Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 08:25:26
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2010.19 | 8651.84 | 8651.84 |
Net Site Energy | 2010.19 | 8651.84 | 8651.84 |
Total Source Energy | 3249.34 | 13985.11 | 13985.11 |
Net Source Energy | 3249.34 | 13985.11 | 13985.11 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 775.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 29.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 276.59 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 95.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 244.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 62.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 513.82 | 1496.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 775.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 22.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 29.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 27.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 95.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 244.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 28.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 775.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 22.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 29.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 27.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 276.59 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 95.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 244.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 62.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 242.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 510.52 | 4386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1457.98 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2211.49 | 6440.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 242.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 510.52 | 4386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1457.98 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2211.49 | 6440.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 513.823 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 513.823 | 100.00 |
Total On-Site and Utility Electric Sources | 513.823 | 100.00 |
Total Electricity End Uses | 513.823 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 6.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4464.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 7.5044 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.8503 | 18.52 | 1074.0064 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.6773 | 2.48 | 595.3967 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.6773 | 2.48 | 595.3967 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 7.5044 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.8503 | 18.52 | 1074.0064 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 8.6773 | 1.24 | 595.3967 | |||||||
Conditioned Total | 232.34 | 8.6773 | 1.24 | 595.3967 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 8.6773 | 2.48 | 595.3967 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JUN-11:20 | 04-JAN-13:09 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 123981.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15495.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1331.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 13514.13 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3920.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27201.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2959.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 37220.27 | 174166.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 123981.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 15495.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1331.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 12146.55 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 3920.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 27201.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1338.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 840.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 72.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 92.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 85.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 875.96 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 303.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 264.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 196.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1627.28 | 1622.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3616.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 311.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 399.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 369.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3770.11 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1305.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1138.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 847.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7003.78 | 6981.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3616.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 311.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 399.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 369.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3770.11 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1305.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1138.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 847.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7003.78 | 6981.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.66 |
KITCHEN DIRECT AIR | 1.28 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.66 | 1.66 | 1.66 | 1.66 | 1.66 | 1.66 | 1.00 | 1.00 | 1.66 |
PSZ-AC_2:2 | 1.28 | 1.28 | 1.28 | 1.28 | 1.28 | 1.28 | 1.00 | 1.00 | 1.28 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.66 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.28 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.66 | 1776.20 |
PSZ-AC_2:2_ADDAQ FAN | 1.28 | 1415.16 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.66 | 1.66 | 1.66 | 1.10 | 39100.66 | 62477.08 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.28 | 1.28 | 1.28 | 1.28 | 31740.45 | 99688.13 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.66 | 0.829964 | 1.11 | 39100.66 | 19550.33 | 0.717370 | 0.717370 |
PSZ-AC_2:2 COOLING COIL | 1.28 | 0.639094 | 0.852127 | 31740.45 | 15870.23 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 62477.08 |
PSZ-AC_2:2 HEATING COIL | 99688.13 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 7.504 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 124.291 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.850 | 282.654 | 791.353 | 0.000 | 0.000 | 0.000 | 1083.857 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 871.800 | 7.504 | 9.958 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 871.800 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1144.319 | 9.850 | 182.411 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1144.319 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 515.917 | 4.441 | 82.240 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 851.667 | 7.331 | 135.761 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.4391 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2452 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2452 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.043 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.002 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.002 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.38584905E-12 | 0.75146531E-15 | -0.12966877E-12 | 0.12247089E-15 |
34 | 6 | 0.32626755E-07 | 0.12794687E-09 | 0.74410738E-08 | -0.15657130E-12 |
35 | 5 | -0.20999199E-03 | 0.10694986E-05 | -0.10771460E-03 | 0.73422529E-08 |
36 | 4 | 0.31512205 | 0.50965885E-03 | 0.10796022 | -0.36842960E-04 |
37 | 3 | -7.7206601 | 0.15495837E-01 | -2.4737779 | 0.31237450E-01 |
38 | 2 | 42.368774 | 0.54174396E-01 | 15.816616 | -0.35002435 |
39 | 1 | -81.692611 | 0.24088120E-01 | -29.635684 | 1.1030598 |
40 | 0 | 46.824332 | 0.47759164E-03 | 16.279740 | |
41 | 7 | -0.17135090E-08 | -0.36864923E-15 | 0.71259317E-14 | -0.97083918E-16 |
42 | 6 | 0.68579659E-05 | 0.47011368E-08 | 0.31862738E-02 | -0.26729135E-04 |
43 | 5 | -0.49396463E-03 | 0.27861516E-05 | -0.22352018 | 0.19543461E-02 |
44 | 4 | 0.11367371E-01 | 0.12683264E-03 | 4.8261412 | -0.45232255E-01 |
45 | 3 | -0.99836882E-01 | 0.10087729E-02 | -38.002184 | 0.39844117 |
46 | 2 | 0.35452054 | 0.16782362E-02 | 116.44652 | -1.4174386 |
47 | 1 | -0.51170991 | 0.51154075E-03 | -143.88527 | 2.0486777 |
48 | 0 | 0.24948649 | 0.12321491E-04 | 60.838472 | |
49 | 7 | -0.17135090E-08 | -0.36864923E-15 | 0.71259317E-14 | -0.97083918E-16 |
50 | 6 | 0.68579659E-05 | 0.47011368E-08 | 0.31862738E-02 | -0.26729135E-04 |
51 | 5 | -0.49396463E-03 | 0.27861516E-05 | -0.22352018 | 0.19543461E-02 |
52 | 4 | 0.11367371E-01 | 0.12683264E-03 | 4.8261412 | -0.45232255E-01 |
53 | 3 | -0.99836882E-01 | 0.10087729E-02 | -38.002184 | 0.39844117 |
54 | 2 | 0.35452054 | 0.16782362E-02 | 116.44652 | -1.4174386 |
55 | 1 | -0.51170991 | 0.51154075E-03 | -143.88527 | 2.0486777 |
56 | 0 | 0.24948649 | 0.12321491E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4116_SHGC_SOUTH_0.45 | 38 | 1 | VerySmooth | 2.339 | 2.339 | 1.000 | 0.451 | ||
2 | NONRESWINDOW_U_0.4116_SHGC_NORTH_0.45 | 39 | 1 | VerySmooth | 2.339 | 2.339 | 1.000 | 0.451 | ||
3 | NONRESWINDOW_U_0.4116_SHGC_EAST_0.45 | 40 | 1 | VerySmooth | 2.339 | 2.339 | 1.000 | 0.451 | ||
4 | NONRESWINDOW_U_0.4116_SHGC_WEST_0.45 | 41 | 1 | VerySmooth | 2.339 | 2.339 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.12284E-002 | 0.36619 | 0.42846 | 0.42846 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12208 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.12284E-002 | 0.36619 | 0.42846 | 0.42846 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12208 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.12284E-002 | 0.36619 | 0.42846 | 0.42846 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12208 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.12284E-002 | 0.36619 | 0.42846 | 0.42846 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12208 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.053 | 0.3093 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.584 | 5.025E-003 | 6.281E-003 | 5.934 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.8262E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.6678E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.6426E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.3987E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.3166E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 3.1936E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.7203E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.6668E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 9.3800E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 9.1223E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 0.1089 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 0.1057 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 6.6025E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.4821E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.7466E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.7478E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.3918E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.5193E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.0480E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.2394E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.8013E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.0675E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.6726E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.7204E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 18033.58473 | 21640.30167 | 1.38327 | 1.65993 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10000 | 1.27259E-002 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 8576.06680 | 10291.28016 | 0.38150 | 0.45781 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -32.70000 | 1.83376E-004 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16680.58309 | 20016.69971 | 1.06516 | 1.27819 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 28.98400 | 1.27239E-002 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 837.45752 | 1004.94902 | 3.37107E-002 | 1.14133 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -32.70000 | 1.83376E-004 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 24311.51 | 1.65993 | 1.65993 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 35992.48 | 0.45781 | 0.45781 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 23521.84 | 1.27819 | 1.27819 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 96212.05 | 1.14133 | 1.14133 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.65993 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.27819 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.65993 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.65993 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.65993 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.65993 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.65993 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.65993 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.27819 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.27819 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.27819 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.27819 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.27819 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.27819 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.65993 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.27819 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.65993 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.65993 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 1776.20175 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.65993 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.65993 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.65993 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.09555 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.65993 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.82996 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.10662 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 39100.66000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19550.33000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71737 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71737 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39100.66000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 62477.07683 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 62477.07683 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.27819 