Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2023-10-16 08:28:22
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1255.71 | 5404.57 | 5404.57 |
Net Site Energy | 1255.71 | 5404.57 | 5404.57 |
Total Source Energy | 2225.15 | 9577.00 | 9577.00 |
Net Source Energy | 2225.15 | 9577.00 | 9577.00 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 213.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 54.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 21.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 239.49 | 451.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 50.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 175.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 37.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 414.76 | 840.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 213.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 54.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 21.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 10.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 220.85 | 451.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 50.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 175.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 11.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 18.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 213.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 54.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 21.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 10.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 239.49 | 451.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 50.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 175.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 37.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 138.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 454.57 | 1676.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1192.56 | 1942.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1785.14 | 3619.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 138.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 454.57 | 1676.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1192.56 | 1942.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1785.14 | 3619.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 414.764 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 414.764 | 100.00 |
Total On-Site and Utility Electric Sources | 414.764 | 100.00 |
Total Electricity End Uses | 414.764 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.83 |
Time Setpoint Not Met During Occupied Cooling | 71.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4178.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 4.0792 | 1.33 | 110.4804 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.6205 | 18.52 | 1009.9592 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 6.8498 | 2.48 | 560.2198 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 6.8498 | 2.48 | 560.2198 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 4.0792 | 1.33 | 110.4804 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.6205 | 18.52 | 1009.9592 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 6.8498 | 1.24 | 560.2198 | |||||||
Conditioned Total | 232.34 | 6.8498 | 1.24 | 560.2198 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 6.8498 | 2.48 | 560.2198 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 19-JUN-10:20 | 06-FEB-11:09 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 56089.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14484.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 989.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 12932.59 | 25220.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2795.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17991.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 3931.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 35132.85 | 99302.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 56089.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14484.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 989.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 12341.79 | 25220.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 2795.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 17991.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 231.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 173.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 67.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 33.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 758.45 | 489.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 160.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 190.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 119.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1313.56 | 911.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 997.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 746.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 290.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 146.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3264.36 | 2105.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 692.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 820.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 512.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5653.53 | 3923.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 997.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 746.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 290.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 146.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3264.36 | 2105.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 692.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 820.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 512.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5653.53 | 3923.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.65 |
KITCHEN DIRECT AIR | 1.14 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.65 | 1.65 | 1.65 | 1.65 | 1.65 | 1.65 | 1.00 | 1.00 | 1.65 |
PSZ-AC_2:2 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.65 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.14 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.65 | 1760.97 |
PSZ-AC_2:2_ADDAQ FAN | 1.14 | 1263.64 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.65 | 1.65 | 1.65 | 1.09 | 40866.54 | 53605.89 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 0.753280 | 28342.03 | 69985.14 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.65 | 0.822848 | 1.10 | 40866.54 | 20433.27 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.14 | 0.570667 | 0.760887 | 28342.03 | 14171.01 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 53605.89 |
PSZ-AC_2:2 HEATING COIL | 69985.14 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 4.079 | 110.480 | 0.000 | 0.000 | 0.000 | 0.000 | 114.560 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.620 | 261.340 | 748.620 | 0.000 | 0.000 | 0.000 | 1019.580 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 473.883 | 4.079 | 5.413 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 473.883 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1117.624 | 9.620 | 178.156 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1117.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 12834.676 | 110.480 | 146.608 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3722.056 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 29769.412 | 256.254 | 4745.415 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 8633.129 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 277.500 | 2.389 | 44.235 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 313.300 | 2.697 | 49.942 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 86968.240 | 748.620 | 13863.236 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 25220.790 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.4841 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2452 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2452 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.832 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.002 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.002 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.35359885E-12 | 0.85086983E-15 | -0.12104587E-12 | 0.11116349E-15 |
34 | 6 | 0.32105830E-07 | 0.14049395E-09 | 0.73260813E-08 | -0.15374192E-12 |
35 | 5 | -0.20739409E-03 | 0.11777713E-05 | -0.10642052E-03 | 0.72305472E-08 |
36 | 4 | 0.31215176 | 0.56271001E-03 | 0.10688868 | -0.36416661E-04 |
37 | 3 | -7.6619962 | 0.17148251E-01 | -2.4563584 | 0.30949505E-01 |
38 | 2 | 42.175481 | 0.60074686E-01 | 15.745559 | -0.34787057 |
39 | 1 | -81.544683 | 0.26760089E-01 | -29.572089 | 1.0999071 |
40 | 0 | 46.824332 | 0.53151391E-03 | 16.281184 | |
41 | 7 | -0.17135090E-08 | -0.36864923E-15 | 0.71259317E-14 | -0.97083918E-16 |
42 | 6 | 0.68579659E-05 | 0.47011368E-08 | 0.31862738E-02 | -0.26729135E-04 |
43 | 5 | -0.49396463E-03 | 0.27861516E-05 | -0.22352018 | 0.19543461E-02 |
44 | 4 | 0.11367371E-01 | 0.12683264E-03 | 4.8261412 | -0.45232255E-01 |
45 | 3 | -0.99836882E-01 | 0.10087729E-02 | -38.002184 | 0.39844117 |
46 | 2 | 0.35452054 | 0.16782362E-02 | 116.44652 | -1.4174386 |
47 | 1 | -0.51170991 | 0.51154075E-03 | -143.88527 | 2.0486777 |
48 | 0 | 0.24948649 | 0.12321491E-04 | 60.838472 | |
49 | 7 | -0.17135090E-08 | -0.36864923E-15 | 0.71259317E-14 | -0.97083918E-16 |
50 | 6 | 0.68579659E-05 | 0.47011368E-08 | 0.31862738E-02 | -0.26729135E-04 |
51 | 5 | -0.49396463E-03 | 0.27861516E-05 | -0.22352018 | 0.19543461E-02 |
52 | 4 | 0.11367371E-01 | 0.12683264E-03 | 4.8261412 | -0.45232255E-01 |
53 | 3 | -0.99836882E-01 | 0.10087729E-02 | -38.002184 | 0.39844117 |
54 | 2 | 0.35452054 | 0.16782362E-02 | 116.44652 | -1.4174386 |
55 | 1 | -0.51170991 | 0.51154075E-03 | -143.88527 | 2.0486777 |
56 | 0 | 0.24948649 | 0.12321491E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.362_SHGC_SOUTH_0.359 | 38 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.360 | ||
2 | NONRESWINDOW_U_0.362_SHGC_NORTH_0.359 | 39 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.360 | ||
3 | NONRESWINDOW_U_0.362_SHGC_EAST_0.359 | 40 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.360 | ||
4 | NONRESWINDOW_U_0.362_SHGC_WEST_0.359 | 41 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.360 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.63679E-002 | 0.27216 | 0.52074 | 0.52074 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.63679E-002 | 0.27216 | 0.52074 | 0.52074 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.63679E-002 | 0.27216 | 0.52074 | 0.52074 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.63679E-002 | 0.27216 | 0.52074 | 0.52074 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.238 | 0.3637 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 1.853E-002 | 1.595E-004 | 1.994E-004 | 0.188 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.584 | 5.025E-003 | 6.281E-003 | 5.934 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 1.853E-002 | 1.595E-004 | 1.953E-004 | 0.188 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.3201E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.7528E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.0931E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.5340E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.9481E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.8826E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5517E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.5543E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.3387E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.2061E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.4666E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.2964E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 4.6535E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.6209E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.6816E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.6816E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6952E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.2505E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.4639E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.0054E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.8076E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.8831E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.5545E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.5517E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 18646.17739 | 22375.41287 | 1.37141 | 1.64570 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.41196E-002 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 5581.00684 | 6697.20821 | 0.23681 | 0.41606 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -10.70000 | 1.50390E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 14757.79512 | 17709.35415 | 0.90347 | 1.14133 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31.43400 | 1.41184E-002 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 418.81080 | 502.57296 | 1.61635E-002 | 1.14133 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -10.70000 | 1.50390E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 26171.74 | 1.64570 | 1.64570 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 25512.04 | 0.41606 | 0.41606 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 26641.29 | 1.14133 | 1.14133 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 69985.14 | 1.14133 | 1.14133 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.64570 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14133 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.64570 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.64570 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.64570 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.64570 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.64570 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.64570 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14133 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14133 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14133 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14133 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14133 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14133 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.64570 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.14133 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.64570 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.64570 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 1760.97196 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.64570 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.64570 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.64570 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.08616 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.64570 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.82285 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.09713 