Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 08:25:27
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1752.88 | 7544.39 | 7544.39 |
Net Site Energy | 1752.88 | 7544.39 | 7544.39 |
Total Source Energy | 2966.53 | 12767.88 | 12767.88 |
Net Source Energy | 2966.53 | 12767.88 | 12767.88 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 532.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 39.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 29.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 276.59 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 76.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 231.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 63.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 511.95 | 1240.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 532.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 39.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 29.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 27.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 76.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 231.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 16.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 29.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 532.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 39.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 29.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 27.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 276.59 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 76.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 231.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 63.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 243.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 498.15 | 3287.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1462.25 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2203.44 | 5340.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 243.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 498.15 | 3287.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1462.25 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2203.44 | 5340.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 511.954 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 511.954 | 100.00 |
Total On-Site and Utility Electric Sources | 511.954 | 100.00 |
Total Electricity End Uses | 511.954 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 17.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4435.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 7.5044 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.8503 | 18.52 | 1074.0064 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.6773 | 2.48 | 595.3967 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.6773 | 2.48 | 595.3967 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 7.5044 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.8503 | 18.52 | 1074.0064 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 8.6773 | 1.24 | 595.3967 | |||||||
Conditioned Total | 232.34 | 8.6773 | 1.24 | 595.3967 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 8.6773 | 2.48 | 595.3967 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-11:20 | 02-FEB-20:40 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 143629.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 16726.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1331.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 13514.13 | 18386.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4073.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16608.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2997.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 38642.29 | 178623.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 143629.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 16726.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1331.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 12146.55 | 18386.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 4073.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 16608.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1376.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 577.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 124.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 93.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 85.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 875.96 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 241.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 250.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 200.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1621.36 | 1345.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2483.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 536.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 400.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 369.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3770.11 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1041.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1079.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 860.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6978.29 | 5789.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2483.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 536.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 400.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 369.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3770.11 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1041.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1079.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 860.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6978.29 | 5789.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.71 |
KITCHEN DIRECT AIR | 1.30 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.71 | 1.71 | 1.71 | 1.71 | 1.71 | 1.71 | 1.00 | 1.00 | 1.71 |
PSZ-AC_2:2 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.000000 | 1.30 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.71 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.30 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.71 | 1833.44 |
PSZ-AC_2:2_ADDAQ FAN | 1.30 | 1438.29 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.71 | 1.71 | 1.71 | 1.13 | 42548.34 | 60240.27 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 0.857392 | 32259.21 | 91164.68 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.71 | 0.856711 | 1.14 | 42548.34 | 21274.17 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.30 | 0.649539 | 0.866053 | 32259.21 | 16129.60 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 60240.27 |
PSZ-AC_2:2 HEATING COIL | 91164.68 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 7.504 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 124.291 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.850 | 282.654 | 791.353 | 0.000 | 0.000 | 0.000 | 1083.857 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 871.800 | 7.504 | 9.958 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 871.800 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1144.319 | 9.850 | 182.411 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1144.319 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 515.917 | 4.441 | 82.240 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 851.667 | 7.331 | 135.761 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.4391 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2550 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2550 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.043 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.845 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.845 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.38584905E-12 | 0.75146531E-15 | -0.12966877E-12 | 0.12247089E-15 |
34 | 6 | 0.32626755E-07 | 0.12794687E-09 | 0.74410738E-08 | -0.15657130E-12 |
35 | 5 | -0.20999199E-03 | 0.10694986E-05 | -0.10771460E-03 | 0.73422529E-08 |
36 | 4 | 0.31512205 | 0.50965885E-03 | 0.10796022 | -0.36842960E-04 |
37 | 3 | -7.7206601 | 0.15495837E-01 | -2.4737779 | 0.31237450E-01 |
38 | 2 | 42.368774 | 0.54174396E-01 | 15.816616 | -0.35002435 |
39 | 1 | -81.692611 | 0.24088120E-01 | -29.635684 | 1.1030598 |
40 | 0 | 46.824332 | 0.47759164E-03 | 16.279740 | |
41 | 7 | -0.16459679E-08 | -0.32692664E-15 | 0.10422529E-13 | -0.14706702E-15 |
42 | 6 | 0.71279470E-05 | 0.48919389E-08 | 0.31855004E-02 | -0.26722647E-04 |
43 | 5 | -0.51387372E-03 | 0.28990711E-05 | -0.22347621 | 0.19539581E-02 |
44 | 4 | 0.11828338E-01 | 0.13198320E-03 | 4.8254089 | -0.45225216E-01 |
45 | 3 | -0.10389352 | 0.10497736E-02 | -37.998046 | 0.39839544 |
46 | 2 | 0.36893606 | 0.17465704E-02 | 116.43846 | -1.4173309 |
47 | 1 | -0.53252332 | 0.53234446E-03 | -143.88053 | 2.0485998 |
48 | 0 | 0.25963561 | 0.12843692E-04 | 60.838472 | |
49 | 7 | -0.16459679E-08 | -0.32692664E-15 | 0.10422529E-13 | -0.14706702E-15 |
50 | 6 | 0.71279470E-05 | 0.48919389E-08 | 0.31855004E-02 | -0.26722647E-04 |
51 | 5 | -0.51387372E-03 | 0.28990711E-05 | -0.22347621 | 0.19539581E-02 |
52 | 4 | 0.11828338E-01 | 0.13198320E-03 | 4.8254089 | -0.45225216E-01 |
53 | 3 | -0.10389352 | 0.10497736E-02 | -37.998046 | 0.39839544 |
54 | 2 | 0.36893606 | 0.17465704E-02 | 116.43846 | -1.4173309 |
55 | 1 | -0.53252332 | 0.53234446E-03 | -143.88053 | 2.0485998 |
56 | 0 | 0.25963561 | 0.12843692E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.4731_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.053 | 0.3093 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.584 | 5.025E-003 | 6.281E-003 | 5.934 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.4119E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.3079E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.2287E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.0631E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.0121E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.7620E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5307E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.3706E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.7750E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.5737E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 0.1019 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 9.9428E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 6.1378E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.0362E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.4417E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.4427E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.0804E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.1814E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.7814E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.9321E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.4412E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.8100E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.3758E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.5308E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 18517.68388 | 22221.22066 | 1.42785 | 1.71342 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53651E-002 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 8727.59602 | 10473.11522 | 0.39012 | 0.46814 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -26.20000 | 3.61342E-004 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16873.78667 | 20248.54401 | 1.08257 | 1.29908 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 30.24600 | 1.53633E-002 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 1021.49725 | 1225.79670 | 4.13099E-002 | 1.14133 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -26.20000 | 3.61342E-004 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 25400.66 | 1.71342 | 1.71342 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 32930.51 | 0.46814 | 0.46814 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 25394.41 | 1.29908 | 1.29908 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 87202.24 | 1.14133 | 1.14133 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.71342 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.29908 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.71342 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.71342 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.71342 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.71342 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.71342 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.71342 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.29908 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.29908 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.29908 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.29908 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.29908 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.29908 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.71342 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.29908 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.71342 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.71342 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 1833.44235 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.71342 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.71342 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.71342 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.13086 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.71342 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.85671 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.14228 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 42548.34000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21274.17000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 42548.34000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 60240.27378 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 60240.27378 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.29908 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.29908 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1438.28608 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.29908 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.29908 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.29908 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85739 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.29908 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64954 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.86605 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32259.21000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16129.60500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32259.21000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 91164.67808 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 91164.67808 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 41330.5 | 11.66 | 11.61 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 31335.9 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | N/A | 2.689 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | N/A | 2.689 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | N/A | 2.689 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.255 | 0.240 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.255 | 0.240 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1231181242 | 0.4964126043 | Pass | Pass | 0.1394711556 | 0.3888110906 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1485260548 | 0.7076939824 | Pass | Pass | 3.2875161887E-002 | 9.5418806592E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.1696322232 | 0.1890503202 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 482.85 | 153.81 | 1161.44 | 5.62 | 570.17 | 2373.90 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.245 | 0.255 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.245 | 0.255 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.689 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.689 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 7.5044 | 116.17 | 871.80 | LightsWired | LTG_SCH_DINING | 91.35 | 168.00 | 65.88 | 0.0000 | Y | 10.78 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.8503 | 116.17 | 1144.32 | LightsWired | LTG_SCH_KITCHEN | 87.05 | 168.00 | 86.54 | 0.0000 | Y | 18.59 |
