Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 08:27:18
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1272.63 | 5477.38 | 5477.38 |
Net Site Energy | 1272.63 | 5477.38 | 5477.38 |
Total Source Energy | 2691.76 | 11585.28 | 11585.28 |
Net Source Energy | 2691.76 | 11585.28 | 11585.28 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 9.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 227.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 21.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 252.09 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 72.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 156.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 40.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 629.97 | 642.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 9.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 227.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 21.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 72.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 156.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 12.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 19.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 9.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 227.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 21.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 15.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 252.09 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 72.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 156.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 40.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 161.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1291.92 | 712.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1257.89 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2711.38 | 2766.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 161.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1291.92 | 712.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1257.89 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2711.38 | 2766.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 629.969 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 629.969 | 100.00 |
Total On-Site and Utility Electric Sources | 629.969 | 100.00 |
Total Electricity End Uses | 629.969 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1680.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5984.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 4.6627 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.9536 | 18.52 | 1067.3199 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 7.3082 | 2.48 | 592.0534 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 7.3082 | 2.48 | 592.0534 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 4.6627 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.9536 | 18.52 | 1067.3199 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 7.3082 | 1.24 | 592.0534 | |||||||
Conditioned Total | 232.34 | 7.3082 | 1.24 | 592.0534 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 7.3082 | 2.48 | 592.0534 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUN-17:10 | 02-JAN-11:30 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 2341.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25309.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1008.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 11387.73 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4409.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 20217.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1251.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 43367.30 | 49219.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 2341.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 25309.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1008.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 10796.93 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 4409.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 20217.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 420.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 10.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 720.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 69.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 49.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 798.38 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 230.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 169.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 127.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1995.11 | 696.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 44.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3100.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 299.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 212.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3436.21 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 991.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 727.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 547.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8586.93 | 2998.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 44.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3100.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 299.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 212.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3436.21 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 991.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 727.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 547.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8586.93 | 2998.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 2.89 |
KITCHEN DIRECT AIR | 1.22 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.89 | 2.89 | 2.89 | 2.89 | 2.89 | 2.89 | 1.00 | 1.00 | 2.89 |
PSZ-AC_2:2 | 1.22 | 1.22 | 1.22 | 1.22 | 1.22 | 1.22 | 1.00 | 1.00 | 1.22 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.89 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.22 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 2.89 | 3097.42 |
PSZ-AC_2:2_ADDAQ FAN | 1.22 | 1351.29 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.89 | 2.89 | 2.89 | 1.91 | 68244.17 | 71762.43 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.22 | 1.22 | 1.22 | 0.805534 | 30308.09 | 49101.95 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.89 | 1.45 | 1.93 | 68244.17 | 34122.08 | 0.717150 | 0.717150 |
PSZ-AC_2:2 COOLING COIL | 1.22 | 0.610253 | 0.813673 | 30308.09 | 15154.05 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 71762.43 |
PSZ-AC_2:2 HEATING COIL | 49101.95 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 4.663 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 121.450 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.954 | 275.967 | 791.353 | 0.000 | 0.000 | 0.000 | 1077.273 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 541.679 | 4.663 | 6.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 541.679 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1156.323 | 9.954 | 184.325 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1156.323 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 277.500 | 2.389 | 44.235 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 313.300 | 2.697 | 49.942 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.6929 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.209 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.33002231E-12 | 0.10712597E-14 | -0.10720425E-12 | 0.10137879E-15 |
34 | 6 | 0.29661659E-07 | 0.19687232E-09 | 0.67865745E-08 | -0.14052424E-12 |
35 | 5 | -0.19512200E-03 | 0.16741682E-05 | -0.10029371E-03 | 0.67057946E-08 |
36 | 4 | 0.29799499 | 0.81016957E-03 | 0.10178761 | -0.34398158E-04 |
37 | 3 | -7.3821031 | 0.24971312E-01 | -2.3732702 | 0.29576512E-01 |
38 | 2 | 41.252923 | 0.88368331E-01 | 15.405914 | -0.33759269 |
39 | 1 | -80.838295 | 0.39713828E-01 | -29.267905 | 1.0848528 |
40 | 0 | 46.824337 | 0.79570062E-03 | 16.288235 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.23 | 38 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 | ||
2 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.23 | 39 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 | ||
3 | NONRESWINDOW_U_0.503_SHGC_EAST_0.23 | 40 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 | ||
4 | NONRESWINDOW_U_0.503_SHGC_WEST_0.23 | 41 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.053 | 0.3093 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5320E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.1901E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.4027E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0695E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.2728E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.2194E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.0078E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0016E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.4811E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.3846E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.8212E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.7076E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.6945E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.6355E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.0845E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.0846E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.8065E-003 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3087E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 8.2367E-003 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.1307E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.5142E-003 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0397E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0017E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0078E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 31916.23723 | 38299.48468 | 2.41222 | 2.89466 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 42.00000 | 9.15790E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 2272.56212 | 2727.07455 | 9.74676E-002 | 0.41606 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 6.30000 | 6.07234E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16159.64312 | 19391.57174 | 1.01709 | 1.22051 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 41.12700 | 9.15644E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.14133 | 00:10:00 | 6.30000 | 6.07234E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 46705.36 | 2.89466 | 2.89466 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 16537.72 | 0.41606 | 0.41606 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 39371.17 | 1.22051 | 1.22051 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 45366.59 | 1.14133 | 1.14133 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.89466 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.22051 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.89466 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.89466 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.89466 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.89466 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.89466 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.89466 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.22051 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.22051 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.22051 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.22051 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.22051 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.22051 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.89466 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.22051 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.89466 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.89466 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 3097.42203 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.89466 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.89466 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.89466 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.91047 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.89466 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.44733 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.92977 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 68244.17000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 34122.08500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71715 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71715 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 68244.17000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 71762.43287 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 71762.43287 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.22051 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.22051 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1351.29476 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.22051 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.22051 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.22051 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80553 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.22051 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61025 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.81367 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30308.09000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15154.04500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30308.09000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 49101.94928 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 49101.94928 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 66177.6 | 11.57 | 11.52 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 29440.6 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_EAST_0.23 | N/A | 2.860 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.23 | N/A | 2.860 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_WEST_0.23 | N/A | 2.860 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 6.4941714574E-002 | 0.2049826552 | Pass | Pass | 0.2260042513 | 0.8966297419 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2321856630 | 0.6033602257 | Pass | Pass | 6.2248609524E-002 | 0.2433332806 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4236118146 | 0.4112802860 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 516.61 | -73.0 | -60.3 | 8.99 | 1402.48 | 1794.69 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.503_SHGC_EAST_0.23 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.860 | 0.231 | 0.254 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.23 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.860 | 0.231 | 0.254 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.503_SHGC_WEST_0.23 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.860 | 0.231 | 0.254 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.860 | 0.231 | 0.254 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.860 | 0.231 | 0.254 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 4.6627 | 116.17 | 541.68 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 43.78 | 0.0000 | Y | 4.45 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.9536 | 116.17 | 1156.32 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 80.60 | 0.0000 | Y | 17.50 |