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 40866.54000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20433.27000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40866.54000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 53605.88506 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 53605.88506 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14133 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14133 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1263.63741 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14133 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14133 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14133 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75328 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14133 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57067 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76089 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28342.03000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14171.01500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28342.03000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 69985.14365 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 69985.14365 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 39696.8 | 11.66 | 11.61 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 27530.8 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.484 | 0.451 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_EAST_0.359 | N/A | 2.057 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.484 | 0.451 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_SOUTH_0.359 | N/A | 2.057 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.484 | 0.451 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_WEST_0.359 | N/A | 2.057 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.245 | 0.231 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.484 | 0.451 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.484 | 0.451 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.484 | 0.451 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.245 | 0.231 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1159442331 | 0.4870265536 | Pass | Pass | 0.1595390025 | 0.3983899566 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1130562892 | 0.5131976385 | Pass | Pass | 5.4498204101E-002 | 0.2197538977 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.3420458099 | 0.2836303126 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 487.88 | 94.42 | 790.34 | 6.65 | 519.06 | 1898.34 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.451 | 0.484 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.451 | 0.484 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.451 | 0.484 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.236 | 0.245 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.451 | 0.484 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.451 | 0.484 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.451 | 0.484 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.236 | 0.245 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.362_SHGC_EAST_0.359 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.057 | 0.360 | 0.396 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.362_SHGC_SOUTH_0.359 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.057 | 0.360 | 0.396 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.362_SHGC_WEST_0.359 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.057 | 0.360 | 0.396 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.057 | 0.360 | 0.396 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.057 | 0.360 | 0.396 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 4.0792 | 116.17 | 473.88 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 44.33 | 0.0000 | Y | 3.94 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.6205 | 116.17 | 1117.62 | LightsWired | LTG_SCH_KITCHEN | 86.84 | 168.00 | 82.89 | 0.0000 | Y | 17.39 |
Interior Lighting Total | 6.8498 | 232.34 | 1591.51 | 21.33 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 473.88 | 180.08 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 473.88 | 180.08 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 209.35 | AstronomicalClock | - | 49.43 | 49.43 | 1.94 | |
EXTERIOR_LIGHTS_B | 742.80 | AstronomicalClock | - | 83.64 | 63.04 | 8.79 | |
Exterior Lighting Total | 952.15 | 10.73 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 40866.54 | 28650.71 | 12215.83 | 0.70 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28342.03 | 19870.03 | 8472.00 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 39696.8 | 11.66 | 11.61 | ||||
PSZ-AC_2:2 COOLING COIL | 27530.8 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 53605.89 | 0.84 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 69985.14 | 0.85 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.65 | 1760.97 | 1070.05 | 1.00 | 1.35 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1263.64 | 1107.16 | 1.00 | 1.37 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.95 | 1.24 | 0.36 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 18646.18 | 22375.41 | 192.61 | 1.371 | 1.646 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 23.89 | 23.87 | 0.01102 | 32.10 | 0.01412 | 0.416 | 0.00 |
KITCHEN | 14757.80 | 17709.35 | 152.44 | 0.903 | 1.141 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.09 | 0.01027 | 31.43 | 0.01412 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 5581.01 | 6697.21 | 57.65 | 0.237 | 0.416 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00770 | -10.70 | 0.00150 | 0.416 | 0.00 |
KITCHEN | 418.81 | 502.57 | 4.33 | 0.016 | 1.141 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 18.89 | 18.89 | 0.00318 | -10.70 | 0.00150 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.65 | 1.65 | 0.42 | 0.42 | 1.6457 | 1.6457 | 1.6457 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.14 | 1.14 | 1.14 | 1.14 | 1.1413 | 1.1413 | 1.1413 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 40866.540 | 28650.714 | 1.645700 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 20433.27 | 12981.29 | 1.097133 | 25.95 | 19.69 | 0.01180002 | 11.93 | 11.73 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 37.9221 | 23.87 | 0.01101517 | 59.4901 | 18646.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 53605.885 | 53605.885 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 53605.89 | 53605.89 | 1.645695 | 13.07 | 9.70 | 0.00609834 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 25.2815 | 19.86 | 0.00765290 | 53.0739 | 3144.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28342.030 | 19870.030 | 1.141330 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14171.01 | 8397.89 | 0.760887 | 32.10 | 23.13 | 0.01411964 | 11.91 | 11.72 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 150.0005 | 26.09 | 0.01051855 | 49.8018 | 13102.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 69985.144 | 69985.144 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 69985.14 | 69985.14 | 1.141334 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 100.0000 | 18.80 | 0.00365542 | 27.2556 | 201.91 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40866.540 | 28650.714 | 1.645700 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.7757 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.645695 | 1.98075083 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 20433.27 | 12981.29 | 1.0000 | 1.32050417 | 1.097133 | 25.95 | 19.69 | 0.01180002 | 56155.1 | 11.93 | 11.73 | 0.00850000 | 33438.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20433.27 | 32.10 | 0.01411964 | 23.13 | 0.41605618 | 37.9221 | 23.87 | 0.01101517 | 23.87 | 0.01101517 | 59.4901 | 18646.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 53605.885 | 53605.885 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.645695 | 1.98075083 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 53605.89 | 53605.89 | 1.0000 | 1.98075083 | 1.645695 | 13.07 | 9.70 | 0.00609834 | 28530.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 53605.89 | -10.70 | 0.00150390 | -10.70 | 0.41605618 | 25.2815 | 21.11 | 0.00765290 | 19.86 | 0.00765290 | 53.0739 | 3144.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28342.030 | 19870.030 | 1.141330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1031.0877 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.141334 | 1.37370333 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 14171.01 | 8397.89 | 1.0000 | 0.91579937 | 0.760887 | 32.10 | 23.13 | 0.01411964 | 68410.3 | 11.91 | 11.72 | 0.00850000 | 33411.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14171.01 | 32.10 | 0.01411964 | 23.13 | 1.14133354 | 150.0005 | 26.04 | 0.01051855 | 26.09 | 0.01051855 | 49.8018 | 13102.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 69985.144 | 69985.144 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.141334 | 1.37370333 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 69985.14 | 69985.14 | 1.0000 | 1.37370333 | 1.141334 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 69985.14 | -10.70 | 0.00150390 | -10.70 | 1.14133354 | 100.0000 | 17.22 | 0.00365542 | 18.80 | 0.00365542 | 27.2556 | 201.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 0.42 | 1.65 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 1.14 | 1.14 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3369.67 | 5552.50 | 1996.83 |
KITCHEN | 4860.67 | 6303.50 | 4149.50 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4889.33 | 7072.67 | 4178.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 32.67 | 46.17 | 0.83 | 0.33 |
KITCHEN | 0.00 | 213.50 | 0.00 | 71.17 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 32.67 | 249.33 | 0.83 | 71.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.802 | 2.704 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 8.166 | 0.013 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.069 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 7.389 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 12392108.72 | 0.00 | 12392108.72 | 6812476.14 | 19204584.86 | 13120747.55 | 1435.26 | 6211.14 | 1113.60 | 399.41 |
KITCHEN | 21238666.24 | 0.00 | 21238666.24 | 56476.49 | 21295142.73 | 35993094.65 | 8601.15 | 158.85 | 0.00 | 530.17 |
Total Facility | 33630774.96 | 0.00 | 33630774.96 | 6868952.63 | 40499727.59 | 49113842.20 | 8605.51 | 6216.69 | 1113.60 | 701.26 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4657 | 0.0000 | 0.4657 | 0.2624 | 0.7281 | 0.4161 | 0.00 | 6096.94 | 1090.06 |
KITCHEN | 0.7906 | 0.0000 | 0.7906 | 0.0013 | 0.7919 | 1.1413 | 7035.24 | 151.76 | 0.00 |
Total Facility | 1.2563 | 0.0000 | 1.2563 | 0.2637 | 1.5200 | 1.5574 | 7035.24 | 6096.94 | 1090.06 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 17952484.88 | 0.00 | 17952484.88 | 13120747.55 | 1424.51 | 1.41 | 7334.08 | 399.39 |
PSZ-AC_2:2 | 30767210.45 | 0.00 | 30767210.45 | 35993094.65 | 6402.33 | 562.60 | 1795.07 | 530.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6747 | 0.0000 | 0.6747 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.1453 | 0.0000 | 1.1453 | 1.1413 | 4887.06 | 553.82 | 1746.12 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1001.91 | 377.21 | 6207.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 173.57 | 1117.08 | 6426.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.1808 | 0.8701 | 0.6028 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.1150 | 1.2187 | 1.1372 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 386 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 414.76 | 2748.73 | 06-FEB-01:20 | 35132.85 | 19-JUN-10:20 |
Electricity:Building | 268.76 | 1624.98 | 01-JAN-01:20 | 17215.91 | 02-JAN-11:10 |
Electricity:Zone:DINING | 70.48 | 280.44 | 01-JAN-01:20 | 3811.41 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 260.82 | 1488.70 | 01-JAN-01:20 | 13921.86 | 02-JAN-11:10 |
InteriorLights:Electricity | 21.33 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:DINING | 3.94 | 20.75 | 16-MAY-05:00 | 389.13 | 02-JAN-16:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 21.33 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 21.33 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 3.94 | 20.75 | 16-MAY-05:00 | 389.13 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 21.33 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-16:40 |
Electricity:Zone:KITCHEN | 198.28 | 1344.54 | 01-JAN-01:20 | 13404.50 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.39 | 25.01 | 01-JAN-01:20 | 895.88 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.39 | 25.01 | 01-JAN-01:20 | 895.88 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 239.49 | 1438.68 | 01-JAN-01:10 | 12932.59 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 66.53 | 255.43 | 01-JAN-01:10 | 3718.02 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 239.49 | 1438.68 | 01-JAN-01:10 | 12932.59 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 220.85 | 847.88 | 01-JAN-01:10 | 12341.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 66.53 | 255.43 | 01-JAN-01:10 | 3718.02 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 220.85 | 847.88 | 01-JAN-01:10 | 12341.79 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 172.95 | 1183.25 | 01-JAN-01:10 | 9214.57 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 154.32 | 592.45 | 01-JAN-01:10 | 8623.77 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 37.60 | 594.45 | 01-JAN-23:30 | 3931.14 | 18-MAY-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 29.66 | 508.67 | 01-JAN-23:10 | 1625.91 | 04-AUG-03:30 |
LowTempRefrigeration:Refrigeration:Electricity | 11.35 | 0.00 | 01-JAN-11:10 | 988.82 | 04-AUG-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 18.30 | 475.34 | 12-JAN-01:10 | 637.09 | 27-MAR-12:30 |
ElectricityPurchased:Facility | 414.76 | 2748.73 | 06-FEB-01:20 | 35132.85 | 19-JUN-10:20 |
ElectricityPurchased:Plant | 414.76 | 2748.73 | 06-FEB-01:20 | 35132.85 | 19-JUN-10:20 |
Cogeneration:ElectricityPurchased | 414.76 | 2748.73 | 06-FEB-01:20 | 35132.85 | 19-JUN-10:20 |
General:Cogeneration:ElectricityPurchased | 414.76 | 2748.73 | 06-FEB-01:20 | 35132.85 | 19-JUN-10:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 414.76 | 2748.73 | 06-FEB-01:20 | 35132.85 | 19-JUN-10:20 |
ElectricityNet:Plant | 414.76 | 2748.73 | 06-FEB-01:20 | 35132.85 | 19-JUN-10:20 |
Cogeneration:ElectricityNet | 414.76 | 2748.73 | 06-FEB-01:20 | 35132.85 | 19-JUN-10:20 |
General:Cogeneration:ElectricityNet | 414.76 | 2748.73 | 06-FEB-01:20 | 35132.85 | 19-JUN-10:20 |
Electricity:HVAC | 105.62 | 0.00 | 01-JAN-01:10 | 20513.83 | 19-JUN-12:00 |
Fans:Electricity | 50.82 | 0.00 | 01-JAN-01:10 | 3216.77 | 19-JUN-12:00 |
General:Fans:Electricity | 50.82 | 0.00 | 01-JAN-01:10 | 3216.77 | 19-JUN-12:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 54.80 | 0.00 | 01-JAN-00:10 | 17297.06 | 19-JUN-12:00 |
General:Cooling:Electricity | 54.80 | 0.00 | 01-JAN-00:10 | 17297.06 | 19-JUN-12:00 |