Interior Lighting Total | 8.6773 | 232.34 | 2016.12 | 29.37 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.22 | 871.80 | 191.80 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.22 | 871.80 | 191.80 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 216.58 | AstronomicalClock | - | 49.24 | 49.24 | 2.00 | |
EXTERIOR_LIGHTS_B | 1823.66 | AstronomicalClock | - | 83.63 | 73.31 | 25.10 | |
Exterior Lighting Total | 2040.24 | 27.10 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 42548.34 | 29829.79 | 12718.55 | 0.70 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32259.21 | 22616.29 | 9642.92 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 41330.5 | 11.66 | 11.61 | ||||
PSZ-AC_2:2 COOLING COIL | 31335.9 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 60240.27 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 91164.68 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 1.56 | 1211.87 | 778.12 | 1.00 | 0.64 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.71 | 1833.44 | 1070.05 | 1.00 | 1.34 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.30 | 1438.29 | 1107.16 | 1.00 | 1.34 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 18517.68 | 22221.22 | 191.28 | 1.428 | 1.713 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.87 | 0.01137 | 31.20 | 0.01537 | 0.416 | 0.00 |
KITCHEN | 16873.79 | 20248.54 | 174.30 | 1.083 | 1.299 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.01023 | 30.25 | 0.01536 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 8727.60 | 10473.12 | 90.15 | 0.390 | 0.468 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00763 | -26.20 | 0.00036 | 0.416 | 0.00 |
KITCHEN | 1021.50 | 1225.80 | 10.55 | 0.041 | 1.141 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 18.89 | 18.89 | 0.00430 | -26.20 | 0.00036 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.71 | 1.71 | 0.47 | 0.47 | 1.7134 | 1.7134 | 1.7134 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.30 | 1.30 | 1.14 | 1.14 | 1.2991 | 1.2991 | 1.2991 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 42548.340 | 29829.790 | 1.713420 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21274.17 | 12897.23 | 1.142280 | 25.64 | 19.48 | 0.01233897 | 11.89 | 11.30 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 36.4233 | 23.87 | 0.01136851 | 58.5691 | 18517.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 60240.274 | 60240.274 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 60240.27 | 60240.27 | 1.713422 | 9.54 | 7.45 | 0.00586705 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 24.2822 | 21.11 | 0.00763269 | 46.7806 | 8727.60 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 32259.210 | 22616.287 | 1.299080 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 16129.60 | 8819.06 | 0.866053 | 29.74 | 22.33 | 0.01473953 | 11.87 | 11.29 | 0.00850000 | 30.25 | 0.01536331 | 22.87 | 131.7856 | 26.10 | 0.01022624 | 46.2130 | 16873.79 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 91164.678 | 91164.678 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 91164.68 | 91164.68 | 1.299078 | -20.80 | -20.80 | 0.00086561 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 87.8572 | 18.61 | 0.00451415 | 32.4570 | 432.65 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 42548.340 | 29829.790 | 1.713420 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.7775 | 1004.8586 | 1.1486 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.713422 | 1.96796062 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 21274.17 | 12897.23 | 1.0000 | 1.31197235 | 1.142280 | 25.64 | 19.48 | 0.01233897 | 57216.1 | 11.89 | 11.30 | 0.00850000 | 33397.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21274.17 | 31.20 | 0.01536508 | 23.13 | 0.41605618 | 36.4233 | 23.86 | 0.01136851 | 23.87 | 0.01136851 | 58.5691 | 18517.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 60240.274 | 60240.274 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.713422 | 1.96796062 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | Sensible | 60240.27 | 60240.27 | 1.0000 | 1.96796062 | 1.713422 | 9.54 | 7.45 | 0.00586705 | 24360.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60240.27 | -26.20 | 0.00036134 | -26.20 | 0.41605618 | 24.2822 | 21.00 | 0.00763269 | 21.11 | 0.00763269 | 46.7806 | 8727.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32259.210 | 22616.287 | 1.299080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1032.2400 | 1004.8586 | 1.1486 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.299078 | 1.49206415 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 16129.60 | 8819.06 | 1.0000 | 0.99471060 | 0.866053 | 29.74 | 22.33 | 0.01473953 | 67558.8 | 11.87 | 11.29 | 0.00850000 | 33369.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16129.60 | 30.25 | 0.01536331 | 22.87 | 1.14133354 | 131.7856 | 26.06 | 0.01022624 | 26.10 | 0.01022624 | 46.2130 | 16873.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 91164.678 | 91164.678 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.299078 | 1.49206415 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 91164.68 | 91164.68 | 1.0000 | 1.49206415 | 1.299078 | -20.80 | -20.80 | 0.00086561 | -18773.6 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 91164.68 | -26.20 | 0.00036134 | -26.20 | 1.14133354 | 87.8572 | 18.24 | 0.00451415 | 18.61 | 0.00451415 | 32.4570 | 432.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.71 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.30 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3989.17 | 5799.83 | 2757.83 |
KITCHEN | 5031.50 | 6249.17 | 4245.33 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5219.17 | 7114.33 | 4435.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 107.17 | 33.17 | 0.17 | 0.00 |
KITCHEN | 0.00 | 200.83 | 0.00 | 17.50 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 107.17 | 202.17 | 0.17 | 17.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.816 | 2.794 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 9.326 | 0.044 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.085 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 8.432 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 12471985.42 | 0.00 | 12471985.42 | 7100432.48 | 19572417.90 | 13120747.55 | 1417.29 | 6153.21 | 1189.50 | 501.90 |
KITCHEN | 24457443.59 | 0.00 | 24457443.59 | 193741.04 | 24651184.63 | 35993094.65 | 8611.24 | 139.32 | 9.44 | 628.29 |
Total Facility | 36929429.00 | 0.00 | 36929429.00 | 7294173.53 | 44223602.53 | 49113842.20 | 8612.41 | 6154.27 | 1194.90 | 841.29 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4671 | 0.0000 | 0.4671 | 0.2713 | 0.7383 | 0.4161 | 0.00 | 6020.27 | 1166.73 |
KITCHEN | 0.9054 | 0.0000 | 0.9054 | 0.0043 | 0.9097 | 1.1413 | 7043.81 | 137.70 | 5.49 |
Total Facility | 1.3724 | 0.0000 | 1.3724 | 0.2756 | 1.6480 | 1.5574 | 7043.81 | 6020.71 | 1171.04 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 16453403.54 | 0.00 | 16453403.54 | 13120747.55 | 1413.88 | 0.12 | 7345.99 | 501.87 |
PSZ-AC_2:2 | 32263751.61 | 0.00 | 32263751.61 | 35993094.65 | 1413.88 | 3760.58 | 3585.54 | 628.29 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6162 | 0.0000 | 0.6162 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.1943 | 0.0000 | 1.1943 | 1.1413 | 0.00 | 3674.27 | 3512.73 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1185.48 | 355.05 | 6148.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 218.37 | 1147.41 | 6449.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.0449 | 0.7688 | 0.5490 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.1856 | 1.2390 | 1.1899 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 374 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 511.95 | 5207.64 | 02-FEB-01:10 | 38642.29 | 04-AUG-11:20 |
Electricity:Building | 323.82 | 2948.69 | 01-JAN-01:10 | 19261.27 | 02-JAN-11:10 |
Electricity:Zone:DINING | 81.11 | 392.54 | 01-JAN-01:10 | 4341.96 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 305.96 | 2539.66 | 01-JAN-01:10 | 15745.17 | 02-JAN-11:10 |
InteriorLights:Electricity | 29.37 | 221.88 | 03-JUN-05:00 | 1654.77 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:DINING | 10.78 | 68.62 | 03-JUN-05:00 | 735.19 | 02-JAN-16:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 29.37 | 221.88 | 03-JUN-05:00 | 1654.77 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 29.37 | 221.88 | 03-JUN-05:00 | 1654.77 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 10.78 | 68.62 | 03-JUN-05:00 | 735.19 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 29.37 | 221.88 | 03-JUN-05:00 | 1654.77 | 02-JAN-16:40 |
Electricity:Zone:KITCHEN | 242.71 | 2556.15 | 01-JAN-01:10 | 14919.31 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 18.59 | 153.26 | 01-JAN-01:10 | 919.59 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 18.59 | 153.26 | 01-JAN-01:10 | 919.59 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 276.59 | 2263.87 | 01-JAN-01:10 | 14413.88 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 276.59 | 2263.87 | 01-JAN-01:10 | 14413.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 206.26 | 1993.86 | 01-JAN-01:10 | 10483.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 63.15 | 1035.58 | 02-FEB-23:30 | 4592.33 | 18-APR-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
Electricity:Plant | 45.29 | 779.93 | 02-FEB-23:30 | 2545.69 | 07-JUL-03:30 |
LowTempRefrigeration:Refrigeration:Electricity | 16.16 | 0.00 | 01-JAN-11:10 | 1469.45 | 07-JUL-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 29.14 | 701.41 | 01-MAR-01:10 | 1076.23 | 19-MAR-13:10 |
ElectricityPurchased:Facility | 511.95 | 5207.64 | 02-FEB-01:10 | 38642.29 | 04-AUG-11:20 |
ElectricityPurchased:Plant | 511.95 | 5207.64 | 02-FEB-01:10 | 38642.29 | 04-AUG-11:20 |
Cogeneration:ElectricityPurchased | 511.95 | 5207.64 | 02-FEB-01:10 | 38642.29 | 04-AUG-11:20 |
General:Cogeneration:ElectricityPurchased | 511.95 | 5207.64 | 02-FEB-01:10 | 38642.29 | 04-AUG-11:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 511.95 | 5207.64 | 02-FEB-01:10 | 38642.29 | 04-AUG-11:20 |
ElectricityNet:Plant | 511.95 | 5207.64 | 02-FEB-01:10 | 38642.29 | 04-AUG-11:20 |
Cogeneration:ElectricityNet | 511.95 | 5207.64 | 02-FEB-01:10 | 38642.29 | 04-AUG-11:20 |
General:Cogeneration:ElectricityNet | 511.95 | 5207.64 | 02-FEB-01:10 | 38642.29 | 04-AUG-11:20 |
Electricity:HVAC | 115.74 | 0.00 | 01-JAN-01:10 | 21658.57 | 04-AUG-13:00 |
Fans:Electricity | 76.39 | 0.00 | 01-JAN-01:10 | 4168.79 | 04-AUG-13:00 |
General:Fans:Electricity | 76.39 | 0.00 | 01-JAN-01:10 | 4168.79 | 04-AUG-13:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 39.35 | 0.00 | 01-JAN-00:10 | 17489.78 | 04-AUG-13:00 |
General:Cooling:Electricity | 39.35 | 0.00 | 01-JAN-00:10 | 17489.78 | 04-AUG-13:00 |
ExteriorLights:Electricity | 27.10 | 0.00 | 01-JAN-08:00 | 2040.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 27.10 | 0.00 | 01-JAN-08:00 | 2040.24 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-10:30 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-10:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1240.93 | 2558.65 | 07-JAN-03:40 | 178623.68 | 02-FEB-20:40 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 532.36 | 0.00 | 01-JAN-01:10 | 145791.44 | 02-FEB-07:10 |
Heating:NaturalGas | 532.36 | 0.00 | 01-JAN-01:10 | 145791.44 | 02-FEB-07:10 |
General:Heating:NaturalGas | 532.36 | 0.00 | 01-JAN-01:10 | 145791.44 | 02-FEB-07:10 |
NaturalGas:Plant | 231.41 | 720.00 | 07-JAN-03:40 | 28547.03 | 20-FEB-13:20 |
WaterSystems:NaturalGas | 231.41 | 720.00 | 07-JAN-03:40 | 28547.03 | 20-FEB-13:20 |
Water Heater:WaterSystems:NaturalGas | 231.41 | 720.00 | 07-JAN-03:40 | 28547.03 | 20-FEB-13:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1302.93 | 2739.67 | 02-FEB-01:10 | 171769.68 | 02-FEB-21:00 |
EnergyTransfer:Building | 485.27 | 1369.84 | 02-FEB-01:10 | 46684.30 | 02-FEB-12:10 |
EnergyTransfer:Zone:KITCHEN | 350.54 | 1369.84 | 02-FEB-01:10 | 22117.61 | 05-SEP-04:10 |
Refrigeration:EnergyTransfer | 144.97 | 2699.59 | 02-FEB-23:30 | 7834.84 | 15-APR-10:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 72.49 | 1349.79 | 02-FEB-23:30 | 3917.42 | 15-APR-10:40 |
General:Refrigeration:EnergyTransfer | 72.49 | 1349.79 | 02-FEB-23:30 | 3917.42 | 15-APR-10:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 72.49 | 1349.79 | 02-FEB-23:30 | 3917.42 | 15-APR-10:40 |
EnergyTransfer:Plant | 232.21 | 1349.81 | 05-FEB-23:10 | 24322.67 | 19-MAR-13:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 16.30 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 56.19 | 1114.23 | 01-MAR-01:10 | 2238.70 | 19-MAR-13:10 |
EnergyTransfer:Zone:DINING | 134.72 | 0.00 | 01-JAN-01:10 | 33923.83 | 02-FEB-21:00 |
Heating:EnergyTransfer | 72.89 | 0.00 | 01-JAN-00:10 | 33923.83 | 02-FEB-21:00 |
Heating:EnergyTransfer:Zone:DINING | 72.87 | 0.00 | 01-JAN-00:10 | 33923.83 | 02-FEB-21:00 |
General:Heating:EnergyTransfer | 72.89 | 0.00 | 01-JAN-00:10 | 33923.83 | 02-FEB-21:00 |
General:Heating:EnergyTransfer:Zone:DINING | 72.87 | 0.00 | 01-JAN-00:10 | 33923.83 | 02-FEB-21:00 |
