Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 08:25:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1163.56 | 5007.96 | 5007.96 |
Net Site Energy | 1163.56 | 5007.96 | 5007.96 |
Total Source Energy | 2226.06 | 9580.91 | 9580.91 |
Net Source Energy | 2226.06 | 9580.91 | 9580.91 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 31.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 34.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 29.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 265.86 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 51.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 191.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 54.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 463.16 | 700.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 31.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 34.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 29.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 27.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 51.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 191.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 31.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 31.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 34.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 29.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 27.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 265.86 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 51.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 191.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 54.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 242.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 371.32 | 960.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1379.95 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1993.41 | 3014.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 242.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 371.32 | 960.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1379.95 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1993.41 | 3014.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 463.156 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 463.156 | 100.00 |
Total On-Site and Utility Electric Sources | 463.156 | 100.00 |
Total Electricity End Uses | 463.156 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4121.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 7.5044 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 11.6310 | 18.52 | 1071.0790 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 9.5677 | 2.48 | 593.9329 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 9.5677 | 2.48 | 593.9329 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 7.5044 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.6310 | 18.52 | 1071.0790 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 9.5677 | 1.24 | 593.9329 | |||||||
Conditioned Total | 232.34 | 9.5677 | 1.24 | 593.9329 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 9.5677 | 2.48 | 593.9329 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-OCT-11:09 | 29-MAR-10:20 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 11500.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15794.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1225.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 13174.05 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3613.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 21011.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2604.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 36411.65 | 59171.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 11500.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 15794.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1225.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 12146.55 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 3613.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 21011.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1353.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1057.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 33.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 109.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 92.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 85.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 841.99 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 208.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 173.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1466.81 | 759.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 472.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 397.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 369.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3623.92 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 703.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 895.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 746.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6313.14 | 3267.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 472.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 397.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 369.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3623.92 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 703.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 895.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 746.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6313.14 | 3267.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.87 |
KITCHEN DIRECT AIR | 1.24 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.87 | 1.87 | 1.87 | 1.87 | 1.87 | 1.87 | 1.00 | 1.00 | 1.87 |
PSZ-AC_2:2 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.00 | 1.00 | 1.24 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.87 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.24 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.87 | 2004.31 |
PSZ-AC_2:2_ADDAQ FAN | 1.24 | 1374.97 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.87 | 1.87 | 1.87 | 1.24 | 34756.62 | 50571.07 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.24 | 1.24 | 1.24 | 0.819645 | 27095.12 | 53840.27 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.87 | 0.936554 | 1.25 | 34756.62 | 17378.31 | 0.800990 | 0.800990 |
PSZ-AC_2:2 COOLING COIL | 1.24 | 0.620943 | 0.827927 | 27095.12 | 13547.56 | 0.743950 | 0.743950 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 50571.07 |
PSZ-AC_2:2 HEATING COIL | 53840.27 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 7.504 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 124.291 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 11.631 | 279.726 | 791.353 | 0.000 | 0.000 | 0.000 | 1082.710 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 871.800 | 7.504 | 9.958 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 871.800 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1351.195 | 11.631 | 215.388 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1351.195 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 457.500 | 3.938 | 72.928 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 570.000 | 4.907 | 90.861 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.6929 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.209 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.33002231E-12 | 0.10712597E-14 | -0.10720425E-12 | 0.10137879E-15 |
34 | 6 | 0.29661659E-07 | 0.19687232E-09 | 0.67865745E-08 | -0.14052424E-12 |
35 | 5 | -0.19512200E-03 | 0.16741682E-05 | -0.10029371E-03 | 0.67057946E-08 |
36 | 4 | 0.29799499 | 0.81016957E-03 | 0.10178761 | -0.34398158E-04 |
37 | 3 | -7.3821031 | 0.24971312E-01 | -2.3732702 | 0.29576512E-01 |
38 | 2 | 41.252923 | 0.88368331E-01 | 15.405914 | -0.33759269 |
39 | 1 | -80.838295 | 0.39713828E-01 | -29.267905 | 1.0848528 |
40 | 0 | 46.824337 | 0.79570062E-03 | 16.288235 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.497_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 2.826 | 2.826 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.497_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 2.826 | 2.826 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.497_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 2.826 | 2.826 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.497_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 2.826 | 2.826 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.02458E-002 | 0.16139 | 0.61152 | 0.61152 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.11029 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.02458E-002 | 0.16139 | 0.61152 | 0.61152 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.11029 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.02458E-002 | 0.16139 | 0.61152 | 0.61152 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.11029 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.02458E-002 | 0.16139 | 0.61152 | 0.61152 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.11029 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.053 | 0.3093 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5236E-003 |
2 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.1450E-002 |
3 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.3439E-003 |
4 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.8007E-003 |
5 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.2603E-003 |
6 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.1873E-002 |
7 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.0943E-003 |
8 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0886E-002 |
9 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 4.5531E-002 |
10 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.6233E-002 |
11 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 5.1575E-002 |
12 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 5.2433E-002 |
13 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.1519E-002 |
14 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.1835E-002 |
15 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.1787E-002 |
16 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.1787E-002 |
17 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.2394E-002 |
18 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.6321E-003 |
19 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0933E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.4787E-003 |
21 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.3100E-002 |
22 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3667E-003 |
23 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0887E-002 |
24 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0943E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 20870.70187 | 25044.84224 | 1.56092 | 1.87311 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 31.30000 | 8.23349E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 3038.11170 | 3645.73404 | 0.12984 | 0.41606 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 3.80000 | 5.05843E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16597.84312 | 19917.41174 | 1.03491 | 1.24189 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 30.49900 | 8.23222E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.14133 | 00:10:00 | 3.80000 | 5.05843E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 28321.00 | 1.87311 | 1.87311 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 17885.52 | 0.41606 | 0.41606 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 25570.96 | 1.24189 | 1.24189 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 49063.92 | 1.14133 | 1.14133 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.87311 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24189 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.87311 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.87311 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.87311 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.87311 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.87311 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.87311 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24189 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24189 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24189 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24189 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.24189 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.24189 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.87311 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.24189 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.87311 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.87311 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2004.31492 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.87311 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.87311 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.87311 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.23625 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.87311 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.93655 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.24874 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34756.62000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17378.31000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80099 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80099 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34756.62000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 50571.06745 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 50571.06745 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.24189 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.24189 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1374.96545 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.24189 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.24189 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.24189 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.81965 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.24189 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62094 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.82793 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27095.12000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13547.56000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74395 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74395 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27095.12000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 53840.26612 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 53840.26612 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 33395.7 | 11.27 | 11.22 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 26203.0 | 11.60 | 11.55 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_EAST_0.25 | N/A | 2.826 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_SOUTH_0.25 | N/A | 2.826 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_WEST_0.25 | N/A | 2.826 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 5.1122111146E-002 | 0.2163690173 | Pass | Pass | 0.1195166422 | 0.2406112245 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2751445528 | 0.6368719155 | Pass | Pass | 0.1404609929 | 0.7051161771 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.3069901944 | 0.3458997815 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 672.22 | 110.72 | 770.02 | 11.25 | 489.26 | 2053.48 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.497_SHGC_EAST_0.25 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.826 | 0.251 | 0.276 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.497_SHGC_SOUTH_0.25 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.826 | 0.251 | 0.276 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.497_SHGC_WEST_0.25 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.826 | 0.251 | 0.276 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.826 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.826 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 7.5044 | 116.17 | 871.80 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 47.99 | 0.0000 | Y | 7.85 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.6310 | 116.17 | 1351.20 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 83.95 | 0.0000 | Y | 21.29 |