ExteriorLights:Electricity | 10.73 | 0.00 | 01-JAN-07:30 | 952.15 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 10.73 | 0.00 | 01-JAN-07:30 | 952.15 | 01-JAN-06:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 17-MAR-13:40 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 17-MAR-13:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 840.95 | 2351.77 | 01-JAN-01:10 | 99302.06 | 06-FEB-11:10 |
NaturalGas:Building | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
NaturalGas:HVAC | 213.73 | 0.00 | 01-JAN-01:10 | 67509.24 | 06-FEB-07:10 |
Heating:NaturalGas | 213.73 | 0.00 | 01-JAN-01:10 | 67509.24 | 06-FEB-07:10 |
General:Heating:NaturalGas | 213.73 | 0.00 | 01-JAN-01:10 | 67509.24 | 06-FEB-07:10 |
NaturalGas:Plant | 175.83 | 612.41 | 01-JAN-00:10 | 23375.86 | 09-FEB-13:20 |
WaterSystems:NaturalGas | 175.83 | 612.41 | 01-JAN-00:10 | 23375.86 | 09-FEB-13:20 |
Water Heater:WaterSystems:NaturalGas | 175.83 | 612.41 | 01-JAN-00:10 | 23375.86 | 09-FEB-13:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 27-MAR-12:40 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 27-MAR-12:40 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 27-MAR-12:40 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 27-MAR-12:40 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 27-MAR-12:40 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 27-MAR-12:40 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 27-MAR-12:40 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 27-MAR-12:40 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1025.73 | 2415.74 | 06-FEB-01:10 | 109851.28 | 16-AUG-13:00 |
EnergyTransfer:Building | 409.26 | 1207.87 | 06-FEB-01:10 | 32050.56 | 19-JUN-11:10 |
EnergyTransfer:Zone:KITCHEN | 307.82 | 1207.87 | 06-FEB-01:10 | 19601.16 | 31-OCT-04:10 |
Refrigeration:EnergyTransfer | 141.33 | 2415.74 | 06-FEB-01:10 | 7834.84 | 18-MAY-10:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 70.67 | 1207.87 | 06-FEB-01:10 | 3917.42 | 18-MAY-10:40 |
General:Refrigeration:EnergyTransfer | 70.67 | 1207.87 | 06-FEB-01:10 | 3917.42 | 18-MAY-10:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 70.67 | 1207.87 | 06-FEB-01:10 | 3917.42 | 18-MAY-10:40 |
EnergyTransfer:Plant | 210.64 | 1207.87 | 06-FEB-01:10 | 21735.13 | 24-JAN-13:30 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 13.09 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 57.57 | 1059.55 | 12-JAN-01:10 | 2238.70 | 27-MAR-12:30 |
EnergyTransfer:Zone:DINING | 101.44 | 0.00 | 01-JAN-01:10 | 16355.80 | 19-JUN-12:00 |
Heating:EnergyTransfer | 25.54 | 0.00 | 01-JAN-00:20 | 13850.09 | 05-FEB-21:00 |
Heating:EnergyTransfer:Zone:DINING | 25.53 | 0.00 | 01-JAN-00:20 | 13850.09 | 05-FEB-21:00 |
General:Heating:EnergyTransfer | 25.54 | 0.00 | 01-JAN-00:20 | 13850.09 | 05-FEB-21:00 |
General:Heating:EnergyTransfer:Zone:DINING | 25.53 | 0.00 | 01-JAN-00:20 | 13850.09 | 05-FEB-21:00 |
Cooling:EnergyTransfer | 313.05 | 0.00 | 01-JAN-01:10 | 28133.14 | 19-JUN-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 75.90 | 0.00 | 01-JAN-01:10 | 16355.80 | 19-JUN-12:00 |
General:Cooling:EnergyTransfer | 313.05 | 0.00 | 01-JAN-01:10 | 28133.14 | 19-JUN-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 75.90 | 0.00 | 01-JAN-01:10 | 16355.80 | 19-JUN-12:00 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:20 | 972.55 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:20 | 972.55 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 237.15 | 0.00 | 01-JAN-01:10 | 15869.71 | 31-OCT-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 237.15 | 0.00 | 01-JAN-01:10 | 15869.71 | 31-OCT-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 139.97 | 0.00 | 01-JAN-00:10 | 19538.94 | 08-FEB-14:00 |
PlantLoopHeatingDemand:Plant | 139.97 | 0.00 | 01-JAN-00:10 | 19538.94 | 08-FEB-14:00 |
WaterSystems:PlantLoopHeatingDemand | 139.97 | 0.00 | 01-JAN-00:10 | 19538.94 | 08-FEB-14:00 |
General:WaterSystems:PlantLoopHeatingDemand | 139.97 | 0.00 | 01-JAN-00:10 | 19538.94 | 08-FEB-14:00 |
EnergyTransfer:HVAC | 405.83 | 0.00 | 01-JAN-01:10 | 67942.19 | 04-AUG-12:00 |
HeatingCoils:EnergyTransfer | 180.30 | 0.00 | 01-JAN-01:10 | 57076.04 | 06-FEB-07:10 |
CoolingCoils:EnergyTransfer | 225.53 | 0.00 | 01-JAN-00:10 | 67942.19 | 04-AUG-12:00 |
WaterSystems:EnergyTransfer | 139.97 | 0.00 | 01-JAN-00:10 | 19538.94 | 08-FEB-14:00 |
WaterUse:WaterSystems:EnergyTransfer | 139.97 | 0.00 | 01-JAN-00:10 | 19538.94 | 08-FEB-14:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 25.535 | -75.902 | 0.000 | 0.000 | 71.257 | 3.943 | 49.900 | 24.127 | 0.000 | 4.316 | 0.000 | 0.000 | -10.714 | 0.000 | -81.435 | -11.028 |
KITCHEN | 0.000 | 0.000 | 0.006 | -237.139 | 0.000 | 0.000 | 4.917 | 17.389 | 178.354 | 0.000 | 0.000 | 0.007 | 37.364 | 0.000 | 0.000 | 0.000 | -0.899 | -0.001 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.675 | 10.079 | 0.000 | 0.000 | 0.000 | -13.754 | -0.000 |
Total Facility | 0.000 | 0.000 | 25.541 | -313.041 | 0.000 | 0.000 | 76.175 | 21.333 | 228.254 | 24.127 | 0.000 | 7.998 | 47.443 | 0.000 | -10.714 | 0.000 | -96.088 | -11.029 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 02-SEP-02:61 | 0.00 | 0.00 | 0.00 | -29664.73 | 0.00 | 0.00 | 0.00 | 25.01 | 191.57 | 0.00 | 0.00 | 0.00 | 29646.48 | 0.00 | -195.88 | 0.00 | -2.45 | 0.00 |
KITCHEN | 07-OCT-02:61 | 0.00 | 0.00 | 0.00 | -43766.09 | 0.00 | 0.00 | 0.00 | 25.01 | 1205.28 | 0.00 | 0.00 | 0.00 | 42650.52 | 0.00 | -0.00 | 0.00 | -114.72 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-SEP-02:61 | 0.00 | 0.00 | 0.00 | -68494.04 | 0.00 | 0.00 | 0.00 | 50.02 | 1396.85 | 0.00 | 0.00 | 329.86 | 67508.55 | 0.00 | -649.10 | 0.00 | -142.15 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 07-FEB-05:01 | 0.00 | 0.00 | 29821.51 | 0.00 | 0.00 | 0.00 | 401.75 | 25.01 | 1153.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1306.44 | 0.00 | -52.82 | -30042.89 |
KITCHEN | 13-FEB-05:03 | 0.00 | 0.00 | 9716.70 | 0.00 | 0.00 | 0.00 | 22.49 | 25.01 | 4283.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -43.60 | -14004.44 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-FEB-05:01 | -28836.76 | 28836.76 | 29821.51 | -28836.76 | 0.00 | 0.00 | 422.13 | 50.02 | 5437.71 | 0.00 | 0.00 | 229.44 | 0.00 | 0.00 | -1306.44 | 0.00 | -109.43 | -5708.19 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.6457 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.6457 | 0.2528 | 1.0000 | Not calculated | 0.4161 | 0.2528 | ||
PSZ-AC_2:2 | 1.1413 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.1413 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1325 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.6457 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.6457 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2528 | ||
PSZ-AC_2:2 | 1.1413 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.1413 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1325 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6457 | 1.6457 | 1.6457 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1413 | 1.1413 | 1.1413 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.6457 | 1.6457 | 1.6457 | 1.6457 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.1413 | 1.1413 | 1.1413 | 1.1413 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6457 | 1.6457 | 1.6457 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1413 | 1.1413 | 1.1413 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.6457 | 1.6457 | 1.6457 | 1.6457 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.1413 | 1.1413 | 1.1413 | 1.1413 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.83 |
Number of hours cooling loads not met | 71.50 |
Number of hours not met | 72.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 213.73 | 67509.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 54.80 | 17297.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 21.33 | 1285.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 10.73 | 952.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 220.85 | 12341.79 | 451.39 | 25220.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 50.82 | 3216.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 175.83 | 23375.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 11.35 | 988.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 18.30 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 277.08 | 414.76 |
Natural Gas | 451.39 | 840.95 |
Additional | 0.00 | 0.00 |
Total | 728.47 | 1255.71 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 91.82 |
Space Heating | 0.00 |
Space Cooling | 235.86 |
Fans (All) | 218.71 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1030.74 |
Miscellaneous (All) | 1785.14 |
Subtotal | 1785.14 |
Natural Gas [MJ/m2] | |
Space Heating | 919.87 |
Service Water Heating | 756.79 |
Miscellaneous (All) | 3619.44 |
Subtotal | 3619.44 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.70 |
Space Heating | 17.02 |
Space Cooling | 4.36 |
Fans (All) | 4.05 |
Service Water Heating | 14.00 |
Receptacle Equipment | 55.02 |
Miscellaneous | 3.85 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4528. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8668.00 | 92.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8119.50 | 563.50 | 77.00 | 0.00 | 0.00 |
ATTIC | 6900.17 | 495.17 | 494.00 | 578.83 | 291.83 |
Min | 6900.17 | 92.00 | 0.00 | 0.00 | 0.00 |
Max | 8668.00 | 563.50 | 494.00 | 578.83 | 291.83 |
Average | 7895.89 | 383.56 | 190.33 | 192.94 | 97.28 |
Sum | 23687.67 | 1150.67 | 571.00 | 578.83 | 291.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254671.67 | 53.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15908.67 | 349.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254671.67 | 349.33 | 0.00 | 0.00 | 0.00 |
Average | 90193.44 | 134.22 | 0.00 | 0.00 | 0.00 |
Sum | 270580.33 | 402.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 7096.00 | 1664.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 5627.83 | 3118.00 | 14.17 | 0.00 | 0.00 |
ATTIC | 6486.00 | 1194.33 | 335.67 | 253.67 | 490.33 |
Min | 5627.83 | 1194.33 | 0.00 | 0.00 | 0.00 |
Max | 7096.00 | 3118.00 | 335.67 | 253.67 | 490.33 |
Average | 6403.28 | 1992.11 | 116.61 | 84.56 | 163.44 |
Sum | 19209.83 | 5976.33 | 349.83 | 253.67 | 490.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 206608.83 | 48116.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 10192.17 | 6065.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 206608.83 | 48116.17 | 0.00 | 0.00 | 0.00 |
Average | 72267.00 | 18060.67 | 0.00 | 0.00 | 0.00 |
Sum | 216801.00 | 54182.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:22
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.837159E+09 | 13928.83 | 02-JAN-00:01 | -10.7 | -12.6 | 0.436699E+10 | 3682.60 | 14-JAN-19:10 | -5.1 | -5.5 |
February | 0.764353E+09 | 15086.38 | 06-FEB-00:01 | -13.3 | -14.9 | 0.395265E+10 | 3682.50 | 25-FEB-19:10 | 3.30 | -0.7 |
March | 0.180251E+10 | 10159.01 | 22-MAR-23:01 | -2.3 | -6.2 | 0.444043E+10 | 4267.75 | 27-MAR-17:30 | 20.00 | 15.02 |
April | 0.370162E+10 | 18914.61 | 08-APR-02:61 | 16.52 | 13.04 | 0.444637E+10 | 4421.49 | 08-APR-18:10 | 15.40 | 12.93 |
May | 0.696916E+10 | 23307.38 | 28-MAY-02:61 | 14.90 | 9.78 | 0.495546E+10 | 4640.87 | 27-MAY-18:00 | 14.90 | 9.78 |
June | 0.107359E+11 | 28381.56 | 04-JUN-02:61 | 15.68 | 9.66 | 0.519134E+10 | 4641.02 | 10-JUN-18:00 | 19.40 | 15.40 |
July | 0.141469E+11 | 24530.01 | 11-JUL-02:61 | 21.52 | 15.80 | 0.532928E+10 | 4641.38 | 08-JUL-18:10 | 21.52 | 15.80 |
August | 0.151235E+11 | 25251.74 | 19-AUG-02:61 | 21.52 | 15.90 | 0.538806E+10 | 4641.14 | 05-AUG-18:00 | 21.52 | 15.90 |
September | 0.105273E+11 | 29678.43 | 02-SEP-02:61 | 23.80 | 16.89 | 0.509655E+10 | 4640.79 | 16-SEP-18:00 | 18.90 | 15.21 |
October | 0.750226E+10 | 24243.86 | 06-OCT-02:61 | 18.98 | 18.10 | 0.489198E+10 | 4640.53 | 21-OCT-18:10 | 17.12 | 14.23 |
November | 0.271709E+10 | 10623.56 | 24-NOV-00:01 | -3.3 | -5.8 | 0.427758E+10 | 4418.52 | 04-NOV-18:10 | -3.3 | -5.8 |
December | 0.107470E+10 | 10641.95 | 22-DEC-00:01 | -3.3 | -6.0 | 0.436567E+10 | 3682.53 | 16-DEC-19:10 | -3.3 | -6.0 |
Annual Sum or Average | 0.759026E+11 | 0.567023E+11 | ||||||||
Minimum of Months | 0.764353E+09 | 10159.01 | -13.3 | -14.9 | 0.395265E+10 | 3682.50 | -5.1 | -6.0 | ||
Maximum of Months | 0.151235E+11 | 29678.43 | 23.80 | 18.10 | 0.538806E+10 | 4641.38 | 21.52 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193923E+11 | 30322.60 | 02-JAN-05:01 | -12.1 | -13.5 | 0.727966E+10 | 4817.19 | 24-JAN-11:00 | 12.20 | 11.93 |
February | 0.171222E+11 | 30549.59 | 06-FEB-05:01 | -13.2 | -14.5 | 0.657249E+10 | 4789.88 | 01-FEB-11:00 | -13.2 | -14.5 |
March | 0.196569E+11 | 27420.94 | 28-MAR-04:01 | 9.90 | 7.72 | 0.729761E+10 | 4837.21 | 03-MAR-11:00 | 9.90 | 7.72 |
April | 0.187090E+11 | 34194.17 | 28-APR-04:01 | 14.22 | 11.81 | 0.711011E+10 | 4868.93 | 10-APR-10:39 | 14.22 | 11.81 |
May | 0.190916E+11 | 40782.95 | 21-MAY-02:61 | 13.12 | 8.11 | 0.742119E+10 | 4868.95 | 18-MAY-10:00 | 13.12 | 8.11 |
June | 0.195571E+11 | 38892.16 | 03-JUN-02:61 | 13.80 | 9.33 | 0.721503E+10 | 4885.50 | 19-JUN-10:50 | 35.63 | 23.79 |
July | 0.210167E+11 | 28862.86 | 11-JUL-02:11 | 21.33 | 15.70 | 0.745464E+10 | 4895.79 | 20-JUL-10:50 | 28.22 | 25.09 |
August | 0.213238E+11 | 32799.98 | 08-AUG-02:11 | 16.10 | 13.26 | 0.746097E+10 | 4907.83 | 04-AUG-10:50 | 16.10 | 13.26 |
September | 0.201628E+11 | 41474.57 | 29-SEP-02:11 | 12.03 | 7.90 | 0.720735E+10 | 4872.05 | 14-SEP-10:00 | 12.03 | 7.90 |
October | 0.208278E+11 | 43800.15 | 07-OCT-02:61 | 9.90 | 6.26 | 0.740193E+10 | 4868.95 | 06-OCT-10:00 | 9.90 | 6.26 |
November | 0.200738E+11 | 31118.54 | 05-NOV-02:61 | 9.90 | 6.67 | 0.708002E+10 | 4868.67 | 10-NOV-11:50 | 15.10 | 13.50 |
December | 0.202115E+11 | 25614.27 | 22-DEC-05:01 | -3.9 | -6.5 | 0.727843E+10 | 4798.78 | 26-DEC-11:00 | 9.40 | 5.22 |
Annual Sum or Average | 0.237145E+12 | 0.867794E+11 | ||||||||
Minimum of Months | 0.171222E+11 | 25614.27 | -13.2 | -14.5 | 0.657249E+10 | 4789.88 | -13.2 | -14.5 | ||
Maximum of Months | 0.213238E+11 | 43800.15 | 21.33 | 15.70 | 0.746097E+10 | 4907.83 | 35.63 | 25.09 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 | -11.5 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.5 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -1.1 | -4.2 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 | 4.35 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.35 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 | 4.90 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 | 9.91 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 | 16.59 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.59 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 20.00 | 19.29 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.29 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 23.90 | 21.46 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 23.43 | 19.79 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 | 11.77 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.40 | 9.04 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 | 2.86 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.86 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -9.6 | -11.5 | 0.00 | 0.00 | -9.6 | -11.5 | ||
