Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 08:25:36
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1427.17 | 6142.54 | 6142.54 |
Net Site Energy | 1427.17 | 6142.54 | 6142.54 |
Total Source Energy | 2524.56 | 10865.68 | 10865.68 |
Net Source Energy | 2524.56 | 10865.68 | 10865.68 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 263.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 36.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 265.86 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 59.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 216.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 51.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 469.28 | 957.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 263.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 36.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 27.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 59.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 216.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 14.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 28.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 263.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 36.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 28.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 27.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 265.86 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 59.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 216.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 51.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 241.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 413.90 | 2069.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1364.51 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2019.76 | 4122.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 241.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 413.90 | 2069.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1364.51 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2019.76 | 4122.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 469.278 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 469.278 | 100.00 |
Total On-Site and Utility Electric Sources | 469.278 | 100.00 |
Total Electricity End Uses | 469.278 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.50 |
Time Setpoint Not Met During Occupied Cooling | 0.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3516.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 7.5044 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 11.6310 | 18.52 | 1071.0790 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 9.5677 | 2.48 | 593.9329 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 9.5677 | 2.48 | 593.9329 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 7.5044 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.6310 | 18.52 | 1071.0790 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 9.5677 | 1.24 | 593.9329 | |||||||
Conditioned Total | 232.34 | 9.5677 | 1.24 | 593.9329 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 9.5677 | 2.48 | 593.9329 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-AUG-11:09 | 20-DEC-13:09 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 71625.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12757.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1225.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 13174.05 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3208.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25901.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2512.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 32877.88 | 120510.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 71625.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 12757.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1225.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 12146.55 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 3208.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 25901.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1313.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1004.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 286.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 116.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 91.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 85.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 841.99 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 188.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 235.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 162.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1486.20 | 1038.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1230.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 499.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 394.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 369.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3623.92 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 810.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1011.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 697.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6396.60 | 4469.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1230.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 499.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 394.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 369.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3623.92 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 810.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1011.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 697.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6396.60 | 4469.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 2.09 |
KITCHEN DIRECT AIR | 1.48 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.09 | 2.09 | 2.09 | 2.09 | 2.09 | 2.09 | 1.00 | 1.00 | 2.09 |
PSZ-AC_2:2 | 1.48 | 1.48 | 1.48 | 1.48 | 1.48 | 1.48 | 1.00 | 1.00 | 1.48 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.09 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.48 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 2.09 | 2234.94 |
PSZ-AC_2:2_ADDAQ FAN | 1.48 | 1586.65 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.09 | 2.09 | 2.09 | 1.38 | 34574.43 | 54693.91 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.48 | 1.48 | 1.48 | 0.978639 | 29595.70 | 78320.84 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.09 | 1.04 | 1.39 | 34574.43 | 17287.22 | 0.800660 | 0.800660 |
PSZ-AC_2:2 COOLING COIL | 1.48 | 0.741393 | 0.988527 | 29595.70 | 14797.85 | 0.776920 | 0.776920 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 54693.91 |
PSZ-AC_2:2 HEATING COIL | 78320.84 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 7.504 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 124.291 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 11.631 | 279.726 | 791.353 | 0.000 | 0.000 | 0.000 | 1082.710 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 871.800 | 7.504 | 9.958 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 871.800 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1351.195 | 11.631 | 215.388 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1351.195 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 457.500 | 3.938 | 72.928 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 570.000 | 4.907 | 90.861 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.4391 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2452 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2452 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.043 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.002 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.002 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.38584905E-12 | 0.75146531E-15 | -0.12966877E-12 | 0.12247089E-15 |
34 | 6 | 0.32626755E-07 | 0.12794687E-09 | 0.74410738E-08 | -0.15657130E-12 |
35 | 5 | -0.20999199E-03 | 0.10694986E-05 | -0.10771460E-03 | 0.73422529E-08 |
36 | 4 | 0.31512205 | 0.50965885E-03 | 0.10796022 | -0.36842960E-04 |
37 | 3 | -7.7206601 | 0.15495837E-01 | -2.4737779 | 0.31237450E-01 |
38 | 2 | 42.368774 | 0.54174396E-01 | 15.816616 | -0.35002435 |
39 | 1 | -81.692611 | 0.24088120E-01 | -29.635684 | 1.1030598 |
40 | 0 | 46.824332 | 0.47759164E-03 | 16.279740 | |
41 | 7 | -0.17135090E-08 | -0.36864923E-15 | 0.71259317E-14 | -0.97083918E-16 |
42 | 6 | 0.68579659E-05 | 0.47011368E-08 | 0.31862738E-02 | -0.26729135E-04 |
43 | 5 | -0.49396463E-03 | 0.27861516E-05 | -0.22352018 | 0.19543461E-02 |
44 | 4 | 0.11367371E-01 | 0.12683264E-03 | 4.8261412 | -0.45232255E-01 |
45 | 3 | -0.99836882E-01 | 0.10087729E-02 | -38.002184 | 0.39844117 |
46 | 2 | 0.35452054 | 0.16782362E-02 | 116.44652 | -1.4174386 |
47 | 1 | -0.51170991 | 0.51154075E-03 | -143.88527 | 2.0486777 |
48 | 0 | 0.24948649 | 0.12321491E-04 | 60.838472 | |
49 | 7 | -0.17135090E-08 | -0.36864923E-15 | 0.71259317E-14 | -0.97083918E-16 |
50 | 6 | 0.68579659E-05 | 0.47011368E-08 | 0.31862738E-02 | -0.26729135E-04 |
51 | 5 | -0.49396463E-03 | 0.27861516E-05 | -0.22352018 | 0.19543461E-02 |
52 | 4 | 0.11367371E-01 | 0.12683264E-03 | 4.8261412 | -0.45232255E-01 |
53 | 3 | -0.99836882E-01 | 0.10087729E-02 | -38.002184 | 0.39844117 |
54 | 2 | 0.35452054 | 0.16782362E-02 | 116.44652 | -1.4174386 |
55 | 1 | -0.51170991 | 0.51154075E-03 | -143.88527 | 2.0486777 |
56 | 0 | 0.24948649 | 0.12321491E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.418_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.375 | 2.375 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.418_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.375 | 2.375 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.418_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.375 | 2.375 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.418_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.375 | 2.375 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.05070E-002 | 0.31435 | 0.47518 | 0.47518 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12234 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.05070E-002 | 0.31435 | 0.47518 | 0.47518 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12234 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.05070E-002 | 0.31435 | 0.47518 | 0.47518 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12234 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.05070E-002 | 0.31435 | 0.47518 | 0.47518 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12234 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.053 | 0.3093 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.584 | 5.025E-003 | 6.281E-003 | 5.934 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.5589E-003 |
2 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.9255E-002 |
3 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.2933E-003 |
4 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.6702E-002 |
5 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.1426E-003 |
6 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.0686E-002 |
7 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.7272E-003 |
8 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.7316E-002 |
9 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.3191E-002 |
10 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.3749E-002 |
11 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 9.6432E-002 |
12 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 9.7144E-002 |
13 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 5.1534E-002 |
14 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 5.1682E-002 |
15 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.8733E-002 |
16 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.8734E-002 |
17 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.9590E-002 |
18 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.6003E-003 |
19 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.7113E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.3460E-003 |
21 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.1121E-002 |
22 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.1800E-003 |
23 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.7318E-002 |
24 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.7272E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 19193.80819 | 23032.56982 | 1.74053 | 2.08864 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 5869.45018 | 7043.34022 | 0.30757 | 0.41606 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -17.90000 | 9.55238E-004 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16346.51092 | 19615.81310 | 1.23565 | 1.48279 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32.56800 | 5.47322E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.14133 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -17.90000 | 9.55238E-004 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 26831.43 | 2.08864 | 2.08864 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 23660.53 | 0.41606 | 0.41606 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 26604.46 | 1.48279 | 1.48279 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 64906.04 | 1.14133 | 1.14133 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.08864 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.48279 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.08864 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.08864 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.08864 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.08864 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.08864 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.08864 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.48279 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.48279 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.48279 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.48279 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.48279 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.48279 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.08864 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.48279 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.08864 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.08864 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2234.94476 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.08864 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.08864 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.08864 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.37850 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.08864 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.04432 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.39243 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34574.43000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17287.21500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34574.43000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 54693.91324 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 54693.91324 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.48279 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.48279 