Interior Lighting Total | 9.5677 | 232.34 | 2222.99 | 29.15 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.38 | 871.80 | 331.28 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.38 | 871.80 | 331.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 216.58 | AstronomicalClock | - | 49.14 | 49.14 | 2.00 | |
EXTERIOR_LIGHTS_B | 1823.66 | AstronomicalClock | - | 83.75 | 73.37 | 25.12 | |
Exterior Lighting Total | 2040.24 | 27.11 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34756.62 | 27839.71 | 6916.91 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27095.12 | 20157.41 | 6937.71 | 0.74 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 33395.7 | 11.27 | 11.22 | ||||
PSZ-AC_2:2 COOLING COIL | 26203.0 | 11.60 | 11.55 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 50571.07 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 53840.27 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.87 | 2004.31 | 1070.05 | 1.00 | 1.32 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.24 | 1374.97 | 1107.16 | 1.00 | 1.35 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 20870.70 | 25044.84 | 215.59 | 1.561 | 1.873 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 23.89 | 23.89 | 0.00914 | 31.30 | 0.00823 | 0.416 | 0.00 |
KITCHEN | 16597.84 | 19917.41 | 171.45 | 1.035 | 1.242 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 26.11 | 26.09 | 0.01012 | 30.50 | 0.00823 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 3038.11 | 3645.73 | 31.38 | 0.130 | 0.416 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 21.11 | 21.11 | 0.00757 | 3.80 | 0.00506 | 0.416 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.141 | 00:10:00 | 15.56 | 26.17 | 0.00451 | 3.80 | 0.00506 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.87 | 1.87 | 0.42 | 0.42 | 1.8731 | 1.8731 | 1.8731 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.24 | 1.24 | 1.14 | 1.14 | 1.2419 | 1.2419 | 1.2419 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 34756.620 | 27839.705 | 1.873110 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 17378.31 | 16140.81 | 1.248740 | 25.53 | 17.10 | 0.00893655 | 11.91 | 11.57 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 33.3181 | 23.89 | 0.00913731 | 48.5551 | 20870.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 50571.067 | 50571.067 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 50571.07 | 50571.07 | 1.873109 | 17.26 | 12.40 | 0.00713141 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 22.2121 | 20.51 | 0.00772334 | 50.5226 | 1709.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 27095.120 | 20157.415 | 1.241890 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 13547.56 | 13547.56 | 0.827927 | 30.14 | 18.19 | 0.00838522 | 11.88 | 11.44 | 0.00838522 | 30.50 | 0.00823222 | 18.19 | 137.8544 | 26.09 | 0.01012191 | 47.0811 | 16597.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 53840.266 | 53840.266 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 53840.27 | 53840.27 | 1.241886 | 3.49 | 3.49 | 0.00501394 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 91.9032 | 26.17 | 0.00450889 | 21.0648 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34756.620 | 27839.705 | 1.873110 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4526 | 1004.8586 | 1.1818 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.873109 | 2.21359997 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 17378.31 | 16140.81 | 1.0000 | 1.47573429 | 1.248740 | 25.53 | 17.10 | 0.00893655 | 48429.7 | 11.91 | 11.57 | 0.00850000 | 33417.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17378.31 | 31.30 | 0.00823349 | 18.45 | 0.41605618 | 33.3181 | 23.89 | 0.00913731 | 23.89 | 0.00913731 | 48.5551 | 20870.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 50571.067 | 50571.067 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.873109 | 2.21359997 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 50571.07 | 50571.07 | 1.0000 | 2.21359997 | 1.873109 | 17.26 | 12.40 | 0.00713141 | 35412.5 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50571.07 | 3.80 | 0.00505843 | 3.80 | 0.41605618 | 22.2121 | 21.11 | 0.00772334 | 20.51 | 0.00772334 | 50.5226 | 1709.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27095.120 | 20157.415 | 1.241890 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4277 | 1004.8586 | 1.1818 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.241886 | 1.46763492 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | Sensible | 13547.56 | 13547.56 | 1.0000 | 0.97842607 | 0.827927 | 30.14 | 18.19 | 0.00838522 | 51725.6 | 11.88 | 11.44 | 0.00838522 | 33095.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13547.56 | 30.50 | 0.00823222 | 18.19 | 1.14133354 | 137.8544 | 26.05 | 0.01012191 | 26.09 | 0.01012191 | 47.0811 | 16597.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 53840.266 | 53840.266 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.241886 | 1.46763492 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 53840.27 | 53840.27 | 1.0000 | 1.46763492 | 1.241886 | 3.49 | 3.49 | 0.00501394 | 16081.3 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 53840.27 | 3.80 | 0.00505843 | 3.80 | 1.14133354 | 91.9032 | 0.00 | 0.00450889 | 26.17 | 0.00450889 | 21.0648 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.87 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.24 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 2754.50 | 4567.00 | 843.00 |
KITCHEN | 6080.83 | 4886.00 | 4079.67 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 6119.33 | 7118.67 | 4121.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 9.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 234.50 | 0.00 | 1.50 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 243.00 | 0.00 | 1.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 5.323 | 4.254 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 8.626 | 0.021 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.163 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 8.201 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 13530358.98 | 0.00 | 13530358.98 | 10664887.14 | 24195246.12 | 13120747.55 | 1451.01 | 5376.54 | 1932.44 | 226.33 |
KITCHEN | 22400375.79 | 0.00 | 22400375.79 | 78242.09 | 22478617.88 | 35993094.65 | 8734.57 | 16.75 | 8.67 | 781.81 |
Total Facility | 35930734.77 | 0.00 | 35930734.77 | 10743129.23 | 46673864.00 | 49113842.20 | 8741.81 | 5376.78 | 1940.04 | 811.78 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.5142 | 0.0000 | 0.5142 | 0.4112 | 0.9254 | 0.4161 | 0.00 | 5265.66 | 1921.34 |
KITCHEN | 0.8272 | 0.0000 | 0.8272 | 0.0020 | 0.8292 | 1.1413 | 7169.73 | 16.52 | 0.75 |
Total Facility | 1.3414 | 0.0000 | 1.3414 | 0.4131 | 1.7546 | 1.5574 | 7169.73 | 5265.66 | 1921.89 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 18896587.53 | 0.00 | 18896587.53 | 13120747.55 | 1450.44 | 0.04 | 7309.52 | 226.33 |
PSZ-AC_2:2 | 31284376.43 | 0.00 | 31284376.43 | 35993094.65 | 1427.10 | 6752.27 | 580.62 | 781.81 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.7182 | 0.0000 | 0.7182 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.1553 | 0.0000 | 1.1553 | 1.1413 | 0.00 | 6624.51 | 562.49 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1420.58 | 625.30 | 5367.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 256.03 | 1157.27 | 6555.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.2095 | 0.8460 | 0.5812 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.2538 | 1.1576 | 1.1553 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 374 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 463.16 | 4582.46 | 30-MAR-00:10 | 36411.65 | 16-OCT-11:10 |
Electricity:Building | 302.95 | 2354.92 | 01-JAN-01:10 | 18592.92 | 02-JAN-11:10 |
Electricity:Zone:DINING | 78.18 | 389.32 | 01-JAN-01:10 | 4239.56 | 02-JAN-16:50 |
Electricity:SpaceType:GENERAL | 295.01 | 2218.64 | 01-JAN-01:10 | 15298.87 | 02-JAN-11:10 |
InteriorLights:Electricity | 29.15 | 249.52 | 27-MAY-05:00 | 1769.15 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:DINING | 7.85 | 57.27 | 01-JAN-07:30 | 715.88 | 02-JAN-16:50 |
InteriorLights:Electricity:SpaceType:GENERAL | 29.15 | 249.52 | 27-MAY-05:00 | 1769.15 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 29.15 | 249.52 | 27-MAY-05:00 | 1769.15 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 7.85 | 57.27 | 01-JAN-07:30 | 715.88 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 29.15 | 249.52 | 27-MAY-05:00 | 1769.15 | 02-JAN-16:50 |
Electricity:Zone:KITCHEN | 224.77 | 1965.60 | 01-JAN-01:10 | 14490.86 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 21.29 | 175.55 | 01-JAN-01:10 | 1053.27 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 21.29 | 175.55 | 01-JAN-01:10 | 1053.27 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 265.86 | 1923.78 | 01-JAN-01:10 | 14073.79 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 265.86 | 1923.78 | 01-JAN-01:10 | 14073.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 195.53 | 1653.77 | 01-JAN-01:10 | 10143.54 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 54.76 | 863.59 | 06-JAN-23:30 | 4370.28 | 28-JUN-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 46.82 | 777.81 | 06-JAN-23:30 | 2537.69 | 25-JUL-03:40 |
LowTempRefrigeration:Refrigeration:Electricity | 15.54 | 0.00 | 01-JAN-11:10 | 1461.46 | 25-JUL-03:40 |
MedTempRefrigeration:Refrigeration:Electricity | 31.28 | 722.43 | 30-MAR-00:10 | 1076.23 | 10-JAN-15:00 |
ElectricityPurchased:Facility | 463.16 | 4582.46 | 30-MAR-00:10 | 36411.65 | 16-OCT-11:10 |
ElectricityPurchased:Plant | 463.16 | 4582.46 | 30-MAR-00:10 | 36411.65 | 16-OCT-11:10 |
Cogeneration:ElectricityPurchased | 463.16 | 4582.46 | 30-MAR-00:10 | 36411.65 | 16-OCT-11:10 |
General:Cogeneration:ElectricityPurchased | 463.16 | 4582.46 | 30-MAR-00:10 | 36411.65 | 16-OCT-11:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 463.16 | 4582.46 | 30-MAR-00:10 | 36411.65 | 16-OCT-11:10 |
ElectricityNet:Plant | 463.16 | 4582.46 | 30-MAR-00:10 | 36411.65 | 16-OCT-11:10 |
Cogeneration:ElectricityNet | 463.16 | 4582.46 | 30-MAR-00:10 | 36411.65 | 16-OCT-11:10 |
General:Cogeneration:ElectricityNet | 463.16 | 4582.46 | 30-MAR-00:10 | 36411.65 | 16-OCT-11:10 |
Electricity:HVAC | 86.27 | 0.00 | 01-JAN-01:10 | 19407.55 | 16-OCT-11:10 |
Fans:Electricity | 51.63 | 0.00 | 01-JAN-01:10 | 3613.26 | 16-OCT-11:10 |
General:Fans:Electricity | 51.63 | 0.00 | 01-JAN-01:10 | 3613.26 | 16-OCT-11:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 34.64 | 0.00 | 01-JAN-00:10 | 15794.29 | 16-OCT-11:10 |
General:Cooling:Electricity | 34.64 | 0.00 | 01-JAN-00:10 | 15794.29 | 16-OCT-11:10 |
ExteriorLights:Electricity | 27.11 | 0.00 | 01-JAN-07:00 | 2040.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 27.11 | 0.00 | 01-JAN-07:00 | 2040.24 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 11-FEB-16:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 11-FEB-16:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 700.41 | 2558.65 | 17-JAN-03:30 | 59171.92 | 29-MAR-10:20 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 31.32 | 0.00 | 01-JAN-00:10 | 31404.53 | 08-JAN-07:10 |
Heating:NaturalGas | 31.32 | 0.00 | 01-JAN-00:10 | 31404.53 | 08-JAN-07:10 |
General:Heating:NaturalGas | 31.32 | 0.00 | 01-JAN-00:10 | 31404.53 | 08-JAN-07:10 |
NaturalGas:Plant | 191.93 | 720.00 | 03-JAN-09:10 | 25680.40 | 01-FEB-14:00 |
WaterSystems:NaturalGas | 191.93 | 720.00 | 03-JAN-09:10 | 25680.40 | 01-FEB-14:00 |
Water Heater:WaterSystems:NaturalGas | 191.93 | 720.00 | 03-JAN-09:10 | 25680.40 | 01-FEB-14:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 783.85 | 2662.04 | 30-MAR-00:10 | 105835.39 | 29-SEP-13:00 |
EnergyTransfer:Building | 419.29 | 1331.02 | 30-MAR-00:10 | 38013.46 | 16-OCT-11:10 |
EnergyTransfer:Zone:KITCHEN | 344.05 | 1331.02 | 30-MAR-00:10 | 22010.49 | 27-JAN-05:10 |
Refrigeration:EnergyTransfer | 151.87 | 2662.04 | 30-MAR-00:10 | 7834.84 | 17-JAN-04:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 75.93 | 1331.02 | 30-MAR-00:10 | 3917.42 | 17-JAN-04:50 |
General:Refrigeration:EnergyTransfer | 75.93 | 1331.02 | 30-MAR-00:10 | 3917.42 | 17-JAN-04:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 75.93 | 1331.02 | 30-MAR-00:10 | 3917.42 | 17-JAN-04:50 |
EnergyTransfer:Plant | 204.46 | 1331.02 | 30-MAR-00:10 | 18975.83 | 12-FEB-14:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 13.33 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 62.61 | 1177.28 | 30-MAR-00:10 | 2238.70 | 10-JAN-15:00 |
EnergyTransfer:Zone:DINING | 75.24 | 0.00 | 01-JAN-01:10 | 20923.29 | 16-OCT-11:10 |
Heating:EnergyTransfer | 3.38 | 0.00 | 01-JAN-00:10 | 8815.75 | 08-JAN-07:10 |
Heating:EnergyTransfer:Zone:DINING | 3.38 | 0.00 | 01-JAN-00:10 | 8815.75 | 08-JAN-07:10 |
General:Heating:EnergyTransfer | 3.38 | 0.00 | 01-JAN-00:10 | 8815.75 | 08-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:DINING | 3.38 | 0.00 | 01-JAN-00:10 | 8815.75 | 08-JAN-07:10 |
Cooling:EnergyTransfer | 339.98 | 0.00 | 01-JAN-01:10 | 34151.11 | 16-OCT-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 71.86 | 0.00 | 01-JAN-01:10 | 20923.29 | 16-OCT-11:10 |
