Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 08:25:22
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1386.49 | 5967.44 | 5967.44 |
Net Site Energy | 1386.49 | 5967.44 | 5967.44 |
Total Source Energy | 2720.76 | 11710.10 | 11710.10 |
Net Source Energy | 2720.76 | 11710.10 | 11710.10 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 134.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 103.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 29.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 276.59 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 82.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 189.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 65.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 584.64 | 801.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 134.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 103.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 29.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 27.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 82.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 189.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 17.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 30.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 134.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 103.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 29.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 27.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 276.59 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 82.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 189.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 65.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 242.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 799.61 | 1397.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1473.99 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2516.27 | 3451.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 242.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 799.61 | 1397.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1473.99 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2516.27 | 3451.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 584.638 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 584.638 | 100.00 |
Total On-Site and Utility Electric Sources | 584.638 | 100.00 |
Total Electricity End Uses | 584.638 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 60.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4671.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 7.5044 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.8503 | 18.52 | 1074.0064 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.6773 | 2.48 | 595.3967 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.6773 | 2.48 | 595.3967 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 7.5044 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.8503 | 18.52 | 1074.0064 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 8.6773 | 1.24 | 595.3967 | |||||||
Conditioned Total | 232.34 | 8.6773 | 1.24 | 595.3967 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 8.6773 | 2.48 | 595.3967 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-JUL-11:00 | 12-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 87179.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19005.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1331.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 13514.13 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4291.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8056.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2151.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 40294.17 | 109025.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 87179.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19005.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1331.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 12146.55 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 4291.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8056.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 530.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 146.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 327.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 92.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 85.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 875.96 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 260.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 205.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 208.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1851.55 | 869.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 629.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1409.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 399.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 368.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3770.11 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1122.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 885.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 898.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7969.03 | 3741.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 629.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1409.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 399.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 368.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3770.11 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1122.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 885.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 898.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7969.03 | 3741.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 2.20 |
KITCHEN DIRECT AIR | 1.32 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.20 | 2.20 | 2.20 | 2.20 | 2.20 | 2.20 | 1.00 | 1.00 | 2.20 |
PSZ-AC_2:2 | 1.32 | 1.32 | 1.32 | 1.32 | 1.32 | 1.32 | 1.00 | 1.000000 | 1.32 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.20 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.32 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 2.20 | 2357.71 |
PSZ-AC_2:2_ADDAQ FAN | 1.32 | 1458.59 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.20 | 2.20 | 2.20 | 1.45 | 54715.02 | 61863.12 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.32 | 1.32 | 1.32 | 0.869495 | 32714.59 | 69865.29 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.20 | 1.10 | 1.47 | 54715.02 | 27357.51 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.32 | 0.658708 | 0.878280 | 32714.59 | 16357.30 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 61863.12 |
PSZ-AC_2:2 HEATING COIL | 69865.29 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 7.504 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 124.291 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.850 | 282.654 | 791.353 | 0.000 | 0.000 | 0.000 | 1083.857 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 871.800 | 7.504 | 9.958 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 871.800 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1144.319 | 9.850 | 182.411 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1144.319 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 515.917 | 4.441 | 82.240 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 851.667 | 7.331 | 135.761 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.6929 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.209 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.33002231E-12 | 0.10712597E-14 | -0.10720425E-12 | 0.10137879E-15 |
34 | 6 | 0.29661659E-07 | 0.19687232E-09 | 0.67865745E-08 | -0.14052424E-12 |
35 | 5 | -0.19512200E-03 | 0.16741682E-05 | -0.10029371E-03 | 0.67057946E-08 |
36 | 4 | 0.29799499 | 0.81016957E-03 | 0.10178761 | -0.34398158E-04 |
37 | 3 | -7.3821031 | 0.24971312E-01 | -2.3732702 | 0.29576512E-01 |
38 | 2 | 41.252923 | 0.88368331E-01 | 15.405914 | -0.33759269 |
39 | 1 | -80.838295 | 0.39713828E-01 | -29.267905 | 1.0848528 |
40 | 0 | 46.824337 | 0.79570062E-03 | 16.288235 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.6141_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.053 | 0.3093 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5856E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.5949E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.4894E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.4765E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.3258E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.8379E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.7474E-004 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.4969E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 5.2087E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.9155E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 5.9486E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 5.5929E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.9143E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.7439E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.5427E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.5434E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.1938E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.2521E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.9679E-003 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0741E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.3067E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0019E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.5001E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 9.7483E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 24063.96037 | 28876.75245 | 1.83614 | 2.20337 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40000 | 1.44733E-002 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 5912.67991 | 7095.21589 | 0.26041 | 0.41606 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -6.30000 | 2.29779E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 17300.63366 | 20760.76039 | 1.09785 | 1.31742 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.54500 | 1.44717E-002 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.14133 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:30:00 | -6.30000 | 2.29779E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 33546.00 | 2.20337 | 2.20337 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 22473.02 | 0.41606 | 0.41606 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 30346.03 | 1.31742 | 1.31742 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 61648.42 | 1.14133 | 1.14133 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.20337 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.31742 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.20337 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.20337 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.20337 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.20337 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.20337 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.20337 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.31742 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.31742 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.31742 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.31742 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.31742 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.31742 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.20337 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.31742 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.20337 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.20337 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2357.71414 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.20337 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.20337 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.20337 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.45423 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.20337 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.10169 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.46891 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 54715.02000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 27357.51000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 54715.02000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 61863.11741 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 61863.11741 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.31742 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.31742 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1458.58941 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.31742 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.31742 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.31742 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.86950 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.31742 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65871 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.87828 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32714.59000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16357.29500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32714.59000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 69865.28806 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 69865.28806 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 53148.9 | 11.66 | 11.61 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 31778.2 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | N/A | 3.491 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | N/A | 3.491 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | N/A | 3.491 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 5.6435112346E-002 | 0.2414758243 | Pass | Pass | 0.2507570378 | 0.9761865012 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2496017850 | 0.4938726937 | Pass | Pass | 6.1645242125E-002 | 0.2009826707 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.2490096986 | 0.2427414451 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 560.55 | 71.69 | 526.68 | 8.55 | 861.89 | 2029.36 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 3.491 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.491 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 7.5044 | 116.17 | 871.80 | LightsWired | LTG_SCH_DINING | 91.35 | 168.00 | 65.56 | 0.0000 | Y | 10.73 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.8503 | 116.17 | 1144.32 | LightsWired | LTG_SCH_KITCHEN | 87.05 | 168.00 | 86.54 | 0.0000 | Y | 18.59 |
