Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 08:28:16
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1655.10 | 7123.50 | 7123.50 |
Net Site Energy | 1655.10 | 7123.50 | 7123.50 |
Total Source Energy | 2589.77 | 11146.31 | 11146.31 |
Net Source Energy | 2589.77 | 11146.31 | 11146.31 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 614.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 21.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 239.49 | 451.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 51.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 207.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 36.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 381.97 | 1273.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 614.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 22.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 21.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 10.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 220.85 | 451.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 51.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 207.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 10.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 17.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 614.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 22.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 21.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 10.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 239.49 | 451.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 51.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 207.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 36.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 137.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 318.31 | 3536.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1187.99 | 1942.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1643.99 | 5479.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 137.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 318.31 | 3536.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1187.99 | 1942.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1643.99 | 5479.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 381.970 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 381.970 | 100.00 |
Total On-Site and Utility Electric Sources | 381.970 | 100.00 |
Total Electricity End Uses | 381.970 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 5.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4561.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 4.0792 | 1.33 | 110.4804 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.6205 | 18.52 | 1009.9592 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 6.8498 | 2.48 | 560.2198 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 6.8498 | 2.48 | 560.2198 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 4.0792 | 1.33 | 110.4804 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.6205 | 18.52 | 1009.9592 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 6.8498 | 1.24 | 560.2198 | |||||||
Conditioned Total | 232.34 | 6.8498 | 1.24 | 560.2198 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 6.8498 | 2.48 | 560.2198 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JUN-10:20 | 04-JAN-13:09 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 104827.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12098.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 989.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 12932.59 | 21742.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2542.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23803.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 3931.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 32494.46 | 150373.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 104827.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 12098.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 989.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 12341.79 | 21742.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 2542.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 23803.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 665.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 69.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 67.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 34.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 758.45 | 489.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 164.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 224.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 115.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1209.70 | 1380.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2865.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 300.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 289.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 146.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3264.36 | 2105.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 707.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 968.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 498.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5206.52 | 5939.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2865.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 300.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 289.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 146.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3264.36 | 2105.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 707.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 968.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 498.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5206.52 | 5939.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.56 |
KITCHEN DIRECT AIR | 1.14 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.56 | 1.56 | 1.56 | 1.56 | 1.56 | 1.56 | 1.00 | 1.00 | 1.56 |
PSZ-AC_2:2 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.56 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.14 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.56 | 1671.29 |
PSZ-AC_2:2_ADDAQ FAN | 1.14 | 1263.64 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.56 | 1.56 | 1.56 | 1.03 | 37254.33 | 60170.83 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 0.753280 | 28342.03 | 96212.05 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.56 | 0.780943 | 1.04 | 37254.33 | 18627.17 | 0.714160 | 0.714160 |
PSZ-AC_2:2 COOLING COIL | 1.14 | 0.570667 | 0.760887 | 28342.03 | 14171.01 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 60170.83 |
PSZ-AC_2:2 HEATING COIL | 96212.05 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 4.079 | 110.480 | 0.000 | 0.000 | 0.000 | 0.000 | 114.560 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.620 | 261.340 | 748.620 | 0.000 | 0.000 | 0.000 | 1019.580 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 473.883 | 4.079 | 5.413 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 473.883 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1117.624 | 9.620 | 178.156 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1117.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 12834.676 | 110.480 | 146.608 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3722.056 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 29769.412 | 256.254 | 4745.415 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 8633.129 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 277.500 | 2.389 | 44.235 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 313.300 | 2.697 | 49.942 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 86968.240 | 748.620 | 13863.236 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 25220.790 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.9832E-01 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.9832E-01 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.4002 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2403 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2403 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 10.07 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 10.07 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.265 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.085 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.085 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.30075618E-16 | 0.17394661E-15 | 0.12402583E-13 | -0.41376697E-16 |
24 | 3 | -0.12971024E-07 | 0.72198543E-07 | -0.59837000E-04 | 0.16553701E-12 |
25 | 2 | 0.68419174E-04 | 0.15226993E-02 | 1.1866788 | -0.78740824E-04 |
26 | 1 | -0.34646128E-01 | 0.38608229E-01 | -17.391783 | 0.34506386 |
27 | 0 | 0.98978059E-01 | 0.24269337E-01 | 16.269565 | |
28 | 4 | 0.12402583E-13 | 0.17394661E-15 | 0.30075618E-16 | -0.41376697E-16 |
29 | 3 | -0.59837000E-04 | 0.72198543E-07 | -0.12971024E-07 | 0.16553701E-12 |
30 | 2 | 1.1866788 | 0.15226993E-02 | 0.68419174E-04 | -0.78740824E-04 |
31 | 1 | -17.391783 | 0.38608229E-01 | -0.34646128E-01 | 0.34506386 |
32 | 0 | 16.269565 | 0.24269337E-01 | 0.98978059E-01 | |
33 | 7 | -0.36497932E-12 | 0.65593627E-15 | -0.12833793E-12 | 0.14057672E-15 |
34 | 6 | 0.33075537E-07 | 0.11699647E-09 | 0.75401566E-08 | -0.15914535E-12 |
35 | 5 | -0.21222498E-03 | 0.97557935E-06 | -0.10882611E-03 | 0.74384351E-08 |
36 | 4 | 0.31766798 | 0.46388355E-03 | 0.10887901 | -0.37209111E-04 |
37 | 3 | -7.7709266 | 0.14076565E-01 | -2.4887051 | 0.31484223E-01 |
38 | 2 | 42.534380 | 0.49126722E-01 | 15.877466 | -0.35186973 |
39 | 1 | -81.819330 | 0.21810079E-01 | -29.690133 | 1.1057606 |
40 | 0 | 46.824331 | 0.43177108E-03 | 16.278511 | |
41 | 7 | -0.17492660E-08 | -0.39206577E-15 | 0.56910466E-14 | -0.74880728E-16 |
42 | 6 | 0.67235958E-05 | 0.46061729E-08 | 0.31866593E-02 | -0.26732369E-04 |
43 | 5 | -0.48404724E-03 | 0.27298576E-05 | -0.22354209 | 0.19545396E-02 |
44 | 4 | 0.11137682E-01 | 0.12426572E-03 | 4.8265062 | -0.45235764E-01 |
45 | 3 | -0.97815318E-01 | 0.98833577E-03 | -38.004246 | 0.39846397 |
46 | 2 | 0.34733640 | 0.16441863E-02 | 116.45053 | -1.4174923 |
47 | 1 | -0.50133706 | 0.50116224E-03 | -143.88764 | 2.0487166 |
48 | 0 | 0.24442836 | 0.12066061E-04 | 60.838472 | |
49 | 7 | -0.17492660E-08 | -0.39206577E-15 | 0.56910466E-14 | -0.74880728E-16 |
50 | 6 | 0.67235958E-05 | 0.46061729E-08 | 0.31866593E-02 | -0.26732369E-04 |
51 | 5 | -0.48404724E-03 | 0.27298576E-05 | -0.22354209 | 0.19545396E-02 |
52 | 4 | 0.11137682E-01 | 0.12426572E-03 | 4.8265062 | -0.45235764E-01 |
53 | 3 | -0.97815318E-01 | 0.98833577E-03 | -38.004246 | 0.39846397 |
54 | 2 | 0.34733640 | 0.16441863E-02 | 116.45053 | -1.4174923 |
55 | 1 | -0.50133706 | 0.50116224E-03 | -143.88764 | 2.0487166 |
56 | 0 | 0.24442836 | 0.12066061E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.292_SHGC_SOUTH_0.399 | 38 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 | ||
2 | NONRESWINDOW_U_0.292_SHGC_NORTH_0.399 | 39 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 | ||
3 | NONRESWINDOW_U_0.292_SHGC_EAST_0.399 | 40 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 | ||
4 | NONRESWINDOW_U_0.292_SHGC_WEST_0.399 | 41 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.238 | 0.3637 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 1.853E-002 | 1.595E-004 | 1.994E-004 | 0.188 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.584 | 5.025E-003 | 6.281E-003 | 5.934 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 1.853E-002 | 1.595E-004 | 1.953E-004 | 0.188 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.8688E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.1546E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.6757E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.9429E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.3432E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.3072E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.7212E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.7269E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.6511E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.4546E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 0.1017 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 9.9247E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 5.0149E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.9449E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.8679E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.8680E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.9203E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.5570E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6449E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.2686E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.0129E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.0889E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.7272E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.7212E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 16968.82568 | 20362.59081 | 1.30157 | 1.56189 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10000 | 1.27259E-002 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 7098.54216 | 8518.25059 | 0.31518 | 0.41606 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -32.70000 | 1.83376E-004 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 14296.73541 | 17156.08249 | 0.91286 | 1.14133 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 28.98400 | 1.27239E-002 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 1589.74564 | 1907.69477 | 6.28922E-002 | 1.14133 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -32.70000 | 1.83376E-004 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 23053.43 | 1.56189 | 1.56189 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 35072.67 | 0.41606 | 0.41606 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 22895.03 | 1.14133 | 1.14133 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 96212.05 | 1.14133 | 1.14133 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.56189 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14133 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.56189 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.56189 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.56189 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.56189 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.56189 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.56189 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14133 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14133 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14133 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14133 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14133 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14133 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.56189 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.14133 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.56189 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.56189 