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1586.65090 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.48279 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.48279 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.48279 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97864 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.48279 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.74139 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.98853 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29595.70000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14797.85000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77692 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77692 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29595.70000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 78320.83705 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 78320.83705 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 33046.4 | 11.01 | 10.96 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 28523.6 | 11.42 | 11.37 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_EAST_0.4 | N/A | 2.375 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_SOUTH_0.4 | N/A | 2.375 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_WEST_0.4 | N/A | 2.375 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.245 | 0.231 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.245 | 0.231 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 7.8298193257E-002 | 0.3458216418 | Pass | Pass | 0.3190751924 | 1.1937732326 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1589733401 | 0.7049122409 | Pass | Pass | 3.2774984412E-002 | 9.4594251311E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4426732404 | 0.5245307430 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 562.14 | 109.80 | 889.39 | 12.69 | 513.35 | 2087.37 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.236 | 0.245 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.236 | 0.245 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.418_SHGC_EAST_0.4 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.375 | 0.401 | 0.442 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.418_SHGC_SOUTH_0.4 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.375 | 0.401 | 0.442 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.418_SHGC_WEST_0.4 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.375 | 0.401 | 0.442 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.375 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.375 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 7.5044 | 116.17 | 871.80 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 46.88 | 0.0000 | Y | 7.67 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.6310 | 116.17 | 1351.20 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 83.95 | 0.0000 | Y | 21.29 |
Interior Lighting Total | 9.5677 | 232.34 | 2222.99 | 28.97 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.38 | 871.80 | 331.28 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.38 | 871.80 | 331.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 216.58 | AstronomicalClock | - | 49.26 | 49.26 | 2.00 | |
EXTERIOR_LIGHTS_B | 1823.66 | AstronomicalClock | - | 83.67 | 73.35 | 25.11 | |
Exterior Lighting Total | 2040.24 | 27.11 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34574.43 | 27682.36 | 6892.07 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29595.70 | 22993.49 | 6602.21 | 0.78 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 33046.4 | 11.01 | 10.96 | ||||
PSZ-AC_2:2 COOLING COIL | 28523.6 | 11.42 | 11.37 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 54693.91 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 78320.84 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 2.09 | 2234.94 | 1070.05 | 1.00 | 1.31 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.48 | 1586.65 | 1070.05 | 1.00 | 1.36 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 19193.81 | 23032.57 | 198.26 | 1.741 | 2.089 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.89 | 0.00756 | 33.90 | 0.00548 | 0.416 | 0.00 |
KITCHEN | 16346.51 | 19615.81 | 168.85 | 1.236 | 1.483 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.00868 | 32.57 | 0.00547 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 5869.45 | 7043.34 | 60.63 | 0.308 | 0.416 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 21.11 | 21.11 | 0.00779 | -17.90 | 0.00096 | 0.416 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.141 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 18.89 | 21.64 | 0.00045 | -17.90 | 0.00096 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.09 | 2.09 | 0.42 | 0.42 | 2.0886 | 2.0886 | 2.0886 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.48 | 1.48 | 1.14 | 1.14 | 1.4828 | 1.4828 | 1.4828 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 34574.430 | 27682.363 | 2.088640 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 17287.22 | 16978.63 | 1.392427 | 25.88 | 13.77 | 0.00714654 | 11.72 | 8.31 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | 29.8799 | 23.89 | 0.00756226 | 33.3221 | 19193.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 54693.913 | 54693.913 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 54693.91 | 54693.91 | 2.088641 | 13.34 | 8.34 | 0.00636165 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 19.9199 | 19.51 | 0.00770650 | 44.3571 | 3371.57 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 29595.700 | 22993.491 | 1.482790 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 14797.85 | 14797.85 | 0.988527 | 31.07 | 14.74 | 0.00621278 | 11.72 | 7.50 | 0.00621278 | 32.57 | 0.00547322 | 14.64 | 115.4580 | 26.10 | 0.00868483 | 33.4828 | 16346.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 78320.837 | 78320.837 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 78320.84 | 78320.84 | 1.482786 | -13.78 | -14.95 | 0.00084199 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 76.9722 | 21.96 | 0.00046347 | 2.3205 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34574.430 | 27682.363 | 2.088640 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1251 | 1004.8586 | 0.9774 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.088641 | 2.04151641 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 17287.22 | 16978.63 | 1.0000 | 1.36101020 | 1.392427 | 25.88 | 13.77 | 0.00714654 | 44221.5 | 11.72 | 8.31 | 0.00700000 | 29440.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17287.22 | 33.90 | 0.00547527 | 15.07 | 0.41605618 | 29.8799 | 23.88 | 0.00756226 | 23.89 | 0.00756226 | 33.3221 | 19193.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 54693.913 | 54693.913 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.088641 | 2.04151641 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 54693.91 | 54693.91 | 1.0000 | 2.04151641 | 2.088641 | 13.34 | 8.34 | 0.00636165 | 29471.1 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54693.91 | -17.90 | 0.00095524 | -17.90 | 0.41605618 | 19.9199 | 21.11 | 0.00770650 | 19.51 | 0.00770650 | 44.3571 | 3371.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29595.700 | 22993.491 | 1.482790 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1016.3892 | 1004.8586 | 0.9774 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.482786 | 1.44933061 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 14797.85 | 14797.85 | 1.0000 | 0.96622314 | 0.988527 | 31.07 | 14.74 | 0.00621278 | 47114.6 | 11.72 | 7.50 | 0.00621278 | 27452.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14797.85 | 32.57 | 0.00547322 | 14.64 | 1.14133354 | 115.4580 | 26.05 | 0.00868483 | 26.10 | 0.00868483 | 33.4828 | 16346.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 78320.837 | 78320.837 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.482786 | 1.44933061 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 78320.84 | 78320.84 | 1.0000 | 1.44933061 | 1.482786 | -13.78 | -14.95 | 0.00084199 | -11760.5 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 78320.84 | -17.90 | 0.00095524 | -17.90 | 1.14133354 | 76.9722 | 0.00 | 0.00046347 | 21.96 | 0.00046347 | 2.3205 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.09 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.48 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 2786.83 | 4539.00 | 952.33 |
KITCHEN | 4408.17 | 6008.17 | 3432.50 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4491.00 | 6703.17 | 3516.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 72.50 | 42.00 | 0.50 | 0.83 |
KITCHEN | 0.00 | 156.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 72.50 | 191.83 | 0.50 | 0.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 5.177 | 2.742 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 10.351 | 0.030 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.105 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 9.651 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 13419628.62 | 0.00 | 13419628.62 | 6981777.24 | 20401405.86 | 13120747.55 | 1427.84 | 5793.19 | 1538.97 | 386.67 |
KITCHEN | 27031187.41 | 0.00 | 27031187.41 | 134202.88 | 27165390.29 | 35993094.65 | 8352.33 | 401.86 | 5.81 | 582.18 |
Total Facility | 40450816.03 | 0.00 | 40450816.03 | 7115980.12 | 47566796.15 | 49113842.20 | 8356.58 | 5793.59 | 1543.54 | 752.71 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.5052 | 0.0000 | 0.5052 | 0.2676 | 0.7727 | 0.4161 | 0.00 | 5683.86 | 1503.14 |
KITCHEN | 1.0091 | 0.0000 | 1.0091 | 0.0029 | 1.0120 | 1.1413 | 6792.65 | 393.22 | 1.13 |
Total Facility | 1.5142 | 0.0000 | 1.5142 | 0.2705 | 1.7847 | 1.5574 | 6792.65 | 5683.91 | 1503.76 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12821352.67 | 0.00 | 12821352.67 | 13120747.55 | 7239.18 | 12.98 | 1507.84 | 386.64 |
PSZ-AC_2:2 | 25824966.51 | 0.00 | 25824966.51 | 35993094.65 | 8754.51 | 0.52 | 4.97 | 582.18 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.4826 | 0.0000 | 0.4826 | 0.4161 | 5700.17 | 12.00 | 1474.82 |
PSZ-AC_2:2 | 0.9640 | 0.0000 | 0.9640 | 1.1413 | 7185.92 | 0.18 | 0.89 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1167.69 | 617.44 | 5788.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 149.51 | 1378.26 | 6241.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.9223 | 0.6255 | 0.3976 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.0288 | 1.0074 | 0.9577 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 374 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 469.28 | 4539.41 | 24-DEC-01:10 | 32877.88 | 16-AUG-11:10 |
Electricity:Building | 302.77 | 2354.92 | 01-JAN-01:10 | 18592.92 | 02-JAN-11:10 |
Electricity:Zone:DINING | 78.00 | 389.32 | 01-JAN-01:10 | 4239.56 | 02-JAN-16:40 |
Electricity:SpaceType:GENERAL | 294.83 | 2218.64 | 01-JAN-01:10 | 15298.87 | 02-JAN-11:10 |
InteriorLights:Electricity | 28.97 | 219.30 | 20-MAY-05:00 | 1769.15 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:DINING | 7.67 | 38.18 | 21-JUN-05:00 | 715.88 | 02-JAN-16:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 28.97 | 219.30 | 20-MAY-05:00 | 1769.15 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 28.97 | 219.30 | 20-MAY-05:00 | 1769.15 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 7.67 | 38.18 | 21-JUN-05:00 | 715.88 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 28.97 | 219.30 | 20-MAY-05:00 | 1769.15 | 02-JAN-16:40 |
Electricity:Zone:KITCHEN | 224.77 | 1965.60 | 01-JAN-01:10 | 14490.86 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 21.29 | 175.55 | 01-JAN-01:10 | 1053.27 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 21.29 | 175.55 | 01-JAN-01:10 | 1053.27 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 265.86 | 1923.78 | 01-JAN-01:10 | 14073.79 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 265.86 | 1923.78 | 01-JAN-01:10 | 14073.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 195.53 | 1653.77 | 01-JAN-01:10 | 10143.54 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 51.17 | 849.94 | 12-FEB-23:30 | 4345.51 | 28-JUL-10:20 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 43.23 | 764.14 | 29-NOV-23:20 | 2551.15 | 11-AUG-03:30 |
LowTempRefrigeration:Refrigeration:Electricity | 14.41 | 0.00 | 01-JAN-11:10 | 1474.92 | 11-AUG-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 28.82 | 683.15 | 12-FEB-01:10 | 1076.23 | 17-MAR-04:10 |
ElectricityPurchased:Facility | 469.28 | 4539.41 | 24-DEC-01:10 | 32877.88 | 16-AUG-11:10 |
ElectricityPurchased:Plant | 469.28 | 4539.41 | 24-DEC-01:10 | 32877.88 | 16-AUG-11:10 |
Cogeneration:ElectricityPurchased | 469.28 | 4539.41 | 24-DEC-01:10 | 32877.88 | 16-AUG-11:10 |
General:Cogeneration:ElectricityPurchased | 469.28 | 4539.41 | 24-DEC-01:10 | 32877.88 | 16-AUG-11:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 469.28 | 4539.41 | 24-DEC-01:10 | 32877.88 | 16-AUG-11:10 |
ElectricityNet:Plant | 469.28 | 4539.41 | 24-DEC-01:10 | 32877.88 | 16-AUG-11:10 |
Cogeneration:ElectricityNet | 469.28 | 4539.41 | 24-DEC-01:10 | 32877.88 | 16-AUG-11:10 |
General:Cogeneration:ElectricityNet | 469.28 | 4539.41 | 24-DEC-01:10 | 32877.88 | 16-AUG-11:10 |
Electricity:HVAC | 96.17 | 0.00 | 01-JAN-01:10 | 17618.47 | 26-JUN-17:10 |
Fans:Electricity | 59.49 | 0.00 | 01-JAN-01:10 | 3425.70 | 26-JUN-17:10 |
General:Fans:Electricity | 59.49 | 0.00 | 01-JAN-01:10 | 3425.70 | 26-JUN-17:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 36.68 | 0.00 | 01-JAN-00:10 | 14192.77 | 26-JUN-17:10 |
General:Cooling:Electricity | 36.68 | 0.00 | 01-JAN-00:10 | 14192.77 | 26-JUN-17:10 |
ExteriorLights:Electricity | 27.11 | 0.00 | 01-JAN-07:30 | 2040.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 27.11 | 0.00 | 01-JAN-07:30 | 2040.24 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JAN-12:30 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JAN-12:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 957.90 | 2558.65 | 13-MAR-02:10 | 120510.88 | 20-DEC-13:10 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 263.84 | 0.00 | 01-JAN-01:10 | 87819.73 | 23-DEC-07:10 |
Heating:NaturalGas | 263.84 | 0.00 | 01-JAN-01:10 | 87819.73 | 23-DEC-07:10 |
General:Heating:NaturalGas | 263.84 | 0.00 | 01-JAN-01:10 | 87819.73 | 23-DEC-07:10 |
NaturalGas:Plant | 216.90 | 720.00 | 01-JAN-09:30 | 27774.50 | 11-FEB-13:40 |
WaterSystems:NaturalGas | 216.90 | 720.00 | 01-JAN-09:30 | 27774.50 | 11-FEB-13:40 |
Water Heater:WaterSystems:NaturalGas | 216.90 | 720.00 | 01-JAN-09:30 | 27774.50 | 11-FEB-13:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1013.18 | 2415.98 | 24-DEC-01:10 | 108605.15 | 21-DEC-20:20 |
EnergyTransfer:Building | 445.12 | 1207.99 | 24-DEC-01:10 | 33751.73 | 16-AUG-11:10 |
EnergyTransfer:Zone:KITCHEN | 339.22 | 1207.99 | 24-DEC-01:10 | 23892.49 | 09-MAY-04:10 |
Refrigeration:EnergyTransfer | 136.48 | 2415.98 | 24-DEC-01:10 | 7834.84 | 17-MAR-04:10 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.24 | 1207.99 | 24-DEC-01:10 | 3917.42 | 17-MAR-04:10 |
General:Refrigeration:EnergyTransfer | 68.24 | 1207.99 | 24-DEC-01:10 | 3917.42 | 17-MAR-04:10 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.24 | 1207.99 | 24-DEC-01:10 | 3917.42 | 17-MAR-04:10 |
EnergyTransfer:Plant | 216.38 | 1207.99 | 24-DEC-01:10 | 22560.42 | 18-FEB-13:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 13.00 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 55.24 | 1059.45 | 12-FEB-01:10 | 2238.70 | 17-MAR-04:10 |