Interior Lighting Total | 8.6773 | 232.34 | 2016.12 | 29.32 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.22 | 871.80 | 191.80 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.22 | 871.80 | 191.80 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 216.58 | AstronomicalClock | - | 48.77 | 48.77 | 1.98 | |
EXTERIOR_LIGHTS_B | 1823.66 | AstronomicalClock | - | 83.77 | 73.27 | 25.08 | |
Exterior Lighting Total | 2040.24 | 27.07 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 54715.02 | 38359.61 | 16355.41 | 0.70 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32714.59 | 22935.54 | 9779.05 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 53148.9 | 11.66 | 11.61 | ||||
PSZ-AC_2:2 COOLING COIL | 31778.2 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 61863.12 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 69865.29 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 1.56 | 1211.87 | 778.12 | 1.00 | 0.64 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 2.20 | 2357.71 | 1070.05 | 1.00 | 1.30 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.32 | 1458.59 | 1107.16 | 1.00 | 1.34 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 24063.96 | 28876.75 | 248.57 | 1.836 | 2.203 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.87 | 0.01106 | 34.40 | 0.01447 | 0.416 | 0.00 |
KITCHEN | 17300.63 | 20760.76 | 178.71 | 1.098 | 1.317 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.01014 | 33.55 | 0.01447 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 5912.68 | 7095.22 | 61.08 | 0.260 | 0.416 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00759 | -6.30 | 0.00230 | 0.416 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.141 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:30:00 | 18.89 | 22.90 | 0.00206 | -6.30 | 0.00230 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.20 | 2.20 | 0.42 | 0.42 | 2.2034 | 2.2034 | 2.2034 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.32 | 1.32 | 1.14 | 1.14 | 1.3174 | 1.3174 | 1.3174 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 54715.020 | 38359.606 | 2.203370 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27357.51 | 17749.85 | 1.468913 | 25.85 | 19.19 | 0.01170829 | 11.90 | 11.40 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 28.3241 | 23.87 | 0.01106465 | 57.6567 | 24063.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 61863.117 | 61863.117 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 61863.12 | 61863.12 | 2.203374 | 15.93 | 11.06 | 0.00650482 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 18.8827 | 19.70 | 0.00748414 | 50.5911 | 3477.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 32714.590 | 22935.545 | 1.317420 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 16357.30 | 10037.68 | 0.878280 | 32.54 | 22.67 | 0.01389297 | 11.87 | 11.39 | 0.00850000 | 33.55 | 0.01447170 | 23.31 | 129.9510 | 26.10 | 0.01014180 | 46.3313 | 17300.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 69865.288 | 69865.288 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 69865.29 | 69865.29 | 1.317417 | -5.46 | -5.82 | 0.00226731 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 86.6342 | 23.33 | 0.00206974 | 11.3015 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 54715.020 | 38359.606 | 2.203370 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.6051 | 1004.8586 | 1.1610 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.203374 | 2.55806531 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 27357.51 | 17749.85 | 1.0000 | 1.70537392 | 1.468913 | 25.85 | 19.19 | 0.01170829 | 55819.9 | 11.90 | 11.40 | 0.00850000 | 33405.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27357.51 | 34.40 | 0.01447326 | 23.54 | 0.41605618 | 28.3241 | 23.86 | 0.01106465 | 23.87 | 0.01106465 | 57.6567 | 24063.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61863.117 | 61863.117 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.203374 | 2.55806531 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 61863.12 | 61863.12 | 1.0000 | 2.55806531 | 2.203374 | 15.93 | 11.06 | 0.00650482 | 32471.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61863.12 | -6.30 | 0.00229779 | -6.30 | 0.41605618 | 18.8827 | 21.11 | 0.00748414 | 19.70 | 0.00748414 | 50.5911 | 3477.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32714.590 | 22935.545 | 1.317420 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1030.6663 | 1004.8586 | 1.1610 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.317417 | 1.52948988 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 16357.30 | 10037.68 | 1.0000 | 1.01966248 | 0.878280 | 32.54 | 22.67 | 0.01389297 | 68288.2 | 11.87 | 11.39 | 0.00850000 | 33377.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16357.30 | 33.55 | 0.01447170 | 23.31 | 1.14133354 | 129.9510 | 26.06 | 0.01014180 | 26.10 | 0.01014180 | 46.3313 | 17300.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 69865.288 | 69865.288 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.317417 | 1.52948988 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 69865.29 | 69865.29 | 1.0000 | 1.52948988 | 1.317417 | -5.46 | -5.82 | 0.00226731 | 163.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 69865.29 | -6.30 | 0.00229779 | -6.30 | 1.14133354 | 86.6342 | 0.00 | 0.00206974 | 23.33 | 0.00206974 | 11.3015 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 0.42 | 2.20 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 1.14 | 1.32 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 4015.50 | 5238.33 | 2435.67 |
KITCHEN | 5523.50 | 6038.33 | 4576.33 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5615.17 | 7136.33 | 4671.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 31.17 | 107.67 | 0.00 | 0.00 |
KITCHEN | 0.00 | 354.67 | 0.00 | 60.33 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 31.17 | 355.83 | 0.00 | 60.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 5.117 | 4.248 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 9.565 | 0.031 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.066 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 8.513 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 13213569.30 | 0.00 | 13213569.30 | 10709627.02 | 23923196.32 | 13120747.55 | 1435.84 | 6072.87 | 1251.29 | 592.43 |
KITCHEN | 25424962.94 | 0.00 | 25424962.94 | 132069.92 | 25557032.87 | 35993094.65 | 7960.92 | 779.39 | 19.69 | 956.43 |
Total Facility | 38638532.24 | 0.00 | 38638532.24 | 10841696.94 | 49480229.19 | 49113842.20 | 7968.98 | 6073.60 | 1268.81 | 1033.06 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4954 | 0.0000 | 0.4954 | 0.4118 | 0.9072 | 0.4161 | 0.00 | 5952.05 | 1234.95 |
KITCHEN | 0.9216 | 0.0000 | 0.9216 | 0.0030 | 0.9246 | 1.1413 | 6407.48 | 778.00 | 1.52 |
Total Facility | 1.4170 | 0.0000 | 1.4170 | 0.4148 | 1.8318 | 1.5574 | 6407.48 | 5952.15 | 1235.92 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 17810347.07 | 0.00 | 17810347.07 | 13120747.55 | 1430.04 | 0.24 | 7329.72 | 592.43 |
PSZ-AC_2:2 | 34269325.15 | 0.00 | 34269325.15 | 35993094.65 | 1405.31 | 2.94 | 7351.75 | 956.43 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6677 | 0.0000 | 0.6677 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.2422 | 0.0000 | 1.2422 | 1.1413 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1182.76 | 528.61 | 6068.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 248.48 | 2070.91 | 5824.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.3721 | 0.9184 | 0.5609 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.1871 | 1.3933 | 1.2100 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 374 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 584.64 | 5208.12 | 12-FEB-01:10 | 40294.17 | 07-JUL-12:00 |
Electricity:Building | 323.77 | 2948.69 | 01-JAN-01:10 | 19261.27 | 02-JAN-11:10 |
Electricity:Zone:DINING | 81.06 | 392.54 | 01-JAN-01:10 | 4341.96 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 305.91 | 2539.66 | 01-JAN-01:10 | 15745.17 | 02-JAN-11:10 |
InteriorLights:Electricity | 29.32 | 275.79 | 01-JAN-01:10 | 1654.77 | 02-JAN-17:30 |
InteriorLights:Electricity:Zone:DINING | 10.73 | 122.53 | 01-JAN-01:10 | 735.19 | 02-JAN-17:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 29.32 | 275.79 | 01-JAN-01:10 | 1654.77 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity | 29.32 | 275.79 | 01-JAN-01:10 | 1654.77 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 10.73 | 122.53 | 01-JAN-01:10 | 735.19 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 29.32 | 275.79 | 01-JAN-01:10 | 1654.77 | 02-JAN-17:30 |
Electricity:Zone:KITCHEN | 242.71 | 2556.15 | 01-JAN-01:10 | 14919.31 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 18.59 | 153.26 | 01-JAN-01:10 | 919.59 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 18.59 | 153.26 | 01-JAN-01:10 | 919.59 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 276.59 | 2263.87 | 01-JAN-01:10 | 14413.88 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 276.59 | 2263.87 | 01-JAN-01:10 | 14413.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 206.26 | 1993.86 | 01-JAN-01:10 | 10483.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 65.88 | 1035.59 | 11-FEB-23:30 | 4592.33 | 09-MAR-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
Electricity:Plant | 48.02 | 779.94 | 11-FEB-23:10 | 2551.44 | 18-AUG-04:10 |
LowTempRefrigeration:Refrigeration:Electricity | 17.18 | 0.00 | 01-JAN-11:10 | 1475.21 | 18-AUG-04:10 |
MedTempRefrigeration:Refrigeration:Electricity | 30.84 | 701.41 | 03-FEB-00:20 | 1076.23 | 19-JAN-13:10 |
ElectricityPurchased:Facility | 584.64 | 5208.12 | 12-FEB-01:10 | 40294.17 | 07-JUL-12:00 |
ElectricityPurchased:Plant | 584.64 | 5208.12 | 12-FEB-01:10 | 40294.17 | 07-JUL-12:00 |
Cogeneration:ElectricityPurchased | 584.64 | 5208.12 | 12-FEB-01:10 | 40294.17 | 07-JUL-12:00 |
General:Cogeneration:ElectricityPurchased | 584.64 | 5208.12 | 12-FEB-01:10 | 40294.17 | 07-JUL-12:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 584.64 | 5208.12 | 12-FEB-01:10 | 40294.17 | 07-JUL-12:00 |
ElectricityNet:Plant | 584.64 | 5208.12 | 12-FEB-01:10 | 40294.17 | 07-JUL-12:00 |
Cogeneration:ElectricityNet | 584.64 | 5208.12 | 12-FEB-01:10 | 40294.17 | 07-JUL-12:00 |
General:Cogeneration:ElectricityNet | 584.64 | 5208.12 | 12-FEB-01:10 | 40294.17 | 07-JUL-12:00 |
Electricity:HVAC | 185.78 | 0.00 | 01-JAN-01:10 | 23297.13 | 07-JUL-12:00 |
Fans:Electricity | 82.38 | 0.00 | 01-JAN-01:10 | 4291.99 | 07-JUL-12:00 |
General:Fans:Electricity | 82.38 | 0.00 | 01-JAN-01:10 | 4291.99 | 07-JUL-12:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 103.40 | 0.00 | 01-JAN-00:10 | 19005.15 | 07-JUL-12:00 |
General:Cooling:Electricity | 103.40 | 0.00 | 01-JAN-00:10 | 19005.15 | 07-JUL-12:00 |
ExteriorLights:Electricity | 27.07 | 0.00 | 01-JAN-07:50 | 2040.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 27.07 | 0.00 | 01-JAN-07:50 | 2040.24 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 20-APR-09:40 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 20-APR-09:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 801.85 | 2558.65 | 20-JAN-01:40 | 109025.81 | 12-FEB-07:10 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 134.94 | 0.00 | 01-JAN-00:10 | 87179.66 | 12-FEB-07:10 |
Heating:NaturalGas | 134.94 | 0.00 | 01-JAN-00:10 | 87179.66 | 12-FEB-07:10 |
General:Heating:NaturalGas | 134.94 | 0.00 | 01-JAN-00:10 | 87179.66 | 12-FEB-07:10 |
NaturalGas:Plant | 189.75 | 720.00 | 01-JAN-00:10 | 26665.20 | 01-FEB-13:50 |
WaterSystems:NaturalGas | 189.75 | 720.00 | 01-JAN-00:10 | 26665.20 | 01-FEB-13:50 |
Water Heater:WaterSystems:NaturalGas | 189.75 | 720.00 | 01-JAN-00:10 | 26665.20 | 01-FEB-13:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1235.01 | 2741.52 | 12-FEB-01:10 | 122182.38 | 07-JUL-12:30 |
EnergyTransfer:Building | 500.05 | 1370.76 | 12-FEB-01:10 | 37109.39 | 11-FEB-20:00 |
EnergyTransfer:Zone:KITCHEN | 370.62 | 1370.76 | 12-FEB-01:10 | 22346.50 | 15-DEC-05:10 |
Refrigeration:EnergyTransfer | 155.58 | 2699.62 | 11-FEB-23:10 | 7834.84 | 29-MAR-10:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 77.79 | 1349.81 | 11-FEB-23:10 | 3917.42 | 29-MAR-10:40 |
General:Refrigeration:EnergyTransfer | 77.79 | 1349.81 | 11-FEB-23:10 | 3917.42 | 29-MAR-10:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 77.79 | 1349.81 | 11-FEB-23:10 | 3917.42 | 29-MAR-10:40 |
EnergyTransfer:Plant | 204.36 | 1349.81 | 11-FEB-23:10 | 20623.42 | 31-JAN-13:30 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 16.49 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 61.30 | 1114.23 | 03-FEB-00:20 | 2238.70 | 19-JAN-13:10 |
EnergyTransfer:Zone:DINING | 129.42 | 0.00 | 01-JAN-01:10 | 24465.88 | 11-FEB-20:00 |
Heating:EnergyTransfer | 28.05 | 0.00 | 01-JAN-00:10 | 24465.88 | 11-FEB-20:00 |
Heating:EnergyTransfer:Zone:DINING | 28.05 | 0.00 | 01-JAN-00:10 | 24465.88 | 11-FEB-20:00 |
General:Heating:EnergyTransfer | 28.05 | 0.00 | 01-JAN-00:10 | 24465.88 | 11-FEB-20:00 |
General:Heating:EnergyTransfer:Zone:DINING | 28.05 | 0.00 | 01-JAN-00:10 | 24465.88 | 11-FEB-20:00 |
Cooling:EnergyTransfer | 394.21 | 0.00 | 01-JAN-01:10 | 32643.64 | 08-JUL-18:10 |
Cooling:EnergyTransfer:Zone:DINING | 101.38 | 0.00 | 01-JAN-01:10 | 19229.01 | 01-AUG-17:10 |
General:Cooling:EnergyTransfer | 394.21 | 0.00 | 01-JAN-01:10 | 32643.64 | 08-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 101.38 | 0.00 | 01-JAN-01:10 | 19229.01 | 01-AUG-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 855.36 | 12-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 855.36 | 12-FEB-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 292.83 | 0.00 | 01-JAN-01:10 | 18537.25 | 15-DEC-05:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 292.83 | 0.00 | 01-JAN-01:10 | 18537.25 | 15-DEC-05:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 126.57 | 0.00 | 01-JAN-00:10 | 17972.58 | 29-JAN-13:50 |
PlantLoopHeatingDemand:Plant | 126.57 | 0.00 | 01-JAN-00:10 | 17972.58 | 29-JAN-13:50 |
WaterSystems:PlantLoopHeatingDemand | 126.57 | 0.00 | 01-JAN-00:10 | 17972.58 | 29-JAN-13:50 |
General:WaterSystems:PlantLoopHeatingDemand | 126.57 | 0.00 | 01-JAN-00:10 | 17972.58 | 29-JAN-13:50 |
EnergyTransfer:HVAC | 530.61 | 0.00 | 01-JAN-00:10 | 77389.34 | 07-JUL-12:00 |
HeatingCoils:EnergyTransfer | 107.96 | 0.00 | 01-JAN-00:10 | 69743.73 | 12-FEB-07:10 |
CoolingCoils:EnergyTransfer | 422.65 | 0.00 | 01-JAN-00:10 | 77389.34 | 07-JUL-12:00 |
WaterSystems:EnergyTransfer | 126.57 | 0.00 | 01-JAN-00:10 | 17972.58 | 29-JAN-13:50 |
WaterUse:WaterSystems:EnergyTransfer | 126.57 | 0.00 | 01-JAN-00:10 | 17972.58 | 29-JAN-13:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 28.047 | -101.376 | 0.000 | 0.000 | 69.498 | 10.730 | 52.748 | 18.895 | 0.000 | 15.743 | 0.000 | 0.000 | -12.943 | 0.000 | -78.797 | -2.545 |