Interior Lighting Total | 7.3082 | 232.34 | 1698.00 | 21.95 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 541.68 | 205.84 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 541.68 | 205.84 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 218.22 | AstronomicalClock | - | 48.75 | 48.75 | 2.00 | |
EXTERIOR_LIGHTS_B | 1154.09 | AstronomicalClock | - | 83.75 | 62.75 | 13.59 | |
Exterior Lighting Total | 1372.31 | 15.59 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 68244.17 | 48941.31 | 19302.86 | 0.72 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30308.09 | 21248.40 | 9059.69 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 66177.6 | 11.57 | 11.52 | ||||
PSZ-AC_2:2 COOLING COIL | 29440.6 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 71762.43 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 49101.95 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 2.89 | 3097.42 | 1070.05 | 1.00 | 1.27 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.22 | 1351.29 | 1107.16 | 1.00 | 1.36 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 31916.24 | 38299.48 | 329.68 | 2.412 | 2.895 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 23.89 | 23.88 | 0.00811 | 42.00 | 0.00916 | 0.416 | 0.00 |
KITCHEN | 16159.64 | 19391.57 | 166.92 | 1.017 | 1.221 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 26.11 | 26.10 | 0.00872 | 41.13 | 0.00916 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 2272.56 | 2727.07 | 23.47 | 0.097 | 0.416 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00791 | 6.30 | 0.00607 | 0.416 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.141 | 00:10:00 | 15.56 | 25.12 | 0.00331 | 6.30 | 0.00607 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.89 | 2.89 | 0.42 | 0.42 | 2.8947 | 2.8947 | 2.8947 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.22 | 1.22 | 1.14 | 1.14 | 1.2205 | 1.2205 | 1.2205 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 68244.170 | 48941.307 | 2.894660 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 34122.08 | 29068.21 | 1.929773 | 26.48 | 16.79 | 0.00825772 | 11.91 | 9.95 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 21.5598 | 23.88 | 0.00810661 | 42.8808 | 31916.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 71762.433 | 71762.433 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 71762.43 | 71762.43 | 2.894659 | 18.98 | 13.55 | 0.00768563 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.3732 | 20.76 | 0.00795644 | 50.9018 | 1228.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 30308.090 | 21248.396 | 1.220510 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 15154.05 | 12959.12 | 0.813673 | 40.15 | 21.72 | 0.00912812 | 11.88 | 9.94 | 0.00700000 | 41.13 | 0.00915644 | 22.02 | 140.2693 | 26.10 | 0.00871997 | 40.3658 | 16159.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 49101.949 | 49101.949 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 49101.95 | 49101.95 | 1.220507 | 5.89 | 5.88 | 0.00589317 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 93.5131 | 25.12 | 0.00331028 | 16.3817 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 68244.170 | 48941.307 | 2.894660 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1907 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.894659 | 3.39770872 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | Sensible | 34122.08 | 29068.21 | 1.0000 | 2.26513988 | 1.929773 | 26.48 | 16.79 | 0.00825772 | 47666.4 | 11.91 | 9.95 | 0.00700000 | 29625.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34122.08 | 42.00 | 0.00915790 | 22.26 | 0.41605618 | 21.5598 | 23.87 | 0.00810661 | 23.88 | 0.00810661 | 42.8808 | 31916.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 71762.433 | 71762.433 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.894659 | 3.39770872 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 71762.43 | 71762.43 | 1.0000 | 3.39770872 | 2.894659 | 18.98 | 13.55 | 0.00768563 | 38565.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 71762.43 | 6.30 | 0.00607234 | 6.30 | 0.41605618 | 14.3732 | 21.11 | 0.00795644 | 20.76 | 0.00795644 | 50.9018 | 1228.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30308.090 | 21248.396 | 1.220510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8087 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.220507 | 1.43261313 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | Sensible | 15154.05 | 12959.12 | 1.0000 | 0.95507793 | 0.813673 | 40.15 | 21.72 | 0.00912812 | 63853.7 | 11.88 | 9.94 | 0.00700000 | 29595.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15154.05 | 41.13 | 0.00915644 | 22.02 | 1.14133354 | 140.2693 | 26.05 | 0.00871997 | 26.10 | 0.00871997 | 40.3658 | 16159.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 49101.949 | 49101.949 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.220507 | 1.43261313 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 49101.95 | 49101.95 | 1.0000 | 1.43261313 | 1.220507 | 5.89 | 5.88 | 0.00589317 | 20722.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49101.95 | 6.30 | 0.00607234 | 6.30 | 1.14133354 | 93.5131 | 0.00 | 0.00331028 | 25.12 | 0.00331028 | 16.3817 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 5631.33 | 3662.83 | 2480.33 |
KITCHEN | 6720.17 | 6346.67 | 5979.67 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 6724.67 | 7064.00 | 5984.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 121.00 | 0.00 | 2.83 |
KITCHEN | 0.00 | 2057.50 | 0.00 | 1677.33 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 2087.00 | 0.00 | 1680.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.362 | 4.109 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 9.970 | 0.012 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 3.982 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 7.760 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 11257645.97 | 0.00 | 11257645.97 | 10163608.31 | 21421254.28 | 13120747.55 | 1343.70 | 7412.33 | 3.97 | 479.96 |
KITCHEN | 26029218.02 | 0.00 | 26029218.02 | 41241.78 | 26070459.80 | 35993094.65 | 6284.42 | 2364.33 | 111.25 | 963.75 |
Total Facility | 37286863.98 | 0.00 | 37286863.98 | 10204850.09 | 47491714.07 | 49113842.20 | 6319.24 | 7413.91 | 114.06 | 1003.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4161 | 0.0000 | 0.4161 | 0.3923 | 0.8084 | 0.4161 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 0.9394 | 0.0000 | 0.9394 | 0.0011 | 0.9406 | 1.1413 | 4847.49 | 2339.51 | 0.00 |
Total Facility | 1.3555 | 0.0000 | 1.3555 | 0.3935 | 1.7490 | 1.5574 | 4847.49 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 15510477.93 | 0.00 | 15510477.93 | 13120747.55 | 1302.38 | 5.00 | 7452.62 | 479.85 |
PSZ-AC_2:2 | 35861659.37 | 0.00 | 35861659.37 | 35993094.65 | 5018.04 | 118.60 | 3623.37 | 963.75 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5733 | 0.0000 | 0.5733 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.2943 | 0.0000 | 1.2943 | 1.1413 | 3673.92 | 111.28 | 3401.80 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 248.37 | 0.00 | 7418.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 0.00 | 3831.80 | 4318.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 0.5733 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 1.4844 | 1.1684 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 386 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 629.97 | 3081.41 | 01-JAN-01:20 | 43367.30 | 22-JUN-17:10 |
Electricity:Building | 281.98 | 1673.38 | 01-JAN-01:20 | 17939.26 | 02-JAN-11:10 |
Electricity:Zone:DINING | 74.78 | 295.02 | 01-JAN-01:20 | 4037.01 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 274.04 | 1537.10 | 01-JAN-01:20 | 14645.21 | 02-JAN-11:10 |
InteriorLights:Electricity | 21.95 | 50.02 | 01-JAN-01:20 | 1346.16 | 02-JAN-17:40 |
InteriorLights:Electricity:Zone:DINING | 4.45 | 25.01 | 01-JAN-01:20 | 444.80 | 02-JAN-17:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 21.95 | 50.02 | 01-JAN-01:20 | 1346.16 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity | 21.95 | 50.02 | 01-JAN-01:20 | 1346.16 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 4.45 | 25.01 | 01-JAN-01:20 | 444.80 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 21.95 | 50.02 | 01-JAN-01:20 | 1346.16 | 02-JAN-17:40 |
Electricity:Zone:KITCHEN | 207.20 | 1378.36 | 01-JAN-01:20 | 13902.25 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.50 | 25.01 | 01-JAN-01:20 | 901.37 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.50 | 25.01 | 01-JAN-01:20 | 901.37 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 252.09 | 1487.08 | 01-JAN-01:10 | 13637.09 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 252.09 | 1487.08 | 01-JAN-01:10 | 13637.09 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 181.76 | 1217.07 | 01-JAN-01:10 | 9706.84 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 40.17 | 608.35 | 31-DEC-23:30 | 3931.14 | 17-APR-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 32.23 | 522.57 | 31-DEC-23:30 | 1662.88 | 18-JUL-04:10 |
LowTempRefrigeration:Refrigeration:Electricity | 12.71 | 0.00 | 01-JAN-11:10 | 1025.79 | 18-JUL-04:10 |
MedTempRefrigeration:Refrigeration:Electricity | 19.52 | 511.64 | 02-JAN-01:10 | 637.09 | 02-JAN-14:10 |
ElectricityPurchased:Facility | 629.97 | 3081.41 | 01-JAN-01:20 | 43367.30 | 22-JUN-17:10 |
ElectricityPurchased:Plant | 629.97 | 3081.41 | 01-JAN-01:20 | 43367.30 | 22-JUN-17:10 |
Cogeneration:ElectricityPurchased | 629.97 | 3081.41 | 01-JAN-01:20 | 43367.30 | 22-JUN-17:10 |
General:Cogeneration:ElectricityPurchased | 629.97 | 3081.41 | 01-JAN-01:20 | 43367.30 | 22-JUN-17:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 629.97 | 3081.41 | 01-JAN-01:20 | 43367.30 | 22-JUN-17:10 |
ElectricityNet:Plant | 629.97 | 3081.41 | 01-JAN-01:20 | 43367.30 | 22-JUN-17:10 |
Cogeneration:ElectricityNet | 629.97 | 3081.41 | 01-JAN-01:20 | 43367.30 | 22-JUN-17:10 |
General:Cogeneration:ElectricityNet | 629.97 | 3081.41 | 01-JAN-01:20 | 43367.30 | 22-JUN-17:10 |
Electricity:HVAC | 300.17 | 0.00 | 01-JAN-01:10 | 30380.95 | 10-JUN-18:10 |
Fans:Electricity | 72.73 | 0.00 | 01-JAN-01:10 | 4557.41 | 01-JUL-18:10 |
General:Fans:Electricity | 72.73 | 0.00 | 01-JAN-01:10 | 4557.41 | 01-JUL-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 227.43 | 0.00 | 01-JAN-00:10 | 26024.02 | 10-JUN-18:10 |
General:Cooling:Electricity | 227.43 | 0.00 | 01-JAN-00:10 | 26024.02 | 10-JUN-18:10 |
ExteriorLights:Electricity | 15.59 | 0.00 | 01-JAN-07:20 | 1372.31 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 15.59 | 0.00 | 01-JAN-07:20 | 1372.31 | 01-JAN-06:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 05-MAR-08:40 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 05-MAR-08:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 642.66 | 2558.65 | 21-JAN-03:10 | 49219.58 | 02-JAN-11:30 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 9.49 | 0.00 | 01-JAN-00:10 | 18648.85 | 03-JAN-07:10 |
Heating:NaturalGas | 9.49 | 0.00 | 01-JAN-00:10 | 18648.85 | 03-JAN-07:10 |
General:Heating:NaturalGas | 9.49 | 0.00 | 01-JAN-00:10 | 18648.85 | 03-JAN-07:10 |
NaturalGas:Plant | 156.02 | 720.00 | 03-JAN-05:20 | 24647.37 | 23-JAN-13:20 |
WaterSystems:NaturalGas | 156.02 | 720.00 | 03-JAN-05:20 | 24647.37 | 23-JAN-13:20 |
Water Heater:WaterSystems:NaturalGas | 156.02 | 720.00 | 03-JAN-05:20 | 24647.37 | 23-JAN-13:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1619.11 | 2964.00 | 02-JAN-01:10 | 132989.78 | 01-JUL-18:10 |
EnergyTransfer:Building | 537.44 | 1482.00 | 02-JAN-01:10 | 40585.92 | 12-JUN-11:10 |
EnergyTransfer:Zone:KITCHEN | 339.72 | 1482.00 | 02-JAN-01:10 | 19325.72 | 06-JAN-05:10 |
Refrigeration:EnergyTransfer | 159.78 | 2807.66 | 31-DEC-23:30 | 7834.84 | 14-APR-03:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 79.89 | 1403.83 | 31-DEC-23:30 | 3917.42 | 14-APR-03:30 |
General:Refrigeration:EnergyTransfer | 79.89 | 1403.83 | 31-DEC-23:30 | 3917.42 | 14-APR-03:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 79.89 | 1403.83 | 31-DEC-23:30 | 3917.42 | 14-APR-03:30 |
EnergyTransfer:Plant | 179.73 | 1403.83 | 31-DEC-23:30 | 17614.21 | 17-JAN-13:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 13.48 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 66.41 | 1324.14 | 02-JAN-01:10 | 2238.70 | 02-JAN-14:10 |
EnergyTransfer:Zone:DINING | 197.72 | 0.00 | 01-JAN-01:10 | 26981.18 | 07-JUN-17:10 |
Heating:EnergyTransfer | 2.01 | 0.00 | 01-JAN-00:10 | 5968.44 | 03-MAY-23:10 |
Heating:EnergyTransfer:Zone:DINING | 1.96 | 0.00 | 01-JAN-00:10 | 5566.87 | 31-DEC-07:10 |
General:Heating:EnergyTransfer | 2.01 | 0.00 | 01-JAN-00:10 | 5968.44 | 03-MAY-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 1.96 | 0.00 | 01-JAN-00:10 | 5566.87 | 31-DEC-07:10 |
Cooling:EnergyTransfer | 455.54 | 0.00 | 01-JAN-01:10 | 36671.63 | 10-JUN-18:10 |
Cooling:EnergyTransfer:Zone:DINING | 195.76 | 0.00 | 01-JAN-01:10 | 26981.18 | 07-JUN-17:10 |
General:Cooling:EnergyTransfer | 455.54 | 0.00 | 01-JAN-01:10 | 36671.63 | 10-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 195.76 | 0.00 | 01-JAN-01:10 | 26981.18 | 07-JUN-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.05 | 0.00 | 01-JAN-00:10 | 1576.74 | 03-MAY-23:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.05 | 0.00 | 01-JAN-00:10 | 1576.74 | 03-MAY-23:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 259.78 | 0.00 | 01-JAN-01:10 | 15521.08 | 06-JAN-05:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 259.78 | 0.00 | 01-JAN-01:10 | 15521.08 | 06-JAN-05:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 99.84 | 0.00 | 01-JAN-00:10 | 15061.37 | 17-JAN-13:20 |
PlantLoopHeatingDemand:Plant | 99.84 | 0.00 | 01-JAN-00:10 | 15061.37 | 17-JAN-13:20 |
WaterSystems:PlantLoopHeatingDemand | 99.84 | 0.00 | 01-JAN-00:10 | 15061.37 | 17-JAN-13:20 |