Cooling:EnergyTransfer | 339.89 | 0.00 | 01-JAN-01:10 | 28314.24 | 07-SEP-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 61.86 | 0.00 | 01-JAN-01:10 | 15157.22 | 01-FEB-03:30 |
General:Cooling:EnergyTransfer | 339.89 | 0.00 | 01-JAN-01:10 | 28314.24 | 07-SEP-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 61.86 | 0.00 | 01-JAN-01:10 | 15157.22 | 01-FEB-03:30 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 1987.73 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 1987.73 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 278.04 | 0.00 | 01-JAN-01:10 | 18247.09 | 05-SEP-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 278.04 | 0.00 | 01-JAN-01:10 | 18247.09 | 05-SEP-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 159.72 | 0.00 | 01-JAN-00:10 | 22006.00 | 20-FEB-13:10 |
PlantLoopHeatingDemand:Plant | 159.72 | 0.00 | 01-JAN-00:10 | 22006.00 | 20-FEB-13:10 |
WaterSystems:PlantLoopHeatingDemand | 159.72 | 0.00 | 01-JAN-00:10 | 22006.00 | 20-FEB-13:10 |
General:WaterSystems:PlantLoopHeatingDemand | 159.72 | 0.00 | 01-JAN-00:10 | 22006.00 | 20-FEB-13:10 |
EnergyTransfer:HVAC | 585.45 | 0.00 | 01-JAN-01:10 | 116633.15 | 02-FEB-07:10 |
HeatingCoils:EnergyTransfer | 425.89 | 0.00 | 01-JAN-01:10 | 116633.15 | 02-FEB-07:10 |
CoolingCoils:EnergyTransfer | 159.56 | 0.00 | 01-JAN-00:10 | 74304.44 | 04-AUG-12:00 |
WaterSystems:EnergyTransfer | 159.72 | 0.00 | 01-JAN-00:10 | 22006.00 | 20-FEB-13:10 |
WaterUse:WaterSystems:EnergyTransfer | 159.72 | 0.00 | 01-JAN-00:10 | 22006.00 | 20-FEB-13:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 72.866 | -61.856 | 0.000 | 0.000 | 72.383 | 10.781 | 52.748 | 23.328 | 0.000 | 2.382 | 0.001 | 0.000 | -20.295 | 0.000 | -128.491 | -23.846 |
KITCHEN | 0.000 | 0.000 | 0.022 | -278.029 | 0.000 | 0.000 | 5.116 | 18.590 | 211.968 | 0.000 | 0.000 | 0.014 | 46.512 | 0.000 | 0.000 | 0.000 | -4.194 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.883 | 10.027 | 0.000 | 0.000 | 0.000 | -12.910 | -0.000 |
Total Facility | 0.000 | 0.000 | 72.888 | -339.885 | 0.000 | 0.000 | 77.499 | 29.371 | 264.717 | 23.328 | 0.000 | 5.279 | 56.540 | 0.000 | -20.295 | 0.000 | -145.595 | -23.847 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 02-FEB-04:52 | 0.00 | 0.00 | 0.00 | -44171.90 | 0.00 | 0.00 | 0.00 | 122.53 | 506.27 | 0.00 | 0.00 | 0.00 | 47471.74 | 0.00 | -3013.73 | 0.00 | -914.91 | 0.00 |
KITCHEN | 03-FEB-05:01 | 0.00 | 0.00 | 0.00 | -54020.03 | 0.00 | 0.00 | 20.65 | 204.35 | 5271.43 | 0.00 | 0.00 | 0.00 | 48641.89 | 0.00 | -0.00 | 0.00 | -118.30 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-FEB-00:01 | 0.00 | 0.00 | 0.00 | -70597.28 | 0.00 | 0.00 | 388.32 | 275.79 | 2648.48 | 0.00 | 0.00 | 4.56 | 70938.21 | 0.00 | -3069.35 | 0.00 | -588.72 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 02-MAR-03:01 | 0.00 | 0.00 | 45005.08 | 0.00 | 0.00 | 0.00 | 0.00 | 122.53 | 202.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1280.82 | 0.00 | -642.83 | -43406.47 |
KITCHEN | 30-JAN-05:02 | 0.00 | 0.00 | 17874.52 | 0.00 | 0.00 | 0.00 | 23.42 | 204.35 | 5271.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -285.93 | -23087.80 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-MAR-03:01 | 0.00 | 0.00 | 45005.08 | 0.00 | 0.00 | 0.00 | 0.00 | 275.79 | 2219.64 | 0.00 | 0.00 | 101.33 | 0.00 | 0.00 | -1280.82 | 0.00 | -1364.26 | -44956.77 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.7134 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.7134 | 0.2428 | 1.0000 | Not calculated | 0.4161 | 0.2428 | ||
PSZ-AC_2:2 | 1.2991 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2991 | 0.1164 | 1.0000 | Not calculated | 0.1513 | 0.1164 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.7134 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.7134 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2428 | ||
PSZ-AC_2:2 | 1.2991 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2991 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1164 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7134 | 1.7134 | 1.7134 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2991 | 1.2991 | 1.2991 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.7134 | 1.7134 | 1.7134 | 1.7134 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2991 | 1.2991 | 1.2991 | 1.2991 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7134 | 1.7134 | 1.7134 | No | 0.4161 | 0.8887 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2991 | 1.2991 | 1.2991 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.7134 | 1.7134 | 1.7134 | 1.7134 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2991 | 1.2991 | 1.2991 | 1.2991 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 17.50 |
Number of hours not met | 17.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 532.36 | 145791.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 39.35 | 17489.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 29.37 | 1654.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 27.10 | 2040.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 76.39 | 4168.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 231.41 | 28547.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 17.86 | 3516.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 16.16 | 1469.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 29.14 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 339.74 | 511.95 |
Natural Gas | 477.16 | 1240.93 |
Additional | 0.00 | 0.00 |
Total | 816.90 | 1752.88 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 126.41 |
Space Heating | 0.00 |
Space Cooling | 169.38 |
Fans (All) | 328.76 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1190.44 |
Miscellaneous (All) | 2203.44 |
Subtotal | 2203.44 |
Natural Gas [MJ/m2] | |
Space Heating | 2291.27 |
Service Water Heating | 995.99 |
Miscellaneous (All) | 5340.95 |
Subtotal | 5340.95 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.68 |
Space Heating | 30.37 |
Space Cooling | 2.25 |
Fans (All) | 4.36 |
Service Water Heating | 13.20 |
Receptacle Equipment | 43.00 |
Miscellaneous | 5.15 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4763. | 8760. |
LTG_SCH_KITCHEN | 4539. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_SETBACK | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_SETBACK | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8581.50 | 178.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 7261.00 | 423.67 | 416.33 | 504.83 | 154.17 |
Min | 7261.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 423.67 | 416.33 | 504.83 | 154.17 |
Average | 8200.83 | 200.72 | 138.78 | 168.28 | 51.39 |
Sum | 24602.50 | 602.17 | 416.33 | 504.83 | 154.17 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16178.83 | 79.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 79.17 | 0.00 | 0.00 | 0.00 |
Average | 90301.28 | 26.39 | 0.00 | 0.00 | 0.00 |
Sum | 270903.83 | 79.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8077.67 | 682.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6537.67 | 2222.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 7196.83 | 733.50 | 278.33 | 223.33 | 328.00 |
Min | 6537.67 | 682.33 | 0.00 | 0.00 | 0.00 |
Max | 8077.67 | 2222.33 | 278.33 | 223.33 | 328.00 |
Average | 7270.72 | 1212.72 | 92.78 | 74.44 | 109.33 |
Sum | 21812.17 | 3638.17 | 278.33 | 223.33 | 328.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 232776.33 | 21948.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 11531.17 | 4726.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 232776.33 | 21948.67 | 0.00 | 0.00 | 0.00 |
Average | 81435.83 | 8891.83 | 0.00 | 0.00 | 0.00 |
Sum | 244307.50 | 26675.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:27
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Environment
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.981395E+09 | 35751.59 | 31-JAN-04:03 | -31.0 | -31.2 | 0.444688E+10 | 3722.95 | 07-JAN-19:10 | -31.0 | -31.2 |
February | 0.815465E+09 | 44173.07 | 02-FEB-04:52 | -36.1 | -36.2 | 0.402517E+10 | 3722.93 | 04-FEB-19:10 | -20.0 | -20.6 |
March | 0.126444E+10 | 15563.10 | 06-MAR-00:01 | -16.3 | -16.8 | 0.451783E+10 | 4081.30 | 25-MAR-18:10 | 14.82 | 10.05 |
April | 0.301896E+10 | 17233.33 | 16-APR-01:51 | 20.00 | 16.75 | 0.449509E+10 | 4681.47 | 15-APR-18:10 | 20.00 | 16.75 |
May | 0.630693E+10 | 11866.29 | 31-MAY-12:00 | 29.40 | 19.85 | 0.496137E+10 | 4681.29 | 27-MAY-18:30 | 29.40 | 19.85 |
June | 0.102861E+11 | 17700.69 | 10-JUN-03:11 | 19.60 | 16.77 | 0.509101E+10 | 4681.46 | 10-JUN-18:49 | 24.87 | 19.34 |
July | 0.121450E+11 | 17610.33 | 28-JUL-03:21 | 18.85 | 16.92 | 0.537353E+10 | 4681.63 | 01-JUL-18:10 | 18.85 | 16.92 |
August | 0.120710E+11 | 16659.13 | 06-AUG-00:41 | 17.12 | 14.32 | 0.540943E+10 | 4681.01 | 19-AUG-18:10 | 19.90 | 18.81 |
September | 0.897079E+10 | 21767.12 | 18-SEP-00:41 | 19.50 | 13.72 | 0.487516E+10 | 4681.01 | 02-SEP-18:00 | 19.50 | 13.72 |
October | 0.354179E+10 | 9015.20 | 18-OCT-23:01 | -0.8 | -2.1 | 0.456681E+10 | 4413.39 | 20-OCT-11:00 | 21.10 | 12.25 |
November | 0.172889E+10 | 25344.46 | 26-NOV-04:49 | -25.0 | -25.3 | 0.431925E+10 | 4117.94 | 03-NOV-11:00 | -25.0 | -25.3 |
December | 0.726332E+09 | 21662.22 | 09-DEC-03:51 | -22.8 | -23.0 | 0.444511E+10 | 3722.94 | 09-DEC-19:10 | -20.0 | -20.4 |
Annual Sum or Average | 0.618571E+11 | 0.565266E+11 | ||||||||
Minimum of Months | 0.726332E+09 | 9015.20 | -36.1 | -36.2 | 0.402517E+10 | 3722.93 | -31.0 | -31.2 | ||
Maximum of Months | 0.121450E+11 | 44173.07 | 29.40 | 19.85 | 0.540943E+10 | 4681.63 | 29.40 | 19.85 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.209478E+11 | 51060.25 | 31-JAN-05:01 | -30.6 | -30.8 | 0.768047E+10 | 5037.83 | 13-JAN-11:00 | -30.6 | -30.8 |
February | 0.193849E+11 | 54047.37 | 03-FEB-05:01 | -33.9 | -34.0 | 0.693791E+10 | 5050.01 | 24-FEB-11:00 | 6.10 | 3.16 |
March | 0.222856E+11 | 36837.67 | 08-MAR-05:01 | -14.7 | -15.0 | 0.769838E+10 | 5091.47 | 28-MAR-10:00 | 12.80 | 7.63 |
April | 0.219665E+11 | 33741.57 | 18-APR-04:01 | 14.18 | 11.97 | 0.748356E+10 | 5135.94 | 17-APR-10:00 | 14.18 | 11.97 |
May | 0.233490E+11 | 42209.93 | 09-MAY-04:01 | 10.60 | 9.66 | 0.781576E+10 | 5136.00 | 16-MAY-10:00 | 18.30 | 16.16 |
June | 0.239625E+11 | 43047.31 | 23-JUN-04:01 | 11.10 | 9.57 | 0.759172E+10 | 5139.72 | 30-JUN-10:00 | 28.30 | 23.10 |
July | 0.253518E+11 | 35181.19 | 19-JUL-04:01 | 11.78 | 11.10 | 0.785622E+10 | 5140.47 | 03-JUL-10:00 | 11.78 | 11.10 |
August | 0.256600E+11 | 43433.04 | 08-AUG-04:01 | 11.20 | 9.38 | 0.785978E+10 | 5171.67 | 04-AUG-10:00 | 11.20 | 9.38 |
September | 0.248569E+11 | 46703.91 | 05-SEP-04:01 | 7.52 | 6.70 | 0.756468E+10 | 5135.99 | 12-SEP-10:00 | 16.10 | 15.06 |
October | 0.249915E+11 | 37272.49 | 03-OCT-03:31 | 7.53 | 6.93 | 0.773515E+10 | 5135.94 | 20-OCT-10:00 | 18.10 | 11.43 |
November | 0.230116E+11 | 45144.10 | 26-NOV-05:01 | -25.2 | -25.5 | 0.745571E+10 | 5130.53 | 08-NOV-11:50 | -25.2 | -25.5 |
December | 0.222673E+11 | 42491.42 | 11-DEC-05:01 | -22.2 | -22.6 | 0.768049E+10 | 5036.86 | 01-DEC-11:00 | -22.2 | -22.6 |
Annual Sum or Average | 0.278035E+12 | 0.913598E+11 | ||||||||
Minimum of Months | 0.193849E+11 | 33741.57 | -33.9 | -34.0 | 0.693791E+10 | 5036.86 | -30.6 | -30.8 | ||
Maximum of Months | 0.256600E+11 | 54047.37 | 14.18 | 11.97 | 0.785978E+10 | 5171.67 | 28.30 | 23.10 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -2.8 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 | -24.4 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 | -12.0 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -12.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 | -2.2 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 | 5.15 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.15 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 | 10.69 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.69 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 | 15.94 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.94 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.15 | 17.82 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 | 15.67 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 | 1.39 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.39 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 1.65 | -0.5 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.5 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.00 | 0.00 | 18.93 | 17.82 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212482E+11 | 40799.32 | 20-JAN-04:01 | -24.9 |
February | 0.144073E+11 | 40744.63 | 13-FEB-03:01 | -5.6 |
March | 0.814643E+10 | 45006.76 | 02-MAR-03:01 | -4.3 |
April | 0.363773E+10 | 44590.59 | 03-APR-02:61 | -6.1 |
May | 0.175863E+09 | 10911.56 | 02-MAY-02:62 | 2.80 |
June | 18179611.94 | 1891.82 | 03-JUN-06:03 | 6.78 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.15 |
September | 0.250831E+09 | 12764.34 | 30-SEP-04:06 | -0.5 |
October | 0.154053E+10 | 9561.27 | 27-OCT-02:62 | -0.2 |
November | 0.795185E+10 | 38932.86 | 26-NOV-03:21 | -25.0 |
December | 0.154893E+11 | 41404.41 | 10-DEC-04:01 | -21.8 |
Annual Sum or Average | 0.728662E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.0 | |
Maximum of Months | 0.212482E+11 | 45006.76 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7998906.01 | 17889.59 | 30-JAN-05:02 | -27.9 |
February | 6361428.73 | 12235.41 | 04-FEB-05:02 | -30.6 |
March | 1625686.37 | 11127.01 | 08-MAR-05:03 | -14.7 |
April | 286201.15 | 1747.21 | 05-APR-04:04 | -2.8 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 1674982.73 | 10031.08 | 28-NOV-05:03 | -21.1 |
December | 4032903.90 | 11167.57 | 16-DEC-05:03 | -14.4 |
Annual Sum or Average | 21980108.89 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 7998906.01 | 17889.59 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.993037E+09 | 735.19 | 02-JAN-16:40 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.870226E+09 | 735.19 | 01-FEB-17:19 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.922977E+09 | 735.19 | 01-MAR-17:30 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.855823E+09 | 735.19 | 01-APR-18:10 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.849406E+09 | 735.19 | 01-MAY-18:00 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.820515E+09 | 735.19 | 01-JUN-19:10 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.837130E+09 | 735.19 | 01-JUL-19:30 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.868542E+09 | 735.19 | 01-AUG-19:30 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.869067E+09 | 735.19 | 01-SEP-18:40 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.932589E+09 | 735.19 | 02-OCT-17:40 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.955131E+09 | 735.19 | 01-NOV-16:40 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.100670E+10 | 735.19 | 01-DEC-16:30 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.107811E+11 | 0.703313E+11 | ||||