KITCHEN | 0.000 | 0.000 | 0.001 | -292.825 | 0.000 | 0.000 | 4.481 | 18.590 | 211.968 | 0.000 | 0.000 | 0.048 | 59.396 | 0.000 | 0.000 | 0.000 | -1.661 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.395 | 12.135 | 0.000 | 0.000 | 0.000 | -15.530 | -0.000 |
Total Facility | 0.000 | 0.000 | 28.049 | -394.201 | 0.000 | 0.000 | 73.979 | 29.320 | 264.717 | 18.895 | 0.000 | 19.186 | 71.532 | 0.000 | -12.943 | 0.000 | -95.988 | -2.545 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 04-JUN-01:01 | 0.00 | 0.00 | 0.00 | -24734.79 | 0.00 | 0.00 | 0.00 | 122.53 | 303.76 | 0.00 | 0.00 | 0.00 | 24753.00 | 0.00 | -433.72 | 0.00 | -10.78 | 0.00 |
KITCHEN | 28-FEB-05:01 | 0.00 | 0.00 | 0.00 | -49688.86 | 0.00 | 0.00 | 8.82 | 204.35 | 5271.43 | 0.00 | 0.00 | 0.00 | 44273.02 | 0.00 | -0.00 | 0.00 | -68.76 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-FEB-05:01 | 0.00 | 0.00 | 0.00 | -54303.00 | 0.00 | 0.00 | 333.48 | 367.73 | 6491.17 | 0.00 | 0.00 | 347.39 | 47910.83 | 0.00 | -1031.40 | 0.00 | -116.20 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 12-FEB-04:35 | 0.00 | 0.00 | 35025.97 | 0.00 | 0.00 | 0.00 | 0.00 | 122.53 | 506.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2324.20 | 0.00 | -834.38 | -32496.19 |
KITCHEN | 12-FEB-05:03 | 0.00 | 0.00 | 8546.87 | 0.00 | 0.00 | 0.00 | 0.00 | 153.26 | 5264.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -203.83 | -13761.20 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-FEB-04:35 | 0.00 | 0.00 | 35025.97 | 0.00 | 0.00 | 0.00 | 0.00 | 275.79 | 3497.73 | 0.00 | 0.00 | 297.73 | 0.00 | 0.00 | -2324.20 | 0.00 | -1754.32 | -35018.71 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.2034 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.2034 | 0.1888 | 1.0000 | Not calculated | 0.4161 | 0.1888 | ||
PSZ-AC_2:2 | 1.3174 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.3174 | 0.1148 | 1.0000 | Not calculated | 0.1513 | 0.1148 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.2034 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.2034 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.1888 | ||
PSZ-AC_2:2 | 1.3174 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.3174 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1148 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2034 | 2.2034 | 2.2034 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3174 | 1.3174 | 1.3174 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.2034 | 2.2034 | 2.2034 | 2.2034 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.3174 | 1.3174 | 1.3174 | 1.3174 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2034 | 2.2034 | 2.2034 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3174 | 1.3174 | 1.3174 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.2034 | 2.2034 | 2.2034 | 2.2034 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.3174 | 1.3174 | 1.3174 | 1.3174 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 60.33 |
Number of hours not met | 60.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 134.94 | 87179.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 103.40 | 19005.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 29.32 | 1654.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 27.07 | 2040.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 82.38 | 4291.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 189.75 | 26665.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 17.86 | 3516.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 17.18 | 1475.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 30.84 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 342.47 | 584.64 |
Natural Gas | 477.16 | 801.85 |
Additional | 0.00 | 0.00 |
Total | 819.63 | 1386.49 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 126.19 |
Space Heating | 0.00 |
Space Cooling | 445.05 |
Fans (All) | 354.56 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1190.44 |
Miscellaneous (All) | 2516.27 |
Subtotal | 2516.27 |
Natural Gas [MJ/m2] | |
Space Heating | 580.80 |
Service Water Heating | 816.69 |
Miscellaneous (All) | 3451.17 |
Subtotal | 3451.17 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.11 |
Space Heating | 9.73 |
Space Cooling | 7.46 |
Fans (All) | 5.94 |
Service Water Heating | 13.69 |
Receptacle Equipment | 54.36 |
Miscellaneous | 6.70 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4763. | 8760. |
LTG_SCH_KITCHEN | 4539. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_SETBACK | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_SETBACK | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8387.67 | 372.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 6148.67 | 607.83 | 632.00 | 762.67 | 608.83 |
Min | 6148.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 607.83 | 632.00 | 762.67 | 608.83 |
Average | 7765.44 | 326.72 | 210.67 | 254.22 | 202.94 |
Sum | 23296.33 | 980.17 | 632.00 | 762.67 | 608.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15902.00 | 356.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 356.00 | 0.00 | 0.00 | 0.00 |
Average | 90209.00 | 118.67 | 0.00 | 0.00 | 0.00 |
Sum | 270627.00 | 356.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 6877.17 | 1882.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 4652.50 | 4107.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 5697.67 | 1427.83 | 394.00 | 325.33 | 915.17 |
Min | 4652.50 | 1427.83 | 0.00 | 0.00 | 0.00 |
Max | 6877.17 | 4107.50 | 394.00 | 325.33 | 915.17 |
Average | 5742.44 | 2472.72 | 131.33 | 108.44 | 305.06 |
Sum | 17227.33 | 7418.17 | 394.00 | 325.33 | 915.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 198093.17 | 56631.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8054.50 | 8203.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 198093.17 | 56631.83 | 0.00 | 0.00 | 0.00 |
Average | 68715.89 | 21611.78 | 0.00 | 0.00 | 0.00 |
Sum | 206147.67 | 64835.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:22
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Environment
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102999E+10 | 12106.33 | 14-JAN-05:02 | -6.2 | -7.4 | 0.449262E+10 | 4398.95 | 31-JAN-12:00 | 19.40 | 13.64 |
February | 0.207834E+10 | 16995.43 | 12-FEB-03:53 | -11.7 | -13.0 | 0.418125E+10 | 4413.36 | 28-FEB-12:00 | 23.30 | 12.72 |
March | 0.417263E+10 | 11105.57 | 30-MAR-17:05 | 26.60 | 17.75 | 0.490489E+10 | 4681.24 | 04-MAR-19:49 | 26.60 | 17.75 |
April | 0.677080E+10 | 11997.85 | 17-APR-17:03 | 28.03 | 16.54 | 0.495601E+10 | 4681.17 | 22-APR-18:00 | 20.60 | 17.72 |
May | 0.104668E+11 | 22150.40 | 19-MAY-00:41 | 20.18 | 16.48 | 0.534990E+10 | 4681.26 | 13-MAY-18:00 | 20.18 | 16.48 |
June | 0.155901E+11 | 24747.97 | 04-JUN-01:01 | 21.10 | 15.34 | 0.527077E+10 | 4681.51 | 03-JUN-18:10 | 21.10 | 15.34 |
July | 0.174885E+11 | 20668.36 | 03-JUL-00:11 | 21.10 | 17.70 | 0.540429E+10 | 4681.30 | 15-JUL-18:19 | 32.77 | 23.81 |
August | 0.185201E+11 | 19229.99 | 01-AUG-17:08 | 34.72 | 23.57 | 0.546712E+10 | 4681.66 | 05-AUG-18:49 | 25.92 | 22.15 |
September | 0.127931E+11 | 19437.65 | 13-SEP-01:22 | 20.00 | 18.13 | 0.521195E+10 | 4681.64 | 16-SEP-18:19 | 25.20 | 23.68 |
October | 0.701095E+10 | 16552.97 | 18-OCT-00:42 | 21.10 | 19.86 | 0.502031E+10 | 4681.24 | 07-OCT-18:10 | 21.10 | 19.86 |
November | 0.374849E+10 | 8532.87 | 22-NOV-00:01 | -0.7 | -2.3 | 0.462471E+10 | 4680.90 | 04-NOV-18:49 | -0.7 | -2.3 |
December | 0.170689E+10 | 9296.96 | 18-DEC-00:01 | -2.4 | -5.1 | 0.452791E+10 | 4413.41 | 13-DEC-12:50 | -2.4 | -5.1 |
Annual Sum or Average | 0.101377E+12 | 0.594117E+11 | ||||||||
Minimum of Months | 0.102999E+10 | 8532.87 | -11.7 | -13.0 | 0.418125E+10 | 4398.95 | -2.4 | -5.1 | ||
Maximum of Months | 0.185201E+11 | 24747.97 | 34.72 | 23.57 | 0.546712E+10 | 4681.66 | 32.77 | 23.81 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231818E+11 | 39253.97 | 20-JAN-05:01 | 12.80 | 12.52 | 0.770796E+10 | 5135.94 | 31-JAN-11:00 | 17.20 | 13.29 |
February | 0.208397E+11 | 49694.02 | 28-FEB-05:01 | 10.60 | 5.93 | 0.699971E+10 | 5135.94 | 28-FEB-11:50 | 21.93 | 12.25 |
March | 0.234693E+11 | 46038.42 | 21-MAR-04:01 | 13.03 | 8.86 | 0.780865E+10 | 5135.99 | 28-MAR-10:00 | 17.80 | 15.36 |
April | 0.228490E+11 | 45187.90 | 11-APR-04:01 | 12.02 | 9.39 | 0.758255E+10 | 5135.99 | 24-APR-10:00 | 18.30 | 14.61 |
May | 0.246408E+11 | 44476.81 | 12-MAY-04:01 | 12.12 | 9.75 | 0.785530E+10 | 5135.99 | 01-MAY-10:00 | 12.12 | 9.75 |
June | 0.252061E+11 | 40571.49 | 09-JUN-03:21 | 15.00 | 9.76 | 0.760881E+10 | 5150.65 | 28-JUN-10:00 | 30.60 | 24.10 |
July | 0.265683E+11 | 26326.67 | 03-JUL-03:21 | 17.80 | 16.72 | 0.785998E+10 | 5156.15 | 07-JUL-10:50 | 32.02 | 24.15 |
August | 0.269946E+11 | 25708.22 | 25-AUG-04:01 | 19.90 | 18.10 | 0.786581E+10 | 5158.96 | 10-AUG-10:50 | 19.90 | 18.10 |
September | 0.253134E+11 | 42020.59 | 29-SEP-04:01 | 11.78 | 11.10 | 0.760502E+10 | 5143.55 | 07-SEP-10:00 | 11.78 | 11.10 |
October | 0.254218E+11 | 45944.06 | 06-OCT-04:01 | 7.70 | 7.70 | 0.782617E+10 | 5135.98 | 23-OCT-10:00 | 16.70 | 13.77 |
November | 0.240773E+11 | 44096.33 | 10-NOV-05:01 | 11.70 | 9.86 | 0.753883E+10 | 5135.96 | 06-NOV-11:00 | 11.70 | 9.86 |
December | 0.242670E+11 | 38911.29 | 12-DEC-05:01 | 12.80 | 12.80 | 0.773551E+10 | 5135.95 | 12-DEC-11:50 | 20.22 | 16.28 |
Annual Sum or Average | 0.292829E+12 | 0.919943E+11 | ||||||||
Minimum of Months | 0.208397E+11 | 25708.22 | 7.70 | 5.93 | 0.699971E+10 | 5135.94 | 11.70 | 9.75 | ||
Maximum of Months | 0.269946E+11 | 49694.02 | 19.90 | 18.10 | 0.786581E+10 | 5158.96 | 32.02 | 24.15 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.70 | 4.97 | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 | 7.50 | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 | 8.51 | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.51 |
April | 0.00 | 0.00 | 01-APR-00:01 | 12.05 | 7.82 | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.82 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 16.68 | 16.68 | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 20.93 | 18.59 | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.28 | 21.38 | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.13 | 21.87 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.40 | 18.46 | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.46 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.85 | 15.92 | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.70 | 6.60 | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.60 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 1.80 | 1.51 | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.80 | 1.51 | 0.00 | 0.00 | 1.80 | 1.51 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 21.87 | 0.00 | 0.00 | 25.13 | 21.87 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113455E+11 | 29906.66 | 14-JAN-05:01 | -6.2 |
February | 0.659960E+10 | 35026.47 | 12-FEB-04:35 | -11.7 |
March | 0.146769E+10 | 9985.79 | 19-MAR-06:50 | 1.20 |
April | 0.494782E+09 | 8514.30 | 06-APR-06:10 | 1.20 |
May | 19614398.61 | 2733.40 | 11-MAY-06:10 | 8.17 |
June | 21723.88 | 145.56 | 13-JUN-04:03 | 21.93 |
July | 357471.61 | 885.74 | 07-JUL-04:03 | 25.22 |
August | 920636.90 | 934.96 | 04-AUG-04:03 | 23.90 |
September | 99686.47 | 260.47 | 16-SEP-04:03 | 22.20 |
October | 0.484424E+09 | 7265.36 | 26-OCT-06:10 | 2.20 |
November | 0.205703E+10 | 11131.81 | 22-NOV-07:10 | -3.2 |
December | 0.557708E+10 | 17265.60 | 18-DEC-05:01 | -5.0 |
Annual Sum or Average | 0.280471E+11 | |||
Minimum of Months | 21723.88 | 145.56 | -11.7 | |
Maximum of Months | 0.113455E+11 | 35026.47 | 25.22 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 767034.09 | 2311.29 | 16-JAN-05:04 | -2.8 |
February | 513218.47 | 8553.64 | 12-FEB-05:03 | -11.8 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.85 |
November | 46645.93 | 777.43 | 22-NOV-05:04 | -2.9 |
December | 146246.12 | 1843.85 | 03-DEC-05:04 | -3.3 |
Annual Sum or Average | 1473144.60 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 767034.09 | 8553.64 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.964916E+09 | 735.19 | 02-JAN-17:30 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.863860E+09 | 735.19 | 01-FEB-17:30 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.919738E+09 | 735.19 | 01-MAR-18:19 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.851341E+09 | 735.19 | 01-APR-18:00 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.862468E+09 | 735.19 | 01-MAY-19:19 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.833409E+09 | 735.19 | 01-JUN-19:30 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.852677E+09 | 735.19 | 01-JUL-19:19 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.882879E+09 | 735.19 | 01-AUG-19:19 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.875113E+09 | 735.19 | 01-SEP-18:30 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.927866E+09 | 735.19 | 02-OCT-18:19 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.928980E+09 | 735.19 | 01-NOV-17:30 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.966460E+09 | 735.19 | 01-DEC-17:30 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.107297E+11 | 0.703313E+11 | ||||
Minimum of Months | 0.833409E+09 | 735.19 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.966460E+09 | 735.19 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.157083E+10 | 919.59 | 02-JAN-10:09 | 0.175178E+11 | 10483.62 | 01-JAN-11:09 |
February | 0.142278E+10 | 919.59 | 01-FEB-10:09 | 0.158225E+11 | 10483.62 | 01-FEB-11:09 |
March | 0.159585E+10 | 919.59 | 01-MAR-10:09 | 0.175179E+11 | 10483.62 | 01-MAR-11:09 |
April | 0.152633E+10 | 919.59 | 01-APR-16:10 | 0.169527E+11 | 10483.62 | 01-APR-10:09 |
May | 0.158334E+10 | 919.59 | 01-MAY-09:09 | 0.175178E+11 | 10483.62 | 01-MAY-10:09 |
June | 0.154251E+10 | 919.59 | 01-JUN-09:09 | 0.169528E+11 | 10483.62 | 01-JUN-10:09 |
July | 0.156734E+10 | 919.59 | 01-JUL-16:10 | 0.175177E+11 | 10483.62 | 01-JUL-10:09 |
August | 0.159585E+10 | 919.59 | 01-AUG-09:09 | 0.175179E+11 | 10483.62 | 01-AUG-10:09 |
September | 0.152669E+10 | 919.59 | 01-SEP-09:09 | 0.169527E+11 | 10483.62 | 01-SEP-10:09 |
October | 0.157065E+10 | 919.59 | 02-OCT-09:09 | 0.175178E+11 | 10483.62 | 01-OCT-10:09 |
November | 0.152062E+10 | 919.59 | 01-NOV-09:09 | 0.169527E+11 | 10483.62 | 01-NOV-10:09 |
December | 0.156752E+10 | 919.59 | 01-DEC-10:09 | 0.175177E+11 | 10483.62 | 01-DEC-11:09 |
Annual Sum or Average | 0.185903E+11 | 0.206258E+12 | ||||
Minimum of Months | 0.142278E+10 | 919.59 | 0.158225E+11 | 10483.62 | ||
Maximum of Months | 0.159585E+10 | 919.59 | 0.175179E+11 | 10483.62 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.964916E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186141E+11 |
February | 0.852256E+10 | 0.863860E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6369646.56 | 0.127713E+11 |
March | 0.954557E+10 | 0.919738E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85136858.91 | 0.798477E+10 |
