Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 08:25:20
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1560.10 | 6714.64 | 6714.64 |
Net Site Energy | 1560.10 | 6714.64 | 6714.64 |
Total Source Energy | 3609.64 | 15535.84 | 15535.84 |
Net Source Energy | 3609.64 | 15535.84 | 15535.84 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 320.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 276.88 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 156.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 68.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 921.03 | 639.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 320.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 41.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.75 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 168.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 156.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 18.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 32.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 320.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 41.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 276.88 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 168.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 156.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 68.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 2106.59 | 696.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1486.85 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 3964.08 | 2750.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 2106.59 | 696.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1486.85 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 3964.08 | 2750.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 921.025 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 921.025 | 100.00 |
Total On-Site and Utility Electric Sources | 921.025 | 100.00 |
Total Electricity End Uses | 921.025 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1589.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5917.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 9.2637 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 11.9458 | 18.52 | 1074.0064 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 10.6047 | 2.48 | 595.3967 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 10.6047 | 2.48 | 595.3967 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 9.2637 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.9458 | 18.52 | 1074.0064 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 10.6047 | 1.24 | 595.3967 | |||||||
Conditioned Total | 232.34 | 10.6047 | 1.24 | 595.3967 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 10.6047 | 2.48 | 595.3967 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-JUN-18:10 | 18-JAN-13:39 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 32649.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2217.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 11275.51 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6149.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24657.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2379.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 54670.79 | 47640.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 32649.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2217.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 9907.93 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6149.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 24657.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 757.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 6.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1015.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 141.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 130.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 876.87 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 534.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 169.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 217.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2916.89 | 692.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 27.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4371.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 611.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 562.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3774.05 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2299.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 728.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 934.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 12554.23 | 2981.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 27.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4371.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 611.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 562.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3774.05 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2299.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 728.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 934.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 12554.23 | 2981.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.06 |
KITCHEN DIRECT AIR | 1.39 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.06 | 3.06 | 3.06 | 3.06 | 3.06 | 3.06 | 1.00 | 1.00 | 3.06 |
PSZ-AC_2:2 | 1.39 | 1.39 | 1.39 | 1.39 | 1.39 | 1.39 | 1.00 | 1.00 | 1.39 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.06 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.39 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.06 | 3348.18 |
PSZ-AC_2:2_ADDAQ FAN | 1.39 | 1589.35 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.06 | 3.06 | 3.06 | 3.06 | 71166.72 | 75426.02 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.39 | 1.39 | 1.39 | 1.39 | 34617.12 | 57288.76 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.06 | 1.53 | 3.06 | 71166.72 | 34226.82 | 71166.72 | 0.721610 | 0.721610 |
PSZ-AC_2:2 COOLING COIL | 1.39 | 0.697016 | 1.39 | 34617.12 | 17308.54 | 34617.12 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 75426.02 |
PSZ-AC_2:2 HEATING COIL | 57288.76 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 9.264 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 126.051 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 11.946 | 282.654 | 791.353 | 0.000 | 0.000 | 0.000 | 1085.952 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 1076.175 | 9.264 | 12.293 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1076.175 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1387.759 | 11.946 | 221.217 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1387.759 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 515.917 | 4.441 | 82.240 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 851.667 | 7.331 | 135.761 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.2003 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.2003 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.6929 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.892 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.892 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.209 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.20636098E-16 | 0.18100998E-15 | 0.17288268E-13 | -0.34766289E-16 |
24 | 3 | -0.71341822E-08 | 0.14427768E-06 | -0.58767875E-04 | 0.16137435E-12 |
25 | 2 | 0.62866063E-04 | 0.30866150E-02 | 1.1745480 | -0.77421164E-04 |
26 | 1 | -0.70719755E-01 | 0.78899699E-01 | -17.315014 | 0.34200793 |
27 | 0 | 0.20250090 | 0.49857543E-01 | 16.272369 | |
28 | 4 | 0.17288268E-13 | 0.18100998E-15 | 0.20636098E-16 | -0.34766289E-16 |
29 | 3 | -0.58767875E-04 | 0.14427768E-06 | -0.71341822E-08 | 0.16137435E-12 |
30 | 2 | 1.1745480 | 0.30866150E-02 | 0.62866063E-04 | -0.77421164E-04 |
31 | 1 | -17.315014 | 0.78899699E-01 | -0.70719755E-01 | 0.34200793 |
32 | 0 | 16.272369 | 0.49857543E-01 | 0.20250090 | |
33 | 7 | -0.33002231E-12 | 0.10712597E-14 | -0.10720425E-12 | 0.10137879E-15 |
34 | 6 | 0.29661659E-07 | 0.19687232E-09 | 0.67865745E-08 | -0.14052424E-12 |
35 | 5 | -0.19512200E-03 | 0.16741682E-05 | -0.10029371E-03 | 0.67057946E-08 |
36 | 4 | 0.29799499 | 0.81016957E-03 | 0.10178761 | -0.34398158E-04 |
37 | 3 | -7.3821031 | 0.24971312E-01 | -2.3732702 | 0.29576512E-01 |
38 | 2 | 41.252923 | 0.88368331E-01 | 15.405914 | -0.33759269 |
39 | 1 | -80.838295 | 0.39713828E-01 | -29.267905 | 1.0848528 |
40 | 0 | 46.824337 | 0.79570062E-03 | 16.288235 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
2 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
3 | NONRESWINDOW_U_1.2_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
4 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.052 | 0.3089 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 9.529E-002 | 8.202E-004 | 1.025E-003 | 0.969 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 9.529E-002 | 8.202E-004 | 1.004E-003 | 0.969 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 33729.14252 | 40474.97102 | 2.54924 | 3.05908 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 42.00000 | 9.15790E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 2692.72322 | 3231.26787 | 0.11550 | 0.41606 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 6.30000 | 6.07234E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 18457.17303 | 22148.60763 | 1.16169 | 1.39403 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 41.12700 | 9.15644E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.14133 | 00:10:00 | 6.30000 | 6.07234E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 48853.08 | 3.05908 | 3.05908 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 16537.72 | 0.41606 | 0.41606 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 42086.48 | 1.39403 | 1.39403 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 45366.59 | 1.14133 | 1.14133 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.05908 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.39403 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.05908 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.05908 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.05908 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.05908 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.05908 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.05908 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.39403 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39403 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.39403 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.39403 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.39403 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.39403 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.05908 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.39403 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.05908 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.05908 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 3348.18234 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.05908 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.05908 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.05908 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.05908 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.05908 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.52954 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.05908 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 71166.72000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 34226.81544 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 71166.72000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72161 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72161 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 71166.72000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 75426.01825 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 75426.01825 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.39403 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.39403 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1589.34907 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.39403 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.39403 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.39403 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.39403 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.39403 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.69702 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.39403 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34617.12000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 17308.54234 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 34617.12000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34617.12000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 57288.76331 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 57288.76331 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 68980.3 | 9.86 | 9.74 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 33626.3 | 10.66 | 10.53 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_EAST_0.25 | N/A | 6.813 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_SOUTH_0.25 | N/A | 6.813 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | N/A | 6.813 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.200 | 0.193 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.200 | 0.193 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.200 | 0.191 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.200 | 0.191 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 6.3801614688E-002 | 0.1160256580 | Pass | Pass | 0.2135677680 | 0.7856592700 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2972204103 | 0.7741036988 | Pass | Pass | 0.1382325770 | 0.6422632418 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4193858011 | 0.4083234024 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 523.75 | -79.8 | -118.0 | 7.75 | 1738.48 | 2072.26 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.190 | 0.200 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.190 | 0.200 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.190 | 0.200 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.190 | 0.200 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_1.2_SHGC_EAST_0.25 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 6.813 | 0.251 | 0.252 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_1.2_SHGC_SOUTH_0.25 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 6.813 | 0.251 | 0.252 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 6.813 | 0.251 | 0.252 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 6.813 | 0.251 | 0.252 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 6.813 | 0.251 | 0.252 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 9.2637 | 116.17 | 1076.18 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 19.58 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.9458 | 116.17 | 1387.76 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 25.25 |