Minimum of Months | 0.820515E+09 | 735.19 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.100670E+10 | 735.19 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.157083E+10 | 919.59 | 02-JAN-10:09 | 0.175178E+11 | 10483.62 | 01-JAN-11:09 |
February | 0.142278E+10 | 919.59 | 01-FEB-10:09 | 0.158225E+11 | 10483.62 | 01-FEB-11:09 |
March | 0.159585E+10 | 919.59 | 01-MAR-10:09 | 0.175179E+11 | 10483.62 | 01-MAR-11:09 |
April | 0.152633E+10 | 919.59 | 01-APR-16:10 | 0.169527E+11 | 10483.62 | 01-APR-10:09 |
May | 0.158334E+10 | 919.59 | 01-MAY-09:09 | 0.175178E+11 | 10483.62 | 01-MAY-10:09 |
June | 0.154251E+10 | 919.59 | 01-JUN-09:09 | 0.169528E+11 | 10483.62 | 01-JUN-10:09 |
July | 0.156734E+10 | 919.59 | 01-JUL-16:10 | 0.175177E+11 | 10483.62 | 01-JUL-10:09 |
August | 0.159585E+10 | 919.59 | 01-AUG-09:09 | 0.175179E+11 | 10483.62 | 01-AUG-10:09 |
September | 0.152669E+10 | 919.59 | 01-SEP-09:09 | 0.169527E+11 | 10483.62 | 01-SEP-10:09 |
October | 0.157065E+10 | 919.59 | 02-OCT-09:09 | 0.175178E+11 | 10483.62 | 01-OCT-10:09 |
November | 0.152062E+10 | 919.59 | 01-NOV-09:09 | 0.169527E+11 | 10483.62 | 01-NOV-10:09 |
December | 0.156752E+10 | 919.59 | 01-DEC-10:09 | 0.175177E+11 | 10483.62 | 01-DEC-11:09 |
Annual Sum or Average | 0.185903E+11 | 0.206258E+12 | ||||
Minimum of Months | 0.142278E+10 | 919.59 | 0.158225E+11 | 10483.62 | ||
Maximum of Months | 0.159585E+10 | 919.59 | 0.175179E+11 | 10483.62 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.993037E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253677E+11 |
February | 0.852256E+10 | 0.870226E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192212E+11 |
March | 0.954557E+10 | 0.922977E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146198E+11 |
April | 0.915225E+10 | 0.855823E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101914E+09 | 0.948938E+10 |
May | 0.947560E+10 | 0.849406E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106225E+09 | 0.482853E+10 |
June | 0.922788E+10 | 0.820515E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703530E+09 | 0.243149E+10 |
July | 0.939996E+10 | 0.837130E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537737E+09 | 0.146226E+10 |
August | 0.954557E+10 | 0.868542E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551162E+09 | 0.192308E+10 |
September | 0.915225E+10 | 0.869067E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381484E+09 | 0.434957E+10 |
October | 0.940563E+10 | 0.932589E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.915803E+10 |
November | 0.909363E+10 | 0.955131E+09 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145499E+11 |
December | 0.939996E+10 | 0.100670E+10 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210905E+11 |
Annual Sum or Average | 0.111326E+12 | 0.107811E+11 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238205E+10 | 0.128491E+12 |
Minimum of Months | 0.852256E+10 | 0.820515E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146226E+10 |
Maximum of Months | 0.954557E+10 | 0.100670E+10 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703530E+09 | 0.253677E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.157083E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731688E+09 |
February | 0.610713E+09 | 0.142278E+10 | 0.120683E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556420E+09 |
March | 0.684021E+09 | 0.159585E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492653E+09 |
April | 0.655836E+09 | 0.152633E+10 | 0.129303E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 1353666.09 | 0.314044E+09 |
May | 0.679007E+09 | 0.158334E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 485059.10 | 0.192592E+09 |
June | 0.661256E+09 | 0.154251E+10 | 0.129304E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 5727247.40 | 0.115239E+09 |
July | 0.673587E+09 | 0.156734E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 1764354.05 | 83995206.72 |
August | 0.684021E+09 | 0.159585E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 2402652.35 | 0.114086E+09 |
September | 0.655836E+09 | 0.152669E+10 | 0.129303E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 2150904.12 | 0.167514E+09 |
October | 0.673993E+09 | 0.157065E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295884E+09 |
November | 0.651635E+09 | 0.152062E+10 | 0.129304E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490585E+09 |
December | 0.673587E+09 | 0.156752E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638871E+09 |
Annual Sum or Average | 0.797748E+10 | 0.185903E+11 | 0.157319E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 13883883.11 | 0.419357E+10 |
Minimum of Months | 0.610713E+09 | 0.142278E+10 | 0.120683E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83995206.72 |
Maximum of Months | 0.684021E+09 | 0.159585E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 5727247.40 | 0.731688E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237992E+09 | 0.637272E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247901E+09 | 0.749755E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218233E+09 | 0.107264E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196074E+09 | 0.132027E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180624E+09 | 0.158768E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195918E+09 | 0.163593E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251463E+09 | 0.170957E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208706E+09 | 0.145835E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309733E+09 | 0.105311E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312205E+09 | 0.794607E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255855E+09 | 0.511006E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268160E+09 | 0.379923E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288286E+10 | 0.129101E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180624E+09 | 0.379923E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312205E+09 | 0.170957E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 735.19 | 02-JAN-16:40 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 32970.60 | 30-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 735.19 | 01-FEB-17:19 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 37181.60 | 02-FEB-21:00 |
March | 9454.80 | 04-MAR-19:10 | 735.19 | 01-MAR-17:30 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 20565.30 | 05-MAR-21:00 |
April | 9454.80 | 01-APR-18:10 | 735.19 | 01-APR-18:10 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2810.27 | 15-APR-17:03 | 15728.67 | 03-APR-20:00 |
May | 9454.80 | 06-MAY-18:10 | 735.19 | 01-MAY-18:00 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2974.32 | 31-MAY-12:00 | 10328.30 | 01-MAY-20:00 |
June | 9454.80 | 03-JUN-18:10 | 735.19 | 01-JUN-19:10 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3817.90 | 26-JUN-17:03 | 7628.51 | 01-JUN-17:52 |
July | 9454.80 | 01-JUL-18:10 | 735.19 | 01-JUL-19:30 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2982.64 | 26-JUL-17:55 | 4420.91 | 10-JUL-12:00 |
August | 9454.80 | 05-AUG-18:10 | 735.19 | 01-AUG-19:30 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3866.23 | 04-AUG-11:53 | 4776.66 | 06-AUG-19:53 |
September | 9454.80 | 02-SEP-18:10 | 735.19 | 01-SEP-18:40 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3722.41 | 07-SEP-13:00 | 10622.64 | 29-SEP-20:00 |
October | 9454.80 | 07-OCT-18:10 | 735.19 | 02-OCT-17:40 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 13229.48 | 31-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 735.19 | 01-NOV-16:40 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 31543.73 | 25-NOV-20:00 |
December | 9454.80 | 02-DEC-19:10 | 735.19 | 01-DEC-16:30 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 29972.81 | 09-DEC-19:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 735.19 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4420.91 | |||||
Maximum of Months | 9454.80 | 735.19 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3866.23 | 37181.60 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 919.59 | 02-JAN-10:09 | 7748.81 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2101.76 | 29-JAN-05:00 |
February | 677.52 | 04-FEB-19:10 | 919.59 | 01-FEB-10:09 | 7748.81 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1477.41 | 28-FEB-05:00 |
March | 677.52 | 04-MAR-19:10 | 919.59 | 01-MAR-10:09 | 7748.81 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1389.23 | 21-MAR-03:20 |
April | 677.52 | 01-APR-18:10 | 919.59 | 01-APR-16:10 | 7748.81 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 42.81 | 15-APR-15:00 | 1004.52 | 03-APR-00:20 |
May | 677.52 | 06-MAY-18:10 | 919.59 | 01-MAY-09:09 | 7748.81 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 19.22 | 31-MAY-13:00 | 763.20 | 02-MAY-03:05 |
June | 677.52 | 03-JUN-18:10 | 919.59 | 01-JUN-09:09 | 7748.81 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 56.88 | 11-JUN-14:53 | 535.96 | 02-JUN-03:30 |
July | 677.52 | 01-JUL-18:10 | 919.59 | 01-JUL-16:10 | 7748.81 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 28.52 | 25-JUL-15:57 | 337.45 | 25-JUL-03:20 |
August | 677.52 | 05-AUG-18:10 | 919.59 | 01-AUG-09:09 | 7748.81 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 25.05 | 03-AUG-16:00 | 394.13 | 19-AUG-04:00 |
September | 677.52 | 02-SEP-18:10 | 919.59 | 01-SEP-09:09 | 7748.81 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 30.12 | 06-SEP-14:00 | 492.38 | 26-SEP-03:30 |
October | 677.52 | 07-OCT-18:10 | 919.59 | 02-OCT-09:09 | 7748.81 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 832.96 | 24-OCT-03:40 |
November | 677.52 | 04-NOV-18:10 | 919.59 | 01-NOV-09:09 | 7748.81 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1590.98 | 21-NOV-04:10 |
December | 677.52 | 02-DEC-19:10 | 919.59 | 01-DEC-10:09 | 7748.81 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2743.87 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 919.59 | 7748.81 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 337.45 | ||||||
Maximum of Months | 677.52 | 919.59 | 7748.81 | 7998.14 | 0.00 | 0.00 | 0.00 | 56.88 | 2743.87 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.10 | 25-JAN-04:52 | 1908.44 | 31-JAN-13:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.27 | 28-FEB-24:00 | 2024.01 | 02-FEB-14:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.81 | 01-MAR-00:13 | 2299.41 | 05-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.38 | 05-APR-23:10 | 2601.65 | 05-APR-12:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.23 | 03-MAY-02:00 | 2601.77 | 21-MAY-13:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.65 | 07-JUN-23:00 | 2645.89 | 09-JUN-13:30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.98 | 23-JUL-23:00 | 2449.65 | 05-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.84 | 09-AUG-01:51 | 2199.40 | 07-AUG-12:30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.71 | 08-SEP-03:51 | 2085.83 | 07-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.32 | 20-OCT-07:03 | 1842.69 | 23-OCT-12:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.83 | 01-NOV-00:01 | 1510.72 | 25-NOV-12:50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.92 | 04-DEC-07:55 | 1166.55 | 15-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.92 | 1166.55 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.71 | 2645.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35751.59 | 31-JAN-04:03 | 0.00 | 1225.31 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901.10 |
February | 44173.07 | 02-FEB-04:52 | 0.00 | 1225.31 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 914.91 |
March | 15563.10 | 06-MAR-00:01 | 5252.67 | 1225.31 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.18 |
April | 17233.33 | 16-APR-01:51 | 0.00 | 980.25 | 3240.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.62 |
May | 11866.29 | 31-MAY-12:00 | 8404.27 | 411.71 | 3659.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2974.32 | 0.00 |
June | 17700.69 | 10-JUN-03:11 | 0.00 | 1102.78 | 6075.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.62 |
July | 17610.33 | 28-JUL-03:21 | 0.00 | 980.25 | 5400.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.66 |
August | 16659.13 | 06-AUG-00:41 | 0.00 | 857.72 | 1890.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.23 |
September | 21767.12 | 18-SEP-00:41 | 0.00 | 857.72 | 1890.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.17 |
October | 9015.20 | 18-OCT-23:01 | 5252.67 | 1225.31 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 |
November | 25344.46 | 26-NOV-04:49 | 0.00 | 1225.31 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 914.17 |
December | 21662.22 | 09-DEC-03:51 | 0.00 | 1225.31 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1691.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9015.20 | 0.00 | 411.71 | 1890.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44173.07 | 8404.27 | 1225.31 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 2974.32 | 1691.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 51060.25 | 31-JAN-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 209.28 |
February | 54047.37 | 03-FEB-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 118.30 |
March | 36837.67 | 08-MAR-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 82.78 |
April | 33741.57 | 18-APR-04:01 | 301.12 | 1634.82 | 32064.72 | 26476.59 | 0.00 | 0.00 | 0.00 | 0.00 | 64.18 |
May | 42209.93 | 09-MAY-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 93.04 |
June | 43047.31 | 23-JUN-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 48.12 |
July | 35181.19 | 19-JUL-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 38.76 |
August | 43433.04 | 08-AUG-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 67.64 |
September | 46703.91 | 05-SEP-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 56.33 |
October | 37272.49 | 03-OCT-03:31 | 0.00 | 1379.33 | 22172.05 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 231.93 |
November | 45144.10 | 26-NOV-05:01 | 0.00 | 1532.59 | 39979.31 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 210.25 |
December | 42491.42 | 11-DEC-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 173.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 33741.57 | 0.00 | 1379.33 | 22172.05 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 38.76 | |