EnergyTransfer:Zone:DINING | 105.90 | 0.00 | 01-JAN-01:10 | 25778.70 | 22-DEC-03:20 |
Heating:EnergyTransfer | 23.92 | 0.00 | 01-JAN-00:10 | 18958.72 | 21-DEC-18:10 |
Heating:EnergyTransfer:Zone:DINING | 23.91 | 0.00 | 01-JAN-00:10 | 18958.72 | 21-DEC-18:10 |
General:Heating:EnergyTransfer | 23.92 | 0.00 | 01-JAN-00:10 | 18958.72 | 21-DEC-18:10 |
General:Heating:EnergyTransfer:Zone:DINING | 23.91 | 0.00 | 01-JAN-00:10 | 18958.72 | 21-DEC-18:10 |
Cooling:EnergyTransfer | 352.95 | 0.00 | 01-JAN-01:10 | 30048.85 | 16-AUG-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 81.99 | 0.00 | 01-JAN-01:10 | 16062.54 | 26-JUN-17:20 |
General:Cooling:EnergyTransfer | 352.95 | 0.00 | 01-JAN-01:10 | 30048.85 | 16-AUG-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 81.99 | 0.00 | 01-JAN-01:10 | 16062.54 | 26-JUN-17:20 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 813.85 | 16-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 813.85 | 16-JAN-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 270.97 | 0.00 | 01-JAN-01:10 | 19989.31 | 09-MAY-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 270.97 | 0.00 | 01-JAN-01:10 | 19989.31 | 09-MAY-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 148.14 | 0.00 | 01-JAN-00:10 | 20164.03 | 14-FEB-13:40 |
PlantLoopHeatingDemand:Plant | 148.14 | 0.00 | 01-JAN-00:10 | 20164.03 | 14-FEB-13:40 |
WaterSystems:PlantLoopHeatingDemand | 148.14 | 0.00 | 01-JAN-00:10 | 20164.03 | 14-FEB-13:40 |
General:WaterSystems:PlantLoopHeatingDemand | 148.14 | 0.00 | 01-JAN-00:10 | 20164.03 | 14-FEB-13:40 |
EnergyTransfer:HVAC | 351.69 | 0.00 | 01-JAN-01:10 | 70255.78 | 23-DEC-07:10 |
HeatingCoils:EnergyTransfer | 211.07 | 0.00 | 01-JAN-01:10 | 70255.78 | 23-DEC-07:10 |
CoolingCoils:EnergyTransfer | 140.61 | 0.00 | 01-JAN-00:10 | 49246.66 | 26-JUN-17:10 |
WaterSystems:EnergyTransfer | 148.14 | 0.00 | 01-JAN-00:10 | 20164.03 | 14-FEB-13:40 |
WaterUse:WaterSystems:EnergyTransfer | 148.14 | 0.00 | 01-JAN-00:10 | 20164.03 | 14-FEB-13:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 23.915 | -81.987 | 0.000 | 0.000 | 71.013 | 7.673 | 52.748 | 34.375 | 0.000 | 4.974 | 0.000 | 0.000 | -15.728 | 0.000 | -81.625 | -15.359 |
KITCHEN | 0.000 | 0.000 | 0.008 | -270.957 | 0.000 | 0.000 | 4.970 | 21.293 | 201.243 | 0.000 | 0.000 | 0.030 | 45.443 | 0.000 | 0.000 | 0.000 | -2.030 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.384 | 10.283 | 0.000 | 0.000 | 0.000 | -13.666 | -0.001 |
Total Facility | 0.000 | 0.000 | 23.923 | -352.944 | 0.000 | 0.000 | 75.983 | 28.966 | 253.992 | 34.375 | 0.000 | 8.388 | 55.726 | 0.000 | -15.728 | 0.000 | -97.321 | -15.360 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 17-AUG-02:61 | 0.00 | 0.00 | 0.00 | -28306.40 | 0.00 | 0.00 | 0.00 | 119.31 | 202.51 | 0.00 | 0.00 | 0.00 | 28708.14 | 0.00 | -647.57 | 0.00 | -75.98 | 0.00 |
KITCHEN | 07-NOV-05:01 | 0.00 | 0.00 | 0.00 | -50682.97 | 0.00 | 0.00 | 8.72 | 234.07 | 4931.35 | 0.00 | 0.00 | 0.00 | 45555.00 | 0.00 | -0.00 | 0.00 | -46.16 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-SEP-02:61 | 0.00 | 0.00 | 0.00 | -71538.15 | 0.00 | 0.00 | 0.00 | 294.86 | 1879.56 | 0.00 | 0.00 | 174.55 | 70052.55 | 0.00 | -747.77 | 0.00 | -115.61 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 24-DEC-04:31 | 0.00 | 0.00 | 40658.24 | 0.00 | 0.00 | 0.00 | 0.00 | 119.31 | 506.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2026.37 | 0.00 | -622.78 | -38634.67 |
KITCHEN | 16-JAN-05:03 | 0.00 | 0.00 | 8129.80 | 0.00 | 0.00 | 0.00 | 0.00 | 175.55 | 4924.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -19.64 | -13210.53 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-DEC-04:31 | 0.00 | 0.00 | 40658.24 | 0.00 | 0.00 | 0.00 | 0.00 | 294.86 | 3157.65 | 0.00 | 0.00 | 350.22 | 0.00 | 0.00 | -2026.37 | 0.00 | -1290.31 | -41144.29 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0886 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.0886 | 0.1992 | 1.0000 | Not calculated | 0.4161 | 0.1992 | ||
PSZ-AC_2:2 | 1.4828 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.4828 | 0.1020 | 1.0000 | Not calculated | 0.1513 | 0.1020 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0886 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.0886 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.1992 | ||
PSZ-AC_2:2 | 1.4828 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.4828 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1020 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0886 | 2.0886 | 2.0886 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4828 | 1.4828 | 1.4828 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0886 | 2.0886 | 2.0886 | 2.0886 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.4828 | 1.4828 | 1.4828 | 1.4828 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0886 | 2.0886 | 2.0886 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4828 | 1.4828 | 1.4828 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0886 | 2.0886 | 2.0886 | 2.0886 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.4828 | 1.4828 | 1.4828 | 1.4828 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.50 |
Number of hours cooling loads not met | 0.83 |
Number of hours not met | 1.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 263.84 | 87819.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 36.68 | 14192.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 28.97 | 1769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 27.11 | 2040.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 59.49 | 3425.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 216.90 | 27774.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 14.41 | 1474.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 28.82 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 317.03 | 469.28 |
Natural Gas | 477.16 | 957.90 |
Additional | 0.00 | 0.00 |
Total | 794.19 | 1427.17 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 124.67 |
Space Heating | 0.00 |
Space Cooling | 157.86 |
Fans (All) | 256.04 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1144.28 |
Miscellaneous (All) | 2019.76 |
Subtotal | 2019.76 |
Natural Gas [MJ/m2] | |
Space Heating | 1135.58 |
Service Water Heating | 933.51 |
Miscellaneous (All) | 4122.77 |
Subtotal | 4122.77 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.03 |
Space Heating | 18.49 |
Space Cooling | 2.57 |
Fans (All) | 4.17 |
Service Water Heating | 15.20 |
Receptacle Equipment | 52.06 |
Miscellaneous | 5.49 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8353.17 | 406.50 | 0.33 | 0.00 | 0.00 |
ATTIC | 6764.33 | 600.00 | 568.33 | 811.83 | 15.50 |
Min | 6764.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 600.00 | 568.33 | 811.83 | 15.50 |
Average | 7959.17 | 335.50 | 189.56 | 270.61 | 5.17 |
Sum | 23877.50 | 1006.50 | 568.67 | 811.83 | 15.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16258.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 90327.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 270983.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8709.67 | 50.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8139.50 | 620.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 7004.83 | 833.67 | 316.33 | 281.00 | 324.17 |
Min | 7004.83 | 50.33 | 0.00 | 0.00 | 0.00 |
Max | 8709.67 | 833.67 | 316.33 | 281.00 | 324.17 |
Average | 7951.33 | 501.50 | 105.44 | 93.67 | 108.06 |
Sum | 23854.00 | 1504.50 | 316.33 | 281.00 | 324.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 253812.67 | 912.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15350.83 | 907.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 253812.67 | 912.33 | 0.00 | 0.00 | 0.00 |
Average | 89721.17 | 606.50 | 0.00 | 0.00 | 0.00 |
Sum | 269163.50 | 1819.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:36
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244437E+10 | 18000.26 | 14-JAN-03:53 | -17.0 | -17.0 | 0.452206E+10 | 4413.16 | 20-JAN-12:00 | 21.00 | 6.97 |
February | 0.199077E+10 | 22767.46 | 12-FEB-04:47 | -19.8 | -19.8 | 0.407027E+10 | 4234.23 | 27-FEB-12:00 | 14.00 | 4.76 |
March | 0.346779E+10 | 10195.95 | 19-MAR-04:02 | -8.7 | -8.7 | 0.469702E+10 | 4488.62 | 11-MAR-19:10 | -8.7 | -8.7 |
April | 0.322128E+10 | 9207.22 | 17-APR-04:02 | -8.0 | -8.7 | 0.454130E+10 | 4525.14 | 08-APR-18:10 | -8.0 | -8.7 |
May | 0.696392E+10 | 9987.41 | 17-MAY-12:55 | 29.00 | 11.92 | 0.506508E+10 | 4681.02 | 20-MAY-18:10 | 18.83 | 11.34 |
June | 0.131069E+11 | 25634.49 | 28-JUN-02:41 | 16.88 | 8.07 | 0.526863E+10 | 4681.48 | 17-JUN-18:00 | 16.88 | 8.07 |
July | 0.135896E+11 | 25074.96 | 01-JUL-02:61 | 19.48 | 7.48 | 0.539437E+10 | 4681.13 | 22-JUL-18:00 | 27.00 | 15.92 |
August | 0.138368E+11 | 28316.35 | 17-AUG-02:61 | 14.67 | 6.30 | 0.544644E+10 | 4681.16 | 19-AUG-18:00 | 24.00 | 12.71 |
September | 0.117275E+11 | 28018.14 | 17-SEP-02:61 | 12.70 | 6.80 | 0.515007E+10 | 4681.19 | 02-SEP-18:00 | 12.70 | 6.80 |
October | 0.567035E+10 | 25454.50 | 11-OCT-02:61 | 11.83 | 4.39 | 0.478824E+10 | 4680.67 | 07-OCT-18:10 | 11.83 | 4.39 |
November | 0.341923E+10 | 12890.77 | 30-NOV-03:19 | -14.0 | -14.3 | 0.442826E+10 | 4413.14 | 07-NOV-12:50 | -14.0 | -14.3 |
December | 0.254917E+10 | 28032.72 | 22-DEC-03:11 | -22.7 | -22.7 | 0.452454E+10 | 4413.12 | 01-DEC-12:09 | -22.7 | -22.7 |
Annual Sum or Average | 0.819877E+11 | 0.578963E+11 | ||||||||
Minimum of Months | 0.199077E+10 | 9207.22 | -22.7 | -22.7 | 0.407027E+10 | 4234.23 | -22.7 | -22.7 | ||
Maximum of Months | 0.138368E+11 | 28316.35 | 29.00 | 11.92 | 0.544644E+10 | 4681.48 | 27.00 | 15.92 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222910E+11 | 37136.87 | 05-JAN-05:01 | -17.0 | -17.0 | 0.769972E+10 | 5135.93 | 20-JAN-11:00 | 20.00 | 7.55 |
February | 0.197427E+11 | 39095.68 | 12-FEB-05:01 | -19.8 | -19.8 | 0.694965E+10 | 5116.83 | 18-FEB-11:00 | 18.00 | 6.83 |
March | 0.219187E+11 | 49262.07 | 14-MAR-04:01 | 7.33 | 1.14 | 0.772967E+10 | 5135.93 | 14-MAR-10:09 | 21.00 | 7.12 |
April | 0.216337E+11 | 43673.13 | 21-APR-02:61 | 8.83 | 6.25 | 0.748629E+10 | 5135.93 | 27-APR-10:50 | 17.67 | 8.15 |
May | 0.222396E+11 | 49605.65 | 09-MAY-04:01 | 3.00 | 0.34 | 0.781278E+10 | 5135.97 | 30-MAY-10:00 | 18.00 | 11.53 |
June | 0.228680E+11 | 50138.05 | 09-JUN-03:21 | 7.15 | 3.80 | 0.760604E+10 | 5135.97 | 02-JUN-10:39 | 7.15 | 3.80 |
July | 0.236676E+11 | 48580.15 | 02-JUL-02:11 | 11.67 | 3.81 | 0.785577E+10 | 5135.97 | 28-JUL-10:39 | 19.67 | 16.52 |
August | 0.241077E+11 | 45365.53 | 17-AUG-02:11 | 14.33 | 6.10 | 0.785951E+10 | 5135.97 | 28-AUG-10:39 | 20.67 | 15.18 |
September | 0.234217E+11 | 48739.23 | 15-SEP-03:21 | 9.95 | 4.65 | 0.759040E+10 | 5135.95 | 01-SEP-10:09 | 9.95 | 4.65 |
October | 0.239445E+11 | 49448.66 | 20-OCT-04:01 | 4.00 | 0.33 | 0.775369E+10 | 5135.93 | 05-OCT-10:00 | 4.00 | 0.33 |
November | 0.227195E+11 | 50643.42 | 07-NOV-05:01 | 5.00 | -0.7 | 0.746231E+10 | 5135.93 | 09-NOV-11:00 | 20.00 | 9.32 |
December | 0.224113E+11 | 41905.37 | 22-DEC-05:01 | -21.0 | -21.0 | 0.770044E+10 | 5135.93 | 04-DEC-11:00 | -21.0 | -21.0 |
Annual Sum or Average | 0.270966E+12 | 0.915063E+11 | ||||||||
Minimum of Months | 0.197427E+11 | 37136.87 | -21.0 | -21.0 | 0.694965E+10 | 5116.83 | -21.0 | -21.0 | ||
Maximum of Months | 0.241077E+11 | 50643.42 | 14.33 | 6.25 | 0.785951E+10 | 5135.97 | 21.00 | 16.52 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.50 | -1.8 | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 | -1.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 | -5.3 | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 | -1.1 | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 | 2.10 | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.10 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 | 4.75 | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 | 11.26 | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.26 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 | 10.91 | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.91 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 | 15.43 | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.43 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 | 10.64 | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.64 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 | 8.03 | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.03 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 | -5.7 | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 2.77 | -0.5 | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 | -0.5 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -5.7 | -5.7 | 0.00 | 0.00 | -5.7 | -5.7 | ||
Maximum of Months | 0.00 | 0.00 | 22.27 | 15.43 | 0.00 | 0.00 | 22.27 | 15.43 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.411742E+10 | 33848.76 | 05-JAN-03:21 | -16.0 |
February | 0.445283E+10 | 40315.14 | 12-FEB-04:31 | -19.7 |
March | 0.289130E+10 | 26786.33 | 19-MAR-04:01 | -8.7 |
April | 0.197575E+10 | 21886.59 | 17-APR-04:01 | -8.0 |
May | 82774451.09 | 5430.40 | 01-MAY-02:62 | 5.73 |
June | 2184899.47 | 5323.85 | 14-JUN-02:43 | 21.92 |
July | 4904031.79 | 7886.99 | 09-JUL-02:04 | 18.00 |
August | 1902215.95 | 7700.26 | 19-AUG-02:03 | 15.83 |
September | 53675211.68 | 4482.22 | 13-SEP-03:50 | 20.50 |
October | 0.168746E+10 | 22370.01 | 30-OCT-04:01 | -10.0 |
November | 0.262320E+10 | 26374.48 | 29-NOV-05:01 | -10.0 |
December | 0.602128E+10 | 40654.29 | 24-DEC-04:31 | -19.3 |
Annual Sum or Average | 0.239147E+11 | |||
Minimum of Months | 1902215.95 | 4482.22 | -19.7 | |
Maximum of Months | 0.602128E+10 | 40654.29 | 21.92 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1714655.59 | 8138.55 | 16-JAN-05:03 | -11.0 |
February | 2063968.67 | 7774.72 | 02-FEB-05:03 | -9.0 |
March | 1126723.28 | 5387.70 | 02-MAR-05:03 | -8.0 |
April | 814229.23 | 7310.91 | 17-APR-04:03 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 259837.53 | 4330.63 | 30-OCT-04:03 | -10.0 |
November | 1049197.45 | 7781.27 | 29-NOV-05:03 | -10.0 |
December | 1257572.54 | 8016.80 | 19-DEC-05:03 | -16.4 |
Annual Sum or Average | 8286184.30 | |||
Minimum of Months | 0.00 | 0.00 | -16.4 | |
Maximum of Months | 2063968.67 | 8138.55 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.770794E+09 | 715.88 | 02-JAN-16:40 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.656849E+09 | 715.88 | 01-FEB-17:19 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.659689E+09 | 715.88 | 01-MAR-17:30 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.582361E+09 | 715.88 | 01-APR-17:49 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.551552E+09 | 715.88 | 01-MAY-18:49 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.513175E+09 | 715.88 | 01-JUN-19:19 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.532879E+09 | 715.88 | 01-JUL-19:30 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.590218E+09 | 715.88 | 01-AUG-18:49 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.600680E+09 | 715.88 | 01-SEP-18:30 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.690497E+09 | 715.88 | 02-OCT-17:10 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.737594E+09 | 715.88 | 01-NOV-16:40 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.786491E+09 | 715.88 | 01-DEC-16:19 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.767278E+10 | 0.703313E+11 | ||||