Interior Lighting Total | 10.6047 | 232.34 | 2463.93 | 44.83 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 2625.88 | AstronomicalClock | - | 83.75 | 83.75 | 41.28 | |
Exterior Lighting Total | 2625.88 | 41.28 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 71166.72 | 51354.62 | 19812.10 | 0.72 | 3.23 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34617.12 | 24269.37 | 10347.75 | 0.70 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 68980.3 | 9.86 | 9.74 | ||||
PSZ-AC_2:2 COOLING COIL | 33626.3 | 10.66 | 10.53 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 75426.02 | 0.79 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 57288.76 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 1.56 | 1211.87 | 778.12 | 1.00 | 0.64 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.57 | 622.50 | 3.06 | 3348.18 | 1094.51 | 1.00 | 1.23 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.55 | 622.50 | 1.39 | 1589.35 | 1140.11 | 1.00 | 1.29 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 33729.14 | 40474.97 | 348.41 | 2.549 | 3.059 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 23.89 | 23.88 | 0.00806 | 42.00 | 0.00916 | 0.416 | 0.00 |
KITCHEN | 18457.17 | 22148.61 | 190.65 | 1.162 | 1.394 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 26.11 | 26.10 | 0.00851 | 41.13 | 0.00916 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 2692.72 | 3231.27 | 27.81 | 0.115 | 0.416 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00787 | 6.30 | 0.00607 | 0.416 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.141 | 00:10:00 | 15.56 | 30.00 | 0.00653 | 6.30 | 0.00607 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.06 | 3.06 | 0.42 | 0.42 | 3.0591 | 3.0591 | 3.0591 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.39 | 1.39 | 1.14 | 1.14 | 1.3940 | 1.3940 | 1.3940 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 71166.720 | 51354.617 | 3.059080 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 71166.72 | 60882.51 | 3.059080 | 26.34 | 16.70 | 0.00821264 | 11.89 | 9.94 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 13.6007 | 23.88 | 0.00806384 | 42.6575 | 33729.14 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 75426.018 | 75426.018 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 75426.02 | 75426.02 | 3.059082 | 19.10 | 13.59 | 0.00768265 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 13.6007 | 20.69 | 0.00793614 | 50.9903 | 1509.61 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 34617.120 | 24269.370 | 1.394030 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 34617.12 | 29547.14 | 1.394030 | 38.40 | 21.16 | 0.00903968 | 11.85 | 9.92 | 0.00700000 | 41.13 | 0.00915644 | 22.02 | 81.8730 | 26.10 | 0.00851237 | 39.4179 | 18457.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 57288.763 | 57288.763 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 57288.76 | 57288.76 | 1.394031 | 5.16 | 5.16 | 0.00615537 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 81.8729 | 30.00 | 0.00653039 | 24.1663 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 71166.720 | 51354.617 | 3.059080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1069 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.059082 | 3.59070627 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | Sensible | 71166.72 | 60882.51 | 1.0000 | 3.59070363 | 3.059080 | 26.34 | 16.70 | 0.00821264 | 47408.6 | 11.89 | 9.94 | 0.00700000 | 29604.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 71166.72 | 42.00 | 0.00915790 | 22.26 | 0.41605618 | 13.6007 | 23.87 | 0.00806384 | 23.88 | 0.00806384 | 42.6575 | 33729.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 75426.018 | 75426.018 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.059082 | 3.59070627 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 75426.02 | 75426.02 | 1.0000 | 3.59070627 | 3.059082 | 19.10 | 13.59 | 0.00768265 | 38674.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 75426.02 | 6.30 | 0.00607234 | 6.30 | 0.41605618 | 13.6007 | 21.11 | 0.00793614 | 20.69 | 0.00793614 | 50.9903 | 1509.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34617.120 | 24269.370 | 1.394030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6443 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.394031 | 1.63629388 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | Sensible | 34617.12 | 29547.14 | 1.0000 | 1.63629215 | 1.394030 | 38.40 | 21.16 | 0.00903968 | 61835.0 | 11.85 | 9.92 | 0.00700000 | 29567.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34617.12 | 41.13 | 0.00915644 | 22.02 | 1.14133354 | 81.8730 | 26.06 | 0.00851237 | 26.10 | 0.00851237 | 39.4179 | 18457.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 57288.763 | 57288.763 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.394031 | 1.63629388 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 57288.76 | 57288.76 | 1.0000 | 1.63629388 | 1.394031 | 5.16 | 5.16 | 0.00615537 | 20636.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57288.76 | 6.30 | 0.00607234 | 6.30 | 1.14133354 | 81.8729 | 0.00 | 0.00653039 | 30.00 | 0.00653039 | 24.1663 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 5996.00 | 3133.00 | 2276.50 |
KITCHEN | 6646.17 | 6347.00 | 5917.67 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 6646.17 | 6766.83 | 5917.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 116.83 | 0.00 | 0.33 |
KITCHEN | 0.00 | 2027.50 | 0.00 | 1589.50 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 2037.83 | 0.00 | 1589.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.363 | 4.119 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 12.077 | 0.021 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.000 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 10.988 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 11231994.10 | 0.00 | 11231994.10 | 10196601.73 | 21428595.83 | 13120747.55 | 1370.25 | 7384.83 | 4.93 | 481.35 |
KITCHEN | 31651791.93 | 0.00 | 31651791.93 | 74235.20 | 31726027.13 | 35993094.65 | 1298.95 | 7303.86 | 157.19 | 1055.39 |
Total Facility | 42883786.03 | 0.00 | 42883786.03 | 10270836.93 | 53154622.97 | 49113842.20 | 1374.44 | 7388.11 | 157.60 | 1076.76 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4161 | 0.0000 | 0.4161 | 0.3932 | 0.8093 | 0.4161 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 1.1413 | 0.0000 | 1.1413 | 0.0020 | 1.1433 | 1.1413 | 0.00 | 7187.00 | 0.00 |
Total Facility | 1.5574 | 0.0000 | 1.5574 | 0.3952 | 1.9527 | 1.5574 | 0.00 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 15475139.26 | 0.00 | 15475139.26 | 13120747.55 | 1326.99 | 1.42 | 7431.58 | 481.32 |
PSZ-AC_2:2 | 43608962.38 | 0.00 | 43608962.38 | 35993094.65 | 1259.49 | 2.83 | 7497.68 | 1055.39 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5733 | 0.0000 | 0.5733 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.5725 | 0.0000 | 1.5725 | 1.1413 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 275.49 | 0.00 | 7392.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 0.00 | 8242.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 0.5733 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 1.5725 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 370 |
Defaulted Fields | 263 |
Fields with Defaults | 871 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 921.03 | 6744.10 | 02-JAN-01:10 | 54670.79 | 10-JUN-18:10 |
Electricity:Building | 339.57 | 3046.93 | 01-JAN-01:10 | 20161.68 | 02-JAN-11:10 |
Electricity:Zone:DINING | 90.00 | 432.77 | 01-JAN-01:10 | 4903.08 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 321.71 | 2637.89 | 01-JAN-01:10 | 16645.57 | 02-JAN-11:10 |
InteriorLights:Electricity | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 19.58 | 161.43 | 01-JAN-01:10 | 968.56 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 19.58 | 161.43 | 01-JAN-01:10 | 968.56 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 249.57 | 2614.16 | 01-JAN-01:10 | 15258.60 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 25.25 | 208.16 | 01-JAN-01:10 | 1248.98 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 25.25 | 208.16 | 01-JAN-01:10 | 1248.98 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 276.88 | 2268.30 | 01-JAN-01:10 | 14428.03 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 276.88 | 2268.30 | 01-JAN-01:10 | 14428.03 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 206.46 | 1996.96 | 01-JAN-01:10 | 10493.51 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.33 | 629.37 | 01-JAN-01:10 | 9125.93 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 68.58 | 1068.10 | 20-DEC-23:30 | 4592.33 | 29-MAR-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
Electricity:Plant | 50.72 | 812.45 | 20-DEC-23:30 | 2608.58 | 14-JUL-04:10 |
LowTempRefrigeration:Refrigeration:Electricity | 18.20 | 0.00 | 01-JAN-11:10 | 1532.35 | 14-JUL-04:10 |
MedTempRefrigeration:Refrigeration:Electricity | 32.52 | 769.13 | 21-DEC-01:10 | 1076.23 | 02-JAN-14:10 |
ElectricityPurchased:Facility | 921.03 | 6744.10 | 02-JAN-01:10 | 54670.79 | 10-JUN-18:10 |
ElectricityPurchased:Plant | 921.03 | 6744.10 | 02-JAN-01:10 | 54670.79 | 10-JUN-18:10 |
Cogeneration:ElectricityPurchased | 921.03 | 6744.10 | 02-JAN-01:10 | 54670.79 | 10-JUN-18:10 |
General:Cogeneration:ElectricityPurchased | 921.03 | 6744.10 | 02-JAN-01:10 | 54670.79 | 10-JUN-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 921.03 | 6744.10 | 02-JAN-01:10 | 54670.79 | 10-JUN-18:10 |
ElectricityNet:Plant | 921.03 | 6744.10 | 02-JAN-01:10 | 54670.79 | 10-JUN-18:10 |
Cogeneration:ElectricityNet | 921.03 | 6744.10 | 02-JAN-01:10 | 54670.79 | 10-JUN-18:10 |
General:Cogeneration:ElectricityNet | 921.03 | 6744.10 | 02-JAN-01:10 | 54670.79 | 10-JUN-18:10 |
Electricity:HVAC | 489.45 | 0.00 | 01-JAN-01:10 | 38798.70 | 10-JUN-18:10 |
Fans:Electricity | 168.73 | 0.00 | 01-JAN-01:10 | 6149.40 | 01-JAN-00:10 |
General:Fans:Electricity | 168.73 | 0.00 | 01-JAN-01:10 | 6149.40 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 320.73 | 0.00 | 01-JAN-00:10 | 32649.30 | 10-JUN-18:10 |
General:Cooling:Electricity | 320.73 | 0.00 | 01-JAN-00:10 | 32649.30 | 10-JUN-18:10 |
ExteriorLights:Electricity | 41.28 | 0.00 | 01-JAN-07:20 | 2625.88 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 41.28 | 0.00 | 01-JAN-07:20 | 2625.88 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 05-MAR-08:50 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 05-MAR-08:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 639.07 | 2560.65 | 04-JAN-03:10 | 47640.49 | 18-JAN-13:40 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 5.83 | 0.00 | 01-JAN-00:10 | 20097.61 | 05-JAN-07:10 |
Heating:NaturalGas | 5.83 | 0.00 | 01-JAN-00:10 | 20097.61 | 05-JAN-07:10 |
General:Heating:NaturalGas | 5.83 | 0.00 | 01-JAN-00:10 | 20097.61 | 05-JAN-07:10 |
NaturalGas:Plant | 156.09 | 722.00 | 03-JAN-05:00 | 24657.34 | 18-JAN-13:40 |
WaterSystems:NaturalGas | 156.09 | 722.00 | 03-JAN-05:00 | 24657.34 | 18-JAN-13:40 |
Water Heater:WaterSystems:NaturalGas | 156.09 | 722.00 | 03-JAN-05:00 | 24657.34 | 18-JAN-13:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1866.63 | 3161.23 | 21-DEC-01:10 | 143700.24 | 01-JUL-18:10 |
EnergyTransfer:Building | 616.62 | 1580.61 | 21-DEC-01:10 | 45520.93 | 04-MAY-11:10 |
EnergyTransfer:Zone:KITCHEN | 403.11 | 1580.61 | 21-DEC-01:10 | 25281.78 | 06-JAN-05:10 |
Refrigeration:EnergyTransfer | 166.01 | 2894.67 | 20-DEC-23:30 | 7834.84 | 10-MAR-04:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 83.00 | 1447.34 | 20-DEC-23:30 | 3917.42 | 10-MAR-04:40 |
General:Refrigeration:EnergyTransfer | 83.00 | 1447.34 | 20-DEC-23:30 | 3917.42 | 10-MAR-04:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 83.00 | 1447.34 | 20-DEC-23:30 | 3917.42 | 10-MAR-04:40 |
EnergyTransfer:Plant | 182.85 | 1447.89 | 21-JAN-23:30 | 17721.28 | 17-JAN-13:40 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 16.67 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 66.34 | 1317.38 | 21-DEC-01:10 | 2238.70 | 02-JAN-14:10 |
EnergyTransfer:Zone:DINING | 213.51 | 0.00 | 01-JAN-01:10 | 28893.87 | 07-JUN-17:10 |
Heating:EnergyTransfer | 2.47 | 0.00 | 01-JAN-00:10 | 5886.99 | 03-MAY-23:10 |
Heating:EnergyTransfer:Zone:DINING | 2.41 | 0.00 | 01-JAN-00:10 | 5871.48 | 21-JAN-07:10 |
General:Heating:EnergyTransfer | 2.47 | 0.00 | 01-JAN-00:10 | 5886.99 | 03-MAY-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 2.41 | 0.00 | 01-JAN-00:10 | 5871.48 | 21-JAN-07:10 |
Cooling:EnergyTransfer | 531.15 | 0.00 | 01-JAN-01:10 | 41603.51 | 04-MAY-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 211.09 | 0.00 | 01-JAN-01:10 | 28893.87 | 07-JUN-17:10 |
General:Cooling:EnergyTransfer | 531.15 | 0.00 | 01-JAN-01:10 | 41603.51 | 04-MAY-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 211.09 | 0.00 | 01-JAN-01:10 | 28893.87 | 07-JUN-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.05 | 0.00 | 01-JAN-00:10 | 1466.32 | 03-JUN-23:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.05 | 0.00 | 01-JAN-00:10 | 1466.32 | 03-JUN-23:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 320.05 | 0.00 | 01-JAN-01:10 | 21429.39 | 06-JAN-05:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 320.05 | 0.00 | 01-JAN-01:10 | 21429.39 | 06-JAN-05:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 99.84 | 0.00 | 01-JAN-00:10 | 15060.23 | 16-JAN-13:20 |
PlantLoopHeatingDemand:Plant | 99.84 | 0.00 | 01-JAN-00:10 | 15060.23 | 16-JAN-13:20 |
WaterSystems:PlantLoopHeatingDemand | 99.84 | 0.00 | 01-JAN-00:10 | 15060.23 | 16-JAN-13:20 |
General:WaterSystems:PlantLoopHeatingDemand | 99.84 | 0.00 | 01-JAN-00:10 | 15060.23 | 16-JAN-13:20 |
EnergyTransfer:HVAC | 1067.16 | 0.00 | 01-JAN-00:10 | 102734.69 | 01-JUL-18:20 |
HeatingCoils:EnergyTransfer | 4.63 | 0.00 | 01-JAN-00:10 | 15983.57 | 05-JAN-07:10 |
CoolingCoils:EnergyTransfer | 1062.54 | 0.00 | 01-JAN-00:10 | 102734.69 | 01-JUL-18:20 |