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 1671.29134 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.56189 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.56189 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.56189 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.03084 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.56189 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78094 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.04126 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 37254.33000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18627.16500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71416 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71416 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 37254.33000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 60170.83100 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 60170.83100 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14133 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14133 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1263.63741 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14133 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14133 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14133 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75328 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14133 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57067 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76089 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28342.03000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14171.01500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28342.03000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 96212.05041 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 96212.05041 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 36140.3 | 11.77 | 11.71 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 27530.8 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.400 | 0.378 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_EAST_0.399 | N/A | 1.658 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.400 | 0.378 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_SOUTH_0.399 | N/A | 1.658 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.400 | 0.378 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_WEST_0.399 | N/A | 1.658 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.240 | 0.227 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 9.832E-002 | 9.653E-002 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.400 | 0.378 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.400 | 0.378 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.400 | 0.378 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.240 | 0.227 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 9.832E-002 | 9.653E-002 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 9.832E-002 | 9.602E-002 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 9.832E-002 | 9.602E-002 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1454441995 | 0.5826181140 | Pass | Pass | 0.1251787095 | 0.2908315986 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 9.8105488676E-002 | 0.4845939602 | Pass | Pass | 7.0234020790E-002 | 0.3312025236 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.3076880025 | 0.2943703344 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 430.07 | 172.98 | 1333.57 | 5.76 | 405.83 | 2348.21 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.378 | 0.400 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.378 | 0.400 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.378 | 0.400 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.231 | 0.240 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.378 | 0.400 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.378 | 0.400 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.378 | 0.400 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.231 | 0.240 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.096 | 0.098 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.096 | 0.098 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.096 | 0.098 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.096 | 0.098 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.292_SHGC_EAST_0.399 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 1.658 | 0.400 | 0.440 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.292_SHGC_SOUTH_0.399 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 1.658 | 0.400 | 0.440 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.292_SHGC_WEST_0.399 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 1.658 | 0.400 | 0.440 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 1.658 | 0.400 | 0.440 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 1.658 | 0.400 | 0.440 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 4.0792 | 116.17 | 473.88 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 43.44 | 0.0000 | Y | 3.86 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.6205 | 116.17 | 1117.62 | LightsWired | LTG_SCH_KITCHEN | 86.84 | 168.00 | 82.89 | 0.0000 | Y | 17.39 |
Interior Lighting Total | 6.8498 | 232.34 | 1591.51 | 21.25 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 473.88 | 180.08 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 473.88 | 180.08 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 209.35 | AstronomicalClock | - | 49.55 | 49.55 | 1.95 | |
EXTERIOR_LIGHTS_B | 742.80 | AstronomicalClock | - | 83.52 | 63.04 | 8.79 | |
Exterior Lighting Total | 952.15 | 10.74 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 37254.33 | 26605.55 | 10648.78 | 0.71 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28342.03 | 19870.03 | 8472.00 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 36140.3 | 11.77 | 11.71 | ||||
PSZ-AC_2:2 COOLING COIL | 27530.8 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 60170.83 | 0.84 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 96212.05 | 0.85 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.56 | 1671.29 | 1070.05 | 1.00 | 1.35 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1263.64 | 1107.16 | 1.00 | 1.37 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.95 | 1.24 | 0.36 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 16968.83 | 20362.59 | 175.28 | 1.302 | 1.562 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.87 | 0.01074 | 30.10 | 0.01273 | 0.416 | 0.00 |
KITCHEN | 14296.74 | 17156.08 | 147.68 | 0.913 | 1.141 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.01035 | 28.98 | 0.01272 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 7098.54 | 8518.25 | 73.32 | 0.315 | 0.416 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00792 | -32.70 | 0.00018 | 0.416 | 0.00 |
KITCHEN | 1589.75 | 1907.69 | 16.42 | 0.063 | 1.141 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 18.89 | 18.89 | 0.00552 | -32.70 | 0.00018 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.56 | 1.56 | 0.42 | 0.42 | 1.5619 | 1.5619 | 1.5619 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.14 | 1.14 | 1.14 | 1.14 | 1.1413 | 1.1413 | 1.1413 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 37254.330 | 26605.552 | 1.561890 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 18627.17 | 12636.62 | 1.041260 | 25.53 | 18.69 | 0.01126696 | 11.90 | 11.35 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 39.9570 | 23.87 | 0.01073723 | 55.6121 | 16968.83 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 60170.831 | 60170.831 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 | 60170.83 | 60170.83 | 1.561886 | 6.78 | 6.12 | 0.00583298 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 26.6381 | 19.39 | 0.00788437 | 53.9525 | 4117.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28342.030 | 19870.030 | 1.141330 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14171.01 | 9124.97 | 0.760887 | 30.10 | 21.13 | 0.01272586 | 11.87 | 11.33 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 150.0005 | 26.09 | 0.01058078 | 48.0255 | 12654.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 96212.050 | 96212.050 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:40:00 | 96212.05 | 96212.05 | 1.141334 | -32.70 | -32.70 | 0.00018338 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 100.0000 | 18.50 | 0.00654146 | 47.4439 | 486.54 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 37254.330 | 26605.552 | 1.561890 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.7847 | 1004.8586 | 1.1539 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.561886 | 1.80229853 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 18627.17 | 12636.62 | 1.0000 | 1.20153580 | 1.041260 | 25.53 | 18.69 | 0.01126696 | 54365.5 | 11.90 | 11.35 | 0.00850000 | 33399.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18627.17 | 30.10 | 0.01272586 | 21.13 | 0.41605618 | 39.9570 | 23.87 | 0.01073723 | 23.87 | 0.01073723 | 55.6121 | 16968.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 60170.831 | 60170.831 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.561886 | 1.80229853 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 | Sensible | 60170.83 | 60170.83 | 1.0000 | 1.80229853 | 1.561886 | 6.78 | 6.12 | 0.00583298 | 21470.0 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60170.83 | -32.70 | 0.00018338 | -32.70 | 0.41605618 | 26.6381 | 21.11 | 0.00788437 | 19.39 | 0.00788437 | 53.9525 | 4117.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28342.030 | 19870.030 | 1.141330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.4967 | 1004.8586 | 1.1539 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.141334 | 1.31701315 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 14171.01 | 9124.97 | 1.0000 | 0.87800604 | 0.760887 | 30.10 | 21.13 | 0.01272586 | 62784.4 | 11.87 | 11.33 | 0.00850000 | 33370.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14171.01 | 30.10 | 0.01272586 | 21.13 | 1.14133354 | 150.0005 | 26.03 | 0.01058078 | 26.09 | 0.01058078 | 48.0255 | 12654.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 96212.050 | 96212.050 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.141334 | 1.31701315 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:40:00 | Sensible | 96212.05 | 96212.05 | 1.0000 | 1.31701315 | 1.141334 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 96212.05 | -32.70 | 0.00018338 | -32.70 | 1.14133354 | 100.0000 | 18.30 | 0.00654146 | 18.50 | 0.00654146 | 47.4439 | 486.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.56 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.14 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3796.17 | 6002.67 | 2848.50 |
KITCHEN | 5322.33 | 6228.17 | 4502.83 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5380.00 | 7026.67 | 4561.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 112.33 | 9.83 | 0.00 | 0.00 |
KITCHEN | 0.00 | 88.83 | 0.00 | 5.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 112.33 | 97.00 | 0.00 | 5.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.728 | 2.789 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 8.157 | 0.011 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.063 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 7.377 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 12196092.89 | 0.00 | 12196092.89 | 7034712.00 | 19230804.89 | 13120747.55 | 1432.63 | 6275.62 | 1051.75 | 377.98 |
KITCHEN | 21080988.92 | 0.00 | 21080988.92 | 44681.22 | 21125670.14 | 35993094.65 | 8743.36 | 16.64 | 0.00 | 360.52 |
Total Facility | 33277081.81 | 0.00 | 33277081.81 | 7079393.22 | 40356475.03 | 49113842.20 | 8744.50 | 6277.73 | 1051.75 | 568.81 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4593 | 0.0000 | 0.4593 | 0.2712 | 0.7305 | 0.4161 | 0.00 | 6144.44 | 1042.56 |
KITCHEN | 0.7939 | 0.0000 | 0.7939 | 0.0010 | 0.7950 | 1.1413 | 7172.50 | 14.50 | 0.00 |
Total Facility | 1.2532 | 0.0000 | 1.2532 | 0.2723 | 1.5255 | 1.5574 | 7172.50 | 6144.48 | 1042.56 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 16240092.53 | 0.00 | 16240092.53 | 13120747.55 | 1429.20 | 0.90 | 7329.90 | 377.98 |
PSZ-AC_2:2 | 28070234.48 | 0.00 | 28070234.48 | 35993094.65 | 7543.24 | 328.59 | 888.18 | 360.52 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6116 | 0.0000 | 0.6116 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.0571 | 0.0000 | 1.0571 | 1.1413 | 5999.77 | 324.91 | 862.32 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 969.25 | 324.84 | 6270.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 83.29 | 907.33 | 6556.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.0295 | 0.7674 | 0.5541 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.1941 | 1.0652 | 1.0566 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 386 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 381.97 | 2743.87 | 05-JAN-01:20 | 32494.46 | 30-JUN-10:20 |
Electricity:Building | 268.68 | 1624.98 | 01-JAN-01:20 | 17215.91 | 02-JAN-11:10 |
Electricity:Zone:DINING | 70.40 | 280.44 | 01-JAN-01:20 | 3811.41 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 260.74 | 1488.70 | 01-JAN-01:20 | 13921.86 | 02-JAN-11:10 |
InteriorLights:Electricity | 21.25 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:DINING | 3.86 | 20.75 | 17-MAY-05:00 | 389.13 | 02-JAN-16:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 21.25 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 21.25 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 3.86 | 20.75 | 17-MAY-05:00 | 389.13 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 21.25 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-16:30 |
Electricity:Zone:KITCHEN | 198.28 | 1344.54 | 01-JAN-01:20 | 13404.50 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.39 | 25.01 | 01-JAN-01:20 | 895.88 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.39 | 25.01 | 01-JAN-01:20 | 895.88 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 239.49 | 1438.68 | 01-JAN-01:10 | 12932.59 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 66.53 | 255.43 | 01-JAN-01:10 | 3718.02 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 239.49 | 1438.68 | 01-JAN-01:10 | 12932.59 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 220.85 | 847.88 | 01-JAN-01:10 | 12341.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 66.53 | 255.43 | 01-JAN-01:10 | 3718.02 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 220.85 | 847.88 | 01-JAN-01:10 | 12341.79 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 172.95 | 1183.25 | 01-JAN-01:10 | 9214.57 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 154.32 | 592.45 | 01-JAN-01:10 | 8623.77 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 36.54 | 594.45 | 06-APR-22:30 | 3931.14 | 19-JUN-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 28.59 | 508.67 | 25-DEC-23:10 | 1618.30 | 01-SEP-03:20 |
LowTempRefrigeration:Refrigeration:Electricity | 10.84 | 0.00 | 01-JAN-11:10 | 981.21 | 01-SEP-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 17.76 | 475.34 | 29-DEC-00:20 | 637.09 | 23-APR-12:10 |