General:Cooling:EnergyTransfer | 339.98 | 0.00 | 01-JAN-01:10 | 34151.11 | 16-OCT-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 71.86 | 0.00 | 01-JAN-01:10 | 20923.29 | 16-OCT-11:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 268.12 | 0.00 | 01-JAN-01:10 | 18161.94 | 27-JAN-05:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 268.12 | 0.00 | 01-JAN-01:10 | 18161.94 | 27-JAN-05:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 128.52 | 0.00 | 01-JAN-00:10 | 16443.37 | 02-FEB-13:20 |
PlantLoopHeatingDemand:Plant | 128.52 | 0.00 | 01-JAN-00:10 | 16443.37 | 02-FEB-13:20 |
WaterSystems:PlantLoopHeatingDemand | 128.52 | 0.00 | 01-JAN-00:10 | 16443.37 | 02-FEB-13:20 |
General:WaterSystems:PlantLoopHeatingDemand | 128.52 | 0.00 | 01-JAN-00:10 | 16443.37 | 02-FEB-13:20 |
EnergyTransfer:HVAC | 160.10 | 0.00 | 01-JAN-00:10 | 56315.79 | 16-OCT-11:10 |
HeatingCoils:EnergyTransfer | 25.06 | 0.00 | 01-JAN-00:10 | 25123.63 | 08-JAN-07:10 |
CoolingCoils:EnergyTransfer | 135.04 | 0.00 | 01-JAN-00:10 | 56315.79 | 16-OCT-11:10 |
WaterSystems:EnergyTransfer | 128.52 | 0.00 | 01-JAN-00:10 | 16443.37 | 02-FEB-13:20 |
WaterUse:WaterSystems:EnergyTransfer | 128.52 | 0.00 | 01-JAN-00:10 | 16443.37 | 02-FEB-13:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 3.376 | -71.864 | 0.000 | 0.000 | 70.022 | 7.854 | 52.748 | 20.963 | 0.000 | 1.430 | 0.041 | 0.000 | -10.477 | 0.000 | -74.093 | -0.000 |
KITCHEN | 0.000 | 0.000 | 0.000 | -268.113 | 0.000 | 0.000 | 4.270 | 21.293 | 201.243 | 0.000 | 0.000 | 0.004 | 42.263 | 0.000 | 0.000 | 0.000 | -0.959 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.938 | 14.860 | 0.000 | 0.000 | 0.000 | -18.798 | -0.000 |
Total Facility | 0.000 | 0.000 | 3.376 | -339.977 | 0.000 | 0.000 | 74.292 | 29.146 | 253.992 | 20.963 | 0.000 | 5.372 | 57.164 | 0.000 | -10.477 | 0.000 | -93.850 | -0.000 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 30-SEP-02:61 | 0.00 | 0.00 | 0.00 | -29086.24 | 0.00 | 0.00 | 0.00 | 119.31 | 202.51 | 0.00 | 0.00 | 0.00 | 29069.95 | 0.00 | -305.24 | 0.00 | -0.30 | 0.00 |
KITCHEN | 26-DEC-05:01 | 0.00 | 0.00 | 0.00 | -49989.15 | 0.00 | 0.00 | 9.88 | 234.07 | 4931.35 | 0.00 | 0.00 | 0.00 | 44813.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-OCT-02:61 | 0.00 | 0.00 | 0.00 | -67118.37 | 0.00 | 0.00 | 0.00 | 294.86 | 1879.56 | 0.00 | 0.00 | 412.81 | 65322.95 | 0.00 | -677.35 | 0.00 | -114.47 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 08-JAN-07:10 | 0.00 | 0.00 | 8816.55 | 0.00 | 0.00 | 0.00 | 3598.60 | 117.72 | 1524.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -272.03 | 0.00 | -12440.44 | -1345.07 |
KITCHEN | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-JAN-07:10 | -9380.82 | 9380.82 | 8816.55 | -9380.82 | 0.00 | 0.00 | 3883.20 | 468.82 | 7431.98 | 0.00 | 0.00 | 344.06 | 1194.30 | 0.00 | -272.03 | 0.00 | -12486.05 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.8731 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.8731 | 0.2221 | 1.0000 | Not calculated | 0.4161 | 0.2221 | ||
PSZ-AC_2:2 | 1.2419 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2419 | 0.1218 | 1.0000 | Not calculated | 0.1513 | 0.1218 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.8731 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.8731 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2221 | ||
PSZ-AC_2:2 | 1.2419 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2419 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1218 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8731 | 1.8731 | 1.8731 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2419 | 1.2419 | 1.2419 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.8731 | 1.8731 | 1.8731 | 1.8731 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2419 | 1.2419 | 1.2419 | 1.2419 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8731 | 1.8731 | 1.8731 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2419 | 1.2419 | 1.2419 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.8731 | 1.8731 | 1.8731 | 1.8731 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2419 | 1.2419 | 1.2419 | 1.2419 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1.50 |
Number of hours not met | 1.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 31.32 | 31404.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 34.64 | 15794.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 29.15 | 1769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 27.11 | 2040.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 51.63 | 3613.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 191.93 | 25680.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.54 | 1461.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 31.28 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 320.62 | 463.16 |
Natural Gas | 477.16 | 700.41 |
Additional | 0.00 | 0.00 |
Total | 797.78 | 1163.56 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 125.45 |
Space Heating | 0.00 |
Space Cooling | 149.10 |
Fans (All) | 222.22 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1144.28 |
Miscellaneous (All) | 1993.41 |
Subtotal | 1993.41 |
Natural Gas [MJ/m2] | |
Space Heating | 134.80 |
Service Water Heating | 826.07 |
Miscellaneous (All) | 3014.55 |
Subtotal | 3014.55 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.50 |
Space Heating | 2.69 |
Space Cooling | 2.98 |
Fans (All) | 4.44 |
Service Water Heating | 16.50 |
Receptacle Equipment | 63.86 |
Miscellaneous | 7.04 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7990.33 | 768.33 | 1.33 | 0.00 | 0.00 |
ATTIC | 6000.50 | 794.00 | 730.33 | 1034.67 | 200.50 |
Min | 6000.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 794.00 | 730.33 | 1034.67 | 200.50 |
Average | 7583.61 | 520.78 | 243.89 | 344.89 | 66.83 |
Sum | 22750.83 | 1562.33 | 731.67 | 1034.67 | 200.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16255.33 | 2.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 2.67 | 0.00 | 0.00 | 0.00 |
Average | 90326.78 | 0.89 | 0.00 | 0.00 | 0.00 |
Sum | 270980.33 | 2.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8090.17 | 669.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 4543.67 | 4216.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 6036.33 | 1272.17 | 408.83 | 410.67 | 632.00 |
Min | 4543.67 | 669.83 | 0.00 | 0.00 | 0.00 |
Max | 8090.17 | 4216.33 | 408.83 | 410.67 | 632.00 |
Average | 6223.39 | 2052.78 | 136.28 | 136.89 | 210.67 |
Sum | 18670.17 | 6158.33 | 408.83 | 410.67 | 632.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 232521.50 | 22203.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7517.67 | 8740.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 232521.50 | 22203.50 | 0.00 | 0.00 | 0.00 |
Average | 80013.06 | 10314.61 | 0.00 | 0.00 | 0.00 |
Sum | 240039.17 | 30943.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:42
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.435871E+10 | 10525.20 | 18-JAN-12:55 | 26.00 | 14.69 | 0.478946E+10 | 4680.82 | 14-JAN-19:10 | 26.00 | 14.69 |
February | 0.330446E+10 | 8993.69 | 01-FEB-12:05 | 25.67 | 14.54 | 0.422871E+10 | 4413.25 | 21-FEB-12:00 | 21.00 | 13.54 |
March | 0.347171E+10 | 6676.69 | 10-MAR-13:00 | 23.00 | 12.77 | 0.469769E+10 | 4413.14 | 23-MAR-11:50 | 22.00 | 16.49 |
April | 0.511736E+10 | 10233.28 | 26-APR-13:00 | 27.00 | 17.13 | 0.476131E+10 | 4525.52 | 01-APR-18:10 | 27.00 | 17.13 |
May | 0.516596E+10 | 8002.12 | 04-MAY-12:00 | 24.00 | 16.55 | 0.496526E+10 | 4413.68 | 02-MAY-11:00 | 24.00 | 16.55 |
June | 0.646511E+10 | 16625.54 | 30-JUN-02:61 | 17.00 | 16.37 | 0.502858E+10 | 4680.93 | 24-JUN-18:10 | 17.00 | 16.37 |
July | 0.866187E+10 | 19711.19 | 11-JUL-02:61 | 17.00 | 14.51 | 0.531011E+10 | 4681.02 | 29-JUL-18:40 | 19.00 | 18.37 |
August | 0.910487E+10 | 17132.28 | 26-AUG-02:61 | 16.42 | 16.16 | 0.537784E+10 | 4681.32 | 19-AUG-18:10 | 16.42 | 16.16 |
September | 0.777182E+10 | 29087.08 | 30-SEP-02:61 | 24.18 | 13.94 | 0.505096E+10 | 4681.30 | 30-SEP-18:19 | 22.33 | 17.07 |
October | 0.886052E+10 | 27698.16 | 17-OCT-02:61 | 17.00 | 9.05 | 0.522226E+10 | 4681.01 | 14-OCT-18:30 | 17.00 | 9.05 |
November | 0.488528E+10 | 9310.81 | 19-NOV-13:00 | 27.00 | 14.96 | 0.466698E+10 | 4413.60 | 10-NOV-12:39 | 27.00 | 14.96 |
December | 0.469697E+10 | 10953.36 | 19-DEC-13:00 | 26.00 | 11.60 | 0.478815E+10 | 4413.55 | 07-DEC-12:39 | 26.00 | 11.60 |
Annual Sum or Average | 0.718646E+11 | 0.588873E+11 | ||||||||
Minimum of Months | 0.330446E+10 | 6676.69 | 16.42 | 9.05 | 0.422871E+10 | 4413.14 | 16.42 | 9.05 | ||
Maximum of Months | 0.910487E+10 | 29087.08 | 27.00 | 17.13 | 0.537784E+10 | 4681.32 | 27.00 | 18.37 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224349E+11 | 47961.14 | 16-JAN-03:01 | 11.17 | 4.13 | 0.780190E+10 | 5135.97 | 25-JAN-11:00 | 18.00 | 12.88 |
February | 0.200354E+11 | 48408.64 | 07-FEB-05:01 | 12.00 | 3.24 | 0.704846E+10 | 5135.97 | 16-FEB-11:00 | 17.50 | 13.81 |
March | 0.224337E+11 | 43469.24 | 12-MAR-02:61 | 8.83 | 6.48 | 0.779849E+10 | 5135.96 | 09-MAR-11:00 | 8.83 | 6.48 |
April | 0.217482E+11 | 43705.51 | 02-APR-02:61 | 10.58 | 5.70 | 0.757812E+10 | 5135.96 | 21-APR-10:00 | 18.00 | 12.36 |
May | 0.226155E+11 | 41657.53 | 27-MAY-02:61 | 8.83 | 7.77 | 0.783811E+10 | 5135.97 | 25-MAY-10:00 | 8.83 | 7.77 |
June | 0.221112E+11 | 35838.89 | 13-JUN-02:11 | 12.67 | 11.55 | 0.760152E+10 | 5135.97 | 08-JUN-10:00 | 12.67 | 11.55 |
July | 0.235209E+11 | 34731.34 | 06-JUL-02:61 | 13.00 | 12.44 | 0.785522E+10 | 5135.95 | 10-JUL-10:39 | 21.67 | 16.08 |
August | 0.235443E+11 | 32050.38 | 22-AUG-02:61 | 16.00 | 14.04 | 0.786084E+10 | 5135.95 | 28-AUG-10:20 | 21.33 | 16.81 |
September | 0.223898E+11 | 37262.18 | 20-SEP-02:61 | 11.83 | 10.73 | 0.760020E+10 | 5148.98 | 29-SEP-10:00 | 36.00 | 17.91 |
October | 0.230806E+11 | 49263.21 | 27-OCT-04:01 | 9.00 | 3.53 | 0.784993E+10 | 5156.54 | 16-OCT-10:00 | 9.00 | 3.53 |
November | 0.217981E+11 | 45561.51 | 29-NOV-03:01 | 13.17 | 4.07 | 0.756884E+10 | 5135.98 | 14-NOV-11:00 | 13.17 | 4.07 |
December | 0.224074E+11 | 49957.60 | 26-DEC-05:01 | 9.50 | 2.09 | 0.780449E+10 | 5135.95 | 07-DEC-11:00 | 9.50 | 2.09 |
Annual Sum or Average | 0.268120E+12 | 0.922061E+11 | ||||||||
Minimum of Months | 0.200354E+11 | 32050.38 | 8.83 | 2.09 | 0.704846E+10 | 5135.95 | 8.83 | 2.09 | ||
Maximum of Months | 0.235443E+11 | 49957.60 | 16.00 | 14.04 | 0.786084E+10 | 5156.54 | 36.00 | 17.91 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 8.83 | 8.36 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 | 11.35 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 7.63 | 6.62 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.62 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9.63 | 8.61 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 15.20 | 14.50 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 | 12.03 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 | 15.81 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.07 | 17.20 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 | 14.83 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.83 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 | 17.39 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 | 11.07 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.07 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 10.63 | 5.44 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.44 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.63 | 5.44 | 0.00 | 0.00 | 7.63 | 5.44 | ||
Maximum of Months | 0.00 | 0.00 | 18.42 | 17.39 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.918930E+09 | 8815.75 | 08-JAN-07:10 | 1.83 |
February | 0.505479E+09 | 5523.36 | 08-FEB-06:04 | 8.83 |
March | 0.102552E+10 | 7002.90 | 29-MAR-19:55 | 6.60 |
April | 70763250.72 | 4997.17 | 01-APR-06:10 | 7.67 |
May | 30770565.41 | 3877.96 | 14-MAY-22:05 | 11.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.07 |
September | 221118.81 | 659.38 | 29-SEP-23:01 | 24.38 |
October | 9800248.50 | 3473.15 | 12-OCT-06:35 | 11.67 |
November | 0.128775E+09 | 4766.52 | 05-NOV-06:10 | 7.17 |
December | 0.685868E+09 | 6662.64 | 28-DEC-06:33 | 7.33 |
Annual Sum or Average | 0.337613E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.83 | |
Maximum of Months | 0.102552E+10 | 8815.75 | 24.38 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.754217E+09 | 715.88 | 02-JAN-16:49 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.646687E+09 | 715.88 | 01-FEB-17:19 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.687757E+09 | 715.88 | 01-MAR-17:30 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.603126E+09 | 715.88 | 01-APR-17:30 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.588643E+09 | 715.88 | 01-MAY-18:19 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.569009E+09 | 715.88 | 01-JUN-18:30 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.581754E+09 | 715.88 | 01-JUL-18:40 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.610657E+09 | 715.88 | 01-AUG-18:30 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.638149E+09 | 715.88 | 01-SEP-17:30 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.687051E+09 | 715.88 | 02-OCT-17:19 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.724174E+09 | 715.88 | 01-NOV-16:40 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.762310E+09 | 715.88 | 01-DEC-16:19 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.785353E+10 | 0.703313E+11 | ||||
Minimum of Months | 0.569009E+09 | 715.88 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.762310E+09 | 715.88 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.179920E+10 | 1053.27 | 02-JAN-10:09 | 0.166069E+11 | 10143.54 | 01-JAN-11:09 |
February | 0.162962E+10 | 1053.27 | 01-FEB-10:09 | 0.149998E+11 | 10143.54 | 01-FEB-11:09 |
March | 0.182785E+10 | 1053.27 | 01-MAR-10:09 | 0.166070E+11 | 10143.54 | 01-MAR-11:09 |
April | 0.174822E+10 | 1053.27 | 01-APR-16:10 | 0.160712E+11 | 10143.54 | 01-APR-10:09 |
May | 0.181352E+10 | 1053.27 | 01-MAY-09:09 | 0.166070E+11 | 10143.54 | 01-MAY-10:09 |
June | 0.176676E+10 | 1053.27 | 01-JUN-09:09 | 0.160713E+11 | 10143.54 | 01-JUN-10:09 |
July | 0.179520E+10 | 1053.27 | 01-JUL-16:10 | 0.166069E+11 | 10143.54 | 01-JUL-10:09 |
August | 0.182785E+10 | 1053.27 | 01-AUG-09:09 | 0.166070E+11 | 10143.54 | 01-AUG-10:09 |
September | 0.174864E+10 | 1053.27 | 01-SEP-09:09 | 0.160712E+11 | 10143.54 | 01-SEP-10:09 |
October | 0.179899E+10 | 1053.27 | 02-OCT-09:09 | 0.166069E+11 | 10143.54 | 01-OCT-10:09 |
November | 0.174169E+10 | 1053.27 | 01-NOV-09:09 | 0.160712E+11 | 10143.54 | 01-NOV-10:09 |
December | 0.179541E+10 | 1053.27 | 01-DEC-10:09 | 0.166069E+11 | 10143.54 | 01-DEC-11:09 |
Annual Sum or Average | 0.212929E+11 | 0.195533E+12 | ||||
Minimum of Months | 0.162962E+10 | 1053.27 | 0.149998E+11 | 10143.54 | ||