WaterSystems:EnergyTransfer | 99.84 | 0.00 | 01-JAN-00:10 | 15060.23 | 16-JAN-13:20 |
WaterUse:WaterSystems:EnergyTransfer | 99.84 | 0.00 | 01-JAN-00:10 | 15060.23 | 16-JAN-13:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 2.415 | -211.092 | 0.000 | 0.000 | 65.809 | 19.580 | 52.814 | 32.012 | 0.000 | 57.543 | 17.416 | 0.000 | -10.107 | 0.000 | -26.389 | -0.000 |
KITCHEN | 0.000 | 0.000 | 0.054 | -320.047 | 0.000 | 0.000 | 3.871 | 25.249 | 212.059 | 0.000 | 0.000 | 0.228 | 78.863 | 0.000 | 0.000 | 0.000 | -0.279 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.437 | 9.922 | 0.000 | 0.000 | 0.000 | -15.358 | -0.000 |
Total Facility | 0.000 | 0.000 | 2.469 | -531.139 | 0.000 | 0.000 | 69.680 | 44.830 | 264.873 | 32.012 | 0.000 | 63.207 | 106.201 | 0.000 | -10.107 | 0.000 | -42.026 | -0.000 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 06-MAY-02:61 | 0.00 | 0.00 | 0.00 | -48292.52 | 0.00 | 0.00 | 0.00 | 161.43 | 203.51 | 34.93 | 0.00 | 62.54 | 47830.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 31-JAN-05:01 | 0.00 | 0.00 | 0.00 | -50974.20 | 0.00 | 0.00 | 9.09 | 277.55 | 5273.28 | 0.00 | 0.00 | 0.00 | 45417.73 | 0.00 | -0.00 | 0.00 | -3.45 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-MAY-02:61 | 0.00 | 0.00 | 0.00 | -78617.61 | 0.00 | 0.00 | 0.00 | 369.59 | 2222.04 | 34.93 | 0.00 | 501.77 | 75489.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 03-MAY-23:11 | 0.00 | 0.00 | 6009.42 | 0.00 | 0.00 | 0.00 | 165.35 | 161.43 | 305.26 | 701.94 | 0.00 | 61.89 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7405.29 |
KITCHEN | 03-MAY-23:01 | 0.00 | 0.00 | 11620.54 | 0.00 | 0.00 | 0.00 | 18.55 | 208.16 | 2344.01 | 0.00 | 0.00 | 62.79 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14254.05 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-MAY-23:01 | 0.00 | 0.00 | 17602.76 | 0.00 | 0.00 | 0.00 | 325.17 | 369.59 | 2649.27 | 939.35 | 0.00 | 529.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22415.78 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.0591 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 3.0591 | 0.1360 | 1.0000 | Not calculated | 0.4161 | 0.1360 | ||
PSZ-AC_2:2 | 1.3940 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.3940 | 0.1085 | 1.0000 | Not calculated | 0.1513 | 0.1085 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.0591 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 3.0591 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.1360 | ||
PSZ-AC_2:2 | 1.3940 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.3940 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1085 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.0591 | 3.0591 | 3.0591 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3940 | 1.3940 | 1.3940 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.0591 | 3.0591 | 3.0591 | 3.0591 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.3940 | 1.3940 | 1.3940 | 1.3940 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.0591 | 3.0591 | 3.0591 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3940 | 1.3940 | 1.3940 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.0591 | 3.0591 | 3.0591 | 3.0591 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.3940 | 1.3940 | 1.3940 | 1.3940 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1589.83 |
Number of hours not met | 1589.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 5.83 | 20097.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 320.73 | 32649.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 44.83 | 2217.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 41.28 | 2625.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.75 | 13060.45 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 168.73 | 6149.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 156.09 | 24657.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 17.86 | 3516.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 18.20 | 1532.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 32.52 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 345.46 | 921.03 |
Natural Gas | 477.16 | 639.07 |
Additional | 0.00 | 0.00 |
Total | 822.62 | 1560.10 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 192.95 |
Space Heating | 0.00 |
Space Cooling | 1380.40 |
Fans (All) | 726.19 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1191.68 |
Miscellaneous (All) | 3964.08 |
Subtotal | 3964.08 |
Natural Gas [MJ/m2] | |
Space Heating | 25.08 |
Service Water Heating | 671.80 |
Miscellaneous (All) | 2750.56 |
Subtotal | 2750.56 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.87 |
Space Heating | 0.37 |
Space Cooling | 20.56 |
Fans (All) | 10.82 |
Service Water Heating | 10.01 |
Receptacle Equipment | 48.33 |
Miscellaneous | 7.04 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 5084. | 8760. |
LTG_SCH_KITCHEN | 5084. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8179.00 | 427.67 | 153.33 | 0.00 | 0.00 |
KITCHEN | 5772.33 | 2350.00 | 637.67 | 0.00 | 0.00 |
ATTIC | 4247.33 | 1064.83 | 1083.67 | 1138.67 | 1225.50 |
Min | 4247.33 | 427.67 | 153.33 | 0.00 | 0.00 |
Max | 8179.00 | 2350.00 | 1083.67 | 1138.67 | 1225.50 |
Average | 6066.22 | 1280.83 | 624.89 | 379.56 | 408.50 |
Sum | 18198.67 | 3842.50 | 1874.67 | 1138.67 | 1225.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 253962.33 | 546.00 | 216.67 | 0.00 | 0.00 |
KITCHEN | 11607.83 | 3640.33 | 1009.83 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 253962.33 | 3640.33 | 1009.83 | 0.00 | 0.00 |
Average | 88523.39 | 1395.44 | 408.83 | 0.00 | 0.00 |
Sum | 265570.17 | 4186.33 | 1226.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 5932.67 | 2778.83 | 48.50 | 0.00 | 0.00 |
KITCHEN | 3148.33 | 5357.00 | 254.67 | 0.00 | 0.00 |
ATTIC | 3473.67 | 2246.33 | 873.67 | 510.33 | 1656.00 |
Min | 3148.33 | 2246.33 | 48.50 | 0.00 | 0.00 |
Max | 5932.67 | 5357.00 | 873.67 | 510.33 | 1656.00 |
Average | 4184.89 | 3460.72 | 392.28 | 170.11 | 552.00 |
Sum | 12554.67 | 10382.17 | 1176.83 | 510.33 | 1656.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 182672.83 | 71969.50 | 82.67 | 0.00 | 0.00 |
KITCHEN | 5731.17 | 10152.67 | 374.17 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 182672.83 | 71969.50 | 374.17 | 0.00 | 0.00 |
Average | 62801.33 | 27374.06 | 152.28 | 0.00 | 0.00 |
Sum | 188404.00 | 82122.17 | 456.83 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:20
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Environment
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.346693E+10 | 8471.66 | 12-JAN-14:00 | 23.30 | 13.98 | 0.502664E+10 | 4681.82 | 14-JAN-19:00 | 18.20 | 13.91 |
February | 0.627544E+10 | 12525.12 | 22-FEB-12:55 | 26.60 | 15.84 | 0.474969E+10 | 4681.83 | 25-FEB-19:19 | 19.33 | 16.87 |
March | 0.137155E+11 | 29879.31 | 11-MAR-03:01 | 24.00 | 17.89 | 0.546186E+10 | 4681.83 | 18-MAR-18:00 | 19.20 | 16.78 |
April | 0.223819E+11 | 44282.00 | 28-APR-02:61 | 29.83 | 17.14 | 0.526603E+10 | 4682.13 | 08-APR-18:00 | 29.83 | 17.14 |
May | 0.282237E+11 | 48292.24 | 06-MAY-02:61 | 31.75 | 18.39 | 0.545206E+10 | 4682.67 | 27-MAY-18:00 | 37.40 | 20.18 |
June | 0.282013E+11 | 43013.05 | 05-JUN-02:61 | 31.48 | 20.26 | 0.530094E+10 | 4682.82 | 10-JUN-18:19 | 40.97 | 26.32 |
July | 0.264024E+11 | 32327.86 | 01-JUL-02:61 | 31.37 | 24.28 | 0.542077E+10 | 4681.84 | 22-JUL-18:10 | 30.30 | 26.77 |
August | 0.248136E+11 | 32111.41 | 03-AUG-02:61 | 29.53 | 23.75 | 0.548079E+10 | 4681.84 | 19-AUG-18:00 | 26.10 | 25.58 |
September | 0.222846E+11 | 34280.32 | 29-SEP-02:61 | 25.03 | 20.73 | 0.526719E+10 | 4681.86 | 09-SEP-18:10 | 25.03 | 20.73 |
October | 0.191357E+11 | 36081.65 | 05-OCT-02:61 | 23.13 | 17.70 | 0.541618E+10 | 4681.83 | 14-OCT-18:00 | 27.00 | 19.45 |
November | 0.112833E+11 | 17556.73 | 09-NOV-03:01 | 17.85 | 16.23 | 0.519290E+10 | 4681.82 | 18-NOV-19:40 | 19.90 | 16.27 |
December | 0.490951E+10 | 9785.84 | 28-DEC-14:00 | 24.60 | 15.30 | 0.508748E+10 | 4681.82 | 16-DEC-19:10 | 24.60 | 15.30 |
Annual Sum or Average | 0.211094E+12 | 0.631225E+11 | ||||||||
Minimum of Months | 0.346693E+10 | 8471.66 | 17.85 | 13.98 | 0.474969E+10 | 4681.82 | 18.20 | 13.91 | ||
Maximum of Months | 0.282237E+11 | 48292.24 | 31.75 | 24.28 | 0.548079E+10 | 4682.82 | 40.97 | 26.77 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.254793E+11 | 51038.43 | 31-JAN-05:01 | 6.43 | 5.71 | 0.780162E+10 | 5138.43 | 19-JAN-11:00 | 6.43 | 5.71 |
February | 0.227558E+11 | 47534.68 | 03-FEB-05:01 | 9.08 | 7.98 | 0.707771E+10 | 5138.45 | 21-FEB-11:00 | 24.30 | 14.53 |
March | 0.256516E+11 | 43451.48 | 01-MAR-03:01 | 13.38 | 10.98 | 0.786327E+10 | 5138.45 | 10-MAR-11:50 | 30.00 | 18.87 |
April | 0.261396E+11 | 39049.95 | 11-APR-02:61 | 20.27 | 13.73 | 0.761119E+10 | 5140.43 | 17-APR-10:00 | 34.50 | 22.99 |
May | 0.282777E+11 | 32789.83 | 28-MAY-02:61 | 28.28 | 17.05 | 0.787520E+10 | 5178.34 | 22-MAY-10:50 | 28.28 | 17.05 |
June | 0.276453E+11 | 27383.02 | 05-JUN-02:61 | 31.48 | 20.26 | 0.765102E+10 | 5211.30 | 28-JUN-10:00 | 32.50 | 28.26 |
July | 0.281864E+11 | 22742.82 | 11-JUL-02:61 | 26.50 | 23.05 | 0.792645E+10 | 5218.03 | 17-JUL-10:50 | 34.45 | 27.92 |
August | 0.282769E+11 | 23289.95 | 29-AUG-02:61 | 28.22 | 24.65 | 0.793776E+10 | 5231.51 | 25-AUG-10:50 | 28.22 | 24.65 |
September | 0.277895E+11 | 26722.50 | 29-SEP-02:61 | 25.03 | 20.73 | 0.763701E+10 | 5201.41 | 12-SEP-10:50 | 25.03 | 20.73 |
October | 0.281770E+11 | 36829.90 | 24-OCT-02:11 | 18.73 | 14.80 | 0.786210E+10 | 5142.75 | 04-OCT-10:00 | 18.73 | 14.80 |
November | 0.256973E+11 | 44530.61 | 27-NOV-03:01 | 11.55 | 9.68 | 0.759765E+10 | 5138.45 | 20-NOV-11:00 | 11.55 | 9.68 |
December | 0.259746E+11 | 49164.49 | 03-DEC-03:01 | 8.93 | 7.78 | 0.781389E+10 | 5138.45 | 06-DEC-11:00 | 20.80 | 12.61 |
Annual Sum or Average | 0.320051E+12 | 0.926549E+11 | ||||||||
Minimum of Months | 0.227558E+11 | 22742.82 | 6.43 | 5.71 | 0.707771E+10 | 5138.43 | 6.43 | 5.71 | ||
Maximum of Months | 0.282777E+11 | 51038.43 | 31.48 | 24.65 | 0.793776E+10 | 5231.51 | 34.50 | 28.26 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 7.83 | 7.49 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.85 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.85 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.96 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.96 |
April | 0.00 | 0.00 | 01-APR-00:01 | 23.70 | 16.77 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.77 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 30.53 | 18.24 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.24 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 28.05 | 22.58 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.58 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 32.95 | 24.65 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.65 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.32 | 26.26 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 28.43 | 25.91 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 26.58 | 21.85 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.85 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.72 | 15.09 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.11 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.11 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.00 | 0.00 | 32.95 | 26.26 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.675828E+09 | 5871.48 | 21-JAN-07:10 | 5.63 |
February | 0.110260E+09 | 3933.06 | 04-FEB-07:10 | 8.40 |
March | 26131337.22 | 2226.01 | 11-MAR-00:01 | 24.75 |
April | 0.183109E+09 | 4915.30 | 27-APR-23:01 | 32.73 |
May | 0.245989E+09 | 6009.33 | 03-MAY-23:11 | 36.00 |
June | 0.237893E+09 | 5874.07 | 05-JUN-23:01 | 35.62 |
July | 0.229962E+09 | 5686.78 | 02-JUL-23:01 | 35.28 |
August | 0.208784E+09 | 4669.16 | 08-AUG-23:11 | 32.03 |
September | 0.186227E+09 | 3942.45 | 17-SEP-23:11 | 29.97 |
October | 50787278.64 | 3810.20 | 22-OCT-23:01 | 29.42 |
November | 1301607.24 | 623.24 | 27-NOV-07:10 | 10.02 |
December | 0.257818E+09 | 5858.04 | 31-DEC-07:10 | 5.53 |
Annual Sum or Average | 0.241409E+10 | |||
Minimum of Months | 1301607.24 | 623.24 | 5.53 | |
Maximum of Months | 0.675828E+09 | 6009.33 | 36.00 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 5700199.15 | 7876.18 | 27-APR-23:01 | 32.73 |
May | 15924345.98 | 11620.81 | 03-MAY-23:01 | 35.95 |
June | 16833704.18 | 11236.61 | 05-JUN-23:01 | 35.62 |
July | 8351640.20 | 9297.08 | 04-JUL-23:01 | 35.10 |
August | 4321010.30 | 5042.85 | 02-AUG-23:01 | 30.53 |
September | 2707751.71 | 2872.77 | 17-SEP-23:02 | 30.23 |
October | 523512.72 | 3973.98 | 22-OCT-23:01 | 29.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 54362164.24 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 16833704.18 | 11620.81 | 35.95 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:01 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.165449E+10 | 968.56 | 02-JAN-10:09 | 0.598074E+10 | 3934.52 | 01-JAN-11:09 |
February | 0.149855E+10 | 968.56 | 01-FEB-10:09 | 0.540196E+10 | 3934.52 | 01-FEB-11:09 |
March | 0.168084E+10 | 968.56 | 01-MAR-10:09 | 0.598074E+10 | 3934.52 | 01-MAR-11:09 |
April | 0.160761E+10 | 968.56 | 01-APR-16:10 | 0.578781E+10 | 3934.52 | 01-APR-10:09 |
May | 0.166766E+10 | 968.56 | 01-MAY-09:09 | 0.598074E+10 | 3934.52 | 01-MAY-10:09 |
June | 0.162466E+10 | 968.56 | 01-JUN-09:09 | 0.578781E+10 | 3934.52 | 01-JUN-10:09 |
July | 0.165081E+10 | 968.56 | 01-JUL-16:10 | 0.598074E+10 | 3934.52 | 01-JUL-10:09 |
August | 0.168084E+10 | 968.56 | 01-AUG-09:09 | 0.598074E+10 | 3934.52 | 01-AUG-10:09 |
September | 0.160800E+10 | 968.56 | 01-SEP-09:09 | 0.578781E+10 | 3934.52 | 01-SEP-10:09 |
October | 0.165430E+10 | 968.56 | 02-OCT-09:09 | 0.598074E+10 | 3934.52 | 01-OCT-10:09 |
November | 0.160161E+10 | 968.56 | 01-NOV-09:09 | 0.578781E+10 | 3934.52 | 01-NOV-10:09 |
December | 0.165100E+10 | 968.56 | 01-DEC-10:09 | 0.598074E+10 | 3934.52 | 01-DEC-11:09 |
Annual Sum or Average | 0.195804E+11 | 0.704184E+11 | ||||
Minimum of Months | 0.149855E+10 | 968.56 | 0.540196E+10 | 3934.52 | ||
Maximum of Months | 0.168084E+10 | 968.56 | 0.598074E+10 | 3934.52 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.213351E+10 | 1248.98 | 02-JAN-10:09 | 0.175350E+11 | 10493.51 | 01-JAN-11:09 |
February | 0.193243E+10 | 1248.98 | 01-FEB-10:09 | 0.158380E+11 | 10493.51 | 01-FEB-11:09 |
March | 0.216749E+10 | 1248.98 | 01-MAR-10:09 | 0.175350E+11 | 10493.51 | 01-MAR-11:09 |
April | 0.207306E+10 | 1248.98 | 01-APR-16:10 | 0.169693E+11 | 10493.51 | 01-APR-10:09 |