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.27819 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1415.15696 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.27819 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.27819 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.27819 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.27819 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.27819 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63909 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.85213 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31740.45000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15870.22500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31740.45000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 99688.13346 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 99688.13346 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 37915.5 | 11.74 | 11.69 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 30832.0 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4116_SHGC_EAST_0.45 | N/A | 2.339 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4116_SHGC_SOUTH_0.45 | N/A | 2.339 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4116_SHGC_WEST_0.45 | N/A | 2.339 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.245 | 0.231 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.245 | 0.231 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1692947168 | 0.6556334404 | Pass | Pass | 0.2090167695 | 1.2347073454 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1147431651 | 0.5737601104 | Pass | Pass | 6.4411510400E-002 | 0.3059739997 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.3021633985 | 0.2873977353 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 439.61 | 178.35 | 1310.95 | 10.01 | 526.25 | 2465.18 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.236 | 0.245 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.236 | 0.245 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.4116_SHGC_EAST_0.45 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.339 | 0.451 | 0.452 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4116_SHGC_SOUTH_0.45 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.339 | 0.451 | 0.452 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.4116_SHGC_WEST_0.45 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.339 | 0.451 | 0.452 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.339 | 0.451 | 0.452 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.339 | 0.451 | 0.452 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 7.5044 | 116.17 | 871.80 | LightsWired | LTG_SCH_DINING | 91.35 | 168.00 | 65.68 | 0.0000 | Y | 10.75 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.8503 | 116.17 | 1144.32 | LightsWired | LTG_SCH_KITCHEN | 87.05 | 168.00 | 86.54 | 0.0000 | Y | 18.59 |
Interior Lighting Total | 8.6773 | 232.34 | 2016.12 | 29.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.22 | 871.80 | 191.80 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.22 | 871.80 | 191.80 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 216.58 | AstronomicalClock | - | 49.55 | 49.55 | 2.01 | |
EXTERIOR_LIGHTS_B | 1823.66 | AstronomicalClock | - | 83.52 | 73.33 | 25.10 | |
Exterior Lighting Total | 2040.24 | 27.12 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 39100.66 | 28049.64 | 11051.02 | 0.72 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31740.45 | 22252.59 | 9487.86 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 37915.5 | 11.74 | 11.69 | ||||
PSZ-AC_2:2 COOLING COIL | 30832.0 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 62477.08 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 99688.13 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 1.56 | 1211.87 | 778.12 | 1.00 | 0.64 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.66 | 1776.20 | 1070.05 | 1.00 | 1.34 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.28 | 1415.16 | 1107.16 | 1.00 | 1.35 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 18033.58 | 21640.30 | 186.28 | 1.383 | 1.660 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.87 | 0.01066 | 30.10 | 0.01273 | 0.416 | 0.00 |
KITCHEN | 16680.58 | 20016.70 | 172.30 | 1.065 | 1.278 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.01019 | 28.98 | 0.01272 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 8576.07 | 10291.28 | 88.59 | 0.382 | 0.458 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00783 | -32.70 | 0.00018 | 0.416 | 0.00 |
KITCHEN | 837.46 | 1004.95 | 8.65 | 0.034 | 1.141 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 18.89 | 18.89 | 0.00442 | -32.70 | 0.00018 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.66 | 1.66 | 0.46 | 0.46 | 1.6599 | 1.6599 | 1.6599 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.28 | 1.28 | 1.14 | 1.14 | 1.2782 | 1.2782 | 1.2782 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 39100.660 | 28049.640 | 1.659930 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 19550.33 | 13372.45 | 1.106620 | 25.43 | 18.59 | 0.01117849 | 11.90 | 11.35 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 37.5970 | 23.87 | 0.01066092 | 55.2245 | 18033.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 62477.077 | 62477.077 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 62477.08 | 62477.08 | 1.659928 | 7.54 | 6.59 | 0.00591193 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 25.0647 | 21.11 | 0.00782804 | 48.1837 | 8576.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 31740.450 | 22252.595 | 1.278190 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 15870.23 | 10183.81 | 0.852127 | 28.67 | 20.52 | 0.01245253 | 11.87 | 11.33 | 0.00850000 | 28.98 | 0.01272390 | 20.81 | 133.9394 | 26.10 | 0.01018938 | 46.2632 | 16680.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 99688.133 | 99688.133 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:50:00 | 99688.13 | 99688.13 | 1.278188 | -27.26 | -27.26 | 0.00067043 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 89.2931 | 18.69 | 0.00473236 | 34.0117 | 371.34 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 39100.660 | 28049.640 | 1.659930 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.6203 | 1004.8586 | 1.1539 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.659928 | 1.91543253 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 19550.33 | 13372.45 | 1.0000 | 1.27695632 | 1.106620 | 25.43 | 18.59 | 0.01117849 | 54039.4 | 11.90 | 11.35 | 0.00850000 | 33399.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19550.33 | 30.10 | 0.01272586 | 21.13 | 0.41605618 | 37.5970 | 23.87 | 0.01066092 | 23.87 | 0.01066092 | 55.2245 | 18033.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 62477.077 | 62477.077 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.659928 | 1.91543253 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | Sensible | 62477.08 | 62477.08 | 1.0000 | 1.91543253 | 1.659928 | 7.54 | 6.59 | 0.00591193 | 22444.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62477.08 | -32.70 | 0.00018338 | -32.70 | 0.41605618 | 25.0647 | 21.00 | 0.00782804 | 21.11 | 0.00782804 | 48.1837 | 8576.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31740.450 | 22252.595 | 1.278190 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.9886 | 1004.8586 | 1.1539 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.278188 | 1.47493286 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 15870.23 | 10183.81 | 1.0000 | 0.98329014 | 0.852127 | 28.67 | 20.52 | 0.01245253 | 60616.1 | 11.87 | 11.33 | 0.00850000 | 33369.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15870.23 | 28.98 | 0.01272390 | 20.81 | 1.14133354 | 133.9394 | 26.06 | 0.01018938 | 26.10 | 0.01018938 | 46.2632 | 16680.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 99688.133 | 99688.133 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.278188 | 1.47493286 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:50:00 | Sensible | 99688.13 | 99688.13 | 1.0000 | 1.47493286 | 1.278188 | -27.26 | -27.26 | 0.00067043 | -25750.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 99688.13 | -32.70 | 0.00018338 | -32.70 | 1.14133354 | 89.2931 | 18.09 | 0.00473236 | 18.69 | 0.00473236 | 34.0117 | 371.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.66 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.28 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3990.17 | 5926.67 | 2958.50 |
KITCHEN | 5109.33 | 6291.00 | 4379.33 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5190.50 | 6883.17 | 4464.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 128.17 | 19.17 | 0.17 | 0.00 |
KITCHEN | 0.00 | 157.83 | 0.00 | 6.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 128.17 | 158.83 | 0.17 | 6.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.752 | 2.809 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 11.927 | 0.031 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.063 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 11.140 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 12301419.17 | 0.00 | 12301419.17 | 7117691.41 | 19419110.58 | 13120747.55 | 1421.35 | 6217.30 | 1121.35 | 470.87 |
KITCHEN | 31053894.41 | 0.00 | 31053894.41 | 127660.64 | 31181555.04 | 35993094.65 | 1442.58 | 6201.55 | 1115.87 | 554.78 |
Total Facility | 43355313.58 | 0.00 | 43355313.58 | 7245352.05 | 50600665.63 | 49113842.20 | 1454.53 | 6433.10 | 1336.29 | 775.51 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4616 | 0.0000 | 0.4616 | 0.2732 | 0.7347 | 0.4161 | 0.00 | 6079.82 | 1107.18 |
KITCHEN | 1.1613 | 0.0000 | 1.1613 | 0.0030 | 1.1643 | 1.1413 | 0.00 | 6089.59 | 1097.41 |
Total Facility | 1.6229 | 0.0000 | 1.6229 | 0.2761 | 1.8991 | 1.5574 | 0.00 | 6293.27 | 1310.85 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 16380341.43 | 0.00 | 16380341.43 | 13120747.55 | 1416.77 | 0.35 | 7342.88 | 470.80 |
PSZ-AC_2:2 | 41349582.51 | 0.00 | 41349582.51 | 35993094.65 | 1426.54 | 1.57 | 7331.88 | 554.78 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6146 | 0.0000 | 0.6146 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.5464 | 0.0000 | 1.5464 | 1.1413 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1113.40 | 331.03 | 6213.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 1235.48 | 6506.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.0217 | 0.7663 | 0.5541 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.6945 | 1.5198 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 374 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 513.82 | 5207.66 | 06-JAN-01:10 | 37220.27 | 30-JUN-11:20 |
Electricity:Building | 323.79 | 2948.69 | 01-JAN-01:10 | 19261.27 | 02-JAN-11:10 |
Electricity:Zone:DINING | 81.08 | 392.54 | 01-JAN-01:10 | 4341.96 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 305.93 | 2539.66 | 01-JAN-01:10 | 15745.17 | 02-JAN-11:10 |
InteriorLights:Electricity | 29.34 | 221.88 | 21-MAY-05:00 | 1654.77 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:DINING | 10.75 | 68.62 | 21-MAY-05:00 | 735.19 | 02-JAN-16:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 29.34 | 221.88 | 21-MAY-05:00 | 1654.77 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 29.34 | 221.88 | 21-MAY-05:00 | 1654.77 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 10.75 | 68.62 | 21-MAY-05:00 | 735.19 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 29.34 | 221.88 | 21-MAY-05:00 | 1654.77 | 02-JAN-16:30 |
Electricity:Zone:KITCHEN | 242.71 | 2556.15 | 01-JAN-01:10 | 14919.31 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 18.59 | 153.26 | 01-JAN-01:10 | 919.59 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 18.59 | 153.26 | 01-JAN-01:10 | 919.59 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 276.59 | 2263.87 | 01-JAN-01:10 | 14413.88 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 276.59 | 2263.87 | 01-JAN-01:10 | 14413.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 206.26 | 1993.86 | 01-JAN-01:10 | 10483.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 62.16 | 1035.59 | 06-APR-22:30 | 4592.33 | 26-MAY-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
Electricity:Plant | 44.30 | 779.93 | 25-DEC-23:10 | 2546.44 | 01-SEP-04:10 |
LowTempRefrigeration:Refrigeration:Electricity | 15.80 | 0.00 | 01-JAN-11:10 | 1470.21 | 01-SEP-04:10 |
MedTempRefrigeration:Refrigeration:Electricity | 28.50 | 701.41 | 20-DEC-00:20 | 1076.23 | 23-APR-13:10 |
ElectricityPurchased:Facility | 513.82 | 5207.66 | 06-JAN-01:10 | 37220.27 | 30-JUN-11:20 |
ElectricityPurchased:Plant | 513.82 | 5207.66 | 06-JAN-01:10 | 37220.27 | 30-JUN-11:20 |
Cogeneration:ElectricityPurchased | 513.82 | 5207.66 | 06-JAN-01:10 | 37220.27 | 30-JUN-11:20 |
General:Cogeneration:ElectricityPurchased | 513.82 | 5207.66 | 06-JAN-01:10 | 37220.27 | 30-JUN-11:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 513.82 | 5207.66 | 06-JAN-01:10 | 37220.27 | 30-JUN-11:20 |
ElectricityNet:Plant | 513.82 | 5207.66 | 06-JAN-01:10 | 37220.27 | 30-JUN-11:20 |
Cogeneration:ElectricityNet | 513.82 | 5207.66 | 06-JAN-01:10 | 37220.27 | 30-JUN-11:20 |
General:Cogeneration:ElectricityNet | 513.82 | 5207.66 | 06-JAN-01:10 | 37220.27 | 30-JUN-11:20 |
Electricity:HVAC | 118.62 | 0.00 | 01-JAN-01:10 | 20334.48 | 29-JUN-17:40 |
Fans:Electricity | 95.80 | 0.00 | 01-JAN-01:10 | 4252.80 | 04-JAN-21:00 |
General:Fans:Electricity | 95.80 | 0.00 | 01-JAN-01:10 | 4252.80 | 04-JAN-21:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 22.82 | 0.00 | 01-JAN-00:10 | 16324.80 | 29-JUN-17:40 |
General:Cooling:Electricity | 22.82 | 0.00 | 01-JAN-00:10 | 16324.80 | 29-JUN-17:40 |
ExteriorLights:Electricity | 27.12 | 0.00 | 01-JAN-08:20 | 2040.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 27.12 | 0.00 | 01-JAN-08:20 | 2040.24 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 05-MAR-09:40 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 05-MAR-09:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1496.37 | 2558.65 | 01-JAN-03:40 | 174166.63 | 04-JAN-13:10 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 775.21 | 0.00 | 01-JAN-01:10 | 139809.13 | 06-JAN-07:10 |
Heating:NaturalGas | 775.21 | 0.00 | 01-JAN-01:10 | 139809.13 | 06-JAN-07:10 |
General:Heating:NaturalGas | 775.21 | 0.00 | 01-JAN-01:10 | 139809.13 | 06-JAN-07:10 |
NaturalGas:Plant | 244.01 | 720.00 | 01-JAN-03:40 | 32454.89 | 24-FEB-13:20 |
WaterSystems:NaturalGas | 244.01 | 720.00 | 01-JAN-03:40 | 32454.89 | 24-FEB-13:20 |
Water Heater:WaterSystems:NaturalGas | 244.01 | 720.00 | 01-JAN-03:40 | 32454.89 | 24-FEB-13:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUN-12:30 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUN-12:30 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUN-12:30 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUN-12:30 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUN-12:30 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUN-12:30 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUN-12:30 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUN-12:30 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1446.34 | 2739.73 | 06-JAN-01:10 | 160351.35 | 04-JAN-21:00 |
