | 0.166530E+09 | 0.519343E+09 | 21038959.35 |
September | 0.203940E+09 | 60135399.20 | 0.143805E+09 | 0.442986E+09 | 31908335.99 |
October | 0.209646E+09 | 81726181.78 | 0.127919E+09 | 0.415431E+09 | 54210006.61 |
November | 0.167357E+09 | 61387443.49 | 0.105970E+09 | 0.297703E+09 | 99632098.64 |
December | 0.173245E+09 | 77456445.60 | 95788625.49 | 0.271632E+09 | 0.166567E+09 |
Annual Sum or Average | 0.261920E+10 | 0.100381E+10 | 0.161539E+10 | 0.498406E+10 | 0.101821E+10 |
Minimum of Months | 0.167337E+09 | 60135399.20 | 95195525.66 | 0.245005E+09 | 18928819.22 |
Maximum of Months | 0.277571E+09 | 0.128524E+09 | 0.171003E+09 | 0.548247E+09 | 0.194662E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 638.79 | 272.83 | 403.53 | 236.65 | 166.89 | 0.00 | 0.00 |
February | 682.59 | 228.80 | 404.05 | 214.65 | 189.40 | 0.00 | 0.00 |
March | 648.48 | 183.67 | 383.92 | 170.51 | 213.41 | 0.00 | 0.00 |
April | 636.50 | 126.19 | 341.72 | 119.55 | 222.17 | 0.00 | 0.00 |
May | 617.78 | 60.86 | 301.04 | 79.89 | 221.15 | 0.00 | 0.00 |
June | 614.65 | 27.77 | 280.04 | 61.55 | 218.49 | 0.00 | 0.00 |
July | 682.42 | 40.36 | 299.43 | 66.39 | 233.05 | 0.00 | 0.00 |
August | 662.47 | 30.81 | 304.64 | 71.32 | 233.32 | 0.00 | 0.00 |
September | 712.23 | 48.82 | 321.09 | 93.08 | 228.00 | 0.00 | 0.00 |
October | 742.82 | 79.28 | 370.70 | 164.52 | 206.18 | 0.00 | 0.00 |
November | 664.47 | 145.52 | 370.27 | 183.59 | 186.69 | 0.00 | 0.00 |
December | 622.86 | 239.86 | 380.65 | 213.13 | 167.52 | 0.00 | 0.00 |
Annual Sum or Average | 660.36 | 123.27 | 346.49 | 139.23 | 207.26 | 0.00 | 0.00 |
Minimum of Months | 614.65 | 27.77 | 280.04 | 61.55 | 166.89 | 0.00 | 0.00 |
Maximum of Months | 742.82 | 272.83 | 404.05 | 236.65 | 233.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.171094E+10 | 0.730742E+09 | 0.108083E+10 | 0.633833E+09 | 0.446993E+09 | 0.00 | 0.00 |
February | 0.165132E+10 | 0.553517E+09 | 0.977479E+09 | 0.519283E+09 | 0.458195E+09 | 0.00 | 0.00 |
March | 0.173690E+10 | 0.491941E+09 | 0.102828E+10 | 0.456692E+09 | 0.571588E+09 | 0.00 | 0.00 |
April | 0.164982E+10 | 0.327084E+09 | 0.885746E+09 | 0.309869E+09 | 0.575877E+09 | 0.00 | 0.00 |
May | 0.165467E+10 | 0.163018E+09 | 0.806315E+09 | 0.213976E+09 | 0.592339E+09 | 0.00 | 0.00 |
June | 0.159316E+10 | 71983690.63 | 0.725871E+09 | 0.159536E+09 | 0.566335E+09 | 0.00 | 0.00 |
July | 0.182780E+10 | 0.108090E+09 | 0.801999E+09 | 0.177810E+09 | 0.624189E+09 | 0.00 | 0.00 |
August | 0.177435E+10 | 82512995.34 | 0.815955E+09 | 0.191023E+09 | 0.624931E+09 | 0.00 | 0.00 |
September | 0.184610E+10 | 0.126542E+09 | 0.832256E+09 | 0.241270E+09 | 0.590986E+09 | 0.00 | 0.00 |
October | 0.198956E+10 | 0.212335E+09 | 0.992894E+09 | 0.440658E+09 | 0.552236E+09 | 0.00 | 0.00 |
November | 0.172231E+10 | 0.377197E+09 | 0.959744E+09 | 0.475853E+09 | 0.483891E+09 | 0.00 | 0.00 |
December | 0.166826E+10 | 0.642435E+09 | 0.101954E+10 | 0.570857E+09 | 0.448684E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.208252E+11 | 0.388740E+10 | 0.109269E+11 | 0.439066E+10 | 0.653625E+10 | 0.00 | 0.00 |
Minimum of Months | 0.159316E+10 | 71983690.63 | 0.725871E+09 | 0.159536E+09 | 0.446993E+09 | 0.00 | 0.00 |
Maximum of Months | 0.198956E+10 | 0.730742E+09 | 0.108083E+10 | 0.633833E+09 | 0.624931E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.101044E+11 | -0.943655E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -667867027.1 | 58.98 | 0.00 | 0.00 |
February | 0.904129E+10 | -0.844014E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -601142256.3 | 58.98 | 0.00 | 0.00 |
March | 0.973937E+10 | -0.907568E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -663695172.5 | 58.99 | 0.00 | 0.00 |