April | 0.915225E+10 | 0.851341E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408025E+09 | 0.455934E+10 |
May | 0.947560E+10 | 0.862468E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119063E+10 | 0.233539E+10 |
June | 0.922788E+10 | 0.833409E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357741E+10 | 0.687103E+09 |
July | 0.939996E+10 | 0.852677E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442053E+10 | 0.624969E+09 |
August | 0.954557E+10 | 0.882879E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436343E+10 | 0.205475E+09 |
September | 0.915225E+10 | 0.875113E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148544E+10 | 0.156961E+10 |
October | 0.940563E+10 | 0.927866E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205657E+09 | 0.618675E+10 |
November | 0.909363E+10 | 0.928980E+09 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 802413.90 | 0.940927E+10 |
December | 0.939996E+10 | 0.966460E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138490E+11 |
Annual Sum or Average | 0.111326E+12 | 0.107297E+11 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157434E+11 | 0.787971E+11 |
Minimum of Months | 0.852256E+10 | 0.833409E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205475E+09 |
Maximum of Months | 0.954557E+10 | 0.966460E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442053E+10 | 0.186141E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.157083E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299104E+09 |
February | 0.610713E+09 | 0.142278E+10 | 0.120683E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265698E+09 |
March | 0.684021E+09 | 0.159585E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 121258.93 | 0.184171E+09 |
April | 0.655836E+09 | 0.152633E+10 | 0.129303E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 415196.22 | 0.116892E+09 |
May | 0.679007E+09 | 0.158334E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 2314072.00 | 77552254.90 |
June | 0.661256E+09 | 0.154251E+10 | 0.129304E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 13746881.97 | 40173181.57 |
July | 0.673587E+09 | 0.156734E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 13985011.95 | 27761316.82 |
August | 0.684021E+09 | 0.159585E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 13973247.88 | 19624942.13 |
September | 0.655836E+09 | 0.152669E+10 | 0.129303E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 3094830.14 | 44443375.18 |
October | 0.673993E+09 | 0.157065E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 332149.35 | 0.134476E+09 |
November | 0.651635E+09 | 0.152062E+10 | 0.129304E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184084E+09 |
December | 0.673587E+09 | 0.156752E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266962E+09 |
Annual Sum or Average | 0.797748E+10 | 0.185903E+11 | 0.157319E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 47982648.44 | 0.166094E+10 |
Minimum of Months | 0.610713E+09 | 0.142278E+10 | 0.120683E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19624942.13 |
Maximum of Months | 0.684021E+09 | 0.159585E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 13985011.95 | 0.299104E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314694E+09 | 0.853720E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277484E+09 | 0.869037E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303175E+09 | 0.133364E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269509E+09 | 0.160598E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222283E+09 | 0.184933E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232413E+09 | 0.178244E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232485E+09 | 0.179394E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259656E+09 | 0.167019E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318928E+09 | 0.118087E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289268E+09 | 0.108286E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339248E+09 | 0.799846E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335785E+09 | 0.708141E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339493E+10 | 0.155300E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222283E+09 | 0.708141E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339248E+09 | 0.184933E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 735.19 | 02-JAN-17:30 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 28634.24 | 07-JAN-19:10 |
February | 9454.80 | 04-FEB-19:10 | 735.19 | 01-FEB-17:30 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 861.67 | 28-FEB-14:00 | 30158.58 | 11-FEB-20:00 |
March | 9454.80 | 04-MAR-19:10 | 735.19 | 01-MAR-18:19 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2331.68 | 30-MAR-17:03 | 15497.84 | 22-MAR-11:10 |
April | 9454.80 | 01-APR-18:10 | 735.19 | 01-APR-18:00 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3542.32 | 17-APR-17:03 | 14348.00 | 05-APR-20:00 |
May | 9454.80 | 06-MAY-18:10 | 735.19 | 01-MAY-19:19 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5537.49 | 19-MAY-17:03 | 6646.68 | 11-MAY-06:10 |
June | 9454.80 | 03-JUN-18:10 | 735.19 | 01-JUN-19:30 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8185.56 | 06-JUN-17:03 | 5255.85 | 10-JUN-06:10 |
July | 9454.80 | 01-JUL-18:10 | 735.19 | 01-JUL-19:19 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9323.48 | 08-JUL-18:02 | 4990.30 | 28-JUL-20:00 |
August | 9454.80 | 05-AUG-18:10 | 735.19 | 01-AUG-19:19 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9111.21 | 01-AUG-17:03 | 2588.69 | 25-AUG-06:10 |
September | 9454.80 | 02-SEP-18:10 | 735.19 | 01-SEP-18:30 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6106.68 | 07-SEP-12:00 | 6211.93 | 28-SEP-18:55 |
October | 9454.80 | 07-OCT-18:10 | 735.19 | 02-OCT-18:19 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3878.84 | 10-OCT-17:02 | 12794.07 | 25-OCT-19:55 |
November | 9454.80 | 04-NOV-18:10 | 735.19 | 01-NOV-17:30 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 195.67 | 19-NOV-15:00 | 17117.51 | 21-NOV-21:00 |
December | 9454.80 | 02-DEC-19:10 | 735.19 | 01-DEC-17:30 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 22327.05 | 02-DEC-20:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 735.19 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2588.69 | |||||
Maximum of Months | 9454.80 | 735.19 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9323.48 | 30158.58 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 919.59 | 02-JAN-10:09 | 7748.81 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 970.98 | 07-JAN-05:00 |
February | 677.52 | 04-FEB-19:10 | 919.59 | 01-FEB-10:09 | 7748.81 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1002.00 | 12-FEB-01:10 |
March | 677.52 | 04-MAR-19:10 | 919.59 | 01-MAR-10:09 | 7748.81 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 9.90 | 30-MAR-15:53 | 874.14 | 22-MAR-03:30 |
April | 677.52 | 01-APR-18:10 | 919.59 | 01-APR-16:10 | 7748.81 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 8.26 | 12-APR-14:00 | 366.34 | 06-APR-02:00 |
May | 677.52 | 06-MAY-18:10 | 919.59 | 01-MAY-09:09 | 7748.81 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 19.61 | 19-MAY-13:00 | 378.06 | 10-MAY-04:00 |
June | 677.52 | 03-JUN-18:10 | 919.59 | 01-JUN-09:09 | 7748.81 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 57.42 | 06-JUN-14:00 | 289.68 | 07-JUN-03:20 |
July | 677.52 | 01-JUL-18:10 | 919.59 | 01-JUL-16:10 | 7748.81 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 41.89 | 22-JUL-14:00 | 265.29 | 28-JUL-04:00 |
August | 677.52 | 05-AUG-18:10 | 919.59 | 01-AUG-09:09 | 7748.81 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 47.08 | 07-AUG-15:00 | 220.40 | 29-AUG-03:20 |
September | 677.52 | 02-SEP-18:10 | 919.59 | 01-SEP-09:09 | 7748.81 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 22.46 | 06-SEP-11:53 | 245.98 | 30-SEP-04:00 |
October | 677.52 | 07-OCT-18:10 | 919.59 | 02-OCT-09:09 | 7748.81 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 11.32 | 10-OCT-16:00 | 598.45 | 28-OCT-04:00 |
November | 677.52 | 04-NOV-18:10 | 919.59 | 01-NOV-09:09 | 7748.81 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 732.66 | 07-NOV-04:30 |
December | 677.52 | 02-DEC-19:10 | 919.59 | 01-DEC-10:09 | 7748.81 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1244.62 | 17-DEC-04:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 919.59 | 7748.81 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 220.40 | ||||||
Maximum of Months | 677.52 | 919.59 | 7748.81 | 7998.14 | 0.00 | 0.00 | 0.00 | 57.42 | 1244.62 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656.20 | 29-JAN-06:55 | 1969.04 | 10-JAN-13:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.54 | 09-FEB-08:32 | 2268.92 | 12-FEB-13:50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.48 | 19-MAR-07:15 | 2453.38 | 19-MAR-13:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572.94 | 10-APR-06:20 | 2715.08 | 09-APR-14:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.69 | 20-MAY-05:50 | 2663.28 | 10-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 591.09 | 11-JUN-06:03 | 2441.71 | 02-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.14 | 05-JUL-03:00 | 2517.38 | 12-JUL-14:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.62 | 10-AUG-05:10 | 2731.84 | 04-AUG-14:52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 566.37 | 15-SEP-07:12 | 2386.40 | 15-SEP-13:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 617.08 | 14-OCT-07:23 | 2050.66 | 13-OCT-12:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 625.21 | 23-NOV-07:30 | 1739.77 | 21-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 612.10 | 10-DEC-06:00 | 1598.89 | 17-DEC-13:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.14 | 1598.89 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656.20 | 2731.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12106.33 | 14-JAN-05:02 | 0.00 | 1225.31 | 16200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.67 |
February | 16995.43 | 12-FEB-03:53 | 0.00 | 1225.31 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 807.69 |
March | 11105.57 | 30-MAR-17:05 | 33617.07 | 1646.82 | 13010.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2331.67 | 0.00 |
April | 11997.85 | 17-APR-17:03 | 33617.07 | 1646.82 | 13010.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3542.32 | 0.00 |
May | 22150.40 | 19-MAY-00:41 | 0.00 | 857.72 | 1890.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.29 |
June | 24747.97 | 04-JUN-01:01 | 0.00 | 980.25 | 3240.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.78 |
July | 20668.36 | 03-JUL-00:11 | 0.00 | 1225.31 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 |
August | 19229.99 | 01-AUG-17:08 | 33617.07 | 1646.82 | 13010.50 | 0.00 | 0.00 | 0.00 | 0.00 | 9110.75 | 0.00 |
September | 19437.65 | 13-SEP-01:22 | 0.00 | 735.19 | 2430.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.44 |
October | 16552.97 | 18-OCT-00:42 | 0.00 | 735.19 | 1620.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.56 |
November | 8532.87 | 22-NOV-00:01 | 4727.40 | 1102.78 | 3659.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.84 |
December | 9296.96 | 18-DEC-00:01 | 5252.67 | 1225.31 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8532.87 | 0.00 | 735.19 | 1620.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24747.97 | 33617.07 | 1646.82 | 16200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 9110.75 | 807.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39253.97 | 20-JAN-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 44.10 |
February | 49694.02 | 28-FEB-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 68.76 |
March | 46038.42 | 21-MAR-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 55.45 |
April | 45187.90 | 11-APR-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 51.10 |
May | 44476.81 | 12-MAY-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 |
June | 40571.49 | 09-JUN-03:21 | 0.00 | 1379.33 | 22172.05 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 121.00 |
July | 26326.67 | 03-JUL-03:21 | 0.00 | 1072.81 | 17244.93 | 9652.92 | 0.00 | 0.00 | 0.00 | 0.00 | 62.04 |
August | 25708.22 | 25-AUG-04:01 | 263.48 | 1430.47 | 28056.63 | 23167.02 | 0.00 | 0.00 | 0.00 | 0.00 | 21.75 |
September | 42020.59 | 29-SEP-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 43.80 |
October | 45944.06 | 06-OCT-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 54.04 |
November | 44096.33 | 10-NOV-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38911.29 | 12-DEC-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 30.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25708.22 | 0.00 | 1072.81 | 17244.93 | 9652.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49694.02 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 121.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.61 | 0.00 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.76 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.59 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.99 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.16 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.70 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.12 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.90 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.92 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.23 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.23 | 50.27 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.410937E+11 | 23552.89 | 06-JAN-11:09 | 0.110951E+12 | 92774.04 | 07-JAN-19:30 |
February | 0.373692E+11 | 25075.79 | 28-FEB-11:00 | 0.837439E+11 | 109025.81 | 12-FEB-07:10 |
March | 0.423753E+11 | 28013.85 | 30-MAR-12:00 | 0.660730E+11 | 67781.77 | 22-MAR-12:20 |
April | 0.436361E+11 | 29225.12 | 18-APR-10:00 | 0.585306E+11 | 54923.52 | 05-APR-12:50 |
May | 0.498742E+11 | 34157.58 | 30-MAY-10:00 | 0.564468E+11 | 47991.37 | 01-MAY-12:39 |
June | 0.573833E+11 | 38445.53 | 23-JUN-11:00 | 0.533805E+11 | 46894.27 | 01-JUN-12:39 |
July | 0.640353E+11 | 40294.17 | 07-JUL-11:00 | 0.544848E+11 | 45962.71 | 01-JUL-12:30 |
August | 0.670897E+11 | 39898.70 | 18-AUG-11:00 | 0.544761E+11 | 45862.65 | 31-AUG-12:39 |
September | 0.541218E+11 | 37848.76 | 07-SEP-11:20 | 0.532394E+11 | 46672.96 | 28-SEP-12:39 |
October | 0.456471E+11 | 33446.72 | 18-OCT-10:00 | 0.595210E+11 | 54958.75 | 25-OCT-10:20 |
November | 0.408607E+11 | 26398.87 | 03-NOV-10:00 | 0.662504E+11 | 68436.91 | 22-NOV-07:10 |
December | 0.411517E+11 | 25582.16 | 13-DEC-11:20 | 0.847570E+11 | 82645.53 | 18-DEC-04:10 |
Annual Sum or Average | 0.584638E+12 | 0.801854E+12 | ||||
Minimum of Months | 0.373692E+11 | 23552.89 | 0.532394E+11 | 45862.65 | ||