EnergyTransfer:Building | 493.82 | 1369.87 | 06-JAN-01:10 | 44547.95 | 04-JAN-12:10 |
EnergyTransfer:Zone:KITCHEN | 345.98 | 1369.87 | 06-JAN-01:10 | 26431.43 | 15-SEP-04:10 |
Refrigeration:EnergyTransfer | 141.02 | 2699.61 | 25-DEC-23:10 | 7834.84 | 26-MAY-03:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 70.51 | 1349.80 | 25-DEC-23:10 | 3917.42 | 26-MAY-03:30 |
General:Refrigeration:EnergyTransfer | 70.51 | 1349.80 | 25-DEC-23:10 | 3917.42 | 26-MAY-03:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 70.51 | 1349.80 | 25-DEC-23:10 | 3917.42 | 26-MAY-03:30 |
EnergyTransfer:Plant | 240.23 | 1349.80 | 25-DEC-23:10 | 25173.05 | 21-FEB-13:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 16.22 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 54.28 | 1114.23 | 20-DEC-00:20 | 2238.70 | 23-APR-13:10 |
EnergyTransfer:Zone:DINING | 147.84 | 0.00 | 01-JAN-01:10 | 34976.40 | 14-FEB-04:50 |
Heating:EnergyTransfer | 93.76 | 0.00 | 01-JAN-00:20 | 30912.29 | 04-JAN-21:00 |
Heating:EnergyTransfer:Zone:DINING | 93.68 | 0.00 | 01-JAN-00:20 | 30912.29 | 04-JAN-21:00 |
General:Heating:EnergyTransfer | 93.76 | 0.00 | 01-JAN-00:20 | 30912.29 | 04-JAN-21:00 |
General:Heating:EnergyTransfer:Zone:DINING | 93.68 | 0.00 | 01-JAN-00:20 | 30912.29 | 04-JAN-21:00 |
Cooling:EnergyTransfer | 329.55 | 0.00 | 01-JAN-01:10 | 27442.18 | 29-JUN-17:10 |
Cooling:EnergyTransfer:Zone:DINING | 54.16 | 0.00 | 01-JAN-01:10 | 16262.75 | 14-FEB-04:50 |
General:Cooling:EnergyTransfer | 329.55 | 0.00 | 01-JAN-01:10 | 27442.18 | 29-JUN-17:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 54.16 | 0.00 | 01-JAN-01:10 | 16262.75 | 14-FEB-04:50 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.08 | 0.00 | 01-JAN-00:20 | 2552.05 | 24-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.08 | 0.00 | 01-JAN-00:20 | 2552.05 | 24-DEC-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 275.39 | 0.00 | 01-JAN-01:10 | 22546.61 | 15-SEP-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 275.39 | 0.00 | 01-JAN-01:10 | 22546.61 | 15-SEP-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 169.72 | 0.00 | 01-JAN-00:10 | 23053.05 | 26-FEB-14:00 |
PlantLoopHeatingDemand:Plant | 169.72 | 0.00 | 01-JAN-00:10 | 23053.05 | 26-FEB-14:00 |
WaterSystems:PlantLoopHeatingDemand | 169.72 | 0.00 | 01-JAN-00:10 | 23053.05 | 26-FEB-14:00 |
General:WaterSystems:PlantLoopHeatingDemand | 169.72 | 0.00 | 01-JAN-00:10 | 23053.05 | 26-FEB-14:00 |
EnergyTransfer:HVAC | 712.28 | 0.00 | 01-JAN-01:10 | 111847.30 | 06-JAN-07:10 |
HeatingCoils:EnergyTransfer | 620.17 | 0.00 | 01-JAN-01:10 | 111847.30 | 06-JAN-07:10 |
CoolingCoils:EnergyTransfer | 92.12 | 0.00 | 01-JAN-00:10 | 67525.10 | 29-JUN-18:00 |
WaterSystems:EnergyTransfer | 169.72 | 0.00 | 01-JAN-00:10 | 23053.05 | 26-FEB-14:00 |
WaterUse:WaterSystems:EnergyTransfer | 169.72 | 0.00 | 01-JAN-00:10 | 23053.05 | 26-FEB-14:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 93.681 | -54.160 | 0.000 | 0.000 | 72.841 | 10.748 | 52.748 | 25.800 | 0.000 | 1.403 | 0.002 | 0.000 | -20.316 | 0.000 | -151.083 | -31.663 |
KITCHEN | 0.000 | 0.000 | 0.078 | -275.385 | 0.000 | 0.000 | 5.322 | 18.590 | 211.968 | 0.000 | 0.000 | 0.006 | 42.477 | 0.000 | 0.000 | 0.000 | -3.057 | -0.002 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.217 | 9.136 | 0.000 | 0.000 | 0.000 | -12.352 | -0.000 |
Total Facility | 0.000 | 0.000 | 93.760 | -329.545 | 0.000 | 0.000 | 78.163 | 29.339 | 264.717 | 25.800 | 0.000 | 4.626 | 51.614 | 0.000 | -20.316 | 0.000 | -166.492 | -31.665 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 06-JAN-04:31 | 0.00 | 0.00 | 0.00 | -38239.53 | 0.00 | 0.00 | 0.00 | 122.53 | 506.27 | 0.00 | 0.00 | 0.00 | 40766.82 | 0.00 | -2698.42 | 0.00 | -457.67 | 0.00 |
KITCHEN | 06-JAN-05:01 | 0.00 | 0.00 | 0.00 | -71153.17 | 0.00 | 0.00 | 20.02 | 204.35 | 5271.43 | 0.00 | 0.00 | 0.00 | 65805.23 | 0.00 | -0.00 | 0.00 | -147.86 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-JAN-05:01 | -33931.13 | 33931.13 | 33931.13 | -71153.17 | 0.00 | 0.00 | 444.86 | 367.73 | 6491.17 | 0.00 | 0.00 | 318.03 | 32526.96 | 0.00 | -2630.09 | 0.00 | -296.60 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 18-FEB-03:01 | 0.00 | 0.00 | 43041.06 | 0.00 | 0.00 | 0.00 | 0.00 | 122.53 | 202.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1406.21 | 0.00 | -626.89 | -41333.00 |
KITCHEN | 24-DEC-05:02 | 0.00 | 0.00 | 25494.30 | 0.00 | 0.00 | 0.00 | 0.00 | 153.26 | 5264.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -148.73 | -30763.73 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-FEB-03:01 | 0.00 | 0.00 | 43041.06 | 0.00 | 0.00 | 0.00 | 0.00 | 275.79 | 2219.64 | 0.00 | 0.00 | 109.04 | 0.00 | 0.00 | -1406.21 | 0.00 | -1310.98 | -42928.35 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.6599 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.6599 | 0.2506 | 1.0000 | Not calculated | 0.4161 | 0.2506 | ||
PSZ-AC_2:2 | 1.2782 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2782 | 0.1184 | 1.0000 | Not calculated | 0.1513 | 0.1184 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.6599 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.6599 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2506 | ||
PSZ-AC_2:2 | 1.2782 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2782 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1184 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6599 | 1.6599 | 1.6599 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2782 | 1.2782 | 1.2782 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.6599 | 1.6599 | 1.6599 | 1.6599 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2782 | 1.2782 | 1.2782 | 1.2782 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6599 | 1.6599 | 1.6599 | No | 0.4161 | 0.9088 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2782 | 1.2782 | 1.2782 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.6599 | 1.6599 | 1.6599 | 1.6599 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2782 | 1.2782 | 1.2782 | 1.2782 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 6.00 |
Number of hours not met | 6.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 775.21 | 139809.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 22.82 | 16324.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 29.34 | 1654.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 27.12 | 2040.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 95.80 | 4252.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 244.01 | 32454.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 17.86 | 3516.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.80 | 1470.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 28.50 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 338.75 | 513.82 |
Natural Gas | 477.16 | 1496.37 |
Additional | 0.00 | 0.00 |
Total | 815.91 | 2010.19 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 126.27 |
Space Heating | 0.00 |
Space Cooling | 98.21 |
Fans (All) | 412.32 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1190.44 |
Miscellaneous (All) | 2211.49 |
Subtotal | 2211.49 |
Natural Gas [MJ/m2] | |
Space Heating | 3336.48 |
Service Water Heating | 1050.19 |
Miscellaneous (All) | 6440.35 |
Subtotal | 6440.35 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.46 |
Space Heating | 38.56 |
Space Cooling | 1.14 |
Fans (All) | 4.77 |
Service Water Heating | 12.14 |
Receptacle Equipment | 37.50 |
Miscellaneous | 4.44 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4763. | 8760. |
LTG_SCH_KITCHEN | 4539. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_SETBACK | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_SETBACK | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8627.83 | 132.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 7471.00 | 451.17 | 371.00 | 382.67 | 84.17 |
Min | 7471.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 451.17 | 371.00 | 382.67 | 84.17 |
Average | 8286.28 | 194.44 | 123.67 | 127.56 | 28.06 |
Sum | 24858.83 | 583.33 | 371.00 | 382.67 | 84.17 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16232.00 | 26.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 26.00 | 0.00 | 0.00 | 0.00 |
Average | 90319.00 | 8.67 | 0.00 | 0.00 | 0.00 |
Sum | 270957.00 | 26.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8276.50 | 483.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7346.00 | 1414.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 7471.83 | 702.83 | 216.50 | 181.83 | 187.00 |
Min | 7346.00 | 483.50 | 0.00 | 0.00 | 0.00 |
Max | 8276.50 | 1414.00 | 216.50 | 181.83 | 187.00 |
Average | 7698.11 | 866.78 | 72.17 | 60.61 | 62.33 |
Sum | 23094.33 | 2600.33 | 216.50 | 181.83 | 187.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 238455.50 | 16269.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 13164.83 | 3093.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 238455.50 | 16269.50 | 0.00 | 0.00 | 0.00 |
Average | 83873.44 | 6454.22 | 0.00 | 0.00 | 0.00 |
Sum | 251620.33 | 19362.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:26
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Environment
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105671E+10 | 38237.54 | 06-JAN-04:31 | -34.8 | -34.9 | 0.444682E+10 | 3722.94 | 07-JAN-19:10 | -20.7 | -20.9 |
February | 0.896157E+09 | 32706.75 | 14-FEB-04:36 | -31.7 | -31.8 | 0.402506E+10 | 3722.89 | 18-FEB-19:00 | -15.0 | -15.6 |
March | 0.875955E+09 | 26943.19 | 05-MAR-04:47 | -28.3 | -28.5 | 0.449104E+10 | 3722.74 | 18-MAR-18:10 | -0.7 | -4.8 |
April | 0.217752E+10 | 13046.67 | 04-APR-23:01 | -10.1 | -11.5 | 0.442107E+10 | 4680.83 | 22-APR-18:10 | 16.73 | 7.31 |
May | 0.665408E+10 | 13851.73 | 26-MAY-03:21 | 19.40 | 15.77 | 0.496382E+10 | 4681.39 | 27-MAY-18:00 | 19.50 | 13.83 |
June | 0.940513E+10 | 15079.57 | 29-JUN-17:10 | 34.13 | 23.50 | 0.508316E+10 | 4681.28 | 17-JUN-18:10 | 34.13 | 23.50 |
July | 0.118260E+11 | 14296.41 | 22-JUL-02:62 | 19.32 | 18.24 | 0.531790E+10 | 4681.48 | 22-JUL-18:10 | 27.43 | 22.57 |
August | 0.105343E+11 | 14851.90 | 09-AUG-02:62 | 20.00 | 18.20 | 0.531255E+10 | 4681.43 | 05-AUG-18:30 | 20.00 | 18.20 |
September | 0.630902E+10 | 13658.22 | 01-SEP-03:21 | 16.60 | 16.44 | 0.472195E+10 | 4681.14 | 02-SEP-18:10 | 17.75 | 14.63 |
October | 0.254126E+10 | 11911.40 | 29-OCT-23:01 | -7.4 | -8.2 | 0.452836E+10 | 4450.82 | 21-OCT-18:10 | -7.4 | -8.2 |
November | 0.957141E+09 | 15160.95 | 25-NOV-00:01 | -15.0 | -15.4 | 0.431163E+10 | 4137.73 | 01-NOV-11:00 | -15.0 | -15.4 |
December | 0.927685E+09 | 30640.56 | 24-DEC-04:41 | -30.4 | -30.6 | 0.444511E+10 | 3722.96 | 09-DEC-19:10 | -30.4 | -30.6 |
Annual Sum or Average | 0.541610E+11 | 0.560685E+11 | ||||||||
Minimum of Months | 0.875955E+09 | 11911.40 | -34.8 | -34.9 | 0.402506E+10 | 3722.74 | -30.4 | -30.6 | ||
Maximum of Months | 0.118260E+11 | 38237.54 | 34.13 | 23.50 | 0.531790E+10 | 4681.48 | 34.13 | 23.50 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204244E+11 | 71208.56 | 06-JAN-05:01 | -34.9 | -35.0 | 0.768047E+10 | 5036.86 | 31-JAN-11:00 | -16.7 | -17.2 |
February | 0.189153E+11 | 68154.40 | 14-FEB-05:01 | -32.1 | -32.3 | 0.693767E+10 | 5036.86 | 15-FEB-11:00 | -13.3 | -14.5 |
March | 0.213299E+11 | 61878.82 | 05-MAR-05:01 | -28.1 | -28.3 | 0.768301E+10 | 5036.86 | 22-MAR-10:00 | -0.6 | -2.0 |
April | 0.218627E+11 | 43739.96 | 05-APR-04:01 | -12.4 | -13.3 | 0.745592E+10 | 5134.32 | 18-APR-10:50 | 17.38 | 11.12 |
May | 0.238240E+11 | 55896.47 | 05-MAY-04:01 | 3.67 | 0.39 | 0.778581E+10 | 5135.96 | 26-MAY-10:09 | 22.85 | 18.47 |
June | 0.234518E+11 | 47116.98 | 02-JUN-03:31 | 8.17 | 5.31 | 0.758229E+10 | 5149.51 | 30-JUN-10:50 | 30.92 | 23.73 |
July | 0.253990E+11 | 42714.79 | 18-JUL-03:31 | 8.30 | 8.06 | 0.784579E+10 | 5140.97 | 05-JUL-10:00 | 8.30 | 8.06 |
August | 0.256917E+11 | 43536.36 | 25-AUG-04:01 | 8.72 | 8.66 | 0.784203E+10 | 5135.98 | 09-AUG-10:09 | 8.72 | 8.66 |
September | 0.250247E+11 | 49822.02 | 15-SEP-04:01 | 5.00 | 4.68 | 0.752275E+10 | 5135.95 | 01-SEP-10:20 | 5.00 | 4.68 |
October | 0.254186E+11 | 45353.34 | 20-OCT-03:31 | 6.50 | 6.40 | 0.770015E+10 | 5113.13 | 19-OCT-10:00 | 6.50 | 6.40 |
November | 0.228771E+11 | 53214.47 | 29-NOV-05:01 | -19.6 | -19.9 | 0.743709E+10 | 5110.00 | 01-NOV-10:00 | -19.6 | -19.9 |
December | 0.211720E+11 | 64563.72 | 24-DEC-05:01 | -30.6 | -30.8 | 0.768036E+10 | 5036.86 | 04-DEC-11:50 | -30.6 | -30.8 |
Annual Sum or Average | 0.275391E+12 | 0.911533E+11 | ||||||||
Minimum of Months | 0.189153E+11 | 42714.79 | -34.9 | -35.0 | 0.693767E+10 | 5036.86 | -30.6 | -30.8 | ||
Maximum of Months | 0.256917E+11 | 71208.56 | 8.72 | 8.66 | 0.784579E+10 | 5149.51 | 30.92 | 23.73 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -23.1 | -23.5 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.5 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.3 | -3.3 | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.3 |
April | 0.00 | 0.00 | 01-APR-00:01 | 3.52 | 0.38 | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.38 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -0.0 | -1.4 | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.4 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 | 8.93 | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 | 13.57 | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.57 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.07 | 15.36 | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 19.75 | 18.15 | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.52 | 6.57 | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3.60 | 0.51 | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.51 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.00 | 0.00 | -23.1 | -23.5 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.00 | 0.00 | 19.75 | 18.15 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250575E+11 | 41884.69 | 14-JAN-04:01 | -25.6 |
February | 0.166399E+11 | 43042.37 | 18-FEB-03:01 | -9.4 |
March | 0.131445E+11 | 42276.72 | 16-MAR-02:21 | -25.0 |
April | 0.429673E+10 | 35754.93 | 04-APR-02:61 | -4.7 |
May | 0.347168E+09 | 15031.76 | 01-MAY-02:62 | -1.4 |
June | 12144288.21 | 2104.00 | 04-JUN-06:03 | 6.23 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 3246305.30 | 1705.18 | 19-AUG-06:05 | 6.23 |
September | 0.113262E+09 | 7700.23 | 28-SEP-05:50 | 6.70 |
October | 0.267687E+10 | 14298.15 | 25-OCT-04:04 | -3.3 |
November | 0.871678E+10 | 29129.03 | 26-NOV-03:01 | -11.5 |
December | 0.226730E+11 | 42196.55 | 26-DEC-04:41 | -25.6 |
Annual Sum or Average | 0.936812E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.250575E+11 | 43042.37 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26289661.26 | 21761.38 | 09-JAN-05:02 | -33.0 |
February | 16455645.29 | 19329.91 | 13-FEB-05:02 | -23.4 |
March | 9100295.11 | 19119.66 | 05-MAR-05:02 | -28.1 |
April | 2105177.67 | 8826.40 | 03-APR-04:03 | -5.4 |
May | 60825.50 | 1013.76 | 07-MAY-04:04 | 1.20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.07 |
September | 43441.69 | 724.03 | 06-SEP-04:04 | 1.10 |