May | 0.215050E+10 | 1248.98 | 01-MAY-09:09 | 0.175350E+11 | 10493.51 | 01-MAY-10:09 |
June | 0.209504E+10 | 1248.98 | 01-JUN-09:09 | 0.169693E+11 | 10493.51 | 01-JUN-10:09 |
July | 0.212877E+10 | 1248.98 | 01-JUL-16:10 | 0.175350E+11 | 10493.51 | 01-JUL-10:09 |
August | 0.216749E+10 | 1248.98 | 01-AUG-09:09 | 0.175350E+11 | 10493.51 | 01-AUG-10:09 |
September | 0.207356E+10 | 1248.98 | 01-SEP-09:09 | 0.169693E+11 | 10493.51 | 01-SEP-10:09 |
October | 0.213326E+10 | 1248.98 | 02-OCT-09:09 | 0.175350E+11 | 10493.51 | 01-OCT-10:09 |
November | 0.206532E+10 | 1248.98 | 01-NOV-09:09 | 0.169693E+11 | 10493.51 | 01-NOV-10:09 |
December | 0.212902E+10 | 1248.98 | 01-DEC-10:09 | 0.175350E+11 | 10493.51 | 01-DEC-11:09 |
Annual Sum or Average | 0.252494E+11 | 0.206460E+12 | ||||
Minimum of Months | 0.193243E+10 | 1248.98 | 0.158380E+11 | 10493.51 | ||
Maximum of Months | 0.216749E+10 | 1248.98 | 0.175350E+11 | 10493.51 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.165449E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844870E+10 |
February | 0.852256E+10 | 0.149855E+10 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135979E+09 | 0.468545E+10 |
March | 0.954557E+10 | 0.168084E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200676E+10 | 0.172856E+10 |
April | 0.915225E+10 | 0.160761E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723360E+10 | 0.134968E+09 |
May | 0.947560E+10 | 0.166766E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109348E+11 | 2942444.72 |
June | 0.922788E+10 | 0.162466E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108603E+11 | 704587.02 |
July | 0.939996E+10 | 0.165081E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861609E+10 | 853090.85 |
August | 0.954557E+10 | 0.168084E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714365E+10 | 842076.05 |
September | 0.915225E+10 | 0.160800E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588964E+10 | 1808275.21 |
October | 0.940563E+10 | 0.165430E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375265E+10 | 0.676679E+09 |
November | 0.909363E+10 | 0.160161E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963105E+09 | 0.324752E+10 |
December | 0.939996E+10 | 0.165100E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5879804.32 | 0.745949E+10 |
Annual Sum or Average | 0.111326E+12 | 0.195804E+11 | 0.704184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575425E+11 | 0.263885E+11 |
Minimum of Months | 0.852256E+10 | 0.149855E+10 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 704587.02 |
Maximum of Months | 0.954557E+10 | 0.168084E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109348E+11 | 0.844870E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.213351E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57124589.92 |
February | 0.610713E+09 | 0.193243E+10 | 0.120792E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 31233.74 | 64176806.41 |
March | 0.684021E+09 | 0.216749E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 6222099.36 | 52184722.78 |
April | 0.655836E+09 | 0.207306E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 34204594.80 | 6330723.33 |
May | 0.679007E+09 | 0.215050E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 63676706.84 | 6077509.92 |
June | 0.661256E+09 | 0.209504E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 42132703.89 | 3037039.41 |
July | 0.673587E+09 | 0.212877E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 36021197.82 | 5544958.64 |
August | 0.684021E+09 | 0.216749E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 18816723.32 | 5087915.56 |
September | 0.655836E+09 | 0.207356E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 15872354.91 | 5264572.22 |
October | 0.673993E+09 | 0.213326E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 9375844.16 | 5270835.01 |
November | 0.651635E+09 | 0.206532E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 1264855.36 | 15476692.54 |
December | 0.673587E+09 | 0.212902E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52999927.03 |
Annual Sum or Average | 0.797748E+10 | 0.252494E+11 | 0.157461E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 0.227618E+09 | 0.278576E+09 |
Minimum of Months | 0.610713E+09 | 0.193243E+10 | 0.120792E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3037039.41 |
Maximum of Months | 0.684021E+09 | 0.216749E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 63676706.84 | 64176806.41 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546510E+09 | 0.965724E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415455E+09 | 0.105120E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448374E+09 | 0.146559E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509930E+09 | 0.165933E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447086E+09 | 0.168156E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418809E+09 | 0.159938E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264101E+09 | 0.128165E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254545E+09 | 0.121766E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370231E+09 | 0.106726E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568817E+09 | 0.130972E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597273E+09 | 0.109002E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595492E+09 | 0.969340E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543662E+10 | 0.153584E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254545E+09 | 0.965724E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597273E+09 | 0.168156E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 968.56 | 02-JAN-10:09 | 3934.52 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 10748.85 | 02-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 968.56 | 01-FEB-10:09 | 3934.52 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2399.00 | 22-FEB-14:00 | 8352.43 | 04-FEB-19:53 |
March | 9454.80 | 04-MAR-19:10 | 968.56 | 01-MAR-10:09 | 3934.52 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8962.27 | 28-MAR-17:10 | 4898.06 | 01-MAR-21:00 |
April | 9454.80 | 01-APR-18:10 | 968.56 | 01-APR-16:10 | 3934.52 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12474.03 | 27-APR-17:02 | 2622.88 | 11-APR-06:10 |
May | 9454.80 | 06-MAY-18:10 | 968.56 | 01-MAY-09:09 | 3934.52 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15259.92 | 03-MAY-17:02 | 465.62 | 13-MAY-06:10 |
June | 9454.80 | 03-JUN-18:10 | 968.56 | 01-JUN-09:09 | 3934.52 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16098.40 | 07-JUN-17:03 | 84.59 | 18-JUN-00:01 |
July | 9454.80 | 01-JUL-18:10 | 968.56 | 01-JUL-16:10 | 3934.52 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12703.69 | 03-JUL-17:03 | 51.33 | 19-JUL-01:51 |
August | 9454.80 | 05-AUG-18:10 | 968.56 | 01-AUG-09:09 | 3934.52 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10476.03 | 07-AUG-17:03 | 65.95 | 16-AUG-00:01 |
September | 9454.80 | 02-SEP-18:10 | 968.56 | 01-SEP-09:09 | 3934.52 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10043.44 | 17-SEP-20:00 | 121.87 | 27-SEP-05:10 |
October | 9454.80 | 07-OCT-18:10 | 968.56 | 02-OCT-09:09 | 3934.52 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9847.21 | 02-OCT-12:00 | 4484.84 | 29-OCT-06:10 |
November | 9454.80 | 04-NOV-18:10 | 968.56 | 01-NOV-09:09 | 3934.52 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4637.65 | 09-NOV-13:00 | 7754.52 | 25-NOV-19:55 |
December | 9454.80 | 02-DEC-19:10 | 968.56 | 01-DEC-10:09 | 3934.52 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 554.89 | 28-DEC-14:00 | 10311.96 | 30-DEC-20:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 968.56 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.33 | |||||
Maximum of Months | 9454.80 | 968.56 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 16098.40 | 10748.85 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 1248.98 | 02-JAN-10:09 | 7755.73 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 275.44 | 15-JAN-03:10 |
February | 677.52 | 04-FEB-19:10 | 1248.98 | 01-FEB-10:09 | 7755.73 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 2.19 | 22-FEB-14:55 | 367.93 | 26-FEB-01:50 |
March | 677.52 | 04-MAR-19:10 | 1248.98 | 01-MAR-10:09 | 7755.73 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 46.96 | 27-MAR-15:00 | 1020.52 | 25-MAR-00:20 |
April | 677.52 | 01-APR-18:10 | 1248.98 | 01-APR-16:10 | 7755.73 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 134.40 | 15-APR-14:30 | 137.74 | 05-APR-00:40 |
May | 677.52 | 06-MAY-18:10 | 1248.98 | 01-MAY-09:09 | 7755.73 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 196.93 | 04-MAY-00:05 | 192.57 | 15-MAY-02:00 |
June | 677.52 | 03-JUN-18:10 | 1248.98 | 01-JUN-09:09 | 7755.73 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 128.26 | 06-JUN-14:55 | 226.17 | 18-JUN-00:40 |
July | 677.52 | 01-JUL-18:10 | 1248.98 | 01-JUL-16:10 | 7755.73 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 124.31 | 03-JUL-03:30 | 137.55 | 26-JUL-02:00 |
August | 677.52 | 05-AUG-18:10 | 1248.98 | 01-AUG-09:09 | 7755.73 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 89.60 | 31-AUG-02:10 | 130.62 | 16-AUG-00:40 |
September | 677.52 | 02-SEP-18:10 | 1248.98 | 01-SEP-09:09 | 7755.73 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 52.52 | 28-SEP-14:00 | 115.25 | 09-SEP-00:40 |
October | 677.52 | 07-OCT-18:10 | 1248.98 | 02-OCT-09:09 | 7755.73 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 62.82 | 03-OCT-14:53 | 206.27 | 12-OCT-02:00 |
November | 677.52 | 04-NOV-18:10 | 1248.98 | 01-NOV-09:09 | 7755.73 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 13.90 | 13-NOV-14:00 | 240.42 | 28-NOV-04:50 |
December | 677.52 | 02-DEC-19:10 | 1248.98 | 01-DEC-10:09 | 7755.73 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 449.63 | 29-DEC-04:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 1248.98 | 7755.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 115.25 | ||||||
Maximum of Months | 677.52 | 1248.98 | 7755.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 196.93 | 1020.52 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.22 | 23-JAN-07:20 | 1914.61 | 31-JAN-13:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.82 | 19-FEB-23:00 | 1983.93 | 20-FEB-13:50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 604.62 | 28-MAR-06:45 | 2269.54 | 31-MAR-13:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 617.10 | 22-APR-15:10 | 2470.27 | 07-APR-12:40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 854.99 | 22-MAY-14:00 | 2395.42 | 14-MAY-13:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 993.42 | 03-JUN-18:40 | 2533.96 | 08-JUN-13:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.71 | 04-JUL-05:40 | 2324.60 | 10-JUL-13:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.33 | 24-AUG-06:10 | 2009.67 | 05-AUG-13:30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.31 | 30-SEP-06:45 | 2002.53 | 26-SEP-13:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.14 | 02-OCT-06:35 | 2202.74 | 09-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 581.72 | 24-NOV-07:15 | 1937.96 | 23-NOV-12:50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 714.03 | 03-DEC-07:23 | 1844.30 | 27-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.33 | 1844.30 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 993.42 | 2533.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8471.66 | 12-JAN-14:00 | 7353.73 | 968.56 | 3391.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.71 |
February | 12525.12 | 22-FEB-12:55 | 16808.53 | 1937.12 | 7326.35 | 0.00 | 0.00 | 0.00 | 0.00 | 2345.05 | 0.00 |
March | 29879.31 | 11-MAR-03:01 | 0.00 | 1614.26 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.01 |
April | 44282.00 | 28-APR-02:61 | 0.00 | 1614.26 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 48292.24 | 06-MAY-02:61 | 0.00 | 1614.26 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 62.54 | 0.00 |
June | 43013.05 | 05-JUN-02:61 | 0.00 | 1614.26 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 | 0.00 |
July | 32327.86 | 01-JUL-02:61 | 0.00 | 1614.26 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 69.98 | 0.00 |
August | 32111.41 | 03-AUG-02:61 | 0.00 | 1614.26 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 40.82 | 0.00 |
September | 34280.32 | 29-SEP-02:61 | 0.00 | 1614.26 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36081.65 | 05-OCT-02:61 | 0.00 | 1614.26 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 |
November | 17556.73 | 09-NOV-03:01 | 0.00 | 1129.98 | 1899.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9785.84 | 28-DEC-14:00 | 7353.73 | 968.56 | 3391.83 | 0.00 | 0.00 | 0.00 | 0.00 | 554.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8471.66 | 0.00 | 968.56 | 1899.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48292.24 | 16808.53 | 1937.12 | 7326.35 | 0.00 | 0.00 | 0.00 | 0.00 | 2345.05 | 464.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 51038.43 | 31-JAN-05:01 | 376.40 | 2775.52 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 3.45 |
February | 47534.68 | 03-FEB-05:01 | 376.40 | 2775.52 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 12.63 |
March | 43451.48 | 01-MAR-03:01 | 0.00 | 2081.64 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 34.55 |
April | 39049.95 | 11-APR-02:61 | 0.00 | 2081.64 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32789.83 | 28-MAY-02:61 | 0.00 | 2081.64 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 |
June | 27383.02 | 05-JUN-02:61 | 0.00 | 2081.64 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.61 | 0.00 |
July | 22742.82 | 11-JUL-02:61 | 0.00 | 2081.64 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 55.51 |
August | 23289.95 | 29-AUG-02:61 | 0.00 | 2081.64 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 44.79 |
September | 26722.50 | 29-SEP-02:61 | 0.00 | 2081.64 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 36829.90 | 24-OCT-02:11 | 0.00 | 2081.64 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 29.62 |
