Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:23
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 08:23:52
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1521.86 | 6550.05 | 6550.05 |
Net Site Energy | 1521.86 | 6550.05 | 6550.05 |
Total Source Energy | 3018.10 | 12989.87 | 12989.87 |
Net Source Energy | 3018.10 | 12989.87 | 12989.87 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 186.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 72.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 276.88 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 201.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 65.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 656.94 | 864.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 186.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 72.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 41.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.75 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 156.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 201.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 17.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 30.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 186.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 72.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 41.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 276.88 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 156.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 201.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 65.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 370.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 984.19 | 1668.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1472.75 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2827.47 | 3722.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 370.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 984.19 | 1668.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1472.75 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2827.47 | 3722.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 656.942 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 656.942 | 100.00 |
Total On-Site and Utility Electric Sources | 656.942 | 100.00 |
Total Electricity End Uses | 656.942 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4266.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:23 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 9.2637 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 11.9458 | 18.52 | 1074.0064 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 10.6047 | 2.48 | 595.3967 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 10.6047 | 2.48 | 595.3967 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 9.2637 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.9458 | 18.52 | 1074.0064 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 10.6047 | 1.24 | 595.3967 | |||||||
Conditioned Total | 232.34 | 10.6047 | 1.24 | 595.3967 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 10.6047 | 2.48 | 595.3967 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-16:10 | 20-JAN-11:20 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 33317.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19267.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2217.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 13076.95 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5730.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 22293.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2022.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 42315.68 | 82271.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 33317.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19267.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2217.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 11709.37 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5730.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 22293.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 510.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 966.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 201.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 228.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 141.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 130.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 876.87 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 496.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 218.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 206.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2080.54 | 937.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 868.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 981.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 611.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 562.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3774.05 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2135.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 941.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 890.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8954.59 | 4035.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 868.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 981.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 611.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 562.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3774.05 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2135.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 941.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 890.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8954.59 | 4035.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 2.57 |
KITCHEN DIRECT AIR | 1.56 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.57 | 2.57 | 2.57 | 2.57 | 2.57 | 2.57 | 1.00 | 1.00 | 2.57 |
PSZ-AC_2:2 | 1.56 | 1.56 | 1.56 | 1.56 | 1.56 | 1.56 | 1.00 | 1.00 | 1.56 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.57 | 0.826211 |
PSZ-AC_2:2_OA_CONTROLLER | 1.56 | 0.731143 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 2.57 | 2812.97 |
PSZ-AC_2:2_ADDAQ FAN | 1.56 | 1705.78 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.57 | 2.57 | 2.57 | 2.57 | 43844.70 | 80552.16 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.56 | 1.56 | 1.56 | 1.56 | 30589.35 | 67790.41 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.57 | 1.29 | 2.57 | 43844.70 | 21271.98 | 43844.70 | 0.800750 | 0.800750 |
PSZ-AC_2:2 COOLING COIL | 1.56 | 0.779249 | 1.56 | 30589.35 | 14640.62 | 30589.35 | 0.784080 | 0.784080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 80552.16 |
PSZ-AC_2:2 HEATING COIL | 67790.41 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 9.264 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 126.051 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 11.946 | 282.654 | 791.353 | 0.000 | 0.000 | 0.000 | 1085.952 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 1076.175 | 9.264 | 12.293 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1076.175 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1387.759 | 11.946 | 221.217 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1387.759 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 515.917 | 4.441 | 82.240 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 851.667 | 7.331 | 135.761 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.2003 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.2003 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.6929 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.892 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.892 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.209 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.20636098E-16 | 0.18100998E-15 | 0.17288268E-13 | -0.34766289E-16 |
24 | 3 | -0.71341822E-08 | 0.14427768E-06 | -0.58767875E-04 | 0.16137435E-12 |
25 | 2 | 0.62866063E-04 | 0.30866150E-02 | 1.1745480 | -0.77421164E-04 |
26 | 1 | -0.70719755E-01 | 0.78899699E-01 | -17.315014 | 0.34200793 |
27 | 0 | 0.20250090 | 0.49857543E-01 | 16.272369 | |
28 | 4 | 0.17288268E-13 | 0.18100998E-15 | 0.20636098E-16 | -0.34766289E-16 |
29 | 3 | -0.58767875E-04 | 0.14427768E-06 | -0.71341822E-08 | 0.16137435E-12 |
30 | 2 | 1.1745480 | 0.30866150E-02 | 0.62866063E-04 | -0.77421164E-04 |
31 | 1 | -17.315014 | 0.78899699E-01 | -0.70719755E-01 | 0.34200793 |
32 | 0 | 16.272369 | 0.49857543E-01 | 0.20250090 | |
33 | 7 | -0.33002231E-12 | 0.10712597E-14 | -0.10720425E-12 | 0.10137879E-15 |
34 | 6 | 0.29661659E-07 | 0.19687232E-09 | 0.67865745E-08 | -0.14052424E-12 |
35 | 5 | -0.19512200E-03 | 0.16741682E-05 | -0.10029371E-03 | 0.67057946E-08 |
36 | 4 | 0.29799499 | 0.81016957E-03 | 0.10178761 | -0.34398158E-04 |
37 | 3 | -7.3821031 | 0.24971312E-01 | -2.3732702 | 0.29576512E-01 |
38 | 2 | 41.252923 | 0.88368331E-01 | 15.405914 | -0.33759269 |
39 | 1 | -80.838295 | 0.39713828E-01 | -29.267905 | 1.0848528 |
40 | 0 | 46.824337 | 0.79570062E-03 | 16.288235 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5722_SHGC_SOUTH_0.39 | 38 | 1 | VerySmooth | 3.253 | 3.253 | 1.000 | 0.391 | ||
2 | NONRESWINDOW_U_0.5722_SHGC_NORTH_0.39 | 39 | 1 | VerySmooth | 3.253 | 3.253 | 1.000 | 0.391 | ||
3 | NONRESWINDOW_U_0.5722_SHGC_EAST_0.39 | 40 | 1 | VerySmooth | 3.253 | 3.253 | 1.000 | 0.391 | ||
4 | NONRESWINDOW_U_0.5722_SHGC_WEST_0.39 | 41 | 1 | VerySmooth | 3.253 | 3.253 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46595 | 0.46595 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.44974E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46595 | 0.46595 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.44974E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46595 | 0.46595 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.44974E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46595 | 0.46595 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.44974E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.052 | 0.3089 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 9.529E-002 | 8.202E-004 | 1.025E-003 | 0.969 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 9.529E-002 | 8.202E-004 | 1.004E-003 | 0.969 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 23935.74600 | 28722.89520 | 2.14173 | 2.57008 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.69938E-003 | 116.17148 | 87.54444 | 0.82621 | 0.00000 |
2 | DINING | Heating | 6002.64632 | 7203.17558 | 0.31046 | 0.82621 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -7.90000 | 2.34317E-003 | 116.17148 | 87.54444 | 0.82621 | 0.00000 |
3 | KITCHEN | Cooling | 17409.70214 | 20891.64256 | 1.29875 | 1.55850 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.88500 | 5.69749E-003 | 116.17148 | 6.27330 | 0.73114 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 0.73114 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -7.90000 | 2.34317E-003 | 116.17148 | 6.27330 | 0.73114 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 37576.91 | 2.57008 | 2.57008 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 39386.36 | 0.82621 | 0.82621 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 26260.28 | 1.55850 | 1.55850 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 34854.36 | 0.73114 | 0.73114 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.57008 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.55850 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.57008 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.57008 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.57008 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.57008 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.57008 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.57008 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.55850 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.55850 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.55850 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.55850 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.55850 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.55850 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.57008 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.55850 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.57008 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.82621 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.57008 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2812.96766 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.57008 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.57008 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.57008 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.57008 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.57008 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.28504 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.57008 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 43844.70000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 21271.98223 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 43844.70000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80075 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80075 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 43844.70000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 80552.15577 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 80552.15577 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.55850 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.73114 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.55850 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1705.78440 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.55850 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.55850 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.55850 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.55850 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.55850 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.77925 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.55850 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30589.35000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 14640.61600 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30589.35000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78408 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78408 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30589.35000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 67790.40510 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 67790.40510 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 41967.7 | 9.64 | 9.52 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 29461.2 | 10.35 | 10.22 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5722_SHGC_EAST_0.39 | N/A | 3.253 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5722_SHGC_SOUTH_0.39 | N/A | 3.253 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5722_SHGC_WEST_0.39 | N/A | 3.253 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.200 | 0.193 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.200 | 0.193 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.200 | 0.191 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.200 | 0.191 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1318436792 | 0.4420759441 | Pass | Pass | 0.5097600457 | 2.0424254881 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2804468791 | 0.6880365374 | Pass | Pass | 0.1044162459 | 0.3907028146 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4976251515 | 0.5288299430 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 639.05 | 113.65 | 951.14 | 67.87 | 679.78 | 2451.49 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.190 | 0.200 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.190 | 0.200 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.190 | 0.200 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.190 | 0.200 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5722_SHGC_EAST_0.39 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 3.253 | 0.391 | 0.391 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5722_SHGC_SOUTH_0.39 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 3.253 | 0.391 | 0.391 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.5722_SHGC_WEST_0.39 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 3.253 | 0.391 | 0.391 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 3.253 | 0.391 | 0.391 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.253 | 0.391 | 0.391 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 9.2637 | 116.17 | 1076.18 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 19.58 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.9458 | 116.17 | 1387.76 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 25.25 |