April | 0.899123E+10 | -0.835536E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -635870332.4 | 58.98 | 0.00 | 0.00 |
May | 0.886619E+10 | -0.821174E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -654451781.0 | 58.98 | 0.00 | 0.00 |
June | 0.825814E+10 | -0.762991E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -628234121.3 | 58.98 | 0.00 | 0.00 |
July | 0.836811E+10 | -0.772211E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -645996611.2 | 58.99 | 0.00 | 0.00 |
August | 0.848557E+10 | -0.783924E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -646336120.6 | 58.98 | 0.00 | 0.00 |
September | 0.848353E+10 | -0.785542E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -628104147.9 | 58.98 | 0.00 | 0.00 |
October | 0.919521E+10 | -0.854270E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -652510960.4 | 58.98 | 0.00 | 0.00 |
November | 0.932887E+10 | -0.869226E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -636608948.2 | 58.98 | 0.00 | 0.00 |
December | 0.995803E+10 | -0.929234E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -665689926.2 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.108820E+12 | -0.101093E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.772651E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.825814E+10 | -0.943655E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -667867027.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.101044E+11 | -0.762991E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -601142256.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.28 | 0.24 | 01-JAN-07:40 | 1551.94 | 24.69 | 119.50 | 292.33 | 1554.54 | 24.37 | 116.33 | 290.67 |
February | 304.33 | 0.27 | 0.24 | 01-FEB-07:49 | 1314.79 | 22.23 | 87.17 | 282.83 | 1232.03 | 20.18 | 47.17 | 275.17 |
March | 362.67 | 0.26 | 0.24 | 01-MAR-07:30 | 1106.58 | 18.24 | 3.67 | 343.33 | 1116.37 | 18.14 | 1.83 | 343.67 |
April | 357.50 | 0.27 | 0.24 | 01-APR-06:00 | 1039.53 | 17.67 | 0.00 | 337.83 | 1121.75 | 17.78 | 0.00 | 336.83 |
May | 389.00 | 0.26 | 0.24 | 01-MAY-06:19 | 925.66 | 17.35 | 0.00 | 366.50 | 1117.71 | 17.37 | 0.00 | 364.33 |
June | 388.17 | 0.28 | 0.24 | 01-JUN-06:30 | 815.05 | 16.83 | 0.00 | 343.50 | 1088.59 | 16.78 | 0.00 | 349.17 |
July | 403.83 | 0.26 | 0.24 | 01-JUL-06:19 | 914.95 | 17.60 | 0.00 | 367.83 | 990.98 | 17.58 | 0.00 | 369.50 |
August | 348.33 | 0.27 | 0.24 | 01-AUG-06:40 | 1011.38 | 17.97 | 0.00 | 351.50 | 1053.34 | 18.01 | 0.00 | 353.83 |
September | 349.67 | 0.27 | 0.24 | 01-SEP-06:49 | 983.43 | 18.46 | 7.00 | 323.33 | 1113.67 | 18.36 | 6.83 | 324.33 |
October | 323.50 | 0.27 | 0.24 | 02-OCT-06:00 | 1197.12 | 20.90 | 61.50 | 316.00 | 1185.25 | 20.70 | 53.50 | 315.33 |
November | 314.83 | 0.26 | 0.24 | 01-NOV-06:00 | 1218.75 | 23.15 | 106.00 | 291.83 | 1113.12 | 21.00 | 54.83 | 291.83 |
December | 282.67 | 0.26 | 0.24 | 01-DEC-08:39 | 1507.20 | 24.42 | 109.17 | 278.83 | 1444.52 | 23.95 | 97.67 | 277.83 |
Annual Sum or Average | 4111.50 | 0.27 | 1108.50 | 19.66 | 494.00 | 3895.67 | 1163.34 | 19.27 | 378.17 | 3892.50 | ||
Minimum of Months | 282.67 | 0.26 | 0.24 | 815.05 | 16.83 | 0.00 | 278.83 | 990.98 | 16.78 | 0.00 | 275.17 | |