October | 833834.45 | 11715.03 | 30-OCT-04:03 | -10.0 |
November | 3912195.82 | 10883.29 | 13-NOV-05:03 | -7.9 |
December | 19511929.97 | 25520.55 | 24-DEC-05:02 | -30.6 |
Annual Sum or Average | 78313006.76 | |||
Minimum of Months | 0.00 | 0.00 | -33.0 | |
Maximum of Months | 26289661.26 | 25520.55 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:01 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -8.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.00 | 0.00 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.100251E+10 | 735.19 | 02-JAN-16:30 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.869047E+09 | 735.19 | 01-FEB-17:10 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.926183E+09 | 735.19 | 01-MAR-17:30 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.848785E+09 | 735.19 | 01-APR-18:19 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.837926E+09 | 735.19 | 01-MAY-19:30 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.798850E+09 | 735.19 | 01-JUN-19:00 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.819604E+09 | 735.19 | 01-JUL-20:19 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.870439E+09 | 735.19 | 01-AUG-19:40 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.865351E+09 | 735.19 | 01-SEP-18:49 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.936291E+09 | 735.19 | 02-OCT-17:30 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.961547E+09 | 735.19 | 01-NOV-16:49 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.101179E+10 | 735.19 | 01-DEC-16:19 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.107483E+11 | 0.703313E+11 | ||||
Minimum of Months | 0.798850E+09 | 735.19 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.101179E+10 | 735.19 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.157083E+10 | 919.59 | 02-JAN-10:09 | 0.175178E+11 | 10483.62 | 01-JAN-11:09 |
February | 0.142278E+10 | 919.59 | 01-FEB-10:09 | 0.158225E+11 | 10483.62 | 01-FEB-11:09 |
March | 0.159585E+10 | 919.59 | 01-MAR-10:09 | 0.175179E+11 | 10483.62 | 01-MAR-11:09 |
April | 0.152633E+10 | 919.59 | 01-APR-16:10 | 0.169527E+11 | 10483.62 | 01-APR-10:09 |
May | 0.158334E+10 | 919.59 | 01-MAY-09:09 | 0.175178E+11 | 10483.62 | 01-MAY-10:09 |
June | 0.154251E+10 | 919.59 | 01-JUN-09:09 | 0.169528E+11 | 10483.62 | 01-JUN-10:09 |
July | 0.156734E+10 | 919.59 | 01-JUL-16:10 | 0.175177E+11 | 10483.62 | 01-JUL-10:09 |
August | 0.159585E+10 | 919.59 | 01-AUG-09:09 | 0.175179E+11 | 10483.62 | 01-AUG-10:09 |
September | 0.152669E+10 | 919.59 | 01-SEP-09:09 | 0.169527E+11 | 10483.62 | 01-SEP-10:09 |
October | 0.157065E+10 | 919.59 | 02-OCT-09:09 | 0.175178E+11 | 10483.62 | 01-OCT-10:09 |
November | 0.152062E+10 | 919.59 | 01-NOV-09:09 | 0.169527E+11 | 10483.62 | 01-NOV-10:09 |
December | 0.156752E+10 | 919.59 | 01-DEC-10:09 | 0.175177E+11 | 10483.62 | 01-DEC-11:09 |
Annual Sum or Average | 0.185903E+11 | 0.206258E+12 | ||||
Minimum of Months | 0.142278E+10 | 919.59 | 0.158225E+11 | 10483.62 | ||
Maximum of Months | 0.159585E+10 | 919.59 | 0.175179E+11 | 10483.62 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.100251E+10 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286457E+11 |
February | 0.852256E+10 | 0.869047E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212746E+11 |
March | 0.954557E+10 | 0.926183E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191151E+11 |
April | 0.915225E+10 | 0.848785E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8702152.19 | 0.108292E+11 |
May | 0.947560E+10 | 0.837926E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169308E+09 | 0.495869E+10 |
June | 0.922788E+10 | 0.798850E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457225E+09 | 0.265664E+10 |
July | 0.939996E+10 | 0.819604E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558961E+09 | 0.191747E+10 |
August | 0.954557E+10 | 0.870439E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202097E+09 | 0.290054E+10 |
September | 0.915225E+10 | 0.865351E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6887942.89 | 0.585937E+10 |
October | 0.940563E+10 | 0.936291E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105302E+11 |
November | 0.909363E+10 | 0.961547E+09 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155670E+11 |
December | 0.939996E+10 | 0.101179E+10 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268284E+11 |
Annual Sum or Average | 0.111326E+12 | 0.107483E+11 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140318E+10 | 0.151083E+12 |
Minimum of Months | 0.852256E+10 | 0.798850E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191747E+10 |
Maximum of Months | 0.954557E+10 | 0.101179E+10 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558961E+09 | 0.286457E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.157083E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499519E+09 |
February | 0.610713E+09 | 0.142278E+10 | 0.120683E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429903E+09 |
March | 0.684021E+09 | 0.159585E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312809E+09 |
April | 0.655836E+09 | 0.152633E+10 | 0.129303E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 13709.35 | 0.263799E+09 |
May | 0.679007E+09 | 0.158334E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 385286.55 | 0.130738E+09 |
June | 0.661256E+09 | 0.154251E+10 | 0.129304E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 2779460.44 | 85669738.90 |
July | 0.673587E+09 | 0.156734E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 2282944.13 | 58340247.82 |
August | 0.684021E+09 | 0.159585E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 638886.36 | 87118072.93 |
September | 0.655836E+09 | 0.152669E+10 | 0.129303E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138601E+09 |
October | 0.673993E+09 | 0.157065E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188370E+09 |
November | 0.651635E+09 | 0.152062E+10 | 0.129304E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346929E+09 |
December | 0.673587E+09 | 0.156752E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515508E+09 |
Annual Sum or Average | 0.797748E+10 | 0.185903E+11 | 0.157319E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 6100286.83 | 0.305730E+10 |
Minimum of Months | 0.610713E+09 | 0.142278E+10 | 0.120683E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58340247.82 |
Maximum of Months | 0.684021E+09 | 0.159585E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 2779460.44 | 0.515508E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314918E+09 | 0.536510E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295584E+09 | 0.728819E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257382E+09 | 0.112020E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268019E+09 | 0.130797E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245357E+09 | 0.163312E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208111E+09 | 0.156850E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263798E+09 | 0.166099E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218963E+09 | 0.133296E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224823E+09 | 0.101160E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311898E+09 | 0.662948E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321092E+09 | 0.370221E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286582E+09 | 0.418229E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321653E+10 | 0.123521E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208111E+09 | 0.370221E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321092E+09 | 0.166099E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 735.19 | 02-JAN-16:30 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 34550.28 | 05-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 735.19 | 01-FEB-17:10 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 30741.53 | 01-FEB-21:00 |
March | 9454.80 | 04-MAR-19:10 | 735.19 | 01-MAR-17:30 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 26406.36 | 06-MAR-21:00 |
April | 9454.80 | 01-APR-18:10 | 735.19 | 01-APR-18:19 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 808.47 | 23-APR-16:05 | 17911.56 | 04-APR-19:55 |
May | 9454.80 | 06-MAY-18:10 | 735.19 | 01-MAY-19:30 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2972.18 | 25-MAY-18:00 | 8607.11 | 01-MAY-19:52 |
June | 9454.80 | 03-JUN-18:10 | 735.19 | 01-JUN-19:00 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5461.43 | 29-JUN-17:03 | 5746.86 | 04-JUN-06:01 |
July | 9454.80 | 01-JUL-18:10 | 735.19 | 01-JUL-20:19 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2783.19 | 29-JUL-17:03 | 5067.26 | 08-JUL-19:00 |
August | 9454.80 | 05-AUG-18:10 | 735.19 | 01-AUG-19:40 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2925.57 | 08-AUG-17:03 | 6027.56 | 17-AUG-12:00 |
September | 9454.80 | 02-SEP-18:10 | 735.19 | 01-SEP-18:49 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 697.94 | 01-SEP-16:05 | 8577.55 | 23-SEP-18:52 |
October | 9454.80 | 07-OCT-18:10 | 735.19 | 02-OCT-17:30 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 14005.82 | 31-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 735.19 | 01-NOV-16:49 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 25348.91 | 25-NOV-19:10 |
December | 9454.80 | 02-DEC-19:10 | 735.19 | 01-DEC-16:19 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 32543.61 | 19-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 735.19 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5067.26 | |||||
Maximum of Months | 9454.80 | 735.19 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5461.43 | 34550.28 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 919.59 | 02-JAN-10:09 | 7748.81 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1380.14 | 04-JAN-03:00 |
February | 677.52 | 04-FEB-19:10 | 919.59 | 01-FEB-10:09 | 7748.81 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1351.95 | 13-FEB-03:51 |
March | 677.52 | 04-MAR-19:10 | 919.59 | 01-MAR-10:09 | 7748.81 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1006.43 | 17-MAR-04:00 |
April | 677.52 | 01-APR-18:10 | 919.59 | 01-APR-16:10 | 7748.81 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 5.31 | 23-APR-15:55 | 803.26 | 02-APR-04:00 |
May | 677.52 | 06-MAY-18:10 | 919.59 | 01-MAY-09:09 | 7748.81 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 7.78 | 24-MAY-15:00 | 460.46 | 09-MAY-03:40 |
June | 677.52 | 03-JUN-18:10 | 919.59 | 01-JUN-09:09 | 7748.81 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 44.30 | 29-JUN-15:10 | 419.89 | 20-JUN-04:00 |
July | 677.52 | 01-JUL-18:10 | 919.59 | 01-JUL-16:10 | 7748.81 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 33.81 | 15-JUL-15:00 | 322.67 | 06-JUL-04:00 |
August | 677.52 | 05-AUG-18:10 | 919.59 | 01-AUG-09:09 | 7748.81 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 26.10 | 08-AUG-16:00 | 351.09 | 17-AUG-02:00 |
September | 677.52 | 02-SEP-18:10 | 919.59 | 01-SEP-09:09 | 7748.81 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 592.19 | 20-SEP-04:00 |
October | 677.52 | 07-OCT-18:10 | 919.59 | 02-OCT-09:09 | 7748.81 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 666.56 | 31-OCT-03:40 |
November | 677.52 | 04-NOV-18:10 | 919.59 | 01-NOV-09:09 | 7748.81 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1157.86 | 22-NOV-02:00 |
December | 677.52 | 02-DEC-19:10 | 919.59 | 01-DEC-10:09 | 7748.81 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1212.44 | 16-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 919.59 | 7748.81 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 322.67 | ||||||
Maximum of Months | 677.52 | 919.59 | 7748.81 | 7998.14 | 0.00 | 0.00 | 0.00 | 44.30 | 1380.14 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586.79 | 28-JAN-02:40 | 1499.39 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 612.96 | 17-FEB-07:53 | 1694.99 | 13-FEB-13:30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.20 | 28-MAR-23:00 | 2710.92 | 23-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 673.22 | 22-APR-03:55 | 2249.91 | 04-APR-13:30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 600.48 | 18-MAY-04:55 | 2657.59 | 01-MAY-13:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.04 | 04-JUN-03:53 | 2356.92 | 14-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 646.09 | 15-JUL-04:53 | 2512.39 | 13-JUL-12:30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 655.52 | 05-AUG-03:45 | 2231.82 | 05-AUG-13:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.54 | 06-SEP-05:30 | 1821.77 | 06-SEP-12:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.35 | 25-OCT-07:00 | 1762.75 | 09-OCT-12:30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561.98 | 19-NOV-07:20 | 1105.95 | 10-NOV-12:50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.27 | 03-DEC-01:45 | 1199.89 | 26-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.27 | 1105.95 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 673.22 | 2710.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 38237.54 | 06-JAN-04:31 | 0.00 | 1225.31 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.67 |
February | 32706.75 | 14-FEB-04:36 | 0.00 | 1225.31 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.31 |
March | 26943.19 | 05-MAR-04:47 | 0.00 | 1225.31 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.40 |
April | 13046.67 | 04-APR-23:01 | 5252.67 | 1225.31 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.83 |
May | 13851.73 | 26-MAY-03:21 | 0.00 | 857.72 | 4725.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.69 |
June | 15079.57 | 29-JUN-17:10 | 25212.80 | 1235.12 | 9757.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5461.20 | 0.00 |
July | 14296.41 | 22-JUL-02:62 | 0.00 | 735.19 | 1620.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.75 |
August | 14851.90 | 09-AUG-02:62 | 0.00 | 735.19 | 1620.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.42 |
September | 13658.22 | 01-SEP-03:21 | 0.00 | 980.25 | 5400.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.73 |
October | 11911.40 | 29-OCT-23:01 | 5252.67 | 1225.31 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15160.95 | 25-NOV-00:01 | 5252.67 | 1633.75 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.58 |
December | 30640.56 | 24-DEC-04:41 | 0.00 | 1225.31 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 581.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11911.40 | 0.00 | 735.19 | 1620.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38237.54 | 25212.80 | 1633.75 | 9757.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5461.20 | 581.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 71208.56 | 06-JAN-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 147.86 |
February | 68154.40 | 14-FEB-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 167.17 |
March | 61878.82 | 05-MAR-05:01 | 0.00 | 1532.59 | 39979.31 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43739.96 | 05-APR-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 69.42 |
May | 55896.47 | 05-MAY-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 |