ElectricityPurchased:Facility | 381.97 | 2743.87 | 05-JAN-01:20 | 32494.46 | 30-JUN-10:20 |
ElectricityPurchased:Plant | 381.97 | 2743.87 | 05-JAN-01:20 | 32494.46 | 30-JUN-10:20 |
Cogeneration:ElectricityPurchased | 381.97 | 2743.87 | 05-JAN-01:20 | 32494.46 | 30-JUN-10:20 |
General:Cogeneration:ElectricityPurchased | 381.97 | 2743.87 | 05-JAN-01:20 | 32494.46 | 30-JUN-10:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 381.97 | 2743.87 | 05-JAN-01:20 | 32494.46 | 30-JUN-10:20 |
ElectricityNet:Plant | 381.97 | 2743.87 | 05-JAN-01:20 | 32494.46 | 30-JUN-10:20 |
Cogeneration:ElectricityNet | 381.97 | 2743.87 | 05-JAN-01:20 | 32494.46 | 30-JUN-10:20 |
General:Cogeneration:ElectricityNet | 381.97 | 2743.87 | 05-JAN-01:20 | 32494.46 | 30-JUN-10:20 |
Electricity:HVAC | 73.96 | 0.00 | 01-JAN-01:10 | 18097.51 | 29-JUN-18:00 |
Fans:Electricity | 51.93 | 0.00 | 01-JAN-01:10 | 3075.59 | 29-JUN-18:00 |
General:Fans:Electricity | 51.93 | 0.00 | 01-JAN-01:10 | 3075.59 | 29-JUN-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 22.02 | 0.00 | 01-JAN-00:10 | 15027.62 | 29-JUN-13:00 |
General:Cooling:Electricity | 22.02 | 0.00 | 01-JAN-00:10 | 15027.62 | 29-JUN-13:00 |
ExteriorLights:Electricity | 10.74 | 0.00 | 01-JAN-08:20 | 952.15 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 10.74 | 0.00 | 01-JAN-08:20 | 952.15 | 01-JAN-06:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 05-MAR-09:40 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 05-MAR-09:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1273.13 | 2351.77 | 01-JAN-01:30 | 150373.60 | 04-JAN-13:10 |
NaturalGas:Building | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
NaturalGas:HVAC | 614.23 | 0.00 | 01-JAN-01:10 | 121485.84 | 06-JAN-07:10 |
Heating:NaturalGas | 614.23 | 0.00 | 01-JAN-01:10 | 121485.84 | 06-JAN-07:10 |
General:Heating:NaturalGas | 614.23 | 0.00 | 01-JAN-01:10 | 121485.84 | 06-JAN-07:10 |
NaturalGas:Plant | 207.50 | 612.41 | 01-JAN-00:10 | 27604.85 | 24-FEB-13:20 |
WaterSystems:NaturalGas | 207.50 | 612.41 | 01-JAN-00:10 | 27604.85 | 24-FEB-13:20 |
Water Heater:WaterSystems:NaturalGas | 207.50 | 612.41 | 01-JAN-00:10 | 27604.85 | 24-FEB-13:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUN-12:30 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUN-12:30 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUN-12:30 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUN-12:30 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUN-12:30 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUN-12:30 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUN-12:30 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUN-12:30 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1273.26 | 2414.92 | 06-JAN-01:10 | 147163.73 | 05-JAN-21:00 |
EnergyTransfer:Building | 429.95 | 1207.46 | 06-JAN-01:10 | 42459.46 | 04-JAN-12:10 |
EnergyTransfer:Zone:KITCHEN | 289.62 | 1207.46 | 06-JAN-01:10 | 19738.22 | 05-MAY-04:10 |
Refrigeration:EnergyTransfer | 133.01 | 2414.91 | 06-JAN-01:00 | 7834.84 | 19-JUN-10:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 66.51 | 1207.46 | 06-JAN-01:00 | 3917.42 | 19-JUN-10:40 |
General:Refrigeration:EnergyTransfer | 66.51 | 1207.46 | 06-JAN-01:00 | 3917.42 | 19-JUN-10:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 66.51 | 1207.46 | 06-JAN-01:00 | 3917.42 | 19-JUN-10:40 |
EnergyTransfer:Plant | 236.23 | 1207.46 | 06-JAN-01:00 | 25022.40 | 21-FEB-13:30 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.92 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 53.58 | 1059.55 | 29-DEC-00:20 | 2238.70 | 23-APR-12:10 |
EnergyTransfer:Zone:DINING | 140.33 | 0.00 | 01-JAN-01:10 | 33029.37 | 09-JAN-04:50 |
Heating:EnergyTransfer | 89.58 | 0.00 | 01-JAN-00:20 | 30209.57 | 05-JAN-21:00 |
Heating:EnergyTransfer:Zone:DINING | 89.53 | 0.00 | 01-JAN-00:20 | 30209.57 | 05-JAN-21:00 |
General:Heating:EnergyTransfer | 89.58 | 0.00 | 01-JAN-00:20 | 30209.57 | 05-JAN-21:00 |
General:Heating:EnergyTransfer:Zone:DINING | 89.53 | 0.00 | 01-JAN-00:20 | 30209.57 | 05-JAN-21:00 |
Cooling:EnergyTransfer | 273.87 | 0.00 | 01-JAN-01:10 | 24651.44 | 30-JUN-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 50.80 | 0.00 | 01-JAN-01:10 | 15694.73 | 06-JAN-03:10 |
General:Cooling:EnergyTransfer | 273.87 | 0.00 | 01-JAN-01:10 | 24651.44 | 30-JUN-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 50.80 | 0.00 | 01-JAN-01:10 | 15694.73 | 06-JAN-03:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.04 | 0.00 | 01-JAN-00:10 | 3659.14 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.04 | 0.00 | 01-JAN-00:10 | 3659.14 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 223.07 | 0.00 | 01-JAN-01:10 | 15978.57 | 05-MAY-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 223.07 | 0.00 | 01-JAN-01:10 | 15978.57 | 05-MAY-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 169.72 | 0.00 | 01-JAN-00:10 | 23072.09 | 27-FEB-13:20 |
PlantLoopHeatingDemand:Plant | 169.72 | 0.00 | 01-JAN-00:10 | 23072.09 | 27-FEB-13:20 |
WaterSystems:PlantLoopHeatingDemand | 169.72 | 0.00 | 01-JAN-00:10 | 23072.09 | 27-FEB-13:20 |
General:WaterSystems:PlantLoopHeatingDemand | 169.72 | 0.00 | 01-JAN-00:10 | 23072.09 | 27-FEB-13:20 |
EnergyTransfer:HVAC | 607.08 | 0.00 | 01-JAN-01:10 | 102735.30 | 06-JAN-07:10 |
HeatingCoils:EnergyTransfer | 518.81 | 0.00 | 01-JAN-01:10 | 102735.30 | 06-JAN-07:10 |
CoolingCoils:EnergyTransfer | 88.27 | 0.00 | 01-JAN-00:10 | 62761.78 | 30-JUN-12:00 |
WaterSystems:EnergyTransfer | 169.72 | 0.00 | 01-JAN-00:10 | 23072.09 | 27-FEB-13:20 |
WaterUse:WaterSystems:EnergyTransfer | 169.72 | 0.00 | 01-JAN-00:10 | 23072.09 | 27-FEB-13:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 89.533 | -50.797 | 0.000 | 0.000 | 72.910 | 3.865 | 49.900 | 24.164 | 0.000 | 1.393 | 0.001 | 0.000 | -14.873 | 0.000 | -149.066 | -27.028 |
KITCHEN | 0.000 | 0.000 | 0.044 | -223.062 | 0.000 | 0.000 | 5.254 | 17.389 | 178.354 | 0.000 | 0.000 | 0.002 | 23.089 | 0.000 | 0.000 | 0.000 | -1.070 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.894 | 8.263 | 0.000 | 0.000 | 0.000 | -12.157 | -0.000 |
Total Facility | 0.000 | 0.000 | 89.577 | -273.859 | 0.000 | 0.000 | 78.164 | 21.254 | 228.254 | 24.164 | 0.000 | 5.289 | 31.353 | 0.000 | -14.873 | 0.000 | -162.294 | -27.028 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 06-JAN-04:42 | 0.00 | 0.00 | 0.00 | -34664.28 | 0.00 | 0.00 | 0.00 | 25.01 | 478.93 | 0.00 | 0.00 | 0.00 | 36394.98 | 0.00 | -2034.15 | 0.00 | -200.49 | 0.00 |
KITCHEN | 06-JAN-05:01 | 0.00 | 0.00 | 0.00 | -48246.15 | 0.00 | 0.00 | 21.93 | 25.01 | 4283.84 | 0.00 | 0.00 | 0.00 | 43967.44 | 0.00 | -0.00 | 0.00 | -52.07 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-JAN-00:01 | 0.00 | 0.00 | 0.00 | -64903.89 | 0.00 | 0.00 | 388.29 | 214.17 | 1802.53 | 0.00 | 0.00 | 264.88 | 64286.81 | 0.00 | -1989.70 | 0.00 | -63.08 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 12-JAN-05:01 | 0.00 | 0.00 | 39688.28 | 0.00 | 0.00 | 0.00 | 421.94 | 25.01 | 1153.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1324.97 | 0.00 | -104.71 | -39859.42 |
KITCHEN | 02-JAN-05:04 | 0.00 | 0.00 | 36564.04 | 0.00 | 0.00 | 0.00 | 23.31 | 25.01 | 4283.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -42.28 | -40853.93 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JAN-05:01 | -32744.19 | 32744.19 | 39688.28 | -32744.19 | 0.00 | 0.00 | 445.35 | 50.02 | 5437.71 | 0.00 | 0.00 | 107.67 | 0.00 | 0.00 | -1324.97 | 0.00 | -210.00 | -11449.86 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.5619 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.5619 | 0.2664 | 1.0000 | Not calculated | 0.4161 | 0.2664 | ||
PSZ-AC_2:2 | 1.1413 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.1413 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1325 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.5619 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.5619 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2664 | ||
PSZ-AC_2:2 | 1.1413 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.1413 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1325 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5619 | 1.5619 | 1.5619 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1413 | 1.1413 | 1.1413 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.5619 | 1.5619 | 1.5619 | 1.5619 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.1413 | 1.1413 | 1.1413 | 1.1413 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5619 | 1.5619 | 1.5619 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1413 | 1.1413 | 1.1413 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.5619 | 1.5619 | 1.5619 | 1.5619 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.1413 | 1.1413 | 1.1413 | 1.1413 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 5.00 |
Number of hours not met | 5.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 614.23 | 121485.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 22.02 | 15027.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 21.25 | 1285.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 10.74 | 952.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 220.85 | 12341.79 | 451.39 | 25220.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 51.93 | 3075.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 207.50 | 27604.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 10.84 | 981.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 17.76 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 276.02 | 381.97 |
Natural Gas | 451.39 | 1273.13 |
Additional | 0.00 | 0.00 |
Total | 727.41 | 1655.10 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 91.48 |
Space Heating | 0.00 |
Space Cooling | 94.79 |
Fans (All) | 223.52 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1030.74 |
Miscellaneous (All) | 1643.99 |
Subtotal | 1643.99 |
Natural Gas [MJ/m2] | |
Space Heating | 2643.65 |
Service Water Heating | 893.09 |
Miscellaneous (All) | 5479.51 |
Subtotal | 5479.51 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.28 |
Space Heating | 37.11 |
Space Cooling | 1.33 |
Fans (All) | 3.14 |
Service Water Heating | 12.54 |
Receptacle Equipment | 41.74 |
Miscellaneous | 2.86 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4528. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8458.67 | 296.17 | 5.17 | 0.00 | 0.00 |
ATTIC | 7471.83 | 442.50 | 371.67 | 385.33 | 88.67 |
Min | 7471.83 | 5.17 | 0.00 | 0.00 | 0.00 |
Max | 8754.83 | 442.50 | 371.67 | 385.33 | 88.67 |
Average | 8228.44 | 247.94 | 125.61 | 128.44 | 29.56 |
Sum | 24685.33 | 743.83 | 376.83 | 385.33 | 88.67 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254722.33 | 2.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16234.17 | 23.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254722.33 | 23.83 | 0.00 | 0.00 | 0.00 |
Average | 90318.83 | 8.83 | 0.00 | 0.00 | 0.00 |
Sum | 270956.50 | 26.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8215.33 | 544.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6999.50 | 1759.00 | 1.50 | 0.00 | 0.00 |
ATTIC | 7471.50 | 695.83 | 212.83 | 183.83 | 196.00 |
Min | 6999.50 | 544.67 | 0.00 | 0.00 | 0.00 |
Max | 8215.33 | 1759.00 | 212.83 | 183.83 | 196.00 |
Average | 7562.11 | 999.83 | 71.44 | 61.28 | 65.33 |
Sum | 22686.33 | 2999.50 | 214.33 | 183.83 | 196.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 237724.67 | 17000.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 12541.83 | 3716.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 237724.67 | 17000.33 | 0.00 | 0.00 | 0.00 |
Average | 83422.17 | 6905.50 | 0.00 | 0.00 | 0.00 |
Sum | 250266.50 | 20716.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102506E+10 | 34664.51 | 06-JAN-04:42 | -34.9 | -35.0 | 0.436633E+10 | 3682.71 | 07-JAN-19:10 | -20.7 | -20.9 |
February | 0.821442E+09 | 30088.55 | 14-FEB-04:47 | -31.9 | -32.1 | 0.395238E+10 | 3682.65 | 18-FEB-19:00 | -15.0 | -15.6 |
March | 0.810160E+09 | 24386.22 | 05-MAR-04:39 | -28.3 | -28.5 | 0.441042E+10 | 3682.49 | 18-MAR-18:30 | -0.9 | -4.9 |
April | 0.200892E+10 | 13181.87 | 04-APR-23:01 | -10.1 | -11.5 | 0.433439E+10 | 4580.41 | 22-APR-18:10 | 16.73 | 7.31 |
May | 0.619084E+10 | 24958.94 | 19-MAY-02:61 | 14.82 | 10.01 | 0.486698E+10 | 4641.11 | 27-MAY-18:49 | 19.68 | 13.91 |
June | 0.875789E+10 | 19863.00 | 07-JUN-02:61 | 17.20 | 13.85 | 0.499358E+10 | 4641.03 | 17-JUN-18:10 | 23.62 | 13.20 |
July | 0.109856E+11 | 22579.80 | 24-JUL-02:61 | 17.38 | 15.86 | 0.523228E+10 | 4641.25 | 22-JUL-18:10 | 17.38 | 15.86 |
August | 0.986816E+10 | 22699.32 | 10-AUG-02:61 | 16.10 | 15.45 | 0.522396E+10 | 4641.16 | 05-AUG-18:19 | 16.10 | 15.45 |
September | 0.604064E+10 | 23553.08 | 02-SEP-02:61 | 12.30 | 10.94 | 0.462959E+10 | 4640.52 | 02-SEP-18:40 | 16.10 | 13.91 |
October | 0.245555E+10 | 12041.55 | 29-OCT-23:01 | -7.4 | -8.2 | 0.444244E+10 | 4363.41 | 19-OCT-11:00 | -7.4 | -8.2 |
November | 0.974146E+09 | 15323.71 | 25-NOV-00:01 | -15.0 | -15.4 | 0.423274E+10 | 4049.80 | 01-NOV-11:00 | -15.0 | -15.4 |
December | 0.859202E+09 | 27938.39 | 25-DEC-03:02 | -30.5 | -30.7 | 0.436462E+10 | 3682.72 | 09-DEC-19:10 | -30.5 | -30.7 |
Annual Sum or Average | 0.507976E+11 | 0.550497E+11 | ||||||||
Minimum of Months | 0.810160E+09 | 12041.55 | -34.9 | -35.0 | 0.395238E+10 | 3682.49 | -30.5 | -30.7 | ||
Maximum of Months | 0.109856E+11 | 34664.51 | 17.38 | 15.86 | 0.523228E+10 | 4641.25 | 23.62 | 15.86 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169676E+11 | 48269.79 | 06-JAN-05:01 | -34.9 | -35.0 | 0.727457E+10 | 4769.83 | 31-JAN-11:00 | -16.7 | -17.2 |
February | 0.156416E+11 | 46157.00 | 14-FEB-05:01 | -32.1 | -32.3 | 0.657118E+10 | 4779.77 | 21-FEB-11:00 | 6.10 | 2.99 |
March | 0.174254E+11 | 41367.21 | 05-MAR-05:01 | -28.1 | -28.3 | 0.727740E+10 | 4771.74 | 28-MAR-10:00 | 4.40 | 2.03 |
April | 0.176639E+11 | 29065.74 | 05-APR-04:01 | -12.4 | -13.3 | 0.706906E+10 | 4868.75 | 18-APR-10:00 | 17.20 | 11.08 |
May | 0.187550E+11 | 39319.52 | 17-MAY-02:61 | 11.25 | 7.76 | 0.739210E+10 | 4868.92 | 24-MAY-10:30 | 23.90 | 16.88 |
June | 0.184324E+11 | 42237.05 | 08-JUN-02:61 | 6.38 | 6.15 | 0.719706E+10 | 4881.42 | 30-JUN-10:50 | 30.92 | 23.73 |
July | 0.200716E+11 | 40263.83 | 02-JUL-02:61 | 7.38 | 7.34 | 0.744409E+10 | 4870.90 | 05-JUL-10:00 | 24.40 | 23.25 |
August | 0.203687E+11 | 38518.01 | 05-AUG-02:61 | 9.18 | 8.72 | 0.744388E+10 | 4868.95 | 09-AUG-10:09 | 22.30 | 19.28 |
September | 0.200716E+11 | 40713.11 | 09-SEP-02:61 | 10.68 | 6.88 | 0.714912E+10 | 4868.93 | 18-SEP-10:00 | 18.30 | 16.51 |
October | 0.209505E+11 | 31428.48 | 20-OCT-04:01 | 6.88 | 6.88 | 0.730415E+10 | 4859.83 | 19-OCT-10:00 | 6.88 | 6.88 |
November | 0.190465E+11 | 35662.73 | 29-NOV-05:01 | -19.6 | -19.9 | 0.704625E+10 | 4852.48 | 01-NOV-10:00 | -19.6 | -19.9 |
December | 0.176749E+11 | 43547.15 | 24-DEC-05:01 | -30.6 | -30.8 | 0.727446E+10 | 4769.83 | 04-DEC-11:00 | -30.6 | -30.8 |
Annual Sum or Average | 0.223070E+12 | 0.864433E+11 | ||||||||
Minimum of Months | 0.156416E+11 | 29065.74 | -34.9 | -35.0 | 0.657118E+10 | 4769.83 | -30.6 | -30.8 | ||