General:WaterSystems:PlantLoopHeatingDemand | 99.84 | 0.00 | 01-JAN-00:10 | 15061.37 | 17-JAN-13:20 |
EnergyTransfer:HVAC | 901.94 | 0.00 | 01-JAN-00:10 | 95507.10 | 01-JUL-18:20 |
HeatingCoils:EnergyTransfer | 7.59 | 0.00 | 01-JAN-00:10 | 14919.08 | 03-JAN-07:10 |
CoolingCoils:EnergyTransfer | 894.35 | 0.00 | 01-JAN-00:10 | 95507.10 | 01-JUL-18:20 |
WaterSystems:EnergyTransfer | 99.84 | 0.00 | 01-JAN-00:10 | 15061.37 | 17-JAN-13:20 |
WaterUse:WaterSystems:EnergyTransfer | 99.84 | 0.00 | 01-JAN-00:10 | 15061.37 | 17-JAN-13:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 1.961 | -195.757 | 0.000 | 0.000 | 66.302 | 4.451 | 52.748 | 23.665 | 0.000 | 57.373 | 19.622 | 0.000 | -5.533 | 0.000 | -24.832 | -0.000 |
KITCHEN | 0.000 | 0.000 | 0.053 | -259.779 | 0.000 | 0.000 | 3.836 | 17.495 | 187.472 | 0.000 | 0.000 | 0.126 | 50.950 | 0.000 | 0.000 | 0.000 | -0.152 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.612 | 9.885 | 0.000 | 0.000 | 0.000 | -15.497 | -0.000 |
Total Facility | 0.000 | 0.000 | 2.013 | -455.536 | 0.000 | 0.000 | 70.138 | 21.947 | 240.220 | 23.665 | 0.000 | 63.112 | 80.456 | 0.000 | -5.533 | 0.000 | -40.482 | -0.000 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 04-MAY-02:61 | 0.00 | 0.00 | 0.00 | -44716.96 | 0.00 | 0.00 | 0.00 | 25.01 | 202.51 | 330.64 | 0.00 | 60.09 | 44098.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 30-DEC-03:01 | 0.00 | 0.00 | 0.00 | -41962.31 | 0.00 | 0.00 | 0.00 | 25.01 | 1240.35 | 0.00 | 0.00 | 0.00 | 40848.41 | 0.00 | -0.00 | 0.00 | -151.46 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-MAY-02:61 | 0.00 | 0.00 | 0.00 | -69355.54 | 0.00 | 0.00 | 0.00 | 50.02 | 1442.86 | 40.71 | 0.00 | 473.94 | 67348.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 03-MAY-23:01 | 0.00 | 0.00 | 5705.15 | 0.00 | 0.00 | 0.00 | 306.62 | 74.13 | 304.93 | 513.11 | 0.00 | 50.82 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6954.77 |
KITCHEN | 03-MAY-23:01 | 0.00 | 0.00 | 8773.18 | 0.00 | 0.00 | 0.00 | 18.55 | 150.23 | 1566.76 | 0.00 | 0.00 | 38.04 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10546.76 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-MAY-23:01 | 0.00 | 0.00 | 14478.32 | 0.00 | 0.00 | 0.00 | 325.17 | 224.36 | 1871.70 | 513.11 | 0.00 | 466.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17878.83 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.8947 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.8947 | 0.1437 | 1.0000 | Not calculated | 0.4161 | 0.1437 | ||
PSZ-AC_2:2 | 1.2205 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2205 | 0.1239 | 1.0000 | Not calculated | 0.1513 | 0.1239 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.8947 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.8947 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.1437 | ||
PSZ-AC_2:2 | 1.2205 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2205 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1239 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8947 | 2.8947 | 2.8947 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2205 | 1.2205 | 1.2205 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.8947 | 2.8947 | 2.8947 | 2.8947 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2205 | 1.2205 | 1.2205 | 1.2205 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8947 | 2.8947 | 2.8947 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2205 | 1.2205 | 1.2205 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.8947 | 2.8947 | 2.8947 | 2.8947 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2205 | 1.2205 | 1.2205 | 1.2205 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1680.17 |
Number of hours not met | 1680.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 9.49 | 18648.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 227.43 | 26024.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 21.95 | 1346.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 15.59 | 1372.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 72.73 | 4557.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 156.02 | 24647.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 12.71 | 1025.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 19.52 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 292.26 | 629.97 |
Natural Gas | 477.16 | 642.66 |
Additional | 0.00 | 0.00 |
Total | 769.42 | 1272.63 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 94.46 |
Space Heating | 0.00 |
Space Cooling | 978.88 |
Fans (All) | 313.04 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1085.00 |
Miscellaneous (All) | 2711.38 |
Subtotal | 2711.38 |
Natural Gas [MJ/m2] | |
Space Heating | 40.84 |
Service Water Heating | 671.49 |
Miscellaneous (All) | 2766.01 |
Subtotal | 2766.01 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.72 |
Space Heating | 0.75 |
Space Cooling | 17.87 |
Fans (All) | 5.72 |
Service Water Heating | 12.26 |
Receptacle Equipment | 57.30 |
Miscellaneous | 4.38 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8233.17 | 410.83 | 116.00 | 0.00 | 0.00 |
KITCHEN | 5705.83 | 2307.33 | 746.83 | 0.00 | 0.00 |
ATTIC | 4261.33 | 1055.50 | 1070.33 | 1132.00 | 1240.83 |
Min | 4261.33 | 410.83 | 116.00 | 0.00 | 0.00 |
Max | 8233.17 | 2307.33 | 1070.33 | 1132.00 | 1240.83 |
Average | 6066.78 | 1257.89 | 644.39 | 377.33 | 413.61 |
Sum | 18200.33 | 3773.67 | 1933.17 | 1132.00 | 1240.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254083.00 | 486.00 | 156.00 | 0.00 | 0.00 |
KITCHEN | 11341.83 | 3659.17 | 1257.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254083.00 | 3659.17 | 1257.00 | 0.00 | 0.00 |
Average | 88474.94 | 1381.72 | 471.00 | 0.00 | 0.00 |
Sum | 265424.83 | 4145.17 | 1413.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 5701.33 | 2980.50 | 78.17 | 0.00 | 0.00 |
KITCHEN | 2661.50 | 5756.83 | 341.67 | 0.00 | 0.00 |
ATTIC | 3481.67 | 2238.67 | 862.17 | 509.67 | 1667.83 |
Min | 2661.50 | 2238.67 | 78.17 | 0.00 | 0.00 |
Max | 5701.33 | 5756.83 | 862.17 | 509.67 | 1667.83 |
Average | 3948.17 | 3658.67 | 427.33 | 169.89 | 555.94 |
Sum | 11844.50 | 10976.00 | 1282.00 | 509.67 | 1667.83 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 174852.83 | 79785.50 | 86.67 | 0.00 | 0.00 |
KITCHEN | 4437.17 | 11280.50 | 540.33 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 174852.83 | 79785.50 | 540.33 | 0.00 | 0.00 |
Average | 59763.33 | 30355.33 | 209.00 | 0.00 | 0.00 |
Sum | 179290.00 | 91066.00 | 627.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:18
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405797E+10 | 10711.15 | 15-JAN-03:01 | 15.85 | 13.69 | 0.487302E+10 | 4681.12 | 14-JAN-19:00 | 15.85 | 13.69 |
February | 0.627439E+10 | 14678.51 | 23-FEB-03:01 | 15.28 | 13.33 | 0.465816E+10 | 4681.01 | 25-FEB-19:00 | 18.60 | 16.34 |
March | 0.125868E+11 | 24427.98 | 12-MAR-02:61 | 22.18 | 17.57 | 0.542537E+10 | 4681.40 | 25-MAR-18:19 | 23.53 | 13.98 |
April | 0.202933E+11 | 39405.18 | 28-APR-02:61 | 29.83 | 17.14 | 0.526146E+10 | 4681.41 | 01-APR-18:10 | 29.83 | 17.14 |
May | 0.257188E+11 | 44722.74 | 04-MAY-02:61 | 35.35 | 20.47 | 0.544796E+10 | 4681.37 | 13-MAY-18:10 | 32.37 | 22.77 |
June | 0.258220E+11 | 40295.41 | 05-JUN-02:61 | 31.48 | 20.26 | 0.529774E+10 | 4681.64 | 24-JUN-18:00 | 27.40 | 25.19 |
July | 0.241944E+11 | 29019.90 | 01-JUL-02:61 | 31.37 | 24.28 | 0.541722E+10 | 4681.17 | 01-JUL-18:10 | 36.60 | 28.74 |
August | 0.227555E+11 | 28896.59 | 03-AUG-02:61 | 29.53 | 23.75 | 0.547656E+10 | 4681.53 | 19-AUG-18:00 | 26.10 | 25.58 |
September | 0.204685E+11 | 31894.60 | 29-SEP-02:61 | 25.03 | 20.73 | 0.526277E+10 | 4681.10 | 02-SEP-18:19 | 25.03 | 20.73 |
October | 0.175165E+11 | 34182.35 | 23-OCT-02:61 | 20.48 | 16.58 | 0.540717E+10 | 4681.62 | 07-OCT-18:19 | 20.48 | 16.58 |
November | 0.107493E+11 | 23504.62 | 09-NOV-03:01 | 17.85 | 16.23 | 0.512514E+10 | 4681.11 | 25-NOV-19:10 | 17.82 | 11.99 |
December | 0.532157E+10 | 8393.95 | 28-DEC-14:00 | 24.60 | 15.30 | 0.495504E+10 | 4622.48 | 16-DEC-19:10 | 24.60 | 15.30 |
Annual Sum or Average | 0.195759E+12 | 0.626076E+11 | ||||||||
Minimum of Months | 0.405797E+10 | 8393.95 | 15.28 | 13.33 | 0.465816E+10 | 4622.48 | 15.85 | 11.99 | ||
Maximum of Months | 0.258220E+11 | 44722.74 | 35.35 | 24.28 | 0.547656E+10 | 4681.64 | 36.60 | 28.74 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205744E+11 | 40057.68 | 13-JAN-03:01 | 10.25 | 8.98 | 0.780586E+10 | 5135.96 | 13-JAN-11:00 | 19.00 | 14.37 |
February | 0.183244E+11 | 38612.82 | 20-FEB-03:01 | 11.80 | 10.13 | 0.707750E+10 | 5135.96 | 13-FEB-11:00 | 11.80 | 10.13 |
March | 0.206738E+11 | 37815.66 | 01-MAR-03:01 | 13.38 | 10.98 | 0.785943E+10 | 5135.96 | 22-MAR-10:30 | 21.70 | 15.26 |
April | 0.211496E+11 | 33290.21 | 11-APR-02:11 | 20.13 | 13.69 | 0.760708E+10 | 5138.87 | 17-APR-10:00 | 34.50 | 22.99 |
May | 0.228860E+11 | 27985.46 | 28-MAY-02:61 | 28.28 | 17.05 | 0.787533E+10 | 5175.75 | 22-MAY-10:50 | 28.28 | 17.05 |
June | 0.224252E+11 | 23204.91 | 05-JUN-02:61 | 31.48 | 20.26 | 0.765086E+10 | 5207.63 | 28-JUN-10:00 | 32.50 | 28.26 |
July | 0.228955E+11 | 19071.51 | 11-JUL-02:61 | 26.50 | 23.05 | 0.792318E+10 | 5214.51 | 17-JUL-10:50 | 34.45 | 27.92 |
August | 0.230056E+11 | 18025.16 | 16-AUG-02:61 | 24.23 | 23.73 | 0.793459E+10 | 5227.51 | 25-AUG-10:50 | 32.72 | 28.77 |
September | 0.227274E+11 | 22538.05 | 29-SEP-02:61 | 25.03 | 20.73 | 0.763454E+10 | 5199.72 | 12-SEP-10:00 | 25.03 | 20.73 |
October | 0.231779E+11 | 30749.41 | 31-OCT-02:61 | 17.02 | 15.21 | 0.785787E+10 | 5141.73 | 04-OCT-10:00 | 17.02 | 15.21 |
November | 0.209002E+11 | 39573.28 | 27-NOV-03:01 | 11.55 | 9.68 | 0.759551E+10 | 5135.96 | 28-NOV-11:30 | 20.05 | 14.53 |
December | 0.210436E+11 | 42016.09 | 30-DEC-03:01 | 11.97 | 8.54 | 0.781797E+10 | 5135.97 | 29-DEC-11:50 | 11.97 | 8.54 |
Annual Sum or Average | 0.259784E+12 | 0.926397E+11 | ||||||||
Minimum of Months | 0.183244E+11 | 18025.16 | 10.25 | 8.54 | 0.707750E+10 | 5135.96 | 11.80 | 8.54 | ||
Maximum of Months | 0.231779E+11 | 42016.09 | 31.48 | 23.73 | 0.793459E+10 | 5227.51 | 34.50 | 28.77 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 7.83 | 7.49 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.73 | 7.85 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.85 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.96 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.96 |
April | 0.00 | 0.00 | 01-APR-00:02 | 23.70 | 16.77 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.77 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 | 18.24 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.24 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 | 22.58 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.58 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 | 24.65 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.65 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 29.32 | 26.26 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 28.43 | 25.91 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 26.58 | 21.85 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.85 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.72 | 15.09 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.11 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.11 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.00 | 0.00 | 32.95 | 26.26 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.673281E+09 | 5549.47 | 21-JAN-07:10 | 5.63 |
February | 0.111691E+09 | 3661.78 | 02-FEB-07:10 | 7.12 |
March | 1273279.39 | 946.99 | 11-MAR-00:01 | 24.75 |
April | 91082159.08 | 4382.68 | 27-APR-23:01 | 32.73 |
May | 0.195797E+09 | 5705.00 | 03-MAY-23:01 | 35.95 |
June | 0.216947E+09 | 5571.16 | 05-JUN-23:01 | 35.62 |
July | 0.182297E+09 | 5132.89 | 02-JUL-23:01 | 35.28 |
August | 0.132931E+09 | 3650.35 | 08-AUG-23:01 | 32.07 |
September | 78945515.34 | 2925.23 | 17-SEP-23:01 | 30.23 |
October | 8863661.63 | 3015.46 | 22-OCT-23:01 | 29.42 |
November | 1844326.73 | 678.52 | 27-NOV-07:10 | 10.02 |
December | 0.265264E+09 | 5566.87 | 31-DEC-07:10 | 5.53 |
Annual Sum or Average | 0.196022E+10 | |||
Minimum of Months | 1273279.39 | 678.52 | 5.53 | |
Maximum of Months | 0.673281E+09 | 5705.00 | 35.95 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 5498557.41 | 5916.02 | 27-APR-23:01 | 32.73 |
May | 17155982.02 | 8773.08 | 03-MAY-23:01 | 35.95 |
June | 17363226.82 | 8493.80 | 05-JUN-23:01 | 35.62 |
July | 6674411.12 | 6672.94 | 04-JUL-23:01 | 35.10 |
August | 3538313.03 | 3841.92 | 02-AUG-23:01 | 30.53 |
September | 1842159.59 | 2190.60 | 17-SEP-23:01 | 30.23 |
October | 408126.39 | 2955.56 | 22-OCT-23:01 | 29.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 52480776.38 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 17363226.82 | 8773.08 | 35.95 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:02 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.421201E+09 | 444.80 | 02-JAN-17:40 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.364234E+09 | 444.80 | 01-FEB-17:00 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.373458E+09 | 444.80 | 01-MAR-18:19 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.341454E+09 | 444.80 | 01-APR-18:40 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.339140E+09 | 444.80 | 01-MAY-18:00 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.329426E+09 | 444.80 | 01-JUN-19:10 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.341096E+09 | 444.80 | 01-JUL-19:19 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.363430E+09 | 444.80 | 01-AUG-18:00 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.358345E+09 | 444.80 | 01-SEP-18:49 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.392258E+09 | 444.80 | 02-OCT-17:00 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.402664E+09 | 444.80 | 01-NOV-17:40 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.424620E+09 | 444.80 | 01-DEC-17:19 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.445132E+10 | 0.703313E+11 | ||||
Minimum of Months | 0.329426E+09 | 444.80 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.424620E+09 | 444.80 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147778E+10 | 901.37 | 02-JAN-10:09 | 0.154373E+11 | 9706.84 | 01-JAN-11:09 |
February | 0.133867E+10 | 901.37 | 01-FEB-10:09 | 0.139433E+11 | 9706.84 | 01-FEB-11:09 |
March | 0.150331E+10 | 901.37 | 01-MAR-10:09 | 0.154374E+11 | 9706.84 | 01-MAR-11:09 |
April | 0.143598E+10 | 901.37 | 01-APR-16:10 | 0.149393E+11 | 9706.84 | 01-APR-10:09 |
May | 0.149055E+10 | 901.37 | 01-MAY-09:09 | 0.154373E+11 | 9706.84 | 01-MAY-10:09 |
June | 0.145287E+10 | 901.37 | 01-JUN-09:09 | 0.149394E+11 | 9706.84 | 01-JUN-10:09 |
July | 0.147384E+10 | 901.37 | 01-JUL-16:10 | 0.154372E+11 | 9706.84 | 01-JUL-10:09 |