Maximum of Months | 0.182785E+10 | 1053.27 | 0.166070E+11 | 10143.54 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.754217E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29780374.89 | 0.845631E+10 |
February | 0.852256E+10 | 0.646687E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4992262.61 | 0.763767E+10 |
March | 0.954557E+10 | 0.687757E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 684187.89 | 0.895746E+10 |
April | 0.915225E+10 | 0.603126E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29542693.96 | 0.645739E+10 |
May | 0.947560E+10 | 0.588643E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 425790.45 | 0.643845E+10 |
June | 0.922788E+10 | 0.569009E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5265383.49 | 0.479754E+10 |
July | 0.939996E+10 | 0.581754E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165277E+09 | 0.359833E+10 |
August | 0.954557E+10 | 0.610657E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188751E+09 | 0.353371E+10 |
September | 0.915225E+10 | 0.638149E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334523E+09 | 0.461684E+10 |
October | 0.940563E+10 | 0.687051E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617049E+09 | 0.430997E+10 |
November | 0.909363E+10 | 0.724174E+09 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29625836.84 | 0.722979E+10 |
December | 0.939996E+10 | 0.762310E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24055968.44 | 0.805934E+10 |
Annual Sum or Average | 0.111326E+12 | 0.785353E+10 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142997E+10 | 0.740928E+11 |
Minimum of Months | 0.852256E+10 | 0.569009E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 425790.45 | 0.353371E+10 |
Maximum of Months | 0.954557E+10 | 0.762310E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617049E+09 | 0.895746E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.179920E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98601400.99 |
February | 0.610713E+09 | 0.162962E+10 | 0.112456E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111988E+09 |
March | 0.684021E+09 | 0.182785E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120499E+09 |
April | 0.655836E+09 | 0.174822E+10 | 0.120488E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 9450.48 | 76163278.42 |
May | 0.679007E+09 | 0.181352E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92069534.21 |
June | 0.661256E+09 | 0.176676E+10 | 0.120489E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50632399.96 |
July | 0.673587E+09 | 0.179520E+10 | 0.124504E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 181368.64 | 35634787.87 |
August | 0.684021E+09 | 0.182785E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 132226.27 | 50206566.81 |
September | 0.655836E+09 | 0.174864E+10 | 0.120488E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 1052117.28 | 46798298.22 |
October | 0.673993E+09 | 0.179899E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 2556359.64 | 74146483.98 |
November | 0.651635E+09 | 0.174169E+10 | 0.120489E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 7368.32 | 97773022.22 |
December | 0.673587E+09 | 0.179541E+10 | 0.124504E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104812E+09 |
Annual Sum or Average | 0.797748E+10 | 0.212929E+11 | 0.146594E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 3938890.62 | 0.959325E+09 |
Minimum of Months | 0.610713E+09 | 0.162962E+10 | 0.112456E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35634787.87 |
Maximum of Months | 0.684021E+09 | 0.182785E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 2556359.64 | 0.120499E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469155E+09 | 0.995795E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314805E+09 | 0.101466E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288156E+09 | 0.148840E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281907E+09 | 0.199480E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253141E+09 | 0.203849E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189550E+09 | 0.208288E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239793E+09 | 0.231772E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253504E+09 | 0.212850E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315734E+09 | 0.163780E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395666E+09 | 0.118523E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424047E+09 | 0.101680E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512241E+09 | 0.896543E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393770E+10 | 0.187976E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189550E+09 | 0.896543E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512241E+09 | 0.231772E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 715.88 | 02-JAN-16:49 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1856.73 | 18-JAN-12:55 | 14299.28 | 02-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 715.88 | 01-FEB-17:19 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1560.26 | 01-FEB-12:05 | 11272.06 | 21-FEB-21:00 |
March | 9454.80 | 04-MAR-19:10 | 715.88 | 01-MAR-17:30 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.47 | 11-MAR-13:25 | 13545.88 | 29-MAR-19:55 |
April | 9454.80 | 01-APR-18:10 | 715.88 | 01-APR-17:30 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2426.32 | 26-APR-13:00 | 9248.30 | 15-APR-18:52 |
May | 9454.80 | 06-MAY-18:10 | 715.88 | 01-MAY-18:19 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 96.62 | 03-MAY-12:00 | 9338.86 | 10-MAY-19:53 |
June | 9454.80 | 03-JUN-18:10 | 715.88 | 01-JUN-18:30 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 830.87 | 29-JUN-11:05 | 6950.55 | 06-JUN-18:52 |
July | 9454.80 | 01-JUL-18:10 | 715.88 | 01-JUL-18:40 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3584.81 | 19-JUL-12:00 | 6542.16 | 15-JUL-18:52 |
August | 9454.80 | 05-AUG-18:10 | 715.88 | 01-AUG-18:30 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3588.66 | 18-AUG-12:00 | 6486.88 | 26-AUG-18:02 |
September | 9454.80 | 02-SEP-18:10 | 715.88 | 01-SEP-17:30 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10262.42 | 29-SEP-11:05 | 7138.83 | 02-SEP-18:53 |
October | 9454.80 | 07-OCT-18:10 | 715.88 | 02-OCT-17:19 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10980.20 | 16-OCT-11:10 | 7618.21 | 07-OCT-18:53 |
November | 9454.80 | 04-NOV-18:10 | 715.88 | 01-NOV-16:40 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1833.34 | 19-NOV-13:00 | 10918.45 | 04-NOV-20:00 |
December | 9454.80 | 02-DEC-19:10 | 715.88 | 01-DEC-16:19 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.88 | 19-DEC-13:00 | 13244.68 | 28-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 715.88 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 65.47 | 6486.88 | |||||
Maximum of Months | 9454.80 | 715.88 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 10980.20 | 14299.28 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 1053.27 | 02-JAN-10:09 | 7408.73 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 440.80 | 02-JAN-03:00 |
February | 677.52 | 04-FEB-19:10 | 1053.27 | 01-FEB-10:09 | 7408.73 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 464.51 | 25-FEB-03:00 |
March | 677.52 | 04-MAR-19:10 | 1053.27 | 01-MAR-10:09 | 7408.73 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 379.64 | 29-MAR-02:00 |
April | 677.52 | 01-APR-18:10 | 1053.27 | 01-APR-16:10 | 7408.73 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 3.03 | 26-APR-13:00 | 264.06 | 17-APR-03:20 |
May | 677.52 | 06-MAY-18:10 | 1053.27 | 01-MAY-09:09 | 7408.73 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 291.25 | 26-MAY-03:50 |
June | 677.52 | 03-JUN-18:10 | 1053.27 | 01-JUN-09:09 | 7408.73 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 205.68 | 07-JUN-01:00 |
July | 677.52 | 01-JUL-18:10 | 1053.27 | 01-JUL-16:10 | 7408.73 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 7.98 | 31-JUL-13:00 | 150.10 | 21-JUL-01:30 |
August | 677.52 | 05-AUG-18:10 | 1053.27 | 01-AUG-09:09 | 7408.73 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 6.42 | 17-AUG-14:00 | 129.05 | 29-AUG-03:30 |
September | 677.52 | 02-SEP-18:10 | 1053.27 | 01-SEP-09:09 | 7408.73 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 32.96 | 29-SEP-13:30 | 180.85 | 02-SEP-02:10 |
October | 677.52 | 07-OCT-18:10 | 1053.27 | 02-OCT-09:09 | 7408.73 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 49.54 | 16-OCT-10:23 | 378.50 | 11-OCT-02:00 |
November | 677.52 | 04-NOV-18:10 | 1053.27 | 01-NOV-09:09 | 7408.73 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 3.03 | 19-NOV-13:00 | 411.26 | 23-NOV-04:20 |
December | 677.52 | 02-DEC-19:10 | 1053.27 | 01-DEC-10:09 | 7408.73 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 344.88 | 13-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 1053.27 | 7408.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 129.05 | ||||||
Maximum of Months | 677.52 | 1053.27 | 7408.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 49.54 | 464.51 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 755.65 | 06-JAN-04:00 | 1880.83 | 30-JAN-11:50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 686.20 | 01-FEB-03:01 | 2097.07 | 18-FEB-12:50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.20 | 07-MAR-06:00 | 2560.78 | 15-MAR-12:20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.51 | 16-APR-00:55 | 2688.66 | 23-APR-12:30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561.53 | 16-MAY-24:00 | 2821.10 | 31-MAY-12:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.97 | 18-JUN-01:35 | 2712.43 | 01-JUN-12:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.48 | 14-JUL-05:25 | 2673.22 | 03-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 566.24 | 24-AUG-03:51 | 2532.94 | 11-AUG-13:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.26 | 29-SEP-22:50 | 2382.44 | 07-SEP-13:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 802.36 | 16-OCT-06:52 | 2154.12 | 18-OCT-12:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 732.58 | 27-NOV-06:53 | 1917.47 | 04-NOV-11:40 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 753.75 | 26-DEC-05:00 | 1773.28 | 02-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.48 | 1773.28 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 802.36 | 2821.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10525.20 | 18-JAN-12:55 | 16808.53 | 343.62 | 7318.41 | 0.00 | 0.00 | 0.00 | 0.00 | 1856.73 | 0.00 |
February | 8993.69 | 01-FEB-12:05 | 16808.53 | 343.62 | 7318.41 | 0.00 | 0.00 | 0.00 | 0.00 | 1560.26 | 0.00 |
March | 6676.69 | 10-MAR-13:00 | 8404.27 | 171.81 | 3659.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 791.29 |
April | 10233.28 | 26-APR-13:00 | 7353.73 | 171.81 | 3388.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2426.32 | 0.00 |
May | 8002.12 | 04-MAY-12:00 | 8404.27 | 171.81 | 3659.20 | 0.00 | 0.00 | 0.00 | 0.00 | 95.98 | 0.00 |
June | 16625.54 | 30-JUN-02:61 | 0.00 | 1193.14 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 19711.19 | 11-JUL-02:61 | 0.00 | 1193.14 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.38 |
August | 17132.28 | 26-AUG-02:61 | 0.00 | 1193.14 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.63 |
September | 29087.08 | 30-SEP-02:61 | 0.00 | 1193.14 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
October | 27698.16 | 17-OCT-02:61 | 0.00 | 1193.14 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.89 |
November | 9310.81 | 19-NOV-13:00 | 5252.67 | 133.63 | 3659.20 | 0.00 | 0.00 | 0.00 | 0.00 | 1833.34 | 0.00 |
December | 10953.36 | 19-DEC-13:00 | 8404.27 | 171.81 | 3659.20 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6676.69 | 0.00 | 133.63 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29087.08 | 16808.53 | 1193.14 | 7318.41 | 0.00 | 0.00 | 0.00 | 0.00 | 2426.32 | 791.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 47961.14 | 16-JAN-03:01 | 0.00 | 1755.47 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 86.54 |
February | 48408.64 | 07-FEB-05:01 | 376.40 | 2340.68 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 72.68 |
March | 43469.24 | 12-MAR-02:61 | 0.00 | 1755.47 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 124.89 |
April | 43705.51 | 02-APR-02:61 | 0.00 | 1755.47 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 200.98 |
May | 41657.53 | 27-MAY-02:61 | 0.00 | 1755.47 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 134.21 |
June | 35838.89 | 13-JUN-02:11 | 0.00 | 1755.47 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 138.41 |
July | 34731.34 | 06-JUL-02:61 | 0.00 | 1755.47 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32050.38 | 22-AUG-02:61 | 0.00 | 1755.47 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 65.26 |
September | 37262.18 | 20-SEP-02:61 | 0.00 | 1755.47 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 83.46 |
October | 49263.21 | 27-OCT-04:01 | 376.40 | 2340.68 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 50.53 |
November | 45561.51 | 29-NOV-03:01 | 0.00 | 1755.47 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 169.20 |
December | 49957.60 | 26-DEC-05:01 | 376.40 | 2340.68 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 32050.38 | 0.00 | 1755.47 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49957.60 | 376.40 | 2340.68 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 200.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.84 | 0.00 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.32 | 0.00 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.79 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.24 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.47 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.48 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.73 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.50 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.85 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.79 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.25 | 0.00 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.32 | 25.24 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.377835E+11 | 25939.71 | 14-JAN-11:20 | 0.638310E+11 | 51397.96 | 01-JAN-13:30 |
February | 0.334500E+11 | 25426.68 | 01-FEB-11:20 | 0.567714E+11 | 54120.73 | 25-FEB-13:39 |
March | 0.369591E+11 | 25049.99 | 11-MAR-11:20 | 0.645091E+11 | 59171.92 | 29-MAR-10:20 |
April | 0.367049E+11 | 27491.16 | 26-APR-10:00 | 0.574358E+11 | 48405.86 | 01-APR-12:20 |
May | 0.376410E+11 | 25637.18 | 03-MAY-10:20 | 0.583871E+11 | 48125.46 | 01-MAY-12:39 |
June | 0.382910E+11 | 28303.71 | 29-JUN-10:00 | 0.547317E+11 | 47810.98 | 01-JUN-12:20 |
July | 0.425977E+11 | 30502.95 | 31-JUL-11:09 | 0.561363E+11 | 47569.85 | 01-JUL-12:39 |