Maximum of Months | 0.209505E+11 | 48269.79 | 11.25 | 8.72 | 0.744409E+10 | 4881.42 | 30.92 | 23.73 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -23.1 | -23.5 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.5 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.3 | -3.3 | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.3 |
April | 0.00 | 0.00 | 01-APR-00:01 | 3.52 | 0.38 | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.38 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -0.0 | -1.4 | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.4 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 | 8.93 | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 | 13.57 | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.57 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.07 | 15.36 | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 19.75 | 18.15 | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.52 | 6.57 | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3.60 | 0.51 | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.51 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.00 | 0.00 | -23.1 | -23.5 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.00 | 0.00 | 19.75 | 18.15 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238955E+11 | 39687.72 | 12-JAN-05:01 | -17.2 |
February | 0.158614E+11 | 39623.22 | 27-FEB-05:01 | -17.4 |
March | 0.126861E+11 | 39377.59 | 07-MAR-03:21 | -25.9 |
April | 0.418890E+10 | 26311.93 | 04-APR-02:61 | -4.7 |
May | 0.336756E+09 | 13350.21 | 01-MAY-02:62 | -1.4 |
June | 14143400.82 | 2097.20 | 04-JUN-06:01 | 6.23 |
July | 42522.25 | 294.06 | 03-JUL-23:02 | 23.80 |
August | 2707279.39 | 2345.83 | 19-AUG-04:03 | 4.40 |
September | 0.100059E+09 | 7140.59 | 20-SEP-08:03 | 6.70 |
October | 0.259628E+10 | 12476.78 | 01-OCT-05:48 | 0.18 |
November | 0.833496E+10 | 25188.50 | 29-NOV-04:22 | -19.7 |
December | 0.215159E+11 | 38997.25 | 21-DEC-03:51 | -26.5 |
Annual Sum or Average | 0.895327E+11 | |||
Minimum of Months | 42522.25 | 294.06 | -26.5 | |
Maximum of Months | 0.238955E+11 | 39687.72 | 23.80 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14363810.27 | 36591.39 | 02-JAN-05:04 | -18.2 |
February | 8849551.57 | 13659.52 | 25-FEB-05:02 | -29.0 |
March | 6936664.16 | 15019.73 | 05-MAR-05:02 | -28.1 |
April | 2157746.95 | 7540.85 | 06-APR-04:03 | -7.0 |
May | 3598.03 | 59.97 | 01-MAY-04:04 | -2.9 |
June | 2476.90 | 37.15 | 29-JUN-23:01 | 26.20 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 19.75 |
October | 129712.70 | 2161.88 | 30-OCT-04:03 | -10.0 |
November | 2033183.18 | 10212.62 | 26-NOV-05:03 | -10.6 |
December | 9887805.18 | 18016.57 | 25-DEC-05:02 | -29.7 |
Annual Sum or Average | 44364548.93 | |||
Minimum of Months | 0.00 | 0.00 | -29.7 | |
Maximum of Months | 14363810.27 | 36591.39 | 26.20 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:01 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -8.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.00 | 0.00 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.411559E+09 | 389.13 | 02-JAN-16:30 | 0.565077E+10 | 3718.02 | 01-JAN-11:09 |
February | 0.338133E+09 | 389.13 | 01-FEB-17:10 | 0.510393E+10 | 3718.02 | 01-FEB-11:09 |
March | 0.335552E+09 | 389.13 | 01-MAR-17:00 | 0.565082E+10 | 3718.02 | 01-MAR-11:09 |
April | 0.285980E+09 | 389.13 | 01-APR-18:40 | 0.546849E+10 | 3718.02 | 01-APR-10:09 |
May | 0.259613E+09 | 389.13 | 01-MAY-19:30 | 0.565080E+10 | 3718.02 | 01-MAY-10:09 |
June | 0.236643E+09 | 389.13 | 01-JUN-19:00 | 0.546853E+10 | 3718.02 | 01-JUN-10:09 |
July | 0.246726E+09 | 389.13 | 01-JUL-20:19 | 0.565075E+10 | 3718.02 | 01-JUL-10:09 |
August | 0.284434E+09 | 389.13 | 01-AUG-19:49 | 0.565082E+10 | 3718.02 | 01-AUG-10:09 |
September | 0.301349E+09 | 389.13 | 01-SEP-18:00 | 0.546849E+10 | 3718.02 | 01-SEP-10:09 |
October | 0.352249E+09 | 389.13 | 02-OCT-17:49 | 0.565077E+10 | 3718.02 | 01-OCT-10:09 |
November | 0.390823E+09 | 389.13 | 01-NOV-16:00 | 0.546851E+10 | 3718.02 | 01-NOV-10:09 |
December | 0.421618E+09 | 389.13 | 01-DEC-16:19 | 0.565075E+10 | 3718.02 | 01-DEC-11:09 |
Annual Sum or Average | 0.386468E+10 | 0.665334E+11 | ||||
Minimum of Months | 0.236643E+09 | 389.13 | 0.510393E+10 | 3718.02 | ||
Maximum of Months | 0.421618E+09 | 389.13 | 0.565082E+10 | 3718.02 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146885E+10 | 895.88 | 02-JAN-10:09 | 0.146891E+11 | 9214.57 | 01-JAN-11:09 |
February | 0.133058E+10 | 895.88 | 01-FEB-10:09 | 0.132676E+11 | 9214.57 | 01-FEB-11:09 |
March | 0.149423E+10 | 895.88 | 01-MAR-10:09 | 0.146892E+11 | 9214.57 | 01-MAR-11:09 |
April | 0.142731E+10 | 895.88 | 01-APR-16:10 | 0.142152E+11 | 9214.57 | 01-APR-10:09 |
May | 0.148154E+10 | 895.88 | 01-MAY-09:09 | 0.146891E+11 | 9214.57 | 01-MAY-10:09 |
June | 0.144409E+10 | 895.88 | 01-JUN-09:09 | 0.142153E+11 | 9214.57 | 01-JUN-10:09 |
July | 0.146494E+10 | 895.88 | 01-JUL-16:10 | 0.146890E+11 | 9214.57 | 01-JUL-10:09 |
August | 0.149423E+10 | 895.88 | 01-AUG-09:09 | 0.146892E+11 | 9214.57 | 01-AUG-10:09 |
September | 0.142766E+10 | 895.88 | 01-SEP-09:09 | 0.142152E+11 | 9214.57 | 01-SEP-10:09 |
October | 0.146867E+10 | 895.88 | 02-OCT-09:09 | 0.146891E+11 | 9214.57 | 01-OCT-10:09 |
November | 0.142226E+10 | 895.88 | 01-NOV-09:09 | 0.142153E+11 | 9214.57 | 01-NOV-10:09 |
December | 0.146511E+10 | 895.88 | 01-DEC-10:09 | 0.146890E+11 | 9214.57 | 01-DEC-11:09 |
Annual Sum or Average | 0.173895E+11 | 0.172953E+12 | ||||
Minimum of Months | 0.133058E+10 | 895.88 | 0.132676E+11 | 9214.57 | ||
Maximum of Months | 0.149423E+10 | 895.88 | 0.146892E+11 | 9214.57 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.411559E+09 | 0.565077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283274E+11 |
February | 0.852256E+10 | 0.338133E+09 | 0.510393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209990E+11 |
March | 0.954557E+10 | 0.335552E+09 | 0.565082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189143E+11 |
April | 0.915225E+10 | 0.285980E+09 | 0.546849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8540204.92 | 0.106476E+11 |
May | 0.947560E+10 | 0.259613E+09 | 0.565080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168402E+09 | 0.485472E+10 |
June | 0.922788E+10 | 0.236643E+09 | 0.546853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453315E+09 | 0.259260E+10 |
July | 0.939996E+10 | 0.246726E+09 | 0.565075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555247E+09 | 0.188097E+10 |
August | 0.954557E+10 | 0.284434E+09 | 0.565082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200638E+09 | 0.284291E+10 |
September | 0.915225E+10 | 0.301349E+09 | 0.546849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6841537.33 | 0.575394E+10 |
October | 0.940563E+10 | 0.352249E+09 | 0.565077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104031E+11 |
November | 0.909363E+10 | 0.390823E+09 | 0.546851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153478E+11 |
December | 0.939996E+10 | 0.421618E+09 | 0.565075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265021E+11 |
Annual Sum or Average | 0.111326E+12 | 0.386468E+10 | 0.665334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139298E+10 | 0.149066E+12 |
Minimum of Months | 0.852256E+10 | 0.236643E+09 | 0.510393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188097E+10 |
Maximum of Months | 0.954557E+10 | 0.421618E+09 | 0.565082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555247E+09 | 0.283274E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.146885E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172825E+09 |
February | 0.610713E+09 | 0.133058E+10 | 0.971608E+10 | 0.103882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148553E+09 |
March | 0.684021E+09 | 0.149423E+10 | 0.107572E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107517E+09 |
April | 0.655836E+09 | 0.142731E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 4785.12 | 91022811.95 |
May | 0.679007E+09 | 0.148154E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 134849.57 | 47562021.62 |
June | 0.661256E+09 | 0.144409E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 949838.26 | 32368272.22 |
July | 0.673587E+09 | 0.146494E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 800546.87 | 22378018.07 |
August | 0.684021E+09 | 0.149423E+10 | 0.107572E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 223773.57 | 33589714.67 |
September | 0.655836E+09 | 0.142766E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51268890.17 |
October | 0.673993E+09 | 0.146867E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65752231.70 |
November | 0.651635E+09 | 0.142226E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119205E+09 |
December | 0.673587E+09 | 0.146511E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178020E+09 |
Annual Sum or Average | 0.797748E+10 | 0.173895E+11 | 0.126656E+12 | 0.135417E+12 | 0.00 | 0.00 | 0.00 | 2113793.38 | 0.107006E+10 |
Minimum of Months | 0.610713E+09 | 0.133058E+10 | 0.971608E+10 | 0.103882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22378018.07 |
Maximum of Months | 0.684021E+09 | 0.149423E+10 | 0.107572E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 949838.26 | 0.178020E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440161E+09 | 0.485868E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384826E+09 | 0.690778E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330545E+09 | 0.108645E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310343E+09 | 0.129537E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270849E+09 | 0.163650E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226051E+09 | 0.157952E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283161E+09 | 0.167464E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240154E+09 | 0.133942E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252809E+09 | 0.100662E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359517E+09 | 0.646780E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391300E+09 | 0.343627E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404464E+09 | 0.371862E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389418E+10 | 0.121574E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226051E+09 | 0.343627E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440161E+09 | 0.167464E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 389.13 | 02-JAN-16:30 | 3718.02 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 34447.00 | 05-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 389.13 | 01-FEB-17:10 | 3718.02 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 30664.38 | 01-FEB-21:00 |
March | 9454.80 | 04-MAR-19:10 | 389.13 | 01-MAR-17:00 | 3718.02 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 26327.40 | 06-MAR-21:00 |
April | 9454.80 | 01-APR-18:10 | 389.13 | 01-APR-18:40 | 3718.02 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 793.33 | 23-APR-16:05 | 17858.08 | 04-APR-19:53 |
May | 9454.80 | 06-MAY-18:10 | 389.13 | 01-MAY-19:30 | 3718.02 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2967.87 | 25-MAY-18:00 | 8599.61 | 01-MAY-19:52 |
June | 9454.80 | 03-JUN-18:10 | 389.13 | 01-JUN-19:00 | 3718.02 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5438.45 | 29-JUN-17:03 | 5746.91 | 04-JUN-06:01 |
July | 9454.80 | 01-JUL-18:10 | 389.13 | 01-JUL-20:19 | 3718.02 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2775.54 | 29-JUL-17:03 | 4978.47 | 08-JUL-19:00 |
August | 9454.80 | 05-AUG-18:10 | 389.13 | 01-AUG-19:49 | 3718.02 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2907.19 | 08-AUG-17:03 | 5983.10 | 17-AUG-11:53 |
September | 9454.80 | 02-SEP-18:10 | 389.13 | 01-SEP-18:00 | 3718.02 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 694.82 | 01-SEP-16:05 | 8566.34 | 23-SEP-19:00 |
October | 9454.80 | 07-OCT-18:10 | 389.13 | 02-OCT-17:49 | 3718.02 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 13915.75 | 31-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 389.13 | 01-NOV-16:00 | 3718.02 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 25348.93 | 25-NOV-19:10 |
December | 9454.80 | 02-DEC-19:10 | 389.13 | 01-DEC-16:19 | 3718.02 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 32444.07 | 19-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 389.13 | 3718.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4978.47 | |||||
Maximum of Months | 9454.80 | 389.13 | 3718.02 | 0.00 | 0.00 | 0.00 | 0.00 | 5438.45 | 34447.00 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 895.88 | 02-JAN-10:09 | 6627.44 | 01-JAN-11:09 | 7566.24 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 479.23 | 04-JAN-03:00 |
February | 677.52 | 04-FEB-19:10 | 895.88 | 01-FEB-10:09 | 6627.44 | 01-FEB-11:09 | 7566.24 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 466.46 | 13-FEB-03:51 |
March | 677.52 | 04-MAR-19:10 | 895.88 | 01-MAR-10:09 | 6627.44 | 01-MAR-11:09 | 7566.24 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 338.22 | 17-MAR-04:00 |
April | 677.52 | 01-APR-18:10 | 895.88 | 01-APR-16:10 | 6627.44 | 01-APR-10:09 | 7566.24 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 1.85 | 23-APR-15:55 | 268.72 | 02-APR-04:00 |
May | 677.52 | 06-MAY-18:10 | 895.88 | 01-MAY-09:09 | 6627.44 | 01-MAY-10:09 | 7566.24 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 2.72 | 24-MAY-15:00 | 153.10 | 09-MAY-03:35 |
June | 677.52 | 03-JUN-18:10 | 895.88 | 01-JUN-09:09 | 6627.44 | 01-JUN-10:09 | 7566.24 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 15.58 | 29-JUN-16:00 | 134.52 | 20-JUN-03:40 |
July | 677.52 | 01-JUL-18:10 | 895.88 | 01-JUL-16:10 | 6627.44 | 01-JUL-10:09 | 7566.24 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 12.01 | 15-JUL-15:00 | 102.96 | 06-JUL-02:10 |
August | 677.52 | 05-AUG-18:10 | 895.88 | 01-AUG-09:09 | 6627.44 | 01-AUG-10:09 | 7566.24 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 9.14 | 08-AUG-16:00 | 130.54 | 17-AUG-02:00 |
September | 677.52 | 02-SEP-18:10 | 895.88 | 01-SEP-09:09 | 6627.44 | 01-SEP-10:09 | 7566.24 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 199.58 | 20-SEP-04:00 |
October | 677.52 | 07-OCT-18:10 | 895.88 | 02-OCT-09:09 | 6627.44 | 01-OCT-10:09 | 7566.24 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 216.33 | 31-OCT-04:00 |
November | 677.52 | 04-NOV-18:10 | 895.88 | 01-NOV-09:09 | 6627.44 | 01-NOV-10:09 | 7566.24 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 395.82 | 22-NOV-02:00 |
December | 677.52 | 02-DEC-19:10 | 895.88 | 01-DEC-10:09 | 6627.44 | 01-DEC-11:09 | 7566.24 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 413.49 | 16-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 895.88 | 6627.44 | 7566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 102.96 | ||||||