Maximum of Months | 403.83 | 0.28 | 0.24 | 1551.94 | 24.69 | 119.50 | 367.83 | 1554.54 | 24.37 | 116.33 | 369.50 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.317353E+09 | 8670.35 | 25-JAN-08:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.393951E+09 | 13164.07 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.321623E+09 | 9940.28 | 16-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 59833779.96 | 4914.87 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.422155E+09 | 9270.31 | 20-DEC-22:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.422155E+09 | 13164.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14188200.18 | 2825.45 | 04-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14188200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14188200.18 | 2825.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.124170E+11 | 0.720370E+10 | 53916.42 | 14-JAN-03:01 | 27081.03 | 0.00 |
February | 0.00 | 0.00 | 0.152225E+11 | 0.933833E+10 | 53400.44 | 11-FEB-03:01 | 24355.18 | 0.00 |
March | 0.00 | 0.00 | 0.196149E+11 | 0.111337E+11 | 53916.42 | 10-MAR-03:01 | 23180.88 | 0.00 |
April | 0.00 | 0.00 | 0.265668E+11 | 0.156301E+11 | 53916.42 | 12-APR-02:61 | 25070.44 | 0.00 |
May | 0.00 | 0.00 | 0.406416E+11 | 0.216520E+11 | 53916.42 | 25-MAY-02:61 | 24709.60 | 0.00 |
June | 0.00 | 0.00 | 0.487571E+11 | 0.238859E+11 | 53916.42 | 10-JUN-02:61 | 24347.81 | 0.00 |
July | 0.00 | 0.00 | 0.535022E+11 | 0.267099E+11 | 53916.42 | 05-JUL-02:61 | 25772.73 | 0.00 |
August | 0.00 | 0.00 | 0.534482E+11 | 0.260721E+11 | 53916.42 | 01-AUG-02:61 | 21759.65 | 0.00 |
September | 0.00 | 0.00 | 0.493406E+11 | 0.245290E+11 | 53916.42 | 19-SEP-02:02 | 21397.87 | 0.00 |
October | 0.00 | 0.00 | 0.433046E+11 | 0.223293E+11 | 53916.42 | 02-OCT-02:61 | 21270.45 | 0.00 |
November | 0.00 | 0.00 | 0.298500E+11 | 0.154704E+11 | 53916.42 | 03-NOV-02:61 | 26392.85 | 0.00 |
December | 0.00 | 0.00 | 0.166141E+11 | 0.887151E+10 | 53916.42 | 11-DEC-03:01 | 22262.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.409280E+12 | 0.212826E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.124170E+11 | 0.720370E+10 | 53400.44 | 21270.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.535022E+11 | 0.267099E+11 | 53916.42 | 27081.03 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.171282E+11 | 0.938500E+10 | 31066.25 | 02-JAN-14:20 | 15537.35 | 0.00 |
February | 0.00 | 0.00 | 0.193381E+11 | 0.112036E+11 | 31066.25 | 11-FEB-11:43 | 14925.85 | 0.00 |
March | 0.00 | 0.00 | 0.250165E+11 | 0.134413E+11 | 31066.25 | 05-MAR-11:31 | 15724.09 | 0.00 |
April | 0.00 | 0.00 | 0.318246E+11 | 0.182416E+11 | 31066.25 | 25-APR-13:35 | 14442.62 | 0.00 |
May | 0.00 | 0.00 | 0.485387E+11 | 0.251993E+11 | 31066.25 | 27-MAY-02:61 | 10685.95 | 0.00 |
June | 0.00 | 0.00 | 0.583213E+11 | 0.276641E+11 | 31066.25 | 02-JUN-21:00 | 14651.05 | 0.00 |
July | 0.00 | 0.00 | 0.617596E+11 | 0.303298E+11 | 31066.25 | 06-JUL-03:22 | 11497.95 | 0.00 |
August | 0.00 | 0.00 | 0.626716E+11 | 0.295612E+11 | 31066.25 | 25-AUG-10:52 | 10169.19 | 0.00 |
September | 0.00 | 0.00 | 0.580421E+11 | 0.278528E+11 | 31066.25 | 09-SEP-08:62 | 12528.91 | 0.00 |
October | 0.00 | 0.00 | 0.514105E+11 | 0.251519E+11 | 31066.25 | 04-OCT-05:40 | 8892.63 | 0.00 |
November | 0.00 | 0.00 | 0.366604E+11 | 0.177068E+11 | 31066.25 | 03-NOV-19:40 | 11356.77 | 0.00 |
December | 0.00 | 0.00 | 0.228478E+11 | 0.112425E+11 | 31066.25 | 24-DEC-13:35 | 13457.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.493559E+12 | 0.246980E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.171282E+11 | 0.938500E+10 | 31066.25 | 8892.