Maximum of Months | 54047.37 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 231.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.73 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.68 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.51 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.82 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.82 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.74 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.87 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.92 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.95 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.83 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.83 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.83 | 17.95 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.413004E+11 | 23804.41 | 30-JAN-11:09 | 0.205985E+12 | 158523.91 | 30-JAN-13:09 |
February | 0.367396E+11 | 24006.85 | 02-FEB-11:09 | 0.157019E+12 | 178623.68 | 02-FEB-20:40 |
March | 0.399405E+11 | 23146.55 | 01-MAR-11:09 | 0.123639E+12 | 108610.63 | 05-MAR-20:30 |
April | 0.393107E+11 | 31971.23 | 18-APR-10:00 | 0.887230E+11 | 91343.83 | 03-APR-10:20 |
May | 0.417267E+11 | 31423.91 | 31-MAY-10:00 | 0.642416E+11 | 59024.28 | 02-MAY-10:20 |
June | 0.470301E+11 | 35516.70 | 30-JUN-11:09 | 0.583492E+11 | 54847.32 | 05-JUN-10:20 |
July | 0.514535E+11 | 35634.68 | 26-JUL-17:00 | 0.582773E+11 | 49502.09 | 01-JUL-12:30 |
August | 0.506416E+11 | 38642.29 | 04-AUG-11:20 | 0.579702E+11 | 49016.32 | 01-AUG-12:50 |
September | 0.433656E+11 | 32875.48 | 11-SEP-10:00 | 0.603021E+11 | 53187.24 | 27-SEP-10:39 |
October | 0.401155E+11 | 22871.65 | 26-OCT-10:09 | 0.771841E+11 | 61244.42 | 26-OCT-10:20 |
November | 0.392705E+11 | 23306.19 | 24-NOV-11:09 | 0.118776E+12 | 140846.68 | 26-NOV-07:19 |
December | 0.410587E+11 | 23593.73 | 11-DEC-11:09 | 0.170465E+12 | 140034.82 | 09-DEC-11:09 |
Annual Sum or Average | 0.511954E+12 | 0.124093E+13 | ||||
Minimum of Months | 0.367396E+11 | 22871.65 | 0.579702E+11 | 49016.32 | ||
Maximum of Months | 0.514535E+11 | 38642.29 | 0.205985E+12 | 178623.68 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.256387E+10 | 0.295740E+10 | 0.234911E+11 | 0.00 | 0.728766E+10 | 0.79 | 0.00 | 162730.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229301E+10 | 0.243431E+10 | 0.212178E+11 | 0.00 | 0.625737E+10 | 0.72 | 0.00 | 318750.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251882E+10 | 0.236736E+10 | 0.234913E+11 | 0.00 | 0.644384E+10 | 0.80 | 0.00 | 5293851.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.238215E+10 | 0.195511E+10 | 0.227333E+11 | 0.00 | 0.598490E+10 | 0.77 | 0.00 | 0.116064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.243275E+10 | 0.174821E+10 | 0.234912E+11 | 0.00 | 0.610568E+10 | 0.80 | 0.00 | 0.235770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.236303E+10 | 0.156545E+10 | 0.227335E+11 | 0.00 | 0.614217E+10 | 0.77 | 0.00 | 0.868035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.240447E+10 | 0.166298E+10 | 0.234911E+11 | 0.00 | 0.642589E+10 | 0.79 | 0.00 | 0.116793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.246439E+10 | 0.189117E+10 | 0.234913E+11 | 0.00 | 0.640487E+10 | 0.80 | 0.00 | 0.106021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.239576E+10 | 0.214118E+10 | 0.227333E+11 | 0.00 | 0.598741E+10 | 0.77 | 0.00 | 0.469202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.250324E+10 | 0.255955E+10 | 0.234911E+11 | 0.00 | 0.611506E+10 | 0.79 | 0.00 | 0.164042E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247576E+10 | 0.277651E+10 | 0.227334E+11 | 0.00 | 0.629448E+10 | 0.77 | 0.00 | 12434570.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.257422E+10 | 0.303942E+10 | 0.234911E+11 | 0.00 | 0.693685E+10 | 0.79 | 0.00 | 546408.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293715E+11 | 0.270987E+11 | 0.276589E+12 | 0.00 | 0.763862E+11 | 9.37 | 0.00 | 0.393550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.229301E+10 | 0.156545E+10 | 0.212178E+11 | 0.00 | 0.598490E+10 | 0.72 | 0.00 | 162730.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.257422E+10 | 0.303942E+10 | 0.234913E+11 | 0.00 | 0.728766E+10 | 0.80 | 0.00 | 0.116793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.143893E+12 | 0.00 | 0.215666E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.100594E+12 | 0.00 | 0.198220E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.613353E+11 | 0.00 | 0.217777E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.292136E+11 | 0.00 | 0.202909E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.387545E+10 | 0.00 | 0.198404E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.105074E+10 | 0.00 | 0.180801E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 21917533.62 | 0.00 | 0.177297E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 74719324.26 | 0.00 | 0.173697E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.408198E+10 | 0.00 | 0.170017E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.182642E+11 | 0.00 | 0.183942E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.606663E+11 | 0.00 | 0.188908E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.109291E+12 | 0.00 | 0.206485E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.532361E+12 | 0.00 | 0.231412E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 21917533.62 | 0.00 | 0.170017E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.143893E+12 | 0.00 | 0.217777E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1654.77 | 02-JAN-16:40 | 2040.24 | 01-JAN-00:10 | 14413.88 | 01-JAN-11:09 | 0.00 | 3908.34 | 30-JAN-20:00 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 1654.77 | 01-FEB-17:19 | 2040.24 | 01-FEB-00:10 | 14413.88 | 01-FEB-11:09 | 0.00 | 4125.64 | 02-FEB-20:00 | 0.00 | 25-FEB-10:30 | 0.00 | 01-FEB-00:10 |
March | 1654.77 | 01-MAR-17:30 | 2040.24 | 01-MAR-00:10 | 14413.88 | 01-MAR-11:09 | 0.00 | 3386.51 | 05-MAR-20:00 | 0.00 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 1654.77 | 01-APR-18:10 | 2040.24 | 01-APR-05:10 | 14413.88 | 01-APR-10:09 | 0.00 | 3116.69 | 03-APR-06:10 | 0.00 | 12-APR-11:00 | 0.00 | 01-APR-00:10 |
May | 1654.77 | 01-MAY-18:00 | 2040.24 | 01-MAY-19:10 | 14413.88 | 01-MAY-10:09 | 0.00 | 2916.32 | 31-MAY-11:09 | 0.00 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 1654.77 | 01-JUN-19:10 | 2040.24 | 01-JUN-19:40 | 14413.88 | 01-JUN-10:09 | 0.00 | 3598.07 | 30-JUN-11:09 | 0.00 | 01-JUN-12:00 | 0.00 | 01-JUN-00:10 |
July | 1654.77 | 01-JUL-19:30 | 2040.24 | 01-JUL-19:00 | 14413.88 | 01-JUL-10:09 | 0.00 | 3964.80 | 26-JUL-17:00 | 0.00 | 04-JUL-13:30 | 0.00 | 01-JUL-00:10 |
August | 1654.77 | 01-AUG-19:30 | 2040.24 | 01-AUG-19:40 | 14413.88 | 01-AUG-10:09 | 0.00 | 4168.79 | 04-AUG-12:00 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 1654.77 | 01-SEP-18:40 | 2040.24 | 01-SEP-05:10 | 14413.88 | 01-SEP-10:09 | 0.00 | 3107.38 | 11-SEP-11:09 | 0.00 | 12-SEP-12:30 | 0.00 | 01-SEP-00:10 |
October | 1654.77 | 02-OCT-17:40 | 2040.24 | 01-OCT-05:10 | 14413.88 | 01-OCT-10:09 | 0.00 | 2940.89 | 23-OCT-06:10 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 1654.77 | 01-NOV-16:40 | 2040.24 | 01-NOV-05:10 | 14413.88 | 01-NOV-10:09 | 0.00 | 3827.47 | 26-NOV-07:10 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 1654.77 | 01-DEC-16:30 | 2040.24 | 01-DEC-00:10 | 14413.88 | 01-DEC-11:09 | 0.00 | 3718.55 | 08-DEC-20:00 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1654.77 | 2040.24 | 14413.88 | 0.00 | 2916.32 | 0.00 | 0.00 | ||||||
Maximum of Months | 1654.77 | 2040.24 | 14413.88 | 0.00 | 4168.79 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 86.46 | 10-JAN-04:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 194.31 | 10-FEB-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 991.95 | 26-MAR-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10936.12 | 18-APR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10594.19 | 31-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14461.42 | 11-JUN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 26-JUL-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17489.78 | 04-AUG-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12102.06 | 06-SEP-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3905.28 | 20-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1560.30 | 09-NOV-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 182.52 | 05-DEC-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 86.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17489.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 23804.41 | 30-JAN-11:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3692.24 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24006.85 | 02-FEB-11:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3894.68 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23146.55 | 01-MAR-11:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3022.88 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31971.23 | 18-APR-10:00 | 1331.29 | 14413.88 | 0.00 | 0.00 | 2993.61 | 0.00 | 0.00 | 10297.63 | 0.00 |
May | 31423.91 | 31-MAY-10:00 | 1331.29 | 14413.88 | 0.00 | 0.00 | 2907.75 | 0.00 | 0.00 | 9855.29 | 0.00 |
June | 35516.70 | 30-JUN-11:09 | 1331.29 | 13514.13 | 0.00 | 0.00 | 3598.07 | 0.00 | 0.00 | 14130.74 | 0.00 |
July | 35634.68 | 26-JUL-17:00 | 1331.29 | 12164.51 | 0.00 | 0.00 | 3964.80 | 0.00 | 0.00 | 16014.58 | 0.00 |
August | 38642.29 | 04-AUG-11:20 | 1331.29 | 13514.13 | 0.00 | 0.00 | 4073.15 | 0.00 | 0.00 | 16726.22 | 0.00 |
September | 32875.48 | 11-SEP-10:00 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3097.68 | 0.00 | 0.00 | 11097.82 | 0.00 |
October | 22871.65 | 26-OCT-10:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 2729.38 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23306.19 | 24-NOV-11:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3192.77 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23593.73 | 11-DEC-11:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3481.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 22871.65 | 1331.29 | 12164.51 | 0.00 | 0.00 | 2729.38 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38642.29 | 1331.29 | 14413.88 | 0.00 | 0.00 | 4073.15 | 0.00 | 0.00 | 16726.22 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 126529.66 | 31-JAN-07:10 | 0.00 | 28490.55 | 31-JAN-13:00 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 145791.44 | 02-FEB-07:10 | 0.00 | 28547.03 | 20-FEB-13:20 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 76392.14 | 05-MAR-20:00 | 0.00 | 28526.51 | 01-MAR-13:00 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 53766.08 | 03-APR-06:10 | 0.00 | 28306.45 | 01-APR-12:00 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 24926.03 | 02-MAY-06:10 | 0.00 | 27846.84 | 01-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 11984.02 | 03-JUN-04:10 | 0.00 | 27177.17 | 01-JUN-12:00 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 2148.42 | 23-JUL-05:10 | 0.00 | 26518.94 | 01-JUL-12:30 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 4977.98 | 07-AUG-06:10 | 0.00 | 26033.17 | 01-AUG-12:50 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 30085.03 | 30-SEP-06:10 | 0.00 | 26322.83 | 30-SEP-12:39 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 36666.64 | 23-OCT-06:10 | 0.00 | 26956.74 | 31-OCT-12:50 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 121857.65 | 26-NOV-07:10 | 0.00 | 27632.88 | 30-NOV-13:20 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 106287.10 | 08-DEC-20:00 | 0.00 | 28180.63 | 31-DEC-13:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 2148.42 | 0.00 | 26033.17 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 145791.44 | 0.00 | 28547.03 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.33 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
February | 21.50 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
March | 13.50 | 19.81 | 0.00 | 19.81 | 0.00 | 19.81 | 0.00 | 19.81 |
April | 6.83 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
May | 0.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.49 | 0.00 | 24.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 24.53 | 0.00 | 24.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 24.57 | 0.00 | 24.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 24.58 | 0.00 | 24.58 |
October | 0.83 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
November | 13.00 | 19.63 | 0.17 | 19.63 | 0.00 | 19.63 | 0.00 | 19.63 |
December | 23.83 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Annual Sum or Average | 107.17 | 19.51 | 0.17 | 19.51 | 33.17 | 20.70 | 0.00 | 20.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.26 | 0.00 | 19.26 |
Maximum of Months | 27.33 | 20.52 | 0.17 | 20.52 | 10.83 | 24.58 | 0.00 | 24.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.92 | 0.00 | 26.92 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.87 | 0.00 | 26.87 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.11 | 0.00 | 27.11 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.76 | 0.00 | 27.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 28.03 | 0.00 | 28.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 28.53 | 0.00 | 28.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 37.67 | 28.50 | 6.67 | 28.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 41.67 | 28.49 | 10.83 | 28.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 28.41 | 0.00 | 28.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.47 | 0.00 | 27.47 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.49 | 0.00 | 27.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.79 | 0.00 | 26.79 |
Annual Sum or Average | 0.00 | 0.00 | 200.83 | 28.23 | 17.50 | 28.16 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.79 | 0.00 | 26.79 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 41.67 | 28.53 | 10.83 | 28.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.84 | 529.00 | 20.82 | 529.00 | 20.81 |
February | 551.00 | 20.84 | 350.33 | 20.78 | 350.33 | 20.76 |
March | 607.83 | 20.93 | 253.67 | 20.81 | 253.33 | 20.75 |
April | 528.50 | 21.11 | 196.67 | 21.21 | 145.67 | 21.12 |
May | 437.17 | 21.70 | 214.67 | 22.27 | 82.50 | 22.32 |
June | 326.00 | 22.62 | 414.67 | 23.30 | 161.33 | 23.39 |
July | 357.67 | 23.63 | 559.33 | 23.76 | 320.33 | 23.78 |
August | 334.67 | 23.39 | 522.00 | 23.66 | 263.00 | 23.70 |
September | 291.83 | 21.38 | 292.33 | 22.52 | 27.17 | 22.48 |
October | 560.00 | 21.04 | 76.83 | 21.03 | 46.17 | 20.90 |
November | 586.17 | 20.93 | 184.83 | 20.82 | 184.17 | 20.75 |
December | 609.00 | 20.84 | 394.83 | 20.78 | 394.83 | 20.76 |
Annual Sum or Average | 5799.83 | 21.41 | 3989.17 | 21.76 | 2757.83 | 21.72 |
Minimum of Months | 291.83 | 20.84 | 76.83 | 20.78 | 27.17 | 20.75 |
Maximum of Months | 610.00 | 23.63 | 559.33 | 23.76 | 529.00 | 23.78 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 18.73 | 514.00 | 18.71 | 514.00 | 18.71 |
February | 551.00 | 18.74 | 380.17 | 18.70 | 380.17 | 18.69 |
March | 569.83 | 19.00 | 317.17 | 19.06 | 288.67 | 18.96 |