Minimum of Months | 0.513175E+09 | 715.88 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.786491E+09 | 715.88 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.179920E+10 | 1053.27 | 02-JAN-10:09 | 0.166069E+11 | 10143.54 | 01-JAN-11:09 |
February | 0.162962E+10 | 1053.27 | 01-FEB-10:09 | 0.149998E+11 | 10143.54 | 01-FEB-11:09 |
March | 0.182785E+10 | 1053.27 | 01-MAR-10:09 | 0.166070E+11 | 10143.54 | 01-MAR-11:09 |
April | 0.174822E+10 | 1053.27 | 01-APR-16:10 | 0.160712E+11 | 10143.54 | 01-APR-10:09 |
May | 0.181352E+10 | 1053.27 | 01-MAY-09:09 | 0.166070E+11 | 10143.54 | 01-MAY-10:09 |
June | 0.176676E+10 | 1053.27 | 01-JUN-09:09 | 0.160713E+11 | 10143.54 | 01-JUN-10:09 |
July | 0.179520E+10 | 1053.27 | 01-JUL-16:10 | 0.166069E+11 | 10143.54 | 01-JUL-10:09 |
August | 0.182785E+10 | 1053.27 | 01-AUG-09:09 | 0.166070E+11 | 10143.54 | 01-AUG-10:09 |
September | 0.174864E+10 | 1053.27 | 01-SEP-09:09 | 0.160712E+11 | 10143.54 | 01-SEP-10:09 |
October | 0.179899E+10 | 1053.27 | 02-OCT-09:09 | 0.166069E+11 | 10143.54 | 01-OCT-10:09 |
November | 0.174169E+10 | 1053.27 | 01-NOV-09:09 | 0.160712E+11 | 10143.54 | 01-NOV-10:09 |
December | 0.179541E+10 | 1053.27 | 01-DEC-10:09 | 0.166069E+11 | 10143.54 | 01-DEC-11:09 |
Annual Sum or Average | 0.212929E+11 | 0.195533E+12 | ||||
Minimum of Months | 0.162962E+10 | 1053.27 | 0.149998E+11 | 10143.54 | ||
Maximum of Months | 0.182785E+10 | 1053.27 | 0.166070E+11 | 10143.54 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.770794E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116218E+11 |
February | 0.852256E+10 | 0.656849E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111454E+11 |
March | 0.954557E+10 | 0.659689E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27517.87 | 0.939199E+10 |
April | 0.915225E+10 | 0.582361E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817253E+10 |
May | 0.947560E+10 | 0.551552E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83149083.93 | 0.422690E+10 |
June | 0.922788E+10 | 0.513175E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148025E+10 | 0.105681E+10 |
July | 0.939996E+10 | 0.532879E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153771E+10 | 0.976850E+09 |
August | 0.954557E+10 | 0.590218E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127632E+10 | 0.127337E+10 |
September | 0.915225E+10 | 0.600680E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585598E+09 | 0.235127E+10 |
October | 0.940563E+10 | 0.690497E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11438864.56 | 0.808220E+10 |
November | 0.909363E+10 | 0.737594E+09 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100445E+11 |
December | 0.939996E+10 | 0.786491E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132812E+11 |
Annual Sum or Average | 0.111326E+12 | 0.767278E+10 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497449E+10 | 0.816248E+11 |
Minimum of Months | 0.852256E+10 | 0.513175E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976850E+09 |
Maximum of Months | 0.954557E+10 | 0.786491E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153771E+10 | 0.132812E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.179920E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144743E+09 |
February | 0.610713E+09 | 0.162962E+10 | 0.112456E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219939E+09 |
March | 0.684021E+09 | 0.182785E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249818E+09 |
April | 0.655836E+09 | 0.174822E+10 | 0.120488E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248999E+09 |
May | 0.679007E+09 | 0.181352E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 246235.27 | 0.153895E+09 |
June | 0.661256E+09 | 0.176676E+10 | 0.120489E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 9923650.82 | 78749432.42 |
July | 0.673587E+09 | 0.179520E+10 | 0.124504E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 10493339.35 | 78381286.18 |
August | 0.684021E+09 | 0.182785E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 6752327.87 | 77747630.87 |
September | 0.655836E+09 | 0.174864E+10 | 0.120488E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 2569788.10 | 0.110165E+09 |
October | 0.673993E+09 | 0.179899E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 9310.06 | 0.182143E+09 |
November | 0.651635E+09 | 0.174169E+10 | 0.120489E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172724E+09 |
December | 0.673587E+09 | 0.179541E+10 | 0.124504E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313166E+09 |
Annual Sum or Average | 0.797748E+10 | 0.212929E+11 | 0.146594E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 29994651.47 | 0.203047E+10 |
Minimum of Months | 0.610713E+09 | 0.162962E+10 | 0.112456E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77747630.87 |
Maximum of Months | 0.684021E+09 | 0.182785E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 10493339.35 | 0.313166E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384729E+09 | 0.740140E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309806E+09 | 0.895588E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278984E+09 | 0.115352E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192349E+09 | 0.118936E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192895E+09 | 0.150811E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227094E+09 | 0.165438E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206305E+09 | 0.149072E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232584E+09 | 0.152877E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313108E+09 | 0.116170E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329313E+09 | 0.973121E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327048E+09 | 0.795848E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389414E+09 | 0.574860E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338363E+10 | 0.136661E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192349E+09 | 0.574860E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389414E+09 | 0.165438E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 715.88 | 02-JAN-16:40 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 21584.43 | 05-JAN-19:00 |
February | 9454.80 | 04-FEB-19:10 | 715.88 | 01-FEB-17:19 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 20957.26 | 11-FEB-20:00 |
March | 9454.80 | 04-MAR-19:10 | 715.88 | 01-MAR-17:30 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.86 | 14-MAR-13:00 | 17993.57 | 04-MAR-20:00 |
April | 9454.80 | 01-APR-18:10 | 715.88 | 01-APR-17:49 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 12096.65 | 15-APR-18:53 |
May | 9454.80 | 06-MAY-18:10 | 715.88 | 01-MAY-18:49 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2119.26 | 17-MAY-13:00 | 8121.52 | 11-MAY-19:53 |
June | 9454.80 | 03-JUN-18:10 | 715.88 | 01-JUN-19:19 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6263.76 | 26-JUN-17:03 | 4109.15 | 02-JUN-20:00 |
July | 9454.80 | 01-JUL-18:10 | 715.88 | 01-JUL-19:30 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5539.34 | 17-JUL-11:55 | 3836.70 | 05-JUL-19:56 |
August | 9454.80 | 05-AUG-18:10 | 715.88 | 01-AUG-18:49 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5366.60 | 16-AUG-17:03 | 4346.64 | 22-AUG-19:55 |
September | 9454.80 | 02-SEP-18:10 | 715.88 | 01-SEP-18:30 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2982.03 | 08-SEP-12:55 | 10849.92 | 21-SEP-19:00 |
October | 9454.80 | 07-OCT-18:10 | 715.88 | 02-OCT-17:10 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 876.76 | 11-OCT-13:00 | 15348.91 | 30-OCT-18:00 |
November | 9454.80 | 04-NOV-18:10 | 715.88 | 01-NOV-16:40 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 19319.69 | 29-NOV-21:00 |
December | 9454.80 | 02-DEC-19:10 | 715.88 | 01-DEC-16:19 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 23801.50 | 21-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 715.88 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3836.70 | |||||
Maximum of Months | 9454.80 | 715.88 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6263.76 | 23801.50 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 1053.27 | 02-JAN-10:09 | 7408.73 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 567.50 | 13-JAN-04:53 |
February | 677.52 | 04-FEB-19:10 | 1053.27 | 01-FEB-10:09 | 7408.73 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 539.95 | 24-FEB-04:40 |
March | 677.52 | 04-MAR-19:10 | 1053.27 | 01-MAR-10:09 | 7408.73 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1203.11 | 19-MAR-02:00 |
April | 677.52 | 01-APR-18:10 | 1053.27 | 01-APR-16:10 | 7408.73 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 796.96 | 15-APR-04:00 |
May | 677.52 | 06-MAY-18:10 | 1053.27 | 01-MAY-09:09 | 7408.73 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 10.16 | 17-MAY-13:00 | 538.02 | 03-MAY-03:10 |
June | 677.52 | 03-JUN-18:10 | 1053.27 | 01-JUN-09:09 | 7408.73 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 54.84 | 14-JUN-12:00 | 340.48 | 09-JUN-02:00 |
July | 677.52 | 01-JUL-18:10 | 1053.27 | 01-JUL-16:10 | 7408.73 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 48.47 | 16-JUL-12:00 | 350.91 | 03-JUL-03:10 |
August | 677.52 | 05-AUG-18:10 | 1053.27 | 01-AUG-09:09 | 7408.73 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 45.08 | 02-AUG-15:23 | 377.50 | 16-AUG-01:30 |
September | 677.52 | 02-SEP-18:10 | 1053.27 | 01-SEP-09:09 | 7408.73 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 30.33 | 09-SEP-14:52 | 354.68 | 02-SEP-02:10 |
October | 677.52 | 07-OCT-18:10 | 1053.27 | 02-OCT-09:09 | 7408.73 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 2.83 | 11-OCT-14:00 | 511.00 | 29-OCT-04:00 |
November | 677.52 | 04-NOV-18:10 | 1053.27 | 01-NOV-09:09 | 7408.73 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 837.84 | 01-NOV-04:00 |
December | 677.52 | 02-DEC-19:10 | 1053.27 | 01-DEC-10:09 | 7408.73 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 811.93 | 24-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 1053.27 | 7408.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 340.48 | ||||||
Maximum of Months | 677.52 | 1053.27 | 7408.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 54.84 | 1203.11 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 746.20 | 08-JAN-03:53 | 1660.03 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.82 | 07-FEB-07:55 | 1977.60 | 12-FEB-13:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.64 | 23-MAR-06:53 | 2238.75 | 26-MAR-11:55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 591.13 | 07-APR-03:51 | 2464.07 | 24-APR-12:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.16 | 13-MAY-05:23 | 2309.06 | 09-MAY-12:20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.93 | 06-JUN-22:00 | 2181.90 | 22-JUN-12:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.92 | 01-JUL-05:23 | 2250.32 | 03-JUL-12:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.99 | 15-AUG-03:00 | 2159.51 | 24-AUG-13:20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.61 | 28-SEP-06:42 | 1943.47 | 20-SEP-12:30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.65 | 14-OCT-07:12 | 1939.87 | 04-OCT-13:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545.80 | 30-NOV-07:53 | 1820.34 | 12-NOV-12:30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 699.05 | 23-DEC-08:41 | 1495.60 | 21-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.92 | 1495.60 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 746.20 | 2464.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18000.26 | 14-JAN-03:53 | 0.00 | 1193.14 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.50 |
February | 22767.46 | 12-FEB-04:47 | 0.00 | 1193.14 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.68 |
March | 10195.95 | 19-MAR-04:02 | 0.00 | 1193.14 | 16200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.34 |
April | 9207.22 | 17-APR-04:02 | 5252.67 | 1590.86 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.08 |
May | 9987.41 | 17-MAY-12:55 | 14707.47 | 343.62 | 6776.30 | 0.00 | 0.00 | 0.00 | 0.00 | 2119.25 | 0.00 |
June | 25634.49 | 28-JUN-02:41 | 0.00 | 1193.14 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.75 |
July | 25074.96 | 01-JUL-02:61 | 0.00 | 1193.14 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.44 |
August | 28316.35 | 17-AUG-02:61 | 0.00 | 954.52 | 2160.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.98 |
September | 28018.14 | 17-SEP-02:61 | 0.00 | 1193.14 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.84 |
October | 25454.50 | 11-OCT-02:61 | 0.00 | 1193.14 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.44 |
November | 12890.77 | 30-NOV-03:19 | 0.00 | 1193.14 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.98 |
December | 28032.72 | 22-DEC-03:11 | 0.00 | 1193.14 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9207.22 | 0.00 | 343.62 | 2160.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28316.35 | 14707.47 | 1590.86 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 2119.25 | 556.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37136.87 | 05-JAN-05:01 | 376.40 | 2340.68 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 33.42 |
February | 39095.68 | 12-FEB-05:01 | 0.00 | 1755.47 | 36578.48 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 122.66 |
March | 49262.07 | 14-MAR-04:01 | 376.40 | 2340.68 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 59.97 |
April | 43673.13 | 21-APR-02:61 | 0.00 | 1755.47 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 65.52 |
May | 49605.65 | 09-MAY-04:01 | 376.40 | 2340.68 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 76.21 |
June | 50138.05 | 09-JUN-03:21 | 0.00 | 1755.47 | 21234.78 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 172.47 |
July | 48580.15 | 02-JUL-02:11 | 0.00 | 1755.47 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 167.29 |
August | 45365.53 | 17-AUG-02:11 | 0.00 | 1755.47 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 120.27 |
September | 48739.23 | 15-SEP-03:21 | 0.00 | 1755.47 | 21234.78 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 146.53 |
October | 49448.66 | 20-OCT-04:01 | 376.40 | 2340.68 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 65.61 |
November | 50643.42 | 07-NOV-05:01 | 376.40 | 2340.68 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 46.16 |
December | 41905.37 | 22-DEC-05:01 | 376.40 | 2340.68 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 48.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37136.87 | 0.00 | 1755.47 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 33.42 | |
Maximum of Months | 50643.42 | 376.40 | 2340.68 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 172.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.23 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.85 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.16 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.56 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.63 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.69 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.01 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.43 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.42 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.05 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.96 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.41 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.373859E+11 | 22413.22 | 05-JAN-11:09 | 0.106386E+12 | 117273.79 | 05-JAN-13:09 |