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.626716E+11 | 0.303298E+11 | 31066.25 | 15724.09 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 3816.04 | 13889.54 | 18-JAN-13:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 3781.04 | 13853.32 | 01-FEB-13:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3683.77 | 13580.14 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:02 | 3515.94 | 13037.48 | 01-APR-12:40 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 3360.86 | 12410.19 | 01-MAY-12:20 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 3239.95 | 11831.05 | 01-JUN-12:50 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 3176.96 | 11488.27 | 01-JUL-12:27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 3223.63 | 11742.41 | 31-AUG-12:50 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 3324.20 | 12268.16 | 30-SEP-12:45 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 3482.42 | 12916.34 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 3647.89 | 13476.31 | 30-NOV-14:00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 3761.00 | 13830.22 | 31-DEC-13:23 |
Annual Sum or Average | 0.00 | 3499.60 | ||||
Minimum of Months | 0.00 | 0.00 | 3176.96 | 11488.27 | ||
Maximum of Months | 0.00 | 0.00 | 3816.04 | 13889.54 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | -0.0 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:02 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:03 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:03 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:02 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.125314E+10 | 0.24 | 503.64 | 01-JAN-00:10 | 0.26 |
February | 0.113487E+10 | 0.24 | 503.64 | 01-FEB-00:10 | 0.26 |
March | 0.126566E+10 | 0.25 | 503.64 | 01-MAR-00:10 | 0.26 |
April | 0.124403E+10 | 0.25 | 503.64 | 01-APR-00:17 | 0.26 |
May | 0.128889E+10 | 0.25 | 503.64 | 01-MAY-00:18 | 0.26 |
June | 0.124619E+10 | 0.25 | 503.64 | 01-JUN-00:08 | 0.26 |
July | 0.128762E+10 | 0.25 | 503.64 | 01-JUL-00:08 | 0.26 |
August | 0.128824E+10 | 0.25 | 503.64 | 01-AUG-00:08 | 0.26 |
September | 0.124666E+10 | 0.25 | 503.64 | 01-SEP-00:08 | 0.26 |
October | 0.128854E+10 | 0.25 | 503.64 | 01-OCT-00:06 | 0.26 |
November | 0.123860E+10 | 0.25 | 503.64 | 01-NOV-00:13 | 0.26 |
December | 0.126138E+10 | 0.25 | 503.64 | 01-DEC-00:01 | 0.26 |
Annual Sum or Average | 0.150438E+11 | 0.25 | |||
Minimum of Months | 0.113487E+10 | 0.24 | 503.64 | 0.26 | |
Maximum of Months | 0.128889E+10 | 0.25 | 503.64 | 0.26 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.191140E+10 | 0.46 | 2119.57 | 07-JAN-03:01 | 0.87 |
February | 0.173053E+10 | 0.47 | 2095.26 | 11-FEB-03:01 | 0.86 |
March | 0.191825E+10 | 0.47 | 2119.57 | 10-MAR-03:01 | 0.87 |
April | 0.186267E+10 | 0.47 | 2119.57 | 12-APR-02:61 | 0.87 |
May | 0.198133E+10 | 0.48 | 2119.57 | 03-MAY-02:61 | 0.87 |
June | 0.205078E+10 | 0.49 | 2119.57 | 01-JUN-02:61 | 0.86 |
July | 0.220288E+10 | 0.50 | 2119.57 | 01-JUL-02:61 | 0.87 |
August | 0.218808E+10 | 0.50 | 2119.57 | 01-AUG-02:61 | 0.86 |
September | 0.207785E+10 | 0.50 | 2119.57 | 01-SEP-02:61 | 0.87 |
October | 0.202045E+10 | 0.48 | 2119.57 | 01-OCT-02:61 | 0.87 |
November | 0.188196E+10 | 0.47 | 2119.57 | 03-NOV-02:61 | 0.87 |
December | 0.192023E+10 | 0.47 | 2119.57 | 01-DEC-03:01 | 0.87 |
Annual Sum or Average | 0.237464E+11 | 0.48 | |||
Minimum of Months | 0.173053E+10 | 0.46 | 2095.26 | 0.86 | |
Maximum of Months | 0.220288E+10 | 0.50 | 2119.57 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.125633E+10 | 0.53 | 1263.64 | 01-JAN-03:01 | 0.90 |
February | 0.115974E+10 | 0.54 | 1263.64 | 01-FEB-03:01 | 0.91 |
March | 0.134883E+10 | 0.55 | 1263.64 | 01-MAR-03:01 | 0.91 |
April | 0.142201E+10 | 0.59 | 1263.64 | 01-APR-02:11 | 0.90 |
May | 0.194286E+10 | 0.67 | 1263.64 | 01-MAY-02:11 | 0.90 |
June | 0.235180E+10 | 0.74 | 1263.64 | 01-JUN-02:61 | 0.90 |
July | 0.251910E+10 | 0.76 | 1263.64 | 01-JUL-02:61 | 0.90 |
August | 0.254720E+10 | 0.76 | 1263.64 | 01-AUG-02:61 | 0.89 |
September | 0.234722E+10 | 0.74 | 1263.64 | 01-SEP-02:61 | 0.90 |