Interior Lighting Total | 10.6047 | 232.34 | 2463.93 | 44.83 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 2625.88 | AstronomicalClock | - | 83.71 | 83.71 | 41.26 | |
Exterior Lighting Total | 2625.88 | 41.26 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 43844.70 | 35108.64 | 8736.06 | 0.80 | 3.30 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30589.35 | 23984.50 | 6604.85 | 0.78 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 41967.7 | 9.64 | 9.52 | ||||
PSZ-AC_2:2 COOLING COIL | 29461.2 | 10.35 | 10.22 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 80552.16 | 0.79 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 67790.41 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.83 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 1.56 | 1211.87 | 778.12 | 1.00 | 0.64 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.57 | 622.50 | 2.57 | 2812.97 | 1094.51 | 1.00 | 1.25 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.57 | 622.50 | 1.56 | 1705.78 | 1094.51 | 1.00 | 1.32 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 23935.75 | 28722.90 | 247.25 | 2.142 | 2.570 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.89 | 0.00733 | 35.10 | 0.00570 | 0.826 | 0.00 |
KITCHEN | 17409.70 | 20891.64 | 179.83 | 1.299 | 1.558 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.00856 | 33.89 | 0.00570 | 0.731 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 6002.65 | 7203.18 | 62.00 | 0.310 | 0.826 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 21.11 | 21.11 | 0.00765 | -7.90 | 0.00234 | 0.826 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 0.731 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 18.89 | 22.47 | 0.00209 | -7.90 | 0.00234 | 0.731 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.57 | 2.57 | 0.83 | 0.83 | 2.5701 | 2.5701 | 2.5701 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.56 | 1.56 | 0.73 | 0.73 | 1.5585 | 1.5585 | 1.5585 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 43844.700 | 35108.644 | 2.570080 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 43844.70 | 43844.70 | 2.570080 | 27.49 | 14.17 | 0.00680466 | 11.71 | 8.22 | 0.00680466 | 35.10 | 0.00569938 | 15.77 | 32.1473 | 23.89 | 0.00732832 | 32.7287 | 23935.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 80552.156 | 80552.156 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 | 80552.16 | 80552.16 | 2.570081 | 8.51 | 4.76 | 0.00493934 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 32.1473 | 18.33 | 0.00616935 | 38.8348 | 1505.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 30589.350 | 23984.498 | 1.558500 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 30589.35 | 29910.93 | 1.558500 | 29.73 | 15.24 | 0.00721543 | 11.71 | 8.42 | 0.00700000 | 33.89 | 0.00569749 | 15.38 | 46.9132 | 26.10 | 0.00855684 | 33.4332 | 17409.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 67790.405 | 67790.405 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 67790.41 | 67790.41 | 1.558498 | -3.71 | -5.55 | 0.00221580 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 46.9133 | 22.90 | 0.00210323 | 10.0534 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 43844.700 | 35108.644 | 2.570080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.4895 | 1004.8586 | 0.9904 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.570081 | 2.54543098 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 43844.70 | 43844.70 | 1.0000 | 2.54543009 | 2.570080 | 27.49 | 14.17 | 0.00680466 | 44990.0 | 11.71 | 8.22 | 0.00680466 | 28936.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 43844.70 | 35.10 | 0.00569938 | 15.77 | 0.82621072 | 32.1473 | 23.89 | 0.00732832 | 23.89 | 0.00732832 | 32.7287 | 23935.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 80552.156 | 80552.156 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.570081 | 2.54543098 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 | Sensible | 80552.16 | 80552.16 | 1.0000 | 2.54543098 | 2.570081 | 8.51 | 4.76 | 0.00493934 | 20979.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 80552.16 | -7.90 | 0.00234317 | -7.90 | 0.82621072 | 32.1473 | 16.28 | 0.00616935 | 18.33 | 0.00616935 | 38.8348 | 1505.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30589.350 | 23984.498 | 1.558500 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.2531 | 1004.8586 | 0.9904 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.558498 | 1.54355008 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 30589.35 | 29910.93 | 1.0000 | 1.54355226 | 1.558500 | 29.73 | 15.24 | 0.00721543 | 48318.7 | 11.71 | 8.42 | 0.00700000 | 29430.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30589.35 | 33.89 | 0.00569749 | 15.38 | 0.73114267 | 46.9132 | 26.06 | 0.00855684 | 26.10 | 0.00855684 | 33.4332 | 17409.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 67790.405 | 67790.405 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.558498 | 1.54355008 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 67790.41 | 67790.41 | 1.0000 | 1.54355008 | 1.558498 | -3.71 | -5.55 | 0.00221580 | 1802.2 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 67790.41 | -7.90 | 0.00234317 | -7.90 | 0.73114267 | 46.9133 | 0.00 | 0.00210323 | 22.90 | 0.00210323 | 10.0534 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.83 | 2.57 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.73 | 1.56 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3059.50 | 4233.00 | 777.00 |
KITCHEN | 5415.33 | 5453.17 | 3994.17 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5687.17 | 7100.83 | 4266.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 39.50 | 77.00 | 0.17 | 0.00 |
KITCHEN | 0.00 | 287.67 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 39.50 | 291.67 | 0.17 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 9.937 | 4.315 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 10.112 | 0.054 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 8.132 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 7.202 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.8262 | 0.826 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1017 | 0.042 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.9279 | 0.869 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 25849265.75 | 0.00 | 25849265.75 | 10993885.83 | 36843151.58 | 26055381.38 | 1414.42 | 5896.05 | 1449.53 | 565.19 |
KITCHEN | 26958896.76 | 0.00 | 26958896.76 | 231843.94 | 27190740.69 | 23057315.35 | 1273.37 | 4346.89 | 3139.74 | 874.33 |
Total Facility | 52808162.51 | 0.00 | 52808162.51 | 11225729.76 | 64033892.27 | 49112696.73 | 1433.17 | 5901.47 | 3158.04 | 1011.89 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.9692 | 0.0000 | 0.9692 | 0.4212 | 1.3904 | 0.8262 | 0.00 | 5795.55 | 1391.45 |
KITCHEN | 0.9774 | 0.0000 | 0.9774 | 0.0052 | 0.9826 | 0.7311 | 0.00 | 4259.36 | 2927.64 |
Total Facility | 1.9466 | 0.0000 | 1.9466 | 0.4264 | 2.3730 | 1.5574 | 0.00 | 5795.61 | 2927.69 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 25355795.42 | 0.00 | 25355795.42 | 26055381.38 | 7309.95 | 16.31 | 1433.75 | 565.13 |
PSZ-AC_2:2 | 26444178.96 | 0.00 | 26444178.96 | 23057315.35 | 5618.67 | 44.41 | 3096.92 | 874.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.9507 | 0.0000 | 0.9507 | 0.8262 | 5795.20 | 15.05 | 1376.75 |
PSZ-AC_2:2 | 0.9587 | 0.0000 | 0.9587 | 0.7311 | 4258.22 | 38.01 | 2890.76 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1255.27 | 609.52 | 5887.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 3207.31 | 4854.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.7658 | 1.2005 | 0.8105 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.3079 | 0.7173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 370 |
Defaulted Fields | 263 |
Fields with Defaults | 871 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 656.94 | 6655.60 | 15-DEC-01:10 | 42315.68 | 28-JUN-16:10 |
Electricity:Building | 339.57 | 3046.93 | 01-JAN-01:10 | 20161.68 | 02-JAN-11:10 |
Electricity:Zone:DINING | 90.00 | 432.77 | 01-JAN-01:10 | 4903.08 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 321.71 | 2637.89 | 01-JAN-01:10 | 16645.57 | 02-JAN-11:10 |
InteriorLights:Electricity | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 19.58 | 161.43 | 01-JAN-01:10 | 968.56 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 19.58 | 161.43 | 01-JAN-01:10 | 968.56 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 249.57 | 2614.16 | 01-JAN-01:10 | 15258.60 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 25.25 | 208.16 | 01-JAN-01:10 | 1248.98 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 25.25 | 208.16 | 01-JAN-01:10 | 1248.98 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 276.88 | 2268.30 | 01-JAN-01:10 | 14428.03 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 276.88 | 2268.30 | 01-JAN-01:10 | 14428.03 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 206.46 | 1996.96 | 01-JAN-01:10 | 10493.51 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.33 | 629.37 | 01-JAN-01:10 | 9125.93 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 65.30 | 1035.59 | 14-DEC-23:30 | 4592.33 | 17-JUL-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
Electricity:Plant | 47.44 | 779.94 | 05-FEB-23:30 | 2555.00 | 25-AUG-04:10 |
LowTempRefrigeration:Refrigeration:Electricity | 17.20 | 0.00 | 01-JAN-11:10 | 1478.77 | 25-AUG-04:10 |
MedTempRefrigeration:Refrigeration:Electricity | 30.25 | 701.41 | 06-FEB-00:20 | 1076.23 | 22-MAY-13:10 |
ElectricityPurchased:Facility | 656.94 | 6655.60 | 15-DEC-01:10 | 42315.68 | 28-JUN-16:10 |
ElectricityPurchased:Plant | 656.94 | 6655.60 | 15-DEC-01:10 | 42315.68 | 28-JUN-16:10 |
Cogeneration:ElectricityPurchased | 656.94 | 6655.60 | 15-DEC-01:10 | 42315.68 | 28-JUN-16:10 |
General:Cogeneration:ElectricityPurchased | 656.94 | 6655.60 | 15-DEC-01:10 | 42315.68 | 28-JUN-16:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 656.94 | 6655.60 | 15-DEC-01:10 | 42315.68 | 28-JUN-16:10 |
ElectricityNet:Plant | 656.94 | 6655.60 | 15-DEC-01:10 | 42315.68 | 28-JUN-16:10 |
Cogeneration:ElectricityNet | 656.94 | 6655.60 | 15-DEC-01:10 | 42315.68 | 28-JUN-16:10 |
General:Cogeneration:ElectricityNet | 656.94 | 6655.60 | 15-DEC-01:10 | 42315.68 | 28-JUN-16:10 |
Electricity:HVAC | 228.67 | 0.00 | 01-JAN-01:10 | 25106.32 | 21-JUL-17:10 |
Fans:Electricity | 156.67 | 0.00 | 01-JAN-01:10 | 5730.62 | 12-DEC-14:10 |
General:Fans:Electricity | 156.67 | 0.00 | 01-JAN-01:10 | 5730.62 | 12-DEC-14:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 72.00 | 0.00 | 01-JAN-00:10 | 19375.69 | 21-JUL-17:10 |
General:Cooling:Electricity | 72.00 | 0.00 | 01-JAN-00:10 | 19375.69 | 21-JUL-17:10 |
ExteriorLights:Electricity | 41.26 | 0.00 | 01-JAN-07:20 | 2625.88 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 41.26 | 0.00 | 01-JAN-07:20 | 2625.88 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-11:40 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-11:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 864.91 | 2560.65 | 11-JAN-01:20 | 82271.74 | 20-JAN-11:20 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 186.06 | 0.00 | 01-JAN-00:20 | 58207.70 | 21-JAN-07:10 |
Heating:NaturalGas | 186.06 | 0.00 | 01-JAN-00:20 | 58207.70 | 21-JAN-07:10 |
General:Heating:NaturalGas | 186.06 | 0.00 | 01-JAN-00:20 | 58207.70 | 21-JAN-07:10 |
NaturalGas:Plant | 201.70 | 722.00 | 03-JAN-05:20 | 27213.89 | 05-FEB-13:40 |
WaterSystems:NaturalGas | 201.70 | 722.00 | 03-JAN-05:20 | 27213.89 | 05-FEB-13:40 |
Water Heater:WaterSystems:NaturalGas | 201.70 | 722.00 | 03-JAN-05:20 | 27213.89 | 05-FEB-13:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1082.03 | 2741.23 | 15-DEC-01:10 | 110002.86 | 29-JUN-13:00 |
EnergyTransfer:Building | 491.52 | 1370.62 | 15-DEC-01:10 | 36337.07 | 29-JUN-11:10 |
EnergyTransfer:Zone:KITCHEN | 361.06 | 1370.62 | 15-DEC-01:10 | 21177.95 | 17-NOV-05:10 |
Refrigeration:EnergyTransfer | 151.87 | 2699.62 | 14-DEC-23:30 | 7834.84 | 30-MAY-03:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 75.93 | 1349.81 | 14-DEC-23:30 | 3917.42 | 30-MAY-03:30 |
General:Refrigeration:EnergyTransfer | 75.93 | 1349.81 | 14-DEC-23:30 | 3917.42 | 30-MAY-03:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 75.93 | 1349.81 | 14-DEC-23:30 | 3917.42 | 30-MAY-03:30 |
EnergyTransfer:Plant | 212.13 | 1349.81 | 05-FEB-23:30 | 21563.63 | 10-FEB-13:30 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 16.42 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 59.52 | 1114.24 | 06-FEB-00:20 | 2238.70 | 22-MAY-13:10 |
EnergyTransfer:Zone:DINING | 130.46 | 0.00 | 01-JAN-01:10 | 20580.98 | 21-JUL-17:10 |
Heating:EnergyTransfer | 29.17 | 0.00 | 01-JAN-00:10 | 16524.70 | 19-JAN-21:00 |
Heating:EnergyTransfer:Zone:DINING | 29.17 | 0.00 | 01-JAN-00:10 | 16524.70 | 19-JAN-21:00 |