Maximum of Months | 0.00 | 0.00 | 23.90 | 21.46 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.721903E+10 | 21062.00 | 02-JAN-03:52 | -11.7 |
February | 0.720046E+10 | 29821.07 | 07-FEB-05:01 | -9.0 |
March | 0.340392E+10 | 13344.01 | 13-MAR-04:06 | -0.1 |
April | 0.874055E+09 | 9658.21 | 02-APR-02:62 | 3.90 |
May | 5066301.18 | 1792.43 | 15-MAY-04:03 | 7.30 |
June | 2165864.72 | 4867.37 | 26-JUN-03:27 | 20.85 |
July | 13743238.85 | 2131.07 | 09-JUL-23:01 | 27.48 |
August | 15302405.75 | 2469.03 | 04-AUG-23:01 | 28.30 |
September | 1089499.30 | 1366.39 | 17-SEP-03:27 | 19.70 |
October | 0.109134E+09 | 5863.72 | 27-OCT-19:04 | 8.12 |
November | 0.190104E+10 | 7972.95 | 22-NOV-21:00 | -1.1 |
December | 0.478995E+10 | 13099.91 | 06-DEC-05:54 | 0.00 |
Annual Sum or Average | 0.255350E+11 | |||
Minimum of Months | 1089499.30 | 1366.39 | -11.7 | |
Maximum of Months | 0.721903E+10 | 29821.07 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1575232.00 | 8095.66 | 02-JAN-05:03 | -12.1 |
February | 2416071.22 | 9725.52 | 13-FEB-05:03 | -9.0 |
March | 505361.15 | 3264.44 | 20-MAR-04:04 | -0.8 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 8355.57 | 125.33 | 19-JUN-23:01 | 26.32 |
July | 210998.10 | 1208.51 | 09-JUL-23:01 | 27.48 |
August | 381609.35 | 1854.15 | 04-AUG-23:01 | 28.30 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 |
November | 222927.75 | 1901.70 | 25-NOV-05:04 | -3.3 |
December | 241763.03 | 2284.44 | 31-DEC-05:04 | -1.2 |
Annual Sum or Average | 5562318.15 | |||
Minimum of Months | 0.00 | 0.00 | -12.1 | |
Maximum of Months | 2416071.22 | 9725.52 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403864E+09 | 389.13 | 02-JAN-16:40 | 0.565077E+10 | 3718.02 | 01-JAN-11:09 |
February | 0.336651E+09 | 389.13 | 01-FEB-17:10 | 0.510393E+10 | 3718.02 | 01-FEB-11:09 |
March | 0.345041E+09 | 389.13 | 01-MAR-17:49 | 0.565082E+10 | 3718.02 | 01-MAR-11:09 |
April | 0.294335E+09 | 389.13 | 01-APR-18:19 | 0.546849E+10 | 3718.02 | 01-APR-10:09 |
May | 0.285818E+09 | 389.13 | 01-MAY-18:49 | 0.565080E+10 | 3718.02 | 01-MAY-10:09 |
June | 0.262378E+09 | 389.13 | 01-JUN-19:19 | 0.546853E+10 | 3718.02 | 01-JUN-10:09 |
July | 0.269089E+09 | 389.13 | 01-JUL-19:30 | 0.565075E+10 | 3718.02 | 01-JUL-10:09 |
August | 0.298182E+09 | 389.13 | 01-AUG-18:00 | 0.565082E+10 | 3718.02 | 01-AUG-10:09 |
September | 0.309165E+09 | 389.13 | 01-SEP-18:30 | 0.546849E+10 | 3718.02 | 01-SEP-10:09 |
October | 0.349487E+09 | 389.13 | 02-OCT-17:40 | 0.565077E+10 | 3718.02 | 01-OCT-10:09 |
November | 0.382105E+09 | 389.13 | 01-NOV-16:49 | 0.546851E+10 | 3718.02 | 01-NOV-10:09 |
December | 0.407270E+09 | 389.13 | 01-DEC-16:30 | 0.565075E+10 | 3718.02 | 01-DEC-11:09 |
Annual Sum or Average | 0.394338E+10 | 0.665334E+11 | ||||
Minimum of Months | 0.262378E+09 | 389.13 | 0.510393E+10 | 3718.02 | ||
Maximum of Months | 0.407270E+09 | 389.13 | 0.565082E+10 | 3718.02 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146885E+10 | 895.88 | 02-JAN-10:09 | 0.146891E+11 | 9214.57 | 01-JAN-11:09 |
February | 0.133058E+10 | 895.88 | 01-FEB-10:09 | 0.132676E+11 | 9214.57 | 01-FEB-11:09 |
March | 0.149423E+10 | 895.88 | 01-MAR-10:09 | 0.146892E+11 | 9214.57 | 01-MAR-11:09 |
April | 0.142731E+10 | 895.88 | 01-APR-16:10 | 0.142152E+11 | 9214.57 | 01-APR-10:09 |
May | 0.148154E+10 | 895.88 | 01-MAY-09:09 | 0.146891E+11 | 9214.57 | 01-MAY-10:09 |
June | 0.144409E+10 | 895.88 | 01-JUN-09:09 | 0.142153E+11 | 9214.57 | 01-JUN-10:09 |
July | 0.146494E+10 | 895.88 | 01-JUL-16:10 | 0.146890E+11 | 9214.57 | 01-JUL-10:09 |
August | 0.149423E+10 | 895.88 | 01-AUG-09:09 | 0.146892E+11 | 9214.57 | 01-AUG-10:09 |
September | 0.142766E+10 | 895.88 | 01-SEP-09:09 | 0.142152E+11 | 9214.57 | 01-SEP-10:09 |
October | 0.146867E+10 | 895.88 | 02-OCT-09:09 | 0.146891E+11 | 9214.57 | 01-OCT-10:09 |
November | 0.142226E+10 | 895.88 | 01-NOV-09:09 | 0.142153E+11 | 9214.57 | 01-NOV-10:09 |
December | 0.146511E+10 | 895.88 | 01-DEC-10:09 | 0.146890E+11 | 9214.57 | 01-DEC-11:09 |
Annual Sum or Average | 0.173895E+11 | 0.172953E+12 | ||||
Minimum of Months | 0.133058E+10 | 895.88 | 0.132676E+11 | 9214.57 | ||
Maximum of Months | 0.149423E+10 | 895.88 | 0.146892E+11 | 9214.57 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.403864E+09 | 0.565077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143676E+11 |
February | 0.852256E+10 | 0.336651E+09 | 0.510393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137327E+11 |
March | 0.954557E+10 | 0.345041E+09 | 0.565082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109674E+11 |
April | 0.915225E+10 | 0.294335E+09 | 0.546849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16459429.36 | 0.689513E+10 |
May | 0.947560E+10 | 0.285818E+09 | 0.565080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97249537.55 | 0.403814E+10 |
June | 0.922788E+10 | 0.262378E+09 | 0.546853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640017E+09 | 0.145179E+10 |
July | 0.939996E+10 | 0.269089E+09 | 0.565075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152415E+10 | 0.217093E+09 |
August | 0.954557E+10 | 0.298182E+09 | 0.565082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176294E+10 | 0.378454E+09 |
September | 0.915225E+10 | 0.309165E+09 | 0.546849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270186E+09 | 0.218600E+10 |
October | 0.940563E+10 | 0.349487E+09 | 0.565077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4628315.05 | 0.534075E+10 |
November | 0.909363E+10 | 0.382105E+09 | 0.546851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923061E+10 |
December | 0.939996E+10 | 0.407270E+09 | 0.565075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126296E+11 |
Annual Sum or Average | 0.111326E+12 | 0.394338E+10 | 0.665334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431563E+10 | 0.814353E+11 |
Minimum of Months | 0.852256E+10 | 0.262378E+09 | 0.510393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217093E+09 |
Maximum of Months | 0.954557E+10 | 0.407270E+09 | 0.565082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176294E+10 | 0.143676E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.146885E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150089E+09 |
February | 0.610713E+09 | 0.133058E+10 | 0.971608E+10 | 0.103882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127122E+09 |
March | 0.684021E+09 | 0.149423E+10 | 0.107572E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107438E+09 |
April | 0.655836E+09 | 0.142731E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 3077.31 | 75293371.11 |
May | 0.679007E+09 | 0.148154E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 128140.08 | 51110002.08 |
June | 0.661256E+09 | 0.144409E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 1235202.44 | 31390207.80 |
July | 0.673587E+09 | 0.146494E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 2349601.72 | 12889354.08 |
August | 0.684021E+09 | 0.149423E+10 | 0.107572E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 3308686.83 | 15716927.36 |
September | 0.655836E+09 | 0.142766E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 325161.85 | 31493727.79 |
October | 0.673993E+09 | 0.146867E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64957274.88 |
November | 0.651635E+09 | 0.142226E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105144E+09 |
December | 0.673587E+09 | 0.146511E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126592E+09 |
Annual Sum or Average | 0.797748E+10 | 0.173895E+11 | 0.126656E+12 | 0.135417E+12 | 0.00 | 0.00 | 0.00 | 7349870.23 | 0.899235E+09 |
Minimum of Months | 0.610713E+09 | 0.133058E+10 | 0.971608E+10 | 0.103882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12889354.08 |
Maximum of Months | 0.684021E+09 | 0.149423E+10 | 0.107572E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 3308686.83 | 0.150089E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383634E+09 | 0.504352E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334122E+09 | 0.746877E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245337E+09 | 0.118778E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267532E+09 | 0.129434E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218131E+09 | 0.170651E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203661E+09 | 0.170153E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225864E+09 | 0.169414E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318693E+09 | 0.168561E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292449E+09 | 0.117536E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421087E+09 | 0.106597E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363453E+09 | 0.564891E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400922E+09 | 0.426585E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367489E+10 | 0.137540E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203661E+09 | 0.426585E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421087E+09 | 0.170651E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 389.13 | 02-JAN-16:40 | 3718.02 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 19216.21 | 14-JAN-20:00 |
February | 9454.80 | 04-FEB-19:10 | 389.13 | 01-FEB-17:10 | 3718.02 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 19481.62 | 06-FEB-12:05 |
March | 9454.80 | 04-MAR-19:10 | 389.13 | 01-MAR-17:49 | 3718.02 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 14377.31 | 17-MAR-20:00 |
April | 9454.80 | 01-APR-18:10 | 389.13 | 01-APR-18:19 | 3718.02 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1421.43 | 07-APR-13:00 | 10216.33 | 01-APR-18:03 |
May | 9454.80 | 06-MAY-18:10 | 389.13 | 01-MAY-18:49 | 3718.02 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3134.41 | 30-MAY-12:00 | 7130.92 | 01-MAY-19:55 |
June | 9454.80 | 03-JUN-18:10 | 389.13 | 01-JUN-19:19 | 3718.02 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7069.80 | 19-JUN-11:55 | 4707.21 | 03-JUN-18:53 |
July | 9454.80 | 01-JUL-18:10 | 389.13 | 01-JUL-19:30 | 3718.02 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5581.02 | 07-JUL-11:55 | 2017.61 | 01-JUL-20:00 |
August | 9454.80 | 05-AUG-18:10 | 389.13 | 01-AUG-18:00 | 3718.02 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5255.93 | 04-AUG-19:00 | 2523.03 | 20-AUG-06:10 |
September | 9454.80 | 02-SEP-18:10 | 389.13 | 01-SEP-18:30 | 3718.02 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3419.85 | 01-SEP-12:00 | 5443.50 | 29-SEP-19:55 |
October | 9454.80 | 07-OCT-18:10 | 389.13 | 02-OCT-17:40 | 3718.02 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 565.47 | 04-OCT-13:00 | 9115.88 | 28-OCT-19:00 |
November | 9454.80 | 04-NOV-18:10 | 389.13 | 01-NOV-16:49 | 3718.02 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 14010.44 | 22-NOV-21:00 |
December | 9454.80 | 02-DEC-19:10 | 389.13 | 01-DEC-16:30 | 3718.02 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 16001.55 | 31-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 389.13 | 3718.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2017.61 | |||||
Maximum of Months | 9454.80 | 389.13 | 3718.02 | 0.00 | 0.00 | 0.00 | 0.00 | 7069.80 | 19481.62 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 895.88 | 02-JAN-10:09 | 6627.44 | 01-JAN-11:09 | 7566.24 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 416.54 | 31-JAN-01:20 |
February | 677.52 | 04-FEB-19:10 | 895.88 | 01-FEB-10:09 | 6627.44 | 01-FEB-11:09 | 7566.24 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 436.07 | 06-FEB-01:20 |
March | 677.52 | 04-MAR-19:10 | 895.88 | 01-MAR-10:09 | 6627.44 | 01-MAR-11:09 | 7566.24 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 318.17 | 22-MAR-04:00 |
April | 677.52 | 01-APR-18:10 | 895.88 | 01-APR-16:10 | 6627.44 | 01-APR-10:09 | 7566.24 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 1.08 | 07-APR-13:00 | 356.42 | 11-APR-04:00 |
May | 677.52 | 06-MAY-18:10 | 895.88 | 01-MAY-09:09 | 6627.44 | 01-MAY-10:09 | 7566.24 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 5.98 | 30-MAY-13:00 | 213.16 | 03-MAY-04:00 |
June | 677.52 | 03-JUN-18:10 | 895.88 | 01-JUN-09:09 | 6627.44 | 01-JUN-10:09 | 7566.24 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 15.42 | 19-JUN-11:55 | 116.21 | 03-JUN-02:00 |
July | 677.52 | 01-JUL-18:10 | 895.88 | 01-JUL-16:10 | 6627.44 | 01-JUL-10:09 | 7566.24 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 14.00 | 10-JUL-14:00 | 77.34 | 22-JUL-02:00 |
August | 677.52 | 05-AUG-18:10 | 895.88 | 01-AUG-09:09 | 6627.44 | 01-AUG-10:09 | 7566.24 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 20.37 | 24-AUG-17:00 | 75.78 | 25-AUG-01:30 |
September | 677.52 | 02-SEP-18:10 | 895.88 | 01-SEP-09:09 | 6627.44 | 01-SEP-10:09 | 7566.24 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 8.79 | 14-SEP-14:00 | 120.67 | 23-SEP-02:10 |
October | 677.52 | 07-OCT-18:10 | 895.88 | 02-OCT-09:09 | 6627.44 | 01-OCT-10:09 | 7566.24 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 253.16 | 08-OCT-02:00 |
November | 677.52 | 04-NOV-18:10 | 895.88 | 01-NOV-09:09 | 6627.44 | 01-NOV-10:09 | 7566.24 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 375.30 | 23-NOV-02:00 |
December | 677.52 | 02-DEC-19:10 | 895.88 | 01-DEC-10:09 | 6627.44 | 01-DEC-11:09 | 7566.24 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 383.99 | 02-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 895.88 | 6627.44 | 7566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 75.78 | ||||||
Maximum of Months | 677.52 | 895.88 | 6627.44 | 7566.24 | 0.00 | 0.00 | 0.00 | 20.37 | 436.07 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 737.29 | 01-JAN-00:53 | 1846.04 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513.90 | 01-FEB-00:01 | 1851.30 | 03-FEB-12:50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660.85 | 23-MAR-06:25 | 2418.01 | 18-MAR-13:30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.53 | 10-APR-04:55 | 2557.55 | 03-APR-13:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.22 | 29-MAY-01:55 | 2616.28 | 14-MAY-11:50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.58 | 03-JUN-23:00 | 2611.34 | 03-JUN-13:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561.10 | 02-JUL-04:00 | 2452.74 | 02-JUL-12:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.08 | 30-AUG-00:10 | 2257.38 | 25-AUG-13:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.68 | 02-SEP-23:10 | 2220.71 | 11-SEP-13:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.84 | 09-OCT-07:12 | 1956.17 | 12-OCT-11:20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.06 | 28-NOV-07:53 | 1495.62 | 18-NOV-12:40 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.57 | 16-DEC-08:63 | 1201.53 | 21-DEC-12:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.06 | 1201.53 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 737.29 | 2616.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13928.83 | 02-JAN-00:01 | 5252.67 | 648.56 | 3846.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.48 |
February | 15086.38 | 06-FEB-00:01 | 5252.67 | 648.56 | 3846.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.63 |
March | 10159.01 | 22-MAR-23:01 | 5252.67 | 648.56 | 3846.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.94 |