November | 44530.61 | 27-NOV-03:01 | 0.00 | 2081.64 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 49164.49 | 03-DEC-03:01 | 0.00 | 2081.64 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 22742.82 | 0.00 | 2081.64 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51038.43 | 376.40 | 2775.52 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.61 | 55.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.77 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.42 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.86 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.91 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.15 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.98 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.39 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.37 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.15 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.94 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.40 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.15 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.529825E+11 | 32209.36 | 26-JAN-11:00 | 0.600201E+11 | 47640.49 | 18-JAN-13:39 |
February | 0.519868E+11 | 35944.65 | 22-FEB-11:00 | 0.511797E+11 | 47546.38 | 02-FEB-13:39 |
March | 0.668954E+11 | 42110.64 | 10-MAR-18:30 | 0.551626E+11 | 46996.25 | 01-MAR-13:50 |
April | 0.776945E+11 | 49177.20 | 27-APR-11:09 | 0.521592E+11 | 45539.68 | 03-APR-12:20 |
May | 0.930962E+11 | 53328.64 | 02-MAY-11:00 | 0.526510E+11 | 43719.60 | 03-MAY-12:20 |
June | 0.961986E+11 | 54670.79 | 10-JUN-18:10 | 0.500203E+11 | 41833.67 | 01-JUN-12:30 |
July | 0.100672E+12 | 53983.76 | 10-JUL-11:00 | 0.512489E+11 | 40322.76 | 01-JUL-12:39 |
August | 0.990421E+11 | 52939.73 | 25-AUG-11:20 | 0.515584E+11 | 41555.48 | 31-AUG-12:50 |
September | 0.905761E+11 | 51488.10 | 17-SEP-19:00 | 0.507423E+11 | 43377.65 | 27-SEP-12:39 |
October | 0.762380E+11 | 47836.01 | 04-OCT-11:20 | 0.536874E+11 | 45493.99 | 31-OCT-12:20 |
November | 0.610918E+11 | 40231.12 | 09-NOV-12:09 | 0.532134E+11 | 46781.69 | 29-NOV-13:39 |
December | 0.545516E+11 | 33703.65 | 18-DEC-11:00 | 0.574297E+11 | 47472.04 | 27-DEC-13:20 |
Annual Sum or Average | 0.921025E+12 | 0.639073E+12 | ||||
Minimum of Months | 0.519868E+11 | 32209.36 | 0.500203E+11 | 40322.76 | ||
Maximum of Months | 0.100672E+12 | 54670.79 | 0.600201E+11 | 47640.49 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.378800E+10 | 0.396718E+10 | 0.235157E+11 | 0.00 | 0.139957E+11 | 0.79 | 0.00 | 0.219597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.343098E+10 | 0.343308E+10 | 0.212400E+11 | 0.00 | 0.127252E+11 | 0.72 | 0.00 | 0.605036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384832E+10 | 0.355754E+10 | 0.235157E+11 | 0.00 | 0.142187E+11 | 0.80 | 0.00 | 0.159772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.368067E+10 | 0.320462E+10 | 0.227571E+11 | 0.00 | 0.138337E+11 | 0.77 | 0.00 | 0.285912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.381816E+10 | 0.310221E+10 | 0.235157E+11 | 0.00 | 0.143976E+11 | 0.80 | 0.00 | 0.423752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.371970E+10 | 0.288952E+10 | 0.227571E+11 | 0.00 | 0.140771E+11 | 0.77 | 0.00 | 0.469722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.377958E+10 | 0.304707E+10 | 0.235157E+11 | 0.00 | 0.146741E+11 | 0.79 | 0.00 | 0.496361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.384832E+10 | 0.321565E+10 | 0.235157E+11 | 0.00 | 0.146679E+11 | 0.80 | 0.00 | 0.477567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.368156E+10 | 0.334012E+10 | 0.227571E+11 | 0.00 | 0.140852E+11 | 0.77 | 0.00 | 0.409153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.378756E+10 | 0.369934E+10 | 0.235157E+11 | 0.00 | 0.143016E+11 | 0.79 | 0.00 | 0.250208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.366693E+10 | 0.378599E+10 | 0.227571E+11 | 0.00 | 0.137319E+11 | 0.77 | 0.00 | 0.116077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.378002E+10 | 0.404123E+10 | 0.235157E+11 | 0.00 | 0.140166E+11 | 0.79 | 0.00 | 0.362847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448298E+11 | 0.412836E+11 | 0.276879E+12 | 0.00 | 0.168725E+12 | 9.37 | 0.00 | 0.320727E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.343098E+10 | 0.288952E+10 | 0.212400E+11 | 0.00 | 0.127252E+11 | 0.72 | 0.00 | 0.219597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.384832E+10 | 0.404123E+10 | 0.235157E+11 | 0.00 | 0.146741E+11 | 0.80 | 0.00 | 0.496361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.370065E+10 | 0.00 | 0.157937E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.593128E+09 | 0.00 | 0.139827E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.146369E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.129408E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.121253E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.108019E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.107231E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.110326E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.115239E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.131617E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 22568716.73 | 0.00 | 0.139724E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.151084E+10 | 0.00 | 0.153932E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.582718E+10 | 0.00 | 0.156088E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.00 | 0.00 | 0.107231E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.370065E+10 | 0.00 | 0.157937E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2217.54 | 02-JAN-10:09 | 2625.88 | 01-JAN-00:10 | 14428.03 | 01-JAN-11:09 | 0.00 | 6149.40 | 01-JAN-00:10 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 2217.54 | 01-FEB-10:09 | 2625.88 | 01-FEB-00:10 | 14428.03 | 01-FEB-11:09 | 0.00 | 6149.40 | 01-FEB-05:40 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 2217.54 | 01-MAR-10:09 | 2625.88 | 01-MAR-00:10 | 14428.03 | 01-MAR-11:09 | 0.00 | 6149.40 | 01-MAR-08:30 | 0.00 | 05-MAR-08:50 | 0.00 | 01-MAR-00:10 |
April | 2217.54 | 01-APR-16:10 | 2625.88 | 01-APR-00:10 | 14428.03 | 01-APR-10:09 | 0.00 | 6149.40 | 01-APR-04:10 | 0.00 | 22-APR-14:09 | 0.00 | 01-APR-00:10 |
May | 2217.54 | 01-MAY-09:09 | 2625.88 | 01-MAY-00:10 | 14428.03 | 01-MAY-10:09 | 0.00 | 6149.40 | 01-MAY-04:10 | 0.00 | 03-MAY-07:40 | 0.00 | 01-MAY-00:10 |
June | 2217.54 | 01-JUN-09:09 | 2625.88 | 01-JUN-00:10 | 14428.03 | 01-JUN-10:09 | 0.00 | 6149.40 | 01-JUN-04:19 | 0.00 | 24-JUN-14:30 | 0.00 | 01-JUN-00:10 |
July | 2217.54 | 01-JUL-16:10 | 2625.88 | 01-JUL-00:10 | 14428.03 | 01-JUL-10:09 | 0.00 | 6149.40 | 01-JUL-04:10 | 0.00 | 22-JUL-10:39 | 0.00 | 01-JUL-00:10 |
August | 2217.54 | 01-AUG-09:09 | 2625.88 | 01-AUG-00:10 | 14428.03 | 01-AUG-10:09 | 0.00 | 6149.40 | 01-AUG-04:19 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 2217.54 | 01-SEP-09:09 | 2625.88 | 01-SEP-00:10 | 14428.03 | 01-SEP-10:09 | 0.00 | 6149.40 | 01-SEP-04:10 | 0.00 | 08-SEP-13:50 | 0.00 | 01-SEP-00:10 |
October | 2217.54 | 02-OCT-09:09 | 2625.88 | 01-OCT-00:10 | 14428.03 | 01-OCT-10:09 | 0.00 | 6149.40 | 01-OCT-04:10 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 2217.54 | 01-NOV-09:09 | 2625.88 | 01-NOV-00:10 | 14428.03 | 01-NOV-10:09 | 0.00 | 6149.40 | 01-NOV-04:10 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 2217.54 | 01-DEC-10:09 | 2625.88 | 01-DEC-00:10 | 14428.03 | 01-DEC-11:09 | 0.00 | 6149.40 | 01-DEC-05:19 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2217.54 | 2625.88 | 14428.03 | 0.00 | 6149.40 | 0.00 | 0.00 | ||||||
Maximum of Months | 2217.54 | 2625.88 | 14428.03 | 0.00 | 6149.40 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 8023.30 | 12-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11979.50 | 22-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19243.53 | 28-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25351.13 | 26-APR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30041.07 | 18-MAY-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32649.30 | 10-JUN-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31011.75 | 01-JUL-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28783.63 | 25-AUG-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 28552.22 | 17-SEP-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23532.87 | 04-OCT-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15427.22 | 09-NOV-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9672.78 | 28-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8023.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32649.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 32209.36 | 26-JAN-11:00 | 2217.54 | 14428.03 | 0.00 | 0.00 | 6149.40 | 0.00 | 0.00 | 6516.19 | 0.00 |
February | 35944.65 | 22-FEB-11:00 | 2217.54 | 14428.03 | 0.00 | 0.00 | 6149.40 | 0.00 | 0.00 | 10248.65 | 0.00 |
March | 42110.64 | 10-MAR-18:30 | 2217.54 | 12176.23 | 2625.88 | 0.00 | 6149.40 | 0.00 | 0.00 | 16868.26 | 0.00 |
April | 49177.20 | 27-APR-11:09 | 2217.54 | 13527.31 | 0.00 | 0.00 | 6149.40 | 0.00 | 0.00 | 24348.14 | 0.00 |
May | 53328.64 | 02-MAY-11:00 | 2217.54 | 13527.31 | 0.00 | 0.00 | 6149.40 | 0.00 | 0.00 | 29291.12 | 0.00 |
June | 54670.79 | 10-JUN-18:10 | 2217.54 | 11275.51 | 0.00 | 0.00 | 6149.40 | 0.00 | 0.00 | 32649.30 | 0.00 |
July | 53983.76 | 10-JUL-11:00 | 2217.54 | 13527.31 | 0.00 | 0.00 | 6149.40 | 0.00 | 0.00 | 29904.82 | 0.00 |
August | 52939.73 | 25-AUG-11:20 | 2217.54 | 13527.31 | 0.00 | 0.00 | 6149.40 | 0.00 | 0.00 | 27974.22 | 0.00 |
September | 51488.10 | 17-SEP-19:00 | 1478.36 | 10374.79 | 2625.88 | 0.00 | 6149.40 | 0.00 | 0.00 | 28552.22 | 0.00 |
October | 47836.01 | 04-OCT-11:20 | 2217.54 | 13527.31 | 0.00 | 0.00 | 6149.40 | 0.00 | 0.00 | 22997.73 | 0.00 |
November | 40231.12 | 09-NOV-12:09 | 2217.54 | 13527.31 | 0.00 | 0.00 | 6149.40 | 0.00 | 0.00 | 15427.22 | 0.00 |
December | 33703.65 | 18-DEC-11:00 | 2217.54 | 14428.03 | 0.00 | 0.00 | 6149.40 | 0.00 | 0.00 | 8005.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 32209.36 | 1478.36 | 10374.79 | 0.00 | 0.00 | 6149.40 | 0.00 | 0.00 | 6516.19 | 0.00 | |
Maximum of Months | 54670.79 | 2217.54 | 14428.03 | 2625.88 | 0.00 | 6149.40 | 0.00 | 0.00 | 32649.30 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 20097.61 | 05-JAN-07:10 | 0.00 | 24657.34 | 18-JAN-13:39 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 12726.08 | 02-FEB-07:10 | 0.00 | 24563.23 | 02-FEB-13:39 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 24013.10 | 01-MAR-13:50 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 22556.53 | 03-APR-12:20 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 20736.45 | 03-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 18850.52 | 01-JUN-12:30 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 17339.61 | 01-JUL-12:39 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 18572.33 | 31-AUG-12:50 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 20394.50 | 27-SEP-12:39 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 22510.84 | 31-OCT-12:20 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 3474.67 | 27-NOV-07:10 | 0.00 | 23798.54 | 29-NOV-13:39 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 19395.64 | 31-DEC-07:10 | 0.00 | 24488.89 | 27-DEC-13:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 0.00 | 0.00 | 17339.61 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 20097.61 | 0.00 | 24657.34 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.45 | 0.00 | 24.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.69 | 0.00 | 24.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 25.00 | 0.00 | 25.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 25.39 | 0.00 | 25.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 25.57 | 0.00 | 25.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 25.69 | 0.00 | 25.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 25.63 | 0.00 | 25.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 25.44 | 0.00 | 25.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 24.98 | 0.33 | 24.98 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.58 | 0.00 | 24.58 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 116.83 | 25.32 | 0.33 | 25.32 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 25.69 | 0.33 | 25.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 28.71 | 0.00 | 28.71 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 29.60 | 0.00 | 29.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 30.41 | 0.00 | 30.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 30.70 | 0.00 | 30.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 151.67 | 28.11 | 117.00 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 328.50 | 28.40 | 282.17 | 28.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 557.17 | 28.45 | 482.33 | 28.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 525.67 | 28.70 | 457.17 | 28.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 294.83 | 28.05 | 250.83 | 27.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 30.82 | 0.00 | 30.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 30.27 | 0.00 | 30.27 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 29.10 | 0.00 | 29.10 |
Annual Sum or Average | 0.00 | 0.00 | 2027.50 | 28.56 | 1589.50 | 28.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 28.05 | 0.00 | 27.79 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 557.17 | 30.82 | 482.33 | 30.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 330.83 | 21.55 | 192.17 | 22.40 | 1.00 | 22.39 |
February | 161.67 | 21.89 | 334.67 | 23.24 | 0.67 | 23.24 |
March | 30.00 | 23.42 | 537.50 | 23.95 | 1.33 | 23.95 |
April | 20.50 | 28.13 | 577.17 | 24.24 | 20.50 | 24.37 |
May | 152.67 | 24.91 | 611.00 | 24.31 | 152.67 | 24.41 |
June | 338.50 | 24.36 | 592.00 | 24.24 | 338.50 | 24.27 |
July | 565.17 | 24.18 | 609.00 | 24.17 | 565.17 | 24.17 |
August | 610.17 | 24.14 | 612.00 | 24.14 | 610.17 | 24.14 |
September | 503.33 | 24.16 | 590.00 | 24.14 | 503.33 | 24.14 |
October | 82.17 | 24.51 | 610.00 | 24.08 | 82.17 | 24.13 |
November | 48.67 | 22.32 | 479.67 | 23.77 | 0.00 | 23.77 |
December | 289.33 | 21.69 | 250.83 | 22.70 | 1.00 | 22.70 |
Annual Sum or Average | 3133.00 | 23.60 | 5996.00 | 23.90 | 2276.50 | 23.98 |
Minimum of Months | 20.50 | 21.55 | 192.17 | 22.40 | 0.00 | 22.39 |
Maximum of Months | 610.17 | 28.13 | 612.00 | 24.31 | 610.17 | 24.41 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 390.17 | 22.80 | 385.50 | 23.82 | 199.17 | 24.21 |
February | 385.00 | 24.99 | 454.67 | 25.19 | 315.33 | 25.42 |
March | 518.67 | 26.12 | 611.17 | 25.97 | 518.67 | 26.02 |
April | 587.33 | 26.27 | 590.00 | 26.27 | 587.33 | 26.27 |
May | 611.00 | 26.58 | 611.00 | 26.58 | 611.00 | 26.58 |
June | 592.00 | 27.31 | 592.00 | 27.31 | 592.00 | 27.31 |
July | 609.00 | 28.08 | 609.00 | 28.08 | 609.00 | 28.08 |
August | 612.00 | 28.18 | 612.00 | 28.18 | 612.00 | 28.18 |
September | 590.00 | 27.02 | 590.00 | 27.02 | 590.00 | 27.02 |