Maximum of Months | 677.52 | 895.88 | 6627.44 | 7566.24 | 0.00 | 0.00 | 0.00 | 15.58 | 479.23 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 705.49 | 28-JAN-02:55 | 1461.77 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729.16 | 17-FEB-07:53 | 1653.51 | 13-FEB-13:30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.36 | 03-MAR-01:00 | 2717.66 | 23-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 719.29 | 22-APR-04:00 | 2253.10 | 21-APR-13:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 628.43 | 18-MAY-04:55 | 2680.69 | 01-MAY-13:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 633.37 | 04-JUN-04:00 | 2390.88 | 14-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672.12 | 15-JUL-04:53 | 2543.65 | 13-JUL-12:30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 698.27 | 05-AUG-03:52 | 2256.16 | 05-AUG-13:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 611.19 | 06-SEP-05:30 | 1836.19 | 06-SEP-12:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 642.17 | 25-OCT-07:00 | 1761.18 | 09-OCT-12:30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.45 | 19-NOV-07:20 | 1083.58 | 10-NOV-12:50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.51 | 03-DEC-01:45 | 1144.65 | 26-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.51 | 1083.58 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729.16 | 2717.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 34664.51 | 06-JAN-04:42 | 0.00 | 250.09 | 6385.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.49 |
February | 30088.55 | 14-FEB-04:47 | 0.00 | 250.09 | 6385.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.71 |
March | 24386.22 | 05-MAR-04:39 | 0.00 | 250.09 | 6385.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.71 |
April | 13181.87 | 04-APR-23:01 | 5252.67 | 648.56 | 3846.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.21 |
May | 24958.94 | 19-MAY-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.97 |
June | 19863.00 | 07-JUN-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.27 |
July | 22579.80 | 24-JUL-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.79 |
August | 22699.32 | 10-AUG-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.85 |
September | 23553.08 | 02-SEP-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.16 |
October | 12041.55 | 29-OCT-23:01 | 5252.67 | 648.56 | 3846.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15323.71 | 25-NOV-00:01 | 5252.67 | 864.74 | 3846.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.85 |
December | 27938.39 | 25-DEC-03:02 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12041.55 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34664.51 | 5252.67 | 864.74 | 6385.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 48269.79 | 06-JAN-05:01 | 376.40 | 250.09 | 30887.20 | 31308.57 | 0.00 | 0.00 | 0.00 | 0.00 | 52.07 |
February | 46157.00 | 14-FEB-05:01 | 376.40 | 250.09 | 30887.20 | 31308.57 | 0.00 | 0.00 | 0.00 | 0.00 | 58.79 |
March | 41367.21 | 05-MAR-05:01 | 0.00 | 225.08 | 27711.98 | 28177.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29065.74 | 05-APR-04:01 | 376.40 | 250.09 | 30887.20 | 31308.57 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 |
May | 39319.52 | 17-MAY-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.17 |
June | 42237.05 | 08-JUN-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.72 |
July | 40263.83 | 02-JUL-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38518.01 | 05-AUG-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 |
September | 40713.11 | 09-SEP-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.41 |
October | 31428.48 | 20-OCT-04:01 | 376.40 | 250.09 | 30887.20 | 31308.57 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 |
November | 35662.73 | 29-NOV-05:01 | 376.40 | 250.09 | 30887.20 | 31308.57 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 |
December | 43547.15 | 24-DEC-05:01 | 0.00 | 225.08 | 27711.98 | 28177.71 | 0.00 | 0.00 | 0.00 | 0.00 | 52.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 29065.74 | 0.00 | 225.08 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48269.79 | 376.40 | 250.09 | 30887.20 | 31308.57 | 0.00 | 0.00 | 0.00 | 0.00 | 65.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.62 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.30 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.53 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.28 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.73 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.76 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.29 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.39 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.36 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.18 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.73 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.317709E+11 | 20494.56 | 05-JAN-11:09 | 0.206899E+12 | 150373.60 | 04-JAN-13:09 |
February | 0.282457E+11 | 20305.96 | 13-FEB-11:09 | 0.158116E+12 | 135142.20 | 14-FEB-07:10 |
March | 0.307865E+11 | 20153.99 | 15-MAR-10:09 | 0.146167E+12 | 128188.38 | 05-MAR-07:10 |
April | 0.291913E+11 | 19971.38 | 23-APR-16:10 | 0.901628E+11 | 84735.54 | 04-APR-10:20 |
May | 0.318328E+11 | 25149.61 | 26-MAY-10:20 | 0.624725E+11 | 58862.11 | 01-MAY-10:09 |
June | 0.344202E+11 | 32494.46 | 30-JUN-10:20 | 0.544718E+11 | 46509.23 | 09-JUN-10:50 |
July | 0.380864E+11 | 30028.43 | 23-JUL-10:20 | 0.546928E+11 | 45536.00 | 01-JUL-10:50 |
August | 0.356028E+11 | 28435.30 | 08-AUG-12:00 | 0.544966E+11 | 46060.96 | 17-AUG-12:30 |
September | 0.300688E+11 | 25218.11 | 01-SEP-10:20 | 0.570406E+11 | 52107.16 | 27-SEP-10:30 |
October | 0.304016E+11 | 19729.56 | 30-OCT-10:09 | 0.802731E+11 | 72112.10 | 30-OCT-07:10 |
November | 0.298501E+11 | 19973.69 | 28-NOV-11:09 | 0.114723E+12 | 106127.17 | 25-NOV-11:09 |
December | 0.317125E+11 | 20347.46 | 20-DEC-11:09 | 0.193611E+12 | 134906.66 | 24-DEC-11:20 |
Annual Sum or Average | 0.381970E+12 | 0.127313E+13 | ||||
Minimum of Months | 0.282457E+11 | 19729.56 | 0.544718E+11 | 45536.00 | ||
Maximum of Months | 0.380864E+11 | 32494.46 | 0.206899E+12 | 150373.60 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.188041E+10 | 0.127238E+10 | 0.203399E+11 | 0.00 | 0.536063E+10 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166871E+10 | 0.101525E+10 | 0.183715E+11 | 0.00 | 0.455076E+10 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182978E+10 | 0.942176E+09 | 0.203400E+11 | 0.00 | 0.474020E+10 | 0.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171329E+10 | 0.728878E+09 | 0.196837E+11 | 0.00 | 0.403598E+10 | 0.77 | 0.00 | 0.122904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174115E+10 | 0.616075E+09 | 0.203399E+11 | 0.00 | 0.390886E+10 | 0.80 | 0.00 | 0.201058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168073E+10 | 0.530892E+09 | 0.196839E+11 | 0.00 | 0.388165E+10 | 0.77 | 0.00 | 0.541004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.171166E+10 | 0.571028E+09 | 0.203398E+11 | 0.00 | 0.406943E+10 | 0.79 | 0.00 | 0.801933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.177866E+10 | 0.681473E+09 | 0.203400E+11 | 0.00 | 0.396786E+10 | 0.80 | 0.00 | 0.546688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172901E+10 | 0.831711E+09 | 0.196837E+11 | 0.00 | 0.378373E+10 | 0.77 | 0.00 | 0.914050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182092E+10 | 0.104901E+10 | 0.203399E+11 | 0.00 | 0.407743E+10 | 0.79 | 0.00 | 78884424.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181308E+10 | 0.118134E+10 | 0.196838E+11 | 0.00 | 0.431069E+10 | 0.77 | 0.00 | 525748.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188673E+10 | 0.131637E+10 | 0.203398E+11 | 0.00 | 0.524721E+10 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212541E+11 | 0.107366E+11 | 0.239486E+12 | 0.00 | 0.519344E+11 | 9.37 | 0.00 | 0.220232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.166871E+10 | 0.530892E+09 | 0.183715E+11 | 0.00 | 0.378373E+10 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.188673E+10 | 0.131637E+10 | 0.203400E+11 | 0.00 | 0.536063E+10 | 0.80 | 0.00 | 0.801933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.383373E+11 | 0.00 | 0.149516E+12 | 0.00 | 0.190450E+11 | 0.00 | 0.00 |
February | 0.346273E+11 | 0.00 | 0.105940E+12 | 0.00 | 0.175490E+11 | 0.00 | 0.00 |
March | 0.383373E+11 | 0.00 | 0.884377E+11 | 0.00 | 0.193924E+11 | 0.00 | 0.00 |
April | 0.371007E+11 | 0.00 | 0.348514E+11 | 0.00 | 0.182107E+11 | 0.00 | 0.00 |
May | 0.383373E+11 | 0.00 | 0.619300E+10 | 0.00 | 0.179422E+11 | 0.00 | 0.00 |
June | 0.371007E+11 | 0.00 | 0.924638E+09 | 0.00 | 0.164465E+11 | 0.00 | 0.00 |
July | 0.383373E+11 | 0.00 | 0.181083E+09 | 0.00 | 0.161743E+11 | 0.00 | 0.00 |
August | 0.383373E+11 | 0.00 | 0.346074E+09 | 0.00 | 0.158132E+11 | 0.00 | 0.00 |
September | 0.371007E+11 | 0.00 | 0.455795E+10 | 0.00 | 0.153820E+11 | 0.00 | 0.00 |
October | 0.383373E+11 | 0.00 | 0.254435E+11 | 0.00 | 0.164923E+11 | 0.00 | 0.00 |
November | 0.371007E+11 | 0.00 | 0.608259E+11 | 0.00 | 0.167962E+11 | 0.00 | 0.00 |
December | 0.383373E+11 | 0.00 | 0.137015E+12 | 0.00 | 0.182583E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.451391E+12 | 0.00 | 0.614233E+12 | 0.00 | 0.207502E+12 | 0.00 | 0.00 |
Minimum of Months | 0.346273E+11 | 0.00 | 0.181083E+09 | 0.00 | 0.153820E+11 | 0.00 | 0.00 |
Maximum of Months | 0.383373E+11 | 0.00 | 0.149516E+12 | 0.00 | 0.193924E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1285.01 | 02-JAN-16:30 | 952.15 | 01-JAN-06:10 | 12932.59 | 01-JAN-11:09 | 0.00 | 2907.54 | 04-JAN-20:10 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 1285.01 | 01-FEB-17:10 | 952.15 | 01-FEB-06:10 | 12932.59 | 01-FEB-11:09 | 0.00 | 2838.87 | 14-FEB-07:10 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 1285.01 | 01-MAR-17:00 | 952.15 | 01-MAR-06:10 | 12932.59 | 01-MAR-11:09 | 0.00 | 2786.24 | 05-MAR-07:10 | 0.00 | 05-MAR-09:39 | 0.00 | 01-MAR-00:10 |
April | 1285.01 | 01-APR-18:40 | 952.15 | 01-APR-05:10 | 12932.59 | 01-APR-10:09 | 0.00 | 2324.28 | 05-APR-06:10 | 0.00 | 22-APR-07:49 | 0.00 | 01-APR-00:10 |
May | 1285.01 | 01-MAY-19:30 | 952.15 | 01-MAY-19:30 | 12932.59 | 01-MAY-10:09 | 0.00 | 2074.65 | 01-MAY-06:10 | 0.00 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 1285.01 | 01-JUN-19:00 | 952.15 | 01-JUN-19:00 | 12932.59 | 01-JUN-10:09 | 0.00 | 3075.59 | 29-JUN-17:00 | 0.00 | 12-JUN-13:50 | 0.00 | 01-JUN-00:10 |
July | 1285.01 | 01-JUL-20:19 | 952.15 | 01-JUL-20:19 | 12932.59 | 01-JUL-10:09 | 0.00 | 2737.13 | 15-JUL-13:00 | 0.00 | 03-JUL-12:30 | 0.00 | 01-JUL-00:10 |
August | 1285.01 | 01-AUG-19:49 | 952.15 | 01-AUG-19:49 | 12932.59 | 01-AUG-10:09 | 0.00 | 2639.61 | 08-AUG-12:00 | 0.00 | 15-AUG-14:50 | 0.00 | 01-AUG-00:10 |
September | 1285.01 | 01-SEP-18:00 | 952.15 | 01-SEP-05:10 | 12932.59 | 01-SEP-10:09 | 0.00 | 1878.53 | 06-SEP-06:10 | 0.00 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 1285.01 | 02-OCT-17:49 | 952.15 | 01-OCT-05:10 | 12932.59 | 01-OCT-10:09 | 0.00 | 2211.00 | 30-OCT-06:10 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 1285.01 | 01-NOV-16:00 | 952.15 | 01-NOV-05:10 | 12932.59 | 01-NOV-10:09 | 0.00 | 2505.85 | 25-NOV-07:10 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 1285.01 | 01-DEC-16:19 | 952.15 | 01-DEC-06:10 | 12932.59 | 01-DEC-11:09 | 0.00 | 2854.67 | 24-DEC-07:10 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1285.01 | 952.15 | 12932.59 | 0.00 | 1878.53 | 0.00 | 0.00 | ||||||
Maximum of Months | 1285.01 | 952.15 | 12932.59 | 0.00 | 3075.59 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4878.26 | 23-APR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8180.91 | 25-MAY-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15027.62 | 29-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13148.28 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12378.87 | 08-AUG-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7791.38 | 01-SEP-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2802.15 | 19-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 413.43 | 21-NOV-04:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15027.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 20494.56 | 05-JAN-11:09 | 989.27 | 12932.59 | 0.00 | 0.00 | 2744.75 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20305.96 | 13-FEB-11:09 | 989.27 | 12932.59 | 0.00 | 0.00 | 2556.15 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20153.99 | 15-MAR-10:09 | 989.27 | 12932.59 | 0.00 | 0.00 | 2404.18 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19971.38 | 23-APR-16:10 | 659.51 | 11655.85 | 0.00 | 0.00 | 1677.61 | 0.00 | 0.00 | 4852.57 | 0.00 |
May | 25149.61 | 26-MAY-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 1677.61 | 0.00 | 0.00 | 5627.69 | 0.00 |
June | 32494.46 | 30-JUN-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 2542.85 | 0.00 | 0.00 | 12098.61 | 0.00 |
July | 30028.43 | 23-JUL-10:20 | 769.42 | 12932.59 | 0.00 | 0.00 | 2214.18 | 0.00 | 0.00 | 10199.94 | 0.00 |
August | 28435.30 | 08-AUG-12:00 | 989.27 | 11230.28 | 0.00 | 0.00 | 2639.61 | 0.00 | 0.00 | 12378.87 | 0.00 |
September | 25218.11 | 01-SEP-10:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 1677.61 | 0.00 | 0.00 | 5687.50 | 0.00 |
October | 19729.56 | 30-OCT-10:09 | 989.27 | 12932.59 | 0.00 | 0.00 | 1971.15 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19973.69 | 28-NOV-11:09 | 989.27 | 12932.59 | 0.00 | 0.00 | 2221.54 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20347.46 | 20-DEC-11:09 | 989.27 | 12932.59 | 0.00 | 0.00 | 2597.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 19729.56 | 659.51 | 11230.28 | 0.00 | 0.00 | 1677.61 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32494.46 | 989.27 | 12932.59 | 0.00 | 0.00 | 2744.75 | 0.00 | 0.00 | 12378.87 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 25220.79 | 01-JAN-11:09 | 0.00 | 121485.84 | 06-JAN-07:10 | 0.00 | 26470.68 | 29-JAN-13:30 | 0.00 |
February | 25220.79 | 01-FEB-11:09 | 0.00 | 115208.76 | 14-FEB-07:10 | 0.00 | 27604.85 | 24-FEB-13:20 | 0.00 |
March | 25220.79 | 01-MAR-11:09 | 0.00 | 108060.28 | 05-MAR-07:10 | 0.00 | 27581.36 | 01-MAR-13:20 | 0.00 |
April | 25220.79 | 01-APR-10:09 | 0.00 | 71631.94 | 05-APR-02:30 | 0.00 | 25691.89 | 02-APR-12:20 | 0.00 |
May | 25220.79 | 01-MAY-10:09 | 0.00 | 37319.60 | 01-MAY-06:10 | 0.00 | 24173.50 | 01-MAY-12:30 | 0.00 |
June | 25220.79 | 01-JUN-10:09 | 0.00 | 18978.46 | 04-JUN-05:10 | 0.00 | 23709.37 | 01-JUN-12:50 | 0.00 |
July | 25220.79 | 01-JUL-10:09 | 0.00 | 4920.27 | 02-JUL-05:10 | 0.00 | 23241.27 | 01-JUL-12:50 | 0.00 |
August | 25220.79 | 01-AUG-10:09 | 0.00 | 10935.25 | 19-AUG-05:10 | 0.00 | 22874.18 | 01-AUG-12:50 | 0.00 |
September | 25220.79 | 01-SEP-10:09 | 0.00 | 16945.77 | 06-SEP-06:10 | 0.00 | 22958.31 | 29-SEP-12:20 | 0.00 |
October | 25220.79 | 01-OCT-10:09 | 0.00 | 50737.46 | 30-OCT-06:10 | 0.00 | 23395.24 | 31-OCT-12:50 | 0.00 |
November | 25220.79 | 01-NOV-10:09 | 0.00 | 79649.04 | 25-NOV-07:10 | 0.00 | 23864.69 | 30-NOV-13:00 | 0.00 |
December | 25220.79 | 01-DEC-11:09 | 0.00 | 114827.42 | 24-DEC-07:10 | 0.00 | 24274.15 | 31-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 25220.79 | 0.00 | 4920.27 | 0.00 | 22874.18 | 0.00 | |||
Maximum of Months | 25220.79 | 0.00 | 121485.84 | 0.00 | 27604.85 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.67 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