August | 0.434027E+11 | 31264.94 | 14-AUG-11:09 | 0.561610E+11 | 47533.44 | 31-AUG-12:00 |
September | 0.398526E+11 | 35523.39 | 29-SEP-11:20 | 0.545483E+11 | 47751.18 | 30-SEP-12:50 |
October | 0.419508E+11 | 36411.65 | 16-OCT-11:09 | 0.570474E+11 | 48056.52 | 31-OCT-12:00 |
November | 0.366049E+11 | 26155.67 | 19-NOV-11:20 | 0.580645E+11 | 48348.08 | 30-NOV-13:39 |
December | 0.379175E+11 | 26374.75 | 19-DEC-11:20 | 0.627848E+11 | 50461.33 | 12-DEC-13:20 |
Annual Sum or Average | 0.463156E+12 | 0.700408E+12 | ||||
Minimum of Months | 0.334500E+11 | 25049.99 | 0.545483E+11 | 47533.44 | ||
Maximum of Months | 0.434027E+11 | 36411.65 | 0.645091E+11 | 59171.92 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.255342E+10 | 0.273461E+10 | 0.225803E+11 | 0.00 | 0.437521E+10 | 0.79 | 0.00 | 0.103087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227631E+10 | 0.231679E+10 | 0.203951E+11 | 0.00 | 0.392904E+10 | 0.72 | 0.00 | 0.439168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251560E+10 | 0.234288E+10 | 0.225804E+11 | 0.00 | 0.437745E+10 | 0.80 | 0.00 | 0.627234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.235135E+10 | 0.204937E+10 | 0.218518E+11 | 0.00 | 0.417250E+10 | 0.77 | 0.00 | 0.178439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240217E+10 | 0.193980E+10 | 0.225803E+11 | 0.00 | 0.430999E+10 | 0.80 | 0.00 | 0.173930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.233577E+10 | 0.179408E+10 | 0.218520E+11 | 0.00 | 0.421309E+10 | 0.77 | 0.00 | 0.349727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.237695E+10 | 0.188074E+10 | 0.225802E+11 | 0.00 | 0.448162E+10 | 0.79 | 0.00 | 0.649342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.243850E+10 | 0.203072E+10 | 0.225804E+11 | 0.00 | 0.451065E+10 | 0.80 | 0.00 | 0.703667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.238679E+10 | 0.217423E+10 | 0.218518E+11 | 0.00 | 0.427955E+10 | 0.77 | 0.00 | 0.454504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.248604E+10 | 0.247264E+10 | 0.225803E+11 | 0.00 | 0.443963E+10 | 0.79 | 0.00 | 0.525060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.246586E+10 | 0.259044E+10 | 0.218519E+11 | 0.00 | 0.418239E+10 | 0.77 | 0.00 | 0.107597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.255772E+10 | 0.278847E+10 | 0.225802E+11 | 0.00 | 0.435981E+10 | 0.79 | 0.00 | 0.112305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.291465E+11 | 0.271148E+11 | 0.265865E+12 | 0.00 | 0.516309E+11 | 9.37 | 0.00 | 0.346430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.227631E+10 | 0.179408E+10 | 0.203951E+11 | 0.00 | 0.392904E+10 | 0.72 | 0.00 | 0.439168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.255772E+10 | 0.278847E+10 | 0.225804E+11 | 0.00 | 0.451065E+10 | 0.80 | 0.00 | 0.703667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.633150E+10 | 0.00 | 0.169738E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.482381E+10 | 0.00 | 0.153437E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.711354E+10 | 0.00 | 0.168699E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.223782E+10 | 0.00 | 0.159795E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.168921E+10 | 0.00 | 0.161722E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.177339E+09 | 0.00 | 0.153359E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.156106E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 3788938.39 | 0.00 | 0.156315E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 75298605.33 | 0.00 | 0.152545E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.454150E+09 | 0.00 | 0.160675E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.291837E+10 | 0.00 | 0.159277E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.549399E+10 | 0.00 | 0.167650E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.313188E+11 | 0.00 | 0.191932E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.00 | 0.00 | 0.152545E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.711354E+10 | 0.00 | 0.169738E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1769.15 | 02-JAN-16:49 | 2040.24 | 01-JAN-00:10 | 14073.79 | 01-JAN-11:09 | 0.00 | 2385.69 | 08-JAN-07:10 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 1769.15 | 01-FEB-17:19 | 2040.24 | 01-FEB-00:10 | 14073.79 | 01-FEB-11:09 | 0.00 | 2110.77 | 05-FEB-07:10 | 0.00 | 11-FEB-16:10 | 0.00 | 01-FEB-00:10 |
March | 1769.15 | 01-MAR-17:30 | 2040.24 | 01-MAR-00:10 | 14073.79 | 01-MAR-11:09 | 0.00 | 2216.63 | 30-MAR-06:10 | 0.00 | 22-MAR-08:09 | 0.00 | 01-MAR-00:10 |
April | 1769.15 | 01-APR-17:30 | 2040.24 | 01-APR-05:10 | 14073.79 | 01-APR-10:09 | 0.00 | 2149.63 | 26-APR-10:00 | 0.00 | 05-APR-17:40 | 0.00 | 01-APR-00:10 |
May | 1769.15 | 01-MAY-18:19 | 2040.24 | 01-MAY-18:30 | 14073.79 | 01-MAY-10:09 | 0.00 | 1999.53 | 14-MAY-06:10 | 0.00 | 06-MAY-08:00 | 0.00 | 01-MAY-00:10 |
June | 1769.15 | 01-JUN-18:30 | 2040.24 | 01-JUN-18:49 | 14073.79 | 01-JUN-10:09 | 0.00 | 2305.59 | 29-JUN-10:00 | 0.00 | 15-JUN-08:30 | 0.00 | 01-JUN-00:10 |
July | 1769.15 | 01-JUL-18:40 | 2040.24 | 01-JUL-18:00 | 14073.79 | 01-JUL-10:09 | 0.00 | 2721.74 | 19-JUL-11:09 | 0.00 | 15-JUL-14:39 | 0.00 | 01-JUL-00:10 |
August | 1769.15 | 01-AUG-18:30 | 2040.24 | 01-AUG-18:49 | 14073.79 | 01-AUG-10:09 | 0.00 | 2883.37 | 14-AUG-11:09 | 0.00 | 05-AUG-14:39 | 0.00 | 01-AUG-00:10 |
September | 1769.15 | 01-SEP-17:30 | 2040.24 | 01-SEP-05:10 | 14073.79 | 01-SEP-10:09 | 0.00 | 3489.31 | 29-SEP-11:20 | 0.00 | 05-SEP-10:20 | 0.00 | 01-SEP-00:10 |
October | 1769.15 | 02-OCT-17:19 | 2040.24 | 01-OCT-05:10 | 14073.79 | 01-OCT-10:09 | 0.00 | 3613.26 | 16-OCT-11:09 | 0.00 | 10-OCT-08:30 | 0.00 | 01-OCT-00:10 |
November | 1769.15 | 01-NOV-16:40 | 2040.24 | 01-NOV-05:10 | 14073.79 | 01-NOV-10:09 | 0.00 | 2111.95 | 05-NOV-06:10 | 0.00 | 01-NOV-10:09 | 0.00 | 01-NOV-00:10 |
December | 1769.15 | 01-DEC-16:19 | 2040.24 | 01-DEC-00:10 | 14073.79 | 01-DEC-11:09 | 0.00 | 2158.81 | 23-DEC-07:10 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1769.15 | 2040.24 | 14073.79 | 0.00 | 1999.53 | 0.00 | 0.00 | ||||||
Maximum of Months | 1769.15 | 2040.24 | 14073.79 | 0.00 | 3613.26 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 6013.16 | 17-JAN-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5918.46 | 01-FEB-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5064.84 | 23-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7892.49 | 26-APR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5858.01 | 04-MAY-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8534.13 | 29-JUN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10817.37 | 31-JUL-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11417.48 | 14-AUG-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15057.78 | 29-SEP-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15794.29 | 16-OCT-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6147.61 | 19-NOV-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6128.67 | 19-DEC-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5064.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15794.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 25939.71 | 14-JAN-11:20 | 1088.96 | 14073.79 | 0.00 | 0.00 | 1855.35 | 0.00 | 0.00 | 4632.17 | 0.00 |
February | 25426.68 | 01-FEB-11:20 | 1225.08 | 14073.79 | 0.00 | 0.00 | 1855.35 | 0.00 | 0.00 | 3951.33 | 0.00 |
March | 25049.99 | 11-MAR-11:20 | 1088.96 | 14073.79 | 0.00 | 0.00 | 1855.35 | 0.00 | 0.00 | 3721.81 | 0.00 |
April | 27491.16 | 26-APR-10:00 | 1225.08 | 14073.79 | 0.00 | 0.00 | 2149.63 | 0.00 | 0.00 | 7486.85 | 0.00 |
May | 25637.18 | 03-MAY-10:20 | 1225.08 | 14073.79 | 0.00 | 0.00 | 1855.35 | 0.00 | 0.00 | 4148.31 | 0.00 |
June | 28303.71 | 29-JUN-10:00 | 1225.08 | 14073.79 | 0.00 | 0.00 | 2305.59 | 0.00 | 0.00 | 8139.07 | 0.00 |
July | 30502.95 | 31-JUL-11:09 | 1225.08 | 13174.05 | 0.00 | 0.00 | 2721.17 | 0.00 | 0.00 | 10817.37 | 0.00 |
August | 31264.94 | 14-AUG-11:09 | 1225.08 | 13174.05 | 0.00 | 0.00 | 2883.37 | 0.00 | 0.00 | 11417.48 | 0.00 |
September | 35523.39 | 29-SEP-11:20 | 1225.08 | 13174.05 | 0.00 | 0.00 | 3489.31 | 0.00 | 0.00 | 15057.78 | 0.00 |
October | 36411.65 | 16-OCT-11:09 | 1225.08 | 13174.05 | 0.00 | 0.00 | 3613.26 | 0.00 | 0.00 | 15794.29 | 0.00 |
November | 26155.67 | 19-NOV-11:20 | 952.85 | 14073.79 | 0.00 | 0.00 | 1855.35 | 0.00 | 0.00 | 4971.03 | 0.00 |
December | 26374.75 | 19-DEC-11:20 | 1225.08 | 14073.79 | 0.00 | 0.00 | 1855.35 | 0.00 | 0.00 | 4920.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 25049.99 | 952.85 | 13174.05 | 0.00 | 0.00 | 1855.35 | 0.00 | 0.00 | 3721.81 | 0.00 | |
Maximum of Months | 36411.65 | 1225.08 | 14073.79 | 0.00 | 0.00 | 3613.26 | 0.00 | 0.00 | 15794.29 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 31404.53 | 08-JAN-07:10 | 0.00 | 25677.84 | 29-JAN-13:20 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 13620.84 | 05-FEB-07:10 | 0.00 | 25680.40 | 01-FEB-13:00 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 21010.21 | 30-MAR-06:10 | 0.00 | 25618.17 | 01-MAR-13:50 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 14699.84 | 01-APR-06:10 | 0.00 | 25422.71 | 01-APR-12:20 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 7579.03 | 14-MAY-06:10 | 0.00 | 25142.31 | 01-MAY-12:39 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 3557.48 | 13-JUN-05:10 | 0.00 | 24827.83 | 01-JUN-12:20 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 24586.70 | 01-JUL-12:39 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 1069.88 | 28-AUG-06:30 | 0.00 | 24550.29 | 31-AUG-12:00 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 4394.56 | 20-SEP-06:10 | 0.00 | 24768.03 | 30-SEP-12:50 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 8796.21 | 29-OCT-06:10 | 0.00 | 25073.37 | 31-OCT-12:00 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 13576.91 | 05-NOV-06:10 | 0.00 | 25364.93 | 30-NOV-13:39 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 16806.62 | 23-DEC-07:10 | 0.00 | 25586.77 | 31-DEC-13:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 0.00 | 0.00 | 24550.29 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 31404.53 | 0.00 | 25680.40 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.52 | 0.00 | 24.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.00 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.49 | 0.00 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.47 | 0.00 | 24.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.58 | 0.00 | 24.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.56 | 0.00 | 24.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.00 | 24.54 | 0.00 | 24.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.58 | 0.00 | 24.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 28.10 | 0.00 | 28.10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 28.00 | 0.00 | 28.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.94 | 0.00 | 27.94 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 28.52 | 0.00 | 28.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 28.85 | 0.00 | 28.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 29.58 | 0.00 | 29.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 29.90 | 0.00 | 29.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 29.98 | 0.00 | 29.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 29.70 | 0.67 | 29.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 29.57 | 0.83 | 29.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 28.49 | 0.00 | 28.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 28.09 | 0.00 | 28.09 |
Annual Sum or Average | 0.00 | 0.00 | 234.50 | 29.07 | 1.50 | 29.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.94 | 0.00 | 27.94 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 29.98 | 0.83 | 29.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 460.00 | 21.39 | 82.50 | 21.62 | 13.50 | 21.54 |
February | 471.33 | 21.34 | 44.50 | 21.45 | 13.17 | 21.42 |
March | 521.33 | 21.21 | 76.50 | 21.43 | 12.00 | 21.36 |
April | 361.33 | 21.39 | 167.33 | 22.15 | 0.00 | 22.15 |
May | 369.83 | 21.52 | 179.00 | 22.26 | 0.67 | 22.27 |
June | 258.67 | 22.04 | 309.50 | 22.95 | 34.17 | 22.97 |
July | 313.17 | 23.26 | 498.17 | 23.53 | 231.17 | 23.55 |
August | 359.00 | 23.39 | 530.00 | 23.57 | 304.33 | 23.58 |
September | 273.50 | 22.59 | 385.83 | 23.24 | 109.33 | 23.27 |
October | 286.17 | 22.66 | 349.67 | 23.30 | 107.17 | 23.39 |
November | 418.67 | 21.47 | 93.17 | 21.84 | 4.33 | 21.82 |
December | 474.00 | 21.47 | 38.33 | 21.52 | 13.17 | 21.45 |
Annual Sum or Average | 4567.00 | 21.86 | 2754.50 | 22.53 | 843.00 | 22.61 |
Minimum of Months | 258.67 | 21.21 | 38.33 | 21.43 | 0.00 | 21.36 |
Maximum of Months | 521.33 | 23.39 | 530.00 | 23.57 | 304.33 | 23.58 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 344.33 | 23.19 | 410.33 | 24.09 | 186.00 | 24.40 |
February | 278.17 | 23.48 | 375.33 | 24.20 | 149.17 | 24.51 |
March | 333.67 | 22.94 | 391.50 | 23.82 | 160.17 | 24.14 |
April | 358.00 | 25.33 | 507.83 | 25.19 | 311.33 | 25.39 |
May | 387.67 | 25.56 | 549.67 | 25.37 | 354.83 | 25.53 |
June | 446.00 | 26.01 | 589.67 | 25.76 | 446.00 | 25.83 |
July | 548.83 | 26.01 | 609.00 | 25.94 | 548.83 | 25.96 |
August | 568.17 | 26.00 | 612.00 | 25.95 | 568.17 | 25.97 |
September | 470.17 | 26.02 | 587.50 | 25.85 | 470.17 | 25.90 |
October | 474.33 | 25.91 | 577.33 | 25.84 | 457.00 | 25.91 |
November | 342.33 | 24.57 | 460.50 | 24.88 | 248.17 | 25.12 |
December | 334.33 | 23.37 | 410.17 | 24.25 | 179.83 | 24.56 |
Annual Sum or Average | 4886.00 | 25.08 | 6080.83 | 25.23 | 4079.67 | 25.43 |
Minimum of Months | 278.17 | 22.94 | 375.33 | 23.82 | 149.17 | 24.14 |
Maximum of Months | 568.17 | 26.02 | 612.00 | 25.95 | 568.17 | 25.97 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 21.93384 | 43.01330 | -0.0065 | 7.05011 |
February | 551.00000 | 21.65377 | 46.80678 | -0.0646 | 6.51453 |
March | 612.00000 | 21.57106 | 50.57404 | -0.0692 | 6.87028 |
April | 590.00000 | 22.27894 | 53.11124 | 0.14403 | 7.35020 |
May | 611.00000 | 22.37449 | 52.40080 | -0.8532 | 23.49317 |
June | 592.00000 | 22.95009 | 57.71579 | -0.6091 | 15.22117 |
July | 609.00000 | 23.48228 | 62.56242 | -0.3619 | 8.96102 |
August | 612.00000 | 23.52069 | 64.49209 | -0.3244 | 8.37539 |
September | 590.00000 | 23.17775 | 59.38254 | -0.4789 | 12.03616 |
October | 610.00000 | 23.23030 | 48.91547 | 0.38552 | 9.74413 |
November | 591.00000 | 22.08781 | 44.35363 | 0.05766 | 6.86641 |
December | 609.00000 | 21.97239 | 37.68647 | -0.0253 | 6.77622 |
Annual Sum or Average | 7187.00000 | 22.52539 | 51.77516 | -0.1846 | 9.96377 |
Minimum of Months | 551.00000 | 21.57106 | 37.68647 | -0.8532 | 6.51453 |
Maximum of Months | 612.00000 | 23.52069 | 64.49209 | 0.38552 | 23.49317 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.49235 | 44.58311 | 0.57627 | 18.67887 |
February | 551.00000 | 23.59394 | 47.00699 | 0.61135 | 17.63885 |