October | 0.207618E+10 | 0.69 | 1263.64 | 01-OCT-02:61 | 0.89 |
November | 0.165490E+10 | 0.62 | 1263.64 | 01-NOV-02:11 | 0.90 |
December | 0.137517E+10 | 0.56 | 1263.64 | 01-DEC-03:11 | 0.90 |
Annual Sum or Average | 0.220013E+11 | 0.65 | |||
Minimum of Months | 0.115974E+10 | 0.53 | 1263.64 | 0.89 | |
Maximum of Months | 0.254720E+10 | 0.76 | 1263.64 | 0.91 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 53.10 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 53.80 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:05 | 0.00 | 0.00 | 53.46 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 53.82 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 53.36 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 54.13 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:10 | 0.00 | 0.00 | 54.48 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 54.34 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 54.76 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 53.81 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 54.19 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 53.49 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 53.10 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 54.76 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 44.31 | 44.31 | 3816.04 | 13889.54 | 18-JAN-13:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 53.99 | 53.99 | 3781.04 | 13853.32 | 01-FEB-13:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 53.74 | 53.74 | 3683.77 | 13580.14 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:02 | 54.25 | 54.25 | 3515.94 | 13037.48 | 01-APR-12:40 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 45.90 | 45.90 | 3360.86 | 12410.19 | 01-MAY-12:20 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 54.13 | 54.13 | 3239.95 | 11831.05 | 01-JUN-12:50 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 54.42 | 54.42 | 3176.96 | 11488.27 | 01-JUL-12:27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 54.60 | 54.60 | 3223.63 | 11742.41 | 31-AUG-12:50 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 54.93 | 54.93 | 3324.20 | 12268.16 | 30-SEP-12:45 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 46.04 | 46.04 | 3482.42 | 12916.34 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 54.25 | 54.25 | 3647.89 | 13476.31 | 30-NOV-14:00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 53.55 | 53.55 | 3761.00 | 13830.22 | 31-DEC-13:23 |
Annual Sum or Average | 0.00 | 3499.60 | ||||||
Minimum of Months | 0.00 | 0.00 | 44.31 | 44.31 | 3176.96 | 11488.27 | ||
Maximum of Months | 0.00 | 0.00 | 54.93 | 54.93 | 3816.04 | 13889.54 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.506983E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.559602E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.681430E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.839332E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.114824E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.131090E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.144035E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.142963E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.133020E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.120315E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.892922E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.602762E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.119455E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.506983E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.144035E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.520111E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