June | 47116.98 | 02-JUN-03:31 | 0.00 | 1379.33 | 22172.05 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 166.31 |
July | 42714.79 | 18-JUL-03:31 | 0.00 | 1379.33 | 22172.05 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43536.36 | 25-AUG-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49822.02 | 15-SEP-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 34.82 |
October | 45353.34 | 20-OCT-03:31 | 0.00 | 1379.33 | 22172.05 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 114.46 |
November | 53214.47 | 29-NOV-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 63.84 |
December | 64563.72 | 24-DEC-05:01 | 0.00 | 1532.59 | 39979.31 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 150.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 42714.79 | 0.00 | 1379.33 | 22172.05 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71208.56 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 167.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.65 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.68 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.88 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.73 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.26 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.28 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.21 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.98 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.85 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.26 | 1.60 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.427849E+11 | 24179.65 | 05-JAN-11:09 | 0.247009E+12 | 174166.63 | 04-JAN-13:09 |
February | 0.381463E+11 | 24059.85 | 13-FEB-11:09 | 0.189978E+12 | 155572.09 | 14-FEB-07:10 |
March | 0.416300E+11 | 23956.08 | 15-MAR-10:09 | 0.174943E+12 | 146962.57 | 05-MAR-07:10 |
April | 0.397170E+11 | 24918.30 | 23-APR-16:10 | 0.106434E+12 | 101146.38 | 04-APR-10:20 |
May | 0.430185E+11 | 30191.78 | 26-MAY-10:00 | 0.697789E+11 | 68985.16 | 01-MAY-06:10 |
June | 0.454882E+11 | 37220.27 | 30-JUN-11:20 | 0.596941E+11 | 51891.58 | 09-JUN-10:20 |
July | 0.497797E+11 | 34746.80 | 21-JUL-11:09 | 0.597437E+11 | 50528.64 | 02-JUL-10:50 |
August | 0.470090E+11 | 33515.59 | 08-AUG-11:09 | 0.595496E+11 | 51225.07 | 17-AUG-12:30 |
September | 0.409071E+11 | 29909.03 | 01-SEP-10:00 | 0.634057E+11 | 58510.02 | 27-SEP-10:20 |
October | 0.417186E+11 | 23692.10 | 30-OCT-10:09 | 0.946328E+11 | 86978.29 | 30-OCT-07:10 |
November | 0.407897E+11 | 23848.08 | 28-NOV-11:09 | 0.138999E+12 | 125205.25 | 25-NOV-11:09 |
December | 0.428341E+11 | 24086.39 | 20-DEC-11:09 | 0.232203E+12 | 158822.19 | 24-DEC-11:20 |
Annual Sum or Average | 0.513823E+12 | 0.149637E+13 | ||||
Minimum of Months | 0.381463E+11 | 23692.10 | 0.595496E+11 | 50528.64 | ||
Maximum of Months | 0.497797E+11 | 37220.27 | 0.247009E+12 | 174166.63 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.257334E+10 | 0.308349E+10 | 0.234911E+11 | 0.00 | 0.864801E+10 | 0.79 | 0.00 | 152781.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229183E+10 | 0.249797E+10 | 0.212178E+11 | 0.00 | 0.762515E+10 | 0.72 | 0.00 | 165987.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252203E+10 | 0.237593E+10 | 0.234913E+11 | 0.00 | 0.821832E+10 | 0.80 | 0.00 | 216163.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237511E+10 | 0.190737E+10 | 0.227333E+11 | 0.00 | 0.761806E+10 | 0.77 | 0.00 | 0.133136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.242127E+10 | 0.165439E+10 | 0.234912E+11 | 0.00 | 0.789586E+10 | 0.80 | 0.00 | 0.211701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.234136E+10 | 0.144130E+10 | 0.227335E+11 | 0.00 | 0.775160E+10 | 0.77 | 0.00 | 0.573737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.238694E+10 | 0.155353E+10 | 0.234911E+11 | 0.00 | 0.806078E+10 | 0.79 | 0.00 | 0.855214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.246629E+10 | 0.181558E+10 | 0.234913E+11 | 0.00 | 0.802162E+10 | 0.80 | 0.00 | 0.550088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.239204E+10 | 0.212771E+10 | 0.227333E+11 | 0.00 | 0.766835E+10 | 0.77 | 0.00 | 0.712178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.250694E+10 | 0.260485E+10 | 0.234911E+11 | 0.00 | 0.789191E+10 | 0.79 | 0.00 | 62930841.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.248217E+10 | 0.287689E+10 | 0.227334E+11 | 0.00 | 0.780980E+10 | 0.77 | 0.00 | 1072039.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.257931E+10 | 0.317775E+10 | 0.234911E+11 | 0.00 | 0.858913E+10 | 0.79 | 0.00 | 192323.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293386E+11 | 0.271168E+11 | 0.276589E+12 | 0.00 | 0.957986E+11 | 9.37 | 0.00 | 0.228174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.229183E+10 | 0.144130E+10 | 0.212178E+11 | 0.00 | 0.761806E+10 | 0.72 | 0.00 | 152781.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.257931E+10 | 0.317775E+10 | 0.234913E+11 | 0.00 | 0.864801E+10 | 0.80 | 0.00 | 0.855214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.184097E+12 | 0.00 | 0.223863E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.132750E+12 | 0.00 | 0.206238E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.111620E+12 | 0.00 | 0.227971E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.458051E+11 | 0.00 | 0.214101E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.814611E+10 | 0.00 | 0.211070E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.112946E+10 | 0.00 | 0.193462E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 0.191246E+09 | 0.00 | 0.190267E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 0.418713E+09 | 0.00 | 0.186052E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.608422E+10 | 0.00 | 0.181030E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.347114E+11 | 0.00 | 0.193957E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.800381E+11 | 0.00 | 0.197425E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.170215E+12 | 0.00 | 0.214616E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.775207E+12 | 0.00 | 0.244005E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.191246E+09 | 0.00 | 0.181030E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.184097E+12 | 0.00 | 0.227971E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1654.77 | 02-JAN-16:30 | 2040.24 | 01-JAN-00:10 | 14413.88 | 01-JAN-11:09 | 0.00 | 4252.80 | 04-JAN-20:00 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 1654.77 | 01-FEB-17:10 | 2040.24 | 01-FEB-00:10 | 14413.88 | 01-FEB-11:09 | 0.00 | 4143.41 | 01-FEB-20:00 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 1654.77 | 01-MAR-17:30 | 2040.24 | 01-MAR-00:10 | 14413.88 | 01-MAR-11:09 | 0.00 | 4104.51 | 05-MAR-07:10 | 0.00 | 05-MAR-09:39 | 0.00 | 01-MAR-00:10 |
April | 1654.77 | 01-APR-18:19 | 2040.24 | 01-APR-05:10 | 14413.88 | 01-APR-10:09 | 0.00 | 3789.26 | 05-APR-06:10 | 0.00 | 01-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 1654.77 | 01-MAY-19:30 | 2040.24 | 01-MAY-19:30 | 14413.88 | 01-MAY-10:09 | 0.00 | 3627.20 | 01-MAY-06:10 | 0.00 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 1654.77 | 01-JUN-19:00 | 2040.24 | 01-JUN-19:00 | 14413.88 | 01-JUN-10:09 | 0.00 | 4015.35 | 29-JUN-17:00 | 0.00 | 12-JUN-13:50 | 0.00 | 01-JUN-00:10 |
July | 1654.77 | 01-JUL-20:19 | 2040.24 | 01-JUL-20:19 | 14413.88 | 01-JUL-10:09 | 0.00 | 3649.12 | 15-JUL-13:00 | 0.00 | 03-JUL-12:30 | 0.00 | 01-JUL-00:10 |
August | 1654.77 | 01-AUG-19:40 | 2040.24 | 01-AUG-19:49 | 14413.88 | 01-AUG-10:09 | 0.00 | 3732.56 | 08-AUG-17:10 | 0.00 | 15-AUG-14:50 | 0.00 | 01-AUG-00:10 |
September | 1654.77 | 01-SEP-18:49 | 2040.24 | 01-SEP-05:10 | 14413.88 | 01-SEP-10:09 | 0.00 | 3510.90 | 23-SEP-06:00 | 0.00 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 1654.77 | 02-OCT-17:30 | 2040.24 | 01-OCT-05:10 | 14413.88 | 01-OCT-10:09 | 0.00 | 3722.33 | 30-OCT-06:10 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 1654.77 | 01-NOV-16:49 | 2040.24 | 01-NOV-05:10 | 14413.88 | 01-NOV-10:09 | 0.00 | 3956.40 | 25-NOV-19:10 | 0.00 | 09-NOV-10:09 | 0.00 | 01-NOV-00:10 |
December | 1654.77 | 01-DEC-16:19 | 2040.24 | 01-DEC-00:10 | 14413.88 | 01-DEC-11:09 | 0.00 | 4192.24 | 19-DEC-20:00 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1654.77 | 2040.24 | 14413.88 | 0.00 | 3510.90 | 0.00 | 0.00 | ||||||
Maximum of Months | 1654.77 | 2040.24 | 14413.88 | 0.00 | 4252.80 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 81.05 | 20-JAN-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 65.99 | 07-FEB-04:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 139.10 | 31-MAR-03:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5652.21 | 23-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9393.85 | 25-MAY-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16324.80 | 29-JUN-17:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14258.98 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13507.23 | 08-AUG-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8315.82 | 01-SEP-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2881.22 | 19-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 293.51 | 21-NOV-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 129.92 | 29-DEC-04:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 65.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16324.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 24179.65 | 05-JAN-11:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 4067.48 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24059.85 | 13-FEB-11:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3947.68 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23956.08 | 15-MAR-10:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3843.91 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24918.30 | 23-APR-16:10 | 887.53 | 13064.26 | 0.00 | 0.00 | 3337.51 | 0.00 | 0.00 | 5652.21 | 0.00 |
May | 30191.78 | 26-MAY-10:00 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3337.51 | 0.00 | 0.00 | 8177.04 | 0.00 |
June | 37220.27 | 30-JUN-11:20 | 1331.29 | 13514.13 | 0.00 | 0.00 | 3920.46 | 0.00 | 0.00 | 15495.03 | 0.00 |
July | 34746.80 | 21-JUL-11:09 | 1331.29 | 13514.13 | 0.00 | 0.00 | 3549.93 | 0.00 | 0.00 | 13415.71 | 0.00 |
August | 33515.59 | 08-AUG-11:09 | 1331.29 | 13514.13 | 0.00 | 0.00 | 3478.25 | 0.00 | 0.00 | 12257.09 | 0.00 |
September | 29909.03 | 01-SEP-10:00 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3337.51 | 0.00 | 0.00 | 7891.52 | 0.00 |
October | 23692.10 | 30-OCT-10:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3565.51 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23848.08 | 28-NOV-11:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3735.12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24086.39 | 20-DEC-11:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3974.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 23692.10 | 887.53 | 13064.26 | 0.00 | 0.00 | 3337.51 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37220.27 | 1331.29 | 14413.88 | 0.00 | 0.00 | 4067.48 | 0.00 | 0.00 | 15495.03 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 139809.13 | 06-JAN-07:10 | 0.00 | 31303.11 | 31-JAN-13:30 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 133673.84 | 14-FEB-07:10 | 0.00 | 32454.89 | 24-FEB-13:20 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 126202.48 | 05-MAR-07:10 | 0.00 | 32427.28 | 01-MAR-13:20 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 78096.35 | 05-APR-02:30 | 0.00 | 30205.50 | 02-APR-12:20 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 47105.79 | 01-MAY-06:10 | 0.00 | 28421.91 | 01-MAY-12:30 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 26614.95 | 04-JUN-04:00 | 0.00 | 27877.60 | 01-JUN-12:50 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 7635.18 | 02-JUL-04:00 | 0.00 | 27325.76 | 01-JUL-12:50 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 17546.49 | 19-AUG-05:10 | 0.00 | 26892.51 | 01-AUG-12:50 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 24900.67 | 06-SEP-06:10 | 0.00 | 26994.78 | 29-SEP-12:20 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 63507.85 | 30-OCT-06:10 | 0.00 | 27504.08 | 31-OCT-12:30 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 96280.63 | 25-NOV-07:10 | 0.00 | 28057.93 | 30-NOV-13:39 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 133788.18 | 24-DEC-07:10 | 0.00 | 28514.82 | 29-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 7635.18 | 0.00 | 26892.51 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 139809.13 | 0.00 | 32454.89 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
February | 24.67 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
March | 23.67 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 |
April | 9.33 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 |
May | 0.67 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.63 | 0.00 | 24.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 24.53 | 0.00 | 24.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 24.54 | 0.00 | 24.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.53 | 0.00 | 24.53 |
October | 1.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
November | 10.00 | 19.93 | 0.17 | 19.94 | 0.00 | 19.94 | 0.00 | 19.94 |
December | 29.83 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
Annual Sum or Average | 128.17 | 19.37 | 0.17 | 19.37 | 19.17 | 20.05 | 0.00 | 20.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.11 | 0.00 | 19.11 |
Maximum of Months | 29.83 | 20.44 | 0.17 | 20.44 | 8.17 | 24.63 | 0.00 | 24.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.76 | 0.00 | 26.76 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.81 | 0.00 | 26.81 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.87 | 0.00 | 26.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.32 | 0.00 | 27.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 27.95 | 0.00 | 27.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 28.10 | 4.33 | 27.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.67 | 28.57 | 1.67 | 28.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 28.62 | 0.00 | 28.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 27.94 | 0.00 | 27.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.34 | 0.00 | 27.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.03 | 0.00 | 27.03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.90 | 0.00 | 26.90 |
Annual Sum or Average | 0.00 | 0.00 | 157.83 | 28.14 | 6.00 | 28.10 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.76 | 0.00 | 26.76 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.67 | 28.62 | 4.33 | 28.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.84 | 551.83 | 20.82 | 551.83 | 20.82 |
February | 551.00 | 20.84 | 395.00 | 20.79 | 395.00 | 20.77 |
March | 612.00 | 20.84 | 367.50 | 20.78 | 367.50 | 20.75 |
April | 559.83 | 21.00 | 166.83 | 20.87 | 159.00 | 20.77 |
May | 394.50 | 21.38 | 171.83 | 21.92 | 28.50 | 21.80 |
June | 361.50 | 22.57 | 354.33 | 23.17 | 170.33 | 23.28 |
July | 311.83 | 23.15 | 492.33 | 23.58 | 214.00 | 23.64 |
August | 339.17 | 22.89 | 441.17 | 23.40 | 192.67 | 23.48 |