March | 612.00000 | 23.22205 | 51.05839 | 0.55264 | 17.30381 |
April | 590.00000 | 24.62301 | 50.71307 | 0.89921 | 25.35646 |
May | 611.00000 | 24.87118 | 49.56550 | 0.26887 | 12.22502 |
June | 592.00000 | 25.55612 | 52.31908 | 0.53219 | 13.62738 |
July | 609.00000 | 25.88139 | 55.42879 | 0.69203 | 16.30232 |
August | 612.00000 | 25.90566 | 56.80452 | 0.70819 | 16.66887 |
September | 590.00000 | 25.70135 | 53.24691 | 0.59749 | 14.52916 |
October | 610.00000 | 25.57460 | 45.55721 | 1.11346 | 32.97471 |
November | 591.00000 | 24.30022 | 43.91890 | 0.77397 | 21.76866 |
December | 609.00000 | 23.65287 | 40.09421 | 0.58251 | 17.73139 |
Annual Sum or Average | 7187.00000 | 24.70321 | 49.20300 | 0.65886 | 18.73942 |
Minimum of Months | 551.00000 | 23.22205 | 40.09421 | 0.26887 | 12.22502 |
Maximum of Months | 612.00000 | 25.90566 | 56.80452 | 1.11346 | 32.97471 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.101740E+10 | 0.284326E+09 | 57.80 | 0.952652E+09 | 64744366.18 | 0.00 | 0.77 | 18-JAN-12:55 | 0.00 | 01-JAN-00:02 | 12372.26 | 18-JAN-12:55 | 12372.26 | 18-JAN-12:55 | 1980.99 | 17-JAN-14:00 | 3170.02 | 18-JAN-12:55 | 0.00 | 01-JAN-00:02 |
February | 0.217339E+09 | 61722542.72 | 16.21 | 0.215070E+09 | 2269207.19 | 0.00 | 0.68 | 01-FEB-12:05 | 0.00 | 01-FEB-00:05 | 10675.84 | 01-FEB-12:05 | 10675.84 | 01-FEB-12:05 | 807.67 | 01-FEB-13:30 | 2803.27 | 01-FEB-12:05 | 0.00 | 01-FEB-00:05 |
March | 0.446131E+09 | 0.127443E+09 | 31.55 | 0.383880E+09 | 62251402.52 | 0.00 | 0.50 | 11-MAR-14:00 | 0.00 | 01-MAR-00:02 | 7425.38 | 23-MAR-14:00 | 7391.02 | 11-MAR-14:00 | 2114.57 | 22-MAR-13:00 | 2038.74 | 11-MAR-14:00 | 0.00 | 01-MAR-00:02 |
April | 0.144648E+10 | 0.406648E+09 | 93.07 | 0.118777E+10 | 0.258713E+09 | 0.00 | 0.87 | 26-APR-11:13 | 0.00 | 01-APR-00:01 | 14581.10 | 26-APR-11:13 | 12580.41 | 26-APR-13:00 | 3153.43 | 26-APR-11:10 | 3585.26 | 26-APR-11:13 | 0.00 | 01-APR-00:01 |
May | 0.863650E+09 | 0.249490E+09 | 82.51 | 0.698377E+09 | 0.165273E+09 | 0.00 | 0.68 | 04-MAY-12:00 | 0.00 | 01-MAY-00:01 | 10606.39 | 04-MAY-12:00 | 8848.74 | 04-MAY-12:00 | 2748.74 | 05-MAY-03:24 | 2787.86 | 04-MAY-12:00 | 0.00 | 01-MAY-00:01 |
June | 0.321658E+10 | 0.888502E+09 | 182.39 | 0.228575E+10 | 0.930836E+09 | 0.00 | 1.00 | 20-JUN-02:61 | 0.00 | 01-JUN-00:01 | 34717.09 | 30-JUN-02:61 | 16774.07 | 30-JUN-02:61 | 17943.02 | 30-JUN-02:61 | 8249.69 | 30-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.821415E+10 | 0.214088E+10 | 298.25 | 0.535901E+10 | 0.285514E+10 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 | 35331.01 | 30-JUL-02:62 | 22532.02 | 04-JUL-02:61 | 18421.72 | 28-JUL-02:62 | 8290.63 | 30-JUL-02:62 | 0.00 | 01-JUL-00:01 |
August | 0.948584E+10 | 0.244093E+10 | 304.39 | 0.608121E+10 | 0.340463E+10 | 0.00 | 1.00 | 01-AUG-02:62 | 0.00 | 01-AUG-00:01 | 35646.02 | 19-AUG-02:62 | 18897.09 | 19-AUG-02:62 | 18451.96 | 15-AUG-02:62 | 8311.50 | 19-AUG-02:62 | 0.00 | 01-AUG-00:01 |
September | 0.497116E+10 | 0.134288E+10 | 215.41 | 0.377882E+10 | 0.119235E+10 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 | 36045.21 | 22-SEP-02:62 | 34289.04 | 30-SEP-02:42 | 19973.25 | 22-SEP-02:62 | 8337.95 | 22-SEP-02:62 | 0.00 | 01-SEP-00:01 |
October | 0.665820E+10 | 0.177471E+10 | 256.37 | 0.563966E+10 | 0.101854E+10 | 0.00 | 1.00 | 01-OCT-02:62 | 0.00 | 01-OCT-00:01 | 36131.89 | 05-OCT-02:41 | 34289.04 | 16-OCT-02:41 | 19560.08 | 01-OCT-03:21 | 8343.71 | 05-OCT-02:41 | 0.00 | 01-OCT-00:01 |
November | 0.871320E+09 | 0.243484E+09 | 51.86 | 0.851125E+09 | 20195296.98 | 0.00 | 0.73 | 19-NOV-13:00 | 0.00 | 01-NOV-00:01 | 11657.22 | 19-NOV-13:00 | 11657.22 | 19-NOV-13:00 | 1579.92 | 10-NOV-13:00 | 3017.62 | 19-NOV-13:00 | 0.00 | 01-NOV-00:01 |
December | 0.126560E+10 | 0.357424E+09 | 88.93 | 0.125551E+10 | 10087824.01 | 0.00 | 0.79 | 19-DEC-13:00 | 0.00 | 01-DEC-00:05 | 12794.26 | 19-DEC-13:00 | 12794.26 | 19-DEC-13:00 | 1108.13 | 07-DEC-13:55 | 3258.51 | 19-DEC-13:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.386738E+11 | 0.103184E+11 | 1678.73 | 0.286888E+11 | 0.998502E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.217339E+09 | 61722542.72 | 16.21 | 0.215070E+09 | 2269207.19 | 0.00 | 0.50 | 0.00 | 7425.38 | 7391.02 | 807.67 | 2038.74 | 0.00 | |||||||
Maximum of Months | 0.948584E+10 | 0.244093E+10 | 304.39 | 0.608121E+10 | 0.340463E+10 | 0.00 | 1.00 | 0.00 | 36131.89 | 34289.04 | 19973.25 | 8343.71 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.278568E+10 | 0.746547E+09 | 165.35 | 0.228542E+10 | 0.500260E+09 | 0.00 | 1.00 | 03-JAN-04:42 | 0.00 | 01-JAN-00:02 | 26730.61 | 14-JAN-04:22 | 26730.61 | 15-JAN-03:01 | 15191.11 | 26-JAN-03:01 | 6408.64 | 14-JAN-04:22 | 0.00 | 01-JAN-00:02 |
February | 0.136418E+10 | 0.377445E+09 | 106.15 | 0.103888E+10 | 0.325301E+09 | 0.00 | 1.00 | 01-FEB-03:01 | 0.00 | 01-FEB-00:05 | 26730.61 | 18-FEB-03:01 | 26730.61 | 07-FEB-05:01 | 14838.22 | 14-FEB-04:11 | 6408.64 | 01-FEB-03:01 | 0.00 | 01-FEB-00:05 |
March | 0.185508E+10 | 0.499791E+09 | 110.62 | 0.128598E+10 | 0.569105E+09 | 0.00 | 1.00 | 02-MAR-04:22 | 0.00 | 01-MAR-00:02 | 26730.61 | 12-MAR-02:61 | 18317.78 | 12-MAR-02:61 | 14802.36 | 24-MAR-02:61 | 6408.64 | 03-MAR-05:01 | 0.00 | 01-MAR-00:02 |
April | 0.521579E+10 | 0.137774E+10 | 244.27 | 0.372339E+10 | 0.149240E+10 | 0.00 | 1.00 | 02-APR-02:61 | 0.00 | 01-APR-00:01 | 26730.61 | 04-APR-04:01 | 23205.74 | 02-APR-03:22 | 14914.29 | 27-APR-02:61 | 6408.64 | 02-APR-03:22 | 0.00 | 01-APR-00:01 |
May | 0.559052E+10 | 0.148981E+10 | 277.69 | 0.392883E+10 | 0.166169E+10 | 0.00 | 1.00 | 01-MAY-02:11 | 0.00 | 01-MAY-00:01 | 26730.61 | 16-MAY-04:01 | 25487.90 | 24-MAY-03:22 | 14385.64 | 05-MAY-03:31 | 6408.64 | 01-MAY-02:11 | 0.00 | 01-MAY-00:01 |
June | 0.102483E+11 | 0.260877E+10 | 370.15 | 0.662754E+10 | 0.362081E+10 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 | 26730.61 | 16-JUN-02:11 | 16374.17 | 23-JUN-03:21 | 15926.88 | 28-JUN-02:11 | 6408.64 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.179015E+11 | 0.435253E+10 | 460.16 | 0.105696E+11 | 0.733186E+10 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 | 26960.06 | 23-JUL-02:11 | 18546.44 | 19-JUL-11:07 | 16584.34 | 24-JUL-02:11 | 6424.18 | 23-JUL-02:11 | 0.00 | 01-JUL-00:01 |
August | 0.190653E+11 | 0.459573E+10 | 467.81 | 0.109538E+11 | 0.811150E+10 | 0.00 | 1.00 | 01-AUG-02:11 | 0.00 | 01-AUG-00:01 | 27795.82 | 14-AUG-10:53 | 18678.51 | 14-AUG-10:57 | 17385.58 | 07-AUG-02:11 | 6451.62 | 07-AUG-02:11 | 0.00 | 01-AUG-00:01 |
September | 0.127052E+11 | 0.320217E+10 | 392.03 | 0.818798E+10 | 0.451719E+10 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 | 27375.90 | 22-SEP-02:11 | 27312.83 | 29-SEP-12:40 | 16412.03 | 22-SEP-02:11 | 7435.11 | 29-SEP-10:55 | 0.00 | 01-SEP-00:01 |
October | 0.137342E+11 | 0.347589E+10 | 435.73 | 0.100677E+11 | 0.366654E+10 | 0.00 | 1.00 | 01-OCT-02:11 | 0.00 | 01-OCT-00:01 | 27972.43 | 05-OCT-02:11 | 27220.34 | 16-OCT-11:00 | 17628.75 | 01-OCT-03:32 | 7607.63 | 16-OCT-10:53 | 0.00 | 01-OCT-00:01 |
November | 0.307896E+10 | 0.832490E+09 | 192.52 | 0.244489E+10 | 0.634070E+09 | 0.00 | 1.00 | 01-NOV-02:11 | 0.00 | 01-NOV-00:01 | 26730.61 | 14-NOV-05:01 | 26730.61 | 28-NOV-03:22 | 15721.32 | 12-NOV-03:52 | 6408.64 | 01-NOV-02:11 | 0.00 | 01-NOV-00:01 |
December | 0.282294E+10 | 0.765622E+09 | 172.43 | 0.263358E+10 | 0.189361E+09 | 0.00 | 1.00 | 01-DEC-03:01 | 0.00 | 01-DEC-00:05 | 26730.61 | 02-DEC-03:01 | 26730.61 | 19-DEC-04:02 | 13872.90 | 02-DEC-03:01 | 6408.64 | 01-DEC-03:01 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.963677E+11 | 0.243245E+11 | 3394.92 | 0.637476E+11 | 0.326201E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.136418E+10 | 0.377445E+09 | 106.15 | 0.103888E+10 | 0.189361E+09 | 0.00 | 1.00 | 0.00 | 26730.61 | 16374.17 | 13872.90 | 6408.64 | 0.00 | |||||||
Maximum of Months | 0.190653E+11 | 0.459573E+10 | 467.81 | 0.109538E+11 | 0.811150E+10 | 0.00 | 1.00 | 0.00 | 27972.43 | 27312.83 | 17628.75 | 7607.63 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.89 | 42.19 | 36.70 | 95.22 | 115.62 | 0.00 | 0.00 | 0.00 |
February | 83.22 | 38.12 | 45.10 | 95.66 | 102.77 | 0.00 | 0.00 | 0.00 |
March | 101.09 | 45.04 | 56.05 | 123.45 | 102.51 | 0.00 | 0.00 | 0.00 |
April | 129.24 | 64.81 | 64.42 | 178.64 | 83.03 | 0.00 | 0.00 | 0.00 |
May | 121.96 | 50.90 | 71.07 | 162.49 | 75.45 | 0.00 | 0.00 | 0.00 |
June | 121.20 | 52.59 | 68.62 | 172.09 | 61.04 | 0.00 | 0.00 | 0.00 |
July | 137.33 | 68.24 | 69.09 | 209.14 | 57.05 | 0.00 | 0.00 | 0.00 |
August | 135.63 | 72.04 | 63.59 | 208.03 | 59.22 | 0.00 | 0.00 | 0.00 |
September | 98.75 | 45.25 | 53.50 | 141.92 | 68.46 | 0.00 | 0.00 | 0.00 |
October | 87.41 | 44.93 | 42.48 | 128.31 | 77.35 | 0.00 | 0.00 | 0.00 |
November | 79.68 | 40.48 | 39.20 | 96.58 | 105.11 | 0.00 | 0.00 | 0.00 |
December | 76.02 | 42.24 | 33.78 | 91.35 | 116.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 104.34 | 50.67 | 53.67 | 142.23 | 85.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.02 | 38.12 | 33.78 | 91.35 | 57.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.33 | 72.04 | 71.07 | 209.14 | 116.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 386.01 | 283.16 | 102.86 | 579.51 | 224.55 | 0.00 | 0.00 | 0.00 |
February | 303.39 | 186.87 | 116.52 | 430.64 | 202.22 | 0.00 | 0.00 | 0.00 |
March | 241.87 | 116.83 | 125.04 | 339.85 | 210.74 | 0.00 | 0.00 | 0.00 |
April | 202.09 | 77.06 | 125.03 | 299.88 | 175.40 | 0.00 | 0.00 | 0.00 |
May | 143.90 | 17.71 | 126.19 | 170.69 | 160.80 | 0.00 | 0.00 | 0.00 |
June | 126.24 | 7.62 | 118.62 | 148.53 | 127.27 | 0.00 | 0.00 | 0.00 |
July | 133.72 | 15.05 | 118.67 | 183.25 | 117.62 | 0.00 | 0.00 | 0.00 |
August | 171.80 | 54.19 | 117.61 | 274.62 | 123.70 | 0.00 | 0.00 | 0.00 |
September | 239.05 | 121.14 | 117.92 | 387.00 | 139.82 | 0.00 | 0.00 | 0.00 |
October | 304.02 | 203.24 | 100.77 | 495.72 | 153.50 | 0.00 | 0.00 | 0.00 |
November | 369.50 | 260.86 | 108.64 | 553.23 | 203.64 | 0.00 | 0.00 | 0.00 |
December | 412.39 | 313.88 | 98.51 | 623.13 | 223.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 252.62 | 137.97 | 114.65 | 373.66 | 171.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 126.24 | 7.62 | 98.51 | 148.53 | 117.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.39 | 313.88 | 126.19 | 623.13 | 224.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.09 | 37.87 | 37.22 | 92.31 | 119.87 | 0.00 | 0.00 | 0.00 |
February | 89.58 | 41.35 | 48.23 | 107.63 | 105.06 | 0.00 | 0.00 | 0.00 |
March | 102.68 | 45.43 | 57.25 | 127.48 | 105.45 | 0.00 | 0.00 | 0.00 |
April | 141.55 | 73.71 | 67.85 | 197.98 | 84.60 | 0.00 | 0.00 | 0.00 |
May | 139.05 | 64.23 | 74.82 | 189.60 | 76.37 | 0.00 | 0.00 | 0.00 |
June | 147.31 | 73.65 | 73.66 | 212.08 | 60.23 | 0.00 | 0.00 | 0.00 |
July | 155.94 | 83.44 | 72.50 | 236.52 | 55.90 | 0.00 | 0.00 | 0.00 |
August | 146.30 | 79.29 | 67.01 | 223.45 | 59.75 | 0.00 | 0.00 | 0.00 |
September | 125.26 | 67.02 | 58.23 | 184.17 | 68.12 | 0.00 | 0.00 | 0.00 |
October | 95.75 | 52.28 | 43.48 | 143.22 | 78.72 | 0.00 | 0.00 | 0.00 |
November | 86.50 | 45.24 | 41.25 | 110.21 | 107.05 | 0.00 | 0.00 | 0.00 |
December | 76.39 | 40.97 | 35.42 | 96.00 | 120.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.22 | 58.78 | 56.43 | 160.31 | 86.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.09 | 37.87 | 35.42 | 92.31 | 55.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.94 | 83.44 | 74.82 | 236.52 | 120.07 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211293E+09 | 0.113004E+09 | 98288646.67 | 0.255044E+09 | 0.309665E+09 |
February | 0.201322E+09 | 92227050.81 | 0.109095E+09 | 0.231418E+09 | 0.248618E+09 |
March | 0.270749E+09 | 0.120631E+09 | 0.150118E+09 | 0.330637E+09 | 0.274551E+09 |
April | 0.334983E+09 | 0.168000E+09 | 0.166983E+09 | 0.463046E+09 | 0.215201E+09 |
May | 0.326666E+09 | 0.136325E+09 | 0.190341E+09 | 0.435213E+09 | 0.202089E+09 |
June | 0.314160E+09 | 0.136308E+09 | 0.177852E+09 | 0.446045E+09 | 0.158214E+09 |
July | 0.367833E+09 | 0.182785E+09 | 0.185047E+09 | 0.560161E+09 | 0.152802E+09 |
August | 0.363265E+09 | 0.192954E+09 | 0.170311E+09 | 0.557187E+09 | 0.158616E+09 |
September | 0.255954E+09 | 0.117287E+09 | 0.138666E+09 | 0.367850E+09 | 0.177455E+09 |
October | 0.234118E+09 | 0.120330E+09 | 0.113788E+09 | 0.343675E+09 | 0.207185E+09 |
November | 0.206541E+09 | 0.104931E+09 | 0.101610E+09 | 0.250334E+09 | 0.272439E+09 |
December | 0.203604E+09 | 0.113125E+09 | 90479850.82 | 0.244669E+09 | 0.310716E+09 |
Annual Sum or Average | 0.329049E+10 | 0.159791E+10 | 0.169258E+10 | 0.448528E+10 | 0.268755E+10 |
Minimum of Months | 0.201322E+09 | 92227050.81 | 90479850.82 | 0.231418E+09 | 0.152802E+09 |
Maximum of Months | 0.367833E+09 | 0.192954E+09 | 0.190341E+09 | 0.560161E+09 | 0.310716E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103390E+10 | 0.758414E+09 | 0.275488E+09 | 0.155216E+10 | 0.601439E+09 |
February | 0.733954E+09 | 0.452077E+09 | 0.281877E+09 | 0.104179E+10 | 0.489220E+09 |
March | 0.647825E+09 | 0.312930E+09 | 0.334896E+09 | 0.910256E+09 | 0.564449E+09 |
April | 0.523814E+09 | 0.199735E+09 | 0.324079E+09 | 0.777284E+09 | 0.454636E+09 |
May | 0.385430E+09 | 47432224.97 | 0.337997E+09 | 0.457165E+09 | 0.430679E+09 |
June | 0.327217E+09 | 19756107.58 | 0.307461E+09 | 0.384996E+09 | 0.329878E+09 |
July | 0.358167E+09 | 40319161.83 | 0.317848E+09 | 0.490820E+09 | 0.315037E+09 |
August | 0.460136E+09 | 0.145141E+09 | 0.314995E+09 | 0.735530E+09 | 0.331322E+09 |
September | 0.619624E+09 | 0.313985E+09 | 0.305640E+09 | 0.100310E+10 | 0.362409E+09 |
October | 0.814284E+09 | 0.544371E+09 | 0.269913E+09 | 0.132774E+10 | 0.411146E+09 |
November | 0.957755E+09 | 0.676160E+09 | 0.281595E+09 | 0.143396E+10 | 0.527829E+09 |
December | 0.110454E+10 | 0.840697E+09 | 0.263841E+09 | 0.166898E+10 | 0.599630E+09 |
Annual Sum or Average | 0.796665E+10 | 0.435102E+10 | 0.361563E+10 | 0.117838E+11 | 0.541768E+10 |
Minimum of Months | 0.327217E+09 | 19756107.58 | 0.263841E+09 | 0.384996E+09 | 0.315037E+09 |
Maximum of Months | 0.110454E+10 | 0.840697E+09 | 0.337997E+09 | 0.166898E+10 | 0.601439E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201114E+09 | 0.101433E+09 | 99681234.71 | 0.247252E+09 | 0.321060E+09 |
February | 0.216711E+09 | 0.100044E+09 | 0.116667E+09 | 0.260387E+09 | 0.254172E+09 |
March | 0.275024E+09 | 0.121675E+09 | 0.153349E+09 | 0.341447E+09 | 0.282426E+09 |
April | 0.366905E+09 | 0.191047E+09 | 0.175858E+09 | 0.513156E+09 | 0.219272E+09 |
May | 0.372430E+09 | 0.172024E+09 | 0.200405E+09 | 0.507828E+09 | 0.204542E+09 |
June | 0.381821E+09 | 0.190903E+09 | 0.190918E+09 | 0.549712E+09 | 0.156108E+09 |
July | 0.417661E+09 | 0.223486E+09 | 0.194175E+09 | 0.633483E+09 | 0.149721E+09 |
August | 0.391848E+09 | 0.212365E+09 | 0.179483E+09 | 0.598477E+09 | 0.160044E+09 |
September | 0.324672E+09 | 0.173727E+09 | 0.150945E+09 | 0.477361E+09 | 0.176568E+09 |