February | 20.67 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
March | 23.67 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
April | 5.33 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
May | 0.50 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.66 | 0.00 | 24.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.55 | 0.00 | 24.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.56 | 0.00 | 24.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.55 | 0.00 | 24.55 |
October | 1.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
November | 6.67 | 19.81 | 0.00 | 19.81 | 0.00 | 19.81 | 0.00 | 19.81 |
December | 27.83 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Annual Sum or Average | 112.33 | 19.46 | 0.00 | 19.46 | 9.83 | 19.87 | 0.00 | 19.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.26 | 0.00 | 19.26 |
Maximum of Months | 27.83 | 20.51 | 0.00 | 20.51 | 4.33 | 24.66 | 0.00 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.32 | 0.00 | 27.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.70 | 0.00 | 27.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 28.09 | 3.50 | 27.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 28.73 | 1.50 | 28.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 28.82 | 0.00 | 28.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.90 | 0.00 | 27.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.34 | 0.00 | 27.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.90 | 0.00 | 26.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 88.83 | 28.25 | 5.00 | 28.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 28.82 | 3.50 | 28.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.84 | 525.50 | 20.81 | 525.50 | 20.81 |
February | 551.00 | 20.84 | 376.17 | 20.79 | 376.17 | 20.76 |
March | 612.00 | 20.84 | 359.50 | 20.78 | 359.50 | 20.74 |
April | 574.83 | 21.05 | 160.33 | 20.91 | 154.00 | 20.80 |
May | 411.83 | 21.41 | 152.67 | 21.87 | 27.50 | 21.76 |
June | 372.17 | 22.56 | 339.67 | 23.14 | 173.83 | 23.25 |
July | 321.50 | 23.15 | 487.17 | 23.57 | 219.83 | 23.64 |
August | 350.33 | 22.88 | 436.17 | 23.39 | 199.33 | 23.46 |
September | 423.33 | 21.39 | 174.00 | 21.98 | 44.17 | 22.00 |
October | 575.67 | 20.96 | 65.33 | 20.88 | 49.00 | 20.74 |
November | 591.00 | 20.88 | 208.67 | 20.75 | 208.67 | 20.68 |
December | 609.00 | 20.84 | 511.00 | 20.81 | 511.00 | 20.80 |
Annual Sum or Average | 6002.67 | 21.30 | 3796.17 | 21.55 | 2848.50 | 21.49 |
Minimum of Months | 321.50 | 20.84 | 65.33 | 20.75 | 27.50 | 20.68 |
Maximum of Months | 612.00 | 23.15 | 525.50 | 23.57 | 525.50 | 23.64 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 18.72 | 568.83 | 18.72 | 568.83 | 18.72 |
February | 551.00 | 18.73 | 477.50 | 18.72 | 477.50 | 18.71 |
March | 612.00 | 18.75 | 489.50 | 18.72 | 489.50 | 18.71 |
April | 526.67 | 19.23 | 312.17 | 19.41 | 264.33 | 19.26 |
May | 382.83 | 22.46 | 381.33 | 23.59 | 188.50 | 23.82 |
June | 434.67 | 25.37 | 516.67 | 25.46 | 379.83 | 25.61 |
July | 509.67 | 25.94 | 588.00 | 25.82 | 499.50 | 25.89 |
August | 470.17 | 25.82 | 588.00 | 25.65 | 457.17 | 25.74 |
September | 400.17 | 22.83 | 352.83 | 23.78 | 197.17 | 24.15 |
October | 543.83 | 19.41 | 182.17 | 19.75 | 127.33 | 19.68 |
November | 578.17 | 18.86 | 321.00 | 18.86 | 308.83 | 18.80 |
December | 609.00 | 18.72 | 544.33 | 18.72 | 544.33 | 18.71 |
Annual Sum or Average | 6228.17 | 20.93 | 5322.33 | 21.36 | 4502.83 | 21.38 |
Minimum of Months | 382.83 | 18.72 | 182.17 | 18.72 | 127.33 | 18.71 |
Maximum of Months | 612.00 | 25.94 | 588.00 | 25.82 | 568.83 | 25.89 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.83541 | 11.76310 | -0.7021 | 16.28117 |
February | 551.00000 | 20.83712 | 13.68914 | -0.6436 | 14.78994 |
March | 612.00000 | 20.84408 | 17.71516 | -0.6107 | 13.90823 |
April | 590.00000 | 21.12353 | 23.42261 | -0.4401 | 10.94483 |
May | 611.00000 | 22.20804 | 36.91637 | -1.0486 | 32.38628 |
June | 592.00000 | 23.02674 | 53.28773 | -0.6211 | 17.24435 |
July | 609.00000 | 23.45150 | 59.74445 | -0.3744 | 10.29469 |
August | 612.00000 | 23.24663 | 58.15812 | -0.4547 | 12.15042 |
September | 590.00000 | 22.05077 | 46.66294 | -0.9689 | 28.74287 |
October | 610.00000 | 21.12111 | 33.49562 | -0.3172 | 8.72173 |
November | 591.00000 | 20.88072 | 22.14019 | -0.5193 | 11.76157 |
December | 609.00000 | 20.83581 | 13.17881 | -0.6803 | 15.61706 |
Annual Sum or Average | 7187.00000 | 21.71191 | 32.63292 | -0.6146 | 16.06966 |
Minimum of Months | 551.00000 | 20.83541 | 11.76310 | -1.0486 | 8.72173 |
Maximum of Months | 612.00000 | 23.45150 | 59.74445 | -0.3172 | 32.38628 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.72427 | 19.64157 | -0.8036 | 19.25466 |
February | 551.00000 | 18.73161 | 22.59495 | -0.7758 | 18.39027 |
March | 612.00000 | 18.74560 | 27.40050 | -0.7468 | 17.47570 |
April | 590.00000 | 19.80905 | 32.80266 | -0.4464 | 14.08307 |
May | 611.00000 | 23.17213 | 40.66853 | -0.4425 | 24.32138 |
June | 592.00000 | 24.99411 | 51.52552 | 0.26691 | 14.18161 |
July | 609.00000 | 25.57053 | 55.85561 | 0.53816 | 14.61851 |
August | 612.00000 | 25.33935 | 54.25534 | 0.45519 | 13.51611 |
September | 590.00000 | 23.07790 | 48.61495 | -0.3497 | 20.92174 |
October | 610.00000 | 19.89702 | 42.01618 | -0.3035 | 11.77812 |
November | 591.00000 | 18.98103 | 30.95732 | -0.6108 | 14.72476 |
December | 609.00000 | 18.72480 | 21.07627 | -0.7760 | 18.32978 |
Annual Sum or Average | 7187.00000 | 21.33181 | 37.36882 | -0.3297 | 16.79513 |
Minimum of Months | 551.00000 | 18.72427 | 19.64157 | -0.8036 | 11.77812 |
Maximum of Months | 612.00000 | 25.57053 | 55.85561 | 0.53816 | 24.32138 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.212609E+09 | 58951678.99 | 11.17 | 0.169999E+09 | 42610629.21 | 0.00 | 0.62 | 23-APR-17:10 | 0.00 | 01-APR-00:01 | 10137.54 | 23-APR-17:10 | 8072.62 | 23-APR-17:03 | 2083.43 | 23-APR-17:20 | 2710.23 | 23-APR-17:10 | 0.00 | 01-APR-00:01 |
May | 0.336394E+10 | 0.903188E+09 | 145.90 | 0.266415E+10 | 0.699789E+09 | 0.00 | 1.00 | 19-MAY-02:61 | 0.00 | 01-MAY-00:01 | 36753.14 | 19-MAY-02:61 | 28198.82 | 19-MAY-02:61 | 11096.15 | 25-MAY-02:61 | 8811.54 | 19-MAY-02:61 | 0.00 | 01-MAY-00:01 |
June | 0.921674E+10 | 0.233784E+10 | 268.55 | 0.589810E+10 | 0.331864E+10 | 0.00 | 1.00 | 07-JUN-02:61 | 0.00 | 01-JUN-00:01 | 40835.16 | 30-JUN-02:61 | 23361.34 | 07-JUN-02:61 | 23964.25 | 30-JUN-02:61 | 9089.05 | 30-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.140466E+11 | 0.349426E+10 | 375.18 | 0.841645E+10 | 0.563019E+10 | 0.00 | 1.00 | 01-JUL-02:62 | 0.00 | 01-JUL-00:01 | 40499.54 | 04-JUL-02:41 | 20107.91 | 31-JUL-02:61 | 26534.74 | 04-JUL-02:61 | 9064.61 | 04-JUL-02:41 | 0.00 | 01-JUL-00:01 |
August | 0.876726E+10 | 0.225283E+10 | 286.80 | 0.541531E+10 | 0.335195E+10 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 | 38329.39 | 09-AUG-02:61 | 23534.77 | 07-AUG-02:61 | 20244.58 | 09-AUG-03:21 | 8916.85 | 09-AUG-02:61 | 0.00 | 01-AUG-00:01 |
September | 0.103975E+10 | 0.286413E+09 | 73.22 | 0.761571E+09 | 0.278177E+09 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 | 37922.71 | 01-SEP-02:61 | 21876.63 | 02-SEP-02:61 | 21484.77 | 01-SEP-02:61 | 8889.91 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 |
October | 91632753.52 | 27223963.36 | 13.83 | 77486336.08 | 14146417.44 | 0.00 | 0.30 | 19-OCT-15:10 | 0.00 | 01-OCT-00:01 | 4599.30 | 19-OCT-15:10 | 3964.10 | 19-OCT-15:10 | 764.53 | 19-OCT-13:00 | 1332.16 | 19-OCT-15:10 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.367386E+11 | 0.936070E+10 | 1174.64 | 0.234031E+11 | 0.133355E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.140466E+11 | 0.349426E+10 | 375.18 | 0.841645E+10 | 0.563019E+10 | 0.00 | 1.00 | 0.00 | 40835.16 | 28198.82 | 26534.74 | 9089.05 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.233134E+09 | 63952641.27 | 16.88 | 0.188280E+09 | 44853585.99 | 0.00 | 1.00 | 14-APR-03:22 | 0.00 | 01-APR-00:01 | 13964.34 | 14-APR-03:22 | 9628.30 | 14-APR-03:22 | 4727.27 | 24-APR-02:61 | 3350.55 | 14-APR-03:22 | 0.00 | 01-APR-00:01 |
May | 0.425542E+10 | 0.110739E+10 | 185.52 | 0.333754E+10 | 0.917874E+09 | 0.00 | 1.00 | 11-MAY-02:61 | 0.00 | 01-MAY-00:01 | 27960.76 | 25-MAY-02:42 | 20503.91 | 19-MAY-02:61 | 14088.43 | 27-MAY-02:61 | 6703.57 | 17-MAY-02:61 | 0.00 | 01-MAY-00:01 |
June | 0.125669E+11 | 0.307220E+10 | 346.15 | 0.779374E+10 | 0.477316E+10 | 0.00 | 1.00 | 02-JUN-02:61 | 0.00 | 01-JUN-00:01 | 31066.25 | 30-JUN-02:61 | 23060.81 | 29-JUN-16:25 | 18678.03 | 30-JUN-02:52 | 7501.26 | 29-JUN-16:00 | 0.00 | 01-JUN-00:01 |
July | 0.189386E+11 | 0.452507E+10 | 447.42 | 0.108434E+11 | 0.809524E+10 | 0.00 | 1.00 | 01-JUL-02:11 | 0.00 | 01-JUL-00:01 | 31066.25 | 23-JUL-10:33 | 18008.94 | 23-JUL-13:00 | 20851.68 | 04-JUL-02:56 | 7089.71 | 15-JUL-13:53 | 0.00 | 01-JUL-00:01 |
August | 0.130372E+11 | 0.321405E+10 | 374.83 | 0.759483E+10 | 0.544235E+10 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 | 28951.84 | 09-AUG-02:52 | 17599.27 | 08-AUG-14:10 | 17331.96 | 01-AUG-02:32 | 6769.91 | 09-AUG-02:52 | 0.00 | 01-AUG-00:01 |
September | 0.231966E+10 | 0.627637E+09 | 149.80 | 0.154111E+10 | 0.778547E+09 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 | 28316.49 | 01-SEP-02:61 | 20437.22 | 09-SEP-02:61 | 17347.16 | 01-SEP-02:02 | 6727.60 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 |
October | 0.177299E+09 | 51660461.31 | 22.11 | 0.142218E+09 | 35080253.98 | 0.00 | 1.00 | 20-OCT-02:61 | 0.00 | 01-OCT-00:01 | 27960.76 | 20-OCT-02:61 | 15535.10 | 20-OCT-02:61 | 12425.66 | 20-OCT-02:61 | 6703.57 | 20-OCT-02:61 | 0.00 | 01-OCT-00:01 |
November | 1725654.88 | 525748.52 | 1.25 | 1036792.63 | 688862.25 | 0.00 | 0.12 | 21-NOV-04:20 | 0.00 | 01-NOV-00:01 | 1367.14 | 21-NOV-04:20 | 960.20 | 03-NOV-03:40 | 667.14 | 21-NOV-04:20 | 413.43 | 21-NOV-04:20 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.515299E+11 | 0.126625E+11 | 1543.97 | 0.314421E+11 | 0.200878E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.189386E+11 | 0.452507E+10 | 447.42 | 0.108434E+11 | 0.809524E+10 | 0.00 | 1.00 | 0.00 | 31066.25 | 23060.81 | 20851.68 | 7501.26 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.14 | 30.10 | 42.04 | 28.49 | 271.94 | 0.00 | 0.00 | 0.00 |
February | 113.38 | 48.35 | 65.03 | 70.22 | 212.86 | 0.00 | 0.00 | 0.00 |
March | 154.53 | 77.53 | 77.00 | 125.23 | 163.29 | 0.00 | 0.00 | 0.00 |
April | 214.24 | 115.58 | 98.66 | 222.29 | 96.49 | 0.00 | 0.00 | 0.00 |
May | 231.86 | 101.95 | 129.91 | 275.01 | 52.18 | 0.00 | 0.00 | 0.00 |
June | 262.51 | 125.61 | 136.90 | 334.56 | 36.99 | 0.00 | 0.00 | 0.00 |
July | 257.15 | 120.78 | 136.38 | 333.79 | 35.92 | 0.00 | 0.00 | 0.00 |
August | 198.25 | 86.67 | 111.58 | 247.24 | 42.70 | 0.00 | 0.00 | 0.00 |
September | 158.76 | 71.08 | 87.69 | 178.00 | 65.22 | 0.00 | 0.00 | 0.00 |
October | 96.12 | 36.45 | 59.67 | 80.46 | 102.90 | 0.00 | 0.00 | 0.00 |
November | 61.18 | 20.44 | 40.73 | 31.18 | 162.75 | 0.00 | 0.00 | 0.00 |
December | 55.82 | 20.62 | 35.20 | 17.43 | 264.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 156.49 | 71.32 | 85.17 | 162.42 | 125.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 55.82 | 20.44 | 35.20 | 17.43 | 35.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 262.51 | 125.61 | 136.90 | 334.56 | 271.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 453.67 | 315.72 | 137.95 | 399.99 | 480.21 | 0.00 | 0.00 | 0.00 |
February | 574.43 | 388.13 | 186.30 | 575.03 | 397.35 | 0.00 | 0.00 | 0.00 |
March | 505.90 | 320.21 | 185.69 | 523.48 | 319.82 | 0.00 | 0.00 | 0.00 |
April | 457.93 | 248.42 | 209.51 | 521.55 | 203.97 | 0.00 | 0.00 | 0.00 |
May | 384.79 | 131.26 | 253.53 | 478.87 | 112.10 | 0.00 | 0.00 | 0.00 |
June | 345.22 | 91.69 | 253.53 | 454.06 | 77.83 | 0.00 | 0.00 | 0.00 |
July | 377.42 | 119.22 | 258.20 | 513.26 | 74.70 | 0.00 | 0.00 | 0.00 |
August | 403.25 | 168.48 | 234.78 | 529.91 | 88.17 | 0.00 | 0.00 | 0.00 |
September | 432.27 | 230.20 | 202.07 | 529.60 | 134.47 | 0.00 | 0.00 | 0.00 |
October | 369.36 | 217.32 | 152.04 | 400.84 | 203.71 | 0.00 | 0.00 | 0.00 |
November | 329.08 | 206.62 | 122.46 | 313.27 | 304.64 | 0.00 | 0.00 | 0.00 |
December | 350.27 | 229.77 | 120.50 | 284.54 | 465.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 414.26 | 221.20 | 193.06 | 459.49 | 237.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 329.08 | 91.69 | 120.50 | 284.54 | 74.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 574.43 | 388.13 | 258.20 | 575.03 | 480.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.92 | 30.52 | 42.39 | 31.55 | 277.28 | 0.00 | 0.00 | 0.00 |
February | 118.83 | 54.27 | 64.56 | 81.56 | 220.05 | 0.00 | 0.00 | 0.00 |
March | 156.40 | 80.04 | 76.36 | 132.19 | 168.63 | 0.00 | 0.00 | 0.00 |
April | 199.79 | 101.21 | 98.58 | 205.89 | 100.91 | 0.00 | 0.00 | 0.00 |
May | 245.50 | 117.13 | 128.36 | 296.81 | 54.87 | 0.00 | 0.00 | 0.00 |
June | 236.90 | 102.47 | 134.43 | 300.85 | 38.17 | 0.00 | 0.00 | 0.00 |
July | 252.90 | 117.60 | 135.30 | 329.18 | 36.93 | 0.00 | 0.00 | 0.00 |
August | 208.11 | 94.58 | 113.53 | 262.11 | 43.64 | 0.00 | 0.00 | 0.00 |
September | 162.65 | 73.09 | 89.56 | 184.12 | 66.91 | 0.00 | 0.00 | 0.00 |
October | 102.73 | 41.24 | 61.49 | 91.26 | 105.31 | 0.00 | 0.00 | 0.00 |
November | 62.38 | 21.02 | 41.36 | 33.75 | 165.94 | 0.00 | 0.00 | 0.00 |
December | 55.60 | 19.45 | 36.15 | 17.58 | 268.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 156.43 | 71.15 | 85.28 | 164.39 | 128.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 55.60 | 19.45 | 36.15 | 17.58 | 36.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 252.90 | 117.60 | 135.30 | 329.18 | 277.28 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.193212E+09 | 80613938.50 | 0.112598E+09 | 76303100.39 | 0.728374E+09 |
February | 0.274287E+09 | 0.116975E+09 | 0.157311E+09 | 0.169867E+09 | 0.514957E+09 |
March | 0.413897E+09 | 0.207647E+09 | 0.206250E+09 | 0.335414E+09 | 0.437346E+09 |
April | 0.555304E+09 | 0.299572E+09 | 0.255732E+09 | 0.576181E+09 | 0.250105E+09 |
May | 0.621023E+09 | 0.273073E+09 | 0.347950E+09 | 0.736584E+09 | 0.139751E+09 |
June | 0.680413E+09 | 0.325571E+09 | 0.354842E+09 | 0.867192E+09 | 95885219.14 |
July | 0.688761E+09 | 0.323487E+09 | 0.365274E+09 | 0.894023E+09 | 96195671.71 |
August | 0.531001E+09 | 0.232137E+09 | 0.298864E+09 | 0.662205E+09 | 0.114378E+09 |
September | 0.411516E+09 | 0.184227E+09 | 0.227289E+09 | 0.461367E+09 | 0.169046E+09 |
October | 0.257454E+09 | 97630329.23 | 0.159823E+09 | 0.215508E+09 | 0.275600E+09 |
November | 0.158568E+09 | 52987804.32 | 0.105580E+09 | 80826274.39 | 0.421848E+09 |
December | 0.149498E+09 | 55223657.32 | 94274240.95 | 46681507.47 | 0.707723E+09 |
Annual Sum or Average | 0.493493E+10 | 0.224915E+10 | 0.268579E+10 | 0.512215E+10 | 0.395121E+10 |
Minimum of Months | 0.149498E+09 | 52987804.32 | 94274240.95 | 46681507.47 | 95885219.14 |
Maximum of Months | 0.688761E+09 | 0.325571E+09 | 0.365274E+09 | 0.894023E+09 | 0.728374E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121512E+10 | 0.845625E+09 | 0.369493E+09 | 0.107133E+10 | 0.128619E+10 |
February | 0.138967E+10 | 0.938968E+09 | 0.450699E+09 | 0.139112E+10 | 0.961280E+09 |