September | 415.67 | 21.40 | 187.67 | 22.04 | 45.33 | 22.05 |
October | 571.17 | 20.96 | 85.33 | 20.93 | 58.00 | 20.79 |
November | 591.00 | 20.88 | 233.00 | 20.76 | 233.00 | 20.70 |
December | 609.00 | 20.84 | 543.33 | 20.82 | 543.33 | 20.81 |
Annual Sum or Average | 5926.67 | 21.29 | 3990.17 | 21.55 | 2958.50 | 21.49 |
Minimum of Months | 311.83 | 20.84 | 85.33 | 20.76 | 28.50 | 20.70 |
Maximum of Months | 612.00 | 23.15 | 551.83 | 23.58 | 551.83 | 23.64 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 18.72 | 567.00 | 18.72 | 567.00 | 18.71 |
February | 551.00 | 18.72 | 475.83 | 18.71 | 475.83 | 18.71 |
March | 612.00 | 18.73 | 482.83 | 18.71 | 482.83 | 18.70 |
April | 533.00 | 19.06 | 299.83 | 19.21 | 265.17 | 19.10 |
May | 416.00 | 21.96 | 342.83 | 23.08 | 190.83 | 23.32 |
June | 452.33 | 24.89 | 477.33 | 25.19 | 365.67 | 25.40 |
July | 505.00 | 25.69 | 568.83 | 25.66 | 474.50 | 25.77 |
August | 454.33 | 25.52 | 565.83 | 25.39 | 423.33 | 25.54 |
September | 411.33 | 21.75 | 304.17 | 22.89 | 157.67 | 23.27 |
October | 558.50 | 19.10 | 167.67 | 19.35 | 128.67 | 19.28 |
November | 578.50 | 18.79 | 314.17 | 18.78 | 304.83 | 18.74 |
December | 609.00 | 18.72 | 543.00 | 18.71 | 543.00 | 18.71 |
Annual Sum or Average | 6291.00 | 20.70 | 5109.33 | 21.13 | 4379.33 | 21.17 |
Minimum of Months | 411.33 | 18.72 | 167.67 | 18.71 | 128.67 | 18.70 |
Maximum of Months | 612.00 | 25.69 | 568.83 | 25.66 | 567.00 | 25.77 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.83529 | 11.84874 | -0.7323 | 17.23363 |
February | 551.00000 | 20.83688 | 13.77352 | -0.6639 | 15.43760 |
March | 612.00000 | 20.84391 | 17.79979 | -0.6188 | 14.21008 |
April | 590.00000 | 21.14536 | 23.44708 | -0.4308 | 10.99951 |
May | 611.00000 | 22.25374 | 36.81853 | -1.0154 | 31.38647 |
June | 592.00000 | 23.05829 | 53.05875 | -0.5871 | 16.53350 |
July | 609.00000 | 23.46541 | 59.44217 | -0.3451 | 9.97667 |
August | 612.00000 | 23.27084 | 57.90886 | -0.4284 | 11.84796 |
September | 590.00000 | 22.08812 | 46.57925 | -0.9506 | 28.38511 |
October | 610.00000 | 21.13323 | 33.53185 | -0.3166 | 8.87739 |
November | 591.00000 | 20.88172 | 22.20862 | -0.5320 | 12.12878 |
December | 609.00000 | 20.83560 | 13.26458 | -0.7111 | 16.55735 |
Annual Sum or Average | 7187.00000 | 21.72754 | 32.59096 | -0.6104 | 16.12781 |
Minimum of Months | 551.00000 | 20.83529 | 11.84874 | -1.0154 | 8.87739 |
Maximum of Months | 612.00000 | 23.46541 | 59.44217 | -0.3166 | 31.38647 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.72364 | 16.98875 | -0.8050 | 19.30389 |
February | 551.00000 | 18.72418 | 19.44635 | -0.7764 | 18.39296 |
March | 612.00000 | 18.72972 | 23.94529 | -0.7442 | 17.36023 |
April | 590.00000 | 19.58135 | 29.19959 | -0.4875 | 14.34976 |
May | 611.00000 | 22.66324 | 38.47298 | -0.5777 | 28.49219 |
June | 592.00000 | 24.61336 | 50.71261 | 0.17132 | 16.13908 |
July | 609.00000 | 25.32065 | 55.72035 | 0.48783 | 15.59961 |
August | 612.00000 | 24.95820 | 54.34605 | 0.36086 | 14.32185 |
September | 590.00000 | 22.28688 | 47.90528 | -0.5764 | 26.61961 |
October | 610.00000 | 19.50713 | 39.32973 | -0.3836 | 12.04274 |
November | 591.00000 | 18.89843 | 27.70433 | -0.6250 | 14.78450 |
December | 609.00000 | 18.72394 | 18.34257 | -0.7772 | 18.37139 |
Annual Sum or Average | 7187.00000 | 21.07799 | 35.26949 | -0.3913 | 17.97779 |
Minimum of Months | 551.00000 | 18.72364 | 16.98875 | -0.8050 | 12.04274 |
Maximum of Months | 612.00000 | 25.32065 | 55.72035 | 0.48783 | 28.49219 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.239942E+09 | 66493934.54 | 12.00 | 0.193663E+09 | 46278516.94 | 0.00 | 0.63 | 23-APR-17:10 | 0.00 | 01-APR-00:01 | 10858.78 | 23-APR-17:10 | 8680.11 | 23-APR-17:03 | 2199.45 | 23-APR-17:20 | 2894.66 | 23-APR-17:10 | 0.00 | 01-APR-00:01 |
May | 0.374072E+10 | 0.100449E+10 | 151.85 | 0.297891E+10 | 0.761817E+09 | 0.00 | 1.00 | 25-MAY-17:03 | 0.00 | 01-MAY-00:01 | 20395.21 | 25-MAY-17:43 | 15303.57 | 25-MAY-17:57 | 7360.05 | 26-MAY-00:42 | 4840.41 | 25-MAY-17:53 | 0.00 | 01-MAY-00:01 |
June | 0.100329E+11 | 0.255144E+10 | 282.84 | 0.648061E+10 | 0.355228E+10 | 0.00 | 1.00 | 19-JUN-00:31 | 0.00 | 01-JUN-00:01 | 40371.53 | 29-JUN-03:47 | 22712.41 | 29-JUN-00:09 | 19054.33 | 29-JUN-03:47 | 9368.21 | 29-JUN-03:47 | 0.00 | 01-JUN-00:01 |
July | 0.152168E+11 | 0.379326E+10 | 392.37 | 0.918719E+10 | 0.602956E+10 | 0.00 | 1.00 | 03-JUL-16:05 | 0.00 | 01-JUL-00:01 | 42858.97 | 04-JUL-00:09 | 18821.13 | 22-JUL-02:62 | 27217.65 | 04-JUL-00:09 | 9539.50 | 04-JUL-00:09 | 0.00 | 01-JUL-00:01 |
August | 0.961188E+10 | 0.247456E+10 | 301.42 | 0.599027E+10 | 0.362160E+10 | 0.00 | 1.00 | 01-AUG-03:21 | 0.00 | 01-AUG-00:01 | 39984.10 | 09-AUG-00:42 | 20887.53 | 09-AUG-00:42 | 20286.58 | 09-AUG-03:22 | 9342.55 | 09-AUG-00:42 | 0.00 | 01-AUG-00:01 |
September | 0.123867E+10 | 0.342728E+09 | 84.19 | 0.916157E+09 | 0.322515E+09 | 0.00 | 1.00 | 01-SEP-00:42 | 0.00 | 01-SEP-00:01 | 20136.05 | 01-SEP-00:42 | 11480.92 | 01-SEP-16:05 | 11295.78 | 01-SEP-00:42 | 4680.62 | 01-SEP-00:42 | 0.00 | 01-SEP-00:01 |
October | 0.128939E+09 | 38205050.81 | 16.67 | 0.110027E+09 | 18912064.87 | 0.00 | 0.33 | 19-OCT-15:10 | 0.00 | 01-OCT-00:01 | 5340.43 | 19-OCT-15:10 | 4628.64 | 19-OCT-15:10 | 891.66 | 19-OCT-13:00 | 1535.52 | 19-OCT-15:10 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.402098E+11 | 0.102712E+11 | 1241.33 | 0.258568E+11 | 0.143530E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.152168E+11 | 0.379326E+10 | 392.37 | 0.918719E+10 | 0.602956E+10 | 0.00 | 1.00 | 0.00 | 42858.97 | 22712.41 | 27217.65 | 9539.50 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 501913.01 | 152781.42 | 0.30 | 399660.11 | 102252.89 | 0.00 | 0.08 | 03-JAN-04:56 | 0.00 | 01-JAN-00:01 | 957.04 | 03-JAN-04:56 | 819.80 | 03-JAN-04:56 | 223.98 | 17-JAN-04:15 | 290.59 | 03-JAN-04:56 | 0.00 | 01-JAN-00:01 |
February | 544162.95 | 165987.96 | 0.28 | 450837.25 | 93325.70 | 0.00 | 0.08 | 28-FEB-04:40 | 0.00 | 01-FEB-00:01 | 942.81 | 28-FEB-04:40 | 855.69 | 28-FEB-04:40 | 159.29 | 07-FEB-04:15 | 286.34 | 28-FEB-04:40 | 0.00 | 01-FEB-00:01 |
March | 707568.14 | 216163.94 | 0.39 | 529431.71 | 178136.43 | 0.00 | 0.09 | 31-MAR-03:27 | 0.00 | 01-MAR-00:01 | 1066.86 | 31-MAR-03:27 | 816.15 | 31-MAR-03:27 | 250.71 | 31-MAR-03:27 | 323.28 | 31-MAR-03:27 | 0.00 | 01-MAR-00:01 |
April | 0.250019E+09 | 66642543.51 | 10.92 | 0.217496E+09 | 32523257.69 | 0.00 | 0.76 | 23-APR-16:00 | 0.00 | 01-APR-00:01 | 11218.29 | 23-APR-16:00 | 10157.59 | 23-APR-15:55 | 2004.59 | 24-APR-00:14 | 2861.94 | 23-APR-16:00 | 0.00 | 01-APR-00:01 |
May | 0.436273E+10 | 0.111252E+10 | 154.16 | 0.369555E+10 | 0.667183E+09 | 0.00 | 1.00 | 05-MAY-04:01 | 0.00 | 01-MAY-00:01 | 31313.45 | 25-MAY-00:42 | 26125.69 | 05-MAY-04:01 | 16229.84 | 27-MAY-02:42 | 7507.37 | 05-MAY-04:01 | 0.00 | 01-MAY-00:01 |
June | 0.132420E+11 | 0.318593E+10 | 301.48 | 0.852100E+10 | 0.472103E+10 | 0.00 | 1.00 | 02-JUN-03:31 | 0.00 | 01-JUN-00:01 | 34791.30 | 30-JUN-02:62 | 25233.13 | 29-JUN-16:35 | 20917.66 | 30-JUN-02:51 | 8400.72 | 29-JUN-16:00 | 0.00 | 01-JUN-00:01 |
July | 0.201574E+11 | 0.475888E+10 | 397.92 | 0.120164E+11 | 0.814105E+10 | 0.00 | 1.00 | 01-JUL-00:42 | 0.00 | 01-JUL-00:01 | 34791.30 | 15-JUL-13:00 | 20367.69 | 23-JUL-13:00 | 23450.83 | 04-JUL-00:55 | 7939.82 | 15-JUL-13:53 | 0.00 | 01-JUL-00:01 |
August | 0.124074E+11 | 0.302632E+10 | 311.59 | 0.763725E+10 | 0.477013E+10 | 0.00 | 1.00 | 01-AUG-00:42 | 0.00 | 01-AUG-00:01 | 32504.49 | 08-AUG-14:10 | 20002.57 | 08-AUG-14:10 | 19495.82 | 01-AUG-02:42 | 7578.81 | 09-AUG-02:42 | 0.00 | 01-AUG-00:01 |
September | 0.139584E+10 | 0.369451E+09 | 87.33 | 0.100231E+10 | 0.393534E+09 | 0.00 | 1.00 | 01-SEP-00:03 | 0.00 | 01-SEP-00:01 | 32479.72 | 01-SEP-00:42 | 19888.75 | 15-SEP-04:01 | 20023.87 | 01-SEP-01:22 | 7585.40 | 01-SEP-00:42 | 0.00 | 01-SEP-00:01 |
October | 84663041.60 | 24725791.18 | 14.97 | 70157698.18 | 14505343.42 | 0.00 | 1.00 | 20-OCT-03:31 | 0.00 | 01-OCT-00:01 | 31313.45 | 20-OCT-03:31 | 17738.34 | 20-OCT-03:31 | 13575.11 | 20-OCT-03:31 | 7507.37 | 20-OCT-03:31 | 0.00 | 01-OCT-00:01 |
November | 3592149.31 | 1072039.86 | 1.34 | 2558359.01 | 1033790.30 | 0.00 | 0.31 | 21-NOV-04:05 | 0.00 | 01-NOV-00:01 | 4090.29 | 21-NOV-04:05 | 2070.27 | 21-NOV-04:05 | 2020.02 | 21-NOV-04:05 | 1174.04 | 21-NOV-04:05 | 0.00 | 01-NOV-00:01 |
December | 631233.11 | 192323.45 | 0.39 | 573282.47 | 57950.64 | 0.00 | 0.12 | 01-DEC-04:40 | 0.00 | 01-DEC-00:01 | 1450.08 | 01-DEC-04:40 | 1313.40 | 01-DEC-04:40 | 136.68 | 01-DEC-04:40 | 436.32 | 01-DEC-04:40 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.519061E+11 | 0.125463E+11 | 1281.08 | 0.331646E+11 | 0.187414E+11 | 0.00 | ||||||||||||||
Minimum of Months | 501913.01 | 152781.42 | 0.28 | 399660.11 | 57950.64 | 0.00 | 0.08 | 0.00 | 942.81 | 816.15 | 136.68 | 286.34 | 0.00 | |||||||
Maximum of Months | 0.201574E+11 | 0.475888E+10 | 397.92 | 0.120164E+11 | 0.814105E+10 | 0.00 | 1.00 | 0.00 | 34791.30 | 26125.69 | 23450.83 | 8400.72 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.46 | 35.25 | 49.20 | 25.52 | 373.43 | 0.00 | 0.00 | 0.00 |
February | 132.71 | 56.61 | 76.10 | 68.91 | 294.11 | 0.00 | 0.00 | 0.00 |
March | 180.83 | 90.71 | 90.12 | 129.36 | 227.10 | 0.00 | 0.00 | 0.00 |
April | 250.68 | 135.21 | 115.47 | 237.17 | 133.31 | 0.00 | 0.00 | 0.00 |
May | 271.31 | 119.27 | 152.04 | 299.26 | 71.20 | 0.00 | 0.00 | 0.00 |
June | 307.15 | 146.92 | 160.22 | 369.87 | 50.71 | 0.00 | 0.00 | 0.00 |
July | 300.89 | 141.28 | 159.61 | 370.51 | 48.31 | 0.00 | 0.00 | 0.00 |
August | 231.99 | 101.39 | 130.59 | 271.67 | 57.97 | 0.00 | 0.00 | 0.00 |
September | 185.78 | 83.16 | 102.63 | 191.44 | 88.58 | 0.00 | 0.00 | 0.00 |
October | 112.49 | 42.66 | 69.84 | 81.66 | 141.54 | 0.00 | 0.00 | 0.00 |
November | 71.61 | 23.94 | 47.67 | 30.03 | 225.74 | 0.00 | 0.00 | 0.00 |
December | 65.35 | 24.15 | 41.19 | 15.54 | 363.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 183.12 | 83.45 | 99.67 | 174.75 | 172.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 65.35 | 23.94 | 41.19 | 15.54 | 48.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 307.15 | 146.92 | 160.22 | 370.51 | 373.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 530.54 | 369.08 | 161.45 | 415.92 | 651.55 | 0.00 | 0.00 | 0.00 |
February | 671.79 | 453.75 | 218.04 | 611.81 | 539.29 | 0.00 | 0.00 | 0.00 |
March | 591.93 | 374.61 | 217.32 | 560.43 | 438.25 | 0.00 | 0.00 | 0.00 |
April | 536.27 | 291.07 | 245.20 | 564.60 | 281.41 | 0.00 | 0.00 | 0.00 |
May | 450.86 | 154.14 | 296.72 | 522.68 | 153.99 | 0.00 | 0.00 | 0.00 |
June | 404.55 | 107.83 | 296.72 | 498.72 | 107.30 | 0.00 | 0.00 | 0.00 |
July | 442.30 | 140.12 | 302.18 | 568.09 | 101.39 | 0.00 | 0.00 | 0.00 |
August | 472.35 | 197.58 | 274.77 | 585.04 | 120.43 | 0.00 | 0.00 | 0.00 |
September | 505.96 | 269.46 | 236.50 | 580.70 | 183.08 | 0.00 | 0.00 | 0.00 |
October | 432.05 | 254.11 | 177.94 | 432.10 | 278.14 | 0.00 | 0.00 | 0.00 |
November | 384.87 | 241.54 | 143.32 | 331.66 | 416.92 | 0.00 | 0.00 | 0.00 |
December | 409.64 | 268.60 | 141.03 | 293.12 | 634.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 484.87 | 258.93 | 225.95 | 496.17 | 324.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 384.87 | 107.83 | 141.03 | 293.12 | 101.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 671.79 | 453.75 | 302.18 | 611.81 | 651.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.36 | 35.74 | 49.62 | 29.30 | 381.56 | 0.00 | 0.00 | 0.00 |
February | 139.08 | 63.52 | 75.55 | 82.30 | 304.76 | 0.00 | 0.00 | 0.00 |
March | 183.01 | 93.65 | 89.37 | 137.91 | 234.37 | 0.00 | 0.00 | 0.00 |
April | 233.79 | 118.41 | 115.38 | 219.43 | 139.92 | 0.00 | 0.00 | 0.00 |
May | 287.25 | 137.02 | 150.23 | 325.42 | 74.74 | 0.00 | 0.00 | 0.00 |
June | 277.19 | 119.85 | 157.34 | 332.12 | 52.18 | 0.00 | 0.00 | 0.00 |
July | 295.93 | 137.58 | 158.35 | 365.44 | 49.89 | 0.00 | 0.00 | 0.00 |
August | 243.53 | 110.66 | 132.87 | 288.85 | 59.36 | 0.00 | 0.00 | 0.00 |
September | 190.33 | 85.51 | 104.82 | 198.64 | 91.24 | 0.00 | 0.00 | 0.00 |
October | 120.23 | 48.27 | 71.96 | 94.06 | 145.14 | 0.00 | 0.00 | 0.00 |
November | 73.02 | 24.62 | 48.40 | 32.46 | 230.47 | 0.00 | 0.00 | 0.00 |
December | 65.10 | 22.78 | 42.31 | 15.54 | 369.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 183.06 | 83.25 | 99.81 | 177.36 | 177.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 65.10 | 22.78 | 42.31 | 15.54 | 49.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 295.93 | 137.58 | 158.35 | 365.44 | 381.56 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226204E+09 | 94424645.84 | 0.131780E+09 | 68365969.59 | 0.100019E+10 |
February | 0.321061E+09 | 0.136950E+09 | 0.184111E+09 | 0.166718E+09 | 0.711521E+09 |
March | 0.484337E+09 | 0.242950E+09 | 0.241387E+09 | 0.346474E+09 | 0.608256E+09 |
April | 0.649773E+09 | 0.350474E+09 | 0.299299E+09 | 0.614743E+09 | 0.345530E+09 |
May | 0.726686E+09 | 0.319459E+09 | 0.407227E+09 | 0.801544E+09 | 0.190690E+09 |
June | 0.796122E+09 | 0.380829E+09 | 0.415293E+09 | 0.958706E+09 | 0.131448E+09 |
July | 0.805903E+09 | 0.378401E+09 | 0.427503E+09 | 0.992374E+09 | 0.129383E+09 |
August | 0.621353E+09 | 0.271574E+09 | 0.349779E+09 | 0.727634E+09 | 0.155260E+09 |
September | 0.481548E+09 | 0.215538E+09 | 0.266010E+09 | 0.496217E+09 | 0.229610E+09 |
October | 0.301305E+09 | 0.114254E+09 | 0.187051E+09 | 0.218713E+09 | 0.379092E+09 |
November | 0.185626E+09 | 62058854.13 | 0.123567E+09 | 77849724.04 | 0.585119E+09 |
December | 0.175028E+09 | 64692994.07 | 0.110335E+09 | 41621707.55 | 0.972573E+09 |
Annual Sum or Average | 0.577495E+10 | 0.263161E+10 | 0.314334E+10 | 0.551096E+10 | 0.543867E+10 |
Minimum of Months | 0.175028E+09 | 62058854.13 | 0.110335E+09 | 41621707.55 | 0.129383E+09 |
Maximum of Months | 0.805903E+09 | 0.380829E+09 | 0.427503E+09 | 0.992374E+09 | 0.100019E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.142099E+10 | 0.988552E+09 | 0.432440E+09 | 0.111401E+10 | 0.174511E+10 |
February | 0.162519E+10 | 0.109771E+10 | 0.527481E+09 | 0.148010E+10 | 0.130465E+10 |
March | 0.158542E+10 | 0.100335E+10 | 0.582070E+09 | 0.150106E+10 | 0.117380E+10 |
April | 0.139001E+10 | 0.754455E+09 | 0.635550E+09 | 0.146345E+10 | 0.729417E+09 |
May | 0.120758E+10 | 0.412843E+09 | 0.794741E+09 | 0.139996E+10 | 0.412440E+09 |
June | 0.104859E+10 | 0.279494E+09 | 0.769094E+09 | 0.129268E+10 | 0.278117E+09 |
July | 0.118466E+10 | 0.375294E+09 | 0.809368E+09 | 0.152158E+10 | 0.271568E+09 |
August | 0.126515E+10 | 0.529202E+09 | 0.735949E+09 | 0.156696E+10 | 0.322548E+09 |
September | 0.131145E+10 | 0.698445E+09 | 0.613005E+09 | 0.150517E+10 | 0.474535E+09 |
October | 0.115721E+10 | 0.680615E+09 | 0.476599E+09 | 0.115735E+10 | 0.744973E+09 |
November | 0.997571E+09 | 0.626076E+09 | 0.371494E+09 | 0.859658E+09 | 0.108066E+10 |
December | 0.109718E+10 | 0.719432E+09 | 0.377745E+09 | 0.785101E+09 | 0.170029E+10 |
Annual Sum or Average | 0.152910E+11 | 0.816547E+10 | 0.712554E+10 | 0.156471E+11 | 0.102381E+11 |
Minimum of Months | 0.997571E+09 | 0.279494E+09 | 0.371494E+09 | 0.785101E+09 | 0.271568E+09 |