.558272E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.697867E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.850970E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.124087E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.148513E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.158923E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.160354E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.148308E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.131399E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.964427E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.651661E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.129591E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.520111E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.160354E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.191140E+10 | 0.124170E+11 | 0.317353E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173053E+10 | 0.152225E+11 | 0.393951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191825E+10 | 0.196149E+11 | 0.321623E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186267E+10 | 0.265668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198133E+10 | 0.406416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.205078E+10 | 0.487571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220288E+10 | 0.535022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.218808E+10 | 0.534482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.207785E+10 | 0.493406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202045E+10 | 0.433046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188196E+10 | 0.298500E+11 | 59833779.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192023E+10 | 0.166141E+11 | 0.422155E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237464E+11 | 0.409280E+12 | 0.151492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.173053E+10 | 0.124170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220288E+10 | 0.535022E+11 | 0.422155E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.125633E+10 | 0.171282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115974E+10 | 0.193381E+11 | 14188200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134883E+10 | 0.250165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142201E+10 | 0.318246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.194286E+10 | 0.485387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.235180E+10 | 0.583213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.251910E+10 | 0.617596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.254720E+10 | 0.626716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.234722E+10 | 0.580421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.207618E+10 | 0.514105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165490E+10 | 0.366604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137517E+10 | 0.228478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220013E+11 | 0.493559E+12 | 14188200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.115974E+10 | 0.171282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.254720E+10 | 0.626716E+11 | 14188200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.191140E+10 | 0.00 | 0.00 | 0.00 | 0.315842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173053E+10 | 0.00 | 0.00 | 0.00 | 0.386549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191825E+10 | 0.00 | 0.00 | 0.00 | 0.489604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186267E+10 | 0.00 | 0.00 | 0.00 | 0.653064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198133E+10 | 0.00 | 0.00 | 0.00 | 0.950111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.205078E+10 | 0.00 | 0.00 | 0.00 | 0.110583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220288E+10 | 0.00 | 0.00 | 0.00 | 0.122006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.218808E+10 | 0.00 | 0.00 | 0.00 | 0.121082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.207785E+10 | 0.00 | 0.00 | 0.00 | 0.112242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202045E+10 | 0.00 | 0.00 | 0.00 | 0.100111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188196E+10 | 0.00 | 0.00 | 0.00 | 0.704726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192023E+10 | 0.00 | 0.00 | 0.00 | 0.410739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237464E+11 | 0.00 | 0.00 | 0.00 | 0.957087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.173053E+10 | 0.00 | 0.00 | 0.00 | 0.315842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220288E+10 | 0.00 | 0.00 | 0.00 | 0.122006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.125633E+10 | 0.00 | 0.00 | 0.00 | 0.394479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115974E+10 | 0.00 | 0.00 | 0.00 | 0.442297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134883E+10 | 0.00 | 0.00 | 0.00 | 0.562984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142201E+10 | 0.00 | 0.00 | 0.00 | 0.708769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.194286E+10 | 0.00 | 0.00 | 0.00 | 0.104658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.235180E+10 | 0.00 | 0.00 | 0.00 | 0.124995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.251910E+10 | 0.00 | 0.00 | 0.00 | 0.133732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.254720E+10 | 0.00 | 0.00 | 0.00 | 0.134882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.234722E+10 | 0.00 | 0.00 | 0.00 | 0.124836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.207618E+10 | 0.00 | 0.00 | 0.00 | 0.110637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165490E+10 | 0.00 | 0.00 | 0.00 | 0.798937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137517E+10 | 0.00 | 0.00 | 0.00 | 0.514145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220013E+11 | 0.00 | 0.00 | 0.00 | 0.107590E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.115974E+10 | 0.00 | 0.00 | 0.00 | 0.394479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.254720E+10 | 0.00 | 0.00 | 0.00 | 0.134882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.297928E+10 | 0.139234E+10 | 0.00 | 13303098.33 | 3717851.56 | 66620482.13 | 0.217523E+10 | 0.00 | 3.63 |
February | 0.158725E+10 | 0.164331E+10 | 0.00 | 13615835.59 | 2847193.78 | 0.238033E+09 | 0.135601E+10 | 0.00 | 3.63 |
March | 0.151964E+10 | 0.273283E+10 | 0.00 | 11287001.98 | 7988482.39 | 0.170986E+09 | 0.119197E+10 | 0.00 | 3.65 |
April | 0.233511E+09 | 0.445246E+10 | 0.00 | 7792452.50 | 19064058.05 | 0.00 | 0.505379E+09 | 0.00 | 3.67 |
May | 19861159.87 | 0.104792E+11 | 0.00 | 1010843.34 | 0.112252E+09 | 0.00 | 19060943.78 | 0.00 | 3.74 |
June | 3210170.45 | 0.148000E+11 | 0.00 | 496071.72 | 0.248668E+09 | 0.00 | 631257.85 | 0.00 | 3.80 |
July | 8187760.12 | 0.167400E+11 | 0.00 | 543376.87 | 0.230867E+09 | 0.00 | 463387.82 | 0.00 | 3.79 |
August | 1809664.65 | 0.166792E+11 | 0.00 | 459491.36 | 0.261598E+09 | 0.00 | 336189.91 | 0.00 | 3.81 |
September | 3890853.30 | 0.147611E+11 | 0.00 | 601510.43 | 0.214444E+09 | 0.00 | 1005135.81 | 0.00 | 3.80 |
October | 19020097.65 | 0.115725E+11 | 0.00 | 989760.44 | 0.136671E+09 | 0.00 | 3999948.53 | 0.00 | 3.78 |
November | 0.647045E+09 | 0.642961E+10 | 0.00 | 7344121.10 | 59577317.79 | 7179955.38 | 0.810278E+09 | 0.00 | 3.71 |