August | 0.150331E+10 | 901.37 | 01-AUG-09:09 | 0.154374E+11 | 9706.84 | 01-AUG-10:09 |
September | 0.143634E+10 | 901.37 | 01-SEP-09:09 | 0.149393E+11 | 9706.84 | 01-SEP-10:09 |
October | 0.147760E+10 | 901.37 | 02-OCT-09:09 | 0.154373E+11 | 9706.84 | 01-OCT-10:09 |
November | 0.143091E+10 | 901.37 | 01-NOV-09:09 | 0.149393E+11 | 9706.84 | 01-NOV-10:09 |
December | 0.147402E+10 | 901.37 | 01-DEC-10:09 | 0.154372E+11 | 9706.84 | 01-DEC-11:09 |
Annual Sum or Average | 0.174952E+11 | 0.181762E+12 | ||||
Minimum of Months | 0.133867E+10 | 901.37 | 0.139433E+11 | 9706.84 | ||
Maximum of Months | 0.150331E+10 | 901.37 | 0.154374E+11 | 9706.84 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.421201E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796412E+10 |
February | 0.852256E+10 | 0.364234E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135516E+09 | 0.438334E+10 |
March | 0.954557E+10 | 0.373458E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200099E+10 | 0.161337E+10 |
April | 0.915225E+10 | 0.341454E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721271E+10 | 0.133099E+09 |
May | 0.947560E+10 | 0.339140E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108962E+11 | 2131160.80 |
June | 0.922788E+10 | 0.329426E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108328E+11 | 403435.64 |
July | 0.939996E+10 | 0.341096E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858321E+10 | 234400.29 |
August | 0.954557E+10 | 0.363430E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712284E+10 | 286470.96 |
September | 0.915225E+10 | 0.358345E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587604E+10 | 908734.08 |
October | 0.940563E+10 | 0.392258E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374585E+10 | 0.660693E+09 |
November | 0.909363E+10 | 0.402664E+09 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961317E+09 | 0.303851E+10 |
December | 0.939996E+10 | 0.424620E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5857896.63 | 0.703473E+10 |
Annual Sum or Average | 0.111326E+12 | 0.445132E+10 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573733E+11 | 0.248318E+11 |
Minimum of Months | 0.852256E+10 | 0.329426E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234400.29 |
Maximum of Months | 0.954557E+10 | 0.424620E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108962E+11 | 0.796412E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.147778E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31879365.68 |
February | 0.610713E+09 | 0.133867E+10 | 0.101891E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 17406.92 | 35586654.93 |
March | 0.684021E+09 | 0.150331E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 3457566.89 | 28503556.63 |
April | 0.655836E+09 | 0.143598E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 18946125.42 | 3362266.61 |
May | 0.679007E+09 | 0.149055E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 34881973.37 | 2964763.25 |
June | 0.661256E+09 | 0.145287E+10 | 0.109170E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 23179715.24 | 1476161.62 |
July | 0.673587E+09 | 0.147384E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 20265375.21 | 2584466.91 |
August | 0.684021E+09 | 0.150331E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 10510372.83 | 2466934.78 |
September | 0.655836E+09 | 0.143634E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 8708094.28 | 2705086.86 |
October | 0.673993E+09 | 0.147760E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 5209271.32 | 2870320.81 |
November | 0.651635E+09 | 0.143091E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 703194.29 | 8581502.86 |
December | 0.673587E+09 | 0.147402E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29500326.69 |
Annual Sum or Average | 0.797748E+10 | 0.174952E+11 | 0.132823E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 0.125879E+09 | 0.152481E+09 |
Minimum of Months | 0.610713E+09 | 0.133867E+10 | 0.101891E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1476161.62 |
Maximum of Months | 0.684021E+09 | 0.150331E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 34881973.37 | 35586654.93 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576009E+09 | 0.965470E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436540E+09 | 0.105451E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465337E+09 | 0.147641E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520084E+09 | 0.167971E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452353E+09 | 0.170460E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422480E+09 | 0.162143E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267991E+09 | 0.129621E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260198E+09 | 0.122992E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378420E+09 | 0.107870E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586153E+09 | 0.132310E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621740E+09 | 0.109706E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625188E+09 | 0.970151E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561249E+10 | 0.154973E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260198E+09 | 0.965470E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625188E+09 | 0.170460E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 444.80 | 02-JAN-17:40 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10748.84 | 02-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 444.80 | 01-FEB-17:00 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2396.74 | 22-FEB-14:00 | 7909.98 | 04-FEB-07:10 |
March | 9454.80 | 04-MAR-19:10 | 444.80 | 01-MAR-18:19 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8962.34 | 28-MAR-17:02 | 4894.89 | 01-MAR-21:00 |
April | 9454.80 | 01-APR-18:10 | 444.80 | 01-APR-18:40 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12429.11 | 27-APR-17:02 | 2479.92 | 11-APR-06:10 |
May | 9454.80 | 06-MAY-18:10 | 444.80 | 01-MAY-18:00 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15240.61 | 03-MAY-17:02 | 464.49 | 13-MAY-06:10 |
June | 9454.80 | 03-JUN-18:10 | 444.80 | 01-JUN-19:10 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16070.68 | 07-JUN-17:03 | 77.04 | 18-JUN-05:10 |
July | 9454.80 | 01-JUL-18:10 | 444.80 | 01-JUL-19:19 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12690.81 | 03-JUL-17:03 | 26.64 | 19-JUL-01:52 |
August | 9454.80 | 05-AUG-18:10 | 444.80 | 01-AUG-18:00 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10454.76 | 07-AUG-17:03 | 26.64 | 16-AUG-00:10 |
September | 9454.80 | 02-SEP-18:10 | 444.80 | 01-SEP-18:49 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10041.51 | 17-SEP-20:00 | 121.76 | 27-SEP-05:10 |
October | 9454.80 | 07-OCT-18:10 | 444.80 | 02-OCT-17:00 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9840.76 | 02-OCT-12:00 | 3853.47 | 29-OCT-06:10 |
November | 9454.80 | 04-NOV-18:10 | 444.80 | 01-NOV-17:40 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4631.98 | 09-NOV-13:00 | 6939.27 | 25-NOV-19:55 |
December | 9454.80 | 02-DEC-19:10 | 444.80 | 01-DEC-17:19 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 553.57 | 28-DEC-14:00 | 10303.66 | 30-DEC-20:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 444.80 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.64 | |||||
Maximum of Months | 9454.80 | 444.80 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 16070.68 | 10748.84 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 901.37 | 02-JAN-10:09 | 6972.03 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 140.36 | 15-JAN-02:20 |
February | 677.52 | 04-FEB-19:10 | 901.37 | 01-FEB-10:09 | 6972.03 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 1.22 | 22-FEB-14:55 | 188.81 | 26-FEB-02:00 |
March | 677.52 | 04-MAR-19:10 | 901.37 | 01-MAR-10:09 | 6972.03 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 26.09 | 27-MAR-15:00 | 532.98 | 25-MAR-00:20 |
April | 677.52 | 01-APR-18:10 | 901.37 | 01-APR-16:10 | 6972.03 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 72.94 | 15-APR-14:25 | 66.12 | 05-APR-00:10 |
May | 677.52 | 06-MAY-18:10 | 901.37 | 01-MAY-09:09 | 6972.03 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 108.09 | 04-MAY-00:08 | 89.23 | 15-MAY-02:00 |
June | 677.52 | 03-JUN-18:10 | 901.37 | 01-JUN-09:09 | 6972.03 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 67.41 | 06-JUN-14:55 | 101.87 | 18-JUN-00:40 |
July | 677.52 | 01-JUL-18:10 | 901.37 | 01-JUL-16:10 | 6972.03 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 79.60 | 03-JUL-03:30 | 64.06 | 19-JUL-02:00 |
August | 677.52 | 05-AUG-18:10 | 901.37 | 01-AUG-09:09 | 6972.03 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 49.78 | 31-AUG-02:10 | 62.79 | 16-AUG-00:40 |
September | 677.52 | 02-SEP-18:10 | 901.37 | 01-SEP-09:09 | 6972.03 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 29.18 | 28-SEP-14:00 | 52.98 | 09-SEP-00:40 |
October | 677.52 | 07-OCT-18:10 | 901.37 | 02-OCT-09:09 | 6972.03 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 34.91 | 03-OCT-14:53 | 100.81 | 12-OCT-02:10 |
November | 677.52 | 04-NOV-18:10 | 901.37 | 01-NOV-09:09 | 6972.03 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 7.73 | 13-NOV-14:00 | 123.65 | 28-NOV-04:50 |
December | 677.52 | 02-DEC-19:10 | 901.37 | 01-DEC-10:09 | 6972.03 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 231.11 | 29-DEC-04:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 901.37 | 6972.03 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 52.98 | ||||||
Maximum of Months | 677.52 | 901.37 | 6972.03 | 7998.14 | 0.00 | 0.00 | 0.00 | 108.09 | 532.98 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.02 | 23-JAN-07:20 | 1927.34 | 31-JAN-13:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651.23 | 19-FEB-23:00 | 2001.23 | 20-FEB-13:50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.00 | 28-MAR-06:45 | 2292.59 | 31-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.47 | 22-APR-15:10 | 2500.20 | 29-APR-14:02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858.56 | 22-MAY-14:00 | 2423.76 | 14-MAY-13:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 995.99 | 03-JUN-18:40 | 2568.61 | 08-JUN-13:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.19 | 04-JUL-05:40 | 2354.40 | 10-JUL-13:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.32 | 24-AUG-06:10 | 2033.43 | 05-AUG-13:30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.25 | 30-SEP-06:45 | 2026.32 | 26-SEP-13:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.03 | 02-OCT-06:35 | 2225.99 | 09-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 603.34 | 24-NOV-07:15 | 1954.14 | 23-NOV-12:50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 735.65 | 03-DEC-07:23 | 1857.46 | 27-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.32 | 1857.46 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 995.99 | 2568.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10711.15 | 15-JAN-03:01 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.96 |
February | 14678.51 | 23-FEB-03:01 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24427.98 | 12-MAR-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.35 |
April | 39405.18 | 28-APR-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44722.74 | 04-MAY-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 60.09 | 0.00 |
June | 40295.41 | 05-JUN-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.77 | 0.00 |
July | 29019.90 | 01-JUL-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.22 | 0.00 |
August | 28896.59 | 03-AUG-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.43 | 0.00 |
September | 31894.60 | 29-SEP-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34182.35 | 23-OCT-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
November | 23504.62 | 09-NOV-03:01 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8393.95 | 28-DEC-14:00 | 7353.73 | 106.75 | 3388.15 | 0.00 | 0.00 | 0.00 | 0.00 | 553.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8393.95 | 0.00 | 106.75 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44722.74 | 7353.73 | 250.09 | 3388.15 | 0.00 | 0.00 | 0.00 | 0.00 | 553.57 | 76.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 40057.68 | 13-JAN-03:01 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 14.20 |
February | 38612.82 | 20-FEB-03:01 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 53.14 |
March | 37815.66 | 01-MAR-03:01 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 18.81 |
April | 33290.21 | 11-APR-02:11 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27985.46 | 28-MAY-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 |
June | 23204.91 | 05-JUN-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.49 | 0.00 |
July | 19071.51 | 11-JUL-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 26.34 |
August | 18025.16 | 16-AUG-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 33.65 |
September | 22538.05 | 29-SEP-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
October | 30749.41 | 31-OCT-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 39573.28 | 27-NOV-03:01 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 42016.09 | 30-DEC-03:01 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 151.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 18025.16 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42016.09 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.49 | 151.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.03 | 0.00 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.70 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.07 | 0.00 |
April | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.39 | 0.00 |
May | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588.81 | 0.00 |
June | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.56 | 0.00 |
July | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.44 | 0.00 |
August | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.85 | 0.00 |
September | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 0.00 |
October | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.68 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.16 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588.81 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.345386E+11 | 23206.85 | 26-JAN-11:20 | 0.614323E+11 | 49219.58 | 02-JAN-11:30 |
February | 0.337244E+11 | 26020.28 | 22-FEB-11:20 | 0.518850E+11 | 47547.26 | 02-FEB-13:20 |
March | 0.434657E+11 | 30329.80 | 28-MAR-16:10 | 0.551589E+11 | 46965.26 | 02-MAR-13:20 |
April | 0.519501E+11 | 36434.77 | 27-APR-11:09 | 0.521552E+11 | 45634.22 | 03-APR-12:20 |