February | 0.336144E+11 | 21957.43 | 01-FEB-11:09 | 0.103370E+12 | 99469.56 | 12-FEB-07:30 |
March | 0.369187E+11 | 23639.89 | 14-MAR-10:20 | 0.921639E+11 | 96811.97 | 04-MAR-13:09 |
April | 0.352678E+11 | 22500.58 | 19-APR-10:00 | 0.816222E+11 | 80393.07 | 03-APR-10:20 |
May | 0.378720E+11 | 27079.70 | 17-MAY-10:20 | 0.616459E+11 | 54109.50 | 02-MAY-10:39 |
June | 0.441353E+11 | 32803.46 | 26-JUN-16:10 | 0.560950E+11 | 49287.88 | 01-JUN-12:39 |
July | 0.461258E+11 | 32807.28 | 17-JUL-11:09 | 0.572475E+11 | 48689.08 | 01-JUL-12:30 |
August | 0.453704E+11 | 32877.88 | 16-AUG-11:09 | 0.570581E+11 | 48328.44 | 31-AUG-12:50 |
September | 0.412876E+11 | 29556.56 | 09-SEP-10:00 | 0.564556E+11 | 50507.94 | 22-SEP-10:20 |
October | 0.374782E+11 | 25842.04 | 11-OCT-10:20 | 0.781094E+11 | 91770.42 | 30-OCT-12:30 |
November | 0.361411E+11 | 23249.03 | 09-NOV-11:20 | 0.900096E+11 | 95394.94 | 29-NOV-20:00 |
December | 0.376810E+11 | 22471.99 | 20-DEC-11:09 | 0.117733E+12 | 120510.88 | 20-DEC-13:09 |
Annual Sum or Average | 0.469278E+12 | 0.957897E+12 | ||||
Minimum of Months | 0.336144E+11 | 21957.43 | 0.560950E+11 | 48328.44 | ||
Maximum of Months | 0.461258E+11 | 32877.88 | 0.117733E+12 | 120510.88 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.256999E+10 | 0.286559E+10 | 0.225803E+11 | 0.00 | 0.526391E+10 | 0.79 | 0.00 | 44875465.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228647E+10 | 0.238657E+10 | 0.203951E+11 | 0.00 | 0.489005E+10 | 0.72 | 0.00 | 15937858.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.248754E+10 | 0.235757E+10 | 0.225804E+11 | 0.00 | 0.508895E+10 | 0.80 | 0.00 | 0.254454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.233058E+10 | 0.199306E+10 | 0.218518E+11 | 0.00 | 0.482788E+10 | 0.77 | 0.00 | 0.211863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.236508E+10 | 0.183023E+10 | 0.225803E+11 | 0.00 | 0.469481E+10 | 0.80 | 0.00 | 0.190697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.227993E+10 | 0.165971E+10 | 0.218520E+11 | 0.00 | 0.480289E+10 | 0.77 | 0.00 | 0.898001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.232807E+10 | 0.175449E+10 | 0.225802E+11 | 0.00 | 0.497846E+10 | 0.79 | 0.00 | 0.976810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.241807E+10 | 0.194871E+10 | 0.225804E+11 | 0.00 | 0.493647E+10 | 0.80 | 0.00 | 0.876413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.234932E+10 | 0.215587E+10 | 0.218518E+11 | 0.00 | 0.465756E+10 | 0.77 | 0.00 | 0.579276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.248949E+10 | 0.252528E+10 | 0.225803E+11 | 0.00 | 0.494070E+10 | 0.79 | 0.00 | 0.674758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247928E+10 | 0.269816E+10 | 0.218519E+11 | 0.00 | 0.495309E+10 | 0.77 | 0.00 | 0.177937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.258190E+10 | 0.293659E+10 | 0.225802E+11 | 0.00 | 0.545513E+10 | 0.79 | 0.00 | 84963159.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.289657E+11 | 0.271118E+11 | 0.265865E+12 | 0.00 | 0.594899E+11 | 9.37 | 0.00 | 0.366768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.227993E+10 | 0.165971E+10 | 0.203951E+11 | 0.00 | 0.465756E+10 | 0.72 | 0.00 | 15937858.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.258190E+10 | 0.293659E+10 | 0.225804E+11 | 0.00 | 0.545513E+10 | 0.80 | 0.00 | 0.976810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.457551E+11 | 0.00 | 0.201053E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.484093E+11 | 0.00 | 0.183569E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.315639E+11 | 0.00 | 0.200742E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.236780E+11 | 0.00 | 0.187258E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.273971E+10 | 0.00 | 0.183805E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 17798428.70 | 0.00 | 0.168587E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 6879977.37 | 0.00 | 0.167149E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 2751271.08 | 0.00 | 0.165296E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.100359E+10 | 0.00 | 0.162336E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.200260E+11 | 0.00 | 0.175577E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.328565E+11 | 0.00 | 0.179347E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.577839E+11 | 0.00 | 0.194237E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.263843E+12 | 0.00 | 0.216895E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 2751271.08 | 0.00 | 0.162336E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.577839E+11 | 0.00 | 0.201053E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1769.15 | 02-JAN-16:40 | 2040.24 | 01-JAN-00:10 | 14073.79 | 01-JAN-11:09 | 0.00 | 3193.70 | 05-JAN-18:00 | 0.00 | 12-JAN-12:30 | 0.00 | 01-JAN-00:10 |
February | 1769.15 | 01-FEB-17:19 | 2040.24 | 01-FEB-00:10 | 14073.79 | 01-FEB-11:09 | 0.00 | 3168.61 | 12-FEB-07:10 | 0.00 | 01-FEB-11:20 | 0.00 | 01-FEB-00:10 |
March | 1769.15 | 01-MAR-17:30 | 2040.24 | 01-MAR-00:10 | 14073.79 | 01-MAR-11:09 | 0.00 | 3032.49 | 19-MAR-06:00 | 0.00 | 05-MAR-08:50 | 0.00 | 01-MAR-00:10 |
April | 1769.15 | 01-APR-17:49 | 2040.24 | 01-APR-05:10 | 14073.79 | 01-APR-10:09 | 0.00 | 2725.01 | 17-APR-06:10 | 0.00 | 13-APR-13:39 | 0.00 | 01-APR-00:10 |
May | 1769.15 | 01-MAY-18:49 | 2040.24 | 01-MAY-18:49 | 14073.79 | 01-MAY-10:09 | 0.00 | 2417.81 | 02-MAY-06:10 | 0.00 | 02-MAY-08:39 | 0.00 | 01-MAY-00:10 |
June | 1769.15 | 01-JUN-19:19 | 2040.24 | 01-JUN-19:19 | 14073.79 | 01-JUN-10:09 | 0.00 | 3425.70 | 26-JUN-17:10 | 0.00 | 13-JUN-06:49 | 0.00 | 01-JUN-00:10 |
July | 1769.15 | 01-JUL-19:30 | 2040.24 | 01-JUL-19:30 | 14073.79 | 01-JUL-10:09 | 0.00 | 3180.39 | 17-JUL-11:09 | 0.00 | 03-JUL-08:30 | 0.00 | 01-JUL-00:10 |
August | 1769.15 | 01-AUG-18:49 | 2040.24 | 01-AUG-19:10 | 14073.79 | 01-AUG-10:09 | 0.00 | 3233.52 | 16-AUG-12:00 | 0.00 | 04-AUG-13:20 | 0.00 | 01-AUG-00:10 |
September | 1769.15 | 01-SEP-18:30 | 2040.24 | 01-SEP-05:10 | 14073.79 | 01-SEP-10:09 | 0.00 | 2553.19 | 09-SEP-11:09 | 0.00 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 1769.15 | 02-OCT-17:10 | 2040.24 | 01-OCT-05:10 | 14073.79 | 01-OCT-10:09 | 0.00 | 2777.63 | 30-OCT-06:10 | 0.00 | 04-OCT-07:49 | 0.00 | 01-OCT-00:10 |
November | 1769.15 | 01-NOV-16:40 | 2040.24 | 01-NOV-05:10 | 14073.79 | 01-NOV-10:09 | 0.00 | 3025.84 | 29-NOV-20:00 | 0.00 | 04-NOV-09:39 | 0.00 | 01-NOV-00:10 |
December | 1769.15 | 01-DEC-16:19 | 2040.24 | 01-DEC-00:10 | 14073.79 | 01-DEC-11:09 | 0.00 | 3308.90 | 21-DEC-18:10 | 0.00 | 21-DEC-11:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1769.15 | 2040.24 | 14073.79 | 0.00 | 2417.81 | 0.00 | 0.00 | ||||||
Maximum of Months | 1769.15 | 2040.24 | 14073.79 | 0.00 | 3425.70 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 2706.89 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1735.68 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4839.76 | 14-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3589.34 | 20-APR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7092.87 | 17-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14192.77 | 26-JUN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12806.47 | 17-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13052.77 | 16-AUG-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9866.04 | 09-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6254.08 | 11-OCT-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3833.33 | 07-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3079.80 | 01-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1735.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14192.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 22413.22 | 05-JAN-11:09 | 1225.08 | 14073.79 | 0.00 | 0.00 | 2994.82 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21957.43 | 01-FEB-11:09 | 1225.08 | 14073.79 | 0.00 | 0.00 | 2525.69 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23639.89 | 14-MAR-10:20 | 1225.08 | 14073.79 | 0.00 | 0.00 | 2032.27 | 0.00 | 0.00 | 2014.05 | 0.00 |
April | 22500.58 | 19-APR-10:00 | 1225.08 | 14073.79 | 0.00 | 0.00 | 2032.27 | 0.00 | 0.00 | 2652.26 | 0.00 |
May | 27079.70 | 17-MAY-10:20 | 1225.08 | 14073.79 | 0.00 | 0.00 | 2032.27 | 0.00 | 0.00 | 5446.71 | 0.00 |
June | 32803.46 | 26-JUN-16:10 | 1225.08 | 12724.18 | 0.00 | 0.00 | 3269.27 | 0.00 | 0.00 | 13991.10 | 0.00 |
July | 32807.28 | 17-JUL-11:09 | 1225.08 | 13174.05 | 0.00 | 0.00 | 3180.39 | 0.00 | 0.00 | 12708.29 | 0.00 |
August | 32877.88 | 16-AUG-11:09 | 1225.08 | 13174.05 | 0.00 | 0.00 | 3208.71 | 0.00 | 0.00 | 12757.78 | 0.00 |
September | 29556.56 | 09-SEP-10:00 | 1088.96 | 14073.79 | 0.00 | 0.00 | 2548.37 | 0.00 | 0.00 | 9338.44 | 0.00 |
October | 25842.04 | 11-OCT-10:20 | 1225.08 | 14073.79 | 0.00 | 0.00 | 2032.27 | 0.00 | 0.00 | 4216.20 | 0.00 |
November | 23249.03 | 09-NOV-11:20 | 1225.08 | 14073.79 | 0.00 | 0.00 | 2032.27 | 0.00 | 0.00 | 1612.69 | 0.00 |
December | 22471.99 | 20-DEC-11:09 | 1225.08 | 14073.79 | 0.00 | 0.00 | 3053.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 21957.43 | 1088.96 | 12724.18 | 0.00 | 0.00 | 2032.27 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32877.88 | 1225.08 | 14073.79 | 0.00 | 0.00 | 3269.27 | 0.00 | 0.00 | 13991.10 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 79572.85 | 05-JAN-18:00 | 0.00 | 27747.69 | 31-JAN-13:30 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 80864.54 | 12-FEB-07:10 | 0.00 | 27774.50 | 11-FEB-13:39 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 70813.66 | 19-MAR-06:00 | 0.00 | 27738.45 | 01-MAR-13:39 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 68367.39 | 03-APR-02:30 | 0.00 | 27461.63 | 01-APR-12:50 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 26007.62 | 02-MAY-06:10 | 0.00 | 26966.97 | 01-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 2320.20 | 09-JUN-05:10 | 0.00 | 26304.73 | 01-JUN-12:39 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 2137.35 | 09-JUL-02:09 | 0.00 | 25705.93 | 01-JUL-12:30 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 1907.77 | 19-AUG-02:09 | 0.00 | 25345.29 | 31-AUG-12:50 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 26824.19 | 22-SEP-06:10 | 0.00 | 25740.20 | 30-SEP-12:39 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 68367.39 | 30-OCT-02:09 | 0.00 | 26396.45 | 31-OCT-12:50 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 68367.39 | 02-NOV-02:09 | 0.00 | 27010.29 | 30-NOV-13:00 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 87819.73 | 23-DEC-07:10 | 0.00 | 27498.86 | 31-DEC-13:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 1907.77 | 0.00 | 25345.29 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 87819.73 | 0.00 | 27774.50 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.67 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 |
February | 18.50 | 19.71 | 0.00 | 19.71 | 0.00 | 19.71 | 0.00 | 19.71 |
March | 13.00 | 19.91 | 0.33 | 19.91 | 0.00 | 19.91 | 0.00 | 19.91 |
April | 6.83 | 19.78 | 0.00 | 19.78 | 0.00 | 19.78 | 0.00 | 19.78 |
May | 0.17 | 20.47 | 0.00 | 20.47 | 0.33 | 23.13 | 0.00 | 23.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 24.59 | 0.00 | 24.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 24.64 | 0.50 | 24.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 24.69 | 0.33 | 24.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 24.70 | 0.00 | 24.70 |
October | 4.33 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
November | 7.50 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
December | 13.50 | 19.67 | 0.17 | 19.68 | 0.00 | 19.68 | 0.00 | 19.68 |
Annual Sum or Average | 72.50 | 19.73 | 0.50 | 19.73 | 42.00 | 21.53 | 0.83 | 21.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.30 | 0.00 | 19.30 |
Maximum of Months | 18.50 | 20.47 | 0.33 | 20.47 | 14.00 | 24.70 | 0.50 | 24.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.28 | 0.00 | 27.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.27 | 0.00 | 27.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.91 | 0.00 | 27.91 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.85 | 0.00 | 27.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 28.62 | 0.00 | 28.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 30.21 | 0.00 | 30.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 30.29 | 0.00 | 30.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 30.38 | 0.00 | 30.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 30.06 | 0.00 | 30.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.15 | 0.00 | 28.15 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.47 | 0.00 | 27.47 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.29 | 0.00 | 27.29 |
Annual Sum or Average | 0.00 | 0.00 | 156.00 | 29.45 | 0.00 | 29.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.27 | 0.00 | 27.27 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 30.38 | 0.00 | 30.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 584.67 | 20.97 | 113.67 | 20.81 | 113.67 | 20.69 |
February | 533.83 | 20.94 | 149.50 | 20.79 | 149.50 | 20.70 |
March | 535.33 | 21.08 | 107.83 | 20.91 | 107.83 | 20.80 |
April | 514.00 | 21.14 | 86.67 | 21.01 | 83.17 | 20.89 |
May | 365.67 | 21.67 | 112.17 | 22.08 | 12.33 | 22.03 |
June | 95.17 | 23.28 | 473.33 | 23.79 | 53.17 | 23.79 |
July | 130.00 | 23.56 | 516.83 | 23.83 | 103.83 | 23.83 |
August | 83.33 | 23.33 | 526.67 | 23.82 | 51.67 | 23.81 |
September | 120.83 | 21.93 | 361.67 | 23.38 | 1.50 | 23.36 |
October | 456.00 | 21.20 | 110.17 | 21.37 | 51.50 | 21.25 |
November | 541.00 | 21.04 | 68.50 | 20.90 | 64.33 | 20.77 |
December | 579.17 | 20.97 | 159.83 | 20.83 | 159.83 | 20.73 |
Annual Sum or Average | 4539.00 | 21.28 | 2786.83 | 21.89 | 952.33 | 21.77 |
Minimum of Months | 83.33 | 20.94 | 68.50 | 20.79 | 1.50 | 20.69 |
Maximum of Months | 584.67 | 23.56 | 526.67 | 23.83 | 159.83 | 23.83 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 557.83 | 18.98 | 225.50 | 19.15 | 184.00 | 19.01 |
February | 519.17 | 18.95 | 231.00 | 19.01 | 206.67 | 18.90 |
March | 509.83 | 19.59 | 252.83 | 20.14 | 172.00 | 20.02 |
April | 469.67 | 19.72 | 228.17 | 20.53 | 131.17 | 20.48 |
May | 387.17 | 23.60 | 421.50 | 24.35 | 238.00 | 24.64 |
June | 507.00 | 26.05 | 586.33 | 25.97 | 503.67 | 26.00 |
July | 553.67 | 26.08 | 604.33 | 26.03 | 553.33 | 26.05 |
August | 533.67 | 26.06 | 609.83 | 25.96 | 533.33 | 26.00 |
September | 457.17 | 25.51 | 532.67 | 25.61 | 416.17 | 25.74 |
October | 442.67 | 20.54 | 252.67 | 21.68 | 130.50 | 21.88 |
November | 514.83 | 19.29 | 180.67 | 19.69 | 124.50 | 19.60 |
December | 555.50 | 19.02 | 282.67 | 19.19 | 239.17 | 19.04 |
Annual Sum or Average | 6008.17 | 21.91 | 4408.17 | 22.76 | 3432.50 | 23.00 |
Minimum of Months | 387.17 | 18.95 | 180.67 | 19.01 | 124.50 | 18.90 |
Maximum of Months | 557.83 | 26.08 | 609.83 | 26.03 | 553.33 | 26.05 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 21.09115 | 24.07270 | -0.3972 | 9.94582 |
February | 551.00000 | 21.02721 | 21.63287 | -0.4437 | 10.84277 |
March | 612.00000 | 21.42703 | 22.05226 | -0.3329 | 9.73955 |