General:Heating:EnergyTransfer | 29.17 | 0.00 | 01-JAN-00:10 | 16524.70 | 19-JAN-21:00 |
General:Heating:EnergyTransfer:Zone:DINING | 29.17 | 0.00 | 01-JAN-00:10 | 16524.70 | 19-JAN-21:00 |
Cooling:EnergyTransfer | 386.42 | 0.00 | 01-JAN-01:10 | 33588.91 | 21-JUL-17:10 |
Cooling:EnergyTransfer:Zone:DINING | 101.29 | 0.00 | 01-JAN-01:10 | 20580.98 | 21-JUL-17:10 |
General:Cooling:EnergyTransfer | 386.42 | 0.00 | 01-JAN-01:10 | 33588.91 | 21-JUL-17:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 101.29 | 0.00 | 01-JAN-01:10 | 20580.98 | 21-JUL-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 285.13 | 0.00 | 01-JAN-01:10 | 17370.45 | 17-NOV-05:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 285.13 | 0.00 | 01-JAN-01:10 | 17370.45 | 17-NOV-05:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 136.19 | 0.00 | 01-JAN-00:10 | 19000.71 | 04-FEB-13:20 |
PlantLoopHeatingDemand:Plant | 136.19 | 0.00 | 01-JAN-00:10 | 19000.71 | 04-FEB-13:20 |
WaterSystems:PlantLoopHeatingDemand | 136.19 | 0.00 | 01-JAN-00:10 | 19000.71 | 04-FEB-13:20 |
General:WaterSystems:PlantLoopHeatingDemand | 136.19 | 0.00 | 01-JAN-00:10 | 19000.71 | 04-FEB-13:20 |
EnergyTransfer:HVAC | 378.39 | 0.00 | 01-JAN-00:20 | 57631.73 | 21-JUL-17:10 |
HeatingCoils:EnergyTransfer | 147.45 | 0.00 | 01-JAN-00:20 | 46129.60 | 21-JAN-07:10 |
CoolingCoils:EnergyTransfer | 230.94 | 0.00 | 01-JAN-00:10 | 57631.73 | 21-JUL-17:10 |
WaterSystems:EnergyTransfer | 136.19 | 0.00 | 01-JAN-00:10 | 19000.71 | 04-FEB-13:20 |
WaterUse:WaterSystems:EnergyTransfer | 136.19 | 0.00 | 01-JAN-00:10 | 19000.71 | 04-FEB-13:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 29.170 | -101.285 | 0.000 | 0.000 | 70.674 | 19.580 | 52.814 | 36.059 | 0.000 | 11.362 | 0.000 | 0.000 | -15.479 | 0.000 | -92.245 | -10.651 |
KITCHEN | 0.000 | 0.000 | 0.000 | -285.121 | 0.000 | 0.000 | 4.421 | 25.249 | 212.059 | 0.000 | 0.000 | 0.078 | 46.202 | 0.000 | 0.000 | 0.000 | -2.888 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.688 | 11.981 | 0.000 | 0.000 | 0.000 | -15.670 | -0.000 |
Total Facility | 0.000 | 0.000 | 29.170 | -386.406 | 0.000 | 0.000 | 75.095 | 44.830 | 264.873 | 36.059 | 0.000 | 15.128 | 58.183 | 0.000 | -15.479 | 0.000 | -110.803 | -10.651 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 22-SEP-03:21 | 0.00 | 0.00 | 0.00 | -44934.08 | 0.00 | 0.00 | 0.00 | 161.43 | 508.77 | 0.00 | 0.00 | 0.00 | 45099.19 | 0.00 | -753.54 | 0.00 | -81.77 | 0.00 |
KITCHEN | 10-MAR-04:41 | 0.00 | 0.00 | 0.00 | -64697.61 | 0.00 | 0.00 | 0.00 | 208.16 | 2994.96 | 0.00 | 0.00 | 0.00 | 62003.05 | 0.00 | -0.00 | 0.00 | -508.56 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-SEP-03:21 | 0.00 | 0.00 | 0.00 | -89987.07 | 0.00 | 0.00 | 0.00 | 369.59 | 3503.73 | 0.00 | 0.00 | 346.12 | 86808.83 | 0.00 | -753.54 | 0.00 | -287.66 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 06-FEB-03:01 | 0.00 | 0.00 | 33938.55 | 0.00 | 0.00 | 0.00 | 0.00 | 161.43 | 203.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1626.98 | 0.00 | -941.74 | -31734.76 |
KITCHEN | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-FEB-03:01 | 0.00 | 0.00 | 33938.55 | 0.00 | 0.00 | 0.00 | 0.00 | 369.59 | 2222.04 | 0.00 | 0.00 | 275.56 | 0.00 | 0.00 | -1626.98 | 0.00 | -1982.22 | -33196.53 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.5701 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.8262 | 2.5701 | 0.3215 | 1.0000 | Not calculated | 0.8262 | 0.3215 | ||
PSZ-AC_2:2 | 1.5585 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1017 | 1.5585 | 0.0652 | 1.0000 | Not calculated | 0.1017 | 0.0652 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.5701 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.8262 | 2.5701 | 1.0000 | 1.0000 | Not calculated | 0.8262 | 0.3215 | ||
PSZ-AC_2:2 | 1.5585 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1017 | 1.5585 | 0.1391 | 1.0000 | Not calculated | 0.1017 | 0.0652 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.007112 | 116.17 | 0.8262 | 1.0000 | 0.8262 | 1.000 | 0.8262 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000366 | 116.17 | 0.1017 | 1.0000 | 0.1017 | 1.000 | 0.1017 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.007112 | 116.1715 | 0.8262 | 0.8262 | 0.8262 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000366 | 116.1715 | 0.1017 | 0.1017 | 0.1017 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5701 | 2.5701 | 2.5701 | No | 0.8262 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5585 | 1.5585 | 1.5585 | No | 0.1017 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.5701 | 2.5701 | 2.5701 | 2.5701 | 0.8262 | 1.0000 |
PSZ-AC_2:2 | 1.5585 | 1.5585 | 1.5585 | 1.5585 | 0.1017 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5701 | 2.5701 | 2.5701 | No | 0.8262 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5585 | 1.5585 | 1.5585 | No | 0.1017 | 0.1391 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.5701 | 2.5701 | 2.5701 | 2.5701 | 0.8262 | 1.0000 |
PSZ-AC_2:2 | 1.5585 | 1.5585 | 1.5585 | 1.5585 | 0.1017 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 186.06 | 58207.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 72.00 | 19375.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 44.83 | 2217.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 41.26 | 2625.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.75 | 13060.45 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 156.67 | 5730.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 201.70 | 27213.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 17.86 | 3516.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 17.20 | 1478.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 30.25 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 342.18 | 656.94 |
Natural Gas | 477.16 | 864.91 |
Additional | 0.00 | 0.00 |
Total | 819.34 | 1521.86 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 192.95 |
Space Heating | 0.00 |
Space Cooling | 309.89 |
Fans (All) | 674.30 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1191.68 |
Miscellaneous (All) | 2827.47 |
Subtotal | 2827.47 |
Natural Gas [MJ/m2] | |
Space Heating | 800.80 |
Service Water Heating | 868.10 |
Miscellaneous (All) | 3722.58 |
Subtotal | 3722.58 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.95 |
Space Heating | 12.23 |
Space Cooling | 4.73 |
Fans (All) | 10.29 |
Service Water Heating | 13.25 |
Receptacle Equipment | 49.55 |
Miscellaneous | 7.00 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 5084. | 8760. |
LTG_SCH_KITCHEN | 5084. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3873. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_SETBACK | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_SETBACK | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8553.83 | 206.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 6369.50 | 660.50 | 593.00 | 941.00 | 196.00 |
Min | 6369.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 660.50 | 593.00 | 941.00 | 196.00 |
Average | 7894.44 | 288.89 | 197.67 | 313.67 | 65.33 |
Sum | 23683.33 | 866.67 | 593.00 | 941.00 | 196.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16258.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 90327.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 270983.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8751.17 | 8.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7825.17 | 934.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 6640.67 | 852.50 | 346.17 | 303.67 | 617.00 |
Min | 6640.67 | 8.83 | 0.00 | 0.00 | 0.00 |
Max | 8751.17 | 934.83 | 346.17 | 303.67 | 617.00 |
Average | 7739.00 | 598.72 | 115.39 | 101.22 | 205.67 |
Sum | 23217.00 | 1796.17 | 346.17 | 303.67 | 617.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 254512.33 | 212.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 14328.50 | 1929.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254512.33 | 1929.50 | 0.00 | 0.00 | 0.00 |
Average | 89613.61 | 714.06 | 0.00 | 0.00 | 0.00 |
Sum | 268840.83 | 2142.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:23:52
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Environment
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197422E+10 | 15754.07 | 20-JAN-00:01 | -6.9 | -7.0 | 0.446267E+10 | 3723.61 | 14-JAN-19:00 | -6.9 | -7.0 |
February | 0.207571E+10 | 14076.17 | 06-FEB-00:01 | -4.4 | -6.2 | 0.407138E+10 | 4413.86 | 14-FEB-12:50 | 19.03 | 6.55 |
March | 0.346208E+10 | 11959.14 | 01-MAR-05:51 | 0.00 | -2.4 | 0.468033E+10 | 4681.72 | 25-MAR-18:10 | 17.33 | 5.38 |
April | 0.632374E+10 | 10422.26 | 13-APR-17:04 | 25.92 | 10.22 | 0.482009E+10 | 4681.82 | 29-APR-18:19 | 23.17 | 8.64 |
May | 0.943480E+10 | 30108.10 | 22-MAY-00:10 | 21.83 | 13.88 | 0.518237E+10 | 4681.82 | 27-MAY-18:10 | 24.40 | 12.44 |
June | 0.153120E+11 | 39823.33 | 23-JUN-03:21 | 17.50 | 10.42 | 0.521471E+10 | 4682.20 | 24-JUN-18:00 | 27.20 | 14.79 |
July | 0.183684E+11 | 35704.07 | 21-JUL-03:31 | 21.67 | 12.54 | 0.540697E+10 | 4682.77 | 29-JUL-18:10 | 28.95 | 16.22 |
August | 0.174372E+11 | 35373.54 | 19-AUG-00:26 | 22.50 | 12.19 | 0.545576E+10 | 4682.27 | 19-AUG-18:40 | 29.47 | 15.89 |
September | 0.134510E+11 | 44938.31 | 22-SEP-03:21 | 16.10 | 8.33 | 0.518415E+10 | 4682.19 | 16-SEP-18:19 | 16.10 | 8.33 |
October | 0.851017E+10 | 32909.74 | 02-OCT-00:41 | 19.22 | 12.81 | 0.497544E+10 | 4681.73 | 14-OCT-18:10 | 16.55 | 6.60 |
November | 0.338309E+10 | 12664.97 | 27-NOV-00:01 | -1.7 | -5.1 | 0.435569E+10 | 4343.25 | 09-NOV-12:00 | -1.7 | -5.1 |
December | 0.155418E+10 | 14709.71 | 15-DEC-00:01 | -5.0 | -9.0 | 0.444754E+10 | 3723.62 | 09-DEC-19:19 | -5.0 | -9.0 |
Annual Sum or Average | 0.101287E+12 | 0.582571E+11 | ||||||||
Minimum of Months | 0.155418E+10 | 10422.26 | -6.9 | -9.0 | 0.407138E+10 | 3723.61 | -6.9 | -9.0 | ||
Maximum of Months | 0.183684E+11 | 44938.31 | 25.92 | 13.88 | 0.545576E+10 | 4682.77 | 29.47 | 16.22 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225832E+11 | 29436.41 | 10-JAN-04:31 | -1.7 | -4.3 | 0.774550E+10 | 5138.08 | 05-JAN-11:00 | -1.7 | -4.3 |
February | 0.199126E+11 | 63968.26 | 14-FEB-04:31 | 0.57 | -2.7 | 0.701107E+10 | 5138.30 | 13-FEB-11:39 | 0.57 | -2.7 |
March | 0.217760E+11 | 64704.35 | 10-MAR-04:41 | -0.9 | -4.2 | 0.781814E+10 | 5138.35 | 08-MAR-11:20 | -0.9 | -4.2 |
April | 0.220535E+11 | 58248.68 | 18-APR-03:21 | 7.50 | 0.43 | 0.759262E+10 | 5138.40 | 17-APR-10:00 | 7.50 | 0.43 |
May | 0.238223E+11 | 53816.72 | 12-MAY-03:21 | 10.60 | 3.14 | 0.785962E+10 | 5138.48 | 24-MAY-10:00 | 17.80 | 14.22 |
June | 0.249152E+11 | 51024.64 | 20-JUN-03:21 | 11.15 | 4.86 | 0.761298E+10 | 5138.46 | 05-JUN-10:00 | 11.15 | 4.86 |
July | 0.267874E+11 | 37039.52 | 21-JUL-03:21 | 21.95 | 12.58 | 0.786230E+10 | 5138.46 | 27-JUL-10:50 | 27.43 | 17.91 |
August | 0.268804E+11 | 36677.99 | 29-AUG-03:21 | 16.10 | 12.92 | 0.786760E+10 | 5138.46 | 09-AUG-10:00 | 16.10 | 12.92 |
September | 0.254252E+11 | 45032.13 | 22-SEP-03:21 | 16.10 | 8.33 | 0.761028E+10 | 5138.45 | 25-SEP-10:00 | 22.80 | 14.10 |
October | 0.248693E+11 | 60961.93 | 13-OCT-03:21 | 2.80 | -1.4 | 0.784144E+10 | 5138.45 | 02-OCT-10:50 | 2.80 | -1.4 |
November | 0.228321E+11 | 54669.46 | 10-NOV-04:31 | 5.00 | 2.37 | 0.754968E+10 | 5138.37 | 09-NOV-11:00 | 5.00 | 2.37 |
December | 0.232714E+11 | 29692.60 | 01-DEC-04:31 | 3.70 | -0.6 | 0.773385E+10 | 5138.10 | 01-DEC-11:00 | 10.60 | 4.03 |
Annual Sum or Average | 0.285129E+12 | 0.921051E+11 | ||||||||
Minimum of Months | 0.199126E+11 | 29436.41 | -1.7 | -4.3 | 0.701107E+10 | 5138.08 | -1.7 | -4.3 | ||
Maximum of Months | 0.268804E+11 | 64704.35 | 21.95 | 12.92 | 0.786760E+10 | 5138.48 | 27.43 | 17.91 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 2.30 | -1.2 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.2 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.2 | -5.2 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 2.47 | -0.8 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.8 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.00 | 2.84 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.84 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 14.45 | 4.92 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.92 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.42 | 8.96 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.96 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 21.95 | 14.90 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.90 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 | 16.86 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.86 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 | 14.47 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.47 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 17.33 | 10.88 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.88 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 12.83 | 5.34 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.34 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.13 | 1.84 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.84 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.2 | -5.2 | 0.00 | 0.00 | -3.2 | -5.2 | ||
Maximum of Months | 0.00 | 0.00 | 21.95 | 16.86 | 0.00 | 0.00 | 21.95 | 16.86 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.821373E+10 | 31935.85 | 17-JAN-03:01 | -3.3 |
February | 0.586890E+10 | 33941.77 | 06-FEB-03:01 | -4.9 |
March | 0.269123E+10 | 23152.48 | 04-MAR-03:01 | -0.7 |
April | 0.615562E+09 | 8867.56 | 08-APR-02:62 | 3.30 |
May | 0.111834E+09 | 4671.46 | 06-MAY-06:03 | 5.78 |
June | 21530734.69 | 23016.39 | 27-JUN-02:23 | 21.10 |
July | 79228442.73 | 22277.98 | 22-JUL-03:43 | 20.78 |
August | 70209140.97 | 23477.87 | 19-AUG-02:55 | 21.70 |
September | 12595269.23 | 23634.93 | 22-SEP-03:22 | 16.10 |
October | 0.884857E+09 | 18657.15 | 26-OCT-04:05 | -2.8 |
November | 0.267555E+10 | 12920.17 | 05-NOV-04:04 | 3.30 |
December | 0.792461E+10 | 18785.40 | 28-DEC-05:59 | -2.8 |
Annual Sum or Average | 0.291698E+11 | |||
Minimum of Months | 12595269.23 | 4671.46 | -4.9 | |
Maximum of Months | 0.821373E+10 | 33941.77 | 21.70 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.165449E+10 | 968.56 | 02-JAN-10:09 | 0.598074E+10 | 3934.52 | 01-JAN-11:09 |
February | 0.149855E+10 | 968.56 | 01-FEB-10:09 | 0.540196E+10 | 3934.52 | 01-FEB-11:09 |
March | 0.168084E+10 | 968.56 | 01-MAR-10:09 | 0.598074E+10 | 3934.52 | 01-MAR-11:09 |
April | 0.160761E+10 | 968.56 | 01-APR-16:10 | 0.578781E+10 | 3934.52 | 01-APR-10:09 |
May | 0.166766E+10 | 968.56 | 01-MAY-09:09 | 0.598074E+10 | 3934.52 | 01-MAY-10:09 |
June | 0.162466E+10 | 968.56 | 01-JUN-09:09 | 0.578781E+10 | 3934.52 | 01-JUN-10:09 |
July | 0.165081E+10 | 968.56 | 01-JUL-16:10 | 0.598074E+10 | 3934.52 | 01-JUL-10:09 |
August | 0.168084E+10 | 968.56 | 01-AUG-09:09 | 0.598074E+10 | 3934.52 | 01-AUG-10:09 |
September | 0.160800E+10 | 968.56 | 01-SEP-09:09 | 0.578781E+10 | 3934.52 | 01-SEP-10:09 |