Maximum of Months | 0.162519E+10 | 0.109771E+10 | 0.809368E+09 | 0.156696E+10 | 0.174511E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228626E+09 | 95734829.67 | 0.132891E+09 | 78485502.21 | 0.102196E+10 |
February | 0.336450E+09 | 0.153668E+09 | 0.182782E+09 | 0.199100E+09 | 0.737280E+09 |
March | 0.490179E+09 | 0.250821E+09 | 0.239358E+09 | 0.369369E+09 | 0.627727E+09 |
April | 0.605978E+09 | 0.306921E+09 | 0.299057E+09 | 0.568773E+09 | 0.362666E+09 |
May | 0.769370E+09 | 0.366993E+09 | 0.402378E+09 | 0.871594E+09 | 0.200189E+09 |
June | 0.718476E+09 | 0.310663E+09 | 0.407813E+09 | 0.860858E+09 | 0.135254E+09 |
July | 0.792611E+09 | 0.368481E+09 | 0.424129E+09 | 0.978793E+09 | 0.133637E+09 |
August | 0.652266E+09 | 0.296385E+09 | 0.355881E+09 | 0.773653E+09 | 0.158977E+09 |
September | 0.493326E+09 | 0.221644E+09 | 0.271682E+09 | 0.514876E+09 | 0.236504E+09 |
October | 0.322026E+09 | 0.129275E+09 | 0.192751E+09 | 0.251937E+09 | 0.388751E+09 |
November | 0.189273E+09 | 63815702.48 | 0.125458E+09 | 84143545.59 | 0.597388E+09 |
December | 0.174351E+09 | 61023947.18 | 0.113327E+09 | 41634133.66 | 0.990209E+09 |
Annual Sum or Average | 0.577293E+10 | 0.262543E+10 | 0.314751E+10 | 0.559322E+10 | 0.559054E+10 |
Minimum of Months | 0.174351E+09 | 61023947.18 | 0.113327E+09 | 41634133.66 | 0.133637E+09 |
Maximum of Months | 0.792611E+09 | 0.368481E+09 | 0.424129E+09 | 0.978793E+09 | 0.102196E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 391.86 | 1327.64 | 700.35 | 440.08 | 260.27 | 0.00 | 0.00 |
February | 708.67 | 1083.81 | 943.58 | 573.88 | 369.70 | 0.00 | 0.00 |
March | 785.52 | 857.54 | 955.77 | 558.96 | 396.81 | 0.00 | 0.00 |
April | 987.05 | 520.48 | 1020.74 | 544.70 | 476.04 | 0.00 | 0.00 |
May | 1128.88 | 281.44 | 1009.42 | 410.43 | 598.99 | 0.00 | 0.00 |
June | 1190.17 | 199.65 | 988.88 | 374.61 | 614.27 | 0.00 | 0.00 |
July | 1295.78 | 191.33 | 1039.12 | 418.97 | 620.15 | 0.00 | 0.00 |
August | 1139.66 | 231.86 | 947.87 | 409.63 | 538.23 | 0.00 | 0.00 |
September | 960.33 | 352.46 | 882.07 | 438.13 | 443.94 | 0.00 | 0.00 |
October | 597.88 | 554.87 | 664.78 | 345.04 | 319.74 | 0.00 | 0.00 |
November | 367.61 | 846.58 | 529.50 | 290.10 | 239.40 | 0.00 | 0.00 |
December | 260.95 | 1304.38 | 540.08 | 315.54 | 224.54 | 0.00 | 0.00 |
Annual Sum or Average | 818.12 | 644.23 | 851.06 | 425.62 | 425.43 | 0.00 | 0.00 |
Minimum of Months | 260.95 | 191.33 | 529.50 | 290.10 | 224.54 | 0.00 | 0.00 |
Maximum of Months | 1295.78 | 1327.64 | 1039.12 | 573.88 | 620.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104955E+10 | 0.355596E+10 | 0.187582E+10 | 0.117871E+10 | 0.697111E+09 | 0.00 | 0.00 |
February | 0.171442E+10 | 0.262196E+10 | 0.228270E+10 | 0.138833E+10 | 0.894374E+09 | 0.00 | 0.00 |
March | 0.210395E+10 | 0.229683E+10 | 0.255993E+10 | 0.149712E+10 | 0.106281E+10 | 0.00 | 0.00 |
April | 0.255844E+10 | 0.134908E+10 | 0.264576E+10 | 0.141185E+10 | 0.123391E+10 | 0.00 | 0.00 |
May | 0.302358E+10 | 0.753807E+09 | 0.270364E+10 | 0.109930E+10 | 0.160435E+10 | 0.00 | 0.00 |
June | 0.308492E+10 | 0.517487E+09 | 0.256319E+10 | 0.970986E+09 | 0.159220E+10 | 0.00 | 0.00 |
July | 0.347061E+10 | 0.512449E+09 | 0.278318E+10 | 0.112218E+10 | 0.166100E+10 | 0.00 | 0.00 |
August | 0.305247E+10 | 0.621004E+09 | 0.253877E+10 | 0.109716E+10 | 0.144161E+10 | 0.00 | 0.00 |
September | 0.248918E+10 | 0.913565E+09 | 0.228632E+10 | 0.113563E+10 | 0.115070E+10 | 0.00 | 0.00 |
October | 0.160136E+10 | 0.148617E+10 | 0.178055E+10 | 0.924144E+09 | 0.856401E+09 | 0.00 | 0.00 |
November | 0.952834E+09 | 0.219435E+10 | 0.137247E+10 | 0.751951E+09 | 0.620519E+09 | 0.00 | 0.00 |
December | 0.698940E+09 | 0.349365E+10 | 0.144656E+10 | 0.845149E+09 | 0.601407E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.258002E+11 | 0.203163E+11 | 0.268389E+11 | 0.134225E+11 | 0.134164E+11 | 0.00 | 0.00 |
Minimum of Months | 0.698940E+09 | 0.512449E+09 | 0.137247E+10 | 0.751951E+09 | 0.601407E+09 | 0.00 | 0.00 |
Maximum of Months | 0.347061E+10 | 0.355596E+10 | 0.278318E+10 | 0.149712E+10 | 0.166100E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.165304E+11 | -0.157294E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -800957081.3 | 59.00 | 0.00 | 0.00 |
February | 0.152577E+11 | -0.145348E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -722863070.0 | 58.99 | 0.00 | 0.00 |
March | 0.168592E+11 | -0.160605E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -798740020.4 | 58.99 | 0.00 | 0.00 |
April | 0.157904E+11 | -0.150341E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -756273190.5 | 58.99 | 0.00 | 0.00 |
May | 0.154945E+11 | -0.147696E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -724971340.1 | 58.99 | 0.00 | 0.00 |
June | 0.141225E+11 | -0.134540E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -668485677.1 | 58.99 | 0.00 | 0.00 |
July | 0.138140E+11 | -0.131361E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -677971389.8 | 58.99 | 0.00 | 0.00 |
August | 0.134737E+11 | -0.127893E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -684344597.5 | 58.99 | 0.00 | 0.00 |
September | 0.131196E+11 | -0.124128E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -706762765.0 | 58.99 | 0.00 | 0.00 |
October | 0.141108E+11 | -0.133309E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -779833403.8 | 58.99 | 0.00 | 0.00 |
November | 0.144451E+11 | -0.136777E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -767361615.7 | 58.99 | 0.00 | 0.00 |
December | 0.157810E+11 | -0.149812E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -799794001.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.178799E+12 | -0.169910E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.888836E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.131196E+11 | -0.160605E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -800957081.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.168592E+11 | -0.124128E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -668485677.1 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.58 | 0.56 | 01-JAN-08:39 | 1424.91 | 15.65 | 5.33 | 238.83 | 1424.08 | 15.71 | 5.83 | 239.00 |
February | 265.33 | 0.57 | 0.56 | 01-FEB-08:39 | 5752.79 | 27.80 | 158.17 | 262.33 | 5743.73 | 27.91 | 159.00 | 261.50 |
March | 254.17 | 0.57 | 0.56 | 02-MAR-10:39 | 9308.85 | 33.11 | 211.67 | 335.17 | 9135.69 | 31.56 | 191.67 | 334.33 |
April | 296.33 | 0.58 | 0.56 | 01-APR-07:10 | 2438.76 | 18.12 | 40.83 | 370.00 | 3403.36 | 18.14 | 39.17 | 367.33 |
May | 437.50 | 0.57 | 0.56 | 01-MAY-05:30 | 2773.92 | 16.39 | 0.00 | 432.83 | 2254.50 | 16.41 | 0.00 | 436.83 |
June | 401.83 | 0.57 | 0.56 | 01-JUN-04:00 | 2878.42 | 16.45 | 0.00 | 441.00 | 2832.99 | 16.43 | 0.00 | 436.33 |
July | 409.17 | 0.57 | 0.56 | 01-JUL-04:00 | 3102.32 | 16.67 | 0.00 | 443.83 | 2849.36 | 16.83 | 3.50 | 440.50 |
August | 352.83 | 0.57 | 0.56 | 01-AUG-07:40 | 3027.49 | 17.18 | 8.17 | 396.00 | 3079.68 | 18.73 | 40.67 | 396.33 |
September | 344.17 | 0.57 | 0.56 | 01-SEP-06:10 | 2899.95 | 20.20 | 78.67 | 346.67 | 2652.82 | 19.35 | 56.83 | 349.17 |
October | 299.00 | 0.57 | 0.56 | 01-OCT-06:40 | 4415.01 | 27.29 | 206.33 | 305.67 | 4731.60 | 28.83 | 227.67 | 305.50 |
November | 255.50 | 0.58 | 0.56 | 01-NOV-07:49 | 2257.34 | 22.07 | 98.33 | 243.83 | 2258.45 | 22.10 | 98.33 | 244.17 |
December | 226.33 | 0.57 | 0.56 | 01-DEC-08:30 | 1131.48 | 14.99 | 0.00 | 228.33 | 1127.28 | 15.04 | 0.00 | 226.67 |
Annual Sum or Average | 3785.50 | 0.57 | 3386.77 | 20.02 | 807.50 | 4044.50 | 3365.00 | 20.14 | 822.67 | 4037.67 | ||
Minimum of Months | 226.33 | 0.57 | 0.56 | 1131.48 | 14.99 | 0.00 | 228.33 | 1127.28 | 15.04 | 0.00 | 226.67 | |
Maximum of Months | 437.50 | 0.58 | 0.56 | 9308.85 | 33.11 | 211.67 | 443.83 | 9135.69 | 31.56 | 227.67 | 440.50 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.663613E+11 | 62477.08 | 01-JAN-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.488525E+11 | 62477.08 | 01-FEB-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.419052E+11 | 62477.08 | 03-MAR-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184817E+11 | 62477.08 | 05-APR-02:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.408711E+10 | 25707.48 | 01-MAY-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.694728E+09 | 9493.31 | 04-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145867E+09 | 4616.24 | 02-JUL-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.273489E+09 | 8126.74 | 19-AUG-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.352531E+10 | 14199.88 | 28-SEP-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152415E+11 | 31750.13 | 30-OCT-02:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.307952E+11 | 62477.08 | 24-NOV-03:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.623646E+11 | 62477.08 | 01-DEC-03:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.292728E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.145867E+09 | 4616.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.663613E+11 | 62477.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.809164E+11 | 88962.17 | 09-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.573475E+11 | 79360.39 | 25-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.473909E+11 | 79821.80 | 05-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181624E+11 | 43007.04 | 05-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.242978E+10 | 24322.80 | 01-MAY-04:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.208836E+09 | 18272.40 | 04-JUN-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7129180.24 | 5023.62 | 02-JUL-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 61481626.15 | 7684.36 | 19-AUG-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134207E+10 | 23083.37 | 06-SEP-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125277E+11 | 48593.86 | 30-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.332353E+11 | 49909.28 | 29-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.738076E+11 | 89475.42 | 24-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327437E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7129180.24 | 5023.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.809164E+11 | 89475.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.239942E+09 | 0.193663E+09 | 10858.78 | 23-APR-17:10 | 8679.76 | 0.00 |
May | 0.00 | 0.00 | 0.374072E+10 | 0.297891E+10 | 20395.21 | 25-MAY-17:43 | 15280.01 | 0.00 |
June | 0.00 | 0.00 | 0.100329E+11 | 0.648061E+10 | 40371.53 | 29-JUN-03:47 | 21317.20 | 0.00 |
July | 0.00 | 0.00 | 0.152168E+11 | 0.918719E+10 | 42858.97 | 04-JUL-00:09 | 15641.32 | 0.00 |
August | 0.00 | 0.00 | 0.961188E+10 | 0.599027E+10 | 39984.10 | 09-AUG-00:42 | 20887.53 | 0.00 |
September | 0.00 | 0.00 | 0.123867E+10 | 0.916157E+09 | 20136.05 | 01-SEP-00:42 | 8840.27 | 0.00 |
October | 0.00 | 0.00 | 0.128939E+09 | 0.110027E+09 | 5340.43 | 19-OCT-15:10 | 4628.64 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.402098E+11 | 0.258568E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.152168E+11 | 0.918719E+10 | 42858.97 | 21317.20 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 501913.01 | 399660.11 | 957.04 | 03-JAN-04:56 | 819.80 | 0.00 |
February | 0.00 | 0.00 | 544162.95 | 450837.25 | 942.81 | 28-FEB-04:40 | 855.69 | 0.00 |
March | 0.00 | 0.00 | 707568.14 | 529431.71 | 1066.86 | 31-MAR-03:27 | 816.15 | 0.00 |
April | 0.00 | 0.00 | 0.250019E+09 | 0.217496E+09 | 11218.29 | 23-APR-16:00 | 10157.34 | 0.00 |
May | 0.00 | 0.00 | 0.436273E+10 | 0.369555E+10 | 31313.45 | 25-MAY-00:42 | 20590.06 | 0.00 |
June | 0.00 | 0.00 | 0.132420E+11 | 0.852100E+10 | 34791.30 | 30-JUN-02:62 | 14278.63 | 0.00 |
July | 0.00 | 0.00 | 0.201574E+11 | 0.120164E+11 | 34791.30 | 15-JUL-13:00 | 15701.08 | 0.00 |
August | 0.00 | 0.00 | 0.124074E+11 | 0.763725E+10 | 32504.49 | 08-AUG-14:10 | 20002.57 | 0.00 |
September | 0.00 | 0.00 | 0.139584E+10 | 0.100231E+10 | 32479.72 | 01-SEP-00:42 | 12465.93 | 0.00 |
October | 0.00 | 0.00 | 84663041.60 | 70157698.18 | 31313.45 | 20-OCT-03:31 | 17738.34 | 0.00 |
November | 0.00 | 0.00 | 3592149.31 | 2558359.01 | 4090.29 | 21-NOV-04:05 | 2070.27 | 0.00 |
December | 0.00 | 0.00 | 631233.11 | 573282.47 | 1450.08 | 01-DEC-04:40 | 1313.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.519061E+11 | 0.331646E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 501913.01 | 399660.11 | 942.81 | 816.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201574E+11 | 0.120164E+11 | 34791.30 | 20590.06 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 6169.88 | 23372.98 | 31-JAN-13:37 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6306.34 | 23609.26 | 26-FEB-14:00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 6296.23 | 23602.82 | 01-MAR-13:40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6095.90 | 23155.89 | 01-APR-12:15 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5809.14 | 22158.81 | 01-MAY-12:15 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5485.21 | 20867.12 | 01-JUN-13:00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 5194.82 | 19670.85 | 01-JUL-12:25 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 5069.33 | 18819.71 | 01-AUG-12:18 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5080.24 | 19003.51 | 30-SEP-12:15 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 5269.58 | 19992.58 | 31-OCT-13:00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 5570.89 | 21240.65 | 30-NOV-13:20 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5887.26 | 22492.12 | 31-DEC-14:00 |
Annual Sum or Average | 0.00 | 5682.54 | ||||
Minimum of Months | 0.00 | 0.00 | 5069.33 | 18819.71 | ||
Maximum of Months | 0.00 | 0.00 | 6306.34 | 23609.26 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271121E+10 | 0.56 | 1211.87 | 01-JAN-00:01 | 0.67 |
February | 0.245055E+10 | 0.56 | 1211.87 | 01-FEB-00:01 | 0.67 |
March | 0.271484E+10 | 0.56 | 1211.87 | 01-MAR-00:01 | 0.67 |
April | 0.269384E+10 | 0.57 | 1211.87 | 01-APR-04:01 | 0.66 |
May | 0.301198E+10 | 0.61 | 1211.87 | 01-MAY-04:01 | 0.66 |
June | 0.298812E+10 | 0.63 | 1211.87 | 01-JUN-02:65 | 0.66 |
July | 0.310208E+10 | 0.63 | 1211.87 | 01-JUL-00:05 | 0.66 |
August | 0.309748E+10 | 0.63 | 1211.87 | 01-AUG-00:05 | 0.66 |
September | 0.294892E+10 | 0.62 | 1211.87 | 01-SEP-00:03 | 0.66 |
October | 0.286929E+10 | 0.59 | 1211.87 | 01-OCT-00:30 | 0.66 |
November | 0.266957E+10 | 0.57 | 1211.87 | 01-NOV-03:15 | 0.66 |
December | 0.271573E+10 | 0.56 | 1211.87 | 01-DEC-00:01 | 0.67 |
Annual Sum or Average | 0.339736E+11 | 0.59 | |||
Minimum of Months | 0.245055E+10 | 0.56 | 1211.87 | 0.66 | |
Maximum of Months | 0.310208E+10 | 0.63 | 1211.87 | 0.67 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.277796E+10 | 0.67 | 1776.20 | 01-JAN-03:01 | 0.92 |
February | 0.232134E+10 | 0.64 | 1776.20 | 01-FEB-03:01 | 0.92 |
March | 0.234435E+10 | 0.61 | 1776.20 | 03-MAR-03:10 | 0.92 |
April | 0.186075E+10 | 0.55 | 1776.20 | 05-APR-02:08 | 0.92 |
May | 0.165917E+10 | 0.49 | 1024.88 | 01-MAY-04:01 | 0.70 |
June | 0.158425E+10 | 0.48 | 1394.93 | 29-JUN-18:00 | 0.81 |
July | 0.162735E+10 | 0.50 | 1022.65 | 15-JUL-13:53 | 0.68 |
August | 0.161443E+10 | 0.50 | 1112.34 | 08-AUG-17:10 | 0.72 |