April | 590.00000 | 21.48717 | 27.09223 | -0.2950 | 9.23105 |
May | 611.00000 | 22.54290 | 32.09006 | -0.9484 | 27.35887 |
June | 592.00000 | 23.78344 | 35.97291 | -0.3955 | 9.00315 |
July | 609.00000 | 23.83110 | 38.92730 | -0.3604 | 8.34778 |
August | 612.00000 | 23.80373 | 37.49980 | -0.3502 | 8.22588 |
September | 590.00000 | 23.46333 | 28.95287 | -0.5213 | 13.13903 |
October | 610.00000 | 21.85772 | 25.10473 | -0.1336 | 8.20681 |
November | 591.00000 | 21.27317 | 25.82398 | -0.3002 | 8.80377 |
December | 609.00000 | 21.11663 | 17.87902 | -0.4336 | 10.80876 |
Annual Sum or Average | 7187.00000 | 22.23263 | 28.13280 | -0.4094 | 11.15294 |
Minimum of Months | 551.00000 | 21.02721 | 17.87902 | -0.9484 | 8.20681 |
Maximum of Months | 612.00000 | 23.83110 | 38.92730 | -0.1336 | 27.35887 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.45201 | 31.13542 | -0.4773 | 13.22574 |
February | 551.00000 | 19.26522 | 28.76322 | -0.5419 | 13.95985 |
March | 612.00000 | 20.43357 | 28.42972 | -0.2685 | 13.35667 |
April | 590.00000 | 20.67755 | 33.14509 | -0.1762 | 13.13385 |
May | 611.00000 | 23.72329 | 34.32643 | -0.2396 | 18.02921 |
June | 592.00000 | 25.85222 | 35.31903 | 0.53316 | 12.62409 |
July | 609.00000 | 25.94483 | 37.45378 | 0.58205 | 13.45192 |
August | 612.00000 | 25.86415 | 36.84465 | 0.56443 | 13.13641 |
September | 590.00000 | 25.21535 | 30.23010 | 0.30518 | 13.74166 |
October | 610.00000 | 21.48568 | 30.35453 | 0.03938 | 13.43127 |
November | 591.00000 | 19.91658 | 32.67116 | -0.3300 | 12.30829 |
December | 609.00000 | 19.52056 | 24.29834 | -0.4901 | 13.95179 |
Annual Sum or Average | 7187.00000 | 22.29814 | 31.93192 | -0.0387 | 13.70187 |
Minimum of Months | 551.00000 | 19.26522 | 24.29834 | -0.5419 | 12.30829 |
Maximum of Months | 612.00000 | 25.94483 | 37.45378 | 0.58205 | 18.02921 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 56637064.78 | 16762255.46 | 8.50 | 56637064.78 | -0.0 | 0.00 | 0.32 | 20-JAN-13:55 | 0.00 | 01-JAN-00:01 | 4544.65 | 20-JAN-13:55 | 4544.65 | 20-JAN-13:55 | 0.00 | 20-JAN-13:50 | 1310.46 | 20-JAN-13:55 | 0.00 | 01-JAN-00:01 |
February | 15274978.16 | 4607720.37 | 2.83 | 15274978.16 | 0.00 | 0.00 | 0.18 | 18-FEB-14:00 | 0.00 | 01-FEB-00:01 | 2420.45 | 18-FEB-14:00 | 2420.45 | 18-FEB-14:00 | 0.00 | 18-FEB-13:30 | 722.75 | 18-FEB-14:00 | 0.00 | 01-FEB-00:01 |
March | 0.355173E+09 | 0.101901E+09 | 28.33 | 0.355173E+09 | 0.00 | 0.00 | 0.60 | 14-MAR-13:00 | 0.00 | 01-MAR-00:01 | 9066.86 | 14-MAR-13:00 | 9066.86 | 14-MAR-13:00 | 0.00 | 14-MAR-11:40 | 2436.45 | 14-MAR-13:00 | 0.00 | 01-MAR-00:01 |
April | 0.221552E+09 | 65826241.02 | 31.17 | 0.221468E+09 | 83884.13 | 0.00 | 0.39 | 20-APR-13:00 | 0.00 | 01-APR-00:01 | 5700.48 | 20-APR-13:00 | 5700.48 | 20-APR-13:00 | 31.46 | 27-APR-16:10 | 1613.62 | 20-APR-13:00 | 0.00 | 01-APR-00:01 |
May | 0.260446E+10 | 0.726264E+09 | 149.73 | 0.255180E+10 | 52653616.50 | 0.00 | 0.81 | 17-MAY-12:55 | 0.00 | 01-MAY-00:01 | 12972.44 | 17-MAY-12:55 | 12972.44 | 17-MAY-12:55 | 1381.84 | 31-MAY-18:40 | 3292.36 | 17-MAY-12:55 | 0.00 | 01-MAY-00:01 |
June | 0.144916E+11 | 0.385911E+10 | 418.63 | 0.135794E+11 | 0.912220E+09 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 | 34109.31 | 14-JUN-02:61 | 34109.31 | 14-JUN-03:36 | 14004.38 | 18-JUN-02:62 | 8177.68 | 05-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.156420E+11 | 0.413805E+10 | 449.26 | 0.143649E+11 | 0.127704E+10 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 | 34109.31 | 15-JUL-03:21 | 34109.31 | 01-JUL-02:41 | 14244.38 | 24-JUL-02:62 | 8177.68 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 |
August | 0.143964E+11 | 0.379770E+10 | 427.30 | 0.133967E+11 | 0.999749E+09 | 0.00 | 1.00 | 01-AUG-02:62 | 0.00 | 01-AUG-00:01 | 34771.15 | 04-AUG-02:41 | 34109.31 | 15-AUG-02:61 | 20508.42 | 04-AUG-02:41 | 8222.25 | 04-AUG-02:41 | 0.00 | 01-AUG-00:01 |
September | 0.944840E+10 | 0.251984E+10 | 337.61 | 0.922163E+10 | 0.226774E+09 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 | 34109.31 | 03-SEP-02:61 | 34109.31 | 30-SEP-03:42 | 12691.67 | 01-SEP-02:61 | 8177.68 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 |
October | 0.101774E+10 | 0.285206E+09 | 70.77 | 0.101748E+10 | 263246.97 | 0.00 | 1.00 | 11-OCT-02:61 | 0.00 | 01-OCT-00:01 | 17035.09 | 11-OCT-02:61 | 16884.74 | 11-OCT-02:61 | 654.94 | 08-OCT-03:15 | 4087.33 | 11-OCT-02:61 | 0.00 | 01-OCT-00:01 |
November | 0.251620E+09 | 73222235.40 | 22.83 | 0.251620E+09 | 0.00 | 0.00 | 0.47 | 07-NOV-14:00 | 0.00 | 01-NOV-00:01 | 6980.88 | 07-NOV-14:00 | 6980.88 | 07-NOV-14:00 | 0.00 | 07-NOV-14:35 | 1936.73 | 07-NOV-14:00 | 0.00 | 01-NOV-00:01 |
December | 0.113231E+09 | 33322874.41 | 11.83 | 0.113231E+09 | 0.00 | 0.00 | 0.38 | 01-DEC-14:00 | 0.00 | 01-DEC-00:01 | 5537.05 | 01-DEC-14:00 | 5537.05 | 01-DEC-14:00 | 0.00 | 01-DEC-13:50 | 1571.43 | 01-DEC-14:00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.586141E+11 | 0.156218E+11 | 1958.79 | 0.551453E+11 | 0.346879E+10 | 0.00 | ||||||||||||||
Minimum of Months | 15274978.16 | 4607720.37 | 2.83 | 15274978.16 | -0.0 | 0.00 | 0.18 | 0.00 | 2420.45 | 2420.45 | 0.00 | 722.75 | 0.00 | |||||||
Maximum of Months | 0.156420E+11 | 0.413805E+10 | 449.26 | 0.143649E+11 | 0.127704E+10 | 0.00 | 1.00 | 0.00 | 34771.15 | 34109.31 | 20508.42 | 8222.25 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 96088367.49 | 28113210.40 | 14.28 | 94560557.32 | 1527810.17 | 0.00 | 1.00 | 20-JAN-04:21 | 0.00 | 01-JAN-00:01 | 14582.03 | 20-JAN-04:21 | 12548.15 | 20-JAN-04:21 | 2033.88 | 20-JAN-04:21 | 3498.75 | 20-JAN-04:21 | 0.00 | 01-JAN-00:01 |
February | 38232725.02 | 11330138.49 | 6.84 | 37386714.84 | 846010.18 | 0.00 | 0.29 | 28-FEB-04:04 | 0.00 | 01-FEB-00:01 | 3529.91 | 28-FEB-04:04 | 3486.06 | 18-FEB-14:00 | 1130.06 | 24-FEB-04:10 | 1024.83 | 28-FEB-04:04 | 0.00 | 01-FEB-00:01 |
March | 0.541370E+09 | 0.152553E+09 | 50.39 | 0.537602E+09 | 3768170.77 | 0.00 | 1.00 | 10-MAR-04:21 | 0.00 | 01-MAR-00:01 | 29197.55 | 17-MAR-04:01 | 28478.68 | 16-MAR-03:21 | 6061.74 | 17-MAR-04:01 | 7000.09 | 14-MAR-02:61 | 0.00 | 01-MAR-00:01 |
April | 0.508110E+09 | 0.146037E+09 | 56.81 | 0.494091E+09 | 14018392.23 | 0.00 | 1.00 | 07-APR-03:21 | 0.00 | 01-APR-00:01 | 29197.55 | 28-APR-04:01 | 23781.07 | 08-APR-02:61 | 10566.87 | 21-APR-02:61 | 7000.09 | 08-APR-02:61 | 0.00 | 01-APR-00:01 |
May | 0.438672E+10 | 0.118070E+10 | 220.86 | 0.416391E+10 | 0.222816E+09 | 0.00 | 1.00 | 05-MAY-02:61 | 0.00 | 01-MAY-00:01 | 29197.55 | 09-MAY-04:01 | 26121.49 | 11-MAY-02:11 | 14696.07 | 22-MAY-02:61 | 7000.09 | 05-MAY-04:01 | 0.00 | 01-MAY-00:01 |
June | 0.199977E+11 | 0.512090E+10 | 478.80 | 0.184923E+11 | 0.150534E+10 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 | 29197.55 | 02-JUN-03:31 | 29197.55 | 07-JUN-02:11 | 17070.35 | 21-JUN-02:11 | 8310.29 | 26-JUN-15:00 | 0.00 | 01-JUN-00:01 |
July | 0.221425E+11 | 0.563005E+10 | 523.38 | 0.199427E+11 | 0.219974E+10 | 0.00 | 1.00 | 01-JUL-00:42 | 0.00 | 01-JUL-00:01 | 29197.55 | 11-JUL-03:24 | 29197.55 | 01-JUL-02:41 | 16656.61 | 20-JUL-02:11 | 7630.53 | 16-JUL-13:00 | 0.00 | 01-JUL-00:01 |
August | 0.195297E+11 | 0.496642E+10 | 488.27 | 0.179162E+11 | 0.161351E+10 | 0.00 | 1.00 | 01-AUG-02:11 | 0.00 | 01-AUG-00:01 | 29666.03 | 04-AUG-02:11 | 29197.55 | 15-AUG-02:52 | 19947.82 | 04-AUG-02:11 | 7663.09 | 16-AUG-14:00 | 0.00 | 01-AUG-00:01 |
September | 0.127916E+11 | 0.327291E+10 | 399.17 | 0.123071E+11 | 0.484480E+09 | 0.00 | 1.00 | 01-SEP-02:11 | 0.00 | 01-SEP-00:01 | 29197.55 | 13-SEP-03:36 | 29197.55 | 30-SEP-03:14 | 16228.90 | 01-SEP-02:11 | 7000.09 | 01-SEP-02:11 | 0.00 | 01-SEP-00:01 |
October | 0.141980E+10 | 0.389552E+09 | 93.69 | 0.139365E+10 | 26154312.46 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:01 | 29197.55 | 06-OCT-04:01 | 24995.29 | 20-OCT-04:01 | 11120.93 | 09-OCT-02:61 | 7000.09 | 06-OCT-04:01 | 0.00 | 01-OCT-00:01 |
November | 0.368278E+09 | 0.104715E+09 | 29.87 | 0.362404E+09 | 5874591.59 | 0.00 | 1.00 | 07-NOV-04:21 | 0.00 | 01-NOV-00:01 | 29197.55 | 07-NOV-05:01 | 27436.12 | 07-NOV-05:01 | 13597.51 | 10-NOV-03:01 | 7000.09 | 07-NOV-05:01 | 0.00 | 01-NOV-00:01 |
December | 0.178450E+09 | 51640284.82 | 18.92 | 0.177630E+09 | 820136.95 | 0.00 | 1.00 | 05-DEC-04:21 | 0.00 | 01-DEC-00:01 | 14582.03 | 05-DEC-04:21 | 12468.48 | 05-DEC-04:21 | 2113.55 | 05-DEC-04:21 | 3498.75 | 05-DEC-04:21 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.819986E+11 | 0.210549E+11 | 2381.29 | 0.759197E+11 | 0.607890E+10 | 0.00 | ||||||||||||||
Minimum of Months | 38232725.02 | 11330138.49 | 6.84 | 37386714.84 | 820136.95 | 0.00 | 0.29 | 0.00 | 3529.91 | 3486.06 | 1130.06 | 1024.83 | 0.00 | |||||||
Maximum of Months | 0.221425E+11 | 0.563005E+10 | 523.38 | 0.199427E+11 | 0.219974E+10 | 0.00 | 1.00 | 0.00 | 29666.03 | 29197.55 | 19947.82 | 8310.29 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 129.31 | 79.25 | 50.07 | 113.58 | 200.64 | 0.00 | 0.00 | 0.00 |
February | 171.78 | 108.44 | 63.33 | 161.77 | 206.23 | 0.00 | 0.00 | 0.00 |
March | 207.33 | 120.93 | 86.40 | 211.68 | 154.61 | 0.00 | 0.00 | 0.00 |
April | 212.63 | 103.57 | 109.05 | 213.53 | 134.39 | 0.00 | 0.00 | 0.00 |
May | 248.56 | 103.82 | 144.74 | 287.03 | 78.05 | 0.00 | 0.00 | 0.00 |
June | 303.27 | 159.21 | 144.06 | 410.31 | 45.44 | 0.00 | 0.00 | 0.00 |
July | 275.69 | 131.28 | 144.42 | 377.45 | 42.30 | 0.00 | 0.00 | 0.00 |
August | 278.08 | 153.15 | 124.92 | 374.96 | 50.36 | 0.00 | 0.00 | 0.00 |
September | 231.37 | 125.69 | 105.68 | 294.77 | 75.09 | 0.00 | 0.00 | 0.00 |
October | 167.56 | 91.81 | 75.75 | 175.64 | 156.68 | 0.00 | 0.00 | 0.00 |
November | 130.42 | 73.64 | 56.79 | 121.04 | 185.67 | 0.00 | 0.00 | 0.00 |
December | 112.91 | 65.05 | 47.87 | 93.32 | 233.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.87 | 109.60 | 96.27 | 236.61 | 129.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.91 | 65.05 | 47.87 | 93.32 | 42.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 303.27 | 159.21 | 144.74 | 410.31 | 233.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 791.59 | 651.17 | 140.42 | 910.80 | 372.17 | 0.00 | 0.00 | 0.00 |
February | 759.28 | 605.34 | 153.93 | 867.60 | 389.52 | 0.00 | 0.00 | 0.00 |
March | 559.80 | 368.32 | 191.48 | 647.80 | 308.78 | 0.00 | 0.00 | 0.00 |
April | 362.57 | 145.79 | 216.78 | 382.58 | 280.88 | 0.00 | 0.00 | 0.00 |
May | 332.25 | 60.90 | 271.35 | 385.19 | 168.52 | 0.00 | 0.00 | 0.00 |
June | 306.33 | 55.99 | 250.34 | 443.03 | 98.73 | 0.00 | 0.00 | 0.00 |
July | 318.88 | 57.10 | 261.78 | 464.50 | 90.12 | 0.00 | 0.00 | 0.00 |
August | 406.00 | 169.72 | 236.28 | 589.40 | 105.10 | 0.00 | 0.00 | 0.00 |
September | 522.36 | 291.47 | 230.88 | 711.05 | 157.04 | 0.00 | 0.00 | 0.00 |
October | 624.58 | 443.16 | 181.43 | 759.87 | 308.30 | 0.00 | 0.00 | 0.00 |
November | 760.97 | 606.60 | 154.37 | 895.35 | 352.81 | 0.00 | 0.00 | 0.00 |
December | 727.68 | 588.98 | 138.71 | 816.52 | 429.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 538.11 | 335.52 | 202.59 | 654.93 | 254.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 306.33 | 55.99 | 138.71 | 382.58 | 90.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 791.59 | 651.17 | 271.35 | 910.80 | 429.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.56 | 87.16 | 50.39 | 129.00 | 204.14 | 0.00 | 0.00 | 0.00 |
February | 165.88 | 102.79 | 63.08 | 155.54 | 207.39 | 0.00 | 0.00 | 0.00 |
March | 194.23 | 107.16 | 87.07 | 194.63 | 156.40 | 0.00 | 0.00 | 0.00 |
April | 182.88 | 77.43 | 105.45 | 176.26 | 137.06 | 0.00 | 0.00 | 0.00 |
May | 223.52 | 78.80 | 144.72 | 257.20 | 81.72 | 0.00 | 0.00 | 0.00 |
June | 273.38 | 131.53 | 141.85 | 373.77 | 49.10 | 0.00 | 0.00 | 0.00 |
July | 222.74 | 81.59 | 141.16 | 306.20 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 232.48 | 114.85 | 117.63 | 312.09 | 51.88 | 0.00 | 0.00 | 0.00 |
September | 206.14 | 98.86 | 107.28 | 262.99 | 78.51 | 0.00 | 0.00 | 0.00 |
October | 173.42 | 99.12 | 74.30 | 185.70 | 157.51 | 0.00 | 0.00 | 0.00 |
November | 142.30 | 86.39 | 55.91 | 136.92 | 186.30 | 0.00 | 0.00 | 0.00 |
December | 114.94 | 67.90 | 47.04 | 96.95 | 233.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 189.18 | 94.35 | 94.83 | 215.86 | 131.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 114.94 | 67.90 | 47.04 | 96.95 | 44.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 273.38 | 131.53 | 144.72 | 373.77 | 233.08 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.346350E+09 | 0.212253E+09 | 0.134096E+09 | 0.304218E+09 | 0.537394E+09 |
February | 0.415563E+09 | 0.262343E+09 | 0.153220E+09 | 0.391351E+09 | 0.498910E+09 |
March | 0.555313E+09 | 0.323908E+09 | 0.231404E+09 | 0.566956E+09 | 0.414098E+09 |
April | 0.551132E+09 | 0.268466E+09 | 0.282667E+09 | 0.553476E+09 | 0.348332E+09 |
May | 0.665741E+09 | 0.278082E+09 | 0.387659E+09 | 0.768774E+09 | 0.209038E+09 |
June | 0.786070E+09 | 0.412665E+09 | 0.373405E+09 | 0.106351E+10 | 0.117771E+09 |
July | 0.738420E+09 | 0.351617E+09 | 0.386803E+09 | 0.101096E+10 | 0.113292E+09 |
August | 0.744797E+09 | 0.410207E+09 | 0.334590E+09 | 0.100428E+10 | 0.134882E+09 |
September | 0.599719E+09 | 0.325784E+09 | 0.273935E+09 | 0.764041E+09 | 0.194621E+09 |
October | 0.448793E+09 | 0.245912E+09 | 0.202881E+09 | 0.470438E+09 | 0.419662E+09 |
November | 0.338059E+09 | 0.190871E+09 | 0.147188E+09 | 0.313734E+09 | 0.481267E+09 |
December | 0.302425E+09 | 0.174218E+09 | 0.128207E+09 | 0.249954E+09 | 0.624369E+09 |
Annual Sum or Average | 0.649238E+10 | 0.345633E+10 | 0.303605E+10 | 0.746170E+10 | 0.409364E+10 |
Minimum of Months | 0.302425E+09 | 0.174218E+09 | 0.128207E+09 | 0.249954E+09 | 0.113292E+09 |
Maximum of Months | 0.786070E+09 | 0.412665E+09 | 0.387659E+09 | 0.106351E+10 | 0.624369E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.212019E+10 | 0.174408E+10 | 0.376106E+09 | 0.243949E+10 | 0.996817E+09 |
February | 0.183685E+10 | 0.146445E+10 | 0.372398E+09 | 0.209891E+10 | 0.942333E+09 |
March | 0.149937E+10 | 0.986497E+09 | 0.512869E+09 | 0.173507E+10 | 0.827049E+09 |
April | 0.939776E+09 | 0.377887E+09 | 0.561889E+09 | 0.991657E+09 | 0.728040E+09 |
May | 0.889909E+09 | 0.163113E+09 | 0.726795E+09 | 0.103170E+10 | 0.451362E+09 |
June | 0.794000E+09 | 0.145120E+09 | 0.648880E+09 | 0.114834E+10 | 0.255919E+09 |
July | 0.854086E+09 | 0.152943E+09 | 0.701144E+09 | 0.124411E+10 | 0.241386E+09 |
August | 0.108743E+10 | 0.454584E+09 | 0.632841E+09 | 0.157865E+10 | 0.281493E+09 |
September | 0.135395E+10 | 0.755493E+09 | 0.598453E+09 | 0.184304E+10 | 0.407046E+09 |
October | 0.167289E+10 | 0.118695E+10 | 0.485937E+09 | 0.203523E+10 | 0.825744E+09 |
November | 0.197243E+10 | 0.157231E+10 | 0.400118E+09 | 0.232076E+10 | 0.914474E+09 |
December | 0.194903E+10 | 0.157752E+10 | 0.371512E+09 | 0.218698E+10 | 0.114982E+10 |
Annual Sum or Average | 0.169699E+11 | 0.105809E+11 | 0.638894E+10 | 0.206539E+11 | 0.802149E+10 |
Minimum of Months | 0.794000E+09 | 0.145120E+09 | 0.371512E+09 | 0.991657E+09 | 0.241386E+09 |
Maximum of Months | 0.212019E+10 | 0.174408E+10 | 0.726795E+09 | 0.243949E+10 | 0.114982E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.368439E+09 | 0.233462E+09 | 0.134976E+09 | 0.345506E+09 | 0.546762E+09 |
February | 0.401290E+09 | 0.248680E+09 | 0.152609E+09 | 0.376291E+09 | 0.501709E+09 |
March | 0.520229E+09 | 0.287021E+09 | 0.233207E+09 | 0.521310E+09 | 0.418904E+09 |
April | 0.474019E+09 | 0.200691E+09 | 0.273328E+09 | 0.456873E+09 | 0.355247E+09 |