Maximum of Months | 0.670897E+11 | 40294.17 | 0.110951E+12 | 109025.81 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.253575E+10 | 0.274930E+10 | 0.234911E+11 | 0.00 | 0.709357E+10 | 0.79 | 0.00 | 65361913.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228664E+10 | 0.232536E+10 | 0.212178E+11 | 0.00 | 0.624905E+10 | 0.72 | 0.00 | 0.494943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251559E+10 | 0.234533E+10 | 0.234913E+11 | 0.00 | 0.666704E+10 | 0.80 | 0.00 | 0.183208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237767E+10 | 0.204080E+10 | 0.227333E+11 | 0.00 | 0.640582E+10 | 0.77 | 0.00 | 0.460909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.244581E+10 | 0.190953E+10 | 0.234912E+11 | 0.00 | 0.673845E+10 | 0.80 | 0.00 | 0.951737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.237592E+10 | 0.176047E+10 | 0.227335E+11 | 0.00 | 0.700281E+10 | 0.77 | 0.00 | 0.178835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.242002E+10 | 0.185200E+10 | 0.234911E+11 | 0.00 | 0.760797E+10 | 0.79 | 0.00 | 0.228301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.247873E+10 | 0.201848E+10 | 0.234913E+11 | 0.00 | 0.780489E+10 | 0.80 | 0.00 | 0.254392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.240181E+10 | 0.217056E+10 | 0.227333E+11 | 0.00 | 0.681398E+10 | 0.77 | 0.00 | 0.143808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.249852E+10 | 0.247999E+10 | 0.234911E+11 | 0.00 | 0.671612E+10 | 0.79 | 0.00 | 0.481250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.244960E+10 | 0.260758E+10 | 0.227334E+11 | 0.00 | 0.648262E+10 | 0.77 | 0.00 | 0.128984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253398E+10 | 0.280561E+10 | 0.234911E+11 | 0.00 | 0.679653E+10 | 0.79 | 0.00 | 0.249248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293200E+11 | 0.270650E+11 | 0.276589E+12 | 0.00 | 0.823788E+11 | 9.37 | 0.00 | 0.103404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.228664E+10 | 0.176047E+10 | 0.212178E+11 | 0.00 | 0.624905E+10 | 0.72 | 0.00 | 65361913.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.253575E+10 | 0.280561E+10 | 0.234913E+11 | 0.00 | 0.780489E+10 | 0.80 | 0.00 | 0.254392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.521107E+11 | 0.00 | 0.183142E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.305988E+11 | 0.00 | 0.165413E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.776982E+10 | 0.00 | 0.177775E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.309693E+10 | 0.00 | 0.162152E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.308660E+09 | 0.00 | 0.156124E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 29244703.48 | 0.00 | 0.141328E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.139590E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.139504E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 25800222.80 | 0.00 | 0.139951E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.352830E+10 | 0.00 | 0.154669E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.109190E+11 | 0.00 | 0.161130E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.265575E+11 | 0.00 | 0.176737E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.134945E+12 | 0.00 | 0.189752E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.00 | 0.00 | 0.139504E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.521107E+11 | 0.00 | 0.183142E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1654.77 | 02-JAN-17:30 | 2040.24 | 01-JAN-00:10 | 14413.88 | 01-JAN-11:09 | 0.00 | 3747.25 | 07-JAN-19:30 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 1654.77 | 01-FEB-17:30 | 2040.24 | 01-FEB-00:10 | 14413.88 | 01-FEB-11:09 | 0.00 | 3995.38 | 12-FEB-07:10 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 1654.77 | 01-MAR-18:19 | 2040.24 | 01-MAR-00:10 | 14413.88 | 01-MAR-11:09 | 0.00 | 3280.65 | 19-MAR-06:00 | 0.00 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 1654.77 | 01-APR-18:00 | 2040.24 | 01-APR-05:10 | 14413.88 | 01-APR-10:09 | 0.00 | 3240.43 | 06-APR-06:10 | 0.00 | 20-APR-09:39 | 0.00 | 01-APR-00:10 |
May | 1654.77 | 01-MAY-19:19 | 2040.24 | 01-MAY-05:10 | 14413.88 | 01-MAY-10:09 | 0.00 | 3367.39 | 31-MAY-11:09 | 0.00 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 1654.77 | 01-JUN-19:30 | 2040.24 | 01-JUN-05:10 | 14413.88 | 01-JUN-10:09 | 0.00 | 4054.58 | 23-JUN-11:00 | 0.00 | 26-JUN-11:30 | 0.00 | 01-JUN-00:10 |
July | 1654.77 | 01-JUL-19:19 | 2040.24 | 01-JUL-05:10 | 14413.88 | 01-JUL-10:09 | 0.00 | 4291.99 | 07-JUL-11:00 | 0.00 | 26-JUL-10:39 | 0.00 | 01-JUL-00:10 |
August | 1654.77 | 01-AUG-19:19 | 2040.24 | 01-AUG-05:10 | 14413.88 | 01-AUG-10:09 | 0.00 | 4207.14 | 18-AUG-11:00 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 1654.77 | 01-SEP-18:30 | 2040.24 | 01-SEP-05:10 | 14413.88 | 01-SEP-10:09 | 0.00 | 3937.96 | 06-SEP-11:00 | 0.00 | 21-SEP-15:09 | 0.00 | 01-SEP-00:10 |
October | 1654.77 | 02-OCT-18:19 | 2040.24 | 01-OCT-05:10 | 14413.88 | 01-OCT-10:09 | 0.00 | 3442.73 | 18-OCT-11:09 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 1654.77 | 01-NOV-17:30 | 2040.24 | 01-NOV-05:10 | 14413.88 | 01-NOV-10:09 | 0.00 | 3430.59 | 22-NOV-07:10 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 1654.77 | 01-DEC-17:30 | 2040.24 | 01-DEC-00:10 | 14413.88 | 01-DEC-11:09 | 0.00 | 3538.84 | 18-DEC-07:40 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1654.77 | 2040.24 | 14413.88 | 0.00 | 3240.43 | 0.00 | 0.00 | ||||||
Maximum of Months | 1654.77 | 2040.24 | 14413.88 | 0.00 | 4291.99 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 1992.66 | 31-JAN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5976.71 | 28-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9066.12 | 30-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8448.66 | 18-APR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12991.42 | 30-MAY-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17403.91 | 23-JUN-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 19005.15 | 07-JUL-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18878.77 | 01-AUG-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16598.94 | 06-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12222.20 | 18-OCT-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6970.73 | 05-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5969.51 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1992.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19005.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 23552.89 | 06-JAN-11:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3438.66 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25075.79 | 28-FEB-11:00 | 1331.29 | 14413.88 | 0.00 | 0.00 | 2738.39 | 0.00 | 0.00 | 3697.99 | 0.00 |
March | 28013.85 | 30-MAR-12:00 | 1331.29 | 12614.39 | 0.00 | 0.00 | 2865.86 | 0.00 | 0.00 | 9066.12 | 0.00 |
April | 29225.12 | 18-APR-10:00 | 1331.29 | 14413.88 | 0.00 | 0.00 | 2833.49 | 0.00 | 0.00 | 7734.90 | 0.00 |
May | 34157.58 | 30-MAY-10:00 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3358.46 | 0.00 | 0.00 | 12119.14 | 0.00 |
June | 38445.53 | 23-JUN-11:00 | 1331.29 | 13514.13 | 0.00 | 0.00 | 4054.58 | 0.00 | 0.00 | 17403.91 | 0.00 |
July | 40294.17 | 07-JUL-11:00 | 1331.29 | 13514.13 | 0.00 | 0.00 | 4291.99 | 0.00 | 0.00 | 19005.15 | 0.00 |
August | 39898.70 | 18-AUG-11:00 | 1331.29 | 13514.13 | 0.00 | 0.00 | 4207.14 | 0.00 | 0.00 | 18705.30 | 0.00 |
September | 37848.76 | 07-SEP-11:20 | 1331.29 | 13514.13 | 0.00 | 0.00 | 3881.80 | 0.00 | 0.00 | 16170.86 | 0.00 |
October | 33446.72 | 18-OCT-10:00 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3435.03 | 0.00 | 0.00 | 11331.70 | 0.00 |
November | 26398.87 | 03-NOV-10:00 | 1331.29 | 14413.88 | 0.00 | 0.00 | 2738.39 | 0.00 | 0.00 | 5000.39 | 0.00 |
December | 25582.16 | 13-DEC-11:20 | 1331.29 | 14413.88 | 0.00 | 0.00 | 2738.39 | 0.00 | 0.00 | 2506.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 23552.89 | 1331.29 | 12614.39 | 0.00 | 0.00 | 2738.39 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40294.17 | 1331.29 | 14413.88 | 0.00 | 0.00 | 4291.99 | 0.00 | 0.00 | 19005.15 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 77328.90 | 06-JAN-03:30 | 0.00 | 26651.31 | 26-JAN-13:20 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 87179.66 | 12-FEB-07:10 | 0.00 | 26665.20 | 01-FEB-13:50 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 35233.50 | 19-MAR-06:00 | 0.00 | 26477.09 | 01-MAR-13:50 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 32652.88 | 06-APR-06:10 | 0.00 | 25894.89 | 01-APR-12:39 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 9933.86 | 11-MAY-06:10 | 0.00 | 25008.22 | 01-MAY-12:39 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 3212.17 | 10-JUN-06:10 | 0.00 | 23911.12 | 01-JUN-12:39 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 22979.56 | 01-JUL-12:30 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 22879.50 | 31-AUG-12:39 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 2480.83 | 29-SEP-06:10 | 0.00 | 23689.81 | 28-SEP-12:39 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 27828.17 | 26-OCT-06:49 | 0.00 | 24864.32 | 31-OCT-12:39 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 52686.12 | 22-NOV-03:30 | 0.00 | 25813.51 | 30-NOV-13:20 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 77328.90 | 18-DEC-03:30 | 0.00 | 26407.02 | 30-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 0.00 | 0.00 | 22879.50 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 87179.66 | 0.00 | 26665.20 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.33 | 19.72 | 0.00 | 19.72 | 0.00 | 19.72 | 0.00 | 19.72 |
February | 11.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.51 | 0.00 | 24.51 |
April | 0.17 | 20.54 | 0.00 | 20.54 | 0.17 | 22.50 | 0.00 | 22.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.49 | 0.00 | 24.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 24.58 | 0.00 | 24.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 24.68 | 0.00 | 24.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 24.77 | 0.00 | 24.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 24.66 | 0.00 | 24.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.56 | 0.00 | 24.56 |
November | 0.83 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
December | 4.83 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
Annual Sum or Average | 31.17 | 19.70 | 0.00 | 19.70 | 107.67 | 23.56 | 0.00 | 23.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.35 | 0.00 | 19.35 |
Maximum of Months | 14.33 | 20.54 | 0.00 | 20.54 | 31.00 | 24.77 | 0.00 | 24.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.46 | 0.00 | 27.46 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.77 | 0.00 | 27.77 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 27.95 | 0.00 | 27.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 28.31 | 0.00 | 28.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.68 | 0.00 | 28.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 28.63 | 5.00 | 28.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 58.67 | 28.08 | 27.67 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 28.12 | 26.50 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 28.96 | 1.17 | 28.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 28.50 | 0.00 | 28.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 28.00 | 0.00 | 28.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.53 | 0.00 | 27.53 |
Annual Sum or Average | 0.00 | 0.00 | 354.67 | 28.27 | 60.33 | 28.07 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.46 | 0.00 | 27.46 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 58.67 | 28.96 | 27.67 | 28.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 602.67 | 20.98 | 203.33 | 20.87 | 203.33 | 20.81 |
February | 495.17 | 21.12 | 112.50 | 21.00 | 112.17 | 20.91 |
March | 459.67 | 21.50 | 129.17 | 21.86 | 34.17 | 21.81 |
April | 349.17 | 22.01 | 255.50 | 22.69 | 85.17 | 22.74 |
May | 286.83 | 23.10 | 495.83 | 23.52 | 205.50 | 23.53 |
June | 304.67 | 23.75 | 548.17 | 23.84 | 280.50 | 23.85 |
July | 437.17 | 23.88 | 609.00 | 23.88 | 437.17 | 23.88 |
August | 500.17 | 23.89 | 612.00 | 23.89 | 500.17 | 23.89 |
September | 347.00 | 23.67 | 534.83 | 23.79 | 306.50 | 23.81 |
October | 399.17 | 21.99 | 287.17 | 22.72 | 117.17 | 22.84 |
November | 471.17 | 21.44 | 119.33 | 21.74 | 63.50 | 21.77 |
December | 585.50 | 21.07 | 108.67 | 21.05 | 90.33 | 20.97 |
Annual Sum or Average | 5238.33 | 22.21 | 4015.50 | 22.75 | 2435.67 | 22.83 |
Minimum of Months | 286.83 | 20.98 | 108.67 | 20.87 | 34.17 | 20.81 |
Maximum of Months | 602.67 | 23.89 | 612.00 | 23.89 | 500.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 570.83 | 19.51 | 271.33 | 19.68 | 238.50 | 19.64 |
February | 438.17 | 20.68 | 299.83 | 21.45 | 206.17 | 21.52 |
March | 398.50 | 23.06 | 387.83 | 24.10 | 205.67 | 24.43 |
April | 418.50 | 25.05 | 502.17 | 25.27 | 352.33 | 25.45 |
May | 549.83 | 25.94 | 591.67 | 25.91 | 540.33 | 25.95 |
June | 566.33 | 26.12 | 588.67 | 26.10 | 566.33 | 26.11 |
July | 609.00 | 26.16 | 609.00 | 26.16 | 609.00 | 26.16 |
August | 612.00 | 26.18 | 612.00 | 26.18 | 612.00 | 26.18 |
September | 554.50 | 26.10 | 590.00 | 26.05 | 554.50 | 26.07 |
October | 438.67 | 24.96 | 500.00 | 25.16 | 355.17 | 25.40 |
November | 408.00 | 22.61 | 353.17 | 23.63 | 203.50 | 23.97 |
December | 474.00 | 20.08 | 217.83 | 20.70 | 132.83 | 20.70 |
Annual Sum or Average | 6038.33 | 24.02 | 5523.50 | 24.56 | 4576.33 | 24.78 |
Minimum of Months | 398.50 | 19.51 | 217.83 | 19.68 | 132.83 | 19.64 |
Maximum of Months | 612.00 | 26.18 | 612.00 | 26.18 | 612.00 | 26.18 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 21.00928 | 27.56275 | -0.4575 | 10.94702 |
February | 551.00000 | 21.39751 | 30.84995 | -0.3134 | 9.49344 |
March | 612.00000 | 22.07775 | 37.55383 | -0.0464 | 7.83957 |
April | 590.00000 | 22.75689 | 46.84654 | 0.19057 | 8.37346 |
May | 611.00000 | 23.50235 | 56.53111 | -0.4250 | 10.87230 |
June | 592.00000 | 23.81339 | 59.82639 | -0.2289 | 6.99039 |
July | 609.00000 | 23.88079 | 67.83435 | -0.1246 | 5.53397 |
August | 612.00000 | 23.89004 | 68.81848 | -0.0908 | 5.35790 |
September | 590.00000 | 23.72169 | 62.31876 | -0.2377 | 7.28887 |
October | 610.00000 | 22.60649 | 51.68360 | 0.24104 | 9.10655 |
November | 591.00000 | 21.91568 | 38.71389 | -0.0479 | 7.92592 |
December | 609.00000 | 21.16821 | 32.84833 | -0.3237 | 8.96151 |
Annual Sum or Average | 7187.00000 | 22.65128 | 48.55981 | -0.1549 | 8.21962 |
Minimum of Months | 551.00000 | 21.00928 | 27.56275 | -0.4575 | 5.35790 |
Maximum of Months | 612.00000 | 23.89004 | 68.81848 | 0.24104 | 10.94702 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.79245 | 35.36687 | -0.3856 | 13.90542 |
February | 551.00000 | 21.38089 | 36.13992 | -0.0071 | 15.56153 |
March | 612.00000 | 23.50476 | 39.59959 | 0.52588 | 18.67144 |