March | 0.135500E+10 | 0.857662E+09 | 0.497342E+09 | 0.140210E+10 | 0.856603E+09 |
April | 0.118694E+10 | 0.643907E+09 | 0.543038E+09 | 0.135187E+10 | 0.528701E+09 |
May | 0.103061E+10 | 0.351557E+09 | 0.679056E+09 | 0.128261E+10 | 0.300249E+09 |
June | 0.894798E+09 | 0.237655E+09 | 0.657143E+09 | 0.117693E+10 | 0.201727E+09 |
July | 0.101088E+10 | 0.319328E+09 | 0.691554E+09 | 0.137472E+10 | 0.200088E+09 |
August | 0.108007E+10 | 0.451253E+09 | 0.628822E+09 | 0.141931E+10 | 0.236147E+09 |
September | 0.112045E+10 | 0.596679E+09 | 0.523775E+09 | 0.137273E+10 | 0.348541E+09 |
October | 0.989294E+09 | 0.582070E+09 | 0.407224E+09 | 0.107362E+10 | 0.545628E+09 |
November | 0.852981E+09 | 0.535563E+09 | 0.317419E+09 | 0.811987E+09 | 0.789633E+09 |
December | 0.938164E+09 | 0.615405E+09 | 0.322759E+09 | 0.762123E+09 | 0.124658E+10 |
Annual Sum or Average | 0.130640E+11 | 0.697567E+10 | 0.608832E+10 | 0.144904E+11 | 0.750137E+10 |
Minimum of Months | 0.852981E+09 | 0.237655E+09 | 0.317419E+09 | 0.762123E+09 | 0.200088E+09 |
Maximum of Months | 0.138967E+10 | 0.938968E+09 | 0.691554E+09 | 0.141931E+10 | 0.128619E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195299E+09 | 81751817.52 | 0.113547E+09 | 84499731.80 | 0.742655E+09 |
February | 0.287463E+09 | 0.131287E+09 | 0.156176E+09 | 0.197307E+09 | 0.532347E+09 |
March | 0.418894E+09 | 0.214377E+09 | 0.204517E+09 | 0.354049E+09 | 0.451654E+09 |
April | 0.517867E+09 | 0.262341E+09 | 0.255525E+09 | 0.533662E+09 | 0.261560E+09 |
May | 0.657537E+09 | 0.313730E+09 | 0.343806E+09 | 0.794979E+09 | 0.146956E+09 |
June | 0.614047E+09 | 0.265596E+09 | 0.348451E+09 | 0.779805E+09 | 98938090.01 |
July | 0.677374E+09 | 0.314982E+09 | 0.362392E+09 | 0.881685E+09 | 98919206.34 |
August | 0.557402E+09 | 0.253325E+09 | 0.304078E+09 | 0.702040E+09 | 0.116891E+09 |
September | 0.421583E+09 | 0.189448E+09 | 0.232136E+09 | 0.477240E+09 | 0.173423E+09 |
October | 0.275159E+09 | 0.110466E+09 | 0.164693E+09 | 0.244423E+09 | 0.282052E+09 |
November | 0.161687E+09 | 54491489.58 | 0.107196E+09 | 87491319.64 | 0.430117E+09 |
December | 0.148921E+09 | 52090351.25 | 96830751.97 | 47095210.75 | 0.718466E+09 |
Annual Sum or Average | 0.493323E+10 | 0.224389E+10 | 0.268935E+10 | 0.518428E+10 | 0.405398E+10 |
Minimum of Months | 0.148921E+09 | 52090351.25 | 96830751.97 | 47095210.75 | 98919206.34 |
Maximum of Months | 0.677374E+09 | 0.314982E+09 | 0.362392E+09 | 0.881685E+09 | 0.742655E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 404.58 | 973.98 | 598.73 | 376.34 | 222.39 | 0.00 | 0.00 |
February | 692.91 | 796.37 | 806.64 | 490.75 | 315.88 | 0.00 | 0.00 |
March | 754.06 | 624.89 | 816.83 | 477.78 | 339.05 | 0.00 | 0.00 |
April | 927.45 | 379.09 | 871.96 | 465.21 | 406.75 | 0.00 | 0.00 |
May | 1038.81 | 207.26 | 862.15 | 350.34 | 511.80 | 0.00 | 0.00 |
June | 1082.74 | 146.26 | 844.62 | 319.76 | 524.86 | 0.00 | 0.00 |
July | 1171.05 | 142.37 | 887.48 | 357.60 | 529.88 | 0.00 | 0.00 |
August | 1035.48 | 170.73 | 809.62 | 349.73 | 459.89 | 0.00 | 0.00 |
September | 885.02 | 259.90 | 753.69 | 374.36 | 379.32 | 0.00 | 0.00 |
October | 566.57 | 405.92 | 568.22 | 295.01 | 273.20 | 0.00 | 0.00 |
November | 361.35 | 616.48 | 452.64 | 248.09 | 204.55 | 0.00 | 0.00 |
December | 273.74 | 952.08 | 461.69 | 269.83 | 191.85 | 0.00 | 0.00 |
Annual Sum or Average | 766.22 | 471.63 | 727.17 | 363.67 | 363.50 | 0.00 | 0.00 |
Minimum of Months | 273.74 | 142.37 | 452.64 | 248.09 | 191.85 | 0.00 | 0.00 |
Maximum of Months | 1171.05 | 973.98 | 887.48 | 490.75 | 529.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.108362E+10 | 0.260871E+10 | 0.160363E+10 | 0.100799E+10 | 0.595638E+09 | 0.00 | 0.00 |
February | 0.167628E+10 | 0.192657E+10 | 0.195142E+10 | 0.118723E+10 | 0.764186E+09 | 0.00 | 0.00 |
March | 0.201967E+10 | 0.167371E+10 | 0.218779E+10 | 0.127969E+10 | 0.908108E+09 | 0.00 | 0.00 |
April | 0.240396E+10 | 0.982611E+09 | 0.226011E+10 | 0.120582E+10 | 0.105430E+10 | 0.00 | 0.00 |
May | 0.278235E+10 | 0.555136E+09 | 0.230917E+10 | 0.938359E+09 | 0.137081E+10 | 0.00 | 0.00 |
June | 0.280647E+10 | 0.379093E+09 | 0.218926E+10 | 0.828822E+09 | 0.136044E+10 | 0.00 | 0.00 |
July | 0.313655E+10 | 0.381328E+09 | 0.237702E+10 | 0.957797E+09 | 0.141922E+10 | 0.00 | 0.00 |
August | 0.277343E+10 | 0.457284E+09 | 0.216848E+10 | 0.936715E+09 | 0.123176E+10 | 0.00 | 0.00 |
September | 0.229398E+10 | 0.673650E+09 | 0.195355E+10 | 0.970354E+09 | 0.983199E+09 | 0.00 | 0.00 |
October | 0.151750E+10 | 0.108723E+10 | 0.152191E+10 | 0.790166E+09 | 0.731741E+09 | 0.00 | 0.00 |
November | 0.936611E+09 | 0.159790E+10 | 0.117324E+10 | 0.643042E+09 | 0.530195E+09 | 0.00 | 0.00 |
December | 0.733187E+09 | 0.255006E+10 | 0.123658E+10 | 0.722719E+09 | 0.513864E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.241636E+11 | 0.148733E+11 | 0.229322E+11 | 0.114687E+11 | 0.114635E+11 | 0.00 | 0.00 |
Minimum of Months | 0.733187E+09 | 0.379093E+09 | 0.117324E+10 | 0.643042E+09 | 0.513864E+09 | 0.00 | 0.00 |
Maximum of Months | 0.313655E+10 | 0.260871E+10 | 0.237702E+10 | 0.127969E+10 | 0.141922E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.165343E+11 | -0.157295E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -804778144.0 | 58.99 | 0.00 | 0.00 |
February | 0.152615E+11 | -0.145350E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -726482050.1 | 58.99 | 0.00 | 0.00 |
March | 0.168637E+11 | -0.160605E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -803174162.4 | 58.99 | 0.00 | 0.00 |
April | 0.157905E+11 | -0.150343E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -756257261.1 | 59.00 | 0.00 | 0.00 |
May | 0.154851E+11 | -0.147696E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -715447126.1 | 58.99 | 0.00 | 0.00 |
June | 0.141130E+11 | -0.134541E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -658935890.4 | 58.99 | 0.00 | 0.00 |
July | 0.138049E+11 | -0.131360E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -668957895.5 | 58.99 | 0.00 | 0.00 |
August | 0.134625E+11 | -0.127893E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -673155387.4 | 58.99 | 0.00 | 0.00 |
September | 0.131049E+11 | -0.124129E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -692056887.2 | 58.98 | 0.00 | 0.00 |
October | 0.141069E+11 | -0.133311E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -775762950.3 | 58.99 | 0.00 | 0.00 |
November | 0.144478E+11 | -0.136778E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -770047508.1 | 58.99 | 0.00 | 0.00 |
December | 0.157848E+11 | -0.149812E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -803605365.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.178760E+12 | -0.169911E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.884866E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.131049E+11 | -0.160605E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -804778144.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.168637E+11 | -0.124129E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -658935890.4 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.26 | 0.24 | 01-JAN-08:39 | 3194.27 | 28.81 | 145.83 | 234.67 | 3216.68 | 28.94 | 147.67 | 234.33 |
February | 265.33 | 0.26 | 0.24 | 01-FEB-08:39 | 5548.33 | 31.00 | 186.17 | 256.33 | 6067.43 | 33.11 | 214.67 | 257.00 |
March | 254.17 | 0.26 | 0.24 | 02-MAR-10:39 | 2104.14 | 21.59 | 80.50 | 328.00 | 2137.14 | 21.55 | 77.33 | 324.33 |
April | 296.33 | 0.27 | 0.24 | 01-APR-07:19 | 2491.63 | 20.41 | 64.33 | 362.33 | 1972.54 | 18.37 | 27.00 | 360.00 |
May | 437.50 | 0.25 | 0.24 | 01-MAY-05:30 | 1687.96 | 18.89 | 31.33 | 425.67 | 2078.85 | 18.90 | 20.17 | 426.33 |
June | 401.83 | 0.26 | 0.24 | 01-JUN-04:00 | 1944.37 | 18.93 | 24.50 | 432.67 | 1739.38 | 18.92 | 21.83 | 425.00 |
July | 409.17 | 0.25 | 0.24 | 01-JUL-04:00 | 2095.49 | 19.18 | 36.50 | 433.67 | 2366.50 | 19.20 | 38.50 | 431.33 |
August | 352.83 | 0.25 | 0.24 | 01-AUG-07:40 | 1864.87 | 19.55 | 54.00 | 385.83 | 2126.79 | 19.62 | 60.50 | 388.67 |
September | 344.17 | 0.25 | 0.24 | 01-SEP-06:10 | 1833.06 | 21.24 | 95.83 | 337.83 | 1824.28 | 21.29 | 95.33 | 341.17 |
October | 299.00 | 0.25 | 0.24 | 01-OCT-06:40 | 2728.73 | 27.28 | 188.83 | 298.00 | 2716.61 | 27.46 | 191.33 | 297.50 |
November | 255.50 | 0.27 | 0.24 | 01-NOV-07:00 | 2794.11 | 30.10 | 187.33 | 238.33 | 2771.88 | 30.02 | 186.00 | 237.67 |
December | 226.33 | 0.26 | 0.24 | 01-DEC-08:30 | 2066.88 | 25.87 | 110.33 | 220.83 | 2062.69 | 25.92 | 110.67 | 219.33 |
Annual Sum or Average | 3785.50 | 0.26 | 2426.69 | 22.82 | 1205.50 | 3954.17 | 2499.71 | 22.84 | 1191.00 | 3942.67 | ||
Minimum of Months | 226.33 | 0.25 | 0.24 | 1687.96 | 18.89 | 24.50 | 220.83 | 1739.38 | 18.37 | 20.17 | 219.33 | |
Maximum of Months | 437.50 | 0.27 | 0.24 | 5548.33 | 31.00 | 188.83 | 433.67 | 6067.43 | 33.11 | 214.67 | 431.33 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.648355E+11 | 60170.83 | 01-JAN-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.475706E+11 | 60170.83 | 01-FEB-03:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.416329E+11 | 60170.83 | 03-MAR-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183793E+11 | 60170.83 | 05-APR-02:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.417392E+10 | 23797.59 | 01-MAY-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.724913E+09 | 9444.19 | 04-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152110E+09 | 5324.63 | 02-JUL-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.279886E+09 | 9611.30 | 19-AUG-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.357641E+10 | 13701.44 | 20-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151941E+11 | 60170.83 | 30-OCT-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.300306E+11 | 60170.83 | 12-NOV-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.608809E+11 | 60170.83 | 01-DEC-03:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287431E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.152110E+09 | 5324.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.648355E+11 | 60170.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.615177E+11 | 81609.42 | 02-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.419366E+11 | 70078.02 | 25-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330630E+11 | 70439.67 | 05-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110322E+11 | 37643.57 | 05-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104106E+10 | 20566.20 | 01-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 52429423.10 | 9141.30 | 04-JUN-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10951467.90 | 2195.31 | 19-AUG-04:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.255426E+09 | 6266.06 | 23-SEP-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.625560E+10 | 30941.24 | 30-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213264E+11 | 46312.24 | 29-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.548896E+11 | 76721.24 | 25-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231381E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.615177E+11 | 81609.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.212609E+09 | 0.169999E+09 | 10137.54 | 23-APR-17:10 | 8072.29 | 0.00 |
May | 0.00 | 0.00 | 0.336394E+10 | 0.266415E+10 | 36753.14 | 19-MAY-02:61 | 28198.82 | 0.00 |
June | 0.00 | 0.00 | 0.921674E+10 | 0.589810E+10 | 40835.16 | 30-JUN-02:61 | 16870.91 | 0.00 |
July | 0.00 | 0.00 | 0.140466E+11 | 0.841645E+10 | 40499.54 | 04-JUL-02:41 | 14554.19 | 0.00 |
August | 0.00 | 0.00 | 0.876726E+10 | 0.541531E+10 | 38329.39 | 09-AUG-02:61 | 18735.36 | 0.00 |
September | 0.00 | 0.00 | 0.103975E+10 | 0.761571E+09 | 37922.71 | 01-SEP-02:61 | 16437.94 | 0.00 |
October | 0.00 | 0.00 | 91632753.52 | 77486336.08 | 4599.30 | 19-OCT-15:10 | 3964.10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.367386E+11 | 0.234031E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.140466E+11 | 0.841645E+10 | 40835.16 | 28198.82 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.233134E+09 | 0.188280E+09 | 13964.34 | 14-APR-03:22 | 9628.30 | 0.00 |
May | 0.00 | 0.00 | 0.425542E+10 | 0.333754E+10 | 27960.76 | 25-MAY-02:42 | 18338.40 | 0.00 |
June | 0.00 | 0.00 | 0.125669E+11 | 0.779374E+10 | 31066.25 | 30-JUN-02:61 | 12749.84 | 0.00 |
July | 0.00 | 0.00 | 0.189386E+11 | 0.108434E+11 | 31066.25 | 23-JUL-10:33 | 15169.61 | 0.00 |
August | 0.00 | 0.00 | 0.130372E+11 | 0.759483E+10 | 28951.84 | 09-AUG-02:52 | 12466.26 | 0.00 |
September | 0.00 | 0.00 | 0.231966E+10 | 0.154111E+10 | 28316.49 | 01-SEP-02:61 | 10969.34 | 0.00 |
October | 0.00 | 0.00 | 0.177299E+09 | 0.142218E+09 | 27960.76 | 20-OCT-02:61 | 15535.10 | 0.00 |
November | 0.00 | 0.00 | 1725654.88 | 1036792.63 | 1367.14 | 21-NOV-04:20 | 700.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.515299E+11 | 0.314421E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.189386E+11 | 0.108434E+11 | 31066.25 | 18338.40 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 6169.90 | 23373.01 | 31-JAN-13:43 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6306.29 | 23609.25 | 26-FEB-14:00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 6296.18 | 23602.82 | 01-MAR-13:40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6095.94 | 23156.01 | 01-APR-12:15 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5809.20 | 22159.93 | 01-MAY-12:14 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5485.43 | 20867.33 | 01-JUN-12:57 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 5194.83 | 19670.70 | 01-JUL-12:34 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 5069.17 | 18819.72 | 01-AUG-12:20 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5080.20 | 19003.55 | 30-SEP-12:25 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 5269.53 | 19992.63 | 31-OCT-12:30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 5570.82 | 21241.10 | 30-NOV-13:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5887.11 | 22492.12 | 31-DEC-14:00 |
Annual Sum or Average | 0.00 | 5682.53 | ||||
Minimum of Months | 0.00 | 0.00 | 5069.17 | 18819.72 | ||
Maximum of Months | 0.00 | 0.00 | 6306.29 | 23609.25 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112411E+10 | 0.23 | 503.64 | 01-JAN-00:01 | 0.28 |
February | 0.101533E+10 | 0.23 | 503.64 | 01-FEB-00:01 | 0.28 |
March | 0.112411E+10 | 0.23 | 503.64 | 01-MAR-00:01 | 0.28 |
April | 0.109790E+10 | 0.23 | 503.64 | 01-APR-04:01 | 0.28 |
May | 0.119180E+10 | 0.24 | 503.64 | 01-MAY-04:01 | 0.27 |
June | 0.118286E+10 | 0.25 | 503.64 | 01-JUN-03:25 | 0.27 |
July | 0.124489E+10 | 0.25 | 503.64 | 01-JUL-01:00 | 0.27 |
August | 0.123802E+10 | 0.25 | 503.64 | 01-AUG-01:13 | 0.27 |
September | 0.116589E+10 | 0.25 | 503.64 | 01-SEP-00:40 | 0.27 |
October | 0.115056E+10 | 0.24 | 503.64 | 01-OCT-02:61 | 0.27 |
November | 0.109284E+10 | 0.23 | 503.64 | 01-NOV-04:01 | 0.27 |
December | 0.112411E+10 | 0.23 | 503.64 | 01-DEC-00:01 | 0.28 |
Annual Sum or Average | 0.137524E+11 | 0.24 | |||
Minimum of Months | 0.101533E+10 | 0.23 | 503.64 | 0.27 | |
Maximum of Months | 0.124489E+10 | 0.25 | 503.64 | 0.28 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.262356E+10 | 0.67 | 1671.29 | 01-JAN-03:01 | 0.92 |