April | 18914.61 | 08-APR-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.03 |
May | 23307.38 | 28-MAY-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.07 |
June | 28381.56 | 04-JUN-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.23 |
July | 24530.01 | 11-JUL-02:61 | 0.00 | 200.07 | 2043.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 |
August | 25251.74 | 19-AUG-02:61 | 0.00 | 200.07 | 2043.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.92 |
September | 29678.43 | 02-SEP-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 |
October | 24243.86 | 06-OCT-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.74 |
November | 10623.56 | 24-NOV-00:01 | 5252.67 | 648.56 | 3846.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 |
December | 10641.95 | 22-DEC-00:01 | 5252.67 | 648.56 | 3846.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10159.01 | 0.00 | 200.07 | 2043.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.23 | |
Maximum of Months | 29678.43 | 5252.67 | 648.56 | 3846.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 30322.60 | 02-JAN-05:01 | 376.40 | 250.09 | 30887.20 | 31308.57 | 0.00 | 0.00 | 0.00 | 0.00 | 32.28 |
February | 30549.59 | 06-FEB-05:01 | 338.76 | 225.08 | 27798.48 | 28177.71 | 0.00 | 0.00 | 0.00 | 0.00 | 92.03 |
March | 27420.94 | 28-MAR-04:01 | 376.40 | 250.09 | 30887.20 | 31308.57 | 0.00 | 0.00 | 0.00 | 0.00 | 31.75 |
April | 34194.17 | 28-APR-04:01 | 301.12 | 200.07 | 24709.76 | 25046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 24.68 |
May | 40782.95 | 21-MAY-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 69.26 |
June | 38892.16 | 03-JUN-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 93.66 |
July | 28862.86 | 11-JUL-02:11 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.24 |
August | 32799.98 | 08-AUG-02:11 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.89 |
September | 41474.57 | 29-SEP-02:11 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.86 |
October | 43800.15 | 07-OCT-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.72 |
November | 31118.54 | 05-NOV-02:61 | 0.00 | 225.08 | 9049.66 | 4696.28 | 0.00 | 0.00 | 0.00 | 0.00 | 134.33 |
December | 25614.27 | 22-DEC-05:01 | 376.40 | 250.09 | 30887.20 | 31308.57 | 0.00 | 0.00 | 0.00 | 0.00 | 36.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25614.27 | 0.00 | 200.07 | 9049.66 | 4696.28 | 0.00 | 0.00 | 0.00 | 0.00 | 24.68 | |
Maximum of Months | 43800.15 | 376.40 | 250.09 | 30887.20 | 31308.57 | 0.00 | 0.00 | 0.00 | 0.00 | 134.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.77 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513.90 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.42 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.29 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.27 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.12 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.76 | 0.00 |
August | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.30 | 0.00 |
September | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.65 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.60 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.38 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.29 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513.90 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.309520E+11 | 20116.84 | 02-JAN-11:09 | 0.109076E+12 | 91416.95 | 02-JAN-11:20 |
February | 0.279041E+11 | 20188.84 | 06-FEB-11:09 | 0.105099E+12 | 99302.06 | 06-FEB-11:09 |
March | 0.304073E+11 | 19895.43 | 17-MAR-10:09 | 0.845482E+11 | 75824.64 | 17-MAR-12:09 |
April | 0.296038E+11 | 24498.19 | 08-APR-10:20 | 0.630694E+11 | 56485.41 | 01-APR-10:09 |
May | 0.320684E+11 | 26787.20 | 31-MAY-10:20 | 0.543115E+11 | 45054.53 | 04-MAY-10:20 |
June | 0.389329E+11 | 35132.85 | 19-JUN-10:20 | 0.504868E+11 | 43412.80 | 01-JUN-12:20 |
July | 0.485383E+11 | 33528.77 | 06-JUL-10:20 | 0.515256E+11 | 42722.34 | 02-JUL-12:50 |
August | 0.469476E+11 | 34536.35 | 04-AUG-10:20 | 0.514011E+11 | 42450.60 | 31-AUG-12:00 |
September | 0.366918E+11 | 30129.44 | 14-SEP-11:20 | 0.501158E+11 | 42937.44 | 29-SEP-12:20 |
October | 0.323345E+11 | 26808.79 | 25-OCT-10:20 | 0.557217E+11 | 47421.52 | 31-OCT-10:39 |
November | 0.296130E+11 | 19830.58 | 24-NOV-11:09 | 0.721293E+11 | 66487.28 | 22-NOV-11:09 |
December | 0.307703E+11 | 19861.97 | 22-DEC-11:09 | 0.934660E+11 | 76904.71 | 31-DEC-20:00 |
Annual Sum or Average | 0.414764E+12 | 0.840951E+12 | ||||
Minimum of Months | 0.279041E+11 | 19830.58 | 0.501158E+11 | 42450.60 | ||
Maximum of Months | 0.485383E+11 | 35132.85 | 0.109076E+12 | 99302.06 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.187271E+10 | 0.118155E+10 | 0.203399E+11 | 0.00 | 0.459669E+10 | 0.79 | 0.00 | 236812.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166723E+10 | 0.967264E+09 | 0.183715E+11 | 0.00 | 0.423890E+10 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183927E+10 | 0.933607E+09 | 0.203400E+11 | 0.00 | 0.426095E+10 | 0.80 | 0.00 | 21780308.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172164E+10 | 0.766012E+09 | 0.196837E+11 | 0.00 | 0.391170E+10 | 0.77 | 0.00 | 0.488226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176736E+10 | 0.692320E+09 | 0.203399E+11 | 0.00 | 0.396258E+10 | 0.80 | 0.00 | 0.200038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.170647E+10 | 0.621752E+09 | 0.196839E+11 | 0.00 | 0.408678E+10 | 0.77 | 0.00 | 0.953344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.173402E+10 | 0.656009E+09 | 0.203398E+11 | 0.00 | 0.470046E+10 | 0.79 | 0.00 | 0.176790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179241E+10 | 0.737683E+09 | 0.203400E+11 | 0.00 | 0.464557E+10 | 0.80 | 0.00 | 0.160059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173683E+10 | 0.843136E+09 | 0.196837E+11 | 0.00 | 0.399257E+10 | 0.77 | 0.00 | 0.715906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.181815E+10 | 0.101416E+10 | 0.203399E+11 | 0.00 | 0.400106E+10 | 0.79 | 0.00 | 0.189488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180436E+10 | 0.110707E+10 | 0.196838E+11 | 0.00 | 0.403653E+10 | 0.77 | 0.00 | 16727892.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187238E+10 | 0.121182E+10 | 0.203398E+11 | 0.00 | 0.438196E+10 | 0.79 | 0.00 | 544373.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213328E+11 | 0.107324E+11 | 0.239486E+12 | 0.00 | 0.508158E+11 | 9.37 | 0.00 | 0.548002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.166723E+10 | 0.621752E+09 | 0.183715E+11 | 0.00 | 0.391170E+10 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.187271E+10 | 0.121182E+10 | 0.203400E+11 | 0.00 | 0.470046E+10 | 0.80 | 0.00 | 0.176790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.383373E+11 | 0.00 | 0.540632E+11 | 0.00 | 0.166758E+11 | 0.00 | 0.00 |
February | 0.346273E+11 | 0.00 | 0.552750E+11 | 0.00 | 0.151965E+11 | 0.00 | 0.00 |
March | 0.383373E+11 | 0.00 | 0.296982E+11 | 0.00 | 0.165127E+11 | 0.00 | 0.00 |
April | 0.371007E+11 | 0.00 | 0.107588E+11 | 0.00 | 0.152100E+11 | 0.00 | 0.00 |
May | 0.383373E+11 | 0.00 | 0.123025E+10 | 0.00 | 0.147439E+11 | 0.00 | 0.00 |
June | 0.371007E+11 | 0.00 | 1205795.17 | 0.00 | 0.133850E+11 | 0.00 | 0.00 |
July | 0.383373E+11 | 0.00 | 0.00 | 0.00 | 0.131883E+11 | 0.00 | 0.00 |
August | 0.383373E+11 | 0.00 | 375988.35 | 0.00 | 0.130633E+11 | 0.00 | 0.00 |
September | 0.371007E+11 | 0.00 | 62705390.87 | 0.00 | 0.129524E+11 | 0.00 | 0.00 |
October | 0.383373E+11 | 0.00 | 0.322005E+10 | 0.00 | 0.141644E+11 | 0.00 | 0.00 |
November | 0.371007E+11 | 0.00 | 0.203487E+11 | 0.00 | 0.146799E+11 | 0.00 | 0.00 |
December | 0.383373E+11 | 0.00 | 0.390665E+11 | 0.00 | 0.160622E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.451391E+12 | 0.00 | 0.213725E+12 | 0.00 | 0.175834E+12 | 0.00 | 0.00 |
Minimum of Months | 0.346273E+11 | 0.00 | 0.00 | 0.00 | 0.129524E+11 | 0.00 | 0.00 |
Maximum of Months | 0.383373E+11 | 0.00 | 0.552750E+11 | 0.00 | 0.166758E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1285.01 | 02-JAN-16:40 | 952.15 | 01-JAN-06:10 | 12932.59 | 01-JAN-11:09 | 0.00 | 2520.38 | 02-JAN-07:10 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 1285.01 | 01-FEB-17:10 | 952.15 | 01-FEB-06:10 | 12932.59 | 01-FEB-11:09 | 0.00 | 2573.66 | 06-FEB-07:10 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 1285.01 | 01-MAR-17:49 | 952.15 | 01-MAR-06:10 | 12932.59 | 01-MAR-11:09 | 0.00 | 2282.60 | 23-MAR-06:10 | 0.00 | 17-MAR-13:39 | 0.00 | 01-MAR-00:10 |
April | 1285.01 | 01-APR-18:19 | 952.15 | 01-APR-05:10 | 12932.59 | 01-APR-10:09 | 0.00 | 2082.04 | 01-APR-06:10 | 0.00 | 01-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 1285.01 | 01-MAY-18:49 | 952.15 | 01-MAY-18:49 | 12932.59 | 01-MAY-10:09 | 0.00 | 2026.72 | 31-MAY-11:09 | 0.00 | 05-MAY-11:20 | 0.00 | 01-MAY-00:10 |
June | 1285.01 | 01-JUN-19:19 | 952.15 | 01-JUN-19:19 | 12932.59 | 01-JUN-10:09 | 0.00 | 3216.77 | 19-JUN-11:00 | 0.00 | 01-JUN-09:39 | 0.00 | 01-JUN-00:10 |
July | 1285.01 | 01-JUL-19:30 | 952.15 | 01-JUL-19:30 | 12932.59 | 01-JUL-10:09 | 0.00 | 3023.46 | 20-JUL-11:00 | 0.00 | 07-JUL-09:39 | 0.00 | 01-JUL-00:10 |
August | 1285.01 | 01-AUG-18:00 | 952.15 | 01-AUG-19:10 | 12932.59 | 01-AUG-10:09 | 0.00 | 3184.05 | 04-AUG-11:00 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 1285.01 | 01-SEP-18:30 | 952.15 | 01-SEP-05:10 | 12932.59 | 01-SEP-10:09 | 0.00 | 2637.69 | 07-SEP-12:00 | 0.00 | 25-SEP-10:39 | 0.00 | 01-SEP-00:10 |
October | 1285.01 | 02-OCT-17:40 | 952.15 | 01-OCT-05:10 | 12932.59 | 01-OCT-10:09 | 0.00 | 2044.28 | 29-OCT-06:00 | 0.00 | 09-OCT-08:30 | 0.00 | 01-OCT-00:10 |
November | 1285.01 | 01-NOV-16:49 | 952.15 | 01-NOV-05:10 | 12932.59 | 01-NOV-10:09 | 0.00 | 2274.05 | 23-NOV-07:10 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 1285.01 | 01-DEC-16:30 | 952.15 | 01-DEC-06:10 | 12932.59 | 01-DEC-11:09 | 0.00 | 2366.22 | 31-DEC-20:00 | 0.00 | 28-DEC-10:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1285.01 | 952.15 | 12932.59 | 0.00 | 2026.72 | 0.00 | 0.00 | ||||||
Maximum of Months | 1285.01 | 952.15 | 12932.59 | 0.00 | 3216.77 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 245.12 | 24-JAN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2432.02 | 27-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6322.30 | 07-APR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9158.01 | 31-MAY-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17297.06 | 19-JUN-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15081.16 | 07-JUL-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15786.11 | 04-AUG-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12753.25 | 07-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8900.89 | 25-OCT-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1133.48 | 10-NOV-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 346.35 | 05-DEC-04:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17297.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 20116.84 | 02-JAN-11:09 | 989.27 | 12932.59 | 0.00 | 0.00 | 2367.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20188.84 | 06-FEB-11:09 | 989.27 | 12932.59 | 0.00 | 0.00 | 2438.97 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19895.43 | 17-MAR-10:09 | 989.27 | 12932.59 | 0.00 | 0.00 | 2136.65 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24498.19 | 08-APR-10:20 | 879.34 | 12932.59 | 0.00 | 0.00 | 1713.48 | 0.00 | 0.00 | 5066.60 | 0.00 |
May | 26787.20 | 31-MAY-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 1750.50 | 0.00 | 0.00 | 7186.59 | 0.00 |
June | 35132.85 | 19-JUN-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 2795.57 | 0.00 | 0.00 | 14484.28 | 0.00 |
July | 33528.77 | 06-JUL-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 2675.14 | 0.00 | 0.00 | 13000.63 | 0.00 |
August | 34536.35 | 04-AUG-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 2833.55 | 0.00 | 0.00 | 13849.80 | 0.00 |
September | 30129.44 | 14-SEP-11:20 | 989.27 | 12081.43 | 0.00 | 0.00 | 2627.33 | 0.00 | 0.00 | 12710.68 | 0.00 |
October | 26808.79 | 25-OCT-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 1751.63 | 0.00 | 0.00 | 7204.16 | 0.00 |
November | 19830.58 | 24-NOV-11:09 | 989.27 | 12932.59 | 0.00 | 0.00 | 2074.48 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19861.97 | 22-DEC-11:09 | 989.27 | 12932.59 | 0.00 | 0.00 | 2107.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 19830.58 | 879.34 | 12081.43 | 0.00 | 0.00 | 1713.48 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35132.85 | 989.27 | 12932.59 | 0.00 | 0.00 | 2833.55 | 0.00 | 0.00 | 14484.28 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 25220.79 | 01-JAN-11:09 | 0.00 | 63816.53 | 05-JAN-03:09 | 0.00 | 23362.05 | 30-JAN-13:00 | 0.00 |
February | 25220.79 | 01-FEB-11:09 | 0.00 | 67509.24 | 06-FEB-07:10 | 0.00 | 23375.86 | 09-FEB-13:20 | 0.00 |
March | 25220.79 | 01-MAR-11:09 | 0.00 | 43712.11 | 23-MAR-06:10 | 0.00 | 23295.64 | 01-MAR-13:20 | 0.00 |
April | 25220.79 | 01-APR-10:09 | 0.00 | 27264.57 | 01-APR-06:10 | 0.00 | 22979.16 | 01-APR-12:00 | 0.00 |
May | 25220.79 | 01-MAY-10:09 | 0.00 | 10760.99 | 01-MAY-05:10 | 0.00 | 22397.45 | 01-MAY-12:30 | 0.00 |
June | 25220.79 | 01-JUN-10:09 | 0.00 | 1893.20 | 26-JUN-03:30 | 0.00 | 21670.74 | 01-JUN-12:20 | 0.00 |
July | 25220.79 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 20980.28 | 02-JUL-12:50 | 0.00 |
August | 25220.79 | 01-AUG-10:09 | 0.00 | 626.65 | 30-AUG-02:30 | 0.00 | 20708.54 | 31-AUG-12:00 | 0.00 |
September | 25220.79 | 01-SEP-10:09 | 0.00 | 4340.56 | 24-SEP-06:10 | 0.00 | 21195.38 | 29-SEP-12:20 | 0.00 |
October | 25220.79 | 01-OCT-10:09 | 0.00 | 23956.95 | 29-OCT-06:00 | 0.00 | 21970.08 | 31-OCT-12:20 | 0.00 |
November | 25220.79 | 01-NOV-10:09 | 0.00 | 42562.86 | 23-NOV-07:10 | 0.00 | 22641.46 | 30-NOV-13:20 | 0.00 |
December | 25220.79 | 01-DEC-11:09 | 0.00 | 50444.84 | 31-DEC-23:30 | 0.00 | 23135.94 | 31-DEC-13:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 25220.79 | 0.00 | 0.00 | 0.00 | 20708.54 | 0.00 | |||
Maximum of Months | 25220.79 | 0.00 | 67509.24 | 0.00 | 23375.86 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.50 | 20.20 | 0.33 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 |
February | 14.50 | 19.77 | 0.00 | 19.77 | 0.00 | 19.77 | 0.00 | 19.77 |
March | 1.67 | 20.50 | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
April | 0.33 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.59 | 0.00 | 24.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 24.73 | 0.00 | 24.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 24.78 | 0.33 | 24.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.74 | 0.00 | 24.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.56 | 0.00 | 24.56 |
November | 0.50 | 20.51 | 0.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