October | 598.17 | 26.17 | 610.00 | 26.15 | 598.17 | 26.16 |
November | 444.33 | 25.88 | 567.33 | 25.69 | 430.17 | 25.80 |
December | 409.33 | 23.82 | 413.50 | 24.47 | 254.83 | 24.81 |
Annual Sum or Average | 6347.00 | 26.33 | 6646.17 | 26.40 | 5917.67 | 26.52 |
Minimum of Months | 385.00 | 22.80 | 385.50 | 23.82 | 199.17 | 24.21 |
Maximum of Months | 612.00 | 28.18 | 612.00 | 28.18 | 612.00 | 28.18 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.57880 | 44.37153 | 0.14504 | 7.61581 |
February | 551.00000 | 23.27933 | 46.25247 | 0.35456 | 9.15864 |
March | 612.00000 | 23.92979 | 45.72068 | 0.55744 | 11.87436 |
April | 590.00000 | 24.09718 | 44.86089 | 0.65428 | 14.49261 |
May | 611.00000 | 24.15331 | 54.29495 | -0.0035 | 6.27298 |
June | 592.00000 | 24.16345 | 61.94398 | 0.07430 | 6.54443 |
July | 609.00000 | 24.15561 | 71.02684 | 0.13415 | 6.73371 |
August | 612.00000 | 24.14078 | 73.46761 | 0.14061 | 6.69751 |
September | 590.00000 | 24.11845 | 69.83808 | 0.08358 | 6.26018 |
October | 610.00000 | 24.02217 | 53.13415 | 0.70571 | 15.79849 |
November | 591.00000 | 23.75098 | 46.44812 | 0.53768 | 11.68950 |
December | 609.00000 | 22.79928 | 43.64116 | 0.22478 | 8.01572 |
Annual Sum or Average | 7187.00000 | 23.76718 | 54.64142 | 0.29986 | 9.25800 |
Minimum of Months | 551.00000 | 22.57880 | 43.64116 | -0.0035 | 6.26018 |
Maximum of Months | 612.00000 | 24.16345 | 73.46761 | 0.70571 | 15.79849 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.09669 | 45.98604 | 0.52030 | 18.01975 |
February | 551.00000 | 24.55442 | 45.83002 | 0.87301 | 25.63981 |
March | 612.00000 | 25.84352 | 44.74133 | 1.19548 | 35.79436 |
April | 590.00000 | 26.26734 | 45.14969 | 1.33214 | 42.09280 |
May | 611.00000 | 26.57544 | 55.03129 | 1.02327 | 28.25586 |
June | 592.00000 | 27.31182 | 61.24539 | 1.34238 | 43.53394 |
July | 609.00000 | 28.08297 | 66.40482 | 1.65257 | 58.48365 |
August | 612.00000 | 28.17838 | 66.38651 | 1.68877 | 59.87547 |
September | 590.00000 | 27.01675 | 64.40550 | 1.26089 | 39.43252 |
October | 610.00000 | 26.13712 | 51.83935 | 1.37303 | 44.23145 |
November | 591.00000 | 25.37304 | 45.83126 | 1.10898 | 32.75807 |
December | 609.00000 | 23.71057 | 44.11365 | 0.67358 | 20.54419 |
Annual Sum or Average | 7187.00000 | 26.01990 | 53.13024 | 1.17197 | 37.46696 |
Minimum of Months | 551.00000 | 23.09669 | 44.11365 | 0.52030 | 18.01975 |
Maximum of Months | 612.00000 | 28.17838 | 66.40482 | 1.68877 | 59.87547 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.370174E+10 | 0.131699E+10 | 221.70 | 0.321529E+10 | 0.486445E+09 | 0.00 | 0.23 | 12-JAN-14:00 | 0.00 | 01-JAN-00:02 | 12936.54 | 12-JAN-14:00 | 11522.91 | 12-JAN-14:00 | 4089.06 | 26-JAN-03:01 | 4481.77 | 12-JAN-14:00 | 0.00 | 01-JAN-00:02 |
February | 0.947548E+10 | 0.331511E+10 | 341.48 | 0.790812E+10 | 0.156736E+10 | 0.00 | 0.34 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 | 19929.53 | 22-FEB-14:00 | 17234.59 | 22-FEB-14:00 | 5426.93 | 25-FEB-03:02 | 6716.07 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.249789E+11 | 0.860298E+10 | 583.19 | 0.202550E+11 | 0.472395E+10 | 0.00 | 0.81 | 29-MAR-02:61 | 0.00 | 01-MAR-00:10 | 56969.32 | 29-MAR-02:61 | 37111.67 | 11-MAR-03:01 | 20345.19 | 29-MAR-02:61 | 16231.22 | 29-MAR-02:61 | 0.00 | 01-MAR-00:10 |
April | 0.428013E+11 | 0.152150E+11 | 612.62 | 0.357646E+11 | 0.703670E+10 | 0.00 | 1.00 | 27-APR-02:61 | 0.00 | 01-APR-00:01 | 77083.33 | 27-APR-02:61 | 58620.49 | 28-APR-02:61 | 30099.06 | 27-APR-02:61 | 20324.12 | 27-APR-02:61 | 0.00 | 01-APR-00:01 |
May | 0.634087E+11 | 0.227206E+11 | 644.64 | 0.464726E+11 | 0.169362E+11 | 0.00 | 1.00 | 02-MAY-02:61 | 0.00 | 01-MAY-00:01 | 78007.19 | 23-MAY-02:61 | 68000.13 | 04-MAY-02:61 | 49682.66 | 23-MAY-02:61 | 21886.57 | 04-MAY-02:61 | 0.00 | 01-MAY-00:01 |
June | 0.734369E+11 | 0.254320E+11 | 628.89 | 0.466480E+11 | 0.267889E+11 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 | 78007.19 | 27-JUN-02:61 | 60079.69 | 05-JUN-02:61 | 50120.84 | 28-JUN-02:61 | 22000.34 | 14-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.834995E+11 | 0.267066E+11 | 646.66 | 0.432704E+11 | 0.402291E+11 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 | 78007.19 | 13-JUL-02:61 | 46137.20 | 01-JUL-02:61 | 51067.09 | 19-JUL-02:61 | 21570.58 | 03-JUL-02:61 | 0.00 | 01-JUL-00:01 |
August | 0.821554E+11 | 0.254690E+11 | 642.82 | 0.396955E+11 | 0.424599E+11 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 | 78007.19 | 15-AUG-02:02 | 44838.20 | 03-AUG-02:61 | 54565.73 | 30-AUG-02:07 | 20955.32 | 09-AUG-02:61 | 0.00 | 01-AUG-00:01 |
September | 0.668891E+11 | 0.210802E+11 | 614.12 | 0.350979E+11 | 0.317911E+11 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 | 78007.19 | 08-SEP-02:61 | 45872.87 | 29-SEP-02:61 | 48847.18 | 13-SEP-02:61 | 20402.71 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 |
October | 0.393519E+11 | 0.132797E+11 | 627.45 | 0.285630E+11 | 0.107889E+11 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:01 | 78007.19 | 04-OCT-02:61 | 45546.69 | 03-OCT-02:61 | 35602.72 | 04-OCT-02:61 | 20402.71 | 01-OCT-02:61 | 0.00 | 01-OCT-00:01 |
November | 0.184359E+11 | 0.633669E+10 | 494.89 | 0.150541E+11 | 0.338180E+10 | 0.00 | 0.47 | 09-NOV-03:01 | 0.00 | 01-NOV-00:01 | 29574.07 | 09-NOV-03:01 | 22302.26 | 09-NOV-13:00 | 11855.07 | 09-NOV-03:01 | 9393.22 | 09-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 0.582775E+10 | 0.206034E+10 | 269.77 | 0.494385E+10 | 0.883900E+09 | 0.00 | 0.27 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 15709.55 | 28-DEC-14:00 | 13481.62 | 28-DEC-14:00 | 2564.39 | 18-DEC-13:00 | 5382.60 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.513963E+12 | 0.171535E+12 | 6328.22 | 0.326888E+12 | 0.187074E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.370174E+10 | 0.131699E+10 | 221.70 | 0.321529E+10 | 0.486445E+09 | 0.00 | 0.23 | 0.00 | 12936.54 | 11522.91 | 2564.39 | 4481.77 | 0.00 | |||||||
Maximum of Months | 0.834995E+11 | 0.267066E+11 | 646.66 | 0.466480E+11 | 0.424599E+11 | 0.00 | 1.00 | 0.00 | 78007.19 | 68000.13 | 54565.73 | 22000.34 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.275122E+10 | 0.878982E+09 | 196.80 | 0.210335E+10 | 0.647862E+09 | 0.00 | 1.00 | 06-JAN-05:01 | 0.00 | 01-JAN-00:02 | 34151.43 | 06-JAN-05:01 | 24017.70 | 24-JAN-05:01 | 18508.51 | 16-JAN-03:11 | 8888.95 | 06-JAN-05:01 | 0.00 | 01-JAN-00:02 |
February | 0.882288E+10 | 0.273525E+10 | 331.31 | 0.697774E+10 | 0.184514E+10 | 0.00 | 1.00 | 03-FEB-05:01 | 0.00 | 01-FEB-00:10 | 34151.43 | 03-FEB-05:01 | 23188.24 | 03-FEB-05:01 | 17062.82 | 16-FEB-03:01 | 8888.95 | 03-FEB-05:01 | 0.00 | 01-FEB-00:10 |
March | 0.249618E+11 | 0.737426E+10 | 561.38 | 0.204064E+11 | 0.455537E+10 | 0.00 | 1.00 | 01-MAR-03:01 | 0.00 | 01-MAR-00:10 | 35550.25 | 29-MAR-02:61 | 28142.28 | 28-MAR-14:10 | 18572.15 | 31-MAR-02:11 | 8990.45 | 29-MAR-02:61 | 0.00 | 01-MAR-00:10 |
April | 0.456031E+11 | 0.133761E+11 | 663.24 | 0.402308E+11 | 0.537235E+10 | 0.00 | 1.00 | 01-APR-02:61 | 0.00 | 01-APR-00:01 | 37627.79 | 20-APR-02:61 | 34757.70 | 15-APR-14:10 | 19066.76 | 23-APR-02:11 | 11020.53 | 15-APR-14:10 | 0.00 | 01-APR-00:01 |
May | 0.688896E+11 | 0.196546E+11 | 707.04 | 0.541998E+11 | 0.146898E+11 | 0.00 | 1.00 | 01-MAY-02:61 | 0.00 | 01-MAY-00:01 | 37944.48 | 24-MAY-02:61 | 35632.66 | 04-MAY-02:61 | 24452.06 | 23-MAY-00:04 | 12118.94 | 03-MAY-14:55 | 0.00 | 01-MAY-00:01 |
June | 0.779601E+11 | 0.215401E+11 | 686.02 | 0.525668E+11 | 0.253933E+11 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 | 37944.48 | 24-JUN-11:20 | 35588.34 | 12-JUN-19:43 | 26602.42 | 28-JUN-00:04 | 11968.44 | 07-JUN-15:53 | 0.00 | 01-JUN-00:01 |
July | 0.884725E+11 | 0.229296E+11 | 710.75 | 0.448948E+11 | 0.435777E+11 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 | 37944.48 | 11-JUL-03:33 | 33955.00 | 04-JUL-17:53 | 27935.07 | 19-JUL-00:04 | 10915.42 | 02-JUL-15:53 | 0.00 | 01-JUL-00:01 |
August | 0.882401E+11 | 0.222877E+11 | 709.35 | 0.390238E+11 | 0.492163E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:01 | 37944.48 | 10-AUG-21:50 | 26337.10 | 07-AUG-14:00 | 27608.90 | 12-AUG-08:00 | 10331.77 | 07-AUG-14:55 | 0.00 | 01-AUG-00:01 |
September | 0.783540E+11 | 0.198351E+11 | 679.49 | 0.376601E+11 | 0.406938E+11 | 0.00 | 1.00 | 01-SEP-00:04 | 0.00 | 01-SEP-00:01 | 37944.48 | 01-SEP-07:30 | 31051.32 | 29-SEP-13:00 | 27075.39 | 10-SEP-02:13 | 10367.28 | 17-SEP-20:00 | 0.00 | 01-SEP-00:01 |
October | 0.419034E+11 | 0.117411E+11 | 648.05 | 0.302601E+11 | 0.116433E+11 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:01 | 37944.48 | 06-OCT-10:32 | 31061.57 | 02-OCT-13:00 | 23553.68 | 12-OCT-03:21 | 9713.90 | 04-OCT-12:13 | 0.00 | 01-OCT-00:01 |
November | 0.176491E+11 | 0.527102E+10 | 454.68 | 0.142222E+11 | 0.342685E+10 | 0.00 | 1.00 | 01-NOV-02:11 | 0.00 | 01-NOV-00:01 | 34151.43 | 13-NOV-03:11 | 24868.00 | 21-NOV-05:01 | 18024.44 | 09-NOV-04:31 | 8888.95 | 01-NOV-02:11 | 0.00 | 01-NOV-00:01 |
December | 0.496677E+10 | 0.156813E+10 | 255.56 | 0.384767E+10 | 0.111910E+10 | 0.00 | 1.00 | 01-DEC-03:01 | 0.00 | 01-DEC-00:10 | 34151.43 | 01-DEC-03:01 | 23976.90 | 30-DEC-03:11 | 16968.27 | 28-DEC-03:11 | 8888.95 | 01-DEC-03:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.548575E+12 | 0.149192E+12 | 6603.66 | 0.346394E+12 | 0.202181E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.275122E+10 | 0.878982E+09 | 196.80 | 0.210335E+10 | 0.647862E+09 | 0.00 | 1.00 | 0.00 | 34151.43 | 23188.24 | 16968.27 | 8888.95 | 0.00 | |||||||
Maximum of Months | 0.884725E+11 | 0.229296E+11 | 710.75 | 0.541998E+11 | 0.492163E+11 | 0.00 | 1.00 | 0.00 | 37944.48 | 35632.66 | 27935.07 | 12118.94 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.05 | 21.42 | 31.63 | 68.87 | 206.73 | 0.00 | 0.00 | 0.00 |
February | 64.29 | 26.59 | 37.69 | 122.69 | 163.51 | 3.67 | 0.00 | 0.00 |
March | 78.22 | 32.23 | 45.99 | 211.07 | 96.02 | 0.00 | 0.00 | 0.00 |
April | 92.97 | 43.24 | 49.73 | 351.93 | 34.45 | 0.00 | 0.00 | 0.00 |
May | 91.71 | 40.66 | 51.05 | 417.04 | 7.21 | 0.00 | 0.00 | 0.00 |
June | 74.98 | 25.11 | 49.87 | 380.58 | 7.15 | 0.83 | 0.00 | 0.00 |
July | 62.77 | 13.28 | 49.48 | 307.45 | 2.18 | 0.67 | 0.00 | 0.00 |
August | 56.49 | 9.81 | 46.69 | 253.62 | 6.05 | 0.00 | 0.00 | 0.00 |
September | 60.34 | 16.79 | 43.55 | 224.47 | 19.67 | 0.00 | 0.00 | 0.00 |
October | 66.33 | 26.96 | 39.37 | 214.62 | 76.37 | 0.00 | 0.00 | 0.00 |
November | 59.10 | 25.67 | 33.43 | 136.53 | 146.74 | 0.00 | 0.00 | 0.00 |
December | 51.45 | 20.61 | 30.84 | 77.48 | 204.50 | 3.17 | 0.00 | 0.00 |
Annual Sum or Average | 67.62 | 25.16 | 42.46 | 230.94 | 80.52 | 8.33 | 0.00 | 0.00 |
Minimum of Months | 51.45 | 9.81 | 30.84 | 68.87 | 2.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.97 | 43.24 | 51.05 | 417.04 | 206.73 | 3.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 221.17 | 133.12 | 88.04 | 476.73 | 405.31 | 0.00 | 0.00 | 0.00 |
February | 213.32 | 118.47 | 94.85 | 515.56 | 331.31 | 3.67 | 0.00 | 0.00 |
March | 188.67 | 86.82 | 101.85 | 554.64 | 200.44 | 0.00 | 0.00 | 0.00 |
April | 137.78 | 45.81 | 91.97 | 582.74 | 71.78 | 0.00 | 0.00 | 0.00 |
May | 96.12 | 10.79 | 85.32 | 562.06 | 14.48 | 0.00 | 0.00 | 0.00 |
June | 85.50 | 2.65 | 82.85 | 550.74 | 14.43 | 0.83 | 0.00 | 0.00 |
July | 88.73 | 2.02 | 86.71 | 497.16 | 4.46 | 0.67 | 0.00 | 0.00 |
August | 94.97 | 6.69 | 88.29 | 455.51 | 12.19 | 0.00 | 0.00 | 0.00 |
September | 128.94 | 36.36 | 92.58 | 490.01 | 40.10 | 0.00 | 0.00 | 0.00 |
October | 217.36 | 122.37 | 94.99 | 718.58 | 156.68 | 0.00 | 0.00 | 0.00 |
November | 264.87 | 173.78 | 91.09 | 734.85 | 298.13 | 0.00 | 0.00 | 0.00 |
December | 235.42 | 145.89 | 89.53 | 539.50 | 397.78 | 3.17 | 0.00 | 0.00 |
Annual Sum or Average | 164.11 | 73.46 | 90.65 | 556.48 | 161.48 | 8.33 | 0.00 | 0.00 |
Minimum of Months | 85.50 | 2.02 | 82.85 | 455.51 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 264.87 | 173.78 | 101.85 | 734.85 | 405.31 | 3.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.96 | 20.38 | 31.58 | 79.66 | 222.38 | 0.00 | 0.00 | 0.00 |
February | 59.29 | 21.96 | 37.33 | 118.98 | 175.69 | 3.67 | 0.00 | 0.00 |
March | 76.57 | 30.55 | 46.02 | 210.21 | 102.97 | 0.00 | 0.00 | 0.00 |
April | 92.98 | 43.50 | 49.48 | 353.10 | 35.18 | 0.00 | 0.00 | 0.00 |
May | 88.31 | 37.51 | 50.81 | 408.96 | 7.22 | 0.00 | 0.00 | 0.00 |
June | 83.11 | 32.42 | 50.68 | 407.96 | 6.87 | 0.83 | 0.00 | 0.00 |
July | 61.56 | 12.02 | 49.54 | 303.54 | 2.36 | 0.67 | 0.00 | 0.00 |
August | 56.45 | 10.01 | 46.44 | 254.09 | 6.09 | 0.00 | 0.00 | 0.00 |
September | 62.00 | 18.15 | 43.86 | 231.56 | 19.89 | 0.00 | 0.00 | 0.00 |
October | 64.94 | 26.05 | 38.89 | 214.64 | 79.98 | 0.00 | 0.00 | 0.00 |
November | 58.99 | 25.44 | 33.54 | 147.42 | 157.34 | 0.00 | 0.00 | 0.00 |
December | 50.37 | 19.43 | 30.95 | 81.96 | 215.32 | 3.17 | 0.00 | 0.00 |
Annual Sum or Average | 67.20 | 24.75 | 42.45 | 234.73 | 85.54 | 8.33 | 0.00 | 0.00 |
Minimum of Months | 50.37 | 10.01 | 30.95 | 79.66 | 2.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.98 | 43.50 | 50.81 | 408.96 | 222.38 | 3.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.142088E+09 | 57365205.62 | 84723099.37 | 0.184459E+09 | 0.553695E+09 |
February | 0.155523E+09 | 64335652.08 | 91187187.37 | 0.296813E+09 | 0.395564E+09 |
March | 0.209510E+09 | 86335693.85 | 0.123174E+09 | 0.565332E+09 | 0.257178E+09 |
April | 0.240986E+09 | 0.112085E+09 | 0.128901E+09 | 0.912192E+09 | 89289714.65 |
May | 0.245641E+09 | 0.108911E+09 | 0.136730E+09 | 0.111699E+10 | 19309230.15 |
June | 0.194357E+09 | 65087175.31 | 0.129270E+09 | 0.986458E+09 | 18538423.27 |
July | 0.168116E+09 | 35579277.01 | 0.132537E+09 | 0.823463E+09 | 5849025.78 |
August | 0.151310E+09 | 26264160.51 | 0.125045E+09 | 0.679285E+09 | 16193399.21 |
September | 0.156398E+09 | 43522739.17 | 0.112875E+09 | 0.581817E+09 | 50979877.75 |
October | 0.177672E+09 | 72210168.59 | 0.105461E+09 | 0.574845E+09 | 0.204561E+09 |
November | 0.153192E+09 | 66544097.41 | 86647913.34 | 0.353894E+09 | 0.380343E+09 |
December | 0.137796E+09 | 55205276.05 | 82591149.32 | 0.207524E+09 | 0.547746E+09 |
Annual Sum or Average | 0.213259E+10 | 0.793445E+09 | 0.133914E+10 | 0.728307E+10 | 0.253925E+10 |
Minimum of Months | 0.137796E+09 | 26264160.51 | 82591149.32 | 0.184459E+09 | 5849025.78 |
Maximum of Months | 0.245641E+09 | 0.112085E+09 | 0.136730E+09 | 0.111699E+10 | 0.553695E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.592371E+09 | 0.356562E+09 | 0.235809E+09 | 0.127686E+10 | 0.108558E+10 |
February | 0.516075E+09 | 0.286612E+09 | 0.229463E+09 | 0.124724E+10 | 0.801517E+09 |