October | 0.256470E+09 | 0.140021E+09 | 0.116448E+09 | 0.383589E+09 | 0.210844E+09 |
November | 0.224196E+09 | 0.117270E+09 | 0.106926E+09 | 0.285675E+09 | 0.277472E+09 |
December | 0.204604E+09 | 0.109740E+09 | 94863948.50 | 0.257135E+09 | 0.321591E+09 |
Annual Sum or Average | 0.363345E+10 | 0.185373E+10 | 0.177972E+10 | 0.505550E+10 | 0.273382E+10 |
Minimum of Months | 0.201114E+09 | 0.100044E+09 | 94863948.50 | 0.247252E+09 | 0.149721E+09 |
Maximum of Months | 0.417661E+09 | 0.223486E+09 | 0.200405E+09 | 0.633483E+09 | 0.321591E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 755.18 | 448.17 | 539.99 | 363.22 | 176.77 | 0.00 | 0.00 |
February | 624.39 | 400.52 | 476.18 | 266.35 | 209.84 | 0.00 | 0.00 |
March | 576.25 | 404.17 | 445.64 | 207.30 | 238.34 | 0.00 | 0.00 |
April | 661.38 | 327.90 | 472.88 | 215.58 | 257.30 | 0.00 | 0.00 |
May | 507.44 | 297.28 | 404.92 | 132.83 | 272.08 | 0.00 | 0.00 |
June | 520.04 | 235.87 | 394.75 | 133.86 | 260.89 | 0.00 | 0.00 |
July | 618.39 | 220.05 | 426.99 | 166.74 | 260.26 | 0.00 | 0.00 |
August | 696.85 | 233.43 | 453.72 | 205.52 | 248.20 | 0.00 | 0.00 |
September | 704.64 | 267.96 | 463.06 | 233.41 | 229.65 | 0.00 | 0.00 |
October | 760.11 | 302.44 | 487.18 | 300.45 | 186.73 | 0.00 | 0.00 |
November | 749.30 | 405.08 | 535.68 | 346.59 | 189.09 | 0.00 | 0.00 |
December | 798.09 | 447.56 | 564.79 | 397.09 | 167.71 | 0.00 | 0.00 |
Annual Sum or Average | 664.73 | 332.23 | 472.18 | 247.42 | 224.76 | 0.00 | 0.00 |
Minimum of Months | 507.44 | 220.05 | 394.75 | 132.83 | 167.71 | 0.00 | 0.00 |
Maximum of Months | 798.09 | 448.17 | 564.79 | 397.09 | 272.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.202267E+10 | 0.120038E+10 | 0.144631E+10 | 0.972851E+09 | 0.473458E+09 | 0.00 | 0.00 |
February | 0.151052E+10 | 0.968935E+09 | 0.115199E+10 | 0.644347E+09 | 0.507639E+09 | 0.00 | 0.00 |
March | 0.154344E+10 | 0.108252E+10 | 0.119360E+10 | 0.555235E+09 | 0.638363E+09 | 0.00 | 0.00 |
April | 0.171430E+10 | 0.849922E+09 | 0.122570E+10 | 0.558782E+09 | 0.666920E+09 | 0.00 | 0.00 |
May | 0.135913E+10 | 0.796237E+09 | 0.108453E+10 | 0.355782E+09 | 0.728744E+09 | 0.00 | 0.00 |
June | 0.134793E+10 | 0.611380E+09 | 0.102320E+10 | 0.346967E+09 | 0.676231E+09 | 0.00 | 0.00 |
July | 0.165629E+10 | 0.589383E+09 | 0.114366E+10 | 0.446591E+09 | 0.697069E+09 | 0.00 | 0.00 |
August | 0.186643E+10 | 0.625219E+09 | 0.121525E+10 | 0.550459E+09 | 0.664789E+09 | 0.00 | 0.00 |
September | 0.182643E+10 | 0.694550E+09 | 0.120025E+10 | 0.604999E+09 | 0.595251E+09 | 0.00 | 0.00 |
October | 0.203589E+10 | 0.810060E+09 | 0.130487E+10 | 0.804723E+09 | 0.500149E+09 | 0.00 | 0.00 |
November | 0.194219E+10 | 0.104996E+10 | 0.138849E+10 | 0.898361E+09 | 0.490131E+09 | 0.00 | 0.00 |
December | 0.213760E+10 | 0.119875E+10 | 0.151275E+10 | 0.106356E+10 | 0.449185E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.209628E+11 | 0.104773E+11 | 0.148906E+11 | 0.780266E+10 | 0.708793E+10 | 0.00 | 0.00 |
Minimum of Months | 0.134793E+10 | 0.589383E+09 | 0.102320E+10 | 0.346967E+09 | 0.449185E+09 | 0.00 | 0.00 |
Maximum of Months | 0.213760E+10 | 0.120038E+10 | 0.151275E+10 | 0.106356E+10 | 0.728744E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.121561E+11 | -0.114485E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -707638865.8 | 58.99 | 0.00 | 0.00 |
February | 0.109894E+11 | -0.103524E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -637054267.3 | 58.99 | 0.00 | 0.00 |
March | 0.120722E+11 | -0.113600E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -712194697.8 | 58.99 | 0.00 | 0.00 |
April | 0.114015E+11 | -0.107375E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -663942704.9 | 58.99 | 0.00 | 0.00 |
May | 0.115082E+11 | -0.108269E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -681292715.3 | 58.99 | 0.00 | 0.00 |
June | 0.108841E+11 | -0.102374E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -646684818.3 | 58.99 | 0.00 | 0.00 |
July | 0.110538E+11 | -0.103915E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -662288868.8 | 58.99 | 0.00 | 0.00 |
August | 0.110698E+11 | -0.104080E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -661730720.3 | 58.99 | 0.00 | 0.00 |
September | 0.108169E+11 | -0.101728E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -644063154.6 | 58.99 | 0.00 | 0.00 |
October | 0.114238E+11 | -0.107557E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -668075218.5 | 58.99 | 0.00 | 0.00 |
November | 0.113614E+11 | -0.106918E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -669658146.5 | 58.98 | 0.00 | 0.00 |
December | 0.119856E+11 | -0.112808E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -704796179.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.136723E+12 | -0.128663E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.805942E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.108169E+11 | -0.114485E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -712194697.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.121561E+11 | -0.101728E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -637054267.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.27 | 0.24 | 01-JAN-07:30 | 1680.29 | 23.63 | 85.83 | 279.00 | 1550.01 | 22.70 | 76.00 | 280.67 |
February | 279.67 | 0.27 | 0.24 | 01-FEB-07:19 | 1429.55 | 23.25 | 92.17 | 275.50 | 1402.29 | 23.27 | 91.83 | 275.67 |
March | 338.17 | 0.30 | 0.24 | 01-MAR-06:00 | 1276.80 | 18.27 | 4.17 | 321.17 | 1291.38 | 20.21 | 56.67 | 322.67 |
April | 358.33 | 0.27 | 0.24 | 01-APR-05:00 | 1466.35 | 17.94 | 0.00 | 349.17 | 1673.74 | 17.96 | 0.00 | 345.50 |
May | 393.83 | 0.27 | 0.24 | 01-MAY-06:10 | 1495.07 | 17.75 | 0.00 | 378.33 | 1083.30 | 17.83 | 0.00 | 386.50 |
June | 381.00 | 0.28 | 0.24 | 01-JUN-06:10 | 1070.36 | 17.38 | 0.00 | 370.17 | 984.07 | 17.53 | 0.00 | 371.83 |
July | 408.67 | 0.28 | 0.24 | 01-JUL-05:40 | 1127.82 | 17.39 | 0.00 | 380.00 | 1050.19 | 17.51 | 0.00 | 381.33 |
August | 390.67 | 0.28 | 0.24 | 01-AUG-06:40 | 1608.15 | 17.55 | 0.00 | 366.50 | 1134.89 | 17.60 | 0.00 | 370.83 |
September | 328.83 | 0.27 | 0.24 | 01-SEP-06:30 | 1379.57 | 18.06 | 6.17 | 319.83 | 1398.87 | 18.46 | 9.17 | 319.83 |
October | 296.17 | 0.27 | 0.24 | 01-OCT-09:39 | 1537.74 | 21.09 | 62.67 | 307.50 | 1404.30 | 20.87 | 54.33 | 308.33 |
November | 300.00 | 0.29 | 0.24 | 01-NOV-06:49 | 1952.75 | 25.18 | 125.83 | 279.50 | 1880.43 | 25.20 | 125.67 | 279.83 |
December | 297.00 | 0.28 | 0.24 | 01-DEC-07:10 | 3436.48 | 29.52 | 176.83 | 279.83 | 2982.66 | 27.07 | 145.00 | 279.17 |
Annual Sum or Average | 4065.67 | 0.28 | 1586.75 | 20.20 | 553.67 | 3906.50 | 1447.07 | 20.17 | 558.67 | 3922.17 | ||
Minimum of Months | 279.67 | 0.27 | 0.24 | 1070.36 | 17.38 | 0.00 | 275.50 | 984.07 | 17.51 | 0.00 | 275.67 | |
Maximum of Months | 408.67 | 0.30 | 0.24 | 3436.48 | 29.52 | 176.83 | 380.00 | 2982.66 | 27.07 | 145.00 | 386.50 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.479371E+10 | 17189.06 | 08-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.384361E+10 | 11091.56 | 08-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.553685E+10 | 18229.52 | 30-MAR-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178513E+10 | 10636.28 | 01-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135137E+10 | 8364.61 | 14-MAY-22:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141871E+09 | 2845.98 | 13-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3031150.71 | 859.83 | 28-AUG-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 60238884.27 | 3515.68 | 20-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.363320E+09 | 7582.13 | 12-OCT-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.233403E+10 | 10662.08 | 05-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.432366E+10 | 12916.94 | 28-DEC-06:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.553685E+10 | 18229.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.271493E+09 | 9061.85 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15431129.77 | 2081.28 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153975E+09 | 7582.57 | 30-MAR-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5127733.29 | 1943.07 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 668242.00 | 440.54 | 05-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71533358.92 | 2759.31 | 23-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.518229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.271493E+09 | 9061.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.101740E+10 | 0.952652E+09 | 12372.26 | 18-JAN-12:55 | 12372.26 | 0.00 |
February | 0.00 | 0.00 | 0.217339E+09 | 0.215070E+09 | 10675.84 | 01-FEB-12:05 | 10675.84 | 0.00 |
March | 0.00 | 0.00 | 0.446131E+09 | 0.383880E+09 | 7425.38 | 23-MAR-14:00 | 5505.46 | 0.00 |
April | 0.00 | 0.00 | 0.144648E+10 | 0.118777E+10 | 14581.10 | 26-APR-11:13 | 11501.30 | 0.00 |
May | 0.00 | 0.00 | 0.863650E+09 | 0.698377E+09 | 10606.39 | 04-MAY-12:00 | 8848.74 | 0.00 |
June | 0.00 | 0.00 | 0.321658E+10 | 0.228575E+10 | 34717.09 | 30-JUN-02:61 | 16774.07 | 0.00 |
July | 0.00 | 0.00 | 0.821415E+10 | 0.535901E+10 | 35331.01 | 30-JUL-02:62 | 16939.00 | 0.00 |
August | 0.00 | 0.00 | 0.948584E+10 | 0.608121E+10 | 35646.02 | 19-AUG-02:62 | 18897.09 | 0.00 |
September | 0.00 | 0.00 | 0.497116E+10 | 0.377882E+10 | 36045.21 | 22-SEP-02:62 | 16071.96 | 0.00 |
October | 0.00 | 0.00 | 0.665820E+10 | 0.563966E+10 | 36131.89 | 05-OCT-02:41 | 18600.66 | 0.00 |
November | 0.00 | 0.00 | 0.871320E+09 | 0.851125E+09 | 11657.22 | 19-NOV-13:00 | 11657.22 | 0.00 |
December | 0.00 | 0.00 | 0.126560E+10 | 0.125551E+10 | 12794.26 | 19-DEC-13:00 | 12794.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.386738E+11 | 0.286888E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.217339E+09 | 0.215070E+09 | 7425.38 | 5505.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.948584E+10 | 0.608121E+10 | 36131.89 | 18897.09 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.278568E+10 | 0.228542E+10 | 26730.61 | 14-JAN-04:22 | 22920.88 | 0.00 |
February | 0.00 | 0.00 | 0.136418E+10 | 0.103888E+10 | 26730.61 | 18-FEB-03:01 | 13542.12 | 0.00 |
March | 0.00 | 0.00 | 0.185508E+10 | 0.128598E+10 | 26730.61 | 12-MAR-02:61 | 18317.78 | 0.00 |
April | 0.00 | 0.00 | 0.521579E+10 | 0.372339E+10 | 26730.61 | 04-APR-04:01 | 14621.84 | 0.00 |
May | 0.00 | 0.00 | 0.559052E+10 | 0.392883E+10 | 26730.61 | 16-MAY-04:01 | 14521.47 | 0.00 |
June | 0.00 | 0.00 | 0.102483E+11 | 0.662754E+10 | 26730.61 | 16-JUN-02:11 | 12951.72 | 0.00 |
July | 0.00 | 0.00 | 0.179015E+11 | 0.105696E+11 | 26960.06 | 23-JUL-02:11 | 11073.24 | 0.00 |
August | 0.00 | 0.00 | 0.190653E+11 | 0.109538E+11 | 27795.82 | 14-AUG-10:53 | 18669.79 | 0.00 |
September | 0.00 | 0.00 | 0.127052E+11 | 0.818798E+10 | 27375.90 | 22-SEP-02:11 | 10963.87 | 0.00 |
October | 0.00 | 0.00 | 0.137342E+11 | 0.100677E+11 | 27972.43 | 05-OCT-02:11 | 12880.37 | 0.00 |
November | 0.00 | 0.00 | 0.307896E+10 | 0.244489E+10 | 26730.61 | 14-NOV-05:01 | 15407.30 | 0.00 |
December | 0.00 | 0.00 | 0.282294E+10 | 0.263358E+10 | 26730.61 | 02-DEC-03:01 | 12857.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.963677E+11 | 0.637476E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.136418E+10 | 0.103888E+10 | 26730.61 | 10963.87 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.190653E+11 | 0.109538E+11 | 27972.43 | 22920.88 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4566.12 | 16800.32 | 31-JAN-13:20 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 4571.05 | 16800.96 | 02-FEB-14:00 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 4534.87 | 16717.47 | 01-MAR-13:35 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4433.65 | 16437.20 | 01-APR-12:40 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 4334.64 | 16049.01 | 01-MAY-13:00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 4243.23 | 15638.47 | 01-JUN-12:40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4170.25 | 15336.15 | 01-JUL-13:00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4179.81 | 15291.55 | 31-AUG-12:30 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 4216.29 | 15561.52 | 30-SEP-12:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4307.48 | 15959.99 | 31-OCT-12:30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4417.59 | 16359.21 | 30-NOV-14:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4502.37 | 16673.25 | 31-DEC-13:40 |
Annual Sum or Average | 0.00 | 4371.98 | ||||
Minimum of Months | 0.00 | 0.00 | 4170.25 | 15291.55 | ||
Maximum of Months | 0.00 | 0.00 | 4571.05 | 16800.96 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | -0.0 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.121728E+10 | 0.24 | 503.64 | 01-JAN-00:02 | 0.27 |
February | 0.109178E+10 | 0.24 | 503.64 | 01-FEB-00:05 | 0.27 |
March | 0.120661E+10 | 0.24 | 503.64 | 01-MAR-00:02 | 0.27 |
April | 0.117790E+10 | 0.24 | 503.64 | 01-APR-02:62 | 0.27 |
May | 0.122625E+10 | 0.24 | 503.64 | 01-MAY-01:00 | 0.27 |
June | 0.122006E+10 | 0.25 | 503.64 | 01-JUN-01:45 | 0.27 |
July | 0.127858E+10 | 0.25 | 503.64 | 01-JUL-00:40 | 0.27 |
August | 0.128079E+10 | 0.25 | 503.64 | 01-AUG-00:17 | 0.27 |
September | 0.122869E+10 | 0.25 | 503.64 | 01-SEP-00:50 | 0.27 |
October | 0.126162E+10 | 0.25 | 503.64 | 01-OCT-00:16 | 0.27 |
November | 0.118002E+10 | 0.24 | 503.64 | 01-NOV-00:55 | 0.27 |
December | 0.121628E+10 | 0.24 | 503.64 | 01-DEC-00:05 | 0.27 |
Annual Sum or Average | 0.145859E+11 | 0.25 | |||
Minimum of Months | 0.109178E+10 | 0.24 | 503.64 | 0.27 | |
Maximum of Months | 0.128079E+10 | 0.25 | 503.64 | 0.27 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.190349E+10 | 0.47 | 1210.48 | 08-JAN-07:10 | 0.70 |
February | 0.170768E+10 | 0.46 | 1065.49 | 08-FEB-06:04 | 0.65 |
March | 0.192142E+10 | 0.47 | 1113.85 | 29-MAR-19:55 | 0.66 |
April | 0.177434E+10 | 0.46 | 1054.66 | 01-APR-06:05 | 0.64 |
May | 0.182196E+10 | 0.45 | 1000.64 | 14-MAY-22:05 | 0.62 |
June | 0.173788E+10 | 0.46 | 869.40 | 13-JUN-05:10 | 0.57 |
July | 0.180511E+10 | 0.47 | 1130.98 | 31-JUL-11:55 | 0.66 |
August | 0.180740E+10 | 0.47 | 1160.56 | 18-AUG-11:55 | 0.67 |
September | 0.174942E+10 | 0.46 | 1863.11 | 30-SEP-02:61 | 0.86 |
October | 0.182252E+10 | 0.46 | 1734.79 | 16-OCT-11:03 | 0.84 |
November | 0.178728E+10 | 0.46 | 1055.27 | 05-NOV-06:10 | 0.64 |
December | 0.189242E+10 | 0.47 | 1108.89 | 28-DEC-06:33 | 0.66 |
Annual Sum or Average | 0.217309E+11 | 0.46 | |||
Minimum of Months | 0.170768E+10 | 0.45 | 869.40 | 0.57 | |
Maximum of Months | 0.192142E+10 | 0.47 | 1863.11 | 0.86 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.125444E+10 | 0.50 | 1374.97 | 15-JAN-03:01 | 0.93 |
February | 0.112958E+10 | 0.50 | 1374.97 | 01-FEB-03:01 | 0.93 |
March | 0.124942E+10 | 0.50 | 1374.97 | 03-MAR-05:01 | 0.92 |