December | 2.17 | 20.51 | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Annual Sum or Average | 32.67 | 20.05 | 0.83 | 20.06 | 46.17 | 22.76 | 0.33 | 22.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.50 | 20.53 | 0.33 | 20.53 | 14.83 | 24.78 | 0.33 | 24.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.89 | 0.00 | 26.89 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.33 | 0.00 | 27.33 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.51 | 0.00 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.81 | 0.00 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 29.08 | 2.33 | 28.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 56.50 | 28.47 | 28.17 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 68.83 | 28.29 | 40.67 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 29.46 | 0.00 | 29.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 28.27 | 0.00 | 28.27 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.32 | 0.00 | 27.32 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.84 | 0.00 | 26.84 |
Annual Sum or Average | 0.00 | 0.00 | 213.50 | 28.45 | 71.17 | 28.15 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 68.83 | 29.46 | 40.67 | 29.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.86 | 201.50 | 20.74 | 201.50 | 20.66 |
February | 551.00 | 20.85 | 199.50 | 20.73 | 199.50 | 20.66 |
March | 605.17 | 20.94 | 91.50 | 20.81 | 86.50 | 20.69 |
April | 499.33 | 21.12 | 79.17 | 21.22 | 33.83 | 21.12 |
May | 383.17 | 21.78 | 182.50 | 22.38 | 49.17 | 22.44 |
June | 348.83 | 23.78 | 537.83 | 23.85 | 322.17 | 23.86 |
July | 442.33 | 23.99 | 609.00 | 23.98 | 442.33 | 23.98 |
August | 278.50 | 24.01 | 599.67 | 23.98 | 274.67 | 23.99 |
September | 229.83 | 23.17 | 466.67 | 23.66 | 138.33 | 23.70 |
October | 419.67 | 21.87 | 245.83 | 22.52 | 96.67 | 22.63 |
November | 575.67 | 21.02 | 52.67 | 20.91 | 48.33 | 20.80 |
December | 609.00 | 20.88 | 103.83 | 20.72 | 103.83 | 20.59 |
Annual Sum or Average | 5552.50 | 21.74 | 3369.67 | 22.26 | 1996.83 | 22.32 |
Minimum of Months | 229.83 | 20.85 | 52.67 | 20.72 | 33.83 | 20.59 |
Maximum of Months | 610.00 | 24.01 | 609.00 | 23.98 | 442.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 609.33 | 18.93 | 331.50 | 18.81 | 331.50 | 18.76 |
February | 551.00 | 18.79 | 344.17 | 18.73 | 344.17 | 18.70 |
March | 571.67 | 19.24 | 207.17 | 19.26 | 183.67 | 19.16 |
April | 436.50 | 20.81 | 254.83 | 21.70 | 138.33 | 21.82 |
May | 377.17 | 24.79 | 495.67 | 25.01 | 295.33 | 25.21 |
June | 554.83 | 26.10 | 590.50 | 26.06 | 554.83 | 26.07 |
July | 609.00 | 26.26 | 609.00 | 26.26 | 609.00 | 26.26 |
August | 600.67 | 26.28 | 612.00 | 26.27 | 600.67 | 26.27 |
September | 496.17 | 26.05 | 581.17 | 25.92 | 491.50 | 25.97 |
October | 408.50 | 23.87 | 420.17 | 24.47 | 266.67 | 24.77 |
November | 479.67 | 19.69 | 187.00 | 20.14 | 106.33 | 20.05 |
December | 609.00 | 18.90 | 227.50 | 18.79 | 227.50 | 18.72 |
Annual Sum or Average | 6303.50 | 22.40 | 4860.67 | 23.05 | 4149.50 | 23.27 |
Minimum of Months | 377.17 | 18.79 | 187.00 | 18.73 | 106.33 | 18.70 |
Maximum of Months | 609.33 | 26.28 | 612.00 | 26.27 | 609.00 | 26.27 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.86269 | 26.43757 | -0.5095 | 11.43414 |
February | 551.00000 | 20.85282 | 21.23388 | -0.5383 | 12.05342 |
March | 612.00000 | 20.97317 | 33.00999 | -0.3931 | 9.31488 |
April | 590.00000 | 21.52520 | 41.03822 | -0.1810 | 8.03046 |
May | 611.00000 | 22.52936 | 49.46574 | -0.8399 | 23.45652 |
June | 592.00000 | 23.81253 | 61.63753 | -0.2566 | 7.15732 |
July | 609.00000 | 23.97178 | 68.89562 | -0.1085 | 5.48920 |
August | 612.00000 | 23.95264 | 60.57630 | -0.1396 | 5.91353 |
September | 590.00000 | 23.57486 | 54.87517 | -0.3455 | 9.44784 |
October | 610.00000 | 22.43376 | 47.70929 | 0.19104 | 9.15044 |
November | 591.00000 | 21.09046 | 36.21554 | -0.3034 | 8.11581 |
December | 609.00000 | 20.87964 | 26.48738 | -0.4684 | 10.37504 |
Annual Sum or Average | 7187.00000 | 22.21313 | 44.10711 | -0.3233 | 9.99817 |
Minimum of Months | 551.00000 | 20.85282 | 21.23388 | -0.8399 | 5.48920 |
Maximum of Months | 612.00000 | 23.97178 | 68.89562 | 0.19104 | 23.45652 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.92966 | 35.77373 | -0.6076 | 14.06447 |
February | 551.00000 | 18.79497 | 30.78963 | -0.6763 | 15.44293 |
March | 612.00000 | 19.51191 | 42.51005 | -0.4273 | 12.01247 |
April | 590.00000 | 21.57739 | 46.54177 | 0.08965 | 13.44236 |
May | 611.00000 | 24.47247 | 48.82762 | 0.07042 | 12.67159 |
June | 592.00000 | 26.00816 | 56.19312 | 0.69496 | 16.28761 |
July | 609.00000 | 26.25996 | 62.44498 | 0.85764 | 21.04705 |
August | 612.00000 | 26.25641 | 56.82156 | 0.82397 | 20.30928 |
September | 590.00000 | 25.74376 | 51.17855 | 0.59088 | 14.85895 |
October | 610.00000 | 23.78051 | 47.71276 | 0.68598 | 22.56262 |
November | 591.00000 | 20.39163 | 43.18156 | -0.1798 | 11.05734 |
December | 609.00000 | 18.90408 | 36.06673 | -0.5917 | 13.31333 |
Annual Sum or Average | 7187.00000 | 22.57476 | 46.60522 | 0.11543 | 15.60807 |
Minimum of Months | 551.00000 | 18.79497 | 30.78963 | -0.6763 | 11.05734 |
Maximum of Months | 612.00000 | 26.25996 | 62.44498 | 0.85764 | 22.56262 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 23903560.82 | 7273546.71 | 3.33 | 16360986.00 | 7542574.82 | 0.00 | 0.26 | 27-MAR-16:05 | 0.00 | 01-MAR-00:01 | 4315.90 | 27-MAR-16:05 | 3019.14 | 27-MAR-16:10 | 1297.74 | 27-MAR-16:05 | 1285.25 | 27-MAR-16:05 | 0.00 | 01-MAR-00:01 |
April | 0.643920E+09 | 0.184732E+09 | 40.02 | 0.525989E+09 | 0.117931E+09 | 0.00 | 1.00 | 08-APR-02:61 | 0.00 | 01-APR-00:01 | 20135.26 | 08-APR-02:61 | 13452.13 | 08-APR-02:61 | 6683.13 | 08-APR-02:61 | 4917.37 | 08-APR-02:61 | 0.00 | 01-APR-00:01 |
May | 0.277174E+10 | 0.772704E+09 | 137.57 | 0.217638E+10 | 0.595362E+09 | 0.00 | 1.00 | 28-MAY-02:61 | 0.00 | 01-MAY-00:01 | 40316.76 | 31-MAY-02:61 | 22691.35 | 31-MAY-02:61 | 17625.41 | 31-MAY-02:61 | 9838.37 | 31-MAY-02:61 | 0.00 | 01-MAY-00:01 |
June | 0.159122E+11 | 0.410652E+10 | 432.94 | 0.935836E+10 | 0.655386E+10 | 0.00 | 1.00 | 01-JUN-02:62 | 0.00 | 01-JUN-00:01 | 44683.55 | 27-JUN-02:61 | 34127.07 | 04-JUN-02:61 | 28438.12 | 27-JUN-02:61 | 10139.91 | 27-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.328408E+11 | 0.804713E+10 | 615.78 | 0.172927E+11 | 0.155482E+11 | 0.00 | 1.00 | 01-JUL-02:62 | 0.00 | 01-JUL-00:01 | 44794.57 | 20-JUL-02:61 | 28614.36 | 11-JUL-02:19 | 29898.72 | 22-JUL-02:61 | 10148.22 | 07-JUL-02:61 | 0.00 | 01-JUL-00:01 |
August | 0.302192E+11 | 0.749241E+10 | 568.10 | 0.179090E+11 | 0.123102E+11 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:02 | 44794.57 | 05-AUG-02:02 | 33698.26 | 25-AUG-02:61 | 29910.17 | 17-AUG-02:61 | 10148.22 | 03-AUG-02:61 | 0.00 | 01-AUG-00:02 |
September | 0.117074E+11 | 0.307815E+10 | 372.19 | 0.726773E+10 | 0.443963E+10 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:02 | 44794.57 | 14-SEP-02:61 | 32641.89 | 11-SEP-02:61 | 28109.33 | 14-SEP-02:61 | 10148.22 | 14-SEP-02:61 | 0.00 | 01-SEP-00:02 |
October | 0.238096E+10 | 0.657093E+09 | 113.61 | 0.146507E+10 | 0.915894E+09 | 0.00 | 1.00 | 03-OCT-02:61 | 0.00 | 01-OCT-00:01 | 41739.38 | 06-OCT-02:61 | 21876.36 | 14-OCT-02:61 | 22955.93 | 24-OCT-02:61 | 9913.15 | 06-OCT-03:22 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.965002E+11 | 0.243460E+11 | 2283.54 | 0.560116E+11 | 0.404886E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.328408E+11 | 0.804713E+10 | 615.78 | 0.179090E+11 | 0.155482E+11 | 0.00 | 1.00 | 0.00 | 44794.57 | 34127.07 | 29910.17 | 10148.22 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 797743.81 | 236812.98 | 0.26 | 457766.62 | 339977.19 | 0.00 | 0.29 | 24-JAN-04:10 | 0.00 | 01-JAN-00:01 | 3377.00 | 24-JAN-04:10 | 1661.07 | 24-JAN-04:10 | 1715.93 | 24-JAN-04:10 | 980.50 | 24-JAN-04:10 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 50153968.02 | 14506761.50 | 5.61 | 32644299.52 | 17509668.50 | 0.00 | 1.00 | 28-MAR-03:22 | 0.00 | 01-MAR-00:01 | 17036.99 | 28-MAR-04:01 | 11220.05 | 28-MAR-04:01 | 5816.95 | 28-MAR-04:01 | 4086.64 | 28-MAR-04:01 | 0.00 | 01-MAR-00:01 |
April | 0.111553E+10 | 0.303494E+09 | 71.61 | 0.880771E+09 | 0.234759E+09 | 0.00 | 1.00 | 07-APR-02:61 | 0.00 | 01-APR-00:01 | 27960.76 | 07-APR-03:22 | 24942.65 | 11-APR-02:61 | 14248.44 | 09-APR-02:61 | 6703.57 | 07-APR-02:61 | 0.00 | 01-APR-00:01 |
May | 0.466854E+10 | 0.122768E+10 | 221.95 | 0.356581E+10 | 0.110274E+10 | 0.00 | 1.00 | 03-MAY-02:62 | 0.00 | 01-MAY-00:01 | 27960.76 | 05-MAY-03:22 | 25308.22 | 13-MAY-02:61 | 16519.01 | 19-MAY-02:61 | 6703.57 | 05-MAY-02:61 | 0.00 | 01-MAY-00:01 |
June | 0.227203E+11 | 0.542692E+10 | 530.35 | 0.126050E+11 | 0.101153E+11 | 0.00 | 1.00 | 01-JUN-02:11 | 0.00 | 01-JUN-00:01 | 31066.25 | 15-JUN-10:35 | 26652.24 | 19-JUN-10:53 | 20775.58 | 27-JUN-02:61 | 7712.76 | 19-JUN-11:55 | 0.00 | 01-JUN-00:01 |
July | 0.422973E+11 | 0.963192E+10 | 639.73 | 0.208956E+11 | 0.214017E+11 | 0.00 | 1.00 | 01-JUL-02:11 | 0.00 | 01-JUL-00:01 | 31066.25 | 07-JUL-02:42 | 24215.92 | 07-JUL-10:52 | 21621.73 | 28-JUL-02:52 | 7333.96 | 07-JUL-12:20 | 0.00 | 01-JUL-00:01 |
August | 0.365813E+11 | 0.851350E+10 | 614.45 | 0.210245E+11 | 0.155568E+11 | 0.00 | 1.00 | 01-AUG-00:53 | 0.00 | 01-AUG-00:02 | 31066.25 | 13-AUG-02:61 | 23296.30 | 22-AUG-02:51 | 21453.50 | 16-AUG-22:00 | 7308.70 | 04-AUG-18:55 | 0.00 | 01-AUG-00:02 |
September | 0.167549E+11 | 0.408091E+10 | 457.19 | 0.985913E+10 | 0.689578E+10 | 0.00 | 1.00 | 01-SEP-00:53 | 0.00 | 01-SEP-00:02 | 31066.25 | 14-SEP-10:33 | 21178.42 | 02-SEP-01:23 | 20577.57 | 14-SEP-02:52 | 6914.69 | 07-SEP-13:50 | 0.00 | 01-SEP-00:02 |
October | 0.478197E+10 | 0.123778E+10 | 206.49 | 0.269746E+10 | 0.208451E+10 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:01 | 28811.90 | 06-OCT-04:02 | 25784.42 | 26-OCT-02:11 | 17916.20 | 15-OCT-02:61 | 6760.63 | 06-OCT-04:02 | 0.00 | 01-OCT-00:01 |
November | 59412284.36 | 16727892.64 | 10.50 | 39720369.22 | 19691915.14 | 0.00 | 1.00 | 03-NOV-03:21 | 0.00 | 01-NOV-00:01 | 27960.76 | 10-NOV-04:22 | 13781.90 | 05-NOV-02:61 | 15270.60 | 10-NOV-04:22 | 6703.57 | 10-NOV-04:22 | 0.00 | 01-NOV-00:01 |
December | 1797728.81 | 544373.87 | 0.44 | 1155121.04 | 642607.77 | 0.00 | 0.15 | 01-DEC-04:40 | 0.00 | 01-DEC-00:01 | 1649.80 | 01-DEC-04:40 | 1072.67 | 01-DEC-04:40 | 577.14 | 01-DEC-04:40 | 496.01 | 01-DEC-04:40 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.129032E+12 | 0.304542E+11 | 2758.61 | 0.716022E+11 | 0.574297E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.422973E+11 | 0.963192E+10 | 639.73 | 0.210245E+11 | 0.214017E+11 | 0.00 | 1.00 | 0.00 | 31066.25 | 26652.24 | 21621.73 | 7712.76 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.23 | 27.35 | 40.87 | 43.23 | 174.93 | 0.00 | 0.00 | 0.00 |
February | 105.80 | 49.36 | 56.45 | 77.51 | 171.24 | 0.00 | 0.00 | 0.00 |
March | 134.97 | 57.40 | 77.57 | 126.01 | 115.98 | 0.00 | 0.00 | 0.00 |
April | 161.98 | 70.95 | 91.03 | 175.91 | 79.24 | 0.00 | 0.00 | 0.00 |
May | 196.44 | 78.51 | 117.93 | 242.30 | 49.80 | 0.00 | 0.00 | 0.00 |
June | 182.06 | 65.91 | 116.16 | 247.20 | 29.17 | 0.00 | 0.00 | 0.00 |
July | 182.86 | 65.99 | 116.87 | 268.80 | 15.56 | 0.00 | 0.00 | 0.00 |
August | 205.90 | 92.84 | 113.06 | 298.46 | 22.18 | 0.00 | 0.00 | 0.00 |
September | 153.56 | 68.90 | 84.67 | 197.87 | 44.46 | 0.00 | 0.00 | 0.00 |
October | 139.22 | 63.10 | 76.12 | 160.88 | 80.14 | 0.00 | 0.00 | 0.00 |
November | 86.10 | 33.06 | 53.03 | 73.20 | 120.27 | 0.00 | 0.00 | 0.00 |
December | 67.07 | 31.49 | 35.58 | 46.81 | 158.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.57 | 58.81 | 81.77 | 163.77 | 88.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.07 | 27.35 | 35.58 | 43.23 | 15.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 205.90 | 92.84 | 117.93 | 298.46 | 174.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 337.94 | 221.29 | 116.66 | 346.40 | 330.59 | 0.00 | 0.00 | 0.00 |
February | 445.73 | 295.04 | 150.69 | 468.04 | 323.98 | 0.00 | 0.00 | 0.00 |
March | 402.13 | 223.19 | 178.94 | 451.54 | 228.58 | 0.00 | 0.00 | 0.00 |
April | 312.04 | 123.39 | 188.65 | 364.59 | 165.71 | 0.00 | 0.00 | 0.00 |
May | 273.46 | 57.04 | 216.42 | 340.76 | 103.66 | 0.00 | 0.00 | 0.00 |
June | 256.63 | 39.23 | 217.40 | 359.84 | 60.60 | 0.00 | 0.00 | 0.00 |
July | 269.00 | 46.73 | 222.28 | 418.15 | 31.35 | 0.00 | 0.00 | 0.00 |
August | 359.22 | 133.24 | 225.98 | 556.67 | 45.88 | 0.00 | 0.00 | 0.00 |
September | 389.77 | 201.60 | 188.16 | 536.05 | 90.97 | 0.00 | 0.00 | 0.00 |
October | 533.94 | 334.82 | 199.12 | 689.52 | 158.77 | 0.00 | 0.00 | 0.00 |
November | 370.24 | 222.35 | 147.90 | 414.27 | 233.63 | 0.00 | 0.00 | 0.00 |
December | 366.28 | 260.03 | 106.24 | 392.93 | 297.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 359.29 | 179.25 | 180.05 | 444.99 | 171.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 256.63 | 39.23 | 106.24 | 340.76 | 31.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 533.94 | 334.82 | 225.98 | 689.52 | 330.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.35 | 27.59 | 39.77 | 42.81 | 178.28 | 0.00 | 0.00 | 0.00 |
February | 99.32 | 43.62 | 55.70 | 71.24 | 177.94 | 0.00 | 0.00 | 0.00 |
March | 146.66 | 67.71 | 78.95 | 140.59 | 114.26 | 0.00 | 0.00 | 0.00 |
April | 160.30 | 68.59 | 91.71 | 174.43 | 80.82 | 0.00 | 0.00 | 0.00 |
May | 186.73 | 70.91 | 115.82 | 230.04 | 50.44 | 0.00 | 0.00 | 0.00 |
June | 204.37 | 82.43 | 121.94 | 278.70 | 29.53 | 0.00 | 0.00 | 0.00 |
July | 191.40 | 72.08 | 119.33 | 280.46 | 15.53 | 0.00 | 0.00 | 0.00 |
August | 211.74 | 98.02 | 113.72 | 307.61 | 22.64 | 0.00 | 0.00 | 0.00 |
September | 150.32 | 65.69 | 84.63 | 194.48 | 45.34 | 0.00 | 0.00 | 0.00 |
October | 149.03 | 72.47 | 76.56 | 173.77 | 81.06 | 0.00 | 0.00 | 0.00 |
November | 69.99 | 20.23 | 49.76 | 50.17 | 123.88 | 0.00 | 0.00 | 0.00 |
December | 62.25 | 26.94 | 35.31 | 40.76 | 163.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.92 | 59.83 | 82.09 | 166.10 | 89.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.25 | 20.23 | 35.31 | 40.76 | 15.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.74 | 98.02 | 121.94 | 307.61 | 178.28 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182737E+09 | 73262745.50 | 0.109474E+09 | 0.115778E+09 | 0.468545E+09 |
February | 0.255962E+09 | 0.119406E+09 | 0.136556E+09 | 0.187523E+09 | 0.414275E+09 |
March | 0.361512E+09 | 0.153753E+09 | 0.207759E+09 | 0.337496E+09 | 0.310638E+09 |
April | 0.419845E+09 | 0.183905E+09 | 0.235940E+09 | 0.455954E+09 | 0.205385E+09 |
May | 0.526157E+09 | 0.210284E+09 | 0.315873E+09 | 0.648985E+09 | 0.133392E+09 |
June | 0.471906E+09 | 0.170826E+09 | 0.301080E+09 | 0.640749E+09 | 75605655.37 |
July | 0.489771E+09 | 0.176746E+09 | 0.313025E+09 | 0.719942E+09 | 41685220.17 |
August | 0.551494E+09 | 0.248668E+09 | 0.302826E+09 | 0.799407E+09 | 59398964.32 |
September | 0.398039E+09 | 0.178584E+09 | 0.219455E+09 | 0.512870E+09 | 0.115247E+09 |
October | 0.372880E+09 | 0.169002E+09 | 0.203879E+09 | 0.430901E+09 | 0.214646E+09 |
November | 0.223159E+09 | 85695159.08 | 0.137464E+09 | 0.189739E+09 | 0.311739E+09 |
December | 0.179649E+09 | 84351849.86 | 95296729.52 | 0.125387E+09 | 0.425434E+09 |
Annual Sum or Average | 0.443311E+10 | 0.185448E+10 | 0.257863E+10 | 0.516473E+10 | 0.277599E+10 |
Minimum of Months | 0.179649E+09 | 73262745.50 | 95296729.52 | 0.115778E+09 | 41685220.17 |
Maximum of Months | 0.551494E+09 | 0.248668E+09 | 0.315873E+09 | 0.799407E+09 | 0.468545E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.905141E+09 | 0.592692E+09 | 0.312449E+09 | 0.927787E+09 | 0.885446E+09 |