October | 0.165430E+10 | 968.56 | 02-OCT-09:09 | 0.598074E+10 | 3934.52 | 01-OCT-10:09 |
November | 0.160161E+10 | 968.56 | 01-NOV-09:09 | 0.578781E+10 | 3934.52 | 01-NOV-10:09 |
December | 0.165100E+10 | 968.56 | 01-DEC-10:09 | 0.598074E+10 | 3934.52 | 01-DEC-11:09 |
Annual Sum or Average | 0.195804E+11 | 0.704184E+11 | ||||
Minimum of Months | 0.149855E+10 | 968.56 | 0.540196E+10 | 3934.52 | ||
Maximum of Months | 0.168084E+10 | 968.56 | 0.598074E+10 | 3934.52 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.213351E+10 | 1248.98 | 02-JAN-10:09 | 0.175350E+11 | 10493.51 | 01-JAN-11:09 |
February | 0.193243E+10 | 1248.98 | 01-FEB-10:09 | 0.158380E+11 | 10493.51 | 01-FEB-11:09 |
March | 0.216749E+10 | 1248.98 | 01-MAR-10:09 | 0.175350E+11 | 10493.51 | 01-MAR-11:09 |
April | 0.207306E+10 | 1248.98 | 01-APR-16:10 | 0.169693E+11 | 10493.51 | 01-APR-10:09 |
May | 0.215050E+10 | 1248.98 | 01-MAY-09:09 | 0.175350E+11 | 10493.51 | 01-MAY-10:09 |
June | 0.209504E+10 | 1248.98 | 01-JUN-09:09 | 0.169693E+11 | 10493.51 | 01-JUN-10:09 |
July | 0.212877E+10 | 1248.98 | 01-JUL-16:10 | 0.175350E+11 | 10493.51 | 01-JUL-10:09 |
August | 0.216749E+10 | 1248.98 | 01-AUG-09:09 | 0.175350E+11 | 10493.51 | 01-AUG-10:09 |
September | 0.207356E+10 | 1248.98 | 01-SEP-09:09 | 0.169693E+11 | 10493.51 | 01-SEP-10:09 |
October | 0.213326E+10 | 1248.98 | 02-OCT-09:09 | 0.175350E+11 | 10493.51 | 01-OCT-10:09 |
November | 0.206532E+10 | 1248.98 | 01-NOV-09:09 | 0.169693E+11 | 10493.51 | 01-NOV-10:09 |
December | 0.212902E+10 | 1248.98 | 01-DEC-10:09 | 0.175350E+11 | 10493.51 | 01-DEC-11:09 |
Annual Sum or Average | 0.252494E+11 | 0.206460E+12 | ||||
Minimum of Months | 0.193243E+10 | 1248.98 | 0.158380E+11 | 10493.51 | ||
Maximum of Months | 0.216749E+10 | 1248.98 | 0.175350E+11 | 10493.51 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.165449E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166067E+11 |
February | 0.852256E+10 | 0.149855E+10 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133821E+11 |
March | 0.954557E+10 | 0.168084E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105217E+11 |
April | 0.915225E+10 | 0.160761E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50946027.48 | 0.621348E+10 |
May | 0.947560E+10 | 0.166766E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546120E+09 | 0.378781E+10 |
June | 0.922788E+10 | 0.162466E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308829E+10 | 0.146387E+10 |
July | 0.939996E+10 | 0.165081E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383964E+10 | 0.586497E+09 |
August | 0.954557E+10 | 0.168084E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275432E+10 | 0.964754E+09 |
September | 0.915225E+10 | 0.160800E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937648E+09 | 0.226878E+10 |
October | 0.940563E+10 | 0.165430E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144964E+09 | 0.708145E+10 |
November | 0.909363E+10 | 0.160161E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120680E+11 |
December | 0.939996E+10 | 0.165100E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172999E+11 |
Annual Sum or Average | 0.111326E+12 | 0.195804E+11 | 0.704184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113619E+11 | 0.922450E+11 |
Minimum of Months | 0.852256E+10 | 0.149855E+10 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586497E+09 |
Maximum of Months | 0.954557E+10 | 0.168084E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383964E+10 | 0.172999E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.213351E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380536E+09 |
February | 0.610713E+09 | 0.193243E+10 | 0.120792E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369514E+09 |
March | 0.684021E+09 | 0.216749E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408036E+09 |
April | 0.655836E+09 | 0.207306E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261338E+09 |
May | 0.679007E+09 | 0.215050E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 2859730.14 | 0.209387E+09 |
June | 0.661256E+09 | 0.209504E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 23704554.69 | 0.112717E+09 |
July | 0.673587E+09 | 0.212877E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 30319276.99 | 58961736.46 |
August | 0.684021E+09 | 0.216749E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 16372294.96 | 83700921.52 |
September | 0.655836E+09 | 0.207356E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 3981788.77 | 0.121294E+09 |
October | 0.673993E+09 | 0.213326E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 442298.16 | 0.217498E+09 |
November | 0.651635E+09 | 0.206532E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326287E+09 |
December | 0.673587E+09 | 0.212902E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338645E+09 |
Annual Sum or Average | 0.797748E+10 | 0.252494E+11 | 0.157461E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 77679943.71 | 0.288791E+10 |
Minimum of Months | 0.610713E+09 | 0.193243E+10 | 0.120792E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58961736.46 |
Maximum of Months | 0.684021E+09 | 0.216749E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 30319276.99 | 0.408036E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344897E+09 | 0.819291E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279907E+09 | 0.999739E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295195E+09 | 0.126189E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318867E+09 | 0.161572E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308007E+09 | 0.170983E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270029E+09 | 0.164988E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245542E+09 | 0.170750E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219934E+09 | 0.167415E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288375E+09 | 0.136255E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354767E+09 | 0.114197E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361010E+09 | 0.910193E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401951E+09 | 0.817227E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368848E+10 | 0.156699E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219934E+09 | 0.817227E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401951E+09 | 0.170983E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 968.56 | 02-JAN-10:09 | 3934.52 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 21990.63 | 19-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 968.56 | 01-FEB-10:09 | 3934.52 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 19955.19 | 04-FEB-19:55 |
March | 9454.80 | 04-MAR-19:10 | 968.56 | 01-MAR-10:09 | 3934.52 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 14782.41 | 04-MAR-19:55 |
April | 9454.80 | 01-APR-18:10 | 968.56 | 01-APR-16:10 | 3934.52 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1498.50 | 13-APR-17:02 | 11949.65 | 15-APR-18:02 |
May | 9454.80 | 06-MAY-18:10 | 968.56 | 01-MAY-09:09 | 3934.52 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4391.87 | 19-MAY-17:10 | 9522.60 | 01-MAY-20:00 |
June | 9454.80 | 03-JUN-18:10 | 968.56 | 01-JUN-09:09 | 3934.52 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9531.90 | 28-JUN-17:02 | 7859.61 | 08-JUN-20:00 |
July | 9454.80 | 01-JUL-18:10 | 968.56 | 01-JUL-16:10 | 3934.52 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9695.42 | 21-JUL-17:10 | 4263.94 | 07-JUL-17:53 |
August | 9454.80 | 05-AUG-18:10 | 968.56 | 01-AUG-09:09 | 3934.52 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6809.49 | 04-AUG-17:10 | 5152.23 | 25-AUG-20:00 |
September | 9454.80 | 02-SEP-18:10 | 968.56 | 01-SEP-09:09 | 3934.52 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4556.52 | 20-SEP-17:10 | 6427.11 | 23-SEP-18:55 |
October | 9454.80 | 07-OCT-18:10 | 968.56 | 02-OCT-09:09 | 3934.52 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.10 | 10-OCT-13:00 | 15478.44 | 24-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 968.56 | 01-NOV-09:09 | 3934.52 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 15699.07 | 27-NOV-21:00 |
December | 9454.80 | 02-DEC-19:10 | 968.56 | 01-DEC-10:09 | 3934.52 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 19765.07 | 09-DEC-19:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 968.56 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4263.94 | |||||
Maximum of Months | 9454.80 | 968.56 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 9695.42 | 21990.63 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 1248.98 | 02-JAN-10:09 | 7755.73 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1427.14 | 17-JAN-04:10 |
February | 677.52 | 04-FEB-19:10 | 1248.98 | 01-FEB-10:09 | 7755.73 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1399.96 | 05-FEB-02:00 |
March | 677.52 | 04-MAR-19:10 | 1248.98 | 01-MAR-10:09 | 7755.73 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1612.88 | 14-MAR-03:20 |
April | 677.52 | 01-APR-18:10 | 1248.98 | 01-APR-16:10 | 7755.73 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 1624.55 | 23-APR-04:00 |
May | 677.52 | 06-MAY-18:10 | 1248.98 | 01-MAY-09:09 | 7755.73 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 45.08 | 19-MAY-14:53 | 1119.75 | 18-MAY-03:20 |
June | 677.52 | 03-JUN-18:10 | 1248.98 | 01-JUN-09:09 | 7755.73 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 102.72 | 17-JUN-15:53 | 901.95 | 02-JUN-04:00 |
July | 677.52 | 01-JUL-18:10 | 1248.98 | 01-JUL-16:10 | 7755.73 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 113.91 | 04-JUL-14:53 | 374.74 | 05-JUL-03:20 |
August | 677.52 | 05-AUG-18:10 | 1248.98 | 01-AUG-09:09 | 7755.73 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 121.34 | 21-AUG-00:27 | 522.05 | 08-AUG-00:40 |
September | 677.52 | 02-SEP-18:10 | 1248.98 | 01-SEP-09:09 | 7755.73 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 37.40 | 03-SEP-15:00 | 654.83 | 08-SEP-02:00 |
October | 677.52 | 07-OCT-18:10 | 1248.98 | 02-OCT-09:09 | 7755.73 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 14.34 | 01-OCT-15:53 | 924.86 | 12-OCT-04:00 |
November | 677.52 | 04-NOV-18:10 | 1248.98 | 01-NOV-09:09 | 7755.73 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1564.41 | 26-NOV-05:00 |
December | 677.52 | 02-DEC-19:10 | 1248.98 | 01-DEC-10:09 | 7755.73 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2129.69 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 1248.98 | 7755.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 374.74 | ||||||
Maximum of Months | 677.52 | 1248.98 | 7755.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 121.34 | 2129.69 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.50 | 11-JAN-00:01 | 1536.70 | 27-JAN-12:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.39 | 14-FEB-07:23 | 1921.37 | 04-FEB-13:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.63 | 08-MAR-05:00 | 2129.60 | 11-MAR-12:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.12 | 01-APR-04:00 | 2694.18 | 08-APR-13:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 606.06 | 09-MAY-03:51 | 2503.66 | 28-MAY-13:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.72 | 20-JUN-01:51 | 2318.73 | 03-JUN-13:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.51 | 23-JUL-05:00 | 2253.44 | 28-JUL-13:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.63 | 17-AUG-04:00 | 2217.76 | 03-AUG-13:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.93 | 27-SEP-23:00 | 2110.48 | 13-SEP-12:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.16 | 29-OCT-22:00 | 2261.45 | 26-OCT-13:30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.78 | 12-NOV-23:00 | 1791.16 | 12-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.22 | 13-DEC-01:55 | 1713.71 | 22-DEC-13:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.63 | 1536.70 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.50 | 2694.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15754.07 | 20-JAN-00:01 | 4202.13 | 1291.41 | 3256.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14076.17 | 06-FEB-00:01 | 4202.13 | 1291.41 | 3256.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.81 |
March | 11959.14 | 01-MAR-05:51 | 5252.67 | 2152.35 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10422.26 | 13-APR-17:04 | 42021.33 | 4842.79 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1498.50 | 0.00 |
May | 30108.10 | 22-MAY-00:10 | 0.00 | 1452.84 | 2442.12 | 0.00 | 0.00 | 0.00 | 0.00 | 10.57 | 0.00 |
June | 39823.33 | 23-JUN-03:21 | 0.00 | 1614.26 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.28 |
July | 35704.07 | 21-JUL-03:31 | 0.00 | 1614.26 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 |
August | 35373.54 | 19-AUG-00:26 | 0.00 | 1614.26 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 10.57 | 0.00 |
September | 44938.31 | 22-SEP-03:21 | 0.00 | 1614.26 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.77 |
October | 32909.74 | 02-OCT-00:41 | 0.00 | 1291.41 | 2170.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 |
November | 12664.97 | 27-NOV-00:01 | 4202.13 | 1291.41 | 3256.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.06 |
December | 14709.71 | 15-DEC-00:01 | 4202.13 | 1291.41 | 3256.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10422.26 | 0.00 | 1291.41 | 2170.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44938.31 | 42021.33 | 4842.79 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1498.50 | 178.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29436.41 | 10-JAN-04:31 | 0.00 | 1457.15 | 17282.92 | 9652.92 | 0.00 | 0.00 | 0.00 | 0.00 | 514.84 |
February | 63968.26 | 14-FEB-04:31 | 0.00 | 2081.64 | 24689.89 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 64704.35 | 10-MAR-04:41 | 0.00 | 1873.47 | 22220.90 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 508.56 |
April | 58248.68 | 18-APR-03:21 | 0.00 | 2081.64 | 24689.89 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 348.49 |
May | 53816.72 | 12-MAY-03:21 | 0.00 | 2081.64 | 24689.89 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 118.38 |
June | 51024.64 | 20-JUN-03:21 | 0.00 | 2081.64 | 24689.89 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 68.15 |
July | 37039.52 | 21-JUL-03:21 | 0.00 | 2081.64 | 24689.89 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 95.93 |
August | 36677.99 | 29-AUG-03:21 | 0.00 | 2081.64 | 24689.89 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 235.42 |
September | 45032.13 | 22-SEP-03:21 | 0.00 | 2081.64 | 24689.89 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 205.89 |
October | 60961.93 | 13-OCT-03:21 | 0.00 | 2081.64 | 24689.89 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 403.92 |
November | 54669.46 | 10-NOV-04:31 | 0.00 | 2081.64 | 24689.89 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 311.63 |