April | 0.122026E+10 | 0.50 | 1374.97 | 03-APR-02:61 | 0.92 |
May | 0.126177E+10 | 0.50 | 1374.97 | 01-MAY-02:11 | 0.92 |
June | 0.125516E+10 | 0.52 | 1374.97 | 01-JUN-02:61 | 0.92 |
July | 0.139793E+10 | 0.54 | 1374.97 | 01-JUL-02:61 | 0.92 |
August | 0.142246E+10 | 0.55 | 1374.97 | 01-AUG-02:11 | 0.92 |
September | 0.130144E+10 | 0.53 | 1374.97 | 01-SEP-02:61 | 0.92 |
October | 0.135548E+10 | 0.53 | 1374.97 | 01-OCT-02:11 | 0.92 |
November | 0.121509E+10 | 0.50 | 1374.97 | 01-NOV-02:11 | 0.93 |
December | 0.125111E+10 | 0.50 | 1374.97 | 01-DEC-03:01 | 0.93 |
Annual Sum or Average | 0.153141E+11 | 0.51 | |||
Minimum of Months | 0.112958E+10 | 0.50 | 1374.97 | 0.92 | |
Maximum of Months | 0.142246E+10 | 0.55 | 1374.97 | 0.93 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 51.62 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 52.83 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 53.09 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:05 | 0.00 | 0.00 | 52.95 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 51.61 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 52.78 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:03 | 0.00 | 0.00 | 53.56 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 53.72 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 52.96 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 52.40 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 53.18 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 52.55 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 51.61 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 53.72 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 41.17 | 41.17 | 4566.12 | 16800.32 | 31-JAN-13:20 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 52.58 | 52.58 | 4571.05 | 16800.96 | 02-FEB-14:00 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 52.65 | 52.65 | 4534.87 | 16717.47 | 01-MAR-13:35 |
April | 0.00 | 0.00 | 01-APR-00:01 | 52.50 | 52.50 | 4433.65 | 16437.20 | 01-APR-12:40 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 41.87 | 41.87 | 4334.64 | 16049.01 | 01-MAY-13:00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 53.01 | 53.01 | 4243.23 | 15638.47 | 01-JUN-12:40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 53.62 | 53.62 | 4170.25 | 15336.15 | 01-JUL-13:00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 53.62 | 53.62 | 4179.81 | 15291.55 | 31-AUG-12:30 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.92 | 52.92 | 4216.29 | 15561.52 | 30-SEP-12:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 42.41 | 42.41 | 4307.48 | 15959.99 | 31-OCT-12:30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 53.00 | 53.00 | 4417.59 | 16359.21 | 30-NOV-14:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 52.90 | 52.90 | 4502.37 | 16673.25 | 31-DEC-13:40 |
Annual Sum or Average | 0.00 | 4371.98 | ||||||
Minimum of Months | 0.00 | 0.00 | 41.17 | 41.17 | 4170.25 | 15291.55 | ||
Maximum of Months | 0.00 | 0.00 | 53.62 | 53.62 | 4571.05 | 16800.96 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.218782E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.176940E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.204886E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.218099E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.207145E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.262638E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.394599E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.424833E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.309230E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.359723E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.203077E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.224984E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.320494E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.176940E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.424833E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.200099E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.150702E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.174921E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.259800E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.275159E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.386393E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.575046E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.601820E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.450361E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.483138E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.204758E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.201673E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.396387E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.150702E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.601820E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.190349E+10 | 0.101740E+10 | 0.479371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170768E+10 | 0.217339E+09 | 0.384361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192142E+10 | 0.446131E+09 | 0.553685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177434E+10 | 0.144648E+10 | 0.178513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182196E+10 | 0.863650E+09 | 0.135137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173788E+10 | 0.321587E+10 | 0.141871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.180511E+10 | 0.820637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180740E+10 | 0.947354E+10 | 3031150.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174942E+10 | 0.496246E+10 | 60238884.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182252E+10 | 0.663609E+10 | 0.363320E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178728E+10 | 0.871320E+09 | 0.233403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189242E+10 | 0.126560E+10 | 0.432366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217309E+11 | 0.386222E+11 | 0.245368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.170768E+10 | 0.217339E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.192142E+10 | 0.947354E+10 | 0.553685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.125444E+10 | 0.277763E+10 | 0.271493E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112958E+10 | 0.136004E+10 | 15431129.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124942E+10 | 0.185508E+10 | 0.153975E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122026E+10 | 0.521397E+10 | 5127733.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126177E+10 | 0.558271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125516E+10 | 0.102288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139793E+10 | 0.178890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142246E+10 | 0.190512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130144E+10 | 0.126724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135548E+10 | 0.136834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121509E+10 | 0.307254E+10 | 668242.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125111E+10 | 0.281118E+10 | 71533358.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153141E+11 | 0.961978E+11 | 0.518229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.112958E+10 | 0.136004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142246E+10 | 0.190512E+11 | 0.271493E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.190349E+10 | 0.00 | 0.00 | 0.00 | 0.284326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170768E+10 | 0.00 | 0.00 | 0.00 | 61722542.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192142E+10 | 0.00 | 0.00 | 0.00 | 0.127443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177434E+10 | 0.00 | 0.00 | 0.00 | 0.406648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182196E+10 | 0.00 | 0.00 | 0.00 | 0.249490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173788E+10 | 0.00 | 0.00 | 0.00 | 0.888502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.180511E+10 | 0.00 | 0.00 | 0.00 | 0.214088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180740E+10 | 0.00 | 0.00 | 0.00 | 0.244093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174942E+10 | 0.00 | 0.00 | 0.00 | 0.134288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182252E+10 | 0.00 | 0.00 | 0.00 | 0.177471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178728E+10 | 0.00 | 0.00 | 0.00 | 0.243484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189242E+10 | 0.00 | 0.00 | 0.00 | 0.357424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217309E+11 | 0.00 | 0.00 | 0.00 | 0.103184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.170768E+10 | 0.00 | 0.00 | 0.00 | 61722542.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.192142E+10 | 0.00 | 0.00 | 0.00 | 0.244093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.125444E+10 | 0.00 | 0.00 | 0.00 | 0.746547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112958E+10 | 0.00 | 0.00 | 0.00 | 0.377445E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124942E+10 | 0.00 | 0.00 | 0.00 | 0.499791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122026E+10 | 0.00 | 0.00 | 0.00 | 0.137774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126177E+10 | 0.00 | 0.00 | 0.00 | 0.148981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125516E+10 | 0.00 | 0.00 | 0.00 | 0.260877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139793E+10 | 0.00 | 0.00 | 0.00 | 0.435253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142246E+10 | 0.00 | 0.00 | 0.00 | 0.459573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130144E+10 | 0.00 | 0.00 | 0.00 | 0.320217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135548E+10 | 0.00 | 0.00 | 0.00 | 0.347589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121509E+10 | 0.00 | 0.00 | 0.00 | 0.832490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.765622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153141E+11 | 0.00 | 0.00 | 0.00 | 0.243245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.112958E+10 | 0.00 | 0.00 | 0.00 | 0.377445E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142246E+10 | 0.00 | 0.00 | 0.00 | 0.459573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.611950E+10 | 193531.79 | 0.00 | 6560668.57 | 0.00 | 0.379876E+10 | 0.169615E+10 | 0.00 | 3.88 |
February | 0.669578E+10 | 0.00 | 0.00 | 2431081.45 | 0.00 | 0.259569E+10 | 0.984873E+09 | 0.00 | 3.73 |
March | 0.686727E+10 | 0.00 | 0.00 | 3853638.28 | 0.00 | 0.393814E+10 | 0.104523E+10 | 0.00 | 3.82 |
April | 0.664538E+10 | 6953177.72 | 0.00 | 10112885.49 | 0.00 | 0.534023E+09 | 0.261663E+10 | 0.00 | 4.26 |
May | 0.675931E+10 | 0.00 | 0.00 | 9665927.16 | 0.00 | 0.345252E+09 | 0.305836E+10 | 0.00 | 4.30 |
June | 0.476227E+10 | 10563291.03 | 0.00 | 16992365.96 | 0.00 | 0.00 | 0.351194E+10 | 0.00 | 4.88 |
July | 0.277654E+10 | 0.414864E+09 | 0.00 | 25034747.73 | 0.00 | 0.00 | 0.411342E+10 | 0.00 | 5.18 |
August | 0.240762E+10 | 0.506068E+09 | 0.00 | 26461674.56 | 0.00 | 0.00 | 0.397109E+10 | 0.00 | 5.17 |
September | 0.399519E+10 | 0.238653E+09 | 0.00 | 21345324.11 | 0.00 | 0.00 | 0.411428E+10 | 0.00 | 5.00 |
October | 0.365517E+10 | 0.436460E+09 | 0.00 | 21767663.62 | 0.00 | 71824182.56 | 0.443830E+10 | 0.00 | 4.98 |
November | 0.753330E+10 | 2110881.80 | 0.00 | 7163579.84 | 0.00 | 0.950180E+09 | 0.196103E+10 | 0.00 | 3.94 |
December | 0.635358E+10 | 8622.97 | 0.00 | 8960238.81 | 0.00 | 0.317008E+10 | 0.195680E+10 | 0.00 | 4.10 |
Annual Sum or Average | 0.645709E+11 | 0.161587E+10 | 0.00 | 0.160350E+09 | 0.00 | 0.154039E+11 | 0.334681E+11 | 0.00 | 4.44 |
Minimum of Months | 0.240762E+10 | 0.00 | 0.00 | 2431081.45 | 0.00 | 0.00 | 0.984873E+09 | 0.00 | 3.73 |
Maximum of Months | 0.753330E+10 | 0.506068E+09 | 0.00 | 26461674.56 | 0.00 | 0.393814E+10 | 0.443830E+10 | 0.00 | 5.18 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.151257E+11 | 0.00 | 0.00 | 36309241.15 | 0.00 | 0.00 | 0.168974E+11 | 0.00 | 7.18 |
February | 0.127389E+11 | 0.00 | 0.00 | 30684869.66 | 0.00 | 0.00 | 0.167999E+11 | 0.00 | 7.22 |
March | 0.168645E+11 | 0.00 | 0.00 | 32548659.88 | 0.00 | 0.00 | 0.156917E+11 | 0.00 | 7.20 |
April | 0.872825E+10 | 411393.71 | 0.00 | 64982912.54 | 0.00 | 0.00 | 0.195379E+11 | 0.00 | 7.28 |
May | 0.758676E+10 | 0.00 | 0.00 | 71127512.27 | 0.00 | 0.00 | 0.217205E+11 | 0.00 | 7.31 |
June | 0.290189E+10 | 0.00 | 0.00 | 88101831.22 | 0.00 | 0.00 | 0.205847E+11 | 0.00 | 7.47 |
July | 0.117529E+10 | 0.291939E+09 | 0.00 | 0.105027E+09 | 0.00 | 0.00 | 0.165959E+11 | 0.00 | 7.75 |
August | 0.117496E+10 | 0.331732E+09 | 0.00 | 0.104380E+09 | 0.00 | 0.00 | 0.154407E+11 | 0.00 | 7.82 |
September | 0.171351E+10 | 0.163575E+09 | 0.00 | 93944979.81 | 102659.87 | 0.00 | 0.197041E+11 | 0.00 | 7.62 |
October | 0.331968E+10 | 0.221811E+09 | 0.00 | 86821876.31 | 0.00 | 0.00 | 0.185621E+11 | 0.00 | 7.60 |
November | 0.919076E+10 | 0.00 | 0.00 | 49816300.23 | 0.00 | 0.00 | 0.213518E+11 | 0.00 | 7.24 |
December | 0.135353E+11 | 0.00 | 0.00 | 40122233.48 | 0.00 | 0.00 | 0.184005E+11 | 0.00 | 7.18 |
Annual Sum or Average | 0.940555E+11 | 0.100947E+10 | 0.00 | 0.803867E+09 | 102659.87 | 0.00 | 0.221287E+12 | 0.00 | 7.41 |
Minimum of Months | 0.117496E+10 | 0.00 | 0.00 | 30684869.66 | 0.00 | 0.00 | 0.154407E+11 | 0.00 | 7.18 |
Maximum of Months | 0.168645E+11 | 0.331732E+09 | 0.00 | 0.105027E+09 | 102659.87 | 0.00 | 0.217205E+11 | 0.00 | 7.82 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:42
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.315309E+11 | 0.113001E+11 | 0.788081E+11 | 0.409311E+09 | 0.298791E+11 |
February | 0.383355E+11 | 0.105270E+11 | 0.712022E+11 | 0.213921E+09 | 0.247986E+11 |
March | 0.534637E+11 | 0.125033E+11 | 0.794387E+11 | 0.325694E+09 | 0.295937E+11 |
April | 0.726632E+11 | 0.102216E+11 | 0.676867E+11 | 0.867533E+09 | 0.370173E+11 |
May | 0.763948E+11 | 0.105186E+11 | 0.705213E+11 | 0.106822E+10 | 0.369472E+11 |
June | 0.765328E+11 | 0.857933E+10 | 0.577515E+11 | 0.140474E+10 | 0.438469E+11 |
July | 0.830539E+11 | 0.646162E+10 | 0.445894E+11 | 0.140523E+10 | 0.617051E+11 |
August | 0.764752E+11 | 0.599112E+10 | 0.417403E+11 | 0.117709E+10 | 0.642973E+11 |
September | 0.588146E+11 | 0.728574E+10 | 0.528035E+11 | 0.153247E+10 | 0.495013E+11 |
October | 0.414525E+11 | 0.648334E+10 | 0.536006E+11 | 0.159637E+10 | 0.523652E+11 |
November | 0.347325E+11 | 0.100774E+11 | 0.737573E+11 | 0.528445E+09 | 0.293858E+11 |
December | 0.287673E+11 | 0.107718E+11 | 0.781248E+11 | 0.724074E+09 | 0.299197E+11 |
Annual Sum or Average | 0.672217E+12 | 0.110721E+12 | 0.770025E+12 | 0.112531E+11 | 0.489257E+12 |
Minimum of Months | 0.287673E+11 | 0.599112E+10 | 0.417403E+11 | 0.213921E+09 | 0.247986E+11 |
Maximum of Months | 0.830539E+11 | 0.125033E+11 | 0.794387E+11 | 0.159637E+10 | 0.642973E+11 |