April | 590.00000 | 24.77996 | 45.60768 | 0.88051 | 26.53469 |
May | 611.00000 | 25.75906 | 51.68834 | 0.58506 | 15.00262 |
June | 592.00000 | 26.05106 | 55.08215 | 0.76047 | 18.35805 |
July | 609.00000 | 26.16204 | 60.76228 | 0.86246 | 21.26467 |
August | 612.00000 | 26.17699 | 61.41015 | 0.88421 | 22.04107 |
September | 590.00000 | 25.99982 | 55.08808 | 0.74653 | 17.79166 |
October | 610.00000 | 24.53811 | 49.00513 | 0.88812 | 26.81562 |
November | 591.00000 | 23.01967 | 40.55719 | 0.45214 | 18.24639 |
December | 609.00000 | 20.85749 | 38.80988 | -0.0884 | 12.32522 |
Annual Sum or Average | 7187.00000 | 24.01396 | 47.50347 | 0.51091 | 18.88928 |
Minimum of Months | 551.00000 | 19.79245 | 35.36687 | -0.3856 | 12.32522 |
Maximum of Months | 612.00000 | 26.17699 | 61.41015 | 0.88812 | 26.81562 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 447309.97 | 141202.59 | 0.50 | 376040.26 | 71269.71 | 0.00 | 0.02 | 31-JAN-15:00 | 0.00 | 01-JAN-00:01 | 396.21 | 31-JAN-15:00 | 334.88 | 31-JAN-15:00 | 61.34 | 31-JAN-15:00 | 124.96 | 31-JAN-15:00 | 0.00 | 01-JAN-00:01 |
February | 0.447715E+09 | 0.133467E+09 | 30.38 | 0.437054E+09 | 10660598.72 | 0.00 | 0.46 | 28-FEB-14:00 | 0.00 | 01-FEB-00:03 | 10582.93 | 28-FEB-14:00 | 10122.14 | 28-FEB-14:00 | 460.80 | 28-FEB-14:00 | 3002.14 | 28-FEB-14:00 | 0.00 | 01-FEB-00:03 |
March | 0.210086E+10 | 0.599387E+09 | 87.10 | 0.155430E+10 | 0.546556E+09 | 0.00 | 0.72 | 30-MAR-17:10 | 0.00 | 01-MAR-00:05 | 17873.66 | 30-MAR-17:10 | 13366.09 | 30-MAR-17:05 | 5398.84 | 30-MAR-11:52 | 4729.63 | 30-MAR-17:10 | 0.00 | 01-MAR-00:05 |
April | 0.619000E+10 | 0.175386E+10 | 213.88 | 0.481377E+10 | 0.137624E+10 | 0.00 | 0.71 | 17-APR-17:10 | 0.00 | 01-APR-00:01 | 17642.80 | 17-APR-17:10 | 14960.48 | 17-APR-17:03 | 5473.99 | 04-APR-17:20 | 4678.92 | 17-APR-17:10 | 0.00 | 01-APR-00:01 |
May | 0.143379E+11 | 0.386853E+10 | 360.73 | 0.970793E+10 | 0.462993E+10 | 0.00 | 1.00 | 19-MAY-00:41 | 0.00 | 01-MAY-00:01 | 53978.96 | 19-MAY-00:41 | 33110.09 | 19-MAY-00:41 | 20868.87 | 19-MAY-00:41 | 13172.31 | 19-MAY-00:41 | 0.00 | 01-MAY-00:01 |
June | 0.308696E+11 | 0.791939E+10 | 565.15 | 0.190254E+11 | 0.118442E+11 | 0.00 | 1.00 | 01-JUN-01:22 | 0.00 | 01-JUN-00:01 | 58717.68 | 23-JUN-00:42 | 38953.94 | 04-JUN-01:01 | 36189.85 | 23-JUN-00:42 | 13495.78 | 23-JUN-00:42 | 0.00 | 01-JUN-00:01 |
July | 0.394750E+11 | 0.996419E+10 | 633.98 | 0.223632E+11 | 0.171118E+11 | 0.00 | 1.00 | 01-JUL-12:25 | 0.00 | 01-JUL-00:01 | 58392.10 | 23-JUL-00:08 | 31883.06 | 03-JUL-00:42 | 34308.83 | 23-JUL-00:08 | 13472.92 | 23-JUL-00:08 | 0.00 | 01-JUL-00:01 |
August | 0.449259E+11 | 0.112233E+11 | 692.29 | 0.241579E+11 | 0.207681E+11 | 0.00 | 1.00 | 01-AUG-10:22 | 0.00 | 01-AUG-00:01 | 40019.68 | 18-AUG-11:53 | 26084.32 | 01-AUG-17:10 | 18343.67 | 19-AUG-17:10 | 10364.92 | 01-AUG-17:10 | 0.00 | 01-AUG-00:01 |
September | 0.231099E+11 | 0.598604E+10 | 497.22 | 0.133474E+11 | 0.976242E+10 | 0.00 | 1.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:01 | 58351.74 | 03-SEP-00:09 | 29916.65 | 01-SEP-00:42 | 34208.84 | 03-SEP-00:09 | 13470.10 | 03-SEP-00:09 | 0.00 | 01-SEP-00:01 |
October | 0.639203E+10 | 0.171921E+10 | 190.51 | 0.386970E+10 | 0.252233E+10 | 0.00 | 1.00 | 02-OCT-00:42 | 0.00 | 01-OCT-00:01 | 57787.04 | 18-OCT-00:42 | 25148.40 | 18-OCT-00:42 | 32638.64 | 18-OCT-00:42 | 13431.04 | 18-OCT-00:42 | 0.00 | 01-OCT-00:01 |
November | 0.839639E+09 | 0.247967E+09 | 62.90 | 0.559355E+09 | 0.280283E+09 | 0.00 | 0.47 | 05-NOV-16:10 | 0.00 | 01-NOV-00:01 | 11056.61 | 05-NOV-16:10 | 7468.68 | 05-NOV-16:03 | 3986.09 | 05-NOV-14:00 | 3096.73 | 05-NOV-16:10 | 0.00 | 01-NOV-00:01 |
December | 0.111546E+09 | 33591671.14 | 10.39 | 74834452.70 | 36711456.44 | 0.00 | 0.39 | 12-DEC-14:00 | 0.00 | 01-DEC-00:01 | 8931.71 | 12-DEC-14:00 | 5895.47 | 12-DEC-14:00 | 3636.61 | 13-DEC-04:59 | 2565.61 | 12-DEC-14:00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.168801E+12 | 0.434491E+11 | 3345.02 | 0.999113E+11 | 0.688893E+11 | 0.00 | ||||||||||||||
Minimum of Months | 447309.97 | 141202.59 | 0.50 | 376040.26 | 71269.71 | 0.00 | 0.02 | 0.00 | 396.21 | 334.88 | 61.34 | 124.96 | 0.00 | |||||||
Maximum of Months | 0.449259E+11 | 0.112233E+11 | 692.29 | 0.241579E+11 | 0.207681E+11 | 0.00 | 1.00 | 0.00 | 58717.68 | 38953.94 | 36189.85 | 13495.78 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.226502E+09 | 65220711.03 | 25.33 | 0.147675E+09 | 78826808.50 | 0.00 | 1.00 | 20-JAN-01:42 | 0.00 | 01-JAN-00:01 | 32274.48 | 20-JAN-05:01 | 15202.38 | 20-JAN-05:01 | 17072.10 | 20-JAN-05:01 | 7737.78 | 20-JAN-05:01 | 0.00 | 01-JAN-00:01 |
February | 0.129630E+10 | 0.361476E+09 | 83.33 | 0.116478E+10 | 0.131517E+09 | 0.00 | 1.00 | 16-FEB-04:12 | 0.00 | 01-FEB-00:03 | 32274.48 | 17-FEB-05:01 | 28626.73 | 22-FEB-01:42 | 15549.47 | 19-FEB-05:01 | 7737.78 | 17-FEB-05:01 | 0.00 | 01-FEB-00:03 |
March | 0.470795E+10 | 0.123270E+10 | 198.63 | 0.343164E+10 | 0.127631E+10 | 0.00 | 1.00 | 01-MAR-01:42 | 0.00 | 01-MAR-00:05 | 32274.48 | 09-MAR-03:42 | 27989.70 | 21-MAR-00:42 | 15633.41 | 09-MAR-05:01 | 7737.78 | 08-MAR-04:32 | 0.00 | 01-MAR-00:05 |
April | 0.112127E+11 | 0.285523E+10 | 333.46 | 0.825793E+10 | 0.295474E+10 | 0.00 | 1.00 | 01-APR-01:22 | 0.00 | 01-APR-00:01 | 33464.05 | 03-APR-00:14 | 27400.72 | 09-APR-02:42 | 18829.01 | 24-APR-02:42 | 7817.37 | 03-APR-00:14 | 0.00 | 01-APR-00:01 |
May | 0.233357E+11 | 0.564885E+10 | 494.92 | 0.151971E+11 | 0.813857E+10 | 0.00 | 1.00 | 01-MAY-00:06 | 0.00 | 01-MAY-00:01 | 34880.43 | 31-MAY-00:03 | 24877.78 | 11-MAY-01:22 | 20807.48 | 31-MAY-03:22 | 7912.12 | 31-MAY-00:03 | 0.00 | 01-MAY-00:01 |
June | 0.424408E+11 | 0.996407E+10 | 636.93 | 0.261746E+11 | 0.162661E+11 | 0.00 | 1.00 | 01-JUN-00:03 | 0.00 | 01-JUN-00:01 | 35859.07 | 26-JUN-10:50 | 28255.50 | 11-JUN-00:41 | 23962.27 | 27-JUN-00:42 | 8375.28 | 23-JUN-13:53 | 0.00 | 01-JUN-00:01 |
July | 0.554035E+11 | 0.128659E+11 | 699.83 | 0.308733E+11 | 0.245303E+11 | 0.00 | 1.00 | 01-JUL-00:03 | 0.00 | 01-JUL-00:01 | 35859.07 | 19-JUL-10:55 | 28585.62 | 08-JUL-15:05 | 25061.02 | 27-JUL-00:03 | 8902.67 | 08-JUL-14:55 | 0.00 | 01-JUL-00:01 |
August | 0.620329E+11 | 0.142159E+11 | 711.30 | 0.322242E+11 | 0.298087E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:01 | 35859.07 | 03-AUG-04:02 | 27502.00 | 18-AUG-13:00 | 24503.56 | 24-AUG-00:03 | 8658.54 | 01-AUG-15:15 | 0.00 | 01-AUG-00:01 |
September | 0.358052E+11 | 0.839478E+10 | 597.25 | 0.195241E+11 | 0.162811E+11 | 0.00 | 1.00 | 01-SEP-00:03 | 0.00 | 01-SEP-00:01 | 35859.07 | 04-SEP-11:05 | 22502.45 | 07-SEP-12:20 | 23501.95 | 17-SEP-00:42 | 8183.50 | 06-SEP-12:55 | 0.00 | 01-SEP-00:01 |
October | 0.126444E+11 | 0.309329E+10 | 327.66 | 0.730986E+10 | 0.533453E+10 | 0.00 | 1.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:01 | 35859.07 | 19-OCT-00:03 | 24746.95 | 12-OCT-00:41 | 24790.68 | 19-OCT-00:03 | 7981.47 | 19-OCT-00:03 | 0.00 | 01-OCT-00:01 |
November | 0.393800E+10 | 0.104187E+10 | 172.16 | 0.252216E+10 | 0.141585E+10 | 0.00 | 1.00 | 01-NOV-02:52 | 0.00 | 01-NOV-00:01 | 32274.48 | 01-NOV-03:32 | 25900.78 | 07-NOV-04:31 | 16896.33 | 20-NOV-01:42 | 7737.78 | 01-NOV-03:32 | 0.00 | 01-NOV-00:01 |
December | 0.805615E+09 | 0.215656E+09 | 41.32 | 0.470100E+09 | 0.335515E+09 | 0.00 | 1.00 | 06-DEC-04:22 | 0.00 | 01-DEC-00:01 | 32274.48 | 13-DEC-01:42 | 25025.67 | 08-DEC-04:11 | 17516.00 | 12-DEC-05:01 | 7737.78 | 08-DEC-04:11 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.253849E+12 | 0.599550E+11 | 4322.12 | 0.147297E+12 | 0.106552E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.226502E+09 | 65220711.03 | 25.33 | 0.147675E+09 | 78826808.50 | 0.00 | 1.00 | 0.00 | 32274.48 | 15202.38 | 15549.47 | 7737.78 | 0.00 | |||||||
Maximum of Months | 0.620329E+11 | 0.142159E+11 | 711.30 | 0.322242E+11 | 0.298087E+11 | 0.00 | 1.00 | 0.00 | 35859.07 | 28626.73 | 25061.02 | 8902.67 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.74 | 26.96 | 32.78 | 36.22 | 239.57 | 0.00 | 0.00 | 0.00 |
February | 75.27 | 40.44 | 34.83 | 69.78 | 191.48 | 0.00 | 0.00 | 0.00 |
March | 94.68 | 43.09 | 51.59 | 108.52 | 115.52 | 0.00 | 0.00 | 0.00 |
April | 114.49 | 52.18 | 62.30 | 167.79 | 88.97 | 0.00 | 0.00 | 0.00 |
May | 125.72 | 53.15 | 72.58 | 207.02 | 60.14 | 0.00 | 0.00 | 0.00 |
June | 130.17 | 54.54 | 75.63 | 249.88 | 37.02 | 0.00 | 0.00 | 0.00 |
July | 126.91 | 53.33 | 73.58 | 254.04 | 25.76 | 0.00 | 0.00 | 0.00 |
August | 116.08 | 46.03 | 70.05 | 235.09 | 21.38 | 0.00 | 0.00 | 0.00 |
September | 95.39 | 42.24 | 53.15 | 160.88 | 53.93 | 0.00 | 0.00 | 0.00 |
October | 81.41 | 42.36 | 39.05 | 105.03 | 111.49 | 0.00 | 0.00 | 0.00 |
November | 65.11 | 29.49 | 35.62 | 59.33 | 150.05 | 0.00 | 0.00 | 0.00 |
December | 56.42 | 25.74 | 30.68 | 36.62 | 194.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.21 | 42.46 | 52.76 | 141.23 | 107.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.42 | 25.74 | 30.68 | 36.22 | 21.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.17 | 54.54 | 75.63 | 254.04 | 239.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 290.39 | 202.32 | 88.07 | 328.94 | 427.91 | 0.00 | 0.00 | 0.00 |
February | 271.30 | 181.81 | 89.49 | 342.13 | 358.63 | 0.00 | 0.00 | 0.00 |
March | 244.58 | 127.68 | 116.90 | 343.00 | 234.93 | 0.00 | 0.00 | 0.00 |
April | 183.60 | 60.28 | 123.31 | 290.86 | 192.57 | 0.00 | 0.00 | 0.00 |
May | 148.21 | 17.66 | 130.55 | 248.92 | 129.23 | 0.00 | 0.00 | 0.00 |
June | 136.89 | 7.91 | 128.98 | 282.99 | 80.33 | 0.00 | 0.00 | 0.00 |
July | 138.44 | 10.65 | 127.79 | 305.05 | 54.38 | 0.00 | 0.00 | 0.00 |
August | 165.45 | 31.39 | 134.06 | 368.19 | 44.81 | 0.00 | 0.00 | 0.00 |
September | 181.85 | 67.98 | 113.87 | 331.70 | 111.49 | 0.00 | 0.00 | 0.00 |
October | 262.96 | 170.39 | 92.57 | 408.30 | 222.86 | 0.00 | 0.00 | 0.00 |
November | 282.43 | 187.31 | 95.13 | 388.45 | 289.92 | 0.00 | 0.00 | 0.00 |
December | 286.20 | 201.20 | 85.00 | 352.20 | 358.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 215.79 | 105.19 | 110.60 | 332.58 | 208.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.89 | 7.91 | 85.00 | 248.92 | 44.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 290.39 | 202.32 | 134.06 | 408.30 | 427.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.35 | 28.47 | 32.88 | 43.10 | 246.94 | 0.00 | 0.00 | 0.00 |
February | 70.41 | 32.92 | 37.49 | 68.74 | 200.45 | 0.00 | 0.00 | 0.00 |
March | 103.74 | 50.11 | 53.63 | 131.12 | 122.18 | 0.00 | 0.00 | 0.00 |
April | 116.70 | 53.37 | 63.32 | 175.62 | 94.75 | 0.00 | 0.00 | 0.00 |
May | 117.31 | 44.42 | 72.88 | 196.73 | 63.65 | 0.00 | 0.00 | 0.00 |
June | 123.37 | 47.44 | 75.92 | 239.25 | 39.87 | 0.00 | 0.00 | 0.00 |
July | 116.36 | 43.13 | 73.24 | 236.65 | 26.84 | 0.00 | 0.00 | 0.00 |
August | 114.01 | 42.62 | 71.40 | 232.99 | 22.30 | 0.00 | 0.00 | 0.00 |
September | 92.87 | 38.66 | 54.21 | 157.96 | 55.73 | 0.00 | 0.00 | 0.00 |
October | 82.76 | 42.96 | 39.81 | 114.03 | 118.84 | 0.00 | 0.00 | 0.00 |
November | 66.08 | 29.67 | 36.41 | 70.86 | 161.72 | 0.00 | 0.00 | 0.00 |
December | 54.53 | 23.87 | 30.66 | 42.43 | 206.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.41 | 39.83 | 53.58 | 142.86 | 112.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.53 | 23.87 | 30.66 | 42.43 | 22.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.37 | 53.37 | 75.92 | 239.25 | 246.94 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160003E+09 | 72209612.19 | 87793297.62 | 97011549.42 | 0.641658E+09 |
February | 0.182099E+09 | 97835435.23 | 84263374.84 | 0.168824E+09 | 0.463218E+09 |
March | 0.253596E+09 | 0.115408E+09 | 0.138188E+09 | 0.290654E+09 | 0.309418E+09 |
April | 0.296754E+09 | 0.135261E+09 | 0.161493E+09 | 0.434913E+09 | 0.230606E+09 |
May | 0.336737E+09 | 0.142349E+09 | 0.194388E+09 | 0.554474E+09 | 0.161088E+09 |
June | 0.337402E+09 | 0.141368E+09 | 0.196034E+09 | 0.647688E+09 | 95943935.29 |
July | 0.339911E+09 | 0.142837E+09 | 0.197074E+09 | 0.680422E+09 | 68999103.13 |
August | 0.310911E+09 | 0.123289E+09 | 0.187622E+09 | 0.629659E+09 | 57272727.63 |
September | 0.247255E+09 | 0.109492E+09 | 0.137763E+09 | 0.416997E+09 | 0.139795E+09 |
October | 0.218040E+09 | 0.113444E+09 | 0.104596E+09 | 0.281302E+09 | 0.298618E+09 |
November | 0.168762E+09 | 76440946.20 | 92320790.08 | 0.153772E+09 | 0.388941E+09 |
December | 0.151104E+09 | 68929974.70 | 82173747.58 | 98078899.86 | 0.520606E+09 |
Annual Sum or Average | 0.300257E+10 | 0.133886E+10 | 0.166371E+10 | 0.445380E+10 | 0.337617E+10 |
Minimum of Months | 0.151104E+09 | 68929974.70 | 82173747.58 | 97011549.42 | 57272727.63 |
Maximum of Months | 0.339911E+09 | 0.142837E+09 | 0.197074E+09 | 0.680422E+09 | 0.641658E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.777779E+09 | 0.541906E+09 | 0.235874E+09 | 0.881041E+09 | 0.114611E+10 |
February | 0.656333E+09 | 0.439844E+09 | 0.216489E+09 | 0.827688E+09 | 0.867590E+09 |
March | 0.655080E+09 | 0.341977E+09 | 0.313103E+09 | 0.918678E+09 | 0.629237E+09 |
April | 0.475886E+09 | 0.156254E+09 | 0.319632E+09 | 0.753904E+09 | 0.499152E+09 |
May | 0.396976E+09 | 47309970.15 | 0.349666E+09 | 0.666702E+09 | 0.346122E+09 |
June | 0.354832E+09 | 20510875.98 | 0.334321E+09 | 0.733511E+09 | 0.208223E+09 |
July | 0.370786E+09 | 28524956.17 | 0.342261E+09 | 0.817038E+09 | 0.145642E+09 |
August | 0.443137E+09 | 84062103.91 | 0.359075E+09 | 0.986173E+09 | 0.120026E+09 |
September | 0.471355E+09 | 0.176206E+09 | 0.295148E+09 | 0.859760E+09 | 0.288984E+09 |
October | 0.704323E+09 | 0.456378E+09 | 0.247945E+09 | 0.109358E+10 | 0.596898E+09 |
November | 0.732070E+09 | 0.485498E+09 | 0.246572E+09 | 0.100686E+10 | 0.751476E+09 |
December | 0.766552E+09 | 0.538891E+09 | 0.227660E+09 | 0.943340E+09 | 0.960479E+09 |
Annual Sum or Average | 0.680511E+10 | 0.331736E+10 | 0.348775E+10 | 0.104883E+11 | 0.655994E+10 |
Minimum of Months | 0.354832E+09 | 20510875.98 | 0.216489E+09 | 0.666702E+09 | 0.120026E+09 |
Maximum of Months | 0.777779E+09 | 0.541906E+09 | 0.359075E+09 | 0.109358E+10 | 0.114611E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.164333E+09 | 76262544.76 | 88070065.93 | 0.115429E+09 | 0.661402E+09 |
February | 0.170328E+09 | 79637430.18 | 90691023.63 | 0.166302E+09 | 0.484940E+09 |
March | 0.277848E+09 | 0.134206E+09 | 0.143642E+09 | 0.351188E+09 | 0.327260E+09 |
April | 0.302474E+09 | 0.138337E+09 | 0.164137E+09 | 0.455203E+09 | 0.245602E+09 |
May | 0.314190E+09 | 0.118985E+09 | 0.195205E+09 | 0.526921E+09 | 0.170487E+09 |
June | 0.319767E+09 | 0.122971E+09 | 0.196796E+09 | 0.620143E+09 | 0.103335E+09 |
July | 0.311668E+09 | 0.115514E+09 | 0.196153E+09 | 0.633846E+09 | 71882345.35 |
August | 0.305367E+09 | 0.114140E+09 | 0.191226E+09 | 0.624053E+09 | 59727708.57 |
September | 0.240723E+09 | 0.100207E+09 | 0.140516E+09 | 0.409433E+09 | 0.144465E+09 |
October | 0.221671E+09 | 0.115055E+09 | 0.106616E+09 | 0.305424E+09 | 0.318309E+09 |