February | 0.107832E+10 | 0.713757E+09 | 0.364559E+09 | 0.113229E+10 | 0.783781E+09 |
March | 0.107708E+10 | 0.597796E+09 | 0.479282E+09 | 0.120941E+10 | 0.612241E+09 |
April | 0.808815E+09 | 0.319829E+09 | 0.488986E+09 | 0.945021E+09 | 0.429526E+09 |
May | 0.732434E+09 | 0.152774E+09 | 0.579660E+09 | 0.912701E+09 | 0.277651E+09 |
June | 0.665194E+09 | 0.101681E+09 | 0.563513E+09 | 0.932708E+09 | 0.157063E+09 |
July | 0.720499E+09 | 0.125150E+09 | 0.595348E+09 | 0.111998E+10 | 83980096.82 |
August | 0.962146E+09 | 0.356875E+09 | 0.605271E+09 | 0.149097E+10 | 0.122884E+09 |
September | 0.101027E+10 | 0.522553E+09 | 0.487718E+09 | 0.138945E+10 | 0.235796E+09 |
October | 0.143012E+10 | 0.896786E+09 | 0.533332E+09 | 0.184682E+10 | 0.425251E+09 |
November | 0.959675E+09 | 0.576330E+09 | 0.383345E+09 | 0.107378E+10 | 0.605575E+09 |
December | 0.981037E+09 | 0.696470E+09 | 0.284566E+09 | 0.105243E+10 | 0.797726E+09 |
Annual Sum or Average | 0.113307E+11 | 0.565269E+10 | 0.567803E+10 | 0.140333E+11 | 0.541692E+10 |
Minimum of Months | 0.665194E+09 | 0.101681E+09 | 0.284566E+09 | 0.912701E+09 | 83980096.82 |
Maximum of Months | 0.143012E+10 | 0.896786E+09 | 0.605271E+09 | 0.184682E+10 | 0.885446E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.180402E+09 | 73893230.13 | 0.106509E+09 | 0.114675E+09 | 0.477514E+09 |
February | 0.240284E+09 | 0.105534E+09 | 0.134751E+09 | 0.172339E+09 | 0.430470E+09 |
March | 0.392824E+09 | 0.181356E+09 | 0.211468E+09 | 0.376560E+09 | 0.306035E+09 |
April | 0.415489E+09 | 0.177777E+09 | 0.237712E+09 | 0.452117E+09 | 0.209496E+09 |
May | 0.500136E+09 | 0.189932E+09 | 0.310204E+09 | 0.616130E+09 | 0.135108E+09 |
June | 0.529727E+09 | 0.213654E+09 | 0.316073E+09 | 0.722386E+09 | 76535426.30 |
July | 0.512655E+09 | 0.193050E+09 | 0.319605E+09 | 0.751197E+09 | 41589989.13 |
August | 0.567136E+09 | 0.262546E+09 | 0.304590E+09 | 0.823900E+09 | 60631458.22 |
September | 0.389633E+09 | 0.170269E+09 | 0.219365E+09 | 0.504101E+09 | 0.117530E+09 |
October | 0.399169E+09 | 0.194106E+09 | 0.205063E+09 | 0.465432E+09 | 0.217107E+09 |
November | 0.181401E+09 | 52426212.36 | 0.128975E+09 | 0.130031E+09 | 0.321102E+09 |
December | 0.166731E+09 | 72145022.91 | 94586299.26 | 0.109165E+09 | 0.436970E+09 |
Annual Sum or Average | 0.447559E+10 | 0.188669E+10 | 0.258890E+10 | 0.523803E+10 | 0.283009E+10 |
Minimum of Months | 0.166731E+09 | 52426212.36 | 94586299.26 | 0.109165E+09 | 41589989.13 |
Maximum of Months | 0.567136E+09 | 0.262546E+09 | 0.319605E+09 | 0.823900E+09 | 0.477514E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 413.79 | 665.16 | 473.52 | 276.23 | 197.29 | 0.00 | 0.00 |
February | 591.26 | 647.63 | 650.86 | 388.02 | 262.84 | 0.00 | 0.00 |
March | 704.11 | 444.79 | 683.77 | 348.31 | 335.46 | 0.00 | 0.00 |
April | 703.69 | 314.54 | 634.32 | 262.93 | 371.39 | 0.00 | 0.00 |
May | 805.80 | 196.61 | 656.63 | 206.46 | 450.17 | 0.00 | 0.00 |
June | 882.63 | 116.18 | 643.07 | 187.56 | 455.50 | 0.00 | 0.00 |
July | 966.61 | 61.64 | 643.27 | 184.79 | 458.47 | 0.00 | 0.00 |
August | 1161.00 | 88.96 | 776.87 | 324.11 | 452.76 | 0.00 | 0.00 |
September | 924.76 | 177.13 | 693.65 | 336.19 | 357.46 | 0.00 | 0.00 |
October | 1019.46 | 315.25 | 822.19 | 470.39 | 351.80 | 0.00 | 0.00 |
November | 528.76 | 468.90 | 526.33 | 275.64 | 250.69 | 0.00 | 0.00 |
December | 461.26 | 600.58 | 495.60 | 318.46 | 177.14 | 0.00 | 0.00 |
Annual Sum or Average | 765.05 | 339.72 | 641.79 | 297.88 | 343.91 | 0.00 | 0.00 |
Minimum of Months | 413.79 | 61.64 | 473.52 | 184.79 | 177.14 | 0.00 | 0.00 |
Maximum of Months | 1161.00 | 665.16 | 822.19 | 470.39 | 458.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.110830E+10 | 0.178157E+10 | 0.126828E+10 | 0.739848E+09 | 0.528432E+09 | 0.00 | 0.00 |
February | 0.143039E+10 | 0.156676E+10 | 0.157456E+10 | 0.938696E+09 | 0.635865E+09 | 0.00 | 0.00 |
March | 0.188588E+10 | 0.119133E+10 | 0.183141E+10 | 0.932906E+09 | 0.898509E+09 | 0.00 | 0.00 |
April | 0.182396E+10 | 0.815281E+09 | 0.164415E+10 | 0.681511E+09 | 0.962638E+09 | 0.00 | 0.00 |
May | 0.215826E+10 | 0.526597E+09 | 0.175873E+10 | 0.552989E+09 | 0.120574E+10 | 0.00 | 0.00 |
June | 0.228777E+10 | 0.301132E+09 | 0.166683E+10 | 0.486161E+09 | 0.118067E+10 | 0.00 | 0.00 |
July | 0.258896E+10 | 0.165102E+09 | 0.172292E+10 | 0.494945E+09 | 0.122798E+10 | 0.00 | 0.00 |
August | 0.310963E+10 | 0.238264E+09 | 0.208077E+10 | 0.868089E+09 | 0.121269E+10 | 0.00 | 0.00 |
September | 0.239697E+10 | 0.459125E+09 | 0.179794E+10 | 0.871405E+09 | 0.926538E+09 | 0.00 | 0.00 |
October | 0.273053E+10 | 0.844377E+09 | 0.220217E+10 | 0.125989E+10 | 0.942273E+09 | 0.00 | 0.00 |
November | 0.137054E+10 | 0.121540E+10 | 0.136424E+10 | 0.714452E+09 | 0.649784E+09 | 0.00 | 0.00 |
December | 0.123545E+10 | 0.160860E+10 | 0.132742E+10 | 0.852967E+09 | 0.474450E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.241266E+11 | 0.107135E+11 | 0.202394E+11 | 0.939386E+10 | 0.108456E+11 | 0.00 | 0.00 |
Minimum of Months | 0.110830E+10 | 0.165102E+09 | 0.126828E+10 | 0.486161E+09 | 0.474450E+09 | 0.00 | 0.00 |
Maximum of Months | 0.310963E+10 | 0.178157E+10 | 0.220217E+10 | 0.125989E+10 | 0.122798E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.142844E+11 | -0.134871E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -797244737.8 | 58.99 | 0.00 | 0.00 |
February | 0.130274E+11 | -0.123044E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -723022441.4 | 58.98 | 0.00 | 0.00 |
March | 0.141282E+11 | -0.133430E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -785173384.0 | 58.99 | 0.00 | 0.00 |
April | 0.129377E+11 | -0.122164E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -721327423.8 | 58.99 | 0.00 | 0.00 |
May | 0.124466E+11 | -0.117565E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -690160883.1 | 58.99 | 0.00 | 0.00 |
June | 0.112059E+11 | -0.105667E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -639216480.2 | 58.99 | 0.00 | 0.00 |
July | 0.109697E+11 | -0.103141E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -655605083.9 | 58.99 | 0.00 | 0.00 |
August | 0.108520E+11 | -0.101962E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -655775209.6 | 58.99 | 0.00 | 0.00 |
September | 0.107949E+11 | -0.101513E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -643633939.4 | 58.98 | 0.00 | 0.00 |
October | 0.118940E+11 | -0.111918E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -702220094.4 | 58.99 | 0.00 | 0.00 |
November | 0.124387E+11 | -0.116969E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -741805942.7 | 58.99 | 0.00 | 0.00 |
December | 0.136982E+11 | -0.129019E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -796317890.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.148678E+12 | -0.140126E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.855150E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.107949E+11 | -0.134871E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -797244737.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.142844E+11 | -0.101513E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -639216480.2 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.28 | 0.24 | 01-JAN-07:49 | 4407.73 | 31.47 | 143.83 | 244.00 | 4478.89 | 31.74 | 144.50 | 243.17 |
February | 216.00 | 0.25 | 0.24 | 01-FEB-07:40 | 1949.75 | 23.78 | 67.00 | 262.17 | 2595.48 | 26.40 | 101.17 | 262.33 |
March | 275.00 | 0.27 | 0.24 | 01-MAR-06:49 | 1881.87 | 21.41 | 95.33 | 324.50 | 1799.87 | 21.43 | 84.83 | 321.67 |
April | 261.17 | 0.26 | 0.24 | 01-APR-06:10 | 1867.41 | 18.91 | 15.17 | 354.00 | 2197.04 | 18.87 | 22.00 | 353.17 |
May | 372.00 | 0.27 | 0.24 | 01-MAY-05:40 | 1863.38 | 18.78 | 5.17 | 402.50 | 1565.29 | 18.80 | 5.17 | 402.67 |
June | 351.83 | 0.26 | 0.24 | 01-JUN-04:00 | 1561.04 | 18.73 | 3.33 | 399.00 | 1428.13 | 18.90 | 5.33 | 397.50 |
July | 365.17 | 0.25 | 0.24 | 01-JUL-04:00 | 1562.52 | 19.04 | 16.67 | 405.67 | 1515.32 | 19.10 | 16.67 | 405.17 |
August | 389.17 | 0.27 | 0.24 | 01-AUG-05:40 | 2172.13 | 18.96 | 34.33 | 379.67 | 2138.28 | 19.17 | 42.83 | 380.83 |
September | 285.33 | 0.26 | 0.24 | 01-SEP-05:49 | 1817.95 | 19.50 | 43.83 | 336.67 | 1869.88 | 21.37 | 84.67 | 333.67 |
October | 305.50 | 0.26 | 0.24 | 01-OCT-14:39 | 2876.63 | 24.04 | 148.50 | 311.50 | 2647.59 | 25.57 | 162.50 | 310.17 |
November | 240.83 | 0.26 | 0.24 | 01-NOV-06:49 | 5039.62 | 34.58 | 213.67 | 257.83 | 4458.90 | 31.50 | 172.17 | 257.83 |
December | 211.17 | 0.28 | 0.24 | 01-DEC-07:40 | 4559.75 | 32.79 | 155.67 | 242.17 | 4391.91 | 32.49 | 155.33 | 242.00 |
Annual Sum or Average | 3472.67 | 0.26 | 2458.66 | 22.55 | 942.50 | 3919.67 | 2400.70 | 22.83 | 997.17 | 3910.17 | ||
Minimum of Months | 199.50 | 0.25 | 0.24 | 1561.04 | 18.73 | 3.33 | 242.17 | 1428.13 | 18.80 | 5.17 | 242.00 | |
Maximum of Months | 389.17 | 0.28 | 0.24 | 5039.62 | 34.58 | 213.67 | 405.67 | 4478.89 | 32.49 | 172.17 | 405.17 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.280373E+11 | 53605.89 | 02-JAN-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.278157E+11 | 53605.89 | 03-FEB-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170233E+11 | 53605.89 | 23-MAR-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.742882E+10 | 18118.18 | 02-APR-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102346E+10 | 7907.53 | 15-MAY-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1012867.94 | 4770.87 | 26-JUN-03:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 315830.22 | 1052.77 | 30-AUG-02:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 52672528.33 | 3646.07 | 24-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.236309E+10 | 12590.76 | 29-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123086E+11 | 48627.87 | 23-NOV-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.215883E+11 | 40312.25 | 15-DEC-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117643E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.280373E+11 | 53605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.175929E+11 | 44650.44 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188481E+11 | 41991.28 | 13-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.802223E+10 | 23643.23 | 20-MAR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162869E+10 | 14770.80 | 01-APR-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10072273.77 | 2266.46 | 01-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.346024E+09 | 10195.80 | 09-OCT-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.484409E+10 | 25205.30 | 25-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113679E+11 | 24010.28 | 31-DEC-23:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.626600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.188481E+11 | 44650.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 23903560.82 | 16360986.00 | 4315.90 | 27-MAR-16:05 | 3018.16 | 0.00 |
April | 0.00 | 0.00 | 0.643920E+09 | 0.525989E+09 | 20135.26 | 08-APR-02:61 | 13452.13 | 0.00 |
May | 0.00 | 0.00 | 0.277174E+10 | 0.217638E+10 | 40316.76 | 31-MAY-02:61 | 22691.35 | 0.00 |
June | 0.00 | 0.00 | 0.159122E+11 | 0.935836E+10 | 44683.55 | 27-JUN-02:61 | 16245.42 | 0.00 |
July | 0.00 | 0.00 | 0.328408E+11 | 0.172927E+11 | 44794.57 | 20-JUL-02:61 | 15345.35 | 0.00 |
August | 0.00 | 0.00 | 0.302192E+11 | 0.179090E+11 | 44794.57 | 05-AUG-02:02 | 20588.47 | 0.00 |
September | 0.00 | 0.00 | 0.117074E+11 | 0.726773E+10 | 44794.57 | 14-SEP-02:61 | 16685.24 | 0.00 |
October | 0.00 | 0.00 | 0.238096E+10 | 0.146507E+10 | 41739.38 | 06-OCT-02:61 | 18865.73 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.965002E+11 | 0.560116E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.328408E+11 | 0.179090E+11 | 44794.57 | 22691.35 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 797743.81 | 457766.62 | 3377.00 | 24-JAN-04:10 | 1661.07 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 50153968.02 | 32644299.52 | 17036.99 | 28-MAR-04:01 | 11220.05 | 0.00 |
April | 0.00 | 0.00 | 0.111553E+10 | 0.880771E+09 | 27960.76 | 07-APR-03:22 | 15926.69 | 0.00 |
May | 0.00 | 0.00 | 0.466854E+10 | 0.356581E+10 | 27960.76 | 05-MAY-03:22 | 13777.37 | 0.00 |
June | 0.00 | 0.00 | 0.227203E+11 | 0.126050E+11 | 31066.25 | 15-JUN-10:35 | 15727.73 | 0.00 |
July | 0.00 | 0.00 | 0.422973E+11 | 0.208956E+11 | 31066.25 | 07-JUL-02:42 | 15282.63 | 0.00 |
August | 0.00 | 0.00 | 0.365813E+11 | 0.210245E+11 | 31066.25 | 13-AUG-02:61 | 15890.87 | 0.00 |
September | 0.00 | 0.00 | 0.167549E+11 | 0.985913E+10 | 31066.25 | 14-SEP-10:33 | 13162.49 | 0.00 |
October | 0.00 | 0.00 | 0.478197E+10 | 0.269746E+10 | 28811.90 | 06-OCT-04:02 | 12119.53 | 0.00 |
November | 0.00 | 0.00 | 59412284.36 | 39720369.22 | 27960.76 | 10-NOV-04:22 | 12690.16 | 0.00 |
December | 0.00 | 0.00 | 1797728.81 | 1155121.04 | 1649.80 | 01-DEC-04:40 | 1072.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.129032E+12 | 0.716022E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.422973E+11 | 0.210245E+11 | 31066.25 | 15926.69 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5328.21 | 19907.96 | 31-JAN-13:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 5378.63 | 19935.94 | 09-FEB-13:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5276.38 | 19780.14 | 01-MAR-13:25 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5004.11 | 19005.45 | 01-APR-12:14 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 4681.89 | 17827.47 | 01-MAY-12:58 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 4370.20 | 16505.00 | 01-JUN-12:55 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4141.80 | 15461.97 | 01-JUL-12:20 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 4100.92 | 15048.00 | 31-AUG-12:30 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 4207.87 | 15789.85 | 30-SEP-12:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4470.47 | 16996.90 | 31-OCT-12:55 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4805.40 | 18279.25 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5108.18 | 19366.48 | 31-DEC-13:50 |
Annual Sum or Average | 0.00 | 4735.82 | ||||
Minimum of Months | 0.00 | 0.00 | 4100.92 | 15048.00 | ||
Maximum of Months | 0.00 | 0.00 | 5378.63 | 19935.94 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112631E+10 | 0.22 | 503.64 | 01-JAN-00:01 | 0.27 |
February | 0.101563E+10 | 0.22 | 503.64 | 01-FEB-00:01 | 0.27 |
March | 0.113250E+10 | 0.22 | 503.64 | 01-MAR-00:01 | 0.26 |
April | 0.112615E+10 | 0.23 | 503.64 | 01-APR-04:01 | 0.26 |
May | 0.121250E+10 | 0.24 | 503.64 | 01-MAY-02:62 | 0.26 |
June | 0.122688E+10 | 0.25 | 503.64 | 01-JUN-00:55 | 0.26 |
July | 0.128489E+10 | 0.25 | 503.64 | 01-JUL-00:55 | 0.26 |
August | 0.128406E+10 | 0.25 | 503.64 | 01-AUG-00:14 | 0.26 |
September | 0.122362E+10 | 0.25 | 503.64 | 01-SEP-00:13 | 0.26 |
October | 0.121583E+10 | 0.24 | 503.64 | 01-OCT-02:61 | 0.26 |
November | 0.112109E+10 | 0.23 | 503.64 | 01-NOV-02:62 | 0.26 |
December | 0.112744E+10 | 0.22 | 503.64 | 01-DEC-00:01 | 0.27 |
Annual Sum or Average | 0.140969E+11 | 0.23 | |||
Minimum of Months | 0.101563E+10 | 0.22 | 503.64 | 0.26 | |
Maximum of Months | 0.128489E+10 | 0.25 | 503.64 | 0.27 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.215140E+10 | 0.57 | 1760.97 | 02-JAN-03:10 | 0.88 |