May | 0.598685E+09 | 0.211058E+09 | 0.387627E+09 | 0.688885E+09 | 0.218869E+09 |
June | 0.708608E+09 | 0.340938E+09 | 0.367670E+09 | 0.968808E+09 | 0.127264E+09 |
July | 0.596593E+09 | 0.218521E+09 | 0.378073E+09 | 0.820139E+09 | 0.119871E+09 |
August | 0.622674E+09 | 0.307609E+09 | 0.315065E+09 | 0.835914E+09 | 0.138953E+09 |
September | 0.534315E+09 | 0.256239E+09 | 0.278076E+09 | 0.681665E+09 | 0.203507E+09 |
October | 0.464484E+09 | 0.265487E+09 | 0.198997E+09 | 0.497385E+09 | 0.421876E+09 |
November | 0.368839E+09 | 0.223930E+09 | 0.144908E+09 | 0.354895E+09 | 0.482900E+09 |
December | 0.307851E+09 | 0.181856E+09 | 0.125996E+09 | 0.259661E+09 | 0.624275E+09 |
Annual Sum or Average | 0.596603E+10 | 0.297549E+10 | 0.299053E+10 | 0.680733E+10 | 0.416014E+10 |
Minimum of Months | 0.307851E+09 | 0.181856E+09 | 0.125996E+09 | 0.259661E+09 | 0.119871E+09 |
Maximum of Months | 0.708608E+09 | 0.340938E+09 | 0.387627E+09 | 0.968808E+09 | 0.624275E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1121.12 | 744.69 | 1058.46 | 817.58 | 240.88 | 0.00 | 0.00 |
February | 1156.59 | 774.81 | 1096.93 | 816.58 | 280.35 | 0.00 | 0.00 |
March | 1034.56 | 600.24 | 961.36 | 596.41 | 364.95 | 0.00 | 0.00 |
April | 752.59 | 532.53 | 758.07 | 326.79 | 431.28 | 0.00 | 0.00 |
May | 914.47 | 313.33 | 804.34 | 243.52 | 560.81 | 0.00 | 0.00 |
June | 1217.24 | 183.40 | 882.98 | 346.73 | 536.25 | 0.00 | 0.00 |
July | 1141.57 | 170.59 | 817.32 | 269.97 | 547.35 | 0.00 | 0.00 |
August | 1270.40 | 201.29 | 916.55 | 437.72 | 478.83 | 0.00 | 0.00 |
September | 1259.16 | 301.00 | 959.87 | 516.02 | 443.85 | 0.00 | 0.00 |
October | 1111.81 | 613.09 | 965.56 | 634.09 | 331.47 | 0.00 | 0.00 |
November | 1133.70 | 705.17 | 1033.69 | 766.63 | 267.06 | 0.00 | 0.00 |
December | 973.75 | 862.44 | 955.54 | 721.92 | 233.62 | 0.00 | 0.00 |
Annual Sum or Average | 1090.04 | 498.72 | 933.17 | 539.47 | 393.69 | 0.00 | 0.00 |
Minimum of Months | 752.59 | 170.59 | 758.07 | 243.52 | 233.62 | 0.00 | 0.00 |
Maximum of Months | 1270.40 | 862.44 | 1096.93 | 817.58 | 560.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.300281E+10 | 0.199457E+10 | 0.283498E+10 | 0.218980E+10 | 0.645178E+09 | 0.00 | 0.00 |
February | 0.279802E+10 | 0.187442E+10 | 0.265370E+10 | 0.197547E+10 | 0.678227E+09 | 0.00 | 0.00 |
March | 0.277096E+10 | 0.160768E+10 | 0.257491E+10 | 0.159743E+10 | 0.977481E+09 | 0.00 | 0.00 |
April | 0.195071E+10 | 0.138032E+10 | 0.196493E+10 | 0.847044E+09 | 0.111788E+10 | 0.00 | 0.00 |
May | 0.244931E+10 | 0.839224E+09 | 0.215433E+10 | 0.652254E+09 | 0.150208E+10 | 0.00 | 0.00 |
June | 0.315509E+10 | 0.475381E+09 | 0.228868E+10 | 0.898724E+09 | 0.138995E+10 | 0.00 | 0.00 |
July | 0.305757E+10 | 0.456911E+09 | 0.218910E+10 | 0.723080E+09 | 0.146602E+10 | 0.00 | 0.00 |
August | 0.340265E+10 | 0.539127E+09 | 0.245490E+10 | 0.117240E+10 | 0.128250E+10 | 0.00 | 0.00 |
September | 0.326375E+10 | 0.780180E+09 | 0.248798E+10 | 0.133752E+10 | 0.115046E+10 | 0.00 | 0.00 |
October | 0.297788E+10 | 0.164211E+10 | 0.258616E+10 | 0.169835E+10 | 0.887814E+09 | 0.00 | 0.00 |
November | 0.293856E+10 | 0.182781E+10 | 0.267933E+10 | 0.198711E+10 | 0.692214E+09 | 0.00 | 0.00 |
December | 0.260809E+10 | 0.230996E+10 | 0.255931E+10 | 0.193359E+10 | 0.625715E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.343754E+11 | 0.157277E+11 | 0.294283E+11 | 0.170128E+11 | 0.124155E+11 | 0.00 | 0.00 |
Minimum of Months | 0.195071E+10 | 0.456911E+09 | 0.196493E+10 | 0.652254E+09 | 0.625715E+09 | 0.00 | 0.00 |
Maximum of Months | 0.340265E+10 | 0.230996E+10 | 0.283498E+10 | 0.218980E+10 | 0.150208E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.146860E+11 | -0.139022E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -783734682.9 | 58.99 | 0.00 | 0.00 |
February | 0.134249E+11 | -0.127131E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -711788359.6 | 58.99 | 0.00 | 0.00 |
March | 0.146619E+11 | -0.138960E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -765896214.5 | 58.99 | 0.00 | 0.00 |
April | 0.136205E+11 | -0.128844E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -736015501.4 | 58.99 | 0.00 | 0.00 |
May | 0.132916E+11 | -0.125884E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -703172586.8 | 58.99 | 0.00 | 0.00 |
June | 0.121139E+11 | -0.114722E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -641710869.4 | 59.00 | 0.00 | 0.00 |
July | 0.119468E+11 | -0.112854E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -661389351.5 | 58.99 | 0.00 | 0.00 |
August | 0.117952E+11 | -0.111329E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -662305087.7 | 58.98 | 0.00 | 0.00 |
September | 0.116086E+11 | -0.109559E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -652722207.5 | 58.99 | 0.00 | 0.00 |
October | 0.126269E+11 | -0.118832E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -743681045.0 | 58.99 | 0.00 | 0.00 |
November | 0.129812E+11 | -0.122321E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -749173040.9 | 58.99 | 0.00 | 0.00 |
December | 0.141352E+11 | -0.133522E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -783051792.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.156893E+12 | -0.148298E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.859464E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.116086E+11 | -0.139022E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -783734682.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.146860E+11 | -0.109559E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -641710869.4 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.29 | 0.24 | 01-JAN-07:00 | 8328.33 | 33.20 | 199.33 | 264.00 | 8541.18 | 33.71 | 201.00 | 264.33 |
February | 245.50 | 0.26 | 0.24 | 01-FEB-10:39 | 3098.07 | 26.01 | 109.83 | 267.00 | 3857.61 | 26.84 | 118.33 | 265.33 |
March | 296.17 | 0.26 | 0.24 | 01-MAR-06:00 | 2055.09 | 21.33 | 74.17 | 337.00 | 2065.42 | 21.46 | 80.17 | 333.83 |
April | 296.67 | 0.26 | 0.24 | 03-APR-09:39 | 2189.10 | 19.14 | 30.83 | 356.67 | 2593.93 | 19.07 | 28.33 | 357.33 |
May | 415.33 | 0.26 | 0.24 | 01-MAY-05:40 | 1562.08 | 19.20 | 26.83 | 408.17 | 1727.95 | 19.17 | 37.17 | 410.33 |
June | 421.50 | 0.26 | 0.24 | 01-JUN-05:19 | 1625.11 | 18.69 | 6.50 | 414.50 | 1806.51 | 18.64 | 4.50 | 414.00 |
July | 430.33 | 0.27 | 0.24 | 01-JUL-05:19 | 1559.66 | 18.87 | 12.67 | 415.83 | 1750.29 | 18.81 | 19.83 | 417.50 |
August | 394.50 | 0.27 | 0.24 | 01-AUG-05:49 | 2207.03 | 18.64 | 24.33 | 384.83 | 2601.90 | 18.54 | 17.00 | 382.33 |
September | 354.00 | 0.26 | 0.24 | 01-SEP-05:00 | 1899.61 | 19.24 | 47.33 | 348.67 | 2080.91 | 19.21 | 61.83 | 346.50 |
October | 262.67 | 0.26 | 0.24 | 01-OCT-06:30 | 2953.02 | 22.54 | 97.83 | 306.50 | 2507.19 | 22.19 | 74.67 | 304.50 |
November | 257.67 | 0.28 | 0.24 | 01-NOV-08:39 | 10892.90 | 36.89 | 224.33 | 263.33 | 9817.37 | 34.17 | 185.67 | 264.33 |
December | 251.17 | 0.28 | 0.24 | 01-DEC-07:49 | 8062.52 | 34.59 | 191.00 | 254.17 | 7953.54 | 34.93 | 193.17 | 254.33 |
Annual Sum or Average | 3902.00 | 0.27 | 3453.86 | 23.02 | 1045.00 | 4020.67 | 3554.89 | 22.90 | 1021.67 | 4014.67 | ||
Minimum of Months | 245.50 | 0.26 | 0.24 | 1559.66 | 18.64 | 6.50 | 254.17 | 1727.95 | 18.54 | 4.50 | 254.33 | |
Maximum of Months | 430.33 | 0.29 | 0.24 | 10892.90 | 36.89 | 224.33 | 415.83 | 9817.37 | 34.93 | 201.00 | 417.50 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.188430E+11 | 54693.91 | 02-JAN-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204405E+11 | 54693.91 | 01-FEB-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141679E+11 | 54693.91 | 02-MAR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112262E+11 | 54693.91 | 03-APR-02:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173381E+10 | 22547.22 | 03-MAY-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14238742.96 | 5273.13 | 07-JUN-02:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5503981.90 | 8549.38 | 09-JUL-02:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2201016.87 | 9157.29 | 19-AUG-02:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.563789E+09 | 11117.12 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.914284E+10 | 54693.91 | 30-OCT-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143612E+11 | 54693.91 | 02-NOV-02:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232999E+11 | 54693.91 | 07-DEC-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113801E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2201016.87 | 5273.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.232999E+11 | 54693.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.177611E+11 | 42426.72 | 14-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182869E+11 | 40709.60 | 12-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110832E+11 | 38844.86 | 05-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.771616E+10 | 36483.25 | 17-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.457957E+09 | 13702.40 | 03-MAY-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.239084E+09 | 10399.21 | 21-SEP-22:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.687792E+10 | 35816.03 | 30-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119239E+11 | 39889.81 | 30-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229272E+11 | 47731.08 | 22-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.972736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.229272E+11 | 47731.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 56637064.78 | 56637064.78 | 4544.65 | 20-JAN-13:55 | 4544.65 | 0.00 |
February | 0.00 | 0.00 | 15274978.16 | 15274978.16 | 2420.45 | 18-FEB-14:00 | 2420.45 | 0.00 |
March | 0.00 | 0.00 | 0.355173E+09 | 0.355173E+09 | 9066.86 | 14-MAR-13:00 | 9066.86 | 0.00 |
April | 0.00 | 0.00 | 0.221552E+09 | 0.221468E+09 | 5700.48 | 20-APR-13:00 | 5700.48 | 0.00 |
May | 0.00 | 0.00 | 0.260446E+10 | 0.255180E+10 | 12972.44 | 17-MAY-12:55 | 12972.44 | 0.00 |
June | 0.00 | 0.00 | 0.144916E+11 | 0.135794E+11 | 34109.31 | 14-JUN-02:61 | 34109.31 | 0.00 |
July | 0.00 | 0.00 | 0.156420E+11 | 0.143649E+11 | 34109.31 | 15-JUL-03:21 | 25409.34 | 0.00 |
August | 0.00 | 0.00 | 0.143964E+11 | 0.133967E+11 | 34771.15 | 04-AUG-02:41 | 14262.73 | 0.00 |
September | 0.00 | 0.00 | 0.944840E+10 | 0.922163E+10 | 34109.31 | 03-SEP-02:61 | 26722.70 | 0.00 |
October | 0.00 | 0.00 | 0.101774E+10 | 0.101748E+10 | 17035.09 | 11-OCT-02:61 | 16884.74 | 0.00 |
November | 0.00 | 0.00 | 0.251620E+09 | 0.251620E+09 | 6980.88 | 07-NOV-14:00 | 6980.88 | 0.00 |
December | 0.00 | 0.00 | 0.113231E+09 | 0.113231E+09 | 5537.05 | 01-DEC-14:00 | 5537.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.586141E+11 | 0.551453E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15274978.16 | 15274978.16 | 2420.45 | 2420.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.156420E+11 | 0.143649E+11 | 34771.15 | 34109.31 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 96088367.49 | 94560557.32 | 14582.03 | 20-JAN-04:21 | 12548.15 | 0.00 |
February | 0.00 | 0.00 | 38232725.02 | 37386714.84 | 3529.91 | 28-FEB-04:04 | 2442.10 | 0.00 |
March | 0.00 | 0.00 | 0.541370E+09 | 0.537602E+09 | 29197.55 | 17-MAR-04:01 | 23135.80 | 0.00 |
April | 0.00 | 0.00 | 0.508110E+09 | 0.494091E+09 | 29197.55 | 28-APR-04:01 | 19066.50 | 0.00 |
May | 0.00 | 0.00 | 0.438672E+10 | 0.416391E+10 | 29197.55 | 09-MAY-04:01 | 23801.19 | 0.00 |
June | 0.00 | 0.00 | 0.199977E+11 | 0.184923E+11 | 29197.55 | 02-JUN-03:31 | 16942.96 | 0.00 |
July | 0.00 | 0.00 | 0.221425E+11 | 0.199427E+11 | 29197.55 | 11-JUL-03:24 | 24350.14 | 0.00 |
August | 0.00 | 0.00 | 0.195297E+11 | 0.179162E+11 | 29666.03 | 04-AUG-02:11 | 9718.22 | 0.00 |
September | 0.00 | 0.00 | 0.127916E+11 | 0.123071E+11 | 29197.55 | 13-SEP-03:36 | 25124.49 | 0.00 |
October | 0.00 | 0.00 | 0.141980E+10 | 0.139365E+10 | 29197.55 | 06-OCT-04:01 | 24738.80 | 0.00 |
November | 0.00 | 0.00 | 0.368278E+09 | 0.362404E+09 | 29197.55 | 07-NOV-05:01 | 27436.12 | 0.00 |
December | 0.00 | 0.00 | 0.178450E+09 | 0.177630E+09 | 14582.03 | 05-DEC-04:21 | 12468.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.819986E+11 | 0.759197E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 38232725.02 | 37386714.84 | 3529.91 | 2442.10 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.221425E+11 | 0.199427E+11 | 29666.03 | 27436.12 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5483.23 | 20523.22 | 31-JAN-13:46 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 5548.00 | 20577.86 | 14-FEB-13:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5483.16 | 20496.16 | 01-MAR-13:57 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5262.68 | 19904.96 | 01-APR-12:40 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 4992.19 | 18933.94 | 01-MAY-12:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 4719.12 | 17791.60 | 01-JUN-13:00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4503.76 | 16849.20 | 01-JUL-12:35 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4449.56 | 16327.70 | 31-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 4517.86 | 16894.97 | 30-SEP-12:47 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4728.18 | 17888.76 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 5011.58 | 18995.60 | 30-NOV-13:50 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5276.51 | 19977.13 | 31-DEC-13:25 |
Annual Sum or Average | 0.00 | 4994.78 | ||||
Minimum of Months | 0.00 | 0.00 | 4449.56 | 16327.70 | ||
Maximum of Months | 0.00 | 0.00 | 5548.00 | 20577.86 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.114645E+10 | 0.28 | 503.64 | 01-JAN-00:01 | 0.33 |
February | 0.103050E+10 | 0.28 | 503.64 | 01-FEB-00:01 | 0.33 |
March | 0.115887E+10 | 0.28 | 503.64 | 01-MAR-00:01 | 0.33 |
April | 0.113270E+10 | 0.28 | 503.64 | 01-APR-02:62 | 0.33 |
May | 0.120960E+10 | 0.29 | 503.64 | 01-MAY-04:01 | 0.32 |
June | 0.124081E+10 | 0.31 | 503.64 | 01-JUN-00:50 | 0.32 |
July | 0.128405E+10 | 0.31 | 503.64 | 01-JUL-00:10 | 0.33 |
August | 0.128518E+10 | 0.31 | 503.64 | 01-AUG-00:16 | 0.32 |
September | 0.122643E+10 | 0.31 | 503.64 | 01-SEP-00:18 | 0.33 |
October | 0.119479E+10 | 0.29 | 503.64 | 01-OCT-01:15 | 0.32 |
November | 0.112708E+10 | 0.28 | 503.64 | 01-NOV-04:01 | 0.33 |
December | 0.114986E+10 | 0.28 | 503.64 | 01-DEC-00:01 | 0.33 |
Annual Sum or Average | 0.141863E+11 | 0.29 | |||
Minimum of Months | 0.103050E+10 | 0.28 | 503.64 | 0.32 | |
Maximum of Months | 0.128518E+10 | 0.31 | 503.64 | 0.33 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.248263E+10 | 0.65 | 2234.94 | 02-JAN-03:02 | 1.08 |
February | 0.235619E+10 | 0.67 | 2234.94 | 01-FEB-03:03 | 1.08 |
March | 0.237213E+10 | 0.63 | 2234.94 | 02-MAR-03:02 | 1.08 |
April | 0.222298E+10 | 0.62 | 2234.94 | 03-APR-02:08 | 1.08 |
May | 0.203879E+10 | 0.56 | 1161.62 | 03-MAY-04:01 | 0.77 |
June | 0.196429E+10 | 0.57 | 1473.68 | 26-JUN-17:17 | 0.88 |
July | 0.203063E+10 | 0.57 | 1572.77 | 15-JUL-02:61 | 0.91 |
August | 0.203337E+10 | 0.57 | 2208.63 | 26-AUG-02:61 | 1.06 |
September | 0.196620E+10 | 0.57 | 1166.54 | 22-SEP-06:10 | 0.77 |
October | 0.223148E+10 | 0.59 | 2234.94 | 30-OCT-02:70 | 1.09 |
November | 0.230502E+10 | 0.62 | 2234.94 | 02-NOV-02:65 | 1.09 |
December | 0.260728E+10 | 0.66 | 2234.94 | 07-DEC-03:03 | 1.08 |
Annual Sum or Average | 0.266110E+11 | 0.61 | |||
Minimum of Months | 0.196429E+10 | 0.56 | 1161.62 | 0.77 | |