May | 0.645696E+11 | 40853.22 | 02-MAY-11:00 | 0.526442E+11 | 43797.93 | 03-MAY-12:20 |
June | 0.684767E+11 | 43367.30 | 22-JUN-17:10 | 0.500141E+11 | 41843.75 | 01-JUN-12:30 |
July | 0.725403E+11 | 42530.73 | 01-JUL-18:10 | 0.512444E+11 | 40286.70 | 03-JUL-12:39 |
August | 0.711664E+11 | 42227.21 | 25-AUG-11:00 | 0.515539E+11 | 41552.37 | 31-AUG-12:50 |
September | 0.638438E+11 | 39420.17 | 17-SEP-19:00 | 0.507373E+11 | 43437.20 | 28-SEP-12:20 |
October | 0.505113E+11 | 35569.90 | 04-OCT-11:20 | 0.536834E+11 | 45492.03 | 31-OCT-12:20 |
November | 0.396783E+11 | 29300.44 | 09-NOV-11:20 | 0.533437E+11 | 46779.42 | 29-NOV-13:39 |
December | 0.355039E+11 | 24568.14 | 18-DEC-11:20 | 0.588096E+11 | 48574.40 | 21-DEC-11:30 |
Annual Sum or Average | 0.629969E+12 | 0.642662E+12 | ||||
Minimum of Months | 0.337244E+11 | 23206.85 | 0.500141E+11 | 40286.70 | ||
Maximum of Months | 0.725403E+11 | 43367.30 | 0.614323E+11 | 49219.58 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.189898E+10 | 0.156513E+10 | 0.214106E+11 | 0.00 | 0.529482E+10 | 0.79 | 0.00 | 0.112423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170290E+10 | 0.133518E+10 | 0.193386E+11 | 0.00 | 0.473496E+10 | 0.72 | 0.00 | 0.361485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187677E+10 | 0.135105E+10 | 0.214107E+11 | 0.00 | 0.533177E+10 | 0.80 | 0.00 | 0.101095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177744E+10 | 0.118300E+10 | 0.207199E+11 | 0.00 | 0.559555E+10 | 0.77 | 0.00 | 0.193788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182969E+10 | 0.111309E+10 | 0.214107E+11 | 0.00 | 0.659666E+10 | 0.80 | 0.00 | 0.301717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.178230E+10 | 0.101833E+10 | 0.207201E+11 | 0.00 | 0.707001E+10 | 0.77 | 0.00 | 0.345027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181494E+10 | 0.108427E+10 | 0.214105E+11 | 0.00 | 0.767204E+10 | 0.79 | 0.00 | 0.370394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.186674E+10 | 0.117237E+10 | 0.214107E+11 | 0.00 | 0.761297E+10 | 0.80 | 0.00 | 0.355733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.179469E+10 | 0.125381E+10 | 0.207199E+11 | 0.00 | 0.682653E+10 | 0.77 | 0.00 | 0.298679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186985E+10 | 0.142515E+10 | 0.214106E+11 | 0.00 | 0.563910E+10 | 0.79 | 0.00 | 0.167110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183357E+10 | 0.148683E+10 | 0.207200E+11 | 0.00 | 0.510245E+10 | 0.77 | 0.00 | 0.728309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189864E+10 | 0.160383E+10 | 0.214105E+11 | 0.00 | 0.525613E+10 | 0.79 | 0.00 | 0.205835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219465E+11 | 0.155921E+11 | 0.252093E+12 | 0.00 | 0.727330E+11 | 9.37 | 0.00 | 0.227435E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.170290E+10 | 0.101833E+10 | 0.193386E+11 | 0.00 | 0.473496E+10 | 0.72 | 0.00 | 0.112423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189898E+10 | 0.160383E+10 | 0.214107E+11 | 0.00 | 0.767204E+10 | 0.80 | 0.00 | 0.370394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.512236E+10 | 0.00 | 0.157842E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.130574E+10 | 0.00 | 0.139753E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 586524.94 | 0.00 | 0.146326E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.129367E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.121185E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.107957E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.107187E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.110282E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.115188E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.131577E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.158791E+09 | 0.00 | 0.139665E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.290057E+10 | 0.00 | 0.153833E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.948805E+10 | 0.00 | 0.156016E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.00 | 0.00 | 0.107187E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.512236E+10 | 0.00 | 0.157842E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1346.16 | 02-JAN-17:40 | 1372.31 | 01-JAN-06:10 | 13637.09 | 01-JAN-11:09 | 0.00 | 2635.85 | 03-JAN-07:10 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 1346.16 | 01-FEB-17:00 | 1372.31 | 01-FEB-06:10 | 13637.09 | 01-FEB-11:09 | 0.00 | 2526.72 | 02-FEB-07:10 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 1346.16 | 01-MAR-18:19 | 1372.31 | 01-MAR-06:10 | 13637.09 | 01-MAR-11:09 | 0.00 | 2781.22 | 28-MAR-14:09 | 0.00 | 05-MAR-08:39 | 0.00 | 01-MAR-00:10 |
April | 1346.16 | 01-APR-18:40 | 1372.31 | 01-APR-05:10 | 13637.09 | 01-APR-10:09 | 0.00 | 3275.14 | 26-APR-17:10 | 0.00 | 22-APR-14:09 | 0.00 | 01-APR-00:10 |
May | 1346.16 | 01-MAY-18:00 | 1372.31 | 01-MAY-05:10 | 13637.09 | 01-MAY-10:09 | 0.00 | 3955.24 | 17-MAY-17:10 | 0.00 | 03-MAY-07:40 | 0.00 | 01-MAY-00:10 |
June | 1346.16 | 01-JUN-19:10 | 1372.31 | 01-JUN-05:10 | 13637.09 | 01-JUN-10:09 | 0.00 | 4409.90 | 22-JUN-17:10 | 0.00 | 24-JUN-14:30 | 0.00 | 01-JUN-00:10 |
July | 1346.16 | 01-JUL-19:19 | 1372.31 | 01-JUL-05:10 | 13637.09 | 01-JUL-10:09 | 0.00 | 4557.41 | 01-JUL-18:10 | 0.00 | 22-JUL-10:39 | 0.00 | 01-JUL-00:10 |
August | 1346.16 | 01-AUG-18:00 | 1372.31 | 01-AUG-05:10 | 13637.09 | 01-AUG-10:09 | 0.00 | 4317.78 | 25-AUG-11:00 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 1346.16 | 01-SEP-18:49 | 1372.31 | 01-SEP-05:10 | 13637.09 | 01-SEP-10:09 | 0.00 | 4022.04 | 14-SEP-17:19 | 0.00 | 08-SEP-13:50 | 0.00 | 01-SEP-00:10 |
October | 1346.16 | 02-OCT-17:00 | 1372.31 | 01-OCT-05:10 | 13637.09 | 01-OCT-10:09 | 0.00 | 3173.34 | 04-OCT-11:20 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 1346.16 | 01-NOV-17:40 | 1372.31 | 01-NOV-05:10 | 13637.09 | 01-NOV-10:09 | 0.00 | 2541.96 | 09-NOV-12:09 | 0.00 | 26-NOV-09:09 | 0.00 | 01-NOV-00:10 |
December | 1346.16 | 01-DEC-17:19 | 1372.31 | 01-DEC-06:10 | 13637.09 | 01-DEC-11:09 | 0.00 | 2628.45 | 31-DEC-07:10 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1346.16 | 1372.31 | 13637.09 | 0.00 | 2526.72 | 0.00 | 0.00 | ||||||
Maximum of Months | 1346.16 | 1372.31 | 13637.09 | 0.00 | 4557.41 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 5211.84 | 12-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7869.93 | 22-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13502.35 | 28-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18997.90 | 26-APR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23250.15 | 17-MAY-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26024.02 | 10-JUN-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 25099.07 | 01-JUL-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22907.45 | 25-AUG-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22299.57 | 17-SEP-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17243.20 | 04-OCT-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10597.11 | 09-NOV-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6355.02 | 28-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5211.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26024.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 23206.85 | 26-JAN-11:20 | 1008.12 | 13637.09 | 0.00 | 0.00 | 2283.12 | 0.00 | 0.00 | 2364.71 | 0.00 |
February | 26020.28 | 22-FEB-11:20 | 1008.12 | 13637.09 | 0.00 | 0.00 | 2283.12 | 0.00 | 0.00 | 5179.03 | 0.00 |
March | 30329.80 | 28-MAR-16:10 | 1008.12 | 12287.48 | 0.00 | 0.00 | 2715.18 | 0.00 | 0.00 | 13161.51 | 0.00 |
April | 36434.77 | 27-APR-11:09 | 1008.12 | 12737.35 | 0.00 | 0.00 | 3160.62 | 0.00 | 0.00 | 17819.96 | 0.00 |
May | 40853.22 | 02-MAY-11:00 | 1008.12 | 12737.35 | 0.00 | 0.00 | 3689.35 | 0.00 | 0.00 | 22207.23 | 0.00 |
June | 43367.30 | 22-JUN-17:10 | 1008.12 | 11387.73 | 0.00 | 0.00 | 4409.90 | 0.00 | 0.00 | 25309.78 | 0.00 |
July | 42530.73 | 01-JUL-18:10 | 1008.12 | 10487.99 | 0.00 | 0.00 | 4557.41 | 0.00 | 0.00 | 25099.07 | 0.00 |
August | 42227.21 | 25-AUG-11:00 | 1008.12 | 12737.35 | 0.00 | 0.00 | 4317.78 | 0.00 | 0.00 | 22907.45 | 0.00 |
September | 39420.17 | 17-SEP-19:00 | 897.44 | 9588.24 | 1372.31 | 0.00 | 3943.29 | 0.00 | 0.00 | 22299.57 | 0.00 |
October | 35569.90 | 04-OCT-11:20 | 1008.12 | 12737.35 | 0.00 | 0.00 | 3173.34 | 0.00 | 0.00 | 16927.48 | 0.00 |
November | 29300.44 | 09-NOV-11:20 | 1008.12 | 13637.09 | 0.00 | 0.00 | 2305.22 | 0.00 | 0.00 | 8431.50 | 0.00 |
December | 24568.14 | 18-DEC-11:20 | 1008.12 | 13637.09 | 0.00 | 0.00 | 2283.12 | 0.00 | 0.00 | 3724.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 23206.85 | 897.44 | 9588.24 | 0.00 | 0.00 | 2283.12 | 0.00 | 0.00 | 2364.71 | 0.00 | |
Maximum of Months | 43367.30 | 1008.12 | 13637.09 | 1372.31 | 0.00 | 4557.41 | 0.00 | 0.00 | 25309.78 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 18648.85 | 03-JAN-07:10 | 0.00 | 24647.37 | 23-JAN-13:20 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 11951.66 | 02-FEB-07:10 | 0.00 | 24564.11 | 02-FEB-13:20 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 445.98 | 01-MAR-07:10 | 0.00 | 23982.11 | 02-MAR-13:20 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 22651.07 | 03-APR-12:20 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 20814.78 | 03-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 18860.60 | 01-JUN-12:30 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 17303.55 | 03-JUL-12:39 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 18569.22 | 31-AUG-12:50 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 20454.05 | 28-SEP-12:20 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 22508.88 | 31-OCT-12:20 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 6038.22 | 27-NOV-07:10 | 0.00 | 23796.27 | 29-NOV-13:39 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 17797.25 | 31-DEC-07:10 | 0.00 | 24548.18 | 31-DEC-13:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 0.00 | 0.00 | 17303.55 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 18648.85 | 0.00 | 24647.37 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 24.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.62 | 0.50 | 24.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 24.82 | 0.67 | 24.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 25.16 | 0.00 | 25.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 25.35 | 0.00 | 25.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 25.46 | 0.00 | 25.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 25.42 | 0.00 | 25.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 25.28 | 0.00 | 25.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 24.89 | 1.67 | 24.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 24.57 | 0.00 | 24.57 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 121.00 | 25.14 | 2.83 | 25.12 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 25.46 | 1.67 | 25.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.57 | 0.00 | 27.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 28.12 | 0.00 | 28.12 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 29.18 | 0.00 | 29.18 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 29.74 | 1.83 | 29.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 184.33 | 28.04 | 151.67 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 345.67 | 28.39 | 304.33 | 28.32 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 556.50 | 28.40 | 488.67 | 28.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 525.67 | 28.66 | 464.33 | 28.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 303.83 | 27.98 | 266.50 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 30.06 | 0.00 | 30.06 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 28.98 | 0.00 | 28.98 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.82 | 0.00 | 27.82 |
Annual Sum or Average | 0.00 | 0.00 | 2057.50 | 28.41 | 1677.33 | 28.33 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.57 | 0.00 | 27.57 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 556.50 | 30.06 | 488.67 | 30.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 420.17 | 21.39 | 82.17 | 21.74 | 4.83 | 21.71 |
February | 230.50 | 21.61 | 252.50 | 22.78 | 3.17 | 22.79 |
March | 73.50 | 22.54 | 496.17 | 23.74 | 5.50 | 23.74 |
April | 23.50 | 25.87 | 572.00 | 24.12 | 23.50 | 24.18 |
May | 201.50 | 24.50 | 611.00 | 24.20 | 201.50 | 24.26 |
June | 382.83 | 24.26 | 592.00 | 24.18 | 382.83 | 24.21 |
July | 583.67 | 24.13 | 609.00 | 24.13 | 583.67 | 24.13 |
August | 612.00 | 24.09 | 612.00 | 24.09 | 612.00 | 24.09 |
September | 533.67 | 24.08 | 590.00 | 24.07 | 533.67 | 24.07 |
October | 122.00 | 24.15 | 601.17 | 23.99 | 121.50 | 24.02 |
November | 124.67 | 22.06 | 422.33 | 23.45 | 5.17 | 23.45 |
December | 354.83 | 21.40 | 191.00 | 22.24 | 3.00 | 22.23 |
Annual Sum or Average | 3662.83 | 23.32 | 5631.33 | 23.74 | 2480.33 | 23.83 |
Minimum of Months | 23.50 | 21.39 | 82.17 | 21.74 | 3.00 | 21.71 |
Maximum of Months | 612.00 | 25.87 | 612.00 | 24.20 | 612.00 | 24.26 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 398.33 | 23.30 | 407.67 | 24.16 | 224.33 | 24.53 |
February | 386.67 | 25.20 | 470.33 | 25.31 | 326.67 | 25.51 |
March | 517.50 | 26.11 | 612.00 | 25.98 | 517.50 | 26.02 |
April | 586.33 | 26.26 | 590.00 | 26.26 | 586.33 | 26.26 |
May | 611.00 | 26.70 | 611.00 | 26.70 | 611.00 | 26.70 |
June | 592.00 | 27.42 | 592.00 | 27.42 | 592.00 | 27.42 |
July | 609.00 | 28.12 | 609.00 | 28.12 | 609.00 | 28.12 |
August | 612.00 | 28.21 | 612.00 | 28.21 | 612.00 | 28.21 |
September | 590.00 | 27.06 | 590.00 | 27.06 | 590.00 | 27.06 |
October | 599.33 | 26.16 | 610.00 | 26.15 | 599.33 | 26.15 |
November | 447.17 | 25.97 | 573.83 | 25.77 | 438.67 | 25.85 |
December | 397.33 | 24.32 | 442.33 | 24.78 | 272.83 | 25.08 |
Annual Sum or Average | 6346.67 | 26.44 | 6720.17 | 26.47 | 5979.67 | 26.58 |
Minimum of Months | 386.67 | 23.30 | 407.67 | 24.16 | 224.33 | 24.53 |
Maximum of Months | 612.00 | 28.21 | 612.00 | 28.21 | 612.00 | 28.21 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.12560 | 45.76498 | 0.04465 | 6.92116 |
February | 551.00000 | 22.88224 | 47.94372 | 0.25881 | 8.13448 |
March | 612.00000 | 23.72834 | 47.34952 | 0.48975 | 10.56432 |
April | 590.00000 | 24.03890 | 46.09827 | 0.59961 | 12.85779 |
May | 611.00000 | 24.10644 | 56.15769 | -0.0851 | 6.05437 |
June | 592.00000 | 24.13437 | 64.24708 | 0.00199 | 6.21341 |
July | 609.00000 | 24.12420 | 73.86203 | 0.07191 | 6.25153 |
August | 612.00000 | 24.09383 | 76.43927 | 0.08026 | 6.06148 |
September | 590.00000 | 24.06293 | 72.76441 | 0.02770 | 5.71164 |
October | 610.00000 | 23.94867 | 55.14690 | 0.66553 | 14.51741 |
November | 591.00000 | 23.42300 | 48.30308 | 0.45210 | 10.25969 |