February | 0.200007E+10 | 0.58 | 1760.97 | 03-FEB-03:02 | 0.88 |
March | 0.191237E+10 | 0.52 | 1760.97 | 23-MAR-02:62 | 0.88 |
April | 0.166901E+10 | 0.48 | 1005.63 | 15-APR-04:04 | 0.66 |
May | 0.159364E+10 | 0.45 | 860.25 | 15-MAY-04:03 | 0.60 |
June | 0.155609E+10 | 0.47 | 1760.97 | 18-JUN-02:61 | 0.87 |
July | 0.166348E+10 | 0.48 | 1760.97 | 03-JUL-02:61 | 0.87 |
August | 0.169995E+10 | 0.48 | 1760.97 | 02-AUG-02:61 | 0.87 |
September | 0.154796E+10 | 0.46 | 1760.97 | 01-SEP-02:61 | 0.87 |
October | 0.162429E+10 | 0.46 | 1745.40 | 06-OCT-02:61 | 0.87 |
November | 0.176671E+10 | 0.49 | 1597.44 | 23-NOV-03:02 | 0.88 |
December | 0.200294E+10 | 0.54 | 1324.27 | 15-DEC-03:02 | 0.88 |
Annual Sum or Average | 0.211879E+11 | 0.50 | |||
Minimum of Months | 0.154796E+10 | 0.45 | 860.25 | 0.60 | |
Maximum of Months | 0.215140E+10 | 0.58 | 1760.97 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131898E+10 | 0.51 | 989.17 | 02-JAN-05:03 | 0.82 |
February | 0.122320E+10 | 0.52 | 960.37 | 13-FEB-05:03 | 0.80 |
March | 0.121608E+10 | 0.48 | 761.59 | 20-MAR-04:04 | 0.71 |
April | 0.111653E+10 | 0.48 | 1263.64 | 08-APR-02:61 | 0.91 |
May | 0.115644E+10 | 0.49 | 1263.64 | 10-MAY-02:61 | 0.91 |
June | 0.130380E+10 | 0.54 | 1263.64 | 01-JUN-02:11 | 0.91 |
July | 0.175209E+10 | 0.62 | 1263.64 | 01-JUL-02:11 | 0.90 |
August | 0.166156E+10 | 0.60 | 1263.64 | 01-AUG-02:11 | 0.90 |
September | 0.122099E+10 | 0.52 | 1263.64 | 01-SEP-02:11 | 0.90 |
October | 0.116094E+10 | 0.49 | 1263.64 | 01-OCT-02:61 | 0.91 |
November | 0.114873E+10 | 0.48 | 1120.25 | 10-NOV-05:01 | 0.86 |
December | 0.125158E+10 | 0.49 | 765.57 | 31-DEC-23:30 | 0.71 |
Annual Sum or Average | 0.155309E+11 | 0.52 | |||
Minimum of Months | 0.111653E+10 | 0.48 | 761.59 | 0.71 | |
Maximum of Months | 0.175209E+10 | 0.62 | 1263.64 | 0.91 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 50.16 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 51.44 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 51.35 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 51.93 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 51.01 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 52.45 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:03 | 0.00 | 0.00 | 52.89 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 53.19 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 53.40 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 51.73 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 52.31 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 52.27 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 50.16 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 53.40 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 38.29 | 38.29 | 5328.21 | 19907.96 | 31-JAN-13:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 51.81 | 51.81 | 5378.63 | 19935.94 | 09-FEB-13:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 51.86 | 51.86 | 5276.38 | 19780.14 | 01-MAR-13:25 |
April | 0.00 | 0.00 | 01-APR-00:01 | 52.13 | 52.13 | 5004.11 | 19005.45 | 01-APR-12:14 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 39.92 | 39.92 | 4681.89 | 17827.47 | 01-MAY-12:58 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 52.68 | 52.68 | 4370.20 | 16505.00 | 01-JUN-12:55 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 53.11 | 53.11 | 4141.80 | 15461.97 | 01-JUL-12:20 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 53.21 | 53.21 | 4100.92 | 15048.00 | 31-AUG-12:30 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 53.52 | 53.52 | 4207.87 | 15789.85 | 30-SEP-12:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 42.18 | 42.18 | 4470.47 | 16996.90 | 31-OCT-12:55 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.72 | 52.72 | 4805.40 | 18279.25 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 51.85 | 51.85 | 5108.18 | 19366.48 | 31-DEC-13:50 |
Annual Sum or Average | 0.00 | 4735.82 | ||||||
Minimum of Months | 0.00 | 0.00 | 38.29 | 38.29 | 4100.92 | 15048.00 | ||
Maximum of Months | 0.00 | 0.00 | 53.52 | 53.52 | 5378.63 | 19935.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.215140E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.200007E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.191965E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.185374E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.236635E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.566262E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.971060E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.919236E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.462611E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.228139E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.176671E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.200294E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.455339E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.176671E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.971060E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.131922E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.122320E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.123059E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.142003E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.238412E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.673072E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.113840E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.101751E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.530190E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.239872E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.116546E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.125213E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.459851E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.116546E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.113840E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.215140E+10 | 0.00 | 0.280373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200007E+10 | 0.00 | 0.278157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191237E+10 | 23903560.82 | 0.170233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166901E+10 | 0.643920E+09 | 0.742882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159364E+10 | 0.277092E+10 | 0.102346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155609E+10 | 0.158730E+11 | 1012867.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166348E+10 | 0.328296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169995E+10 | 0.301535E+11 | 315830.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154796E+10 | 0.116744E+11 | 52672528.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162429E+10 | 0.237347E+10 | 0.236309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176671E+10 | 0.00 | 0.123086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200294E+10 | 0.00 | 0.215883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211879E+11 | 0.963428E+11 | 0.117643E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.215140E+10 | 0.328296E+11 | 0.280373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.131898E+10 | 797743.81 | 0.175929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122320E+10 | 0.00 | 0.188481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121608E+10 | 50153968.02 | 0.802223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111653E+10 | 0.111191E+10 | 0.162869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115644E+10 | 0.465675E+10 | 10072273.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130380E+10 | 0.226538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175209E+10 | 0.422596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166156E+10 | 0.364967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122099E+10 | 0.167194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116094E+10 | 0.476614E+10 | 0.346024E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114873E+10 | 58461618.49 | 0.484409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125158E+10 | 1797728.81 | 0.113679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155309E+11 | 0.128776E+12 | 0.626600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175209E+10 | 0.422596E+11 | 0.188481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.215140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191237E+10 | 0.00 | 0.00 | 0.00 | 7273546.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166901E+10 | 0.00 | 0.00 | 0.00 | 0.184732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159364E+10 | 0.00 | 0.00 | 0.00 | 0.772704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155609E+10 | 0.00 | 0.00 | 0.00 | 0.410652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166348E+10 | 0.00 | 0.00 | 0.00 | 0.804713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169995E+10 | 0.00 | 0.00 | 0.00 | 0.749241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154796E+10 | 0.00 | 0.00 | 0.00 | 0.307815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162429E+10 | 0.00 | 0.00 | 0.00 | 0.657093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211879E+11 | 0.00 | 0.00 | 0.00 | 0.243460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.215140E+10 | 0.00 | 0.00 | 0.00 | 0.804713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.131898E+10 | 0.00 | 0.00 | 0.00 | 236812.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121608E+10 | 0.00 | 0.00 | 0.00 | 14506761.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111653E+10 | 0.00 | 0.00 | 0.00 | 0.303494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115644E+10 | 0.00 | 0.00 | 0.00 | 0.122768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130380E+10 | 0.00 | 0.00 | 0.00 | 0.542692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175209E+10 | 0.00 | 0.00 | 0.00 | 0.963192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166156E+10 | 0.00 | 0.00 | 0.00 | 0.851350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122099E+10 | 0.00 | 0.00 | 0.00 | 0.408091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116094E+10 | 0.00 | 0.00 | 0.00 | 0.123778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114873E+10 | 0.00 | 0.00 | 0.00 | 16727892.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125158E+10 | 0.00 | 0.00 | 0.00 | 544373.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155309E+11 | 0.00 | 0.00 | 0.00 | 0.304542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175209E+10 | 0.00 | 0.00 | 0.00 | 0.963192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.304564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232932E+11 | 0.00 | 0.00 | 3.58 |
February | 0.273977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229330E+11 | 0.00 | 0.00 | 3.61 |
March | 0.580929E+10 | 0.00 | 0.00 | 436923.52 | 0.00 | 0.139943E+11 | 0.126861E+09 | 0.00 | 3.59 |
April | 0.721983E+10 | 9722315.17 | 0.00 | 4292032.33 | 0.00 | 0.546815E+10 | 0.135481E+10 | 0.00 | 3.84 |
May | 0.662058E+10 | 0.183170E+09 | 0.00 | 12147720.73 | 0.00 | 0.102129E+09 | 0.363984E+10 | 0.00 | 4.32 |
June | 0.761255E+09 | 0.249253E+10 | 82417.17 | 17933246.40 | 6928136.76 | 0.00 | 0.391523E+10 | 4805.93 | 4.91 |
July | 76494712.70 | 0.848575E+10 | 0.00 | 3217565.77 | 63176708.91 | 0.00 | 0.367442E+09 | 0.00 | 3.95 |
August | 0.210634E+09 | 0.707319E+10 | 21944.67 | 12222719.49 | 67937632.20 | 0.00 | 0.150104E+10 | 1179.52 | 4.38 |
September | 0.183134E+10 | 0.136289E+10 | 0.00 | 21324492.83 | 3536173.22 | 6873.58 | 0.489341E+10 | 0.00 | 4.99 |
October | 0.738801E+10 | 74439612.05 | 0.00 | 13383853.58 | 216861.92 | 0.779077E+09 | 0.431717E+10 | 0.00 | 4.29 |
November | 0.834520E+10 | 0.00 | 0.00 | 468116.18 | 0.00 | 0.879471E+10 | 0.302768E+09 | 0.00 | 3.58 |
December | 0.452298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179257E+11 | 0.00 | 0.00 | 3.59 |
Annual Sum or Average | 0.485710E+11 | 0.196817E+11 | 104361.84 | 85426670.82 | 0.141796E+09 | 0.932903E+11 | 0.204186E+11 | 5985.45 | 4.05 |
Minimum of Months | 76494712.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.58 |
Maximum of Months | 0.834520E+10 | 0.848575E+10 | 82417.17 | 21324492.83 | 67937632.20 | 0.232932E+11 | 0.489341E+10 | 4805.93 | 4.99 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.476176E+11 | 0.00 | 0.00 | 42549.57 | 0.00 | 17094340.95 | 65732393.45 | 0.00 | 6.72 |
February | 0.460236E+11 | 0.00 | 0.00 | 15896.07 | 0.00 | 24891963.64 | 8386697.85 | 0.00 | 6.82 |
March | 0.375782E+11 | 0.00 | 0.00 | 1345357.40 | 0.00 | 7356786.83 | 0.102654E+10 | 0.00 | 6.54 |
April | 0.237304E+11 | 0.00 | 0.00 | 12838840.29 | 0.00 | 0.00 | 0.619672E+10 | 0.00 | 6.52 |
May | 0.990771E+10 | 23713104.41 | 0.00 | 42011193.26 | 0.00 | 0.00 | 0.160507E+11 | 0.00 | 6.67 |
June | 0.124495E+10 | 0.255914E+10 | 0.00 | 56367116.80 | 4549788.51 | 0.00 | 0.927386E+10 | 0.00 | 7.24 |
July | 0.293739E+09 | 0.113446E+11 | 0.00 | 18070306.00 | 38545702.14 | 0.00 | 0.132944E+10 | 0.00 | 8.14 |
August | 0.397187E+09 | 0.910729E+10 | 0.00 | 45471175.32 | 31204397.16 | 0.00 | 0.526285E+10 | 0.00 | 7.94 |
September | 0.215842E+10 | 0.120703E+10 | 0.00 | 58436852.97 | 2252005.14 | 0.00 | 0.134357E+11 | 0.00 | 7.01 |
October | 0.132927E+11 | 333056.32 | 0.00 | 36580367.04 | 0.00 | 0.00 | 0.142325E+11 | 0.00 | 6.65 |
November | 0.312234E+11 | 0.00 | 0.00 | 3593626.19 | 0.00 | 3940870.75 | 0.402624E+10 | 0.00 | 6.56 |
December | 0.420899E+11 | 0.00 | 0.00 | 57968.96 | 0.00 | 3631917.94 | 56159808.88 | 0.00 | 6.65 |
Annual Sum or Average | 0.255558E+12 | 0.242421E+11 | 0.00 | 0.274831E+09 | 76551892.96 | 56915880.11 | 0.709648E+11 | 0.00 | 6.96 |
Minimum of Months | 0.293739E+09 | 0.00 | 0.00 | 15896.07 | 0.00 | 0.00 | 8386697.85 | 0.00 | 6.52 |
Maximum of Months | 0.476176E+11 | 0.113446E+11 | 0.00 | 58436852.97 | 38545702.14 | 24891963.64 | 0.160507E+11 | 0.00 | 8.14 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:22
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.128604E+11 | 0.164602E+11 | 0.119936E+12 | 0.00 | 0.205177E+11 |
February | 0.232279E+11 | 0.159447E+11 | 0.114544E+12 | 0.00 | 0.202892E+11 |
March | 0.436494E+11 | 0.138681E+11 | 0.999576E+11 | 44999841.22 | 0.200751E+11 |
April | 0.488120E+11 | 0.967051E+10 | 0.788708E+11 | 0.413862E+09 | 0.205677E+11 |
May | 0.650384E+11 | 0.706485E+10 | 0.679953E+11 | 0.111365E+10 | 0.299965E+11 |
June | 0.644339E+11 | 0.164858E+10 | 0.223041E+11 | 0.140354E+10 | 0.694119E+11 |
July | 0.635520E+11 | -0.375345E+10 | -0.216312E+11 | 0.183492E+09 | 0.115289E+12 |
August | 0.614386E+11 | -0.270661E+10 | -0.555481E+10 | 0.585705E+09 | 0.105563E+12 |
September | 0.414714E+11 | 0.293390E+10 | 0.385094E+11 | 0.168022E+10 | 0.550158E+11 |
October | 0.381329E+11 | 0.735266E+10 | 0.740141E+11 | 0.120054E+10 | 0.280734E+11 |
November | 0.157668E+11 | 0.113044E+11 | 0.926735E+11 | 19503818.30 | 0.165754E+11 |
December | 0.949407E+10 | 0.146301E+11 | 0.108719E+12 | 0.00 | 0.176857E+11 |
Annual Sum or Average | 0.487878E+12 | 0.944180E+11 | 0.790337E+12 | 0.664550E+10 | 0.519060E+12 |
Minimum of Months | 0.949407E+10 | -0.375345E+10 | -0.216312E+11 | 0.00 | 0.165754E+11 |
Maximum of Months | 0.650384E+11 | 0.164602E+11 | 0.119936E+12 | 0.168022E+10 | 0.115289E+12 |