November | 0.171274E+09 | 76901102.86 | 94373066.52 | 0.183666E+09 | 0.419181E+09 |
December | 0.146056E+09 | 63932029.07 | 82123774.66 | 0.113649E+09 | 0.552949E+09 |
Annual Sum or Average | 0.294570E+10 | 0.125615E+10 | 0.168955E+10 | 0.450526E+10 | 0.355954E+10 |
Minimum of Months | 0.146056E+09 | 63932029.07 | 82123774.66 | 0.113649E+09 | 59727708.57 |
Maximum of Months | 0.319767E+09 | 0.138337E+09 | 0.196796E+09 | 0.633846E+09 | 0.661402E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 362.33 | 868.48 | 411.48 | 257.76 | 153.73 | 0.00 | 0.00 |
February | 445.27 | 715.17 | 416.98 | 255.17 | 161.81 | 0.00 | 0.00 |
March | 562.82 | 452.83 | 443.00 | 220.87 | 222.12 | 0.00 | 0.00 |
April | 614.90 | 356.93 | 414.78 | 165.84 | 248.94 | 0.00 | 0.00 |
May | 643.28 | 243.63 | 391.24 | 115.23 | 276.01 | 0.00 | 0.00 |
June | 766.10 | 151.19 | 390.43 | 109.90 | 280.54 | 0.00 | 0.00 |
July | 792.64 | 103.88 | 381.71 | 107.11 | 274.60 | 0.00 | 0.00 |
August | 834.30 | 86.52 | 395.54 | 120.03 | 275.51 | 0.00 | 0.00 |
September | 645.33 | 215.95 | 370.11 | 148.88 | 221.23 | 0.00 | 0.00 |
October | 614.06 | 439.90 | 427.13 | 255.70 | 171.43 | 0.00 | 0.00 |
November | 499.73 | 582.79 | 413.62 | 246.47 | 167.16 | 0.00 | 0.00 |
December | 398.39 | 726.56 | 397.14 | 250.80 | 146.34 | 0.00 | 0.00 |
Annual Sum or Average | 599.16 | 410.43 | 404.41 | 187.48 | 216.93 | 0.00 | 0.00 |
Minimum of Months | 362.33 | 86.52 | 370.11 | 107.11 | 146.34 | 0.00 | 0.00 |
Maximum of Months | 834.30 | 868.48 | 443.00 | 257.76 | 280.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.970458E+09 | 0.232615E+10 | 0.110211E+10 | 0.690378E+09 | 0.411737E+09 | 0.00 | 0.00 |
February | 0.107720E+10 | 0.173014E+10 | 0.100876E+10 | 0.617317E+09 | 0.391443E+09 | 0.00 | 0.00 |
March | 0.150747E+10 | 0.121286E+10 | 0.118652E+10 | 0.591590E+09 | 0.594933E+09 | 0.00 | 0.00 |
April | 0.159382E+10 | 0.925161E+09 | 0.107511E+10 | 0.429851E+09 | 0.645263E+09 | 0.00 | 0.00 |
May | 0.172295E+10 | 0.652549E+09 | 0.104790E+10 | 0.308644E+09 | 0.739259E+09 | 0.00 | 0.00 |
June | 0.198573E+10 | 0.391886E+09 | 0.101200E+10 | 0.284850E+09 | 0.727150E+09 | 0.00 | 0.00 |
July | 0.212301E+10 | 0.278231E+09 | 0.102236E+10 | 0.286876E+09 | 0.735488E+09 | 0.00 | 0.00 |
August | 0.223459E+10 | 0.231727E+09 | 0.105941E+10 | 0.321491E+09 | 0.737923E+09 | 0.00 | 0.00 |
September | 0.167269E+10 | 0.559740E+09 | 0.959332E+09 | 0.385905E+09 | 0.573427E+09 | 0.00 | 0.00 |
October | 0.164471E+10 | 0.117823E+10 | 0.114403E+10 | 0.684876E+09 | 0.459158E+09 | 0.00 | 0.00 |
November | 0.129529E+10 | 0.151060E+10 | 0.107211E+10 | 0.638840E+09 | 0.433266E+09 | 0.00 | 0.00 |
December | 0.106705E+10 | 0.194602E+10 | 0.106371E+10 | 0.671753E+09 | 0.391958E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.188950E+11 | 0.129433E+11 | 0.127534E+11 | 0.591237E+10 | 0.684101E+10 | 0.00 | 0.00 |
Minimum of Months | 0.970458E+09 | 0.231727E+09 | 0.959332E+09 | 0.284850E+09 | 0.391443E+09 | 0.00 | 0.00 |
Maximum of Months | 0.223459E+10 | 0.232615E+10 | 0.118652E+10 | 0.690378E+09 | 0.739259E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.132407E+11 | -0.124635E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -777126235.0 | 58.99 | 0.00 | 0.00 |
February | 0.119558E+11 | -0.112798E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -675988466.8 | 58.99 | 0.00 | 0.00 |
March | 0.128044E+11 | -0.120946E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -709718848.8 | 58.99 | 0.00 | 0.00 |
April | 0.115926E+11 | -0.109274E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -665253953.5 | 58.99 | 0.00 | 0.00 |
May | 0.110581E+11 | -0.103881E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -670007871.5 | 58.99 | 0.00 | 0.00 |
June | 0.991029E+10 | -0.926701E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -643280530.9 | 58.99 | 0.00 | 0.00 |
July | 0.971857E+10 | -0.905622E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -662349232.0 | 58.99 | 0.00 | 0.00 |
August | 0.971167E+10 | -0.904993E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -661744827.8 | 58.98 | 0.00 | 0.00 |
September | 0.979956E+10 | -0.915581E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -643756417.8 | 58.98 | 0.00 | 0.00 |
October | 0.109392E+11 | -0.102481E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -691096572.0 | 58.98 | 0.00 | 0.00 |
November | 0.115100E+11 | -0.108152E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -694800940.5 | 58.98 | 0.00 | 0.00 |
December | 0.127198E+11 | -0.119632E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -756544862.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.134961E+12 | -0.126709E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.825167E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.971167E+10 | -0.124635E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -777126235.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.132407E+11 | -0.904993E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -643280530.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.58 | 0.56 | 01-JAN-08:39 | 4222.29 | 27.37 | 192.67 | 272.33 | 4159.26 | 27.33 | 192.00 | 272.83 |
February | 263.00 | 0.58 | 0.56 | 01-FEB-09:00 | 2053.95 | 21.41 | 100.17 | 255.00 | 1913.87 | 20.09 | 85.33 | 255.33 |
March | 351.67 | 0.58 | 0.56 | 01-MAR-07:00 | 1553.11 | 17.34 | 48.83 | 331.83 | 1349.38 | 17.36 | 41.17 | 333.33 |
April | 369.33 | 0.58 | 0.56 | 01-APR-07:49 | 1780.07 | 14.89 | 0.00 | 349.17 | 1422.29 | 14.93 | 0.00 | 346.00 |
May | 407.00 | 0.57 | 0.56 | 01-MAY-06:49 | 1286.56 | 15.09 | 0.00 | 391.67 | 1774.79 | 15.09 | 0.00 | 391.17 |
June | 411.67 | 0.58 | 0.56 | 01-JUN-06:19 | 1276.68 | 14.85 | 0.00 | 385.17 | 1275.66 | 14.86 | 0.00 | 387.67 |
July | 411.00 | 0.58 | 0.56 | 01-JUL-06:10 | 1301.82 | 15.04 | 0.00 | 388.67 | 1759.46 | 14.99 | 0.00 | 390.67 |
August | 390.50 | 0.58 | 0.56 | 01-AUG-06:49 | 1411.58 | 15.71 | 3.67 | 367.83 | 1706.67 | 15.58 | 0.00 | 369.33 |
September | 298.50 | 0.58 | 0.56 | 01-SEP-06:00 | 1517.45 | 17.77 | 49.33 | 325.17 | 1510.46 | 15.46 | 2.33 | 324.50 |
October | 293.50 | 0.58 | 0.56 | 01-OCT-07:30 | 1653.86 | 19.84 | 89.50 | 303.67 | 1708.10 | 17.92 | 51.83 | 304.33 |
November | 299.00 | 0.59 | 0.56 | 01-NOV-07:00 | 4055.93 | 26.96 | 193.50 | 274.00 | 4195.34 | 29.57 | 234.50 | 274.17 |
December | 285.17 | 0.57 | 0.56 | 01-DEC-07:00 | 3722.76 | 26.35 | 176.17 | 271.50 | 3678.56 | 25.98 | 171.17 | 271.83 |
Annual Sum or Average | 4071.00 | 0.58 | 2043.54 | 18.78 | 853.83 | 3916.00 | 2113.69 | 18.54 | 778.33 | 3921.17 | ||
Minimum of Months | 263.00 | 0.57 | 0.56 | 1276.68 | 14.85 | 0.00 | 255.00 | 1275.66 | 14.86 | 0.00 | 255.33 | |
Maximum of Months | 411.67 | 0.59 | 0.56 | 4222.29 | 27.37 | 193.50 | 391.67 | 4195.34 | 29.57 | 234.50 | 391.17 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.289295E+11 | 61863.12 | 06-JAN-03:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172582E+11 | 61863.12 | 03-FEB-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.556503E+10 | 18604.66 | 19-MAR-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216214E+10 | 28038.05 | 06-APR-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.246928E+09 | 7947.09 | 11-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23395762.78 | 2569.83 | 10-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20640178.24 | 1985.07 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.272213E+10 | 15227.32 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.737314E+10 | 61863.12 | 22-NOV-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165832E+11 | 61863.12 | 01-DEC-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.808844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.289295E+11 | 61863.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.127590E+11 | 28660.00 | 27-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.722082E+10 | 48290.02 | 12-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.650825E+09 | 10530.07 | 19-MAR-04:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.315407E+09 | 11869.51 | 06-APR-04:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100512E+09 | 12831.52 | 26-OCT-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136203E+10 | 26393.80 | 22-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.466279E+10 | 29190.33 | 18-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.270714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.127590E+11 | 48290.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 447309.97 | 376040.26 | 396.21 | 31-JAN-15:00 | 334.88 | 0.00 |
February | 0.00 | 0.00 | 0.447715E+09 | 0.437054E+09 | 10582.93 | 28-FEB-14:00 | 10122.14 | 0.00 |
March | 0.00 | 0.00 | 0.210086E+10 | 0.155430E+10 | 17873.66 | 30-MAR-17:10 | 13364.40 | 0.00 |
April | 0.00 | 0.00 | 0.619000E+10 | 0.481377E+10 | 17642.80 | 17-APR-17:10 | 14957.99 | 0.00 |
May | 0.00 | 0.00 | 0.143379E+11 | 0.970793E+10 | 53978.96 | 19-MAY-00:41 | 33110.09 | 0.00 |
June | 0.00 | 0.00 | 0.308696E+11 | 0.190254E+11 | 58717.68 | 23-JUN-00:42 | 22527.83 | 0.00 |
July | 0.00 | 0.00 | 0.394750E+11 | 0.223632E+11 | 58392.10 | 23-JUL-00:08 | 24083.27 | 0.00 |
August | 0.00 | 0.00 | 0.449259E+11 | 0.241579E+11 | 40019.68 | 18-AUG-11:53 | 24844.50 | 0.00 |
September | 0.00 | 0.00 | 0.231099E+11 | 0.133474E+11 | 58351.74 | 03-SEP-00:09 | 24142.90 | 0.00 |
October | 0.00 | 0.00 | 0.639203E+10 | 0.386970E+10 | 57787.04 | 18-OCT-00:42 | 25148.40 | 0.00 |
November | 0.00 | 0.00 | 0.839639E+09 | 0.559355E+09 | 11056.61 | 05-NOV-16:10 | 7467.92 | 0.00 |
December | 0.00 | 0.00 | 0.111546E+09 | 74834452.70 | 8931.71 | 12-DEC-14:00 | 5895.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168801E+12 | 0.999113E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 447309.97 | 376040.26 | 396.21 | 334.88 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.449259E+11 | 0.241579E+11 | 58717.68 | 33110.09 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.226502E+09 | 0.147675E+09 | 32274.48 | 20-JAN-05:01 | 15202.38 | 0.00 |
February | 0.00 | 0.00 | 0.129630E+10 | 0.116478E+10 | 32274.48 | 17-FEB-05:01 | 17052.17 | 0.00 |
March | 0.00 | 0.00 | 0.470795E+10 | 0.343164E+10 | 32274.48 | 09-MAR-03:42 | 17232.81 | 0.00 |
April | 0.00 | 0.00 | 0.112127E+11 | 0.825793E+10 | 33464.05 | 03-APR-00:14 | 16033.17 | 0.00 |
May | 0.00 | 0.00 | 0.233357E+11 | 0.151971E+11 | 34880.43 | 31-MAY-00:03 | 14106.66 | 0.00 |
June | 0.00 | 0.00 | 0.424408E+11 | 0.261746E+11 | 35859.07 | 26-JUN-10:50 | 17364.94 | 0.00 |
July | 0.00 | 0.00 | 0.554035E+11 | 0.308733E+11 | 35859.07 | 19-JUL-10:55 | 14715.02 | 0.00 |
August | 0.00 | 0.00 | 0.620329E+11 | 0.322242E+11 | 35859.07 | 03-AUG-04:02 | 15231.70 | 0.00 |
September | 0.00 | 0.00 | 0.358052E+11 | 0.195241E+11 | 35859.07 | 04-SEP-11:05 | 18566.19 | 0.00 |
October | 0.00 | 0.00 | 0.126444E+11 | 0.730986E+10 | 35859.07 | 19-OCT-00:03 | 11068.39 | 0.00 |
November | 0.00 | 0.00 | 0.393800E+10 | 0.252216E+10 | 32274.48 | 01-NOV-03:32 | 18082.38 | 0.00 |
December | 0.00 | 0.00 | 0.805615E+09 | 0.470100E+09 | 32274.48 | 13-DEC-01:42 | 17174.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.253849E+12 | 0.147297E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.226502E+09 | 0.147675E+09 | 32274.48 | 11068.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.620329E+11 | 0.322242E+11 | 35859.07 | 18566.19 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 4944.72 | 18347.38 | 31-JAN-13:50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 4954.45 | 18347.70 | 01-FEB-13:25 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 4809.34 | 18054.39 | 01-MAR-13:40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4506.85 | 17130.38 | 01-APR-12:32 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 4171.04 | 15871.04 | 01-MAY-12:45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 3869.61 | 14550.98 | 01-JUN-13:00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 3672.85 | 13593.58 | 01-JUL-12:50 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 3674.01 | 13497.68 | 31-AUG-13:00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 3824.70 | 14384.40 | 30-SEP-13:00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4118.16 | 15678.73 | 31-OCT-13:00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4464.93 | 16961.92 | 30-NOV-13:20 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4757.37 | 17958.67 | 31-DEC-13:40 |
Annual Sum or Average | 0.00 | 4310.36 | ||||
Minimum of Months | 0.00 | 0.00 | 3672.85 | 13497.68 | ||
Maximum of Months | 0.00 | 0.00 | 4954.45 | 18347.70 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.280590E+10 | 0.57 | 1211.87 | 01-JAN-00:01 | 0.66 |
February | 0.263999E+10 | 0.59 | 1211.87 | 01-FEB-00:03 | 0.66 |
March | 0.307238E+10 | 0.62 | 1211.87 | 01-MAR-00:05 | 0.66 |
April | 0.298780E+10 | 0.62 | 1211.87 | 01-APR-00:09 | 0.66 |
May | 0.310263E+10 | 0.62 | 1211.87 | 01-MAY-00:06 | 0.65 |
June | 0.300564E+10 | 0.62 | 1211.87 | 01-JUN-00:03 | 0.65 |
July | 0.310623E+10 | 0.62 | 1211.87 | 01-JUL-00:03 | 0.65 |
August | 0.310613E+10 | 0.62 | 1211.87 | 01-AUG-00:03 | 0.65 |
September | 0.300521E+10 | 0.62 | 1211.87 | 01-SEP-00:03 | 0.65 |
October | 0.309705E+10 | 0.63 | 1211.87 | 01-OCT-00:05 | 0.65 |
November | 0.295311E+10 | 0.62 | 1211.87 | 01-NOV-00:19 | 0.66 |
December | 0.292012E+10 | 0.59 | 1211.87 | 01-DEC-00:01 | 0.66 |
Annual Sum or Average | 0.358022E+11 | 0.61 | |||
Minimum of Months | 0.263999E+10 | 0.57 | 1211.87 | 0.65 | |
Maximum of Months | 0.310623E+10 | 0.63 | 1211.87 | 0.66 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.281847E+10 | 0.58 | 2357.71 | 06-JAN-03:08 | 0.92 |
February | 0.232357E+10 | 0.53 | 2357.71 | 03-FEB-03:10 | 0.92 |
March | 0.223460E+10 | 0.48 | 1362.26 | 19-MAR-06:50 | 0.69 |
April | 0.208822E+10 | 0.47 | 1329.68 | 06-APR-06:10 | 0.68 |
May | 0.212615E+10 | 0.49 | 1124.81 | 11-MAY-06:10 | 0.62 |
June | 0.210355E+10 | 0.52 | 1390.18 | 23-JUN-11:53 | 0.69 |
July | 0.222202E+10 | 0.53 | 1624.38 | 07-JUL-12:00 | 0.75 |
August | 0.224666E+10 | 0.54 | 1548.23 | 01-AUG-17:10 | 0.73 |
September | 0.208029E+10 | 0.52 | 1307.86 | 06-SEP-11:53 | 0.67 |
October | 0.217737E+10 | 0.48 | 1291.29 | 26-OCT-06:10 | 0.67 |
November | 0.221103E+10 | 0.49 | 2357.71 | 22-NOV-03:02 | 0.91 |
December | 0.249997E+10 | 0.53 | 2357.71 | 01-DEC-03:02 | 0.91 |
Annual Sum or Average | 0.271319E+11 | 0.51 | |||
Minimum of Months | 0.208029E+10 | 0.47 | 1124.81 | 0.62 | |
Maximum of Months | 0.281847E+10 | 0.58 | 2357.71 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146919E+10 | 0.53 | 1458.59 | 20-JAN-05:01 | 0.94 |
February | 0.128549E+10 | 0.53 | 1458.59 | 17-FEB-05:01 | 0.94 |
March | 0.136007E+10 | 0.54 | 1458.59 | 09-MAR-05:01 | 0.94 |
April | 0.132980E+10 | 0.54 | 1458.59 | 04-APR-03:21 | 0.94 |
May | 0.150966E+10 | 0.56 | 1458.59 | 02-MAY-03:21 | 0.94 |