December | 609.00000 | 22.38744 | 44.93988 | 0.13113 | 7.34501 |
Annual Sum or Average | 7187.00000 | 23.59063 | 56.64464 | 0.22746 | 8.40572 |
Minimum of Months | 551.00000 | 22.12560 | 44.93988 | -0.0851 | 5.71164 |
Maximum of Months | 612.00000 | 24.13437 | 76.43927 | 0.66553 | 14.51741 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.45148 | 47.84695 | 0.58609 | 19.00541 |
February | 551.00000 | 24.75454 | 47.74770 | 0.90530 | 26.20259 |
March | 612.00000 | 25.86516 | 47.02780 | 1.18879 | 35.39532 |
April | 590.00000 | 26.25520 | 47.04417 | 1.31237 | 41.07648 |
May | 611.00000 | 26.69820 | 56.26871 | 1.02573 | 28.59053 |
June | 592.00000 | 27.42056 | 62.80872 | 1.34393 | 43.77852 |
July | 609.00000 | 28.11695 | 68.59073 | 1.63682 | 57.82620 |
August | 612.00000 | 28.21180 | 68.50320 | 1.67382 | 59.30496 |
September | 590.00000 | 27.05646 | 66.16265 | 1.24736 | 38.88471 |
October | 610.00000 | 26.13531 | 53.40517 | 1.35626 | 43.33843 |
November | 591.00000 | 25.49309 | 47.88328 | 1.12503 | 33.16827 |
December | 609.00000 | 24.06640 | 45.86255 | 0.74007 | 21.68635 |
Annual Sum or Average | 7187.00000 | 26.13445 | 54.97896 | 1.17999 | 37.43040 |
Minimum of Months | 551.00000 | 23.45148 | 45.86255 | 0.58609 | 19.00541 |
Maximum of Months | 612.00000 | 28.21180 | 68.59073 | 1.67382 | 59.30496 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.149375E+10 | 0.455961E+09 | 136.56 | 0.128428E+10 | 0.209469E+09 | 0.00 | 0.41 | 15-JAN-03:01 | 0.00 | 01-JAN-00:03 | 11780.89 | 15-JAN-03:01 | 8067.66 | 12-JAN-14:00 | 4425.60 | 15-JAN-03:01 | 3379.91 | 15-JAN-03:01 | 0.00 | 01-JAN-00:03 |
February | 0.568721E+10 | 0.168481E+10 | 269.83 | 0.470271E+10 | 0.984503E+09 | 0.00 | 0.58 | 23-FEB-03:01 | 0.00 | 01-FEB-00:05 | 17506.17 | 23-FEB-03:01 | 13564.29 | 22-FEB-13:00 | 5760.60 | 26-FEB-03:01 | 4802.49 | 23-FEB-03:01 | 0.00 | 01-FEB-00:05 |
March | 0.183985E+11 | 0.523411E+10 | 513.43 | 0.147213E+11 | 0.367713E+10 | 0.00 | 1.00 | 12-MAR-02:61 | 0.00 | 01-MAR-00:10 | 42721.09 | 29-MAR-02:61 | 28702.24 | 12-MAR-02:61 | 16709.42 | 29-MAR-02:61 | 9949.47 | 29-MAR-02:61 | 0.00 | 01-MAR-00:10 |
April | 0.353194E+11 | 0.101356E+11 | 605.35 | 0.293026E+11 | 0.601687E+10 | 0.00 | 1.00 | 02-APR-02:61 | 0.00 | 01-APR-00:02 | 74005.21 | 27-APR-02:61 | 51785.62 | 28-APR-02:61 | 30890.82 | 27-APR-02:61 | 16887.84 | 27-APR-02:61 | 0.00 | 01-APR-00:02 |
May | 0.546535E+11 | 0.155238E+11 | 633.64 | 0.394829E+11 | 0.151706E+11 | 0.00 | 1.00 | 01-MAY-02:61 | 0.00 | 01-MAY-00:03 | 74803.72 | 22-MAY-02:61 | 63258.67 | 04-MAY-02:61 | 51217.78 | 23-MAY-02:61 | 18161.74 | 04-MAY-02:61 | 0.00 | 01-MAY-00:03 |
June | 0.650736E+11 | 0.178284E+11 | 621.19 | 0.402531E+11 | 0.248205E+11 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:03 | 74803.72 | 01-JUN-02:61 | 55926.55 | 05-JUN-02:61 | 49990.07 | 28-JUN-02:61 | 18273.80 | 14-JUN-02:61 | 0.00 | 01-JUN-00:03 |
July | 0.749683E+11 | 0.189105E+11 | 639.33 | 0.370305E+11 | 0.379379E+11 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:02 | 74803.72 | 13-JUL-02:02 | 41463.27 | 01-JUL-02:61 | 50568.36 | 19-JUL-02:61 | 17916.84 | 03-JUL-02:61 | 0.00 | 01-JUL-00:02 |
August | 0.732675E+11 | 0.179831E+11 | 633.65 | 0.334322E+11 | 0.398353E+11 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:02 | 74803.72 | 13-AUG-02:61 | 40254.54 | 03-AUG-02:61 | 52267.05 | 30-AUG-02:61 | 17405.79 | 09-AUG-02:61 | 0.00 | 01-AUG-00:02 |
September | 0.582030E+11 | 0.145153E+11 | 611.84 | 0.289820E+11 | 0.292210E+11 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:02 | 74803.72 | 26-SEP-02:61 | 42180.19 | 29-SEP-02:61 | 49127.34 | 12-SEP-02:61 | 16946.79 | 01-SEP-02:61 | 0.00 | 01-SEP-00:02 |
October | 0.315470E+11 | 0.864051E+10 | 606.47 | 0.223923E+11 | 0.915471E+10 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:02 | 74803.72 | 01-OCT-02:61 | 42435.12 | 03-OCT-02:61 | 35900.69 | 04-OCT-02:61 | 16946.79 | 01-OCT-02:61 | 0.00 | 01-OCT-00:02 |
November | 0.129573E+11 | 0.370407E+10 | 404.93 | 0.104620E+11 | 0.249530E+10 | 0.00 | 1.00 | 01-NOV-02:61 | 0.00 | 01-NOV-00:01 | 41953.62 | 09-NOV-03:01 | 25404.68 | 09-NOV-03:01 | 16548.94 | 09-NOV-03:01 | 9882.95 | 09-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 0.287670E+10 | 0.868029E+09 | 197.08 | 0.239949E+10 | 0.477212E+09 | 0.00 | 0.41 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 11854.33 | 28-DEC-14:00 | 9978.97 | 28-DEC-14:00 | 2007.36 | 18-DEC-13:00 | 3398.98 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.434446E+12 | 0.115484E+12 | 5873.31 | 0.264445E+12 | 0.170000E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.149375E+10 | 0.455961E+09 | 136.56 | 0.128428E+10 | 0.209469E+09 | 0.00 | 0.41 | 0.00 | 11780.89 | 8067.66 | 2007.36 | 3379.91 | 0.00 | |||||||
Maximum of Months | 0.749683E+11 | 0.189105E+11 | 639.33 | 0.402531E+11 | 0.398353E+11 | 0.00 | 1.00 | 0.00 | 74803.72 | 63258.67 | 52267.05 | 18273.80 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.235879E+10 | 0.668273E+09 | 203.56 | 0.180363E+10 | 0.555153E+09 | 0.00 | 1.00 | 06-JAN-05:01 | 0.00 | 01-JAN-00:03 | 29900.35 | 12-JAN-03:01 | 18531.52 | 12-JAN-03:01 | 16194.89 | 16-JAN-03:01 | 7168.59 | 12-JAN-03:01 | 0.00 | 01-JAN-00:03 |
February | 0.719965E+10 | 0.193004E+10 | 324.12 | 0.564436E+10 | 0.155529E+10 | 0.00 | 1.00 | 03-FEB-05:01 | 0.00 | 01-FEB-00:05 | 29900.35 | 20-FEB-03:01 | 19888.45 | 18-FEB-03:01 | 14938.88 | 16-FEB-03:01 | 7168.59 | 07-FEB-03:01 | 0.00 | 01-FEB-00:05 |
March | 0.193183E+11 | 0.487542E+10 | 546.97 | 0.158997E+11 | 0.341857E+10 | 0.00 | 1.00 | 01-MAR-03:01 | 0.00 | 01-MAR-00:10 | 31083.25 | 29-MAR-02:11 | 24562.07 | 28-MAR-14:10 | 16260.34 | 31-MAR-02:11 | 7247.68 | 29-MAR-02:11 | 0.00 | 01-MAR-00:10 |
April | 0.361655E+11 | 0.924317E+10 | 652.71 | 0.325114E+11 | 0.365413E+10 | 0.00 | 1.00 | 01-APR-02:11 | 0.00 | 01-APR-00:02 | 32943.98 | 20-APR-02:61 | 31284.04 | 16-APR-12:20 | 16732.00 | 23-APR-02:61 | 8952.14 | 27-APR-15:00 | 0.00 | 01-APR-00:02 |
May | 0.572559E+11 | 0.146479E+11 | 702.90 | 0.461420E+11 | 0.111140E+11 | 0.00 | 1.00 | 01-MAY-02:61 | 0.00 | 01-MAY-00:03 | 33221.26 | 24-MAY-02:61 | 31305.97 | 26-MAY-10:43 | 21913.95 | 22-MAY-23:00 | 9712.93 | 03-MAY-14:55 | 0.00 | 01-MAY-00:03 |
June | 0.664286E+11 | 0.166742E+11 | 684.57 | 0.455446E+11 | 0.208840E+11 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:03 | 33221.26 | 24-JUN-12:20 | 31359.46 | 12-JUN-20:15 | 23080.10 | 28-JUN-02:61 | 9604.31 | 07-JUN-15:53 | 0.00 | 01-JUN-00:03 |
July | 0.762972E+11 | 0.181289E+11 | 708.59 | 0.387360E+11 | 0.375611E+11 | 0.00 | 1.00 | 01-JUL-00:06 | 0.00 | 01-JUL-00:02 | 33221.26 | 19-JUL-04:02 | 30949.64 | 04-JUL-17:10 | 23752.60 | 19-JUL-03:22 | 8802.85 | 02-JUL-15:53 | 0.00 | 01-JUL-00:02 |
August | 0.760476E+11 | 0.175903E+11 | 705.05 | 0.330026E+11 | 0.430449E+11 | 0.00 | 1.00 | 01-AUG-00:05 | 0.00 | 01-AUG-00:02 | 33221.26 | 19-AUG-20:40 | 23849.98 | 07-AUG-14:00 | 24936.90 | 12-AUG-08:00 | 8332.17 | 07-AUG-14:55 | 0.00 | 01-AUG-00:02 |
September | 0.669022E+11 | 0.153525E+11 | 670.90 | 0.317359E+11 | 0.351663E+11 | 0.00 | 1.00 | 01-SEP-00:05 | 0.00 | 01-SEP-00:02 | 33221.26 | 13-SEP-19:10 | 28669.30 | 29-SEP-13:00 | 23705.12 | 10-SEP-02:13 | 8360.81 | 17-SEP-20:00 | 0.00 | 01-SEP-00:02 |
October | 0.335420E+11 | 0.807053E+10 | 647.09 | 0.244212E+11 | 0.912084E+10 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:02 | 33221.26 | 06-OCT-10:53 | 28540.14 | 02-OCT-13:00 | 20623.15 | 12-OCT-03:32 | 7909.89 | 04-OCT-12:13 | 0.00 | 01-OCT-00:02 |
November | 0.140753E+11 | 0.357901E+10 | 446.38 | 0.113512E+11 | 0.272410E+10 | 0.00 | 1.00 | 01-NOV-02:61 | 0.00 | 01-NOV-00:01 | 29900.35 | 13-NOV-03:11 | 18157.93 | 03-NOV-03:31 | 15636.64 | 09-NOV-03:01 | 7168.59 | 01-NOV-02:61 | 0.00 | 01-NOV-00:01 |
December | 0.431328E+10 | 0.119032E+10 | 257.93 | 0.330991E+10 | 0.100337E+10 | 0.00 | 1.00 | 01-DEC-03:01 | 0.00 | 01-DEC-00:10 | 29900.35 | 17-DEC-03:01 | 20765.46 | 30-DEC-03:01 | 14881.74 | 28-DEC-03:01 | 7168.59 | 01-DEC-03:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.459904E+12 | 0.111951E+12 | 6550.78 | 0.290102E+12 | 0.169802E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.235879E+10 | 0.668273E+09 | 203.56 | 0.180363E+10 | 0.555153E+09 | 0.00 | 1.00 | 0.00 | 29900.35 | 18157.93 | 14881.74 | 7168.59 | 0.00 | |||||||
Maximum of Months | 0.762972E+11 | 0.181289E+11 | 708.59 | 0.461420E+11 | 0.430449E+11 | 0.00 | 1.00 | 0.00 | 33221.26 | 31359.46 | 24936.90 | 9712.93 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.96 | 25.67 | 38.29 | 71.29 | 113.00 | 0.00 | 0.00 | 0.00 |
February | 77.70 | 32.08 | 45.62 | 109.54 | 88.56 | 0.00 | 0.00 | 0.00 |
March | 94.79 | 39.12 | 55.66 | 166.84 | 53.28 | 0.00 | 0.00 | 0.00 |
April | 112.77 | 52.58 | 60.19 | 252.00 | 18.56 | 0.00 | 0.00 | 0.00 |
May | 111.00 | 49.21 | 61.79 | 288.25 | 3.23 | 0.00 | 0.00 | 0.00 |
June | 90.34 | 29.97 | 60.36 | 258.28 | 2.61 | 0.00 | 0.00 | 0.00 |
July | 75.93 | 16.03 | 59.89 | 212.46 | 0.88 | 0.00 | 0.00 | 0.00 |
August | 68.41 | 11.91 | 56.51 | 177.46 | 2.65 | 0.00 | 0.00 | 0.00 |
September | 73.09 | 20.38 | 52.71 | 165.65 | 9.49 | 0.00 | 0.00 | 0.00 |
October | 79.95 | 32.30 | 47.66 | 158.82 | 44.21 | 0.00 | 0.00 | 0.00 |
November | 70.89 | 30.43 | 40.46 | 111.87 | 82.50 | 0.00 | 0.00 | 0.00 |
December | 61.81 | 24.49 | 37.32 | 74.03 | 112.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81.70 | 30.30 | 51.40 | 170.75 | 44.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 61.81 | 11.91 | 37.32 | 71.29 | 0.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.77 | 52.58 | 61.79 | 288.25 | 113.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.58 | 165.02 | 106.56 | 406.47 | 222.55 | 0.00 | 0.00 | 0.00 |
February | 258.23 | 143.43 | 114.80 | 420.73 | 179.11 | 0.00 | 0.00 | 0.00 |
March | 220.79 | 97.52 | 123.27 | 419.64 | 110.82 | 0.00 | 0.00 | 0.00 |
April | 155.09 | 43.77 | 111.32 | 399.20 | 38.67 | 0.00 | 0.00 | 0.00 |
May | 111.53 | 8.26 | 103.27 | 373.29 | 6.48 | 0.00 | 0.00 | 0.00 |
June | 102.02 | 1.74 | 100.28 | 364.14 | 5.24 | 0.00 | 0.00 | 0.00 |
July | 106.42 | 1.46 | 104.95 | 338.27 | 1.80 | 0.00 | 0.00 | 0.00 |
August | 112.88 | 6.03 | 106.86 | 314.18 | 5.33 | 0.00 | 0.00 | 0.00 |
September | 151.33 | 39.28 | 112.05 | 354.44 | 19.29 | 0.00 | 0.00 | 0.00 |
October | 260.35 | 145.38 | 114.97 | 523.62 | 90.25 | 0.00 | 0.00 | 0.00 |
November | 325.19 | 214.94 | 110.25 | 570.80 | 167.13 | 0.00 | 0.00 | 0.00 |
December | 290.22 | 181.86 | 108.36 | 450.41 | 219.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 196.78 | 87.07 | 109.72 | 411.07 | 88.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.02 | 1.46 | 100.28 | 314.18 | 1.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 325.19 | 214.94 | 123.27 | 570.80 | 222.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.57 | 24.35 | 38.22 | 75.71 | 120.22 | 0.00 | 0.00 | 0.00 |
February | 71.55 | 26.37 | 45.18 | 103.20 | 93.72 | 0.00 | 0.00 | 0.00 |
March | 92.79 | 37.09 | 55.70 | 165.29 | 56.04 | 0.00 | 0.00 | 0.00 |
April | 112.78 | 52.89 | 59.89 | 252.37 | 18.97 | 0.00 | 0.00 | 0.00 |
May | 106.79 | 45.30 | 61.49 | 280.87 | 3.33 | 0.00 | 0.00 | 0.00 |
June | 100.31 | 38.96 | 61.34 | 277.58 | 2.59 | 0.00 | 0.00 | 0.00 |
July | 74.43 | 14.48 | 59.95 | 208.84 | 0.97 | 0.00 | 0.00 | 0.00 |
August | 68.36 | 12.15 | 56.21 | 177.62 | 2.68 | 0.00 | 0.00 | 0.00 |
September | 75.14 | 22.06 | 53.08 | 169.80 | 9.59 | 0.00 | 0.00 | 0.00 |
October | 78.21 | 31.14 | 47.07 | 157.48 | 45.87 | 0.00 | 0.00 | 0.00 |
November | 70.76 | 30.16 | 40.60 | 116.60 | 87.02 | 0.00 | 0.00 | 0.00 |
December | 60.55 | 23.09 | 37.46 | 75.41 | 116.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81.17 | 29.80 | 51.37 | 171.94 | 46.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.55 | 12.15 | 37.46 | 75.41 | 0.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.78 | 52.89 | 61.49 | 280.87 | 120.22 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171302E+09 | 68758244.32 | 0.102544E+09 | 0.190949E+09 | 0.302657E+09 |
February | 0.187971E+09 | 77603017.01 | 0.110368E+09 | 0.264998E+09 | 0.214247E+09 |
March | 0.253873E+09 | 0.104790E+09 | 0.149083E+09 | 0.446860E+09 | 0.142717E+09 |
April | 0.292300E+09 | 0.136285E+09 | 0.156015E+09 | 0.653183E+09 | 48094840.99 |
May | 0.297293E+09 | 0.131803E+09 | 0.165490E+09 | 0.772054E+09 | 8658563.62 |
June | 0.234153E+09 | 77691470.85 | 0.156461E+09 | 0.669473E+09 | 6775418.51 |
July | 0.203359E+09 | 42943938.22 | 0.160415E+09 | 0.569056E+09 | 2360561.03 |
August | 0.183235E+09 | 31887135.15 | 0.151348E+09 | 0.475299E+09 | 7088070.24 |
September | 0.189451E+09 | 52833016.04 | 0.136618E+09 | 0.429364E+09 | 24603460.24 |
October | 0.214145E+09 | 86500154.89 | 0.127645E+09 | 0.425382E+09 | 0.118408E+09 |
November | 0.183745E+09 | 78871726.17 | 0.104874E+09 | 0.289976E+09 | 0.213837E+09 |
December | 0.165559E+09 | 65595291.96 | 99963664.62 | 0.198276E+09 | 0.300484E+09 |
Annual Sum or Average | 0.257639E+10 | 0.955562E+09 | 0.162082E+10 | 0.538487E+10 | 0.138993E+10 |
Minimum of Months | 0.165559E+09 | 31887135.15 | 99963664.62 | 0.190949E+09 | 2360561.03 |
Maximum of Months | 0.297293E+09 | 0.136285E+09 | 0.165490E+09 | 0.772054E+09 | 0.302657E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.727392E+09 | 0.441982E+09 | 0.285410E+09 | 0.108868E+10 | 0.596079E+09 |
February | 0.624711E+09 | 0.346982E+09 | 0.277729E+09 | 0.101784E+10 | 0.433304E+09 |
March | 0.591373E+09 | 0.261204E+09 | 0.330169E+09 | 0.112396E+10 | 0.296810E+09 |
April | 0.401984E+09 | 0.113452E+09 | 0.288532E+09 | 0.103471E+10 | 0.100243E+09 |
May | 0.298716E+09 | 22112978.05 | 0.276603E+09 | 0.999823E+09 | 17352931.87 |
June | 0.264433E+09 | 4512464.01 | 0.259921E+09 | 0.943855E+09 | 13571952.09 |
July | 0.285023E+09 | 3920248.80 | 0.281103E+09 | 0.906030E+09 | 4818043.75 |
August | 0.302349E+09 | 16147681.32 | 0.286201E+09 | 0.841502E+09 | 14275969.40 |
September | 0.392248E+09 | 0.101809E+09 | 0.290440E+09 | 0.918719E+09 | 50007644.37 |
October | 0.697316E+09 | 0.389378E+09 | 0.307938E+09 | 0.140247E+10 | 0.241714E+09 |
November | 0.842888E+09 | 0.557131E+09 | 0.285757E+09 | 0.147951E+10 | 0.433193E+09 |
December | 0.777331E+09 | 0.487097E+09 | 0.290234E+09 | 0.120637E+10 | 0.588431E+09 |
Annual Sum or Average | 0.620576E+10 | 0.274573E+10 | 0.346004E+10 | 0.129635E+11 | 0.278980E+10 |
Minimum of Months | 0.264433E+09 | 3920248.80 | 0.259921E+09 | 0.841502E+09 | 4818043.75 |
Maximum of Months | 0.842888E+09 | 0.557131E+09 | 0.330169E+09 | 0.147951E+10 | 0.596079E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167592E+09 | 65220211.76 | 0.102372E+09 | 0.202774E+09 | 0.322002E+09 |
February | 0.173099E+09 | 63791643.98 | 0.109308E+09 | 0.249662E+09 | 0.226726E+09 |