December | 29692.60 | 01-DEC-04:31 | 0.00 | 1873.47 | 22220.90 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 261.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 29436.41 | 0.00 | 1457.15 | 17282.92 | 9652.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 64704.35 | 0.00 | 2081.64 | 24689.89 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 514.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.77 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.55 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.84 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.47 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.04 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.42 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.87 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.49 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.15 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.65 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.97 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.47 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.496455E+11 | 26865.60 | 05-JAN-11:09 | 0.104739E+12 | 82271.74 | 20-JAN-11:20 |
February | 0.447760E+11 | 26898.65 | 15-FEB-11:09 | 0.880855E+11 | 78010.27 | 05-FEB-08:09 |
March | 0.497311E+11 | 27677.98 | 08-MAR-13:00 | 0.788271E+11 | 68977.30 | 21-MAR-12:30 |
April | 0.501543E+11 | 31381.72 | 13-APR-16:00 | 0.640088E+11 | 60521.78 | 06-APR-10:30 |
May | 0.552588E+11 | 35306.84 | 23-MAY-10:00 | 0.598821E+11 | 54215.40 | 05-MAY-10:20 |
June | 0.618966E+11 | 42315.68 | 28-JUN-16:10 | 0.548827E+11 | 48080.73 | 01-JUN-12:00 |
July | 0.694904E+11 | 41528.66 | 21-JUL-17:10 | 0.557732E+11 | 47274.08 | 02-JUL-12:20 |
August | 0.668064E+11 | 39837.57 | 17-AUG-11:09 | 0.556606E+11 | 47022.11 | 31-AUG-12:30 |
September | 0.580299E+11 | 37010.92 | 03-SEP-10:20 | 0.543177E+11 | 47633.47 | 29-SEP-12:50 |
October | 0.530910E+11 | 35104.24 | 11-OCT-10:00 | 0.651207E+11 | 71922.19 | 25-OCT-12:00 |
November | 0.483911E+11 | 26923.64 | 01-NOV-10:20 | 0.783503E+11 | 68182.06 | 04-NOV-12:20 |
December | 0.496711E+11 | 26863.41 | 01-DEC-11:09 | 0.105267E+12 | 81764.24 | 21-DEC-13:20 |
Annual Sum or Average | 0.656942E+12 | 0.864915E+12 | ||||
Minimum of Months | 0.447760E+11 | 26863.41 | 0.543177E+11 | 47022.11 | ||
Maximum of Months | 0.694904E+11 | 42315.68 | 0.105267E+12 | 82271.74 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.378800E+10 | 0.411213E+10 | 0.235157E+11 | 0.00 | 0.129804E+11 | 0.79 | 0.00 | 2454085.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.343098E+10 | 0.350240E+10 | 0.212400E+11 | 0.00 | 0.117535E+11 | 0.72 | 0.00 | 62380587.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384832E+10 | 0.357172E+10 | 0.235157E+11 | 0.00 | 0.131936E+11 | 0.80 | 0.00 | 0.128556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.368067E+10 | 0.314318E+10 | 0.227571E+11 | 0.00 | 0.128585E+11 | 0.77 | 0.00 | 0.230910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.381816E+10 | 0.298090E+10 | 0.235157E+11 | 0.00 | 0.133616E+11 | 0.80 | 0.00 | 0.590709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.371970E+10 | 0.274299E+10 | 0.227571E+11 | 0.00 | 0.130594E+11 | 0.77 | 0.00 | 0.140739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.377958E+10 | 0.290842E+10 | 0.235157E+11 | 0.00 | 0.136349E+11 | 0.79 | 0.00 | 0.198954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.384832E+10 | 0.312742E+10 | 0.235157E+11 | 0.00 | 0.136494E+11 | 0.80 | 0.00 | 0.168964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.368156E+10 | 0.332436E+10 | 0.227571E+11 | 0.00 | 0.130868E+11 | 0.77 | 0.00 | 0.961888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.378756E+10 | 0.375291E+10 | 0.235157E+11 | 0.00 | 0.133433E+11 | 0.79 | 0.00 | 0.307716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.366693E+10 | 0.390573E+10 | 0.227571E+11 | 0.00 | 0.127750E+11 | 0.77 | 0.00 | 26875740.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.378002E+10 | 0.418775E+10 | 0.235157E+11 | 0.00 | 0.129722E+11 | 0.79 | 0.00 | 3231477.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448298E+11 | 0.412599E+11 | 0.276879E+12 | 0.00 | 0.156669E+12 | 9.37 | 0.00 | 0.720015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.343098E+10 | 0.274299E+10 | 0.212400E+11 | 0.00 | 0.117535E+11 | 0.72 | 0.00 | 2454085.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.384832E+10 | 0.418775E+10 | 0.235157E+11 | 0.00 | 0.136494E+11 | 0.80 | 0.00 | 0.198954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.450809E+11 | 0.00 | 0.191328E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.340934E+11 | 0.00 | 0.173882E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.194681E+11 | 0.00 | 0.188332E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.745644E+10 | 0.00 | 0.173339E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.250921E+10 | 0.00 | 0.168472E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.328555E+09 | 0.00 | 0.153357E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 93953076.77 | 0.00 | 0.151535E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 85324101.53 | 0.00 | 0.150496E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.162428E+09 | 0.00 | 0.149368E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.826520E+10 | 0.00 | 0.163297E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.222441E+11 | 0.00 | 0.168878E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.462721E+11 | 0.00 | 0.184689E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.186060E+12 | 0.00 | 0.201697E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 85324101.53 | 0.00 | 0.149368E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.462721E+11 | 0.00 | 0.191328E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2217.54 | 02-JAN-10:09 | 2625.88 | 01-JAN-00:10 | 14428.03 | 01-JAN-11:09 | 0.00 | 5730.62 | 01-JAN-00:40 | 0.00 | 06-JAN-11:39 | 0.00 | 01-JAN-00:10 |
February | 2217.54 | 01-FEB-10:09 | 2625.88 | 01-FEB-00:10 | 14428.03 | 01-FEB-11:09 | 0.00 | 5730.62 | 02-FEB-14:50 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 2217.54 | 01-MAR-10:09 | 2625.88 | 01-MAR-00:10 | 14428.03 | 01-MAR-11:09 | 0.00 | 5730.62 | 01-MAR-00:49 | 0.00 | 02-MAR-08:39 | 0.00 | 01-MAR-00:10 |
April | 2217.54 | 01-APR-16:10 | 2625.88 | 01-APR-00:10 | 14428.03 | 01-APR-10:09 | 0.00 | 5730.62 | 01-APR-05:49 | 0.00 | 02-APR-08:30 | 0.00 | 01-APR-00:10 |
May | 2217.54 | 01-MAY-09:09 | 2625.88 | 01-MAY-00:10 | 14428.03 | 01-MAY-10:09 | 0.00 | 5730.62 | 01-MAY-06:49 | 0.00 | 07-MAY-06:00 | 0.00 | 01-MAY-00:10 |
June | 2217.54 | 01-JUN-09:09 | 2625.88 | 01-JUN-00:10 | 14428.03 | 01-JUN-10:09 | 0.00 | 5730.62 | 01-JUN-20:00 | 0.00 | 03-JUN-14:30 | 0.00 | 01-JUN-00:10 |
July | 2217.54 | 01-JUL-16:10 | 2625.88 | 01-JUL-00:10 | 14428.03 | 01-JUL-10:09 | 0.00 | 5730.62 | 01-JUL-23:30 | 0.00 | 07-JUL-07:40 | 0.00 | 01-JUL-00:10 |
August | 2217.54 | 01-AUG-09:09 | 2625.88 | 01-AUG-00:10 | 14428.03 | 01-AUG-10:09 | 0.00 | 5730.62 | 01-AUG-21:40 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 2217.54 | 01-SEP-09:09 | 2625.88 | 01-SEP-00:10 | 14428.03 | 01-SEP-10:09 | 0.00 | 5730.62 | 01-SEP-16:00 | 0.00 | 28-SEP-07:00 | 0.00 | 01-SEP-00:10 |
October | 2217.54 | 02-OCT-09:09 | 2625.88 | 01-OCT-00:10 | 14428.03 | 01-OCT-10:09 | 0.00 | 5730.62 | 01-OCT-20:49 | 0.00 | 20-OCT-10:39 | 0.00 | 01-OCT-00:10 |
November | 2217.54 | 01-NOV-09:09 | 2625.88 | 01-NOV-00:10 | 14428.03 | 01-NOV-10:09 | 0.00 | 5730.62 | 01-NOV-18:40 | 0.00 | 08-NOV-10:30 | 0.00 | 01-NOV-00:10 |
December | 2217.54 | 01-DEC-10:09 | 2625.88 | 01-DEC-00:10 | 14428.03 | 01-DEC-11:09 | 0.00 | 5730.62 | 12-DEC-14:09 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2217.54 | 2625.88 | 14428.03 | 0.00 | 5730.62 | 0.00 | 0.00 | ||||||
Maximum of Months | 2217.54 | 2625.88 | 14428.03 | 0.00 | 5730.62 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 280.70 | 13-JAN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3302.08 | 14-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5006.80 | 08-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8672.85 | 13-APR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11756.31 | 19-MAY-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19267.82 | 28-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 19375.69 | 21-JUL-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15658.58 | 17-AUG-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13608.21 | 03-SEP-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11186.29 | 10-OCT-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1446.12 | 08-NOV-03:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 284.81 | 05-DEC-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 280.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19375.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 26865.60 | 05-JAN-11:09 | 2217.54 | 14428.03 | 0.00 | 0.00 | 5730.62 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26898.65 | 15-FEB-11:09 | 2217.54 | 14428.03 | 0.00 | 0.00 | 5730.62 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27677.98 | 08-MAR-13:00 | 2217.54 | 12626.59 | 0.00 | 0.00 | 5730.62 | 0.00 | 0.00 | 5006.80 | 0.00 |
April | 31381.72 | 13-APR-16:00 | 2217.54 | 13076.95 | 0.00 | 0.00 | 5730.62 | 0.00 | 0.00 | 8342.46 | 0.00 |
May | 35306.84 | 23-MAY-10:00 | 2217.54 | 14428.03 | 0.00 | 0.00 | 5730.62 | 0.00 | 0.00 | 10028.59 | 0.00 |
June | 42315.68 | 28-JUN-16:10 | 2217.54 | 13076.95 | 0.00 | 0.00 | 5730.62 | 0.00 | 0.00 | 19267.82 | 0.00 |
July | 41528.66 | 21-JUL-17:10 | 2217.54 | 12176.23 | 0.00 | 0.00 | 5730.62 | 0.00 | 0.00 | 19375.69 | 0.00 |
August | 39837.57 | 17-AUG-11:09 | 2217.54 | 13527.31 | 0.00 | 0.00 | 5730.62 | 0.00 | 0.00 | 15448.79 | 0.00 |
September | 37010.92 | 03-SEP-10:20 | 1724.75 | 14428.03 | 0.00 | 0.00 | 5730.62 | 0.00 | 0.00 | 10609.62 | 0.00 |
October | 35104.24 | 11-OCT-10:00 | 2217.54 | 14428.03 | 0.00 | 0.00 | 5730.62 | 0.00 | 0.00 | 9823.43 | 0.00 |
November | 26923.64 | 01-NOV-10:20 | 2217.54 | 14428.03 | 0.00 | 0.00 | 5730.62 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26863.41 | 01-DEC-11:09 | 2217.54 | 14428.03 | 0.00 | 0.00 | 5730.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 26863.41 | 1724.75 | 12176.23 | 0.00 | 0.00 | 5730.62 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42315.68 | 2217.54 | 14428.03 | 0.00 | 0.00 | 5730.62 | 0.00 | 0.00 | 19375.69 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 58207.70 | 21-JAN-07:10 | 0.00 | 27200.47 | 31-JAN-13:20 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 55663.41 | 05-FEB-07:10 | 0.00 | 27213.89 | 05-FEB-13:39 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 43488.86 | 05-MAR-07:10 | 0.00 | 27095.89 | 01-MAR-13:20 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 27119.85 | 08-APR-06:10 | 0.00 | 26672.61 | 01-APR-12:39 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 18305.75 | 06-MAY-06:10 | 0.00 | 25980.49 | 01-MAY-12:50 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 9808.06 | 09-JUN-06:10 | 0.00 | 25097.58 | 01-JUN-12:00 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 6345.10 | 21-JUL-02:20 | 0.00 | 24290.93 | 02-JUL-12:20 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 5927.95 | 19-AUG-02:30 | 0.00 | 24038.96 | 31-AUG-12:30 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 5897.86 | 09-SEP-06:10 | 0.00 | 24650.32 | 29-SEP-12:50 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 37415.80 | 26-OCT-06:00 | 0.00 | 25563.90 | 31-OCT-12:39 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 42378.84 | 27-NOV-07:10 | 0.00 | 26360.53 | 30-NOV-13:20 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 54848.19 | 15-DEC-07:10 | 0.00 | 26938.91 | 31-DEC-13:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 5897.86 | 0.00 | 24038.96 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 58207.70 | 0.00 | 27213.89 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.33 | 20.25 | 0.17 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
February | 10.33 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
March | 5.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
April | 0.50 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 24.57 | 0.00 | 24.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 24.61 | 0.00 | 24.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 24.66 | 0.00 | 24.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 24.64 | 0.00 | 24.64 |
October | 0.17 | 20.55 | 0.00 | 20.55 | 8.00 | 24.56 | 0.00 | 24.56 |
November | 1.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
December | 9.67 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Annual Sum or Average | 39.50 | 20.27 | 0.17 | 20.27 | 77.00 | 23.15 | 0.00 | 23.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.33 | 20.55 | 0.17 | 20.55 | 22.83 | 24.66 | 0.00 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.10 | 0.00 | 27.10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.29 | 0.00 | 27.29 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 27.57 | 0.00 | 27.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 | 28.35 | 0.00 | 28.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.70 | 0.00 | 28.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 28.84 | 0.00 | 28.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.87 | 0.00 | 28.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.91 | 0.00 | 28.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 29.14 | 0.00 | 29.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 28.72 | 0.00 | 28.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 27.77 | 0.00 | 27.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.30 | 0.00 | 27.30 |
Annual Sum or Average | 0.00 | 0.00 | 287.67 | 28.45 | 0.00 | 28.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.10 | 0.00 | 27.10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 29.14 | 0.00 | 29.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 609.67 | 20.90 | 153.00 | 20.72 | 153.00 | 20.61 |
February | 533.17 | 20.90 | 114.83 | 20.72 | 114.83 | 20.60 |
March | 554.83 | 21.13 | 79.33 | 20.94 | 79.33 | 20.79 |
April | 392.00 | 21.49 | 57.83 | 21.53 | 29.00 | 21.43 |
May | 266.83 | 21.80 | 182.83 | 22.57 | 8.00 | 22.52 |
June | 85.50 | 21.88 | 408.67 | 23.53 | 0.00 | 23.53 |
July | 91.83 | 23.84 | 595.00 | 23.88 | 91.83 | 23.87 |
August | 75.67 | 23.50 | 590.33 | 23.82 | 67.00 | 23.81 |
September | 104.50 | 22.29 | 469.17 | 23.55 | 28.00 | 23.53 |
October | 333.83 | 21.26 | 217.00 | 22.15 | 17.33 | 22.06 |
November | 576.17 | 21.01 | 57.83 | 20.84 | 55.00 | 20.69 |
December | 609.00 | 20.85 | 133.67 | 20.68 | 133.67 | 20.56 |
Annual Sum or Average | 4233.00 | 21.24 | 3059.50 | 22.01 | 777.00 | 21.89 |
Minimum of Months | 75.67 | 20.85 | 57.83 | 20.68 | 0.00 | 20.56 |
Maximum of Months | 609.67 | 23.84 | 595.00 | 23.88 | 153.00 | 23.87 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 425.67 | 19.56 | 266.50 | 20.47 | 127.00 | 20.18 |