March | 0.505325E+09 | 0.232535E+09 | 0.272789E+09 | 0.148555E+10 | 0.536855E+09 |
April | 0.357138E+09 | 0.118750E+09 | 0.238388E+09 | 0.151047E+10 | 0.186058E+09 |
May | 0.257445E+09 | 28912524.95 | 0.228532E+09 | 0.150542E+10 | 38795194.47 |
June | 0.221612E+09 | 6862714.70 | 0.214750E+09 | 0.142751E+10 | 37404648.72 |
July | 0.237658E+09 | 5407292.08 | 0.232251E+09 | 0.133160E+10 | 11942770.66 |
August | 0.254371E+09 | 17907819.11 | 0.236463E+09 | 0.122003E+10 | 32643387.64 |
September | 0.334216E+09 | 94250996.54 | 0.239965E+09 | 0.127012E+10 | 0.103935E+09 |
October | 0.582171E+09 | 0.327749E+09 | 0.254422E+09 | 0.192466E+10 | 0.419659E+09 |
November | 0.686533E+09 | 0.450437E+09 | 0.236096E+09 | 0.190474E+10 | 0.772762E+09 |
December | 0.630539E+09 | 0.390744E+09 | 0.239795E+09 | 0.144500E+10 | 0.106541E+10 |
Annual Sum or Average | 0.517545E+10 | 0.231673E+10 | 0.285872E+10 | 0.175492E+11 | 0.509256E+10 |
Minimum of Months | 0.221612E+09 | 5407292.08 | 0.214750E+09 | 0.122003E+10 | 11942770.66 |
Maximum of Months | 0.686533E+09 | 0.450437E+09 | 0.272789E+09 | 0.192466E+10 | 0.108558E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139176E+09 | 54594941.36 | 84580577.09 | 0.213354E+09 | 0.595611E+09 |
February | 0.143442E+09 | 53130803.73 | 90311245.02 | 0.287834E+09 | 0.425026E+09 |
March | 0.205078E+09 | 81827304.42 | 0.123250E+09 | 0.563026E+09 | 0.275798E+09 |
April | 0.240997E+09 | 0.112740E+09 | 0.128257E+09 | 0.915234E+09 | 91188155.66 |
May | 0.236535E+09 | 0.100456E+09 | 0.136079E+09 | 0.109537E+10 | 19340251.44 |
June | 0.215412E+09 | 84040273.10 | 0.131371E+09 | 0.105744E+10 | 17819602.24 |
July | 0.164873E+09 | 32196698.83 | 0.132676E+09 | 0.812994E+09 | 6309816.49 |
August | 0.151201E+09 | 26815526.22 | 0.124386E+09 | 0.680552E+09 | 16323345.59 |
September | 0.160716E+09 | 47035866.51 | 0.113680E+09 | 0.600208E+09 | 51546626.00 |
October | 0.173926E+09 | 69767068.27 | 0.104159E+09 | 0.574887E+09 | 0.214210E+09 |
November | 0.152891E+09 | 65943976.33 | 86947467.41 | 0.382104E+09 | 0.407813E+09 |
December | 0.134924E+09 | 52029993.37 | 82893593.10 | 0.219515E+09 | 0.576707E+09 |
Annual Sum or Average | 0.211917E+10 | 0.780578E+09 | 0.133859E+10 | 0.740252E+10 | 0.269769E+10 |
Minimum of Months | 0.134924E+09 | 26815526.22 | 82893593.10 | 0.213354E+09 | 6309816.49 |
Maximum of Months | 0.240997E+09 | 0.112740E+09 | 0.136079E+09 | 0.109537E+10 | 0.595611E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 600.69 | 809.85 | 326.18 | 174.93 | 151.25 | 0.00 | 0.00 |
February | 742.66 | 655.94 | 336.90 | 167.03 | 169.87 | 0.00 | 0.00 |
March | 966.07 | 389.58 | 343.46 | 149.60 | 193.85 | 0.00 | 0.00 |
April | 1285.05 | 138.69 | 323.73 | 132.55 | 191.18 | 0.00 | 0.00 |
May | 1387.59 | 28.44 | 276.14 | 88.96 | 187.18 | 0.00 | 0.00 |
June | 1339.15 | 28.33 | 243.59 | 60.18 | 183.41 | 0.00 | 0.00 |
July | 1108.14 | 8.99 | 213.06 | 27.32 | 185.73 | 0.00 | 0.00 |
August | 963.18 | 24.30 | 207.92 | 26.50 | 181.41 | 0.00 | 0.00 |
September | 945.58 | 79.19 | 251.28 | 71.30 | 179.98 | 0.00 | 0.00 |
October | 1145.10 | 310.29 | 348.63 | 175.38 | 173.25 | 0.00 | 0.00 |
November | 1010.53 | 593.93 | 382.95 | 224.89 | 158.06 | 0.00 | 0.00 |
December | 677.74 | 796.40 | 337.24 | 185.92 | 151.31 | 0.00 | 0.00 |
Annual Sum or Average | 1015.09 | 320.48 | 298.93 | 123.37 | 175.56 | 0.00 | 0.00 |
Minimum of Months | 600.69 | 8.99 | 207.92 | 26.50 | 151.25 | 0.00 | 0.00 |
Maximum of Months | 1387.59 | 809.85 | 382.95 | 224.89 | 193.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160890E+10 | 0.216910E+10 | 0.873635E+09 | 0.468522E+09 | 0.405113E+09 | 0.00 | 0.00 |
February | 0.179663E+10 | 0.158685E+10 | 0.815040E+09 | 0.404078E+09 | 0.410962E+09 | 0.00 | 0.00 |
March | 0.258753E+10 | 0.104345E+10 | 0.919913E+09 | 0.400698E+09 | 0.519214E+09 | 0.00 | 0.00 |
April | 0.333085E+10 | 0.359492E+09 | 0.839121E+09 | 0.343574E+09 | 0.495547E+09 | 0.00 | 0.00 |
May | 0.371651E+10 | 76177674.33 | 0.739621E+09 | 0.238280E+09 | 0.501341E+09 | 0.00 | 0.00 |
June | 0.347108E+10 | 73436551.49 | 0.631381E+09 | 0.155990E+09 | 0.475391E+09 | 0.00 | 0.00 |
July | 0.296804E+10 | 24080563.12 | 0.570647E+09 | 73183267.92 | 0.497463E+09 | 0.00 | 0.00 |
August | 0.257978E+10 | 65077171.61 | 0.556882E+09 | 70987505.83 | 0.485894E+09 | 0.00 | 0.00 |
September | 0.245094E+10 | 0.205258E+09 | 0.651330E+09 | 0.184810E+09 | 0.466520E+09 | 0.00 | 0.00 |
October | 0.306703E+10 | 0.831076E+09 | 0.933769E+09 | 0.469726E+09 | 0.464043E+09 | 0.00 | 0.00 |
November | 0.261928E+10 | 0.153946E+10 | 0.992616E+09 | 0.582925E+09 | 0.409691E+09 | 0.00 | 0.00 |
December | 0.181526E+10 | 0.213308E+10 | 0.903259E+09 | 0.497979E+09 | 0.405280E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.320118E+11 | 0.101065E+11 | 0.942721E+10 | 0.389075E+10 | 0.553646E+10 | 0.00 | 0.00 |
Minimum of Months | 0.160890E+10 | 24080563.12 | 0.556882E+09 | 70987505.83 | 0.405113E+09 | 0.00 | 0.00 |
Maximum of Months | 0.371651E+10 | 0.216910E+10 | 0.992616E+09 | 0.582925E+09 | 0.519214E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.111995E+11 | -0.104864E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -713137894.3 | 58.99 | 0.00 | 0.00 |
February | 0.988659E+10 | -0.926684E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -619751872.6 | 58.99 | 0.00 | 0.00 |
March | 0.102606E+11 | -0.959819E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -662377447.4 | 58.98 | 0.00 | 0.00 |
April | 0.894486E+10 | -0.831168E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -633177763.9 | 58.98 | 0.00 | 0.00 |
May | 0.823425E+10 | -0.758554E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -648713357.0 | 58.98 | 0.00 | 0.00 |
June | 0.721240E+10 | -0.659737E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -615032721.9 | 58.98 | 0.00 | 0.00 |
July | 0.710278E+10 | -0.648144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -621348761.6 | 58.98 | 0.00 | 0.00 |
August | 0.735011E+10 | -0.673031E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -619801278.8 | 58.98 | 0.00 | 0.00 |
September | 0.779892E+10 | -0.717891E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -620012165.8 | 58.99 | 0.00 | 0.00 |
October | 0.907042E+10 | -0.841391E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -656510010.3 | 58.98 | 0.00 | 0.00 |
November | 0.977719E+10 | -0.912797E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -649215169.9 | 58.98 | 0.00 | 0.00 |
December | 0.108741E+11 | -0.101725E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -701593111.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.107712E+12 | -0.999511E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.776067E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.710278E+10 | -0.104864E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -713137894.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.111995E+11 | -0.648144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -615032721.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 319.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 364.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 372.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 317.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 315.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.222165E+10 | 10195.19 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.421025E+09 | 7523.74 | 02-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17885708.01 | 2753.67 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.982928E+09 | 10230.48 | 31-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.222165E+10 | 10230.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.717843E+09 | 6181.22 | 05-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 49492667.70 | 2716.59 | 02-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216440E+09 | 6253.37 | 23-DEC-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.983776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.717843E+09 | 6253.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.370174E+10 | 0.321529E+10 | 12936.54 | 12-JAN-14:00 | 11522.91 | 0.00 |
February | 0.00 | 0.00 | 0.947548E+10 | 0.790812E+10 | 19929.53 | 22-FEB-14:00 | 17234.59 | 0.00 |
March | 0.00 | 0.00 | 0.249789E+11 | 0.202550E+11 | 56969.32 | 29-MAR-02:61 | 36624.12 | 0.00 |
April | 0.00 | 0.00 | 0.428013E+11 | 0.357646E+11 | 77083.33 | 27-APR-02:61 | 46984.27 | 0.00 |
May | 0.00 | 0.00 | 0.634087E+11 | 0.464726E+11 | 78007.19 | 23-MAY-02:61 | 28324.53 | 0.00 |
June | 0.00 | 0.00 | 0.734369E+11 | 0.466480E+11 | 78007.19 | 27-JUN-02:61 | 32009.16 | 0.00 |
July | 0.00 | 0.00 | 0.834995E+11 | 0.432704E+11 | 78007.19 | 13-JUL-02:61 | 29931.97 | 0.00 |
August | 0.00 | 0.00 | 0.821554E+11 | 0.396955E+11 | 78007.19 | 15-AUG-02:02 | 27318.01 | 0.00 |
September | 0.00 | 0.00 | 0.668891E+11 | 0.350979E+11 | 78007.19 | 08-SEP-02:61 | 33207.06 | 0.00 |
October | 0.00 | 0.00 | 0.393519E+11 | 0.285630E+11 | 78007.19 | 04-OCT-02:61 | 42404.48 | 0.00 |
November | 0.00 | 0.00 | 0.184359E+11 | 0.150541E+11 | 29574.07 | 09-NOV-03:01 | 17719.00 | 0.00 |
December | 0.00 | 0.00 | 0.582775E+10 | 0.494385E+10 | 15709.55 | 28-DEC-14:00 | 13481.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.513963E+12 | 0.326888E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.370174E+10 | 0.321529E+10 | 12936.54 | 11522.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.834995E+11 | 0.466480E+11 | 78007.19 | 46984.27 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.275122E+10 | 0.210335E+10 | 34151.43 | 06-JAN-05:01 | 23239.25 | 0.00 |
February | 0.00 | 0.00 | 0.882288E+10 | 0.697774E+10 | 34151.43 | 03-FEB-05:01 | 23188.24 | 0.00 |
March | 0.00 | 0.00 | 0.249618E+11 | 0.204064E+11 | 35550.25 | 29-MAR-02:61 | 18445.75 | 0.00 |
April | 0.00 | 0.00 | 0.456031E+11 | 0.402308E+11 | 37627.79 | 20-APR-02:61 | 23825.90 | 0.00 |
May | 0.00 | 0.00 | 0.688896E+11 | 0.541998E+11 | 37944.48 | 24-MAY-02:61 | 16013.40 | 0.00 |
June | 0.00 | 0.00 | 0.779601E+11 | 0.525668E+11 | 37944.48 | 24-JUN-11:20 | 13664.03 | 0.00 |
July | 0.00 | 0.00 | 0.884725E+11 | 0.448948E+11 | 37944.48 | 11-JUL-03:33 | 15900.86 | 0.00 |
August | 0.00 | 0.00 | 0.882401E+11 | 0.390238E+11 | 37944.48 | 10-AUG-21:50 | 14115.60 | 0.00 |
September | 0.00 | 0.00 | 0.783540E+11 | 0.376601E+11 | 37944.48 | 01-SEP-07:30 | 14487.22 | 0.00 |
October | 0.00 | 0.00 | 0.419034E+11 | 0.302601E+11 | 37944.48 | 06-OCT-10:32 | 20199.17 | 0.00 |
November | 0.00 | 0.00 | 0.176491E+11 | 0.142222E+11 | 34151.43 | 13-NOV-03:11 | 18284.71 | 0.00 |
December | 0.00 | 0.00 | 0.496677E+10 | 0.384767E+10 | 34151.43 | 01-DEC-03:01 | 21187.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.548575E+12 | 0.346394E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.275122E+10 | 0.210335E+10 | 34151.43 | 13664.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.884725E+11 | 0.541998E+11 | 37944.48 | 23825.90 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4206.99 | 15410.70 | 18-JAN-14:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 4122.46 | 15318.00 | 01-FEB-13:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3878.06 | 14662.50 | 01-MAR-13:20 |
April | 0.00 | 0.00 | 01-APR-00:01 | 3499.90 | 13379.22 | 01-APR-12:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 3127.37 | 11908.78 | 01-MAY-13:00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 2842.56 | 10558.86 | 01-JUN-12:30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 2714.40 | 9769.23 | 01-JUL-12:30 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 2811.07 | 10394.60 | 31-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 3065.12 | 11636.20 | 30-SEP-12:25 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3434.72 | 13155.23 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3814.70 | 14462.22 | 30-NOV-13:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4088.85 | 15281.79 | 31-DEC-13:20 |
Annual Sum or Average | 0.00 | 3463.57 | ||||
Minimum of Months | 0.00 | 0.00 | 2714.40 | 9769.23 | ||
Maximum of Months | 0.00 | 0.00 | 4206.99 | 15410.70 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:02 | -0.0 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.294151E+10 | 0.59 | 1211.87 | 01-JAN-00:02 | 0.65 |
February | 0.272104E+10 | 0.60 | 1211.87 | 01-FEB-00:10 | 0.65 |
March | 0.309443E+10 | 0.62 | 1211.87 | 01-MAR-00:10 | 0.65 |
April | 0.300227E+10 | 0.62 | 1211.87 | 01-APR-00:07 | 0.65 |
May | 0.310417E+10 | 0.62 | 1211.87 | 01-MAY-00:04 | 0.65 |
June | 0.300473E+10 | 0.61 | 1211.87 | 01-JUN-00:04 | 0.64 |
July | 0.310536E+10 | 0.61 | 1211.87 | 01-JUL-00:04 | 0.64 |
August | 0.310532E+10 | 0.61 | 1211.87 | 01-AUG-00:03 | 0.64 |
September | 0.300467E+10 | 0.61 | 1211.87 | 01-SEP-00:04 | 0.64 |
October | 0.310022E+10 | 0.62 | 1211.87 | 01-OCT-00:04 | 0.64 |
November | 0.298072E+10 | 0.62 | 1211.87 | 01-NOV-00:13 | 0.65 |
December | 0.295728E+10 | 0.59 | 1211.87 | 01-DEC-00:10 | 0.65 |
Annual Sum or Average | 0.361217E+11 | 0.61 | |||
Minimum of Months | 0.272104E+10 | 0.59 | 1211.87 | 0.64 | |
Maximum of Months | 0.310536E+10 | 0.62 | 1211.87 | 0.65 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.747364E+10 | 0.77 | 3348.18 | 01-JAN-19:13 | 0.91 |
February | 0.675237E+10 | 0.78 | 3348.18 | 01-FEB-05:50 | 0.92 |
March | 0.748833E+10 | 0.82 | 3348.18 | 02-MAR-11:20 | 0.91 |
April | 0.726951E+10 | 0.82 | 3348.18 | 01-APR-10:17 | 0.91 |
May | 0.754871E+10 | 0.82 | 3348.18 | 03-MAY-07:22 | 0.91 |
June | 0.735357E+10 | 0.82 | 3348.18 | 01-JUN-07:00 | 0.91 |
July | 0.765258E+10 | 0.82 | 3348.18 | 01-JUL-23:19 | 0.90 |
August | 0.764599E+10 | 0.82 | 3348.18 | 02-AUG-09:02 | 0.91 |
September | 0.735170E+10 | 0.82 | 3348.18 | 01-SEP-23:50 | 0.90 |
October | 0.751405E+10 | 0.82 | 3348.18 | 01-OCT-17:36 | 0.91 |
November | 0.724484E+10 | 0.81 | 3348.18 | 01-NOV-10:38 | 0.92 |
December | 0.747339E+10 | 0.76 | 3348.18 | 01-DEC-18:17 | 0.91 |
Annual Sum or Average | 0.887687E+11 | 0.81 | |||
Minimum of Months | 0.675237E+10 | 0.76 | 3348.18 | 0.90 | |
Maximum of Months | 0.765258E+10 | 0.82 | 3348.18 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.358059E+10 | 0.88 | 1589.35 | 02-JAN-06:00 | 0.96 |
February | 0.325174E+10 | 0.90 | 1589.35 | 01-FEB-13:50 | 0.95 |
March | 0.363591E+10 | 0.93 | 1589.35 | 01-MAR-16:03 | 0.95 |
April | 0.356193E+10 | 0.93 | 1589.35 | 02-APR-06:40 | 0.95 |
May | 0.374474E+10 | 0.92 | 1589.35 | 02-MAY-07:50 | 0.95 |
June | 0.371876E+10 | 0.92 | 1589.35 | 01-JUN-21:40 | 0.95 |
July | 0.391614E+10 | 0.91 | 1589.35 | 07-JUL-23:11 | 0.94 |