September | 0.159767E+10 | 0.48 | 952.70 | 28-SEP-05:50 | 0.67 |
October | 0.184837E+10 | 0.52 | 1148.32 | 25-OCT-04:04 | 0.74 |
November | 0.207984E+10 | 0.59 | 1776.20 | 24-NOV-03:08 | 0.92 |
December | 0.271443E+10 | 0.66 | 1776.20 | 01-DEC-03:05 | 0.92 |
Annual Sum or Average | 0.240299E+11 | 0.56 | |||
Minimum of Months | 0.158425E+10 | 0.48 | 952.70 | 0.67 | |
Maximum of Months | 0.277796E+10 | 0.67 | 1776.20 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.315884E+10 | 0.80 | 1415.16 | 16-JAN-08:55 | 0.95 |
February | 0.285326E+10 | 0.80 | 1415.16 | 18-FEB-11:10 | 0.95 |
March | 0.315913E+10 | 0.80 | 1415.16 | 01-MAR-23:20 | 0.95 |
April | 0.306347E+10 | 0.81 | 1415.16 | 02-APR-04:09 | 0.95 |
May | 0.322470E+10 | 0.87 | 1415.16 | 08-MAY-19:55 | 0.95 |
June | 0.317923E+10 | 0.88 | 1415.16 | 17-JUN-19:14 | 0.94 |
July | 0.333135E+10 | 0.89 | 1415.16 | 20-JUL-18:12 | 0.94 |
August | 0.330971E+10 | 0.89 | 1415.16 | 01-AUG-17:50 | 0.94 |
September | 0.312175E+10 | 0.88 | 1415.16 | 01-SEP-09:10 | 0.93 |
October | 0.317425E+10 | 0.83 | 1415.16 | 27-OCT-05:30 | 0.95 |
November | 0.306038E+10 | 0.81 | 1415.16 | 09-NOV-17:13 | 0.95 |
December | 0.315896E+10 | 0.80 | 1415.16 | 16-DEC-11:55 | 0.95 |
Annual Sum or Average | 0.377950E+11 | 0.84 | |||
Minimum of Months | 0.285326E+10 | 0.80 | 1415.16 | 0.93 | |
Maximum of Months | 0.333135E+10 | 0.89 | 1415.16 | 0.95 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 48.82 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 50.04 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 50.31 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 50.11 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 49.37 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 51.15 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:03 | 0.00 | 0.00 | 51.67 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 51.78 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 51.92 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 50.42 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 51.39 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 50.91 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 48.82 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 51.92 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 34.90 | 34.90 | 6169.88 | 23372.98 | 31-JAN-13:37 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 50.34 | 50.34 | 6306.34 | 23609.26 | 26-FEB-14:00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 49.98 | 49.98 | 6296.23 | 23602.82 | 01-MAR-13:40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 50.12 | 50.12 | 6095.90 | 23155.89 | 01-APR-12:15 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 35.39 | 35.39 | 5809.14 | 22158.81 | 01-MAY-12:15 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 51.06 | 51.06 | 5485.21 | 20867.12 | 01-JUN-13:00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 51.26 | 51.26 | 5194.82 | 19670.85 | 01-JUL-12:25 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 51.74 | 51.74 | 5069.33 | 18819.71 | 01-AUG-12:18 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 51.79 | 51.79 | 5080.24 | 19003.51 | 30-SEP-12:15 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 38.72 | 38.72 | 5269.58 | 19992.58 | 31-OCT-13:00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 51.63 | 51.63 | 5570.89 | 21240.65 | 30-NOV-13:20 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 51.20 | 51.20 | 5887.26 | 22492.12 | 31-DEC-14:00 |
Annual Sum or Average | 0.00 | 5682.54 | ||||||
Minimum of Months | 0.00 | 0.00 | 34.90 | 34.90 | 5069.33 | 18819.71 | ||
Maximum of Months | 0.00 | 0.00 | 51.79 | 51.79 | 6306.34 | 23609.26 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.277796E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.232134E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.234435E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.192724E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.266366E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.413569E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.542061E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.408899E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.194040E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.188657E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.207984E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.271443E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.343011E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.188657E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.542061E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.315899E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.285343E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.315935E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.313012E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.433723E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.636516E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.809023E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.633603E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.349121E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.319897E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.306145E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.315915E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.503413E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.285343E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.809023E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.277796E+10 | 0.00 | 0.663613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.232134E+10 | 0.00 | 0.488525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234435E+10 | 0.00 | 0.419052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186075E+10 | 0.239942E+09 | 0.184817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165917E+10 | 0.374072E+10 | 0.408711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158425E+10 | 0.100184E+11 | 0.694728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162735E+10 | 0.151820E+11 | 0.145867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161443E+10 | 0.960511E+10 | 0.273489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159767E+10 | 0.123867E+10 | 0.352531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184837E+10 | 0.128939E+09 | 0.152415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207984E+10 | 0.00 | 0.307952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271443E+10 | 0.00 | 0.623646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240299E+11 | 0.401537E+11 | 0.292728E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158425E+10 | 0.00 | 0.145867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.277796E+10 | 0.151820E+11 | 0.663613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.315884E+10 | 501913.01 | 0.809164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285326E+10 | 544162.95 | 0.573475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.315913E+10 | 707568.14 | 0.473909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.306347E+10 | 0.250019E+09 | 0.181624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.322470E+10 | 0.436273E+10 | 0.242978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.317923E+10 | 0.132420E+11 | 0.208836E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.333135E+10 | 0.201574E+11 | 7129180.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.330971E+10 | 0.124074E+11 | 61481626.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.312175E+10 | 0.139584E+10 | 0.134207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.317425E+10 | 84663041.60 | 0.125277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.306038E+10 | 3592149.31 | 0.332353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.315896E+10 | 631233.11 | 0.738076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377950E+11 | 0.519061E+11 | 0.327437E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.285326E+10 | 501913.01 | 7129180.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.333135E+10 | 0.201574E+11 | 0.809164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.277796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.232134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186075E+10 | 0.00 | 0.00 | 0.00 | 66493934.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165917E+10 | 0.00 | 0.00 | 0.00 | 0.100449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158425E+10 | 0.00 | 0.00 | 0.00 | 0.255144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162735E+10 | 0.00 | 0.00 | 0.00 | 0.379326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161443E+10 | 0.00 | 0.00 | 0.00 | 0.247456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159767E+10 | 0.00 | 0.00 | 0.00 | 0.342728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184837E+10 | 0.00 | 0.00 | 0.00 | 38205050.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240299E+11 | 0.00 | 0.00 | 0.00 | 0.102712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.277796E+10 | 0.00 | 0.00 | 0.00 | 0.379326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.315884E+10 | 0.00 | 0.00 | 0.00 | 152781.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285326E+10 | 0.00 | 0.00 | 0.00 | 165987.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.315913E+10 | 0.00 | 0.00 | 0.00 | 216163.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.306347E+10 | 0.00 | 0.00 | 0.00 | 66642543.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.322470E+10 | 0.00 | 0.00 | 0.00 | 0.111252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.317923E+10 | 0.00 | 0.00 | 0.00 | 0.318593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.333135E+10 | 0.00 | 0.00 | 0.00 | 0.475888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.330971E+10 | 0.00 | 0.00 | 0.00 | 0.302632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.312175E+10 | 0.00 | 0.00 | 0.00 | 0.369451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.317425E+10 | 0.00 | 0.00 | 0.00 | 24725791.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.306038E+10 | 0.00 | 0.00 | 0.00 | 1072039.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.315896E+10 | 0.00 | 0.00 | 0.00 | 192323.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377950E+11 | 0.00 | 0.00 | 0.00 | 0.125463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.285326E+10 | 0.00 | 0.00 | 0.00 | 152781.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.333135E+10 | 0.00 | 0.00 | 0.00 | 0.475888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.185432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458157E+11 | 0.00 | 0.00 | 3.64 |
February | 0.211471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356166E+11 | 0.00 | 0.00 | 3.63 |
March | 0.223512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323269E+11 | 0.00 | 0.00 | 3.62 |
April | 0.488947E+10 | 10341411.92 | 0.00 | 1646674.79 | 0.00 | 0.150427E+11 | 0.669649E+09 | 0.00 | 3.67 |
May | 0.672852E+10 | 0.187620E+09 | 0.00 | 11523234.70 | 0.00 | 0.238164E+10 | 0.278845E+10 | 0.00 | 4.15 |
June | 0.398681E+10 | 0.163055E+10 | 0.00 | 18318101.11 | 0.00 | 0.155654E+09 | 0.373673E+10 | 0.00 | 4.64 |
July | 0.228921E+10 | 0.235705E+10 | 0.00 | 22407289.43 | 0.00 | 0.00 | 0.414604E+10 | 0.00 | 4.90 |
August | 0.327299E+10 | 0.921404E+09 | 0.00 | 24561179.76 | 0.00 | 52142880.51 | 0.519139E+10 | 0.00 | 4.88 |
September | 0.830539E+10 | 29883203.40 | 0.00 | 10190476.85 | 0.00 | 0.133133E+10 | 0.354734E+10 | 0.00 | 4.13 |
October | 0.706502E+10 | 0.00 | 0.00 | 1791128.97 | 0.00 | 0.117477E+11 | 0.734647E+09 | 0.00 | 3.66 |
November | 0.286877E+10 | 0.00 | 0.00 | 29499.90 | 0.00 | 0.246658E+11 | 73301444.08 | 0.00 | 3.61 |
December | 0.176101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441019E+11 | 0.00 | 0.00 | 3.62 |
Annual Sum or Average | 0.473713E+11 | 0.513685E+10 | 0.00 | 90467585.52 | 0.00 | 0.213238E+12 | 0.208876E+11 | 0.00 | 4.02 |
Minimum of Months | 0.176101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 |
Maximum of Months | 0.830539E+10 | 0.235705E+10 | 0.00 | 24561179.76 | 0.00 | 0.458157E+11 | 0.519139E+10 | 0.00 | 4.90 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114015E+12 | 0.00 | 0.00 | 60572.55 | 0.00 | 0.150142E+09 | 37622798.69 | 0.00 | 9.64 |
February | 0.880376E+11 | 0.00 | 0.00 | 67348.81 | 0.00 | 0.105950E+09 | 41030858.47 | 0.00 | 9.64 |
March | 0.818359E+11 | 0.00 | 0.00 | 91931.36 | 0.00 | 71954770.02 | 54729675.55 | 0.00 | 9.65 |
April | 0.502057E+11 | 0.00 | 0.00 | 3970483.62 | 0.00 | 16469805.74 | 0.256202E+10 | 0.00 | 9.74 |
May | 0.221995E+11 | 46017608.95 | 0.00 | 34015706.65 | 0.00 | 1785740.12 | 0.133335E+11 | 0.00 | 10.31 |
June | 0.882957E+10 | 0.226665E+10 | 0.00 | 53859021.63 | 0.00 | 0.00 | 0.167282E+11 | 0.00 | 10.86 |
July | 0.483333E+10 | 0.279387E+10 | 0.00 | 71704221.89 | 0.00 | 0.00 | 0.163795E+11 | 0.00 | 11.17 |
August | 0.589938E+10 | 0.808347E+09 | 0.00 | 71481185.00 | 0.00 | 0.00 | 0.210847E+11 | 0.00 | 11.01 |
September | 0.214285E+11 | 0.00 | 0.00 | 29527947.47 | 0.00 | 1729648.02 | 0.157489E+11 | 0.00 | 10.26 |
October | 0.470888E+11 | 0.00 | 0.00 | 4703589.48 | 0.00 | 6703061.32 | 0.314759E+10 | 0.00 | 9.76 |
November | 0.674152E+11 | 0.00 | 0.00 | 824983.75 | 0.00 | 25894863.41 | 0.756524E+09 | 0.00 | 9.72 |
December | 0.107394E+12 | 0.00 | 0.00 | 141325.65 | 0.00 | 0.118443E+09 | 61787235.18 | 0.00 | 9.60 |
Annual Sum or Average | 0.619182E+12 | 0.591489E+10 | 0.00 | 0.270448E+09 | 0.00 | 0.499073E+09 | 0.899361E+11 | 0.00 | 10.12 |
Minimum of Months | 0.483333E+10 | 0.00 | 0.00 | 60572.55 | 0.00 | 0.00 | 37622798.69 | 0.00 | 9.60 |
Maximum of Months | 0.114015E+12 | 0.279387E+10 | 0.00 | 71704221.89 | 0.00 | 0.150142E+09 | 0.210847E+11 | 0.00 | 11.17 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:26
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.150104E+11 | 0.313240E+11 | 0.205809E+12 | 0.00 | 0.544510E+11 |
February | 0.247665E+11 | 0.239080E+11 | 0.159784E+12 | 0.00 | 0.439685E+11 |
March | 0.375041E+11 | 0.222314E+11 | 0.149489E+12 | 0.00 | 0.424551E+11 |
April | 0.497294E+11 | 0.139893E+11 | 0.996470E+11 | 0.183570E+09 | 0.301151E+11 |
May | 0.597004E+11 | 0.793793E+10 | 0.703766E+11 | 0.144608E+10 | 0.364623E+11 |
June | 0.620265E+11 | 0.403547E+10 | 0.455669E+11 | 0.208868E+10 | 0.568058E+11 |
July | 0.634284E+11 | 0.213764E+10 | 0.358778E+11 | 0.207987E+10 | 0.747349E+11 |
August | 0.522255E+11 | 0.425791E+10 | 0.501519E+11 | 0.246273E+10 | 0.555663E+11 |
September | 0.374378E+11 | 0.838632E+10 | 0.743095E+11 | 0.147570E+10 | 0.262840E+11 |
October | 0.198948E+11 | 0.128976E+11 | 0.983247E+11 | 0.272999E+09 | 0.247758E+11 |
November | 0.848338E+10 | 0.178197E+11 | 0.127001E+12 | 0.00 | 0.305988E+11 |
December | 0.940300E+10 | 0.294291E+11 | 0.194611E+12 | 0.00 | 0.500336E+11 |
Annual Sum or Average | 0.439610E+12 | 0.178354E+12 | 0.131095E+13 | 0.100096E+11 | 0.526251E+12 |
Minimum of Months | 0.848338E+10 | 0.213764E+10 | 0.358778E+11 | 0.00 | 0.247758E+11 |
Maximum of Months | 0.634284E+11 | 0.313240E+11 | 0.205809E+12 | 0.246273E+10 | 0.747349E+11 |