February | 361.33 | 20.02 | 253.17 | 21.19 | 102.67 | 20.95 |
March | 310.67 | 22.19 | 367.83 | 23.84 | 107.83 | 24.02 |
April | 354.00 | 25.05 | 482.67 | 25.47 | 279.00 | 25.63 |
May | 442.00 | 25.96 | 583.33 | 25.94 | 427.00 | 25.99 |
June | 531.67 | 26.11 | 592.00 | 26.09 | 531.67 | 26.09 |
July | 608.50 | 26.11 | 609.00 | 26.11 | 608.50 | 26.11 |
August | 612.00 | 26.11 | 612.00 | 26.11 | 612.00 | 26.11 |
September | 560.00 | 26.11 | 590.00 | 26.09 | 560.00 | 26.10 |
October | 451.17 | 25.30 | 515.83 | 25.54 | 386.67 | 25.69 |
November | 313.50 | 22.17 | 337.33 | 23.58 | 114.67 | 23.83 |
December | 482.67 | 19.85 | 205.67 | 20.09 | 137.17 | 19.87 |
Annual Sum or Average | 5453.17 | 24.04 | 5415.33 | 24.68 | 3994.17 | 24.87 |
Minimum of Months | 310.67 | 19.56 | 205.67 | 20.09 | 102.67 | 19.87 |
Maximum of Months | 612.00 | 26.11 | 612.00 | 26.11 | 612.00 | 26.11 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.89726 | 17.96120 | -0.4686 | 11.03496 |
February | 551.00000 | 20.99837 | 19.86461 | -0.4244 | 10.49393 |
March | 612.00000 | 21.38880 | 19.99432 | -0.3081 | 9.08808 |
April | 590.00000 | 22.29193 | 17.02521 | -0.0668 | 7.70941 |
May | 611.00000 | 22.94990 | 24.94867 | -0.7847 | 21.57688 |
June | 592.00000 | 23.56911 | 32.63582 | -0.4603 | 11.26668 |
July | 609.00000 | 23.87985 | 45.07298 | -0.2340 | 6.51822 |
August | 612.00000 | 23.82567 | 44.47469 | -0.2379 | 6.80918 |
September | 590.00000 | 23.55348 | 39.44237 | -0.3721 | 9.80334 |
October | 610.00000 | 22.39929 | 26.47409 | 0.08902 | 8.48908 |
November | 591.00000 | 21.06524 | 20.26729 | -0.3216 | 8.55578 |
December | 609.00000 | 20.84734 | 15.93351 | -0.4726 | 10.89612 |
Annual Sum or Average | 7187.00000 | 22.31317 | 27.06509 | -0.3382 | 10.19460 |
Minimum of Months | 551.00000 | 20.84734 | 15.93351 | -0.7847 | 6.51822 |
Maximum of Months | 612.00000 | 23.87985 | 45.07298 | 0.08902 | 21.57688 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 21.03962 | 28.86527 | -0.1453 | 11.93913 |
February | 551.00000 | 21.62215 | 29.63287 | -0.0174 | 12.53220 |
March | 612.00000 | 23.55640 | 26.30106 | 0.41021 | 14.85378 |
April | 590.00000 | 25.05500 | 20.90449 | 0.74902 | 20.19675 |
May | 611.00000 | 25.77035 | 26.40769 | 0.37329 | 10.51493 |
June | 592.00000 | 26.06780 | 34.01185 | 0.59254 | 13.21975 |
July | 609.00000 | 26.11200 | 44.58232 | 0.72274 | 16.54451 |
August | 612.00000 | 26.11142 | 43.59043 | 0.71651 | 16.35299 |
September | 590.00000 | 26.07987 | 38.19674 | 0.64803 | 14.53140 |
October | 610.00000 | 25.05841 | 28.57352 | 0.85771 | 24.78716 |
November | 591.00000 | 23.18573 | 27.18217 | 0.37613 | 14.32104 |
December | 609.00000 | 20.67117 | 27.32470 | -0.2204 | 10.84164 |
Annual Sum or Average | 7187.00000 | 24.20640 | 31.32529 | 0.42381 | 15.06735 |
Minimum of Months | 551.00000 | 20.67117 | 20.90449 | -0.2204 | 10.51493 |
Maximum of Months | 612.00000 | 26.11200 | 44.58232 | 0.85771 | 24.78716 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 74592444.04 | 26075174.10 | 7.17 | 74592444.04 | 0.00 | 0.00 | 0.15 | 14-FEB-15:53 | 0.00 | 01-FEB-00:01 | 5145.23 | 14-FEB-15:53 | 5145.23 | 14-FEB-15:53 | 0.00 | 14-FEB-15:50 | 1779.27 | 14-FEB-15:53 | 0.00 | 01-FEB-00:01 |
March | 0.125676E+09 | 43754892.86 | 14.06 | 0.125676E+09 | 0.00 | 0.00 | 0.22 | 08-MAR-14:00 | 0.00 | 01-MAR-00:01 | 7670.84 | 08-MAR-14:00 | 7670.84 | 08-MAR-14:00 | 0.00 | 08-MAR-13:40 | 2608.95 | 08-MAR-14:00 | 0.00 | 01-MAR-00:01 |
April | 0.310958E+10 | 0.105102E+10 | 134.68 | 0.310954E+10 | 32988.69 | 0.00 | 0.41 | 13-APR-17:02 | 0.00 | 01-APR-00:01 | 14905.22 | 13-APR-17:02 | 14905.22 | 13-APR-17:02 | 22.21 | 14-APR-19:20 | 4841.02 | 13-APR-17:02 | 0.00 | 01-APR-00:01 |
May | 0.866649E+10 | 0.287158E+10 | 265.13 | 0.858288E+10 | 83616401.06 | 0.00 | 1.00 | 22-MAY-00:10 | 0.00 | 01-MAY-00:01 | 43254.87 | 22-MAY-00:10 | 36137.80 | 22-MAY-00:10 | 7117.07 | 22-MAY-00:10 | 11940.06 | 22-MAY-00:10 | 0.00 | 01-MAY-00:01 |
June | 0.225668E+11 | 0.744902E+10 | 431.84 | 0.220261E+11 | 0.540726E+09 | 0.00 | 1.00 | 07-JUN-00:09 | 0.00 | 01-JUN-00:01 | 43254.87 | 24-JUN-01:38 | 43254.87 | 27-JUN-00:51 | 9501.22 | 24-JUN-03:07 | 11940.06 | 07-JUN-00:09 | 0.00 | 01-JUN-00:01 |
July | 0.323782E+11 | 0.105289E+11 | 548.37 | 0.285909E+11 | 0.378722E+10 | 0.00 | 1.00 | 01-JUL-00:08 | 0.00 | 01-JUL-00:01 | 45196.36 | 01-JUL-01:21 | 43254.87 | 19-JUL-00:11 | 24170.03 | 01-JUL-01:21 | 12089.36 | 01-JUL-01:21 | 0.00 | 01-JUL-00:01 |
August | 0.273619E+11 | 0.883185E+10 | 507.22 | 0.242467E+11 | 0.311516E+10 | 0.00 | 1.00 | 01-AUG-00:41 | 0.00 | 01-AUG-00:01 | 43724.12 | 14-AUG-01:21 | 43130.94 | 19-AUG-00:08 | 20335.68 | 14-AUG-03:21 | 11976.60 | 14-AUG-01:21 | 0.00 | 01-AUG-00:01 |
September | 0.147899E+11 | 0.481285E+10 | 350.85 | 0.135963E+11 | 0.119357E+10 | 0.00 | 1.00 | 01-SEP-00:08 | 0.00 | 01-SEP-00:01 | 43254.87 | 03-SEP-00:43 | 43071.44 | 22-SEP-00:41 | 12111.47 | 01-SEP-02:61 | 11940.06 | 01-SEP-00:08 | 0.00 | 01-SEP-00:01 |
October | 0.443600E+10 | 0.146555E+10 | 141.33 | 0.417413E+10 | 0.261867E+09 | 0.00 | 1.00 | 02-OCT-00:41 | 0.00 | 01-OCT-00:01 | 43254.87 | 02-OCT-00:41 | 34838.28 | 02-OCT-00:41 | 8416.59 | 02-OCT-00:41 | 11940.06 | 02-OCT-00:41 | 0.00 | 01-OCT-00:01 |
November | 267380.26 | 93377.67 | 0.08 | 173785.30 | 93594.96 | 0.00 | 0.12 | 01-NOV-03:16 | 0.00 | 01-NOV-00:01 | 4040.97 | 01-NOV-03:16 | 2638.60 | 01-NOV-03:16 | 1402.37 | 01-NOV-03:16 | 1407.72 | 01-NOV-03:16 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.113509E+12 | 0.370807E+11 | 2400.71 | 0.104527E+12 | 0.898228E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.323782E+11 | 0.105289E+11 | 548.37 | 0.285909E+11 | 0.378722E+10 | 0.00 | 1.00 | 0.00 | 45196.36 | 43254.87 | 24170.03 | 12089.36 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 7374345.78 | 2454085.05 | 2.88 | 5882267.88 | 1492077.90 | 0.00 | 0.23 | 03-JAN-05:01 | 0.00 | 01-JAN-00:01 | 5686.52 | 03-JAN-05:01 | 4807.44 | 03-JAN-05:01 | 1297.76 | 13-JAN-04:04 | 1817.95 | 03-JAN-05:01 | 0.00 | 01-JAN-00:01 |
February | 0.112016E+09 | 36305413.82 | 11.77 | 0.108320E+09 | 3696032.52 | 0.00 | 1.00 | 14-FEB-04:31 | 0.00 | 01-FEB-00:01 | 30177.83 | 14-FEB-04:31 | 25136.09 | 14-FEB-04:31 | 5044.52 | 15-FEB-04:21 | 7854.70 | 14-FEB-04:31 | 0.00 | 01-FEB-00:01 |
March | 0.261515E+09 | 84801506.95 | 33.55 | 0.254047E+09 | 7467708.15 | 0.00 | 1.00 | 10-MAR-04:41 | 0.00 | 01-MAR-00:01 | 30177.83 | 10-MAR-04:41 | 26876.38 | 17-MAR-03:21 | 7782.77 | 21-MAR-03:31 | 7854.70 | 10-MAR-04:41 | 0.00 | 01-MAR-00:01 |
April | 0.404457E+10 | 0.125808E+10 | 181.75 | 0.403261E+10 | 11962433.12 | 0.00 | 1.00 | 02-APR-01:21 | 0.00 | 01-APR-00:01 | 30177.83 | 18-APR-01:21 | 30177.83 | 11-APR-00:41 | 7170.04 | 15-APR-03:21 | 7854.70 | 02-APR-01:21 | 0.00 | 01-APR-00:01 |
May | 0.100172E+11 | 0.303551E+10 | 310.34 | 0.980563E+10 | 0.211603E+09 | 0.00 | 1.00 | 02-MAY-03:21 | 0.00 | 01-MAY-00:01 | 30177.83 | 27-MAY-01:21 | 30177.83 | 09-MAY-00:41 | 14837.22 | 24-MAY-03:21 | 7854.70 | 02-MAY-03:21 | 0.00 | 01-MAY-00:01 |
June | 0.220035E+11 | 0.662488E+10 | 461.55 | 0.211634E+11 | 0.840038E+09 | 0.00 | 1.00 | 01-JUN-00:41 | 0.00 | 01-JUN-00:01 | 30177.83 | 27-JUN-02:62 | 30177.83 | 26-JUN-00:06 | 16448.21 | 05-JUN-02:61 | 7973.27 | 28-JUN-15:57 | 0.00 | 01-JUN-00:01 |
July | 0.318524E+11 | 0.936649E+10 | 586.68 | 0.272908E+11 | 0.456157E+10 | 0.00 | 1.00 | 01-JUL-00:06 | 0.00 | 01-JUL-00:01 | 31726.24 | 01-JUL-00:53 | 30177.83 | 21-JUL-00:03 | 18885.55 | 01-JUL-01:45 | 8004.01 | 22-JUL-14:10 | 0.00 | 01-JUL-00:01 |
August | 0.275180E+11 | 0.806460E+10 | 543.91 | 0.236375E+11 | 0.388055E+10 | 0.00 | 1.00 | 01-AUG-00:04 | 0.00 | 01-AUG-00:01 | 30293.95 | 14-AUG-00:41 | 29475.33 | 16-AUG-00:54 | 18949.16 | 30-AUG-00:41 | 7863.26 | 14-AUG-00:41 | 0.00 | 01-AUG-00:01 |
September | 0.162012E+11 | 0.480602E+10 | 399.97 | 0.144213E+11 | 0.177993E+10 | 0.00 | 1.00 | 01-SEP-00:04 | 0.00 | 01-SEP-00:01 | 30177.83 | 05-SEP-03:21 | 28318.72 | 22-SEP-00:41 | 17333.31 | 06-SEP-03:21 | 7854.70 | 01-SEP-00:04 | 0.00 | 01-SEP-00:01 |
October | 0.531461E+10 | 0.161162E+10 | 194.62 | 0.492284E+10 | 0.391768E+09 | 0.00 | 1.00 | 01-OCT-00:41 | 0.00 | 01-OCT-00:01 | 30177.83 | 04-OCT-00:41 | 29213.34 | 16-OCT-00:41 | 14093.24 | 23-OCT-01:21 | 7854.70 | 01-OCT-00:41 | 0.00 | 01-OCT-00:01 |
November | 86348374.08 | 26782362.44 | 10.39 | 71160474.62 | 15187899.46 | 0.00 | 1.00 | 01-NOV-03:21 | 0.00 | 01-NOV-00:01 | 30177.83 | 01-NOV-03:21 | 28322.31 | 17-NOV-05:01 | 11787.00 | 03-NOV-03:21 | 7854.70 | 01-NOV-03:21 | 0.00 | 01-NOV-00:01 |
December | 9750476.32 | 3231477.41 | 2.72 | 8388379.41 | 1362096.91 | 0.00 | 0.22 | 01-DEC-04:34 | 0.00 | 01-DEC-00:01 | 5421.61 | 01-DEC-04:34 | 4529.92 | 01-DEC-04:34 | 1076.36 | 26-DEC-04:04 | 1737.55 | 01-DEC-04:34 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.117429E+12 | 0.349208E+11 | 2740.14 | 0.105722E+12 | 0.117066E+11 | 0.00 | ||||||||||||||
Minimum of Months | 7374345.78 | 2454085.05 | 2.72 | 5882267.88 | 1362096.91 | 0.00 | 0.22 | 0.00 | 5421.61 | 4529.92 | 1076.36 | 1737.55 | 0.00 | |||||||
Maximum of Months | 0.318524E+11 | 0.936649E+10 | 586.68 | 0.272908E+11 | 0.456157E+10 | 0.00 | 1.00 | 0.00 | 31726.24 | 30177.83 | 18949.16 | 8004.01 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.58 | 77.48 | 61.10 | 105.00 | 230.67 | 0.00 | 0.00 | 0.00 |
February | 168.38 | 90.77 | 77.60 | 145.02 | 204.47 | 0.00 | 0.00 | 0.00 |
March | 222.11 | 126.27 | 95.85 | 228.41 | 154.29 | 0.00 | 0.00 | 0.00 |
April | 303.45 | 172.88 | 130.58 | 352.08 | 105.50 | 0.00 | 0.00 | 0.00 |
May | 289.56 | 165.02 | 124.54 | 360.09 | 80.92 | 0.00 | 0.00 | 0.00 |
June | 312.17 | 192.31 | 119.86 | 436.04 | 52.22 | 0.00 | 0.00 | 0.00 |
July | 288.85 | 165.18 | 123.68 | 425.45 | 34.16 | 0.00 | 0.00 | 0.00 |
August | 285.84 | 157.59 | 128.25 | 401.46 | 41.15 | 0.00 | 0.00 | 0.00 |
September | 237.91 | 133.11 | 104.80 | 308.77 | 74.39 | 0.00 | 0.00 | 0.00 |
October | 206.91 | 131.28 | 75.63 | 228.73 | 128.33 | 0.00 | 0.00 | 0.00 |
November | 161.71 | 95.07 | 66.64 | 144.07 | 184.02 | 0.00 | 0.00 | 0.00 |
December | 131.03 | 79.75 | 51.29 | 101.76 | 246.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 229.10 | 132.39 | 96.71 | 270.32 | 127.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.03 | 77.48 | 51.29 | 101.76 | 34.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 312.17 | 192.31 | 130.58 | 436.04 | 246.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 739.93 | 575.77 | 164.16 | 825.63 | 436.25 | 0.00 | 0.00 | 0.00 |
February | 724.13 | 528.95 | 195.18 | 829.45 | 395.74 | 0.00 | 0.00 | 0.00 |
March | 533.61 | 322.60 | 211.01 | 624.76 | 316.08 | 0.00 | 0.00 | 0.00 |
April | 416.15 | 170.82 | 245.33 | 502.67 | 229.77 | 0.00 | 0.00 | 0.00 |
May | 277.54 | 61.05 | 216.48 | 336.16 | 171.30 | 0.00 | 0.00 | 0.00 |
June | 234.77 | 28.93 | 205.84 | 349.43 | 113.02 | 0.00 | 0.00 | 0.00 |
July | 259.79 | 41.49 | 218.30 | 427.00 | 72.21 | 0.00 | 0.00 | 0.00 |
August | 357.23 | 116.12 | 241.11 | 550.40 | 87.86 | 0.00 | 0.00 | 0.00 |
September | 493.97 | 275.45 | 218.52 | 697.06 | 155.33 | 0.00 | 0.00 | 0.00 |
October | 675.80 | 497.73 | 178.08 | 851.74 | 253.62 | 0.00 | 0.00 | 0.00 |
November | 752.72 | 577.71 | 175.01 | 871.76 | 345.69 | 0.00 | 0.00 | 0.00 |
December | 802.81 | 662.23 | 140.58 | 902.41 | 447.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 521.24 | 320.50 | 200.73 | 646.34 | 251.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 234.77 | 28.93 | 140.58 | 336.16 | 72.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 802.81 | 662.23 | 245.33 | 902.41 | 447.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.94 | 81.52 | 61.43 | 124.10 | 243.91 | 0.00 | 0.00 | 0.00 |
February | 184.02 | 106.30 | 77.72 | 175.66 | 216.81 | 0.00 | 0.00 | 0.00 |
March | 205.53 | 109.41 | 96.12 | 212.67 | 164.80 | 0.00 | 0.00 | 0.00 |
April | 262.31 | 139.60 | 122.71 | 297.60 | 111.94 | 0.00 | 0.00 | 0.00 |
May | 248.71 | 128.15 | 120.56 | 303.71 | 83.91 | 0.00 | 0.00 | 0.00 |
June | 266.62 | 148.77 | 117.85 | 377.14 | 56.69 | 0.00 | 0.00 | 0.00 |
July | 240.48 | 117.69 | 122.79 | 358.96 | 36.05 | 0.00 | 0.00 | 0.00 |
August | 245.73 | 113.66 | 132.07 | 349.04 | 43.72 | 0.00 | 0.00 | 0.00 |
September | 221.95 | 116.89 | 105.06 | 291.24 | 77.44 | 0.00 | 0.00 | 0.00 |
October | 203.05 | 126.21 | 76.85 | 230.94 | 136.56 | 0.00 | 0.00 | 0.00 |
November | 159.40 | 93.78 | 65.62 | 149.18 | 191.00 | 0.00 | 0.00 | 0.00 |
December | 137.85 | 86.44 | 51.40 | 117.52 | 253.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 209.90 | 113.98 | 95.92 | 249.26 | 134.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.85 | 81.52 | 51.40 | 117.52 | 36.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 266.62 | 148.77 | 132.07 | 377.14 | 253.98 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.371184E+09 | 0.207526E+09 | 0.163657E+09 | 0.281228E+09 | 0.617840E+09 |
February | 0.407338E+09 | 0.219598E+09 | 0.187739E+09 | 0.350823E+09 | 0.494660E+09 |
March | 0.594912E+09 | 0.338196E+09 | 0.256716E+09 | 0.611774E+09 | 0.413259E+09 |
April | 0.786553E+09 | 0.448094E+09 | 0.338458E+09 | 0.912587E+09 | 0.273463E+09 |
May | 0.775556E+09 | 0.441982E+09 | 0.333574E+09 | 0.964470E+09 | 0.216730E+09 |
June | 0.809137E+09 | 0.498467E+09 | 0.310671E+09 | 0.113021E+10 | 0.135343E+09 |
July | 0.773666E+09 | 0.442413E+09 | 0.331253E+09 | 0.113951E+10 | 91506887.02 |
August | 0.765595E+09 | 0.422086E+09 | 0.343509E+09 | 0.107527E+10 | 0.110222E+09 |
September | 0.616673E+09 | 0.345034E+09 | 0.271640E+09 | 0.800319E+09 | 0.192810E+09 |
October | 0.554193E+09 | 0.351614E+09 | 0.202580E+09 | 0.612625E+09 | 0.343713E+09 |
November | 0.419158E+09 | 0.246420E+09 | 0.172738E+09 | 0.373437E+09 | 0.476973E+09 |
December | 0.350958E+09 | 0.213590E+09 | 0.137368E+09 | 0.272561E+09 | 0.660306E+09 |
Annual Sum or Average | 0.722492E+10 | 0.417502E+10 | 0.304990E+10 | 0.852482E+10 | 0.402682E+10 |
Minimum of Months | 0.350958E+09 | 0.207526E+09 | 0.137368E+09 | 0.272561E+09 | 91506887.02 |
Maximum of Months | 0.809137E+09 | 0.498467E+09 | 0.343509E+09 | 0.113951E+10 | 0.660306E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198184E+10 | 0.154214E+10 | 0.439696E+09 | 0.221136E+10 | 0.116846E+10 |
February | 0.175181E+10 | 0.127963E+10 | 0.472172E+09 | 0.200661E+10 | 0.957368E+09 |
March | 0.142921E+10 | 0.864046E+09 | 0.565167E+09 | 0.167336E+10 | 0.846585E+09 |
April | 0.107865E+10 | 0.442765E+09 | 0.635885E+09 | 0.130293E+10 | 0.595561E+09 |
May | 0.743350E+09 | 0.163523E+09 | 0.579828E+09 | 0.900378E+09 | 0.458802E+09 |
June | 0.608528E+09 | 74994162.37 | 0.533534E+09 | 0.905727E+09 | 0.292956E+09 |
July | 0.695812E+09 | 0.111114E+09 | 0.584698E+09 | 0.114368E+10 | 0.193399E+09 |
August | 0.956792E+09 | 0.311005E+09 | 0.645787E+09 | 0.147420E+10 | 0.235317E+09 |
September | 0.128036E+10 | 0.713964E+09 | 0.566394E+09 | 0.180678E+10 | 0.402613E+09 |