August | 0.391657E+10 | 0.91 | 1589.35 | 01-AUG-23:50 | 0.94 |
September | 0.372879E+10 | 0.91 | 1589.35 | 01-SEP-23:15 | 0.94 |
October | 0.368732E+10 | 0.93 | 1589.35 | 02-OCT-09:12 | 0.95 |
November | 0.350632E+10 | 0.92 | 1589.35 | 02-NOV-18:33 | 0.95 |
December | 0.358592E+10 | 0.88 | 1589.35 | 01-DEC-12:30 | 0.96 |
Annual Sum or Average | 0.438347E+11 | 0.91 | |||
Minimum of Months | 0.325174E+10 | 0.88 | 1589.35 | 0.94 | |
Maximum of Months | 0.391657E+10 | 0.93 | 1589.35 | 0.96 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 52.26 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 53.20 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 53.13 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 53.73 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 54.07 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 55.19 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:10 | 0.00 | 0.00 | 55.03 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 55.74 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 55.34 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 53.65 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 54.56 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 53.18 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 52.26 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 55.74 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 42.70 | 42.70 | 4206.99 | 15410.70 | 18-JAN-14:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 53.54 | 53.54 | 4122.46 | 15318.00 | 01-FEB-13:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 53.38 | 53.38 | 3878.06 | 14662.50 | 01-MAR-13:20 |
April | 0.00 | 0.00 | 01-APR-00:01 | 53.89 | 53.89 | 3499.90 | 13379.22 | 01-APR-12:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 46.30 | 46.30 | 3127.37 | 11908.78 | 01-MAY-13:00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 55.13 | 55.13 | 2842.56 | 10558.86 | 01-JUN-12:30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 54.99 | 54.99 | 2714.40 | 9769.23 | 01-JUL-12:30 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 55.59 | 55.59 | 2811.07 | 10394.60 | 31-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 55.62 | 55.62 | 3065.12 | 11636.20 | 30-SEP-12:25 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 46.68 | 46.68 | 3434.72 | 13155.23 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 54.47 | 54.47 | 3814.70 | 14462.22 | 30-NOV-13:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 53.43 | 53.43 | 4088.85 | 15281.79 | 31-DEC-13:20 |
Annual Sum or Average | 0.00 | 3463.57 | ||||||
Minimum of Months | 0.00 | 0.00 | 42.70 | 42.70 | 2714.40 | 9769.23 | ||
Maximum of Months | 0.00 | 0.00 | 55.62 | 55.62 | 4206.99 | 15410.70 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.879062E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.100675E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.160913E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.224846E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.302693E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.327856E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.343591E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.331150E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.284319E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.207938E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.135815E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.953374E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.260304E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.879062E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.343591E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.445957E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.598699E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.110102E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.169381E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.233994E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.252589E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.268457E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.262043E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.235639E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.154284E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.877735E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.515405E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.193027E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.445957E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.268457E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.747364E+10 | 0.370174E+10 | 0.222165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.675237E+10 | 0.947548E+10 | 0.421025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.748833E+10 | 0.249789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.726951E+10 | 0.428013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.754871E+10 | 0.634087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.735357E+10 | 0.734369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.765258E+10 | 0.834995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.764599E+10 | 0.821554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.735170E+10 | 0.668891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.751405E+10 | 0.393519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724484E+10 | 0.184359E+11 | 17885708.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.747339E+10 | 0.582775E+10 | 0.982928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.887687E+11 | 0.513963E+12 | 0.364349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.675237E+10 | 0.370174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.765258E+10 | 0.834995E+11 | 0.222165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.358059E+10 | 0.275122E+10 | 0.717843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325174E+10 | 0.882288E+10 | 49492667.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.363591E+10 | 0.249618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.356193E+10 | 0.456031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.374474E+10 | 0.688896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.371876E+10 | 0.779601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.391614E+10 | 0.884725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.391657E+10 | 0.882401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.372879E+10 | 0.783540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.368732E+10 | 0.419034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.350632E+10 | 0.176491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358592E+10 | 0.496677E+10 | 0.216440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438347E+11 | 0.548575E+12 | 0.983776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.325174E+10 | 0.275122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.391657E+10 | 0.884725E+11 | 0.717843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.747364E+10 | 0.00 | 0.00 | 0.00 | 0.131699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.675237E+10 | 0.00 | 0.00 | 0.00 | 0.331511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.748833E+10 | 0.00 | 0.00 | 0.00 | 0.860298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.726951E+10 | 0.00 | 0.00 | 0.00 | 0.152150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.754871E+10 | 0.00 | 0.00 | 0.00 | 0.227206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.735357E+10 | 0.00 | 0.00 | 0.00 | 0.254320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.765258E+10 | 0.00 | 0.00 | 0.00 | 0.267066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.764599E+10 | 0.00 | 0.00 | 0.00 | 0.254690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.735170E+10 | 0.00 | 0.00 | 0.00 | 0.210802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.751405E+10 | 0.00 | 0.00 | 0.00 | 0.132797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724484E+10 | 0.00 | 0.00 | 0.00 | 0.633669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.747339E+10 | 0.00 | 0.00 | 0.00 | 0.206034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.887687E+11 | 0.00 | 0.00 | 0.00 | 0.171535E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.675237E+10 | 0.00 | 0.00 | 0.00 | 0.131699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.765258E+10 | 0.00 | 0.00 | 0.00 | 0.267066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.358059E+10 | 0.00 | 0.00 | 0.00 | 0.878982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325174E+10 | 0.00 | 0.00 | 0.00 | 0.273525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.363591E+10 | 0.00 | 0.00 | 0.00 | 0.737426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.356193E+10 | 0.00 | 0.00 | 0.00 | 0.133761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.374474E+10 | 0.00 | 0.00 | 0.00 | 0.196546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.371876E+10 | 0.00 | 0.00 | 0.00 | 0.215401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.391614E+10 | 0.00 | 0.00 | 0.00 | 0.229296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.391657E+10 | 0.00 | 0.00 | 0.00 | 0.222877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.372879E+10 | 0.00 | 0.00 | 0.00 | 0.198351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.368732E+10 | 0.00 | 0.00 | 0.00 | 0.117411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.350632E+10 | 0.00 | 0.00 | 0.00 | 0.527102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358592E+10 | 0.00 | 0.00 | 0.00 | 0.156813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438347E+11 | 0.00 | 0.00 | 0.00 | 0.149192E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.325174E+10 | 0.00 | 0.00 | 0.00 | 0.878982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.391657E+10 | 0.00 | 0.00 | 0.00 | 0.229296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.582046E+10 | 0.00 | 0.00 | 10944003.80 | 0.00 | 0.286792E+10 | 0.295280E+10 | 0.00 | 3.58 |
February | 0.370428E+10 | 68682278.36 | 0.00 | 22422944.28 | 0.00 | 0.603332E+09 | 0.282262E+10 | 0.00 | 3.60 |
March | 0.893413E+09 | 0.202892E+10 | 0.00 | 24629344.26 | 1844782.14 | 0.00 | 0.223667E+10 | 0.00 | 3.65 |
April | 63910279.68 | 0.779678E+10 | 0.00 | 4176807.74 | 70652744.03 | 0.00 | 0.210103E+09 | 0.00 | 3.71 |
May | 5237819.08 | 0.170464E+11 | 0.00 | 418427.18 | 0.268801E+09 | 0.00 | 303319.38 | 0.00 | 3.80 |
June | 0.00 | 0.227550E+11 | 0.00 | 46855.30 | 0.526807E+09 | 0.00 | 340842.34 | 0.00 | 3.88 |
July | 0.00 | 0.283471E+11 | 0.00 | 73149.29 | 0.650467E+09 | 0.00 | 329261.55 | 0.00 | 3.92 |
August | 554630.34 | 0.273573E+11 | 0.00 | 29273.42 | 0.533217E+09 | 0.00 | 0.00 | 0.00 | 3.91 |
September | 1349412.33 | 0.200633E+11 | 0.00 | 248183.90 | 0.337968E+09 | 0.00 | 58231.50 | 0.00 | 3.87 |
October | 0.203255E+09 | 0.602294E+10 | 0.00 | 7915868.49 | 21261924.71 | 0.00 | 0.695860E+09 | 0.00 | 3.70 |
November | 0.206412E+10 | 0.917725E+09 | 0.00 | 26194219.25 | 0.00 | 24400682.21 | 0.315032E+10 | 0.00 | 3.63 |
December | 0.608921E+10 | 67339.68 | 0.00 | 17133140.23 | 0.00 | 0.137656E+10 | 0.295078E+10 | 0.00 | 3.58 |
Annual Sum or Average | 0.188458E+11 | 0.132404E+12 | 0.00 | 0.114232E+09 | 0.241102E+10 | 0.487222E+10 | 0.150202E+11 | 0.00 | 3.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 29273.42 | 0.00 | 0.00 | 0.00 | 0.00 | 3.58 |
Maximum of Months | 0.608921E+10 | 0.283471E+11 | 0.00 | 26194219.25 | 0.650467E+09 | 0.286792E+10 | 0.315032E+10 | 0.00 | 3.92 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.175823E+11 | 0.00 | 0.00 | 42151174.83 | 0.00 | 0.00 | 0.197611E+11 | 0.00 | 9.93 |
February | 0.839518E+10 | 0.00 | 0.00 | 64450982.94 | 0.00 | 0.00 | 0.182176E+11 | 0.00 | 10.07 |
March | 0.169789E+10 | 0.103625E+10 | 0.00 | 93723019.09 | 380839.12 | 0.00 | 0.142881E+11 | 0.00 | 10.25 |
April | 0.163890E+09 | 0.850827E+10 | 0.00 | 42918212.89 | 18933735.81 | 0.00 | 0.297240E+10 | 0.00 | 10.46 |
May | 16009782.65 | 0.265115E+11 | 0.00 | 3541648.77 | 58094800.40 | 0.00 | 75403069.47 | 0.00 | 10.76 |
June | 0.00 | 0.367077E+11 | 0.00 | 192288.98 | 68124029.01 | 0.00 | 10461478.79 | 0.00 | 11.19 |
July | 0.00 | 0.468060E+11 | 0.00 | 127241.14 | 73477552.68 | 0.00 | 6479018.62 | 0.00 | 11.55 |
August | 117850.26 | 0.465661E+11 | 0.00 | 480235.10 | 85949163.74 | 0.00 | 49309318.26 | 0.00 | 11.51 |
September | 1779947.38 | 0.378344E+11 | 0.00 | 1483922.52 | 0.103417E+09 | 0.00 | 0.153184E+09 | 0.00 | 11.18 |
October | 0.638002E+09 | 0.586789E+10 | 0.00 | 56229924.56 | 8065189.21 | 0.00 | 0.550255E+10 | 0.00 | 10.44 |
November | 0.393311E+10 | 40897942.99 | 0.00 | 0.102277E+09 | 0.00 | 0.00 | 0.179217E+11 | 0.00 | 10.17 |
December | 0.140730E+11 | 0.00 | 0.00 | 54398577.58 | 0.00 | 0.00 | 0.211397E+11 | 0.00 | 9.95 |
Annual Sum or Average | 0.465012E+11 | 0.209879E+12 | 0.00 | 0.461974E+09 | 0.416443E+09 | 0.00 | 0.100098E+12 | 0.00 | 10.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 127241.14 | 0.00 | 0.00 | 6479018.62 | 0.00 | 9.93 |
Maximum of Months | 0.175823E+11 | 0.468060E+11 | 0.00 | 0.102277E+09 | 0.103417E+09 | 0.00 | 0.211397E+11 | 0.00 | 11.55 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:20
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.303505E+11 | 0.110107E+11 | 0.715733E+11 | 0.332045E+10 | 0.345597E+11 |
February | 0.351932E+11 | 0.670189E+10 | 0.515197E+11 | 0.243621E+10 | 0.487005E+11 |
March | 0.497962E+11 | 0.112535E+10 | 0.291331E+11 | 0.118129E+10 | 0.955610E+11 |
April | 0.584373E+11 | -0.666055E+10 | -0.112430E+11 | 30654663.99 | 0.148982E+12 |
May | 0.629543E+11 | -0.151858E+11 | -0.514768E+11 | -535789352.6 | 0.208524E+12 |
June | 0.576341E+11 | -0.197170E+11 | -0.712205E+11 | -0.114553E+10 | 0.231447E+12 |
July | 0.467158E+11 | -0.236961E+11 | -0.893644E+11 | -0.145338E+10 | 0.251937E+12 |
August | 0.394999E+11 | -0.236140E+11 | -0.878531E+11 | -0.116220E+10 | 0.247569E+12 |
September | 0.417955E+11 | -0.178264E+11 | -0.694736E+11 | -707168349.6 | 0.214930E+12 |
October | 0.404181E+11 | -0.512522E+10 | -185690549.7 | 0.568002E+09 | 0.139092E+12 |
November | 0.336223E+11 | 0.342390E+10 | 0.429564E+11 | 0.175857E+10 | 0.766892E+11 |
December | 0.273325E+11 | 0.979755E+10 | 0.676698E+11 | 0.346105E+10 | 0.404914E+11 |
Annual Sum or Average | 0.523750E+12 | -0.797657E+11 | -0.117965E+12 | 0.775216E+10 | 0.173848E+13 |
Minimum of Months | 0.273325E+11 | -0.236961E+11 | -0.893644E+11 | -0.145338E+10 | 0.345597E+11 |
Maximum of Months | 0.629543E+11 | 0.110107E+11 | 0.715733E+11 | 0.346105E+10 | 0.251937E+12 |