December | 0.218394E+10 | 0.260505E+10 | 0.00 | 10615561.50 | 13089366.18 | 0.167236E+09 | 0.194938E+10 | 0.00 | 3.65 |
Annual Sum or Average | 0.920664E+10 | 0.104288E+12 | 0.00 | 68059125.15 | 0.131078E+10 | 0.650056E+09 | 0.801375E+10 | 0.00 | 3.72 |
Minimum of Months | 1809664.65 | 0.139234E+10 | 0.00 | 459491.36 | 2847193.78 | 0.00 | 336189.91 | 0.00 | 3.63 |
Maximum of Months | 0.297928E+10 | 0.167400E+11 | 0.00 | 13615835.59 | 0.261598E+09 | 0.238033E+09 | 0.217523E+10 | 0.00 | 3.81 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.327953E+10 | 0.144363E+10 | 0.00 | 51541056.44 | 3026071.83 | 0.00 | 0.126917E+11 | 0.00 | 6.93 |
February | 0.237036E+10 | 0.161756E+10 | 0.00 | 49616608.63 | 2937631.25 | 0.00 | 0.859449E+10 | 0.00 | 6.98 |
March | 0.256341E+10 | 0.323081E+10 | 0.00 | 47311690.46 | 9960174.22 | 0.00 | 0.758827E+10 | 0.00 | 7.14 |
April | 0.459144E+09 | 0.442089E+10 | 0.00 | 46117785.80 | 12920764.75 | 0.00 | 0.359390E+10 | 0.00 | 7.43 |
May | 0.153813E+09 | 0.156657E+11 | 0.00 | 5243199.44 | 61879584.09 | 0.00 | 0.312364E+09 | 0.00 | 8.50 |
June | 30380624.38 | 0.254838E+11 | 0.00 | 762245.36 | 96432085.22 | 0.00 | 84126123.86 | 0.00 | 9.58 |
July | 53531245.94 | 0.274487E+11 | 0.00 | 1091060.92 | 93837348.06 | 0.00 | 0.111024E+09 | 0.00 | 9.75 |
August | 28676517.27 | 0.284070E+11 | 0.00 | 706213.66 | 98910070.83 | 0.00 | 86356954.81 | 0.00 | 9.84 |
September | 70704794.11 | 0.249626E+11 | 0.00 | 1122162.43 | 79242033.02 | 0.00 | 72633149.74 | 0.00 | 9.58 |
October | 0.133974E+09 | 0.181644E+11 | 0.00 | 8057270.19 | 69201894.29 | 0.00 | 0.337980E+09 | 0.00 | 8.82 |
November | 0.106189E+10 | 0.102873E+11 | 0.00 | 24433931.88 | 34222445.38 | 0.00 | 0.419038E+10 | 0.00 | 7.96 |
December | 0.261048E+10 | 0.389299E+10 | 0.00 | 46247156.21 | 15162278.76 | 0.00 | 0.103612E+11 | 0.00 | 7.20 |
Annual Sum or Average | 0.128159E+11 | 0.165025E+12 | 0.00 | 0.282250E+09 | 0.577732E+09 | 0.00 | 0.480244E+11 | 0.00 | 8.32 |
Minimum of Months | 28676517.27 | 0.144363E+10 | 0.00 | 706213.66 | 2937631.25 | 0.00 | 72633149.74 | 0.00 | 6.93 |
Maximum of Months | 0.327953E+10 | 0.284070E+11 | 0.00 | 51541056.44 | 98910070.83 | 0.00 | 0.126917E+11 | 0.00 | 9.84 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:21
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.354409E+11 | 0.394913E+10 | 0.389621E+11 | 0.156816E+10 | 0.563992E+11 |
February | 0.397934E+11 | 0.191375E+10 | 0.252042E+11 | 0.113246E+10 | 0.611902E+11 |
March | 0.558779E+11 | 0.115175E+10 | 0.189213E+11 | 0.957786E+09 | 0.761604E+11 |
April | 0.624541E+11 | -0.254554E+10 | -164732424.6 | 0.387774E+09 | 0.942555E+11 |
May | 0.614179E+11 | -0.879540E+10 | -0.340660E+11 | -3539255.6 | 0.131706E+12 |
June | 0.554476E+11 | -0.127619E+11 | -0.529553E+11 | -431047692.7 | 0.153442E+12 |
July | 0.606222E+11 | -0.143328E+11 | -0.568674E+11 | -375443744.0 | 0.165727E+12 |
August | 0.632289E+11 | -0.144323E+11 | -0.583984E+11 | -480526266.8 | 0.166247E+12 |
September | 0.486989E+11 | -0.129686E+11 | -0.517351E+11 | -319056794.1 | 0.153709E+12 |
October | 0.464689E+11 | -0.101725E+11 | -0.380441E+11 | -120514076.4 | 0.138505E+12 |
November | 0.339409E+11 | -0.476226E+10 | -0.800842E+10 | 0.610019E+09 | 0.100556E+12 |
December | 0.342103E+11 | 0.217266E+10 | 0.257619E+11 | 0.123042E+10 | 0.681419E+11 |
Annual Sum or Average | 0.597602E+12 | -0.715840E+11 | -0.191390E+12 | 0.415650E+10 | 0.136604E+13 |
Minimum of Months | 0.339409E+11 | -0.144323E+11 | -0.583984E+11 | -480526266.8 | 0.563992E+11 |
Maximum of Months | 0.632289E+11 | 0.394913E+10 | 0.389621E+11 | 0.156816E+10 | 0.166247E+12 |