October | 0.181007E+10 | 0.133311E+10 | 0.476965E+09 | 0.228130E+10 | 0.679287E+09 |
November | 0.195104E+10 | 0.149742E+10 | 0.453624E+09 | 0.225960E+10 | 0.896027E+09 |
December | 0.215024E+10 | 0.177372E+10 | 0.376517E+09 | 0.241701E+10 | 0.119838E+10 |
Annual Sum or Average | 0.164377E+11 | 0.101074E+11 | 0.633027E+10 | 0.203829E+11 | 0.792476E+10 |
Minimum of Months | 0.608528E+09 | 74994162.37 | 0.376517E+09 | 0.900378E+09 | 0.193399E+09 |
Maximum of Months | 0.215024E+10 | 0.177372E+10 | 0.645787E+09 | 0.241701E+10 | 0.119838E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382862E+09 | 0.218334E+09 | 0.164528E+09 | 0.332395E+09 | 0.653298E+09 |
February | 0.445174E+09 | 0.257164E+09 | 0.188011E+09 | 0.424956E+09 | 0.524514E+09 |
March | 0.550482E+09 | 0.293032E+09 | 0.257450E+09 | 0.569620E+09 | 0.441392E+09 |
April | 0.679916E+09 | 0.361854E+09 | 0.318062E+09 | 0.771389E+09 | 0.290138E+09 |
May | 0.666148E+09 | 0.343245E+09 | 0.322902E+09 | 0.813467E+09 | 0.224757E+09 |
June | 0.691073E+09 | 0.385611E+09 | 0.305462E+09 | 0.977539E+09 | 0.146929E+09 |
July | 0.644104E+09 | 0.315215E+09 | 0.328889E+09 | 0.961446E+09 | 96550767.96 |
August | 0.658160E+09 | 0.304425E+09 | 0.353735E+09 | 0.934861E+09 | 0.117112E+09 |
September | 0.575296E+09 | 0.302985E+09 | 0.272312E+09 | 0.754884E+09 | 0.200729E+09 |
October | 0.543862E+09 | 0.338030E+09 | 0.205833E+09 | 0.618548E+09 | 0.365749E+09 |
November | 0.413158E+09 | 0.243070E+09 | 0.170088E+09 | 0.386665E+09 | 0.495067E+09 |
December | 0.369207E+09 | 0.231532E+09 | 0.137675E+09 | 0.314778E+09 | 0.680264E+09 |
Annual Sum or Average | 0.661944E+10 | 0.359450E+10 | 0.302495E+10 | 0.786055E+10 | 0.423650E+10 |
Minimum of Months | 0.369207E+09 | 0.218334E+09 | 0.137675E+09 | 0.314778E+09 | 96550767.96 |
Maximum of Months | 0.691073E+09 | 0.385611E+09 | 0.353735E+09 | 0.977539E+09 | 0.680264E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1019.56 | 875.67 | 1021.46 | 734.77 | 286.69 | 0.00 | 0.00 |
February | 1121.49 | 788.38 | 1076.52 | 726.02 | 350.50 | 0.00 | 0.00 |
March | 1038.72 | 608.04 | 961.25 | 558.27 | 402.98 | 0.00 | 0.00 |
April | 1121.19 | 416.04 | 981.91 | 483.30 | 498.61 | 0.00 | 0.00 |
May | 983.41 | 319.57 | 815.81 | 354.22 | 461.58 | 0.00 | 0.00 |
June | 1150.23 | 209.55 | 813.56 | 370.01 | 443.54 | 0.00 | 0.00 |
July | 1207.03 | 138.04 | 789.12 | 324.35 | 464.77 | 0.00 | 0.00 |
August | 1293.89 | 165.73 | 888.79 | 387.36 | 501.43 | 0.00 | 0.00 |
September | 1286.47 | 296.56 | 953.83 | 525.46 | 428.37 | 0.00 | 0.00 |
October | 1292.22 | 499.31 | 1085.77 | 755.21 | 330.56 | 0.00 | 0.00 |
November | 1136.43 | 692.12 | 1073.83 | 766.55 | 307.27 | 0.00 | 0.00 |
December | 1072.33 | 898.56 | 1071.69 | 828.42 | 243.26 | 0.00 | 0.00 |
Annual Sum or Average | 1143.43 | 490.84 | 960.24 | 566.87 | 393.36 | 0.00 | 0.00 |
Minimum of Months | 983.41 | 138.04 | 789.12 | 324.35 | 243.26 | 0.00 | 0.00 |
Maximum of Months | 1293.89 | 898.56 | 1085.77 | 828.42 | 501.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.273079E+10 | 0.234540E+10 | 0.273588E+10 | 0.196800E+10 | 0.767881E+09 | 0.00 | 0.00 |
February | 0.271310E+10 | 0.190725E+10 | 0.260432E+10 | 0.175640E+10 | 0.847922E+09 | 0.00 | 0.00 |
March | 0.278211E+10 | 0.162859E+10 | 0.257461E+10 | 0.149527E+10 | 0.107933E+10 | 0.00 | 0.00 |
April | 0.290611E+10 | 0.107837E+10 | 0.254512E+10 | 0.125271E+10 | 0.129240E+10 | 0.00 | 0.00 |
May | 0.263396E+10 | 0.855934E+09 | 0.218505E+10 | 0.948750E+09 | 0.123630E+10 | 0.00 | 0.00 |
June | 0.298139E+10 | 0.543141E+09 | 0.210874E+10 | 0.959072E+09 | 0.114967E+10 | 0.00 | 0.00 |
July | 0.323290E+10 | 0.369721E+09 | 0.211358E+10 | 0.868743E+09 | 0.124484E+10 | 0.00 | 0.00 |
August | 0.346556E+10 | 0.443885E+09 | 0.238055E+10 | 0.103752E+10 | 0.134303E+10 | 0.00 | 0.00 |
September | 0.333453E+10 | 0.768695E+09 | 0.247233E+10 | 0.136198E+10 | 0.111035E+10 | 0.00 | 0.00 |
October | 0.346109E+10 | 0.133736E+10 | 0.290813E+10 | 0.202275E+10 | 0.885377E+09 | 0.00 | 0.00 |
November | 0.294562E+10 | 0.179399E+10 | 0.278336E+10 | 0.198691E+10 | 0.796450E+09 | 0.00 | 0.00 |
December | 0.287212E+10 | 0.240672E+10 | 0.287040E+10 | 0.221884E+10 | 0.651561E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.360593E+11 | 0.154791E+11 | 0.302821E+11 | 0.178769E+11 | 0.124051E+11 | 0.00 | 0.00 |
Minimum of Months | 0.263396E+10 | 0.369721E+09 | 0.210874E+10 | 0.868743E+09 | 0.651561E+09 | 0.00 | 0.00 |
Maximum of Months | 0.346556E+10 | 0.240672E+10 | 0.290813E+10 | 0.221884E+10 | 0.134303E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.138978E+11 | -0.131434E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -754423019.8 | 58.99 | 0.00 | 0.00 |
February | 0.126355E+11 | -0.119628E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -672664966.0 | 58.99 | 0.00 | 0.00 |
March | 0.136541E+11 | -0.129447E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -709392102.6 | 58.99 | 0.00 | 0.00 |
April | 0.124927E+11 | -0.118315E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -661164041.6 | 58.99 | 0.00 | 0.00 |
May | 0.120490E+11 | -0.113785E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -670421717.8 | 58.99 | 0.00 | 0.00 |
June | 0.108794E+11 | -0.102353E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -644159247.4 | 58.99 | 0.00 | 0.00 |
July | 0.106790E+11 | -0.100138E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -665208924.4 | 58.99 | 0.00 | 0.00 |
August | 0.105959E+11 | -0.993089E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -665009444.9 | 58.98 | 0.00 | 0.00 |
September | 0.105575E+11 | -0.991444E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -643088444.9 | 58.99 | 0.00 | 0.00 |
October | 0.116287E+11 | -0.109463E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -682405896.8 | 58.99 | 0.00 | 0.00 |
November | 0.121313E+11 | -0.114390E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -692320693.8 | 58.99 | 0.00 | 0.00 |
December | 0.133604E+11 | -0.126001E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -760265527.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.144561E+12 | -0.136341E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.822052E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.105575E+11 | -0.131434E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -760265527.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.138978E+11 | -0.991444E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -643088444.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 301.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 282.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 381.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 378.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 395.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 359.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 329.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 284.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4149.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.328665E+11 | 55110.94 | 22-JAN-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.251723E+11 | 80278.46 | 01-FEB-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151327E+11 | 40658.89 | 04-MAR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.590718E+10 | 20832.70 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198855E+10 | 14507.58 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.260379E+09 | 22186.15 | 27-JUN-02:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 74457813.34 | 21683.29 | 22-JUL-03:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 67619350.46 | 22196.05 | 19-AUG-02:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128724E+09 | 26796.17 | 22-SEP-03:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.647656E+10 | 37130.30 | 26-OCT-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173931E+11 | 27491.52 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.341008E+11 | 58304.45 | 22-DEC-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139569E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 67619350.46 | 14507.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.341008E+11 | 80278.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.286010E+10 | 12353.71 | 21-JAN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184670E+10 | 13031.74 | 04-FEB-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.295760E+09 | 6731.27 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2053567.58 | 2888.90 | 06-APR-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 73611442.84 | 7768.58 | 26-OCT-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.235328E+09 | 7735.35 | 27-NOV-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.256983E+10 | 12634.74 | 15-DEC-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.788339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.286010E+10 | 13031.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 74592444.04 | 74592444.04 | 5145.23 | 14-FEB-15:53 | 5145.23 | 0.00 |
March | 0.00 | 0.00 | 0.125676E+09 | 0.125676E+09 | 7670.84 | 08-MAR-14:00 | 7670.84 | 0.00 |
April | 0.00 | 0.00 | 0.310958E+10 | 0.310954E+10 | 14905.22 | 13-APR-17:02 | 14905.22 | 0.00 |
May | 0.00 | 0.00 | 0.866649E+10 | 0.858288E+10 | 43254.87 | 22-MAY-00:10 | 36137.80 | 0.00 |
June | 0.00 | 0.00 | 0.225668E+11 | 0.220261E+11 | 43254.87 | 24-JUN-01:38 | 35088.83 | 0.00 |
July | 0.00 | 0.00 | 0.323782E+11 | 0.285909E+11 | 45196.36 | 01-JUL-01:21 | 21026.33 | 0.00 |
August | 0.00 | 0.00 | 0.273619E+11 | 0.242467E+11 | 43724.12 | 14-AUG-01:21 | 23804.39 | 0.00 |
September | 0.00 | 0.00 | 0.147899E+11 | 0.135963E+11 | 43254.87 | 03-SEP-00:43 | 37694.45 | 0.00 |
October | 0.00 | 0.00 | 0.443600E+10 | 0.417413E+10 | 43254.87 | 02-OCT-00:41 | 34838.28 | 0.00 |
November | 0.00 | 0.00 | 267380.26 | 173785.30 | 4040.97 | 01-NOV-03:16 | 2638.60 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.113509E+12 | 0.104527E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.323782E+11 | 0.285909E+11 | 45196.36 | 37694.45 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7374345.78 | 5882267.88 | 5686.52 | 03-JAN-05:01 | 4807.44 | 0.00 |
February | 0.00 | 0.00 | 0.112016E+09 | 0.108320E+09 | 30177.83 | 14-FEB-04:31 | 25136.09 | 0.00 |
March | 0.00 | 0.00 | 0.261515E+09 | 0.254047E+09 | 30177.83 | 10-MAR-04:41 | 25987.58 | 0.00 |
April | 0.00 | 0.00 | 0.404457E+10 | 0.403261E+10 | 30177.83 | 18-APR-01:21 | 30177.83 | 0.00 |
May | 0.00 | 0.00 | 0.100172E+11 | 0.980563E+10 | 30177.83 | 27-MAY-01:21 | 19592.25 | 0.00 |
June | 0.00 | 0.00 | 0.220035E+11 | 0.211634E+11 | 30177.83 | 27-JUN-02:62 | 27785.28 | 0.00 |
July | 0.00 | 0.00 | 0.318524E+11 | 0.272908E+11 | 31726.24 | 01-JUL-00:53 | 12995.32 | 0.00 |
August | 0.00 | 0.00 | 0.275180E+11 | 0.236375E+11 | 30293.95 | 14-AUG-00:41 | 15123.92 | 0.00 |
September | 0.00 | 0.00 | 0.162012E+11 | 0.144213E+11 | 30177.83 | 05-SEP-03:21 | 15121.13 | 0.00 |
October | 0.00 | 0.00 | 0.531461E+10 | 0.492284E+10 | 30177.83 | 04-OCT-00:41 | 25403.61 | 0.00 |
November | 0.00 | 0.00 | 86348374.08 | 71160474.62 | 30177.83 | 01-NOV-03:21 | 19782.70 | 0.00 |
December | 0.00 | 0.00 | 9750476.32 | 8388379.41 | 5421.61 | 01-DEC-04:34 | 4529.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.117429E+12 | 0.105722E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7374345.78 | 5882267.88 | 5421.61 | 4529.92 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.318524E+11 | 0.272908E+11 | 31726.24 | 30177.83 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5198.89 | 19381.58 | 31-JAN-13:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 5236.61 | 19396.72 | 07-FEB-13:35 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5126.52 | 19213.52 | 01-MAR-13:40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4855.46 | 18423.02 | 01-APR-12:45 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 4540.69 | 17264.63 | 01-MAY-12:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 4242.32 | 15986.51 | 01-JUN-12:30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4029.38 | 15003.09 | 01-JUL-12:40 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4001.95 | 14687.72 | 31-AUG-12:15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 4116.53 | 15443.89 | 30-SEP-12:50 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4378.69 | 16633.54 | 31-OCT-12:25 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4705.57 | 17873.59 | 30-NOV-13:50 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4994.79 | 18899.48 | 31-DEC-13:15 |
Annual Sum or Average | 0.00 | 4615.40 | ||||
Minimum of Months | 0.00 | 0.00 | 4001.95 | 14687.72 | ||
Maximum of Months | 0.00 | 0.00 | 5236.61 | 19396.72 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | -0.0 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.285297E+10 | 0.68 | 1211.87 | 01-JAN-00:01 | 0.78 |
February | 0.260427E+10 | 0.69 | 1211.87 | 01-FEB-00:01 | 0.78 |
March | 0.305699E+10 | 0.73 | 1211.87 | 01-MAR-00:01 | 0.78 |
April | 0.299900E+10 | 0.74 | 1211.87 | 01-APR-00:16 | 0.77 |
May | 0.310354E+10 | 0.74 | 1211.87 | 01-MAY-00:04 | 0.78 |
June | 0.300625E+10 | 0.74 | 1211.87 | 01-JUN-00:03 | 0.78 |
July | 0.310787E+10 | 0.73 | 1211.87 | 01-JUL-00:03 | 0.77 |
August | 0.310806E+10 | 0.73 | 1211.87 | 01-AUG-00:02 | 0.76 |
September | 0.300701E+10 | 0.74 | 1211.87 | 01-SEP-00:02 | 0.77 |
October | 0.309642E+10 | 0.74 | 1211.87 | 01-OCT-00:03 | 0.77 |
November | 0.296347E+10 | 0.73 | 1211.87 | 01-NOV-00:04 | 0.78 |
December | 0.284780E+10 | 0.68 | 1211.87 | 01-DEC-00:01 | 0.77 |
Annual Sum or Average | 0.357536E+11 | 0.72 | |||
Minimum of Months | 0.260427E+10 | 0.68 | 1211.87 | 0.76 | |
Maximum of Months | 0.310806E+10 | 0.74 | 1211.87 | 0.78 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.631076E+10 | 0.97 | 2812.97 | 30-JAN-11:15 | 1.09 |
February | 0.569668E+10 | 0.97 | 2812.97 | 08-FEB-08:37 | 1.09 |
March | 0.628879E+10 | 0.94 | 2812.97 | 01-MAR-00:50 | 1.09 |
April | 0.607801E+10 | 0.92 | 2812.97 | 08-APR-12:10 | 1.09 |
May | 0.629239E+10 | 0.94 | 2812.97 | 05-MAY-07:43 | 1.09 |
June | 0.615793E+10 | 0.98 | 2812.97 | 01-JUN-10:52 | 1.08 |
July | 0.645727E+10 | 0.99 | 2812.97 | 12-JUL-06:55 | 1.08 |
August | 0.647834E+10 | 1.00 | 2812.97 | 01-AUG-06:42 | 1.08 |
September | 0.616220E+10 | 1.01 | 2812.97 | 30-SEP-19:10 | 1.09 |
October | 0.630486E+10 | 0.95 | 2812.97 | 01-OCT-09:40 | 1.08 |
November | 0.608009E+10 | 0.93 | 2812.97 | 28-NOV-05:14 | 1.09 |
December | 0.630602E+10 | 0.97 | 2812.97 | 12-DEC-14:10 | 1.10 |
Annual Sum or Average | 0.746133E+11 | 0.96 | |||
Minimum of Months | 0.569668E+10 | 0.92 | 2812.97 | 1.08 | |
Maximum of Months | 0.647834E+10 | 1.01 | 2812.97 | 1.10 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.381665E+10 | 0.96 | 1705.78 | 02-JAN-05:10 | 1.09 |
February | 0.345257E+10 | 0.96 | 1705.78 | 01-FEB-00:55 | 1.09 |
March | 0.384782E+10 | 1.02 | 1705.78 | 01-MAR-05:54 | 1.09 |