February | 0.218596E+10 | 0.64 | 1671.29 | 01-FEB-03:06 | 0.92 |
March | 0.222736E+10 | 0.62 | 1671.29 | 03-MAR-03:03 | 0.92 |
April | 0.175830E+10 | 0.55 | 1671.29 | 05-APR-02:08 | 0.92 |
May | 0.156357E+10 | 0.48 | 1006.73 | 26-MAY-02:61 | 0.71 |
June | 0.148781E+10 | 0.48 | 1671.29 | 30-JUN-02:61 | 0.90 |
July | 0.152197E+10 | 0.48 | 1671.29 | 04-JUL-02:61 | 0.90 |
August | 0.151294E+10 | 0.48 | 1671.29 | 09-AUG-02:61 | 0.91 |
September | 0.150533E+10 | 0.48 | 1671.29 | 01-SEP-02:61 | 0.91 |
October | 0.174642E+10 | 0.52 | 1671.29 | 30-OCT-02:62 | 0.92 |
November | 0.195761E+10 | 0.59 | 1671.29 | 12-NOV-03:02 | 0.92 |
December | 0.256237E+10 | 0.66 | 1671.29 | 01-DEC-03:05 | 0.92 |
Annual Sum or Average | 0.226532E+11 | 0.55 | |||
Minimum of Months | 0.148781E+10 | 0.48 | 1006.73 | 0.71 | |
Maximum of Months | 0.262356E+10 | 0.67 | 1671.29 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.161295E+10 | 0.60 | 1148.56 | 02-JAN-05:04 | 0.91 |
February | 0.134947E+10 | 0.57 | 1057.69 | 25-FEB-05:02 | 0.88 |
March | 0.138872E+10 | 0.55 | 1060.54 | 05-MAR-05:02 | 0.88 |
April | 0.117978E+10 | 0.51 | 802.10 | 05-APR-04:03 | 0.76 |
May | 0.115348E+10 | 0.51 | 1263.64 | 17-MAY-02:61 | 0.95 |
June | 0.121098E+10 | 0.53 | 1263.64 | 07-JUN-02:61 | 0.95 |
July | 0.130258E+10 | 0.55 | 1263.64 | 01-JUL-02:11 | 0.95 |
August | 0.121691E+10 | 0.53 | 1263.64 | 01-AUG-02:61 | 0.94 |
September | 0.111251E+10 | 0.51 | 1263.64 | 01-SEP-02:61 | 0.94 |
October | 0.118046E+10 | 0.50 | 845.00 | 20-OCT-04:01 | 0.78 |
November | 0.126024E+10 | 0.53 | 870.41 | 29-NOV-05:03 | 0.80 |
December | 0.156072E+10 | 0.59 | 1110.04 | 25-DEC-05:02 | 0.90 |
Annual Sum or Average | 0.155288E+11 | 0.54 | |||
Minimum of Months | 0.111251E+10 | 0.50 | 802.10 | 0.76 | |
Maximum of Months | 0.161295E+10 | 0.60 | 1263.64 | 0.95 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 48.84 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 50.07 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 50.25 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 50.07 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 49.23 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 51.33 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:03 | 0.00 | 0.00 | 51.20 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 51.64 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 51.71 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 50.35 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 51.64 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 50.92 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 48.84 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 51.71 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 34.90 | 34.90 | 6169.90 | 23373.01 | 31-JAN-13:43 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 50.38 | 50.38 | 6306.29 | 23609.25 | 26-FEB-14:00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 50.03 | 50.03 | 6296.18 | 23602.82 | 01-MAR-13:40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 50.11 | 50.11 | 6095.94 | 23156.01 | 01-APR-12:15 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 35.36 | 35.36 | 5809.20 | 22159.93 | 01-MAY-12:14 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 51.13 | 51.13 | 5485.43 | 20867.33 | 01-JUN-12:57 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 51.28 | 51.28 | 5194.83 | 19670.70 | 01-JUL-12:34 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 51.98 | 51.98 | 5069.17 | 18819.72 | 01-AUG-12:20 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 51.96 | 51.96 | 5080.20 | 19003.55 | 30-SEP-12:25 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 38.63 | 38.63 | 5269.53 | 19992.63 | 31-OCT-12:30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 51.27 | 51.27 | 5570.82 | 21241.10 | 30-NOV-13:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 51.25 | 51.25 | 5887.11 | 22492.12 | 31-DEC-14:00 |
Annual Sum or Average | 0.00 | 5682.53 | ||||||
Minimum of Months | 0.00 | 0.00 | 34.90 | 34.90 | 5069.17 | 18819.72 | ||
Maximum of Months | 0.00 | 0.00 | 51.98 | 51.98 | 6306.29 | 23609.25 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.262356E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.218596E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.222736E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.181725E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.246676E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.382564E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.501623E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.376577E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.179174E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.177364E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.195761E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.256237E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.320139E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.177364E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.501623E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.161295E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134947E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.138872E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.124374E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.226087E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.428318E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.582765E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.443096E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.174014E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.123212E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.126076E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.156072E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.281913E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.123212E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.582765E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.262356E+10 | 0.00 | 0.648355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.218596E+10 | 0.00 | 0.475706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.222736E+10 | 0.00 | 0.416329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.175830E+10 | 0.212609E+09 | 0.183793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156357E+10 | 0.336244E+10 | 0.417392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148781E+10 | 0.919656E+10 | 0.724913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152197E+10 | 0.140176E+11 | 0.152110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151294E+10 | 0.875119E+10 | 0.279886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150533E+10 | 0.103825E+10 | 0.357641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174642E+10 | 91632753.52 | 0.151941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195761E+10 | 0.00 | 0.300306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.256237E+10 | 0.00 | 0.608809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226532E+11 | 0.366703E+11 | 0.287431E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148781E+10 | 0.00 | 0.152110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.262356E+10 | 0.140176E+11 | 0.648355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.161295E+10 | 0.00 | 0.615177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134947E+10 | 0.00 | 0.419366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138872E+10 | 0.00 | 0.330630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117978E+10 | 0.233134E+09 | 0.110322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115348E+10 | 0.424747E+10 | 0.104106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121098E+10 | 0.125122E+11 | 52429423.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.130258E+10 | 0.188931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.121691E+10 | 0.130111E+11 | 10951467.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111251E+10 | 0.231623E+10 | 0.255426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118046E+10 | 0.176586E+09 | 0.625560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126024E+10 | 1725654.88 | 0.213264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156072E+10 | 0.00 | 0.548896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155288E+11 | 0.513916E+11 | 0.231381E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161295E+10 | 0.188931E+11 | 0.615177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.262356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.218596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.222736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.175830E+10 | 0.00 | 0.00 | 0.00 | 58951678.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156357E+10 | 0.00 | 0.00 | 0.00 | 0.903188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148781E+10 | 0.00 | 0.00 | 0.00 | 0.233784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152197E+10 | 0.00 | 0.00 | 0.00 | 0.349426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151294E+10 | 0.00 | 0.00 | 0.00 | 0.225283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150533E+10 | 0.00 | 0.00 | 0.00 | 0.286413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174642E+10 | 0.00 | 0.00 | 0.00 | 27223963.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.256237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226532E+11 | 0.00 | 0.00 | 0.00 | 0.936070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.262356E+10 | 0.00 | 0.00 | 0.00 | 0.349426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.161295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117978E+10 | 0.00 | 0.00 | 0.00 | 63952641.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115348E+10 | 0.00 | 0.00 | 0.00 | 0.110739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121098E+10 | 0.00 | 0.00 | 0.00 | 0.307220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.130258E+10 | 0.00 | 0.00 | 0.00 | 0.452507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.121691E+10 | 0.00 | 0.00 | 0.00 | 0.321405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111251E+10 | 0.00 | 0.00 | 0.00 | 0.627637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118046E+10 | 0.00 | 0.00 | 0.00 | 51660461.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126024E+10 | 0.00 | 0.00 | 0.00 | 525748.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155288E+11 | 0.00 | 0.00 | 0.00 | 0.126625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161295E+10 | 0.00 | 0.00 | 0.00 | 0.452507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.191144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451762E+11 | 0.00 | 0.00 | 3.62 |
February | 0.213765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348474E+11 | 0.00 | 0.00 | 3.62 |
March | 0.226494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322604E+11 | 0.00 | 0.00 | 3.61 |
April | 0.491539E+10 | 9600084.96 | 0.00 | 1306435.14 | 0.00 | 0.148940E+11 | 0.513740E+09 | 0.00 | 3.64 |
May | 0.685067E+10 | 0.179026E+09 | 0.00 | 10231918.96 | 0.00 | 0.234364E+10 | 0.253472E+10 | 0.00 | 4.11 |
June | 0.416253E+10 | 0.153201E+10 | 0.00 | 16553017.08 | 7098168.54 | 0.160344E+09 | 0.342820E+10 | 0.00 | 4.57 |
July | 0.250468E+10 | 0.223671E+10 | 0.00 | 20552439.14 | 2608776.25 | 0.00 | 0.386133E+10 | 0.00 | 4.81 |
August | 0.354134E+10 | 0.871895E+09 | 0.00 | 22429640.32 | 0.00 | 22351019.79 | 0.484788E+10 | 0.00 | 4.82 |
September | 0.846293E+10 | 27626018.45 | 0.00 | 8933764.10 | 0.00 | 0.126105E+10 | 0.328568E+10 | 0.00 | 4.08 |
October | 0.719141E+10 | 0.00 | 0.00 | 1485468.47 | 0.00 | 0.115505E+11 | 0.647759E+09 | 0.00 | 3.65 |
November | 0.314102E+10 | 0.00 | 0.00 | 9505.31 | 0.00 | 0.239040E+11 | 43121812.34 | 0.00 | 3.60 |
December | 0.179960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434757E+11 | 0.00 | 0.00 | 3.60 |
Annual Sum or Average | 0.488836E+11 | 0.485686E+10 | 0.00 | 81502188.53 | 9706944.78 | 0.209896E+12 | 0.191624E+11 | 0.00 | 3.98 |
Minimum of Months | 0.179960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 |
Maximum of Months | 0.846293E+10 | 0.223671E+10 | 0.00 | 22429640.32 | 7098168.54 | 0.451762E+11 | 0.484788E+10 | 0.00 | 4.82 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.899328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110527E+09 | 0.00 | 0.00 | 7.30 |
February | 0.680908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78461220.09 | 0.00 | 0.00 | 7.07 |
March | 0.620449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64619590.40 | 0.00 | 0.00 | 6.87 |
April | 0.378040E+11 | 0.00 | 0.00 | 3017768.20 | 0.00 | 25030303.84 | 0.202120E+10 | 0.00 | 6.59 |
May | 0.168431E+11 | 14668973.69 | 0.00 | 27975624.32 | 0.00 | 0.00 | 0.107367E+11 | 0.00 | 6.61 |
June | 0.649974E+10 | 0.164012E+10 | 0.00 | 45790200.35 | 3651955.44 | 0.00 | 0.125798E+11 | 0.00 | 6.93 |
July | 0.377609E+10 | 0.201820E+10 | 0.00 | 60889099.42 | 2246623.87 | 0.00 | 0.112277E+11 | 0.00 | 7.10 |
August | 0.417369E+10 | 0.583004E+09 | 0.00 | 61301830.52 | 0.00 | 0.00 | 0.151694E+11 | 0.00 | 6.89 |
September | 0.157246E+11 | 0.00 | 0.00 | 27385654.36 | 0.00 | 0.00 | 0.130346E+11 | 0.00 | 6.63 |
October | 0.351057E+11 | 0.00 | 0.00 | 3912595.55 | 0.00 | 2531273.95 | 0.265233E+10 | 0.00 | 6.52 |
November | 0.503597E+11 | 0.00 | 0.00 | 397322.12 | 0.00 | 26851725.35 | 0.485168E+09 | 0.00 | 6.75 |
December | 0.837076E+11 | 0.00 | 0.00 | 3.67 | 0.00 | 84487800.72 | 1921421.17 | 0.00 | 7.17 |
Annual Sum or Average | 0.474063E+12 | 0.425599E+10 | 0.00 | 0.230670E+09 | 5898579.31 | 0.392509E+09 | 0.679087E+11 | 0.00 | 6.87 |
Minimum of Months | 0.377609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.52 |
Maximum of Months | 0.899328E+11 | 0.201820E+10 | 0.00 | 61301830.52 | 3651955.44 | 0.110527E+09 | 0.151694E+11 | 0.00 | 7.30 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.132947E+11 | 0.304191E+11 | 0.207614E+12 | 0.00 | 0.366959E+11 |
February | 0.234316E+11 | 0.231455E+11 | 0.162001E+12 | 0.00 | 0.298136E+11 |
March | 0.363412E+11 | 0.216382E+11 | 0.152396E+12 | 0.00 | 0.291007E+11 |
April | 0.490217E+11 | 0.135005E+11 | 0.102777E+12 | 0.101479E+09 | 0.219937E+11 |
May | 0.593807E+11 | 0.769452E+10 | 0.732984E+11 | 0.785292E+09 | 0.300925E+11 |
June | 0.618290E+11 | 0.394690E+10 | 0.469400E+11 | 0.111322E+10 | 0.491891E+11 |
July | 0.632763E+11 | 0.214247E+10 | 0.360991E+11 | 0.126429E+10 | 0.650355E+11 |
August | 0.519746E+11 | 0.417677E+10 | 0.508031E+11 | 0.141089E+10 | 0.490221E+11 |
September | 0.370588E+11 | 0.810632E+10 | 0.774717E+11 | 0.900579E+09 | 0.224585E+11 |
October | 0.192222E+11 | 0.125067E+11 | 0.995584E+11 | 0.180042E+09 | 0.183281E+11 |
November | 0.746071E+10 | 0.171898E+11 | 0.128508E+12 | 0.00 | 0.207653E+11 |
December | 0.777450E+10 | 0.285135E+11 | 0.196107E+12 | 0.00 | 0.333364E+11 |
Annual Sum or Average | 0.430066E+12 | 0.172980E+12 | 0.133357E+13 | 0.575580E+10 | 0.405831E+12 |
Minimum of Months | 0.746071E+10 | 0.214247E+10 | 0.360991E+11 | 0.00 | 0.183281E+11 |
Maximum of Months | 0.632763E+11 | 0.304191E+11 | 0.207614E+12 | 0.141089E+10 | 0.650355E+11 |