Maximum of Months | 0.260728E+10 | 0.67 | 2234.94 | 1.09 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.163484E+10 | 0.61 | 1150.36 | 14-JAN-05:03 | 0.93 |
February | 0.150336E+10 | 0.61 | 1129.49 | 12-FEB-05:03 | 0.92 |
March | 0.155796E+10 | 0.59 | 1586.65 | 14-MAR-04:01 | 1.08 |
April | 0.147221E+10 | 0.59 | 1586.65 | 14-APR-04:01 | 1.08 |
May | 0.144642E+10 | 0.58 | 1586.65 | 05-MAY-04:01 | 1.08 |
June | 0.159779E+10 | 0.65 | 1586.65 | 01-JUN-02:61 | 1.08 |
July | 0.166377E+10 | 0.65 | 1586.65 | 01-JUL-02:61 | 1.08 |
August | 0.161792E+10 | 0.64 | 1586.65 | 01-AUG-02:11 | 1.08 |
September | 0.146493E+10 | 0.62 | 1586.65 | 01-SEP-02:11 | 1.08 |
October | 0.151442E+10 | 0.60 | 1586.65 | 06-OCT-04:01 | 1.08 |
November | 0.152099E+10 | 0.60 | 1586.65 | 07-NOV-05:01 | 1.08 |
December | 0.169799E+10 | 0.62 | 1214.83 | 22-DEC-05:03 | 0.96 |
Annual Sum or Average | 0.186926E+11 | 0.61 | |||
Minimum of Months | 0.144642E+10 | 0.58 | 1129.49 | 0.92 | |
Maximum of Months | 0.169799E+10 | 0.65 | 1586.65 | 1.08 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 49.93 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 51.49 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 51.28 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 51.31 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 50.78 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 52.13 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:02 | 0.00 | 0.00 | 52.98 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:05 | 0.00 | 0.00 | 53.00 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 53.02 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 51.33 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:05 | 0.00 | 0.00 | 52.45 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 51.94 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 49.93 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 53.02 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 37.60 | 37.60 | 5483.23 | 20523.22 | 31-JAN-13:46 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 51.08 | 51.08 | 5548.00 | 20577.86 | 14-FEB-13:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 51.37 | 51.37 | 5483.16 | 20496.16 | 01-MAR-13:57 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.62 | 51.62 | 5262.68 | 19904.96 | 01-APR-12:40 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 38.71 | 38.71 | 4992.19 | 18933.94 | 01-MAY-12:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 51.99 | 51.99 | 4719.12 | 17791.60 | 01-JUN-13:00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 53.05 | 53.05 | 4503.76 | 16849.20 | 01-JUL-12:35 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.96 | 52.96 | 4449.56 | 16327.70 | 31-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.91 | 52.91 | 4517.86 | 16894.97 | 30-SEP-12:47 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 40.99 | 40.99 | 4728.18 | 17888.76 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.38 | 52.38 | 5011.58 | 18995.60 | 30-NOV-13:50 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 52.28 | 52.28 | 5276.51 | 19977.13 | 31-DEC-13:25 |
Annual Sum or Average | 0.00 | 4994.78 | ||||||
Minimum of Months | 0.00 | 0.00 | 37.60 | 37.60 | 4449.56 | 16327.70 | ||
Maximum of Months | 0.00 | 0.00 | 53.05 | 53.05 | 5548.00 | 20577.86 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.249939E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.236080E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.247403E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.228880E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.276506E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.582340E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.616869E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.583107E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.448604E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.251669E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.237824E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.264061E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.422328E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.228880E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.616869E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.166295E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.151469E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.171051E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.161825E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.262712E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.671869E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.729382E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.658434E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.473784E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.190397E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.162571E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.174963E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.397475E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.151469E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.729382E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.248263E+10 | 56637064.78 | 0.188430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235619E+10 | 15274978.16 | 0.204405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.237213E+10 | 0.355173E+09 | 0.141679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.222298E+10 | 0.221552E+09 | 0.112262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.203879E+10 | 0.260446E+10 | 0.173381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.196429E+10 | 0.144661E+11 | 14238742.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.203063E+10 | 0.156000E+11 | 5503981.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.203337E+10 | 0.143602E+11 | 2201016.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196620E+10 | 0.942256E+10 | 0.563789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223148E+10 | 0.101774E+10 | 0.914284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.230502E+10 | 0.251620E+09 | 0.143612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.260728E+10 | 0.113231E+09 | 0.232999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266110E+11 | 0.584845E+11 | 0.113801E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.196429E+10 | 15274978.16 | 2201016.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.260728E+10 | 0.156000E+11 | 0.232999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.163484E+10 | 96088367.49 | 0.177611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150336E+10 | 38232725.02 | 0.182869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155796E+10 | 0.537419E+09 | 0.110832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147221E+10 | 0.507448E+09 | 0.771616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144642E+10 | 0.438185E+10 | 0.457957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159779E+10 | 0.199427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166377E+10 | 0.220553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161792E+10 | 0.194770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146493E+10 | 0.127398E+11 | 0.239084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151442E+10 | 0.141980E+10 | 0.687792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152099E+10 | 0.367617E+09 | 0.119239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169799E+10 | 0.178450E+09 | 0.229272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186926E+11 | 0.817417E+11 | 0.972736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144642E+10 | 38232725.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169799E+10 | 0.220553E+11 | 0.229272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.248263E+10 | 0.00 | 0.00 | 0.00 | 16762255.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235619E+10 | 0.00 | 0.00 | 0.00 | 4607720.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.237213E+10 | 0.00 | 0.00 | 0.00 | 0.101901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.222298E+10 | 0.00 | 0.00 | 0.00 | 65826241.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.203879E+10 | 0.00 | 0.00 | 0.00 | 0.726264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.196429E+10 | 0.00 | 0.00 | 0.00 | 0.385911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.203063E+10 | 0.00 | 0.00 | 0.00 | 0.413805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.203337E+10 | 0.00 | 0.00 | 0.00 | 0.379770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196620E+10 | 0.00 | 0.00 | 0.00 | 0.251984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223148E+10 | 0.00 | 0.00 | 0.00 | 0.285206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.230502E+10 | 0.00 | 0.00 | 0.00 | 73222235.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.260728E+10 | 0.00 | 0.00 | 0.00 | 33322874.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266110E+11 | 0.00 | 0.00 | 0.00 | 0.156218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.196429E+10 | 0.00 | 0.00 | 0.00 | 4607720.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.260728E+10 | 0.00 | 0.00 | 0.00 | 0.413805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.163484E+10 | 0.00 | 0.00 | 0.00 | 28113210.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150336E+10 | 0.00 | 0.00 | 0.00 | 11330138.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155796E+10 | 0.00 | 0.00 | 0.00 | 0.152553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147221E+10 | 0.00 | 0.00 | 0.00 | 0.146037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144642E+10 | 0.00 | 0.00 | 0.00 | 0.118070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159779E+10 | 0.00 | 0.00 | 0.00 | 0.512090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166377E+10 | 0.00 | 0.00 | 0.00 | 0.563005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161792E+10 | 0.00 | 0.00 | 0.00 | 0.496642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146493E+10 | 0.00 | 0.00 | 0.00 | 0.327291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151442E+10 | 0.00 | 0.00 | 0.00 | 0.389552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152099E+10 | 0.00 | 0.00 | 0.00 | 0.104715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169799E+10 | 0.00 | 0.00 | 0.00 | 51640284.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186926E+11 | 0.00 | 0.00 | 0.00 | 0.210549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144642E+10 | 0.00 | 0.00 | 0.00 | 11330138.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169799E+10 | 0.00 | 0.00 | 0.00 | 0.563005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.665272E+10 | 0.00 | 0.00 | 1576548.30 | 0.00 | 0.149500E+11 | 0.701255E+09 | 0.00 | 3.72 |
February | 0.543390E+10 | 0.00 | 0.00 | 1005258.41 | 0.00 | 0.168548E+11 | 0.430963E+09 | 0.00 | 3.68 |
March | 0.604657E+10 | 0.00 | 0.00 | 6489344.21 | 0.00 | 0.117775E+11 | 0.177830E+10 | 0.00 | 3.96 |
April | 0.604110E+10 | 0.00 | 0.00 | 5729700.27 | 0.00 | 0.933804E+10 | 0.187849E+10 | 0.00 | 3.98 |
May | 0.644795E+10 | 10710867.68 | 0.00 | 19111333.57 | 0.00 | 0.627441E+09 | 0.428889E+10 | 0.00 | 4.64 |
June | 0.978795E+09 | 0.909460E+09 | 0.00 | 36515642.67 | 0.00 | 428828.32 | 0.426423E+10 | 2.35 | 5.01 |
July | 0.719307E+09 | 0.104651E+10 | 0.00 | 34075421.43 | 0.00 | 842215.73 | 0.422210E+10 | 0.00 | 5.08 |
August | 0.865032E+09 | 0.699388E+09 | 0.00 | 40818490.62 | 0.00 | 798783.09 | 0.516985E+10 | 0.00 | 5.21 |
September | 0.228865E+10 | 0.191729E+09 | 0.00 | 42847253.95 | 0.00 | 0.340303E+09 | 0.582786E+10 | 3537.44 | 5.29 |
October | 0.762610E+10 | 0.00 | 0.00 | 13090941.40 | 0.00 | 0.647702E+10 | 0.323267E+10 | 0.00 | 4.19 |
November | 0.742327E+10 | 0.00 | 0.00 | 3847876.90 | 0.00 | 0.113031E+11 | 0.117004E+10 | 0.00 | 3.82 |
December | 0.609882E+10 | 0.00 | 0.00 | 1994105.62 | 0.00 | 0.181171E+11 | 0.795028E+09 | 0.00 | 3.74 |
Annual Sum or Average | 0.566222E+11 | 0.285780E+10 | 0.00 | 0.207102E+09 | 0.00 | 0.897875E+11 | 0.337597E+11 | 3539.79 | 4.36 |
Minimum of Months | 0.719307E+09 | 0.00 | 0.00 | 1005258.41 | 0.00 | 428828.32 | 0.430963E+09 | 0.00 | 3.68 |
Maximum of Months | 0.762610E+10 | 0.104651E+10 | 0.00 | 42847253.95 | 0.00 | 0.181171E+11 | 0.582786E+10 | 3537.44 | 5.29 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.494107E+11 | 0.00 | 0.00 | 3053971.85 | 74776567.77 | 14872811.57 | 0.224518E+10 | 0.00 | 8.78 |
February | 0.476203E+11 | 0.00 | 0.00 | 1960403.54 | 5867211.90 | 15321466.25 | 0.144375E+10 | 0.00 | 8.81 |
March | 0.388010E+11 | 0.00 | 0.00 | 13266698.16 | 0.00 | 10333129.72 | 0.626367E+10 | 0.00 | 8.66 |
April | 0.346460E+11 | 0.00 | 0.00 | 14761817.27 | 0.00 | 5169875.10 | 0.647312E+10 | 0.00 | 8.59 |
May | 0.147190E+11 | 0.00 | 0.00 | 50095554.84 | 0.00 | 0.00 | 0.169381E+11 | 0.00 | 8.54 |
June | 0.201580E+10 | 0.957646E+09 | 0.00 | 0.100220E+09 | 0.00 | 0.00 | 0.146320E+11 | 0.00 | 9.09 |
July | 0.146283E+10 | 0.131350E+10 | 0.00 | 0.101098E+09 | 0.00 | 0.00 | 0.138017E+11 | 0.00 | 9.13 |
August | 0.163599E+10 | 0.948412E+09 | 0.00 | 0.113615E+09 | 0.00 | 0.00 | 0.167074E+11 | 0.00 | 9.08 |
September | 0.528498E+10 | 65234070.48 | 0.00 | 91580487.87 | 0.00 | 0.00 | 0.186201E+11 | 0.00 | 8.80 |
October | 0.313492E+11 | 0.00 | 0.00 | 25177476.61 | 0.00 | 2794623.96 | 0.107158E+11 | 0.00 | 8.59 |
November | 0.418279E+11 | 0.00 | 0.00 | 7411743.30 | 11099853.23 | 8388767.39 | 0.430752E+10 | 0.00 | 8.67 |
December | 0.544250E+11 | 0.00 | 0.00 | 3724856.00 | 8097967.63 | 13434815.56 | 0.266399E+10 | 0.00 | 8.81 |
Annual Sum or Average | 0.323199E+12 | 0.328479E+10 | 0.00 | 0.525967E+09 | 99841600.54 | 70315489.55 | 0.114812E+12 | 0.00 | 8.80 |
Minimum of Months | 0.146283E+10 | 0.00 | 0.00 | 1960403.54 | 0.00 | 0.00 | 0.144375E+10 | 0.00 | 8.54 |
Maximum of Months | 0.544250E+11 | 0.131350E+10 | 0.00 | 0.113615E+09 | 74776567.77 | 15321466.25 | 0.186201E+11 | 0.00 | 9.13 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:36
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.280712E+11 | 0.138812E+11 | 0.103691E+12 | 0.209286E+09 | 0.283638E+11 |
February | 0.367192E+11 | 0.136153E+11 | 0.967106E+11 | 0.115834E+09 | 0.274527E+11 |
March | 0.482103E+11 | 0.124205E+11 | 0.909552E+11 | 0.639604E+09 | 0.286952E+11 |
April | 0.518924E+11 | 0.112636E+11 | 0.843444E+11 | 0.668991E+09 | 0.269393E+11 |
May | 0.638170E+11 | 0.746145E+10 | 0.657352E+11 | 0.167636E+10 | 0.364780E+11 |
June | 0.698863E+11 | 0.266813E+10 | 0.346144E+11 | 0.161929E+10 | 0.731346E+11 |
July | 0.647515E+11 | 0.229520E+10 | 0.316663E+11 | 0.163306E+10 | 0.771684E+11 |
August | 0.634666E+11 | 0.294963E+10 | 0.378952E+11 | 0.196009E+10 | 0.737590E+11 |
September | 0.464087E+11 | 0.442041E+10 | 0.504105E+11 | 0.229280E+10 | 0.554130E+11 |
October | 0.367602E+11 | 0.107233E+11 | 0.871812E+11 | 0.118540E+10 | 0.293297E+11 |
November | 0.305156E+11 | 0.124015E+11 | 0.939417E+11 | 0.402371E+09 | 0.262745E+11 |
December | 0.216416E+11 | 0.157002E+11 | 0.112249E+12 | 0.286771E+09 | 0.303372E+11 |
Annual Sum or Average | 0.562141E+12 | 0.109800E+12 | 0.889394E+12 | 0.126899E+11 | 0.513345E+12 |
Minimum of Months | 0.216416E+11 | 0.229520E+10 | 0.316663E+11 | 0.115834E+09 | 0.262745E+11 |
Maximum of Months | 0.698863E+11 | 0.157002E+11 | 0.112249E+12 | 0.229280E+10 | 0.771684E+11 |