April | 0.378154E+10 | 1.03 | 1705.78 | 01-APR-10:45 | 1.10 |
May | 0.396571E+10 | 1.03 | 1705.78 | 02-MAY-15:37 | 1.09 |
June | 0.389523E+10 | 1.02 | 1705.78 | 01-JUN-10:15 | 1.08 |
July | 0.406973E+10 | 1.00 | 1705.78 | 01-JUL-09:10 | 1.07 |
August | 0.406306E+10 | 1.00 | 1705.78 | 01-AUG-04:40 | 1.08 |
September | 0.391755E+10 | 1.02 | 1705.78 | 01-SEP-07:35 | 1.08 |
October | 0.394203E+10 | 1.03 | 1705.78 | 01-OCT-09:26 | 1.09 |
November | 0.373147E+10 | 1.02 | 1705.78 | 06-NOV-05:50 | 1.09 |
December | 0.381840E+10 | 0.96 | 1705.78 | 03-DEC-22:40 | 1.09 |
Annual Sum or Average | 0.463018E+11 | 1.00 | |||
Minimum of Months | 0.345257E+10 | 0.96 | 1705.78 | 1.07 | |
Maximum of Months | 0.406973E+10 | 1.03 | 1705.78 | 1.10 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 50.55 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 51.57 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 51.97 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 52.27 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 51.38 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 53.08 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:10 | 0.00 | 0.00 | 53.10 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 53.85 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 53.44 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 52.01 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 52.57 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 52.28 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 50.55 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 53.85 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 38.73 | 38.73 | 5198.89 | 19381.58 | 31-JAN-13:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 51.94 | 51.94 | 5236.61 | 19396.72 | 07-FEB-13:35 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 51.63 | 51.63 | 5126.52 | 19213.52 | 01-MAR-13:40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.90 | 51.90 | 4855.46 | 18423.02 | 01-APR-12:45 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 40.50 | 40.50 | 4540.69 | 17264.63 | 01-MAY-12:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 52.91 | 52.91 | 4242.32 | 15986.51 | 01-JUN-12:30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 53.53 | 53.53 | 4029.38 | 15003.09 | 01-JUL-12:40 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 53.62 | 53.62 | 4001.95 | 14687.72 | 31-AUG-12:15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 53.32 | 53.32 | 4116.53 | 15443.89 | 30-SEP-12:50 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 42.54 | 42.54 | 4378.69 | 16633.54 | 31-OCT-12:25 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.45 | 52.45 | 4705.57 | 17873.59 | 30-NOV-13:50 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 52.02 | 52.02 | 4994.79 | 18899.48 | 31-DEC-13:15 |
Annual Sum or Average | 0.00 | 4615.40 | ||||||
Minimum of Months | 0.00 | 0.00 | 38.73 | 38.73 | 4001.95 | 14687.72 | ||
Maximum of Months | 0.00 | 0.00 | 53.62 | 53.62 | 5236.61 | 19396.72 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.631076E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.572275E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.633255E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.712902E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.916397E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.136070E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.169862E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.153102E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.109750E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.777041E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.608019E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.630602E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.111694E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.572275E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.169862E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.381910E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.348887E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.393262E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.503962E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.700122E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.105201E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.134362E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.121277E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.872358E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.555365E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.375825E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.382164E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.812225E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.348887E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.134362E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.631076E+10 | 0.00 | 0.328665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.569668E+10 | 74592444.04 | 0.251723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.628879E+10 | 0.125676E+09 | 0.151327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.607801E+10 | 0.310958E+10 | 0.590718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.629239E+10 | 0.866649E+10 | 0.198855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.615793E+10 | 0.225668E+11 | 0.260379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.645727E+10 | 0.323782E+11 | 74457813.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.647834E+10 | 0.273619E+11 | 67619350.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.616220E+10 | 0.147899E+11 | 0.128724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.630486E+10 | 0.443600E+10 | 0.647656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.608009E+10 | 267380.26 | 0.173931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.630602E+10 | 0.00 | 0.341008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.746133E+11 | 0.113509E+12 | 0.139569E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.569668E+10 | 0.00 | 67619350.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.647834E+10 | 0.323782E+11 | 0.341008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.381665E+10 | 7374345.78 | 0.286010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.345257E+10 | 0.112016E+09 | 0.184670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384782E+10 | 0.261515E+09 | 0.295760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.378154E+10 | 0.404457E+10 | 2053567.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.396571E+10 | 0.100172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.389523E+10 | 0.220035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.406973E+10 | 0.318524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.406306E+10 | 0.275180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.391755E+10 | 0.162012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.394203E+10 | 0.531461E+10 | 73611442.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373147E+10 | 86348374.08 | 0.235328E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.381840E+10 | 9750476.32 | 0.256983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.463018E+11 | 0.117429E+12 | 0.788339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.345257E+10 | 7374345.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.406973E+10 | 0.318524E+11 | 0.286010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.631076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.569668E+10 | 0.00 | 0.00 | 0.00 | 26075174.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.628879E+10 | 0.00 | 0.00 | 0.00 | 43754892.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.607801E+10 | 0.00 | 0.00 | 0.00 | 0.105102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.629239E+10 | 0.00 | 0.00 | 0.00 | 0.287158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.615793E+10 | 0.00 | 0.00 | 0.00 | 0.744902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.645727E+10 | 0.00 | 0.00 | 0.00 | 0.105289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.647834E+10 | 0.00 | 0.00 | 0.00 | 0.883185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.616220E+10 | 0.00 | 0.00 | 0.00 | 0.481285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.630486E+10 | 0.00 | 0.00 | 0.00 | 0.146555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.608009E+10 | 0.00 | 0.00 | 0.00 | 93377.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.630602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.746133E+11 | 0.00 | 0.00 | 0.00 | 0.370807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.569668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.647834E+10 | 0.00 | 0.00 | 0.00 | 0.105289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.381665E+10 | 0.00 | 0.00 | 0.00 | 2454085.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.345257E+10 | 0.00 | 0.00 | 0.00 | 36305413.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384782E+10 | 0.00 | 0.00 | 0.00 | 84801506.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.378154E+10 | 0.00 | 0.00 | 0.00 | 0.125808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.396571E+10 | 0.00 | 0.00 | 0.00 | 0.303551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.389523E+10 | 0.00 | 0.00 | 0.00 | 0.662488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.406973E+10 | 0.00 | 0.00 | 0.00 | 0.936649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.406306E+10 | 0.00 | 0.00 | 0.00 | 0.806460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.391755E+10 | 0.00 | 0.00 | 0.00 | 0.480602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.394203E+10 | 0.00 | 0.00 | 0.00 | 0.161162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373147E+10 | 0.00 | 0.00 | 0.00 | 26782362.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.381840E+10 | 0.00 | 0.00 | 0.00 | 3231477.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.463018E+11 | 0.00 | 0.00 | 0.00 | 0.349208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.345257E+10 | 0.00 | 0.00 | 0.00 | 2454085.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.406973E+10 | 0.00 | 0.00 | 0.00 | 0.936649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.723076E+10 | 0.00 | 0.00 | 18889.25 | 0.00 | 0.284720E+11 | 82276451.65 | 0.00 | 7.07 |
February | 0.694184E+10 | 0.00 | 0.00 | 1177304.52 | 0.00 | 0.221375E+11 | 0.544786E+09 | 0.00 | 7.22 |
March | 0.966073E+10 | 0.00 | 0.00 | 3922437.93 | 0.00 | 0.133857E+11 | 0.208352E+10 | 0.00 | 7.46 |
April | 0.885912E+10 | 222970.59 | 0.00 | 19155348.55 | 0.00 | 0.420321E+10 | 0.488102E+10 | 0.00 | 8.71 |
May | 0.632685E+10 | 0.290168E+09 | 0.00 | 27783727.22 | 0.00 | 0.108905E+10 | 0.543017E+10 | 0.00 | 9.09 |
June | 0.241427E+10 | 0.358972E+10 | 1876516.53 | 22438862.80 | 0.00 | 19349058.38 | 0.405107E+10 | 176312.55 | 9.03 |
July | 52460884.51 | 0.612136E+10 | 7361435.36 | 14538777.86 | 735726.81 | 26247.48 | 0.345177E+10 | 833082.67 | 9.56 |
August | 0.470234E+09 | 0.395727E+10 | 5974854.08 | 22397543.83 | 21078.72 | 172523.35 | 0.483932E+10 | 698248.43 | 9.93 |
September | 0.241146E+10 | 0.949327E+09 | 51012.72 | 37180658.58 | 0.00 | 677421.37 | 0.748575E+10 | 63503.59 | 9.87 |
October | 0.896825E+10 | 96958176.82 | 0.00 | 22384505.95 | 0.00 | 0.469871E+10 | 0.595866E+10 | 0.00 | 8.77 |
November | 0.120828E+11 | 0.00 | 0.00 | 331616.40 | 0.00 | 0.145219E+11 | 0.399357E+09 | 0.00 | 7.01 |
December | 0.710251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297864E+11 | 0.00 | 0.00 | 7.06 |
Annual Sum or Average | 0.725213E+11 | 0.150050E+11 | 15263818.68 | 0.171330E+09 | 756805.53 | 0.118315E+12 | 0.392077E+11 | 1771147.24 | 8.40 |
Minimum of Months | 52460884.51 | 0.00 | 0.00 | 0.00 | 0.00 | 26247.48 | 0.00 | 0.00 | 7.01 |
Maximum of Months | 0.120828E+11 | 0.612136E+10 | 7361435.36 | 37180658.58 | 735726.81 | 0.297864E+11 | 0.748575E+10 | 833082.67 | 9.93 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.310910E+11 | 0.00 | 0.00 | 11089479.42 | 0.00 | 0.00 | 0.942329E+10 | 0.00 | 6.30 |
February | 0.243716E+11 | 0.00 | 0.00 | 16976131.99 | 0.00 | 0.00 | 0.110187E+11 | 0.00 | 6.57 |
March | 0.147160E+11 | 0.00 | 0.00 | 48063953.00 | 0.00 | 0.00 | 0.229930E+11 | 0.00 | 7.50 |
April | 0.651499E+10 | 0.00 | 0.00 | 82063158.10 | 0.00 | 0.00 | 0.272564E+11 | 0.00 | 9.60 |
May | 0.205350E+10 | 0.00 | 0.00 | 0.110182E+09 | 0.00 | 0.00 | 0.278453E+11 | 0.00 | 10.50 |
June | 0.125783E+09 | 0.105724E+09 | 0.00 | 0.126287E+09 | 0.00 | 0.00 | 0.183673E+11 | 0.00 | 10.09 |
July | 0.00 | 0.298315E+09 | 0.00 | 0.127456E+09 | 0.00 | 0.00 | 0.105739E+11 | 0.00 | 10.41 |
August | 0.00 | 60870190.13 | 0.00 | 0.135372E+09 | 0.00 | 0.00 | 0.148811E+11 | 0.00 | 10.88 |
September | 0.00 | 162909.54 | 0.00 | 0.129088E+09 | 0.00 | 0.00 | 0.241326E+11 | 0.00 | 11.40 |
October | 0.615041E+10 | 0.00 | 0.00 | 89935829.40 | 0.00 | 0.00 | 0.291301E+11 | 0.00 | 9.69 |
November | 0.152268E+11 | 0.00 | 0.00 | 35900897.03 | 0.00 | 0.00 | 0.226579E+11 | 0.00 | 6.82 |
December | 0.334916E+11 | 0.00 | 0.00 | 5797028.69 | 0.00 | 0.00 | 0.727202E+10 | 0.00 | 6.24 |
Annual Sum or Average | 0.133742E+12 | 0.465072E+09 | 0.00 | 0.918211E+09 | 0.00 | 0.00 | 0.225552E+12 | 0.00 | 8.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 5797028.69 | 0.00 | 0.00 | 0.727202E+10 | 0.00 | 6.24 |
Maximum of Months | 0.334916E+11 | 0.298315E+09 | 0.00 | 0.135372E+09 | 0.00 | 0.00 | 0.291301E+11 | 0.00 | 11.40 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:23:52
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.313996E+11 | 0.192187E+11 | 0.132947E+12 | 0.326159E+09 | 0.321295E+11 |
February | 0.397365E+11 | 0.160650E+11 | 0.113133E+12 | 0.106577E+10 | 0.296031E+11 |
March | 0.533256E+11 | 0.137128E+11 | 0.110835E+12 | 0.441255E+10 | 0.328263E+11 |
April | 0.682746E+11 | 0.935731E+10 | 0.811594E+11 | 0.940916E+10 | 0.406497E+11 |
May | 0.730442E+11 | 0.656118E+10 | 0.629350E+11 | 0.105355E+11 | 0.563646E+11 |
June | 0.696806E+11 | 0.149300E+10 | 0.334034E+11 | 0.701918E+10 | 0.911468E+11 |
July | 0.711392E+11 | -0.110085E+10 | 0.126122E+11 | 0.517001E+10 | 0.118458E+12 |
August | 0.693622E+11 | 0.584269E+09 | 0.230011E+11 | 0.715868E+10 | 0.105147E+12 |
September | 0.557469E+11 | 0.377313E+10 | 0.453044E+11 | 0.108509E+11 | 0.710565E+11 |
October | 0.442019E+11 | 0.953734E+10 | 0.846665E+11 | 0.100380E+11 | 0.432358E+11 |
November | 0.341631E+11 | 0.146472E+11 | 0.116681E+12 | 0.185101E+10 | 0.282778E+11 |
December | 0.289722E+11 | 0.197965E+11 | 0.134460E+12 | 33845375.01 | 0.308881E+11 |
Annual Sum or Average | 0.639047E+12 | 0.113646E+12 | 0.951138E+12 | 0.678708E+11 | 0.679782E+12 |
Minimum of Months | 0.289722E+11 | -0.110085E+10 | 0.126122E+11 | 33845375.01 | 0.282778E+11 |
Maximum of Months | 0.730442E+11 | 0.197965E+11 | 0.134460E+12 | 0.108509E+11 | 0.118458E+12 |