March | 0.248516E+09 | 99340234.55 | 0.149175E+09 | 0.442709E+09 | 0.150108E+09 |
April | 0.292324E+09 | 0.137089E+09 | 0.155236E+09 | 0.654146E+09 | 49167377.24 |
May | 0.286030E+09 | 0.121328E+09 | 0.164702E+09 | 0.752288E+09 | 8905900.04 |
June | 0.259992E+09 | 0.100988E+09 | 0.159005E+09 | 0.719488E+09 | 6701529.91 |
July | 0.199359E+09 | 38775257.33 | 0.160583E+09 | 0.559359E+09 | 2606698.62 |
August | 0.183090E+09 | 32540604.47 | 0.150549E+09 | 0.475732E+09 | 7177201.21 |
September | 0.194772E+09 | 57179271.37 | 0.137592E+09 | 0.440127E+09 | 24844713.20 |
October | 0.209485E+09 | 83416332.71 | 0.126068E+09 | 0.421788E+09 | 0.122868E+09 |
November | 0.183400E+09 | 78163883.48 | 0.105236E+09 | 0.302232E+09 | 0.225551E+09 |
December | 0.162168E+09 | 61838181.87 | 0.100330E+09 | 0.201973E+09 | 0.312273E+09 |
Annual Sum or Average | 0.255983E+10 | 0.939670E+09 | 0.162016E+10 | 0.542228E+10 | 0.145893E+10 |
Minimum of Months | 0.162168E+09 | 32540604.47 | 0.100330E+09 | 0.201973E+09 | 2606698.62 |
Maximum of Months | 0.292324E+09 | 0.137089E+09 | 0.164702E+09 | 0.752288E+09 | 0.322002E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 541.32 | 443.63 | 398.11 | 215.04 | 183.07 | 0.00 | 0.00 |
February | 626.43 | 354.35 | 407.48 | 201.88 | 205.61 | 0.00 | 0.00 |
March | 747.01 | 215.39 | 408.36 | 173.74 | 234.63 | 0.00 | 0.00 |
April | 902.30 | 74.93 | 380.64 | 149.24 | 231.40 | 0.00 | 0.00 |
May | 942.35 | 12.97 | 329.32 | 102.76 | 226.55 | 0.00 | 0.00 |
June | 899.94 | 10.37 | 292.66 | 70.68 | 221.99 | 0.00 | 0.00 |
July | 759.57 | 3.65 | 256.77 | 31.97 | 224.80 | 0.00 | 0.00 |
August | 669.24 | 10.64 | 249.65 | 30.08 | 219.57 | 0.00 | 0.00 |
September | 689.73 | 38.21 | 299.56 | 81.72 | 217.84 | 0.00 | 0.00 |
October | 838.45 | 178.86 | 418.51 | 208.82 | 209.70 | 0.00 | 0.00 |
November | 795.38 | 332.75 | 466.83 | 275.53 | 191.31 | 0.00 | 0.00 |
December | 590.40 | 439.04 | 412.58 | 229.44 | 183.14 | 0.00 | 0.00 |
Annual Sum or Average | 750.41 | 175.45 | 359.65 | 147.16 | 212.49 | 0.00 | 0.00 |
Minimum of Months | 541.32 | 3.65 | 249.65 | 30.08 | 183.07 | 0.00 | 0.00 |
Maximum of Months | 942.35 | 443.63 | 466.83 | 275.53 | 234.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.144988E+10 | 0.118822E+10 | 0.106629E+10 | 0.575960E+09 | 0.490326E+09 | 0.00 | 0.00 |
February | 0.151547E+10 | 0.857246E+09 | 0.985781E+09 | 0.488376E+09 | 0.497405E+09 | 0.00 | 0.00 |
March | 0.200080E+10 | 0.576902E+09 | 0.109376E+10 | 0.465334E+09 | 0.628428E+09 | 0.00 | 0.00 |
April | 0.233875E+10 | 0.194213E+09 | 0.986607E+09 | 0.386825E+09 | 0.599782E+09 | 0.00 | 0.00 |
May | 0.252398E+10 | 34736386.80 | 0.882039E+09 | 0.275244E+09 | 0.606795E+09 | 0.00 | 0.00 |
June | 0.233265E+10 | 26882019.45 | 0.758579E+09 | 0.183192E+09 | 0.575387E+09 | 0.00 | 0.00 |
July | 0.203443E+10 | 9767056.48 | 0.687741E+09 | 85639444.35 | 0.602102E+09 | 0.00 | 0.00 |
August | 0.179248E+10 | 28487360.90 | 0.668674E+09 | 80575420.94 | 0.588099E+09 | 0.00 | 0.00 |
September | 0.178779E+10 | 99031691.19 | 0.776470E+09 | 0.211821E+09 | 0.564650E+09 | 0.00 | 0.00 |
October | 0.224570E+10 | 0.479049E+09 | 0.112095E+10 | 0.559294E+09 | 0.561651E+09 | 0.00 | 0.00 |
November | 0.206162E+10 | 0.862487E+09 | 0.121003E+10 | 0.714166E+09 | 0.495867E+09 | 0.00 | 0.00 |
December | 0.158134E+10 | 0.117591E+10 | 0.110506E+10 | 0.614530E+09 | 0.490528E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.236649E+11 | 0.553293E+10 | 0.113420E+11 | 0.464096E+10 | 0.670102E+10 | 0.00 | 0.00 |
Minimum of Months | 0.144988E+10 | 9767056.48 | 0.668674E+09 | 80575420.94 | 0.490326E+09 | 0.00 | 0.00 |
Maximum of Months | 0.252398E+10 | 0.118822E+10 | 0.121003E+10 | 0.714166E+09 | 0.628428E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.111955E+11 | -0.104863E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -709216039.8 | 58.99 | 0.00 | 0.00 |
February | 0.988512E+10 | -0.926692E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -618200179.1 | 58.99 | 0.00 | 0.00 |
March | 0.102613E+11 | -0.959837E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -662952032.0 | 58.98 | 0.00 | 0.00 |
April | 0.894584E+10 | -0.831160E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -634242240.5 | 58.99 | 0.00 | 0.00 |
May | 0.823303E+10 | -0.758562E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -647409658.9 | 58.98 | 0.00 | 0.00 |
June | 0.721167E+10 | -0.659746E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -614204854.9 | 58.98 | 0.00 | 0.00 |
July | 0.710351E+10 | -0.648142E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -622097333.0 | 58.98 | 0.00 | 0.00 |
August | 0.735078E+10 | -0.673030E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -620478601.3 | 58.98 | 0.00 | 0.00 |
September | 0.779922E+10 | -0.717891E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -620317210.5 | 58.99 | 0.00 | 0.00 |
October | 0.907131E+10 | -0.841389E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -657418508.0 | 58.98 | 0.00 | 0.00 |
November | 0.977635E+10 | -0.912801E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -648344399.0 | 58.98 | 0.00 | 0.00 |
December | 0.108701E+11 | -0.101727E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -697453937.7 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.107704E+12 | -0.999515E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.775233E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.710351E+10 | -0.104863E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -709216039.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.111955E+11 | -0.648142E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -614204854.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.29 | 0.24 | 01-JAN-07:00 | 1325.88 | 23.21 | 108.17 | 285.67 | 1325.14 | 23.12 | 106.83 | 284.83 |
February | 303.83 | 0.27 | 0.24 | 01-FEB-07:49 | 1269.80 | 22.66 | 91.33 | 276.50 | 1291.18 | 22.57 | 93.33 | 272.83 |
March | 364.50 | 0.27 | 0.24 | 01-MAR-07:30 | 1453.60 | 20.43 | 57.83 | 338.67 | 1107.95 | 18.50 | 3.67 | 338.17 |
April | 379.83 | 0.29 | 0.24 | 01-APR-06:00 | 993.25 | 17.22 | 0.00 | 338.67 | 1077.48 | 17.23 | 0.00 | 339.00 |
May | 406.00 | 0.28 | 0.24 | 01-MAY-06:10 | 926.70 | 17.11 | 0.00 | 368.50 | 1153.10 | 17.08 | 0.00 | 364.33 |
June | 386.67 | 0.29 | 0.24 | 01-JUN-06:49 | 907.02 | 16.78 | 0.00 | 344.33 | 935.55 | 16.86 | 0.00 | 346.17 |
July | 379.83 | 0.27 | 0.24 | 01-JUL-06:19 | 819.19 | 17.29 | 0.00 | 343.17 | 858.98 | 17.31 | 0.00 | 345.33 |
August | 372.50 | 0.28 | 0.24 | 01-AUG-06:40 | 847.38 | 17.31 | 0.00 | 330.00 | 845.79 | 17.31 | 0.00 | 331.17 |
September | 344.33 | 0.28 | 0.24 | 01-SEP-06:00 | 1113.03 | 18.15 | 5.83 | 311.33 | 982.21 | 18.14 | 6.67 | 313.17 |
October | 347.33 | 0.29 | 0.24 | 01-OCT-06:49 | 1152.94 | 20.26 | 60.67 | 309.83 | 1138.72 | 20.19 | 60.67 | 308.33 |
November | 317.83 | 0.27 | 0.24 | 01-NOV-07:10 | 1253.58 | 23.40 | 110.17 | 287.33 | 1505.72 | 23.14 | 106.67 | 285.67 |
December | 315.50 | 0.28 | 0.24 | 01-DEC-07:30 | 1403.26 | 25.22 | 133.50 | 287.83 | 1475.83 | 23.28 | 96.83 | 283.83 |
Annual Sum or Average | 4237.50 | 0.28 | 1107.95 | 19.69 | 567.50 | 3821.83 | 1127.49 | 19.34 | 474.67 | 3812.83 | ||
Minimum of Months | 303.83 | 0.27 | 0.24 | 819.19 | 16.78 | 0.00 | 276.50 | 845.79 | 16.86 | 0.00 | 272.83 | |
Maximum of Months | 406.00 | 0.29 | 0.24 | 1453.60 | 25.22 | 133.50 | 368.50 | 1505.72 | 23.28 | 106.83 | 364.33 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.382523E+10 | 11680.31 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104209E+10 | 9134.03 | 02-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 469219.95 | 356.79 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127033E+09 | 4830.58 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.225277E+10 | 11744.80 | 31-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.724759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.382523E+10 | 11744.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.272662E+09 | 6533.23 | 01-JAN-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2500153.87 | 581.77 | 02-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 67686911.97 | 5528.79 | 23-DEC-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.272662E+09 | 6533.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.149375E+10 | 0.128428E+10 | 11780.89 | 15-JAN-03:01 | 7355.29 | 0.00 |
February | 0.00 | 0.00 | 0.568721E+10 | 0.470271E+10 | 17506.17 | 23-FEB-03:01 | 11805.29 | 0.00 |
March | 0.00 | 0.00 | 0.183985E+11 | 0.147213E+11 | 42721.09 | 29-MAR-02:61 | 26011.67 | 0.00 |
April | 0.00 | 0.00 | 0.353194E+11 | 0.293026E+11 | 74005.21 | 27-APR-02:61 | 43114.39 | 0.00 |
May | 0.00 | 0.00 | 0.546535E+11 | 0.394829E+11 | 74803.72 | 22-MAY-02:61 | 33962.05 | 0.00 |
June | 0.00 | 0.00 | 0.650736E+11 | 0.402531E+11 | 74803.72 | 01-JUN-02:61 | 40265.11 | 0.00 |
July | 0.00 | 0.00 | 0.749683E+11 | 0.370305E+11 | 74803.72 | 13-JUL-02:02 | 25029.59 | 0.00 |
August | 0.00 | 0.00 | 0.732675E+11 | 0.334322E+11 | 74803.72 | 13-AUG-02:61 | 25938.77 | 0.00 |
September | 0.00 | 0.00 | 0.582030E+11 | 0.289820E+11 | 74803.72 | 26-SEP-02:61 | 38701.82 | 0.00 |
October | 0.00 | 0.00 | 0.315470E+11 | 0.223923E+11 | 74803.72 | 01-OCT-02:61 | 41708.84 | 0.00 |
November | 0.00 | 0.00 | 0.129573E+11 | 0.104620E+11 | 41953.62 | 09-NOV-03:01 | 25404.68 | 0.00 |
December | 0.00 | 0.00 | 0.287670E+10 | 0.239949E+10 | 11854.33 | 28-DEC-14:00 | 9978.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.434446E+12 | 0.264445E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.149375E+10 | 0.128428E+10 | 11780.89 | 7355.29 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.749683E+11 | 0.402531E+11 | 74803.72 | 43114.39 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.235879E+10 | 0.180363E+10 | 29900.35 | 12-JAN-03:01 | 18531.52 | 0.00 |
February | 0.00 | 0.00 | 0.719965E+10 | 0.564436E+10 | 29900.35 | 20-FEB-03:01 | 17487.72 | 0.00 |
March | 0.00 | 0.00 | 0.193183E+11 | 0.158997E+11 | 31083.25 | 29-MAR-02:11 | 16153.26 | 0.00 |
April | 0.00 | 0.00 | 0.361655E+11 | 0.325114E+11 | 32943.98 | 20-APR-02:61 | 20860.10 | 0.00 |
May | 0.00 | 0.00 | 0.572559E+11 | 0.461420E+11 | 33221.26 | 24-MAY-02:61 | 14020.09 | 0.00 |
June | 0.00 | 0.00 | 0.664286E+11 | 0.455446E+11 | 33221.26 | 24-JUN-12:20 | 10756.17 | 0.00 |
July | 0.00 | 0.00 | 0.762972E+11 | 0.387360E+11 | 33221.26 | 19-JUL-04:02 | 10031.10 | 0.00 |
August | 0.00 | 0.00 | 0.760476E+11 | 0.330026E+11 | 33221.26 | 19-AUG-20:40 | 9593.41 | 0.00 |
September | 0.00 | 0.00 | 0.669022E+11 | 0.317359E+11 | 33221.26 | 13-SEP-19:10 | 13047.30 | 0.00 |
October | 0.00 | 0.00 | 0.335420E+11 | 0.244212E+11 | 33221.26 | 06-OCT-10:53 | 18186.02 | 0.00 |
November | 0.00 | 0.00 | 0.140753E+11 | 0.113512E+11 | 29900.35 | 13-NOV-03:11 | 16008.68 | 0.00 |
December | 0.00 | 0.00 | 0.431328E+10 | 0.330991E+10 | 29900.35 | 17-DEC-03:01 | 16622.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.459904E+12 | 0.290102E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.235879E+10 | 0.180363E+10 | 29900.35 | 9593.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.762972E+11 | 0.461420E+11 | 33221.26 | 20860.10 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4207.04 | 15410.56 | 18-JAN-14:00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 4122.46 | 15317.90 | 01-FEB-13:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3878.15 | 14662.34 | 01-MAR-13:20 |
April | 0.00 | 0.00 | 01-APR-00:02 | 3499.71 | 13379.47 | 01-APR-12:45 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 3127.30 | 11908.79 | 01-MAY-13:00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 2842.78 | 10558.86 | 01-JUN-12:30 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 2714.41 | 9769.24 | 01-JUL-12:30 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 2810.95 | 10394.62 | 31-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 3065.11 | 11636.15 | 30-SEP-12:25 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 3434.76 | 13155.23 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3814.69 | 14462.12 | 30-NOV-13:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4088.87 | 15281.68 | 31-DEC-13:15 |
Annual Sum or Average | 0.00 | 3463.57 | ||||
Minimum of Months | 0.00 | 0.00 | 2714.41 | 9769.24 | ||
Maximum of Months | 0.00 | 0.00 | 4207.04 | 15410.56 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:02 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | -0.0 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.120661E+10 | 0.24 | 503.64 | 01-JAN-00:03 | 0.27 |
February | 0.110064E+10 | 0.24 | 503.64 | 01-FEB-00:05 | 0.27 |
March | 0.125789E+10 | 0.25 | 503.64 | 01-MAR-00:10 | 0.27 |
April | 0.124509E+10 | 0.26 | 503.64 | 01-APR-00:15 | 0.27 |
May | 0.128892E+10 | 0.26 | 503.64 | 01-MAY-00:08 | 0.27 |
June | 0.124755E+10 | 0.25 | 503.64 | 01-JUN-00:08 | 0.27 |
July | 0.128953E+10 | 0.25 | 503.64 | 01-JUL-00:06 | 0.27 |
August | 0.128961E+10 | 0.25 | 503.64 | 01-AUG-00:05 | 0.26 |
September | 0.124704E+10 | 0.25 | 503.64 | 01-SEP-00:05 | 0.26 |
October | 0.128509E+10 | 0.26 | 503.64 | 01-OCT-00:06 | 0.27 |
November | 0.120616E+10 | 0.25 | 503.64 | 01-NOV-00:40 | 0.27 |
December | 0.120933E+10 | 0.24 | 503.64 | 01-DEC-00:10 | 0.27 |
Annual Sum or Average | 0.148735E+11 | 0.25 | |||
Minimum of Months | 0.110064E+10 | 0.24 | 503.64 | 0.26 | |
Maximum of Months | 0.128961E+10 | 0.26 | 503.64 | 0.27 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.286466E+10 | 0.46 | 1541.46 | 21-JAN-07:10 | 0.62 |
February | 0.252605E+10 | 0.46 | 1475.52 | 02-FEB-07:10 | 0.61 |
March | 0.277381E+10 | 0.48 | 1598.20 | 12-MAR-02:61 | 0.63 |
April | 0.270360E+10 | 0.48 | 3097.42 | 27-APR-02:61 | 0.89 |
May | 0.291719E+10 | 0.49 | 3097.42 | 02-MAY-02:61 | 0.89 |
June | 0.305247E+10 | 0.51 | 3097.42 | 01-JUN-02:61 | 0.89 |
July | 0.321748E+10 | 0.51 | 3097.42 | 01-JUL-02:61 | 0.89 |
August | 0.318796E+10 | 0.51 | 3097.42 | 01-AUG-02:61 | 0.88 |
September | 0.283667E+10 | 0.49 | 3097.42 | 01-SEP-02:61 | 0.88 |
October | 0.279109E+10 | 0.48 | 3097.42 | 01-OCT-02:61 | 0.89 |
November | 0.268649E+10 | 0.48 | 1585.51 | 09-NOV-03:01 | 0.63 |
December | 0.282388E+10 | 0.46 | 1543.13 | 31-DEC-07:10 | 0.62 |
Annual Sum or Average | 0.343814E+11 | 0.48 | |||
Minimum of Months | 0.252605E+10 | 0.46 | 1475.52 | 0.61 | |
Maximum of Months | 0.321748E+10 | 0.51 | 3097.42 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.122355E+10 | 0.50 | 1351.29 | 12-JAN-03:01 | 0.93 |
February | 0.110827E+10 | 0.51 | 1351.29 | 07-FEB-03:01 | 0.93 |
March | 0.130007E+10 | 0.54 | 1351.29 | 01-MAR-03:01 | 0.93 |
April | 0.164686E+10 | 0.63 | 1351.29 | 01-APR-02:11 | 0.93 |
May | 0.239055E+10 | 0.73 | 1351.29 | 01-MAY-02:61 | 0.92 |