June | 0.189362E+10 | 0.64 | 1458.59 | 02-JUN-03:21 | 0.94 |
July | 0.227972E+10 | 0.69 | 1458.59 | 01-JUL-00:03 | 0.93 |
August | 0.245211E+10 | 0.71 | 1458.59 | 01-AUG-00:03 | 0.93 |
September | 0.172847E+10 | 0.61 | 1458.59 | 01-SEP-03:21 | 0.93 |
October | 0.144169E+10 | 0.55 | 1458.59 | 02-OCT-00:03 | 0.93 |
November | 0.131847E+10 | 0.53 | 1458.59 | 03-NOV-03:21 | 0.94 |
December | 0.137644E+10 | 0.52 | 1458.59 | 12-DEC-05:01 | 0.94 |
Annual Sum or Average | 0.194447E+11 | 0.58 | |||
Minimum of Months | 0.128549E+10 | 0.52 | 1458.59 | 0.93 | |
Maximum of Months | 0.245211E+10 | 0.71 | 1458.59 | 0.94 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 51.00 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 51.94 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 52.57 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 52.63 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 51.66 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 53.58 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:05 | 0.00 | 0.00 | 53.71 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 54.48 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 53.94 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 52.56 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 52.93 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 52.52 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 51.00 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 54.48 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 39.75 | 39.75 | 4944.72 | 18347.38 | 31-JAN-13:50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 52.42 | 52.42 | 4954.45 | 18347.70 | 01-FEB-13:25 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 52.51 | 52.51 | 4809.34 | 18054.39 | 01-MAR-13:40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 52.64 | 52.64 | 4506.85 | 17130.38 | 01-APR-12:32 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 42.03 | 42.03 | 4171.04 | 15871.04 | 01-MAY-12:45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 53.74 | 53.74 | 3869.61 | 14550.98 | 01-JUN-13:00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 54.02 | 54.02 | 3672.85 | 13593.58 | 01-JUL-12:50 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 54.50 | 54.50 | 3674.01 | 13497.68 | 31-AUG-13:00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 53.87 | 53.87 | 3824.70 | 14384.40 | 30-SEP-13:00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 43.68 | 43.68 | 4118.16 | 15678.73 | 31-OCT-13:00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 53.37 | 53.37 | 4464.93 | 16961.92 | 30-NOV-13:20 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 52.59 | 52.59 | 4757.37 | 17958.67 | 31-DEC-13:40 |
Annual Sum or Average | 0.00 | 4310.36 | ||||||
Minimum of Months | 0.00 | 0.00 | 39.75 | 39.75 | 3672.85 | 13497.68 | ||
Maximum of Months | 0.00 | 0.00 | 54.50 | 54.50 | 4954.45 | 18347.70 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.281862E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.245704E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.283398E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.384208E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.599468E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.100229E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.121862E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.134699E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.806633E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.389659E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.245900E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.253357E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.705810E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.245704E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.134699E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.153441E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.164697E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.259276E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.418503E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.715851E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.118577E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.151456E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.166680E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.101233E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.453498E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.236035E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.159209E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.793997E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.153441E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.166680E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.281847E+10 | 447309.97 | 0.289295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.232357E+10 | 0.447715E+09 | 0.172582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.223460E+10 | 0.210086E+10 | 0.556503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.208822E+10 | 0.619000E+10 | 0.216214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.212615E+10 | 0.143363E+11 | 0.246928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.210355E+10 | 0.308519E+11 | 23395762.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.222202E+10 | 0.394705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.224666E+10 | 0.449259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.208029E+10 | 0.230998E+11 | 20640178.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.217737E+10 | 0.639006E+10 | 0.272213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.221103E+10 | 0.839639E+09 | 0.737314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.249997E+10 | 0.111546E+09 | 0.165832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271319E+11 | 0.168765E+12 | 0.808844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.208029E+10 | 447309.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.281847E+10 | 0.449259E+11 | 0.289295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146919E+10 | 0.226502E+09 | 0.127590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128549E+10 | 0.128877E+10 | 0.722082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136007E+10 | 0.467314E+10 | 0.650825E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132980E+10 | 0.111503E+11 | 0.315407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150966E+10 | 0.232751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.189362E+10 | 0.423870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.227972E+10 | 0.553994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.245211E+10 | 0.620329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172847E+10 | 0.357907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144169E+10 | 0.126146E+11 | 0.100512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131847E+10 | 0.392209E+10 | 0.136203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137644E+10 | 0.800285E+09 | 0.466279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194447E+11 | 0.253561E+12 | 0.270714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128549E+10 | 0.226502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.245211E+10 | 0.620329E+11 | 0.127590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.281847E+10 | 0.00 | 0.00 | 0.00 | 141202.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.232357E+10 | 0.00 | 0.00 | 0.00 | 0.133467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.223460E+10 | 0.00 | 0.00 | 0.00 | 0.599387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.208822E+10 | 0.00 | 0.00 | 0.00 | 0.175386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.212615E+10 | 0.00 | 0.00 | 0.00 | 0.386853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.210355E+10 | 0.00 | 0.00 | 0.00 | 0.791939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.222202E+10 | 0.00 | 0.00 | 0.00 | 0.996419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.224666E+10 | 0.00 | 0.00 | 0.00 | 0.112233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.208029E+10 | 0.00 | 0.00 | 0.00 | 0.598604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.217737E+10 | 0.00 | 0.00 | 0.00 | 0.171921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.221103E+10 | 0.00 | 0.00 | 0.00 | 0.247967E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.249997E+10 | 0.00 | 0.00 | 0.00 | 33591671.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271319E+11 | 0.00 | 0.00 | 0.00 | 0.434491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.208029E+10 | 0.00 | 0.00 | 0.00 | 141202.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.281847E+10 | 0.00 | 0.00 | 0.00 | 0.112233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146919E+10 | 0.00 | 0.00 | 0.00 | 65220711.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128549E+10 | 0.00 | 0.00 | 0.00 | 0.361476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136007E+10 | 0.00 | 0.00 | 0.00 | 0.123270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132980E+10 | 0.00 | 0.00 | 0.00 | 0.285523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150966E+10 | 0.00 | 0.00 | 0.00 | 0.564885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.189362E+10 | 0.00 | 0.00 | 0.00 | 0.996407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.227972E+10 | 0.00 | 0.00 | 0.00 | 0.128659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.245211E+10 | 0.00 | 0.00 | 0.00 | 0.142159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172847E+10 | 0.00 | 0.00 | 0.00 | 0.839478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144169E+10 | 0.00 | 0.00 | 0.00 | 0.309329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131847E+10 | 0.00 | 0.00 | 0.00 | 0.104187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137644E+10 | 0.00 | 0.00 | 0.00 | 0.215656E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194447E+11 | 0.00 | 0.00 | 0.00 | 0.599550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128549E+10 | 0.00 | 0.00 | 0.00 | 65220711.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.245211E+10 | 0.00 | 0.00 | 0.00 | 0.142159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.256475E+10 | 0.00 | 0.00 | 135497.38 | 0.00 | 0.208892E+11 | 0.122770E+09 | 0.00 | 3.60 |
February | 0.344734E+10 | 0.00 | 0.00 | 3198318.26 | 0.00 | 0.124041E+11 | 0.875679E+09 | 0.00 | 3.94 |
March | 0.517686E+10 | 81124280.11 | 0.00 | 6549574.14 | 0.00 | 0.416099E+10 | 0.192954E+10 | 0.00 | 4.26 |
April | 0.393946E+10 | 0.300314E+09 | 0.00 | 14790877.21 | 0.00 | 0.154661E+10 | 0.253533E+10 | 0.00 | 4.81 |
May | 0.196533E+10 | 0.174102E+10 | 0.00 | 16330059.12 | 0.00 | 0.117930E+09 | 0.337480E+10 | 0.00 | 5.08 |
June | 0.425928E+09 | 0.668083E+10 | 0.00 | 8560835.00 | 1675796.32 | 0.00 | 0.156573E+10 | 0.00 | 4.61 |
July | 70945438.25 | 0.102379E+11 | 0.00 | 3552805.54 | 4594338.96 | 0.00 | 0.117190E+10 | 0.00 | 4.28 |
August | 0.00 | 0.121066E+11 | 0.00 | 1270550.04 | 7580449.44 | 0.00 | 0.337000E+09 | 0.00 | 4.03 |
September | 0.875125E+09 | 0.416342E+10 | 0.00 | 11531433.96 | 2730761.28 | 0.00 | 0.240545E+10 | 0.00 | 4.71 |
October | 0.471770E+10 | 0.714940E+09 | 0.00 | 12115178.26 | 0.00 | 0.191617E+10 | 0.304418E+10 | 0.00 | 4.66 |
November | 0.525047E+10 | 11396615.59 | 0.00 | 5689728.18 | 0.00 | 0.544562E+10 | 0.228551E+10 | 0.00 | 4.26 |
December | 0.410503E+10 | 0.00 | 0.00 | 1012102.01 | 0.00 | 0.127618E+11 | 0.478900E+09 | 0.00 | 3.69 |
Annual Sum or Average | 0.325389E+11 | 0.360375E+11 | 0.00 | 84736959.10 | 16581346.01 | 0.592424E+11 | 0.201268E+11 | 0.00 | 4.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 135497.38 | 0.00 | 0.00 | 0.122770E+09 | 0.00 | 3.60 |
Maximum of Months | 0.525047E+10 | 0.121066E+11 | 0.00 | 16330059.12 | 7580449.44 | 0.208892E+11 | 0.337480E+10 | 0.00 | 5.08 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.438756E+11 | 0.00 | 0.00 | 5170994.17 | 0.00 | 17108260.29 | 0.355288E+10 | 0.00 | 7.69 |
February | 0.284395E+11 | 0.00 | 0.00 | 18927287.76 | 0.00 | 3059015.69 | 0.921093E+10 | 0.00 | 7.72 |
March | 0.150346E+11 | 0.00 | 0.00 | 46662019.59 | 0.00 | 0.00 | 0.168898E+11 | 0.00 | 7.78 |
April | 0.743392E+10 | 12921481.30 | 0.00 | 76499418.03 | 0.00 | 0.00 | 0.168471E+11 | 0.00 | 7.90 |
May | 0.155305E+10 | 0.110486E+10 | 0.00 | 91394530.85 | 0.00 | 0.00 | 0.132478E+11 | 0.00 | 8.37 |
June | 0.376179E+09 | 0.110430E+11 | 0.00 | 40510568.62 | 0.00 | 0.00 | 0.477694E+10 | 0.00 | 9.11 |
July | 1562799.26 | 0.192218E+11 | 0.00 | 12269918.40 | 0.00 | 0.00 | 0.145238E+10 | 0.00 | 9.60 |
August | 0.00 | 0.243976E+11 | 0.00 | 5913492.05 | 0.00 | 0.00 | 0.434340E+09 | 0.00 | 9.93 |
September | 0.209914E+09 | 0.748402E+10 | 0.00 | 51489312.46 | 0.00 | 0.00 | 0.787859E+10 | 0.00 | 8.88 |
October | 0.852149E+10 | 0.116771E+10 | 0.00 | 59624647.40 | 0.00 | 0.00 | 0.173724E+11 | 0.00 | 8.07 |
November | 0.165129E+11 | 0.00 | 0.00 | 37976428.40 | 0.00 | 2169380.54 | 0.166361E+11 | 0.00 | 7.75 |
December | 0.322758E+11 | 0.00 | 0.00 | 9923656.69 | 0.00 | 4694426.69 | 0.753416E+10 | 0.00 | 7.59 |
Annual Sum or Average | 0.154234E+12 | 0.644319E+11 | 0.00 | 0.456362E+09 | 0.00 | 27031083.21 | 0.115834E+12 | 0.00 | 8.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 5170994.17 | 0.00 | 0.00 | 0.434340E+09 | 0.00 | 7.59 |
Maximum of Months | 0.438756E+11 | 0.243976E+11 | 0.00 | 91394530.85 | 0.00 | 17108260.29 | 0.173724E+11 | 0.00 | 9.93 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:22
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.289910E+11 | 0.218688E+11 | 0.108474E+12 | 34387039.12 | 0.293752E+11 |
February | 0.312732E+11 | 0.157842E+11 | 0.877610E+11 | 0.359357E+09 | 0.278209E+11 |
March | 0.498989E+11 | 0.113111E+11 | 0.777364E+11 | 0.725409E+09 | 0.356210E+11 |
April | 0.587011E+11 | 0.719175E+10 | 0.580818E+11 | 0.116486E+10 | 0.512095E+11 |
May | 0.664445E+11 | 0.288437E+10 | 0.331197E+11 | 0.150817E+10 | 0.778161E+11 |
June | 0.669803E+11 | -0.474899E+10 | -0.801687E+10 | 0.711617E+09 | 0.121314E+12 |
July | 0.642547E+11 | -0.799431E+10 | -0.311981E+11 | 0.510360E+09 | 0.148046E+12 |
August | 0.592578E+11 | -0.101573E+11 | -0.433069E+11 | 0.173458E+09 | 0.162569E+12 |
September | 0.444562E+11 | -0.141269E+10 | 0.575419E+10 | 0.910271E+09 | 0.100674E+12 |
October | 0.395178E+11 | 0.792705E+10 | 0.606312E+11 | 0.136518E+10 | 0.509669E+11 |
November | 0.269362E+11 | 0.121874E+11 | 0.812740E+11 | 0.906502E+09 | 0.304738E+11 |
December | 0.238374E+11 | 0.168512E+11 | 0.963712E+11 | 0.176912E+09 | 0.260045E+11 |
Annual Sum or Average | 0.560549E+12 | 0.716927E+11 | 0.526681E+12 | 0.854648E+10 | 0.861890E+12 |
Minimum of Months | 0.238374E+11 | -0.101573E+11 | -0.433069E+11 | 34387039.12 | 0.260045E+11 |
Maximum of Months | 0.669803E+11 | 0.218688E+11 | 0.108474E+12 | 0.150817E+10 | 0.162569E+12 |