April | 497.33 | 20.17 | 288.17 | 20.77 | 213.00 | 20.81 |
May | 407.67 | 23.91 | 451.67 | 24.52 | 271.83 | 24.79 |
June | 469.00 | 25.57 | 541.17 | 25.59 | 426.00 | 25.73 |
July | 566.67 | 26.08 | 606.33 | 26.02 | 566.67 | 26.04 |
August | 535.67 | 26.05 | 604.17 | 25.94 | 532.00 | 25.99 |
September | 440.67 | 24.30 | 438.83 | 24.82 | 322.17 | 25.08 |
October | 485.00 | 20.17 | 200.33 | 20.85 | 107.67 | 20.89 |
November | 507.33 | 19.09 | 277.83 | 19.38 | 211.50 | 19.24 |
December | 609.00 | 18.73 | 411.67 | 18.70 | 411.67 | 18.68 |
Annual Sum or Average | 6249.17 | 21.55 | 5031.50 | 22.08 | 4245.33 | 22.20 |
Minimum of Months | 407.67 | 18.73 | 200.33 | 18.70 | 107.67 | 18.68 |
Maximum of Months | 610.00 | 26.08 | 606.33 | 26.02 | 566.67 | 26.04 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.83845 | 14.60350 | -0.6995 | 16.28119 |
February | 551.00000 | 20.84187 | 19.22353 | -0.6303 | 14.52778 |
March | 612.00000 | 20.94764 | 25.74301 | -0.5145 | 12.09798 |
April | 590.00000 | 21.39758 | 34.55746 | -0.2985 | 10.35557 |
May | 611.00000 | 22.29111 | 49.93673 | -0.9339 | 27.65469 |
June | 592.00000 | 23.16204 | 57.24729 | -0.5065 | 14.79760 |
July | 609.00000 | 23.70907 | 62.41487 | -0.2471 | 7.37191 |
August | 612.00000 | 23.57169 | 60.45770 | -0.2955 | 8.64247 |
September | 590.00000 | 22.60015 | 44.37823 | -0.7580 | 22.95708 |
October | 610.00000 | 21.25545 | 34.27851 | -0.2536 | 8.15099 |
November | 591.00000 | 20.95024 | 27.93703 | -0.4603 | 10.94684 |
December | 609.00000 | 20.83887 | 17.44432 | -0.6382 | 14.58314 |
Annual Sum or Average | 7187.00000 | 21.87404 | 37.46819 | -0.5189 | 14.01885 |
Minimum of Months | 551.00000 | 20.83845 | 14.60350 | -0.9339 | 7.37191 |
Maximum of Months | 612.00000 | 23.70907 | 62.41487 | -0.2471 | 27.65469 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.72690 | 21.58809 | -0.7627 | 17.93538 |
February | 551.00000 | 18.73964 | 27.04665 | -0.7207 | 16.75197 |
March | 612.00000 | 19.34582 | 33.43454 | -0.5234 | 14.20042 |
April | 590.00000 | 20.76166 | 40.30764 | -0.1391 | 15.33236 |
May | 611.00000 | 23.94154 | 48.42549 | -0.0996 | 17.62467 |
June | 592.00000 | 25.20055 | 53.24567 | 0.40956 | 15.74310 |
July | 609.00000 | 25.94172 | 55.55264 | 0.70085 | 16.76864 |
August | 612.00000 | 25.78657 | 54.04653 | 0.64844 | 16.41633 |
September | 590.00000 | 24.13465 | 44.33691 | 0.02235 | 18.98373 |
October | 610.00000 | 20.88438 | 39.69320 | -0.0591 | 11.72548 |
November | 591.00000 | 19.70579 | 34.16429 | -0.3949 | 13.46340 |
December | 609.00000 | 18.73338 | 24.82171 | -0.7111 | 16.32206 |
Annual Sum or Average | 7187.00000 | 21.84479 | 39.79567 | -0.1320 | 15.93225 |
Minimum of Months | 551.00000 | 18.72690 | 21.58809 | -0.7627 | 11.72548 |
Maximum of Months | 612.00000 | 25.94172 | 55.55264 | 0.70085 | 18.98373 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.186512E+10 | 0.487594E+09 | 54.07 | 0.121202E+10 | 0.653101E+09 | 0.00 | 1.00 | 16-APR-01:51 | 0.00 | 01-APR-00:01 | 42119.71 | 16-APR-01:51 | 24271.82 | 16-APR-01:51 | 17847.89 | 16-APR-01:51 | 10253.19 | 16-APR-01:51 | 0.00 | 01-APR-00:01 |
May | 0.296466E+10 | 0.803657E+09 | 112.97 | 0.195564E+10 | 0.100902E+10 | 0.00 | 1.00 | 31-MAY-12:00 | 0.00 | 01-MAY-00:01 | 21660.79 | 31-MAY-12:00 | 15257.95 | 31-MAY-12:00 | 7197.72 | 30-MAY-18:00 | 5203.59 | 31-MAY-12:00 | 0.00 | 01-MAY-00:01 |
June | 0.137454E+11 | 0.351318E+10 | 333.00 | 0.843838E+10 | 0.530702E+10 | 0.00 | 1.00 | 10-JUN-00:31 | 0.00 | 01-JUN-00:01 | 45445.83 | 26-JUN-00:09 | 25108.64 | 30-JUN-00:42 | 23956.09 | 26-JUN-00:21 | 10479.68 | 26-JUN-00:09 | 0.00 | 01-JUN-00:01 |
July | 0.182314E+11 | 0.463756E+10 | 437.06 | 0.102950E+11 | 0.793637E+10 | 0.00 | 1.00 | 01-JUL-00:42 | 0.00 | 01-JUL-00:01 | 45992.35 | 04-JUL-00:13 | 25646.26 | 26-JUL-01:22 | 28376.77 | 04-JUL-00:13 | 10518.42 | 04-JUL-00:13 | 0.00 | 01-JUL-00:01 |
August | 0.164519E+11 | 0.420693E+10 | 395.11 | 0.949270E+10 | 0.695922E+10 | 0.00 | 1.00 | 01-AUG-11:05 | 0.00 | 01-AUG-00:01 | 46638.04 | 04-AUG-00:42 | 20331.74 | 03-AUG-00:42 | 28614.45 | 04-AUG-01:23 | 10565.85 | 04-AUG-00:42 | 0.00 | 01-AUG-00:01 |
September | 0.730491E+10 | 0.194766E+10 | 214.29 | 0.543029E+10 | 0.187462E+10 | 0.00 | 1.00 | 06-SEP-11:13 | 0.00 | 01-SEP-00:01 | 43033.83 | 12-SEP-00:42 | 31507.44 | 18-SEP-00:41 | 19893.31 | 12-SEP-00:42 | 10315.58 | 12-SEP-00:42 | 0.00 | 01-SEP-00:01 |
October | 0.108308E+09 | 32256660.89 | 10.33 | 93779736.08 | 14528266.06 | 0.00 | 0.35 | 20-OCT-15:10 | 0.00 | 01-OCT-00:01 | 6141.63 | 20-OCT-15:10 | 5528.42 | 20-OCT-14:55 | 672.40 | 20-OCT-13:00 | 1789.65 | 20-OCT-15:10 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.606717E+11 | 0.156288E+11 | 1556.83 | 0.369179E+11 | 0.237539E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.182314E+11 | 0.463756E+10 | 437.06 | 0.102950E+11 | 0.793637E+10 | 0.00 | 1.00 | 0.00 | 46638.04 | 31507.44 | 28614.45 | 10565.85 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 535229.70 | 162730.20 | 0.21 | 451165.63 | 84064.07 | 0.00 | 0.17 | 10-JAN-04:46 | 0.00 | 01-JAN-00:01 | 2104.54 | 10-JAN-04:46 | 1873.10 | 10-JAN-04:46 | 231.44 | 10-JAN-04:46 | 630.15 | 10-JAN-04:46 | 0.00 | 01-JAN-00:01 |
February | 1052090.81 | 318750.95 | 0.38 | 773432.79 | 278658.03 | 0.00 | 0.20 | 10-FEB-04:10 | 0.00 | 01-FEB-00:01 | 2619.84 | 10-FEB-04:10 | 1821.67 | 10-FEB-04:10 | 798.17 | 10-FEB-04:10 | 777.25 | 10-FEB-04:10 | 0.00 | 01-FEB-00:01 |
March | 19282490.71 | 5293851.87 | 4.16 | 12115343.39 | 7167147.32 | 0.00 | 1.00 | 20-MAR-03:32 | 0.00 | 01-MAR-00:01 | 15894.36 | 20-MAR-03:32 | 11789.50 | 24-MAR-03:52 | 7383.25 | 26-MAR-03:52 | 3813.63 | 20-MAR-03:32 | 0.00 | 01-MAR-00:01 |
April | 0.277342E+10 | 0.673050E+09 | 72.44 | 0.181840E+10 | 0.955018E+09 | 0.00 | 1.00 | 11-APR-02:12 | 0.00 | 01-APR-00:01 | 31825.23 | 17-APR-03:21 | 17210.25 | 17-APR-03:21 | 15176.54 | 16-APR-02:42 | 7630.07 | 16-APR-02:42 | 0.00 | 01-APR-00:01 |
May | 0.612228E+10 | 0.155405E+10 | 215.46 | 0.386599E+10 | 0.225629E+10 | 0.00 | 1.00 | 05-MAY-00:42 | 0.00 | 01-MAY-00:01 | 31825.23 | 12-MAY-04:01 | 22011.18 | 05-MAY-00:42 | 19019.88 | 12-MAY-03:21 | 7630.07 | 05-MAY-00:42 | 0.00 | 01-MAY-00:01 |
June | 0.216700E+11 | 0.516717E+10 | 407.43 | 0.130124E+11 | 0.865761E+10 | 0.00 | 1.00 | 01-JUN-00:42 | 0.00 | 01-JUN-00:01 | 35359.92 | 30-JUN-10:34 | 22536.06 | 25-JUN-14:10 | 21035.19 | 26-JUN-03:41 | 8318.84 | 11-JUN-14:53 | 0.00 | 01-JUN-00:01 |
July | 0.298211E+11 | 0.704178E+10 | 545.25 | 0.158407E+11 | 0.139805E+11 | 0.00 | 1.00 | 01-JUL-00:03 | 0.00 | 01-JUL-00:01 | 35359.92 | 03-JUL-13:00 | 19337.87 | 02-JUL-11:07 | 23234.16 | 04-JUL-01:42 | 7960.36 | 26-JUL-14:53 | 0.00 | 01-JUL-00:01 |
August | 0.269709E+11 | 0.639521E+10 | 496.00 | 0.145664E+11 | 0.124045E+11 | 0.00 | 1.00 | 01-AUG-00:04 | 0.00 | 01-AUG-00:01 | 35359.92 | 03-AUG-11:57 | 21810.13 | 04-AUG-14:55 | 24265.75 | 04-AUG-04:02 | 8393.64 | 04-AUG-14:55 | 0.00 | 01-AUG-00:01 |
September | 0.109960E+11 | 0.274437E+10 | 282.68 | 0.813973E+10 | 0.285627E+10 | 0.00 | 1.00 | 01-SEP-00:04 | 0.00 | 01-SEP-00:01 | 32731.74 | 12-SEP-03:06 | 23378.25 | 18-SEP-00:10 | 20262.12 | 12-SEP-03:06 | 7690.89 | 12-SEP-03:06 | 0.00 | 01-SEP-00:01 |
October | 0.465872E+09 | 0.131786E+09 | 43.14 | 0.345664E+09 | 0.120209E+09 | 0.00 | 1.00 | 02-OCT-00:52 | 0.00 | 01-OCT-00:01 | 24450.60 | 03-OCT-03:31 | 14069.68 | 03-OCT-03:31 | 11291.05 | 10-OCT-03:31 | 5863.38 | 03-OCT-03:31 | 0.00 | 01-OCT-00:01 |
November | 47095186.77 | 12434570.78 | 5.09 | 26699819.86 | 20395366.90 | 0.00 | 1.00 | 03-NOV-02:12 | 0.00 | 01-NOV-00:01 | 31825.23 | 09-NOV-04:22 | 17036.66 | 09-NOV-05:01 | 14987.95 | 09-NOV-04:22 | 7630.07 | 09-NOV-04:22 | 0.00 | 01-NOV-00:01 |
December | 1798235.63 | 546408.61 | 0.64 | 1390884.58 | 407351.05 | 0.00 | 0.19 | 05-DEC-04:10 | 0.00 | 01-DEC-00:01 | 2453.57 | 05-DEC-04:10 | 1798.18 | 05-DEC-04:10 | 655.40 | 05-DEC-04:10 | 730.08 | 05-DEC-04:10 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.988894E+11 | 0.237262E+11 | 2072.88 | 0.576307E+11 | 0.412587E+11 | 0.00 | ||||||||||||||
Minimum of Months | 535229.70 | 162730.20 | 0.21 | 451165.63 | 84064.07 | 0.00 | 0.17 | 0.00 | 2104.54 | 1798.18 | 231.44 | 630.15 | 0.00 | |||||||
Maximum of Months | 0.298211E+11 | 0.704178E+10 | 545.25 | 0.158407E+11 | 0.139805E+11 | 0.00 | 1.00 | 0.00 | 35359.92 | 23378.25 | 24265.75 | 8393.64 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.29 | 34.27 | 49.02 | 27.17 | 381.91 | 0.00 | 0.00 | 0.00 |
February | 110.40 | 48.55 | 61.86 | 53.12 | 301.47 | 0.00 | 0.00 | 0.00 |
March | 150.00 | 59.54 | 90.46 | 105.01 | 193.09 | 0.00 | 0.00 | 0.00 |
April | 184.19 | 80.66 | 103.53 | 171.89 | 133.98 | 0.00 | 0.00 | 0.00 |
May | 231.33 | 101.08 | 130.25 | 259.21 | 74.15 | 0.00 | 0.00 | 0.00 |
June | 254.57 | 110.86 | 143.71 | 318.70 | 52.94 | 0.00 | 0.00 | 0.00 |
July | 257.30 | 118.73 | 138.58 | 328.46 | 46.87 | 0.00 | 0.00 | 0.00 |
August | 216.90 | 93.51 | 123.39 | 275.58 | 56.29 | 0.00 | 0.00 | 0.00 |
September | 193.46 | 91.42 | 102.04 | 225.01 | 94.06 | 0.00 | 0.00 | 0.00 |
October | 123.28 | 51.49 | 71.79 | 100.33 | 145.60 | 0.00 | 0.00 | 0.00 |
November | 72.74 | 23.63 | 49.11 | 31.49 | 237.36 | 0.00 | 0.00 | 0.00 |
December | 56.34 | 24.20 | 32.15 | 19.72 | 343.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.40 | 69.93 | 91.47 | 160.22 | 171.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.34 | 23.63 | 32.15 | 19.72 | 46.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 257.30 | 118.73 | 143.71 | 328.46 | 381.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 483.48 | 330.85 | 152.62 | 392.48 | 675.28 | 0.00 | 0.00 | 0.00 |
February | 518.04 | 349.99 | 168.05 | 445.45 | 538.73 | 0.00 | 0.00 | 0.00 |
March | 450.81 | 237.38 | 213.43 | 417.88 | 380.20 | 0.00 | 0.00 | 0.00 |
April | 406.15 | 189.88 | 216.27 | 433.34 | 277.85 | 0.00 | 0.00 | 0.00 |
May | 336.48 | 91.22 | 245.26 | 384.99 | 159.68 | 0.00 | 0.00 | 0.00 |
June | 326.67 | 66.51 | 260.16 | 417.56 | 112.70 | 0.00 | 0.00 | 0.00 |
July | 345.81 | 87.13 | 258.67 | 459.22 | 99.09 | 0.00 | 0.00 | 0.00 |
August | 389.61 | 139.72 | 249.89 | 526.37 | 119.46 | 0.00 | 0.00 | 0.00 |
September | 472.12 | 248.77 | 223.35 | 594.44 | 194.12 | 0.00 | 0.00 | 0.00 |
October | 493.00 | 309.28 | 183.71 | 534.12 | 288.24 | 0.00 | 0.00 | 0.00 |
November | 371.96 | 232.86 | 139.11 | 329.76 | 438.47 | 0.00 | 0.00 | 0.00 |
December | 396.65 | 300.45 | 96.19 | 355.76 | 624.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 415.30 | 214.57 | 200.73 | 440.88 | 324.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 326.67 | 66.51 | 96.19 | 329.76 | 99.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 518.04 | 349.99 | 260.16 | 594.44 | 675.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.60 | 33.42 | 49.18 | 28.96 | 391.26 | 0.00 | 0.00 | 0.00 |
February | 121.12 | 59.69 | 61.44 | 67.62 | 311.78 | 0.00 | 0.00 | 0.00 |
March | 144.60 | 53.80 | 90.80 | 98.37 | 199.41 | 0.00 | 0.00 | 0.00 |
April | 210.92 | 104.30 | 106.63 | 211.24 | 137.52 | 0.00 | 0.00 | 0.00 |
May | 211.53 | 84.50 | 127.03 | 236.59 | 77.32 | 0.00 | 0.00 | 0.00 |
June | 248.21 | 107.57 | 140.64 | 311.88 | 55.33 | 0.00 | 0.00 | 0.00 |
July | 266.50 | 126.59 | 139.91 | 343.73 | 48.95 | 0.00 | 0.00 | 0.00 |
August | 232.99 | 106.93 | 126.06 | 300.56 | 58.62 | 0.00 | 0.00 | 0.00 |
September | 188.60 | 89.52 | 99.08 | 219.16 | 97.42 | 0.00 | 0.00 | 0.00 |
October | 131.42 | 58.43 | 72.99 | 113.41 | 152.18 | 0.00 | 0.00 | 0.00 |
November | 78.67 | 29.09 | 49.58 | 41.63 | 241.78 | 0.00 | 0.00 | 0.00 |
December | 60.50 | 28.52 | 31.98 | 26.68 | 350.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.98 | 73.54 | 91.44 | 167.15 | 176.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.50 | 28.52 | 31.98 | 26.68 | 48.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 266.50 | 126.59 | 140.64 | 343.73 | 391.26 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223086E+09 | 91800452.76 | 0.131286E+09 | 72781040.36 | 0.102290E+10 |
February | 0.267083E+09 | 0.117442E+09 | 0.149642E+09 | 0.128520E+09 | 0.729310E+09 |
March | 0.401765E+09 | 0.159472E+09 | 0.242293E+09 | 0.281267E+09 | 0.517182E+09 |
April | 0.477415E+09 | 0.209075E+09 | 0.268340E+09 | 0.445529E+09 | 0.347285E+09 |
May | 0.619582E+09 | 0.270729E+09 | 0.348853E+09 | 0.694271E+09 | 0.198610E+09 |
June | 0.659839E+09 | 0.287349E+09 | 0.372490E+09 | 0.826060E+09 | 0.137229E+09 |
July | 0.689159E+09 | 0.317993E+09 | 0.371166E+09 | 0.879757E+09 | 0.125546E+09 |
August | 0.580948E+09 | 0.250459E+09 | 0.330489E+09 | 0.738123E+09 | 0.150773E+09 |
September | 0.501438E+09 | 0.236955E+09 | 0.264483E+09 | 0.583225E+09 | 0.243810E+09 |
October | 0.330203E+09 | 0.137923E+09 | 0.192280E+09 | 0.268711E+09 | 0.389986E+09 |
November | 0.188538E+09 | 61240585.29 | 0.127298E+09 | 81621134.65 | 0.615227E+09 |
December | 0.150911E+09 | 64804922.64 | 86106467.03 | 52827065.39 | 0.920675E+09 |
Annual Sum or Average | 0.508997E+10 | 0.220524E+10 | 0.288472E+10 | 0.505269E+10 | 0.539853E+10 |
Minimum of Months | 0.150911E+09 | 61240585.29 | 86106467.03 | 52827065.39 | 0.125546E+09 |
Maximum of Months | 0.689159E+09 | 0.317993E+09 | 0.372490E+09 | 0.879757E+09 | 0.102290E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129495E+10 | 0.886161E+09 | 0.408788E+09 | 0.105122E+10 | 0.180867E+10 |
February | 0.125324E+10 | 0.846697E+09 | 0.406541E+09 | 0.107762E+10 | 0.130331E+10 |
March | 0.120745E+10 | 0.635802E+09 | 0.571647E+09 | 0.111925E+10 | 0.101834E+10 |
April | 0.105274E+10 | 0.492176E+09 | 0.560564E+09 | 0.112322E+10 | 0.720181E+09 |
May | 0.901232E+09 | 0.244336E+09 | 0.656896E+09 | 0.103115E+10 | 0.427692E+09 |
June | 0.846735E+09 | 0.172400E+09 | 0.674336E+09 | 0.108231E+10 | 0.292111E+09 |
July | 0.926207E+09 | 0.233379E+09 | 0.692828E+09 | 0.122997E+10 | 0.265393E+09 |
August | 0.104353E+10 | 0.374233E+09 | 0.669294E+09 | 0.140983E+10 | 0.319972E+09 |
September | 0.122374E+10 | 0.644811E+09 | 0.578931E+09 | 0.154079E+10 | 0.503151E+09 |
October | 0.132044E+10 | 0.828389E+09 | 0.492049E+09 | 0.143059E+10 | 0.772035E+09 |
November | 0.964130E+09 | 0.603563E+09 | 0.360567E+09 | 0.854729E+09 | 0.113651E+10 |
December | 0.106238E+10 | 0.804736E+09 | 0.257639E+09 | 0.952875E+09 | 0.167133E+10 |
Annual Sum or Average | 0.130968E+11 | 0.676668E+10 | 0.633008E+10 | 0.139036E+11 | 0.102387E+11 |
Minimum of Months | 0.846735E+09 | 0.172400E+09 | 0.257639E+09 | 0.854729E+09 | 0.265393E+09 |
Maximum of Months | 0.132044E+10 | 0.886161E+09 | 0.692828E+09 | 0.154079E+10 | 0.180867E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221247E+09 | 89518934.04 | 0.131728E+09 | 77570180.09 | 0.104794E+10 |
February | 0.293024E+09 | 0.144393E+09 | 0.148631E+09 | 0.163590E+09 | 0.754264E+09 |
March | 0.387289E+09 | 0.144093E+09 | 0.243197E+09 | 0.263477E+09 | 0.534097E+09 |