June | 0.276999E+10 | 0.80 | 1351.29 | 01-JUN-02:61 | 0.92 |
July | 0.316503E+10 | 0.83 | 1351.29 | 01-JUL-02:61 | 0.92 |
August | 0.313540E+10 | 0.83 | 1351.29 | 01-AUG-02:61 | 0.91 |
September | 0.274282E+10 | 0.79 | 1351.29 | 01-SEP-02:61 | 0.91 |
October | 0.156292E+10 | 0.60 | 1351.29 | 01-OCT-02:61 | 0.92 |
November | 0.120981E+10 | 0.53 | 1351.29 | 01-NOV-02:61 | 0.93 |
December | 0.122292E+10 | 0.50 | 1351.29 | 01-DEC-03:01 | 0.93 |
Annual Sum or Average | 0.234782E+11 | 0.65 | |||
Minimum of Months | 0.110827E+10 | 0.50 | 1351.29 | 0.91 | |
Maximum of Months | 0.316503E+10 | 0.83 | 1351.29 | 0.93 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 52.24 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 53.45 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 53.13 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 53.69 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 54.07 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 55.19 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:10 | 0.00 | 0.00 | 55.12 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 55.69 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 55.37 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 53.56 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 54.56 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 53.27 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 52.24 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 55.69 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 42.70 | 42.70 | 4207.04 | 15410.56 | 18-JAN-14:00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 53.54 | 53.54 | 4122.46 | 15317.90 | 01-FEB-13:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 53.39 | 53.39 | 3878.15 | 14662.34 | 01-MAR-13:20 |
April | 0.00 | 0.00 | 01-APR-00:02 | 53.94 | 53.94 | 3499.71 | 13379.47 | 01-APR-12:45 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 46.30 | 46.30 | 3127.30 | 11908.79 | 01-MAY-13:00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 55.14 | 55.14 | 2842.78 | 10558.86 | 01-JUN-12:30 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 54.95 | 54.95 | 2714.41 | 9769.24 | 01-JUL-12:30 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 55.58 | 55.58 | 2810.95 | 10394.62 | 31-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 55.63 | 55.63 | 3065.11 | 11636.15 | 30-SEP-12:25 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 46.69 | 46.69 | 3434.76 | 13155.23 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 54.47 | 54.47 | 3814.69 | 14462.12 | 30-NOV-13:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 53.55 | 53.55 | 4088.87 | 15281.68 | 31-DEC-13:15 |
Annual Sum or Average | 0.00 | 3463.57 | ||||||
Minimum of Months | 0.00 | 0.00 | 42.70 | 42.70 | 2714.41 | 9769.24 | ||
Maximum of Months | 0.00 | 0.00 | 55.63 | 55.63 | 4207.04 | 15410.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.332062E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.421086E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.800793E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.128392E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.184410E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.208809E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.221280E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.211710E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.173520E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.114316E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.639056E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.369191E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.149866E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.332062E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.221280E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.189182E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.303830E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.617549E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.108900E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.170384E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.194442E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.212939E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.207257E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.180954E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.963345E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.478882E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.241324E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.135429E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.189182E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.212939E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.286466E+10 | 0.149375E+10 | 0.382523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.252605E+10 | 0.568721E+10 | 0.104209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.277381E+10 | 0.183985E+11 | 469219.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.270360E+10 | 0.353194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.291719E+10 | 0.546535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.305247E+10 | 0.650736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.321748E+10 | 0.749683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.318796E+10 | 0.732675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.283667E+10 | 0.582030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.279109E+10 | 0.315470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.268649E+10 | 0.129573E+11 | 0.127033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.282388E+10 | 0.287670E+10 | 0.225277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.343814E+11 | 0.434446E+12 | 0.724759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.252605E+10 | 0.149375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.321748E+10 | 0.749683E+11 | 0.382523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.122355E+10 | 0.235879E+10 | 0.272662E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110827E+10 | 0.719965E+10 | 2500153.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130007E+10 | 0.193183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164686E+10 | 0.361655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.239055E+10 | 0.572559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.276999E+10 | 0.664286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.316503E+10 | 0.762972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.313540E+10 | 0.760476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.274282E+10 | 0.669022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156292E+10 | 0.335420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120981E+10 | 0.140753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122292E+10 | 0.431328E+10 | 67686911.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234782E+11 | 0.459904E+12 | 0.342849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110827E+10 | 0.235879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.316503E+10 | 0.762972E+11 | 0.272662E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.286466E+10 | 0.00 | 0.00 | 0.00 | 0.455961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.252605E+10 | 0.00 | 0.00 | 0.00 | 0.168481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.277381E+10 | 0.00 | 0.00 | 0.00 | 0.523411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.270360E+10 | 0.00 | 0.00 | 0.00 | 0.101356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.291719E+10 | 0.00 | 0.00 | 0.00 | 0.155238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.305247E+10 | 0.00 | 0.00 | 0.00 | 0.178284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.321748E+10 | 0.00 | 0.00 | 0.00 | 0.189105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.318796E+10 | 0.00 | 0.00 | 0.00 | 0.179831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.283667E+10 | 0.00 | 0.00 | 0.00 | 0.145153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.279109E+10 | 0.00 | 0.00 | 0.00 | 0.864051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.268649E+10 | 0.00 | 0.00 | 0.00 | 0.370407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.282388E+10 | 0.00 | 0.00 | 0.00 | 0.868029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.343814E+11 | 0.00 | 0.00 | 0.00 | 0.115484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.252605E+10 | 0.00 | 0.00 | 0.00 | 0.455961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.321748E+10 | 0.00 | 0.00 | 0.00 | 0.189105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.122355E+10 | 0.00 | 0.00 | 0.00 | 0.668273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110827E+10 | 0.00 | 0.00 | 0.00 | 0.193004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130007E+10 | 0.00 | 0.00 | 0.00 | 0.487542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164686E+10 | 0.00 | 0.00 | 0.00 | 0.924317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.239055E+10 | 0.00 | 0.00 | 0.00 | 0.146479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.276999E+10 | 0.00 | 0.00 | 0.00 | 0.166742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.316503E+10 | 0.00 | 0.00 | 0.00 | 0.181289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.313540E+10 | 0.00 | 0.00 | 0.00 | 0.175903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.274282E+10 | 0.00 | 0.00 | 0.00 | 0.153525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156292E+10 | 0.00 | 0.00 | 0.00 | 0.807053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120981E+10 | 0.00 | 0.00 | 0.00 | 0.357901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122292E+10 | 0.00 | 0.00 | 0.00 | 0.119032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234782E+11 | 0.00 | 0.00 | 0.00 | 0.111951E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110827E+10 | 0.00 | 0.00 | 0.00 | 0.668273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.316503E+10 | 0.00 | 0.00 | 0.00 | 0.181289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.630631E+10 | 0.00 | 0.00 | 7166102.16 | 0.00 | 0.297644E+10 | 0.187876E+10 | 0.00 | 3.57 |
February | 0.411289E+10 | 51331445.69 | 0.00 | 18336552.54 | 0.00 | 0.619068E+09 | 0.220797E+10 | 0.00 | 3.60 |
March | 0.138637E+10 | 0.181951E+10 | 0.00 | 22194026.15 | 1291334.66 | 0.00 | 0.188309E+10 | 0.00 | 3.65 |
April | 43939635.55 | 0.730515E+10 | 0.00 | 4570387.58 | 84494465.91 | 0.00 | 0.284824E+09 | 0.00 | 3.72 |
May | 2400377.17 | 0.161693E+11 | 0.00 | 436343.06 | 0.275489E+09 | 0.00 | 394229.40 | 0.00 | 3.83 |
June | 0.00 | 0.220527E+11 | 0.00 | 85590.57 | 0.471661E+09 | 0.00 | 418287.70 | 0.00 | 3.89 |
July | 0.00 | 0.276170E+11 | 0.00 | 77556.68 | 0.548524E+09 | 0.00 | 386404.85 | 0.00 | 3.93 |
August | 324665.53 | 0.261211E+11 | 0.00 | 148412.02 | 0.486636E+09 | 0.00 | 35579.96 | 0.00 | 3.92 |
September | 797135.83 | 0.186643E+11 | 0.00 | 384859.23 | 0.312275E+09 | 0.00 | 169634.41 | 0.00 | 3.89 |
October | 0.288279E+09 | 0.532416E+10 | 0.00 | 8715913.95 | 18987850.18 | 0.00 | 0.841637E+09 | 0.00 | 3.71 |
November | 0.279870E+10 | 0.798763E+09 | 0.00 | 22784161.43 | 0.00 | 33973040.53 | 0.238692E+10 | 0.00 | 3.63 |
December | 0.634258E+10 | 0.00 | 0.00 | 12330266.31 | 0.00 | 0.146691E+10 | 0.224100E+10 | 0.00 | 3.57 |
Annual Sum or Average | 0.212826E+11 | 0.125923E+12 | 0.00 | 97230171.68 | 0.219936E+10 | 0.509640E+10 | 0.117256E+11 | 0.00 | 3.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 77556.68 | 0.00 | 0.00 | 35579.96 | 0.00 | 3.57 |
Maximum of Months | 0.634258E+10 | 0.276170E+11 | 0.00 | 22784161.43 | 0.548524E+09 | 0.297644E+10 | 0.238692E+10 | 0.00 | 3.93 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145200E+11 | 493996.58 | 0.00 | 33726247.64 | 0.00 | 0.00 | 0.159796E+11 | 0.00 | 7.02 |
February | 0.719004E+10 | 0.00 | 0.00 | 51771785.54 | 0.00 | 0.00 | 0.148629E+11 | 0.00 | 7.10 |
March | 0.149047E+10 | 0.383190E+09 | 0.00 | 84275958.81 | 343737.94 | 0.00 | 0.126689E+11 | 0.00 | 7.35 |
April | 0.184960E+09 | 0.650206E+10 | 0.00 | 48107885.40 | 15831224.37 | 0.00 | 0.315362E+10 | 0.00 | 8.26 |
May | 11938961.02 | 0.230614E+11 | 0.00 | 3702092.97 | 53776586.32 | 0.00 | 97640224.73 | 0.00 | 9.63 |
June | 194685.27 | 0.333324E+11 | 0.00 | 244192.31 | 63174196.50 | 0.00 | 11142630.68 | 0.00 | 10.60 |
July | 0.00 | 0.429448E+11 | 0.00 | 208846.04 | 60527205.89 | 0.00 | 11535763.42 | 0.00 | 11.21 |
August | 1640789.85 | 0.425050E+11 | 0.00 | 300135.82 | 72614983.32 | 0.00 | 40026862.04 | 0.00 | 11.13 |
September | 9105353.35 | 0.344863E+11 | 0.00 | 873115.28 | 98475721.62 | 0.00 | 0.103140E+09 | 0.00 | 10.51 |
October | 0.525227E+09 | 0.402373E+10 | 0.00 | 63471753.19 | 8640653.13 | 0.00 | 0.500552E+10 | 0.00 | 7.99 |
November | 0.333160E+10 | 192844.29 | 0.00 | 85729561.10 | 0.00 | 0.00 | 0.154696E+11 | 0.00 | 7.21 |
December | 0.116157E+11 | 0.00 | 0.00 | 44227444.55 | 0.00 | 0.00 | 0.172879E+11 | 0.00 | 7.03 |
Annual Sum or Average | 0.388808E+11 | 0.187240E+12 | 0.00 | 0.416639E+09 | 0.373384E+09 | 0.00 | 0.846915E+11 | 0.00 | 8.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 208846.04 | 0.00 | 0.00 | 11142630.68 | 0.00 | 7.02 |
Maximum of Months | 0.145200E+11 | 0.429448E+11 | 0.00 | 85729561.10 | 98475721.62 | 0.00 | 0.172879E+11 | 0.00 | 11.21 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:18
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.290322E+11 | 0.104915E+11 | 0.765651E+11 | 0.329446E+10 | 0.257679E+11 |
February | 0.341183E+11 | 0.659520E+10 | 0.546217E+11 | 0.239689E+10 | 0.361822E+11 |
March | 0.489771E+11 | 0.147704E+10 | 0.331944E+11 | 0.121829E+10 | 0.712838E+11 |
April | 0.581006E+11 | -0.614808E+10 | -0.747128E+10 | 40128411.12 | 0.115681E+12 |
May | 0.628461E+11 | -0.142623E+11 | -0.472988E+11 | -471020348.3 | 0.168920E+12 |
June | 0.575768E+11 | -0.186594E+11 | -0.658790E+11 | -904607273.9 | 0.192160E+12 |
July | 0.466210E+11 | -0.223341E+11 | -0.824285E+11 | -0.107039E+10 | 0.211962E+12 |
August | 0.393621E+11 | -0.222532E+11 | -0.809447E+11 | -844173243.2 | 0.207718E+12 |
September | 0.413898E+11 | -0.165977E+11 | -0.635594E+11 | -518308097.7 | 0.177369E+12 |
October | 0.398577E+11 | -0.437552E+10 | 0.396420E+10 | 0.657149E+09 | 0.107878E+12 |
November | 0.326720E+11 | 0.359598E+10 | 0.468282E+11 | 0.176084E+10 | 0.574124E+11 |
December | 0.260590E+11 | 0.942714E+10 | 0.720656E+11 | 0.342596E+10 | 0.301457E+11 |
Annual Sum or Average | 0.516613E+12 | -0.730436E+11 | -0.603425E+11 | 0.898522E+10 | 0.140248E+13 |
Minimum of Months | 0.260590E+11 | -0.223341E+11 | -0.824285E+11 | -0.107039E+10 | 0.257679E+11 |
Maximum of Months | 0.628461E+11 | 0.104915E+11 | 0.765651E+11 | 0.342596E+10 | 0.211962E+12 |