April | 0.546716E+09 | 0.270341E+09 | 0.276375E+09 | 0.547529E+09 | 0.356458E+09 |
May | 0.566574E+09 | 0.226333E+09 | 0.340242E+09 | 0.633688E+09 | 0.207084E+09 |
June | 0.643362E+09 | 0.278817E+09 | 0.364545E+09 | 0.808389E+09 | 0.143425E+09 |
July | 0.713801E+09 | 0.339066E+09 | 0.374735E+09 | 0.920648E+09 | 0.131105E+09 |
August | 0.624042E+09 | 0.286394E+09 | 0.337648E+09 | 0.805014E+09 | 0.157005E+09 |
September | 0.488849E+09 | 0.232033E+09 | 0.256817E+09 | 0.568061E+09 | 0.252523E+09 |
October | 0.352005E+09 | 0.156497E+09 | 0.195508E+09 | 0.303755E+09 | 0.407601E+09 |
November | 0.203902E+09 | 75402587.82 | 0.128499E+09 | 0.107901E+09 | 0.626684E+09 |
December | 0.162038E+09 | 76386940.35 | 85651040.84 | 71464094.67 | 0.938809E+09 |
Annual Sum or Average | 0.520285E+10 | 0.231927E+10 | 0.288357E+10 | 0.527109E+10 | 0.555700E+10 |
Minimum of Months | 0.162038E+09 | 75402587.82 | 85651040.84 | 71464094.67 | 0.131105E+09 |
Maximum of Months | 0.713801E+09 | 0.339066E+09 | 0.374735E+09 | 0.920648E+09 | 0.104794E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 372.88 | 1372.70 | 649.37 | 398.55 | 250.82 | 0.00 | 0.00 |
February | 498.22 | 1084.01 | 749.56 | 458.22 | 291.34 | 0.00 | 0.00 |
March | 590.77 | 742.21 | 745.41 | 350.72 | 394.69 | 0.00 | 0.00 |
April | 792.90 | 525.79 | 801.26 | 374.84 | 426.42 | 0.00 | 0.00 |
May | 865.05 | 295.41 | 779.34 | 276.81 | 502.54 | 0.00 | 0.00 |
June | 1038.93 | 211.77 | 829.45 | 284.94 | 544.51 | 0.00 | 0.00 |
July | 1124.88 | 188.38 | 869.61 | 332.45 | 537.16 | 0.00 | 0.00 |
August | 1093.92 | 225.78 | 839.50 | 340.16 | 499.34 | 0.00 | 0.00 |
September | 1027.51 | 374.50 | 854.18 | 429.71 | 424.47 | 0.00 | 0.00 |
October | 732.63 | 570.81 | 747.70 | 419.21 | 328.49 | 0.00 | 0.00 |
November | 372.66 | 887.38 | 523.37 | 285.57 | 237.79 | 0.00 | 0.00 |
December | 351.96 | 1268.04 | 513.49 | 353.17 | 160.32 | 0.00 | 0.00 |
Annual Sum or Average | 739.74 | 643.56 | 741.68 | 358.04 | 383.64 | 0.00 | 0.00 |
Minimum of Months | 351.96 | 188.38 | 513.49 | 276.81 | 160.32 | 0.00 | 0.00 |
Maximum of Months | 1124.88 | 1372.70 | 869.61 | 458.22 | 544.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.998711E+09 | 0.367665E+10 | 0.173928E+10 | 0.106748E+10 | 0.671801E+09 | 0.00 | 0.00 |
February | 0.120529E+10 | 0.262244E+10 | 0.181335E+10 | 0.110853E+10 | 0.704813E+09 | 0.00 | 0.00 |
March | 0.158231E+10 | 0.198793E+10 | 0.199650E+10 | 0.939367E+09 | 0.105714E+10 | 0.00 | 0.00 |
April | 0.205519E+10 | 0.136284E+10 | 0.207687E+10 | 0.971592E+09 | 0.110528E+10 | 0.00 | 0.00 |
May | 0.231696E+10 | 0.791234E+09 | 0.208739E+10 | 0.741397E+09 | 0.134599E+10 | 0.00 | 0.00 |
June | 0.269290E+10 | 0.548901E+09 | 0.214994E+10 | 0.738566E+09 | 0.141137E+10 | 0.00 | 0.00 |
July | 0.301288E+10 | 0.504547E+09 | 0.232917E+10 | 0.890438E+09 | 0.143873E+10 | 0.00 | 0.00 |
August | 0.292994E+10 | 0.604724E+09 | 0.224852E+10 | 0.911086E+09 | 0.133743E+10 | 0.00 | 0.00 |
September | 0.266329E+10 | 0.970706E+09 | 0.221403E+10 | 0.111380E+10 | 0.110023E+10 | 0.00 | 0.00 |
October | 0.196228E+10 | 0.152885E+10 | 0.200265E+10 | 0.112281E+10 | 0.879837E+09 | 0.00 | 0.00 |
November | 0.965930E+09 | 0.230010E+10 | 0.135657E+10 | 0.740207E+09 | 0.616364E+09 | 0.00 | 0.00 |
December | 0.942685E+09 | 0.339633E+10 | 0.137532E+10 | 0.945928E+09 | 0.429397E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.233284E+11 | 0.202952E+11 | 0.233896E+11 | 0.112912E+11 | 0.120984E+11 | 0.00 | 0.00 |
Minimum of Months | 0.942685E+09 | 0.504547E+09 | 0.135657E+10 | 0.738566E+09 | 0.429397E+09 | 0.00 | 0.00 |
Maximum of Months | 0.301288E+10 | 0.367665E+10 | 0.232917E+10 | 0.112281E+10 | 0.143873E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.158679E+11 | -0.150674E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -800484585.1 | 58.99 | 0.00 | 0.00 |
February | 0.146081E+11 | -0.138860E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -722077683.3 | 58.99 | 0.00 | 0.00 |
March | 0.160367E+11 | -0.152503E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -786348228.5 | 58.99 | 0.00 | 0.00 |
April | 0.148873E+11 | -0.141520E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -735266689.2 | 58.99 | 0.00 | 0.00 |
May | 0.144727E+11 | -0.137704E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -702228807.2 | 58.99 | 0.00 | 0.00 |
June | 0.130987E+11 | -0.124408E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -657957318.5 | 58.99 | 0.00 | 0.00 |
July | 0.127651E+11 | -0.120979E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -667131641.3 | 58.99 | 0.00 | 0.00 |
August | 0.124753E+11 | -0.118058E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -669498608.8 | 58.99 | 0.00 | 0.00 |
September | 0.122294E+11 | -0.115535E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -675976725.1 | 58.99 | 0.00 | 0.00 |
October | 0.133022E+11 | -0.125465E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -755643120.3 | 58.99 | 0.00 | 0.00 |
November | 0.137548E+11 | -0.130012E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -753664682.6 | 58.98 | 0.00 | 0.00 |
December | 0.151267E+11 | -0.143283E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -798421372.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.168625E+12 | -0.159900E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.872470E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.122294E+11 | -0.152503E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -800484585.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.160367E+11 | -0.115535E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -657957318.5 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.58 | 0.56 | 01-JAN-09:39 | 4584.74 | 27.80 | 119.67 | 250.00 | 4575.34 | 27.68 | 119.67 | 251.00 |
February | 226.83 | 0.58 | 0.56 | 01-FEB-07:00 | 6052.35 | 29.84 | 153.83 | 259.50 | 6069.26 | 29.89 | 153.83 | 260.00 |
March | 334.33 | 0.57 | 0.56 | 01-MAR-07:40 | 2406.38 | 19.74 | 63.17 | 340.17 | 2132.54 | 18.61 | 42.67 | 338.83 |
April | 285.17 | 0.58 | 0.56 | 01-APR-06:40 | 2431.91 | 16.21 | 0.00 | 363.00 | 2828.12 | 18.26 | 33.00 | 361.17 |
May | 428.67 | 0.57 | 0.56 | 01-MAY-05:40 | 2160.19 | 16.11 | 0.00 | 419.00 | 2019.56 | 16.06 | 0.00 | 419.00 |
June | 400.67 | 0.58 | 0.56 | 01-JUN-04:00 | 2559.67 | 16.25 | 0.00 | 420.17 | 2465.99 | 16.26 | 0.00 | 417.67 |
July | 414.00 | 0.57 | 0.56 | 01-JUL-05:40 | 2888.88 | 16.43 | 0.00 | 427.33 | 2570.15 | 16.65 | 3.50 | 428.83 |
August | 410.83 | 0.57 | 0.56 | 01-AUG-05:49 | 2591.65 | 16.64 | 5.67 | 399.67 | 2647.53 | 18.10 | 44.83 | 398.83 |
September | 326.50 | 0.57 | 0.56 | 01-SEP-05:00 | 3259.85 | 21.17 | 86.00 | 347.17 | 3220.84 | 19.98 | 61.83 | 348.50 |
October | 325.17 | 0.57 | 0.56 | 01-OCT-06:49 | 5399.11 | 29.25 | 246.00 | 311.67 | 5828.15 | 29.74 | 248.17 | 311.00 |
November | 254.83 | 0.58 | 0.56 | 01-NOV-07:40 | 3771.13 | 27.52 | 175.17 | 252.50 | 3604.18 | 26.07 | 153.17 | 252.67 |
December | 186.17 | 0.58 | 0.56 | 01-DEC-07:00 | 3309.93 | 23.93 | 76.83 | 229.67 | 3316.95 | 24.03 | 76.83 | 231.33 |
Annual Sum or Average | 3807.33 | 0.57 | 3273.23 | 20.72 | 926.33 | 4019.83 | 3247.48 | 20.79 | 937.50 | 4018.83 | ||
Minimum of Months | 186.17 | 0.57 | 0.56 | 2160.19 | 16.11 | 0.00 | 229.67 | 2019.56 | 16.06 | 0.00 | 231.33 | |
Maximum of Months | 428.67 | 0.58 | 0.56 | 6052.35 | 29.84 | 246.00 | 427.33 | 6069.26 | 29.89 | 248.17 | 428.83 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.575149E+11 | 60240.27 | 03-JAN-03:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.414495E+11 | 60240.27 | 01-FEB-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286564E+11 | 60240.27 | 01-MAR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150506E+11 | 60240.27 | 03-APR-02:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.265893E+10 | 19186.80 | 02-MAY-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.826947E+09 | 7970.12 | 03-JUN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17534026.89 | 3316.79 | 23-JUL-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 59775459.41 | 4130.59 | 07-AUG-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.272671E+10 | 22658.29 | 30-SEP-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108398E+11 | 20144.30 | 08-OCT-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.276404E+11 | 60240.27 | 21-NOV-03:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.467250E+11 | 60240.27 | 06-DEC-03:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 17534026.89 | 3316.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.575149E+11 | 60240.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.575993E+11 | 78169.05 | 30-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.390253E+11 | 80708.40 | 02-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204118E+11 | 53341.28 | 08-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.832029E+10 | 30665.81 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.441433E+09 | 11845.47 | 03-MAY-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13641163.35 | 10742.20 | 03-JUN-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.538878E+09 | 15849.49 | 30-SEP-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377155E+10 | 17724.65 | 28-OCT-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.208926E+11 | 61627.08 | 28-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.407077E+11 | 63039.12 | 09-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191722E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.575993E+11 | 80708.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.186512E+10 | 0.121202E+10 | 42119.71 | 16-APR-01:51 | 24271.82 | 0.00 |
May | 0.00 | 0.00 | 0.296466E+10 | 0.195564E+10 | 21660.79 | 31-MAY-12:00 | 15257.95 | 0.00 |
June | 0.00 | 0.00 | 0.137454E+11 | 0.843838E+10 | 45445.83 | 26-JUN-00:09 | 21498.20 | 0.00 |
July | 0.00 | 0.00 | 0.182314E+11 | 0.102950E+11 | 45992.35 | 04-JUL-00:13 | 17615.58 | 0.00 |
August | 0.00 | 0.00 | 0.164519E+11 | 0.949270E+10 | 46638.04 | 04-AUG-00:42 | 18031.40 | 0.00 |
September | 0.00 | 0.00 | 0.730491E+10 | 0.543029E+10 | 43033.83 | 12-SEP-00:42 | 23140.52 | 0.00 |
October | 0.00 | 0.00 | 0.108308E+09 | 93779736.08 | 6141.63 | 20-OCT-15:10 | 5514.02 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.606717E+11 | 0.369179E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.182314E+11 | 0.102950E+11 | 46638.04 | 24271.82 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 535229.70 | 451165.63 | 2104.54 | 10-JAN-04:46 | 1873.10 | 0.00 |
February | 0.00 | 0.00 | 1052090.81 | 773432.79 | 2619.84 | 10-FEB-04:10 | 1821.67 | 0.00 |
March | 0.00 | 0.00 | 19282490.71 | 12115343.39 | 15894.36 | 20-MAR-03:32 | 9661.13 | 0.00 |
April | 0.00 | 0.00 | 0.277342E+10 | 0.181840E+10 | 31825.23 | 17-APR-03:21 | 17210.25 | 0.00 |
May | 0.00 | 0.00 | 0.612228E+10 | 0.386599E+10 | 31825.23 | 12-MAY-04:01 | 12909.77 | 0.00 |
June | 0.00 | 0.00 | 0.216700E+11 | 0.130124E+11 | 35359.92 | 30-JUN-10:34 | 18245.75 | 0.00 |
July | 0.00 | 0.00 | 0.298211E+11 | 0.158407E+11 | 35359.92 | 03-JUL-13:00 | 16922.88 | 0.00 |
August | 0.00 | 0.00 | 0.269709E+11 | 0.145664E+11 | 35359.92 | 03-AUG-11:57 | 16435.89 | 0.00 |
September | 0.00 | 0.00 | 0.109960E+11 | 0.813973E+10 | 32731.74 | 12-SEP-03:06 | 12469.62 | 0.00 |
October | 0.00 | 0.00 | 0.465872E+09 | 0.345664E+09 | 24450.60 | 03-OCT-03:31 | 14069.68 | 0.00 |
November | 0.00 | 0.00 | 47095186.77 | 26699819.86 | 31825.23 | 09-NOV-04:22 | 16837.28 | 0.00 |
December | 0.00 | 0.00 | 1798235.63 | 1390884.58 | 2453.57 | 05-DEC-04:10 | 1798.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.988894E+11 | 0.576307E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 535229.70 | 451165.63 | 2104.54 | 1798.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.298211E+11 | 0.158407E+11 | 35359.92 | 18245.75 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5920.46 | 22340.33 | 31-JAN-13:20 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6035.91 | 22493.75 | 21-FEB-13:15 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5991.35 | 22457.15 | 01-MAR-13:50 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5752.87 | 21864.38 | 01-APR-12:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5434.87 | 20758.74 | 01-MAY-12:30 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5093.02 | 19371.42 | 01-JUN-12:44 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4807.21 | 18146.92 | 01-JUL-12:30 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4701.39 | 17350.92 | 01-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 4748.61 | 17791.29 | 30-SEP-12:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4976.13 | 18924.01 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 5309.16 | 20267.03 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5642.21 | 21537.81 | 31-DEC-13:15 |
Annual Sum or Average | 0.00 | 5363.83 | ||||
Minimum of Months | 0.00 | 0.00 | 4701.39 | 17350.92 | ||
Maximum of Months | 0.00 | 0.00 | 6035.91 | 22493.75 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271316E+10 | 0.56 | 1211.87 | 01-JAN-00:01 | 0.67 |
February | 0.245532E+10 | 0.56 | 1211.87 | 01-FEB-00:01 | 0.67 |
March | 0.277278E+10 | 0.57 | 1211.87 | 01-MAR-00:01 | 0.67 |
April | 0.276701E+10 | 0.59 | 1211.87 | 01-APR-04:01 | 0.67 |
May | 0.307204E+10 | 0.63 | 1211.87 | 01-MAY-01:05 | 0.67 |
June | 0.300175E+10 | 0.63 | 1211.87 | 01-JUN-00:05 | 0.67 |
July | 0.310380E+10 | 0.63 | 1211.87 | 01-JUL-00:03 | 0.66 |
August | 0.310338E+10 | 0.63 | 1211.87 | 01-AUG-00:04 | 0.66 |
September | 0.297987E+10 | 0.63 | 1211.87 | 01-SEP-00:04 | 0.66 |
October | 0.294187E+10 | 0.60 | 1211.87 | 01-OCT-02:35 | 0.67 |
November | 0.273031E+10 | 0.58 | 1211.87 | 01-NOV-02:35 | 0.67 |
December | 0.272245E+10 | 0.56 | 1211.87 | 01-DEC-00:01 | 0.67 |
Annual Sum or Average | 0.343637E+11 | 0.60 | |||
Minimum of Months | 0.245532E+10 | 0.56 | 1211.87 | 0.66 | |
Maximum of Months | 0.310380E+10 | 0.63 | 1211.87 | 0.67 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.274497E+10 | 0.66 | 1833.44 | 03-JAN-03:06 | 0.93 |
February | 0.227241E+10 | 0.63 | 1833.44 | 01-FEB-03:01 | 0.93 |
March | 0.219016E+10 | 0.59 | 1833.44 | 01-MAR-03:01 | 0.92 |
April | 0.186679E+10 | 0.54 | 1833.44 | 03-APR-02:61 | 0.92 |
May | 0.168628E+10 | 0.47 | 990.41 | 18-MAY-05:53 | 0.67 |
June | 0.162759E+10 | 0.49 | 990.03 | 26-JUN-18:00 | 0.66 |
July | 0.168541E+10 | 0.50 | 1316.98 | 26-JUL-18:00 | 0.78 |
August | 0.168797E+10 | 0.51 | 1518.63 | 04-AUG-13:00 | 0.83 |
September | 0.165210E+10 | 0.49 | 1147.15 | 30-SEP-04:06 | 0.73 |
October | 0.183650E+10 | 0.51 | 1029.56 | 23-OCT-06:10 | 0.69 |
November | 0.211489E+10 | 0.58 | 1833.44 | 21-NOV-03:07 | 0.92 |
December | 0.254451E+10 | 0.64 | 1833.44 | 06-DEC-03:08 | 0.93 |
Annual Sum or Average | 0.239096E+11 | 0.55 | |||
Minimum of Months | 0.162759E+10 | 0.47 | 990.03 | 0.66 | |
Maximum of Months | 0.274497E+10 | 0.66 | 1833.44 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.182954E+10 | 0.60 | 1315.27 | 30-JAN-05:02 | 0.92 |
February | 0.152964E+10 | 0.57 | 1339.31 | 02-FEB-05:03 | 0.93 |
March | 0.148091E+10 | 0.54 | 1080.25 | 08-MAR-05:03 | 0.84 |
April | 0.135111E+10 | 0.53 | 1331.03 | 18-APR-04:01 | 0.92 |
May | 0.134735E+10 | 0.54 | 1438.29 | 09-MAY-04:01 | 0.95 |
June | 0.151283E+10 | 0.58 | 1438.29 | 09-JUN-03:21 | 0.95 |
July | 0.163668E+10 | 0.58 | 1438.29 | 02-JUL-03:21 | 0.95 |
August | 0.161352E+10 | 0.58 | 1438.29 | 01-AUG-03:21 | 0.95 |
September | 0.135545E+10 | 0.55 | 1438.29 | 01-SEP-03:21 | 0.95 |
October | 0.133668E+10 | 0.53 | 1038.80 | 03-OCT-03:31 | 0.82 |
November | 0.144928E+10 | 0.55 | 1438.29 | 09-NOV-05:01 | 0.95 |
December | 0.166989E+10 | 0.57 | 1172.05 | 09-DEC-05:03 | 0.87 |
Annual Sum or Average | 0.181129E+11 | 0.56 | |||
Minimum of Months | 0.133668E+10 | 0.53 | 1038.80 | 0.82 | |
Maximum of Months | 0.182954E+10 | 0.60 | 1438.29 | 0.95 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 49.23 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 50.44 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 50.39 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 51.01 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 49.93 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 51.65 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:03 | 0.00 | 0.00 | 52.53 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 52.30 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 52.36 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 50.86 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 51.87 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 51.52 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 49.23 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 52.53 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 35.92 | 35.92 | 5920.46 | 22340.33 | 31-JAN-13:20 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 50.68 | 50.68 | 6035.91 | 22493.75 | 21-FEB-13:15 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 50.66 | 50.66 | 5991.35 | 22457.15 | 01-MAR-13:50 |
April | 0.00 | 0.00 | 01-APR-00:01 | 50.90 | 50.90 | 5752.87 | 21864.38 | 01-APR-12:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 36.72 | 36.72 | 5434.87 | 20758.74 | 01-MAY-12:30 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 52.00 | 52.00 | 5093.02 | 19371.42 | 01-JUN-12:44 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 52.60 | 52.60 | 4807.21 | 18146.92 | 01-JUL-12:30 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.17 | 52.17 | 4701.39 | 17350.92 | 01-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.23 | 52.23 | 4748.61 | 17791.29 | 30-SEP-12:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 39.96 | 39.96 | 4976.13 | 18924.01 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 51.81 | 51.81 | 5309.16 | 20267.03 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 51.32 | 51.32 | 5642.21 | 21537.81 | 31-DEC-13:15 |
Annual Sum or Average | 0.00 | 5363.83 | ||||||
Minimum of Months | 0.00 | 0.00 | 35.92 | 35.92 | 4701.39 | 17350.92 | ||
Maximum of Months | 0.00 | 0.00 | 52.60 | 52.60 | 6035.91 | 22493.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.274497E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.227241E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.219016E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.235438E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.248994E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.514077E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.632297E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.589490E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.359976E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.186876E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.211489E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.254451E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.395384E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.186876E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.632297E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.182970E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.152996E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.148620E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.202416E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.290140E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.668000E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.867845E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.800872E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.409981E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.146847E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.146171E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.167044E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.418390E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.146171E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.867845E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.274497E+10 | 0.00 | 0.575149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227241E+10 | 0.00 | 0.414495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.219016E+10 | 0.00 | 0.286564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186679E+10 | 0.186405E+10 | 0.150506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168628E+10 | 0.296466E+10 | 0.265893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162759E+10 | 0.136808E+11 | 0.826947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168541E+10 | 0.181269E+11 | 17534026.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168797E+10 | 0.163961E+11 | 59775459.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165210E+10 | 0.727805E+10 | 0.272671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183650E+10 | 0.108308E+09 | 0.108398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.211489E+10 | 0.00 | 0.276404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254451E+10 | 0.00 | 0.467250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239096E+11 | 0.604189E+11 | 0.234167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162759E+10 | 0.00 | 17534026.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.274497E+10 | 0.181269E+11 | 0.575149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.182954E+10 | 535229.70 | 0.575993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152964E+10 | 1052090.81 | 0.390253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148091E+10 | 19282490.71 | 0.204118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135111E+10 | 0.277141E+10 | 0.832029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134735E+10 | 0.610064E+10 | 0.441433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151283E+10 | 0.215189E+11 | 13641163.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163668E+10 | 0.296462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161352E+10 | 0.267861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135545E+10 | 0.109248E+11 | 0.538878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133668E+10 | 0.465872E+09 | 0.377155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144928E+10 | 46013128.95 | 0.208926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166989E+10 | 1798235.63 | 0.407077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181129E+11 | 0.982826E+11 | 0.191722E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133668E+10 | 535229.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182954E+10 | 0.296462E+11 | 0.575993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.274497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.219016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186679E+10 | 0.00 | 0.00 | 0.00 | 0.487594E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168628E+10 | 0.00 | 0.00 | 0.00 | 0.803657E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162759E+10 | 0.00 | 0.00 | 0.00 | 0.351318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168541E+10 | 0.00 | 0.00 | 0.00 | 0.463756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168797E+10 | 0.00 | 0.00 | 0.00 | 0.420693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165210E+10 | 0.00 | 0.00 | 0.00 | 0.194766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183650E+10 | 0.00 | 0.00 | 0.00 | 32256660.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.211489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239096E+11 | 0.00 | 0.00 | 0.00 | 0.156288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.274497E+10 | 0.00 | 0.00 | 0.00 | 0.463756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.182954E+10 | 0.00 | 0.00 | 0.00 | 162730.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152964E+10 | 0.00 | 0.00 | 0.00 | 318750.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148091E+10 | 0.00 | 0.00 | 0.00 | 5293851.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135111E+10 | 0.00 | 0.00 | 0.00 | 0.673050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134735E+10 | 0.00 | 0.00 | 0.00 | 0.155405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151283E+10 | 0.00 | 0.00 | 0.00 | 0.516717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163668E+10 | 0.00 | 0.00 | 0.00 | 0.704178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161352E+10 | 0.00 | 0.00 | 0.00 | 0.639521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135545E+10 | 0.00 | 0.00 | 0.00 | 0.274437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133668E+10 | 0.00 | 0.00 | 0.00 | 0.131786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144928E+10 | 0.00 | 0.00 | 0.00 | 12434570.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166989E+10 | 0.00 | 0.00 | 0.00 | 546408.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181129E+11 | 0.00 | 0.00 | 0.00 | 0.237262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133668E+10 | 0.00 | 0.00 | 0.00 | 162730.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182954E+10 | 0.00 | 0.00 | 0.00 | 0.704178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.164217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408929E+11 | 0.00 | 0.00 | 3.65 |
February | 0.179637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306416E+11 | 0.00 | 0.00 | 3.65 |
March | 0.350221E+10 | 0.00 | 0.00 | 190003.83 | 0.00 | 0.229119E+11 | 0.147966E+09 | 0.00 | 3.63 |
April | 0.487766E+10 | 0.299703E+09 | 0.00 | 2699992.06 | 0.00 | 0.120659E+11 | 0.711369E+09 | 0.00 | 3.77 |
May | 0.716057E+10 | 0.251438E+09 | 0.00 | 9054356.83 | 0.00 | 0.114644E+10 | 0.290515E+10 | 0.00 | 4.13 |
June | 0.343210E+10 | 0.252340E+10 | 0.00 | 15557120.29 | 10717.50 | 0.194411E+09 | 0.313804E+10 | 0.00 | 4.65 |
July | 0.101740E+10 | 0.298338E+10 | 0.00 | 21321462.15 | 0.00 | 0.00 | 0.407870E+10 | 0.00 | 5.13 |
August | 0.170398E+10 | 0.277725E+10 | 0.00 | 21932554.33 | 0.00 | 0.00 | 0.453673E+10 | 0.00 | 4.99 |
September | 0.556947E+10 | 0.766833E+09 | 3963.11 | 16212294.16 | 0.00 | 0.137935E+10 | 0.340878E+10 | 2993.41 | 4.41 |
October | 0.929528E+10 | 0.00 | 0.00 | 1746859.73 | 0.00 | 0.710851E+10 | 0.891636E+09 | 0.00 | 3.66 |
November | 0.465804E+10 | 0.00 | 0.00 | 98087.53 | 0.00 | 0.212417E+11 | 0.130245E+09 | 0.00 | 3.60 |
December | 0.173456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353051E+11 | 0.00 | 0.00 | 3.62 |
Annual Sum or Average | 0.463898E+11 | 0.960201E+10 | 3963.11 | 88812730.90 | 10717.50 | 0.172888E+12 | 0.199486E+11 | 2993.41 | 4.08 |
Minimum of Months | 0.101740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 |
Maximum of Months | 0.929528E+10 | 0.298338E+10 | 3963.11 | 21932554.33 | 10717.50 | 0.408929E+11 | 0.453673E+10 | 2993.41 | 5.13 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.905369E+11 | 0.00 | 0.00 | 85631.83 | 0.00 | 76755797.56 | 29971056.51 | 0.00 | 8.30 |
February | 0.685935E+11 | 0.00 | 0.00 | 122716.60 | 0.00 | 52184657.97 | 51950495.25 | 0.00 | 8.06 |
March | 0.525639E+11 | 0.00 | 0.00 | 1871727.14 | 0.00 | 14623503.70 | 0.187678E+10 | 0.00 | 7.71 |
April | 0.343305E+11 | 0.186423E+09 | 0.00 | 13946163.38 | 0.00 | 6505722.91 | 0.487882E+10 | 0.00 | 7.61 |
May | 0.119255E+11 | 95571633.31 | 0.00 | 46382734.73 | 0.00 | 0.00 | 0.178978E+11 | 0.00 | 7.73 |
June | 0.482943E+10 | 0.344071E+10 | 0.00 | 56979087.04 | 0.00 | 0.00 | 0.126489E+11 | 0.00 | 8.33 |
July | 0.973254E+09 | 0.429167E+10 | 0.00 | 74676528.86 | 0.00 | 0.00 | 0.110788E+11 | 0.00 | 8.54 |
August | 0.123817E+10 | 0.434042E+10 | 0.00 | 75091444.50 | 0.00 | 0.00 | 0.137504E+11 | 0.00 | 8.50 |
September | 0.105905E+11 | 0.321903E+09 | 0.00 | 61509016.23 | 0.00 | 0.00 | 0.160292E+11 | 0.00 | 7.92 |
October | 0.315012E+11 | 0.00 | 0.00 | 11576802.56 | 0.00 | 0.00 | 0.840625E+10 | 0.00 | 7.49 |
November | 0.509600E+11 | 0.00 | 0.00 | 3671170.51 | 0.00 | 11503149.75 | 0.396667E+10 | 0.00 | 7.75 |
December | 0.744933E+11 | 0.00 | 0.00 | 178163.95 | 0.00 | 28568658.99 | 57497819.70 | 0.00 | 7.97 |
Annual Sum or Average | 0.432536E+12 | 0.126767E+11 | 0.00 | 0.346091E+09 | 0.00 | 0.190141E+09 | 0.906730E+11 | 0.00 | 7.99 |
Minimum of Months | 0.973254E+09 | 0.00 | 0.00 | 85631.83 | 0.00 | 0.00 | 29971056.51 | 0.00 | 7.49 |
Maximum of Months | 0.905369E+11 | 0.434042E+10 | 0.00 | 75091444.50 | 0.00 | 76755797.56 | 0.178978E+11 | 0.00 | 8.54 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:27
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.206287E+11 | 0.284891E+11 | 0.185989E+12 | 0.00 | 0.465428E+11 |
February | 0.254901E+11 | 0.220689E+11 | 0.145513E+12 | 0.00 | 0.362075E+11 |
March | 0.419723E+11 | 0.179784E+11 | 0.124417E+12 | 7192118.93 | 0.311162E+11 |
April | 0.522973E+11 | 0.124718E+11 | 0.930218E+11 | 0.227995E+09 | 0.328257E+11 |
May | 0.620713E+11 | 0.785807E+10 | 0.742083E+11 | 0.738867E+09 | 0.378637E+11 |
June | 0.655362E+11 | 0.305908E+10 | 0.370228E+11 | 0.103026E+10 | 0.727217E+11 |
July | 0.661109E+11 | 0.113508E+10 | 0.220682E+11 | 0.112109E+10 | 0.908096E+11 |
August | 0.573146E+11 | 0.189485E+10 | 0.298463E+11 | 0.126561E+10 | 0.825922E+11 |
September | 0.389331E+11 | 0.597096E+10 | 0.649313E+11 | 0.105360E+10 | 0.497061E+11 |
October | 0.278104E+11 | 0.118765E+11 | 0.992623E+11 | 0.179789E+09 | 0.241752E+11 |
November | 0.149830E+11 | 0.171961E+11 | 0.124502E+12 | 386081.22 | 0.285433E+11 |
December | 0.969837E+10 | 0.238144E+11 | 0.160658E+12 | 0.00 | 0.370690E+11 |
Annual Sum or Average | 0.482846E+12 | 0.153813E+12 | 0.116144E+13 | 0.562479E+10 | 0.570173E+12 |
Minimum of Months | 0.969837E+10 | 0.113508E+10 | 0.220682E+11 | 0.00 | 0.241752E+11 |
Maximum of Months | 0.661109E+11 | 0.284891E+11 | 0.185989E+12 | 0.126561E+10 | 0.908096E+11 |