Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:25:25
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1657.03 | 7131.82 | 7131.82 |
Net Site Energy | 1657.03 | 7131.82 | 7131.82 |
Total Source Energy | 2878.47 | 12388.87 | 12388.87 |
Net Source Energy | 2878.47 | 12388.87 | 12388.87 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 439.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 30.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 29.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 276.59 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 93.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 221.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 62.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 519.56 | 1137.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 439.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 30.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 29.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 27.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 93.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 221.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 16.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 29.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 439.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 30.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 29.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 27.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 276.59 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 93.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 221.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 62.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 242.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 531.92 | 2841.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1461.45 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2236.19 | 4895.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 242.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 531.92 | 2841.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1461.45 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2236.19 | 4895.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 519.563 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 519.563 | 100.00 |
Total On-Site and Utility Electric Sources | 519.563 | 100.00 |
Total Electricity End Uses | 519.563 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 0.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3942.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 7.5044 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.8503 | 18.52 | 1074.0064 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.6773 | 2.48 | 595.3967 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.6773 | 2.48 | 595.3967 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 7.5044 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.8503 | 18.52 | 1074.0064 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 8.6773 | 1.24 | 595.3967 | |||||||
Conditioned Total | 232.34 | 8.6773 | 1.24 | 595.3967 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 8.6773 | 2.48 | 595.3967 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 20-JUL-11:09 | 06-FEB-11:09 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 82717.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13917.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1331.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 13514.13 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3577.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 19531.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2940.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 35281.51 | 128909.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 82717.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 13917.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1331.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 12146.55 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 3577.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 19531.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1319.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 476.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 95.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 92.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 85.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 875.96 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 295.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 239.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 199.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1645.46 | 1233.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2049.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 413.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 399.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 369.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3770.11 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1271.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1031.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 858.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7082.01 | 5306.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2049.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 413.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 399.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 369.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3770.11 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1271.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1031.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 858.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7082.01 | 5306.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.61 |
KITCHEN DIRECT AIR | 1.25 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.61 | 1.61 | 1.61 | 1.61 | 1.61 | 1.61 | 1.00 | 1.00 | 1.61 |
PSZ-AC_2:2 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.00 | 1.00 | 1.25 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.61 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.25 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.61 | 1719.70 |
PSZ-AC_2:2_ADDAQ FAN | 1.25 | 1384.97 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.61 | 1.61 | 1.61 | 1.06 | 39843.90 | 55376.50 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.25 | 1.25 | 1.25 | 1.25 | 31063.44 | 80970.58 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.61 | 0.803563 | 1.07 | 39843.90 | 19921.95 | 0.701480 | 0.701480 |
PSZ-AC_2:2 COOLING COIL | 1.25 | 0.625462 | 0.833947 | 31063.44 | 15531.72 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 55376.50 |
PSZ-AC_2:2 HEATING COIL | 80970.58 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 7.504 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 124.291 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.850 | 282.654 | 791.353 | 0.000 | 0.000 | 0.000 | 1083.857 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 871.800 | 7.504 | 9.958 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 871.800 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1144.319 | 9.850 | 182.411 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1144.319 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 515.917 | 4.441 | 82.240 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 851.667 | 7.331 | 135.761 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.5240 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.675 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.34551204E-12 | 0.74231739E-15 | -0.11570264E-12 | 0.10846093E-15 |
34 | 6 | 0.31642787E-07 | 0.15149359E-09 | 0.72238643E-08 | -0.15123089E-12 |
35 | 5 | -0.20507995E-03 | 0.12733022E-05 | -0.10526694E-03 | 0.71312208E-08 |
36 | 4 | 0.30949825 | 0.60977726E-03 | 0.10593178 | -0.36036635E-04 |
37 | 3 | -7.6095708 | 0.18621275E-01 | -2.4407927 | 0.30692231E-01 |
38 | 2 | 42.002723 | 0.65356122E-01 | 15.682022 | -0.34594571 |
39 | 1 | -81.412450 | 0.29160263E-01 | -29.515211 | 1.0970889 |
40 | 0 | 46.824333 | 0.58011625E-03 | 16.282484 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.4731_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.053 | 0.3093 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.584 | 5.025E-003 | 6.281E-003 | 5.934 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.4362E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.3408E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.2606E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.1048E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.0309E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.7940E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5307E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.3706E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.8884E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.6413E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 0.1033 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 0.1003 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 6.1859E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.0584E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.4417E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.4427E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.0536E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.1518E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.7508E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.8957E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.3922E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.7792E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.3758E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.5308E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 17761.59128 | 21313.90954 | 1.33927 | 1.60713 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 7402.73500 | 8883.28200 | 0.32316 | 0.41606 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -16.30000 | 9.24091E-004 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16607.78806 | 19929.34568 | 1.04244 | 1.25092 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 29.46300 | 1.33655E-002 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.14133 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -16.30000 | 9.24091E-004 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 24140.72 | 1.60713 | 1.60713 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 27631.58 | 0.41606 | 0.41606 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 24148.06 | 1.25092 | 1.25092 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 75799.51 | 1.14133 | 1.14133 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.60713 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.25092 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.60713 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.60713 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.60713 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.60713 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.60713 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.60713 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.25092 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.25092 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.25092 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.25092 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.25092 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.25092 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.60713 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.25092 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.60713 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.60713 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 1719.70039 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.60713 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.60713 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.60713 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.06070 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.60713 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.80356 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.07142 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 39843.90000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19921.95000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70148 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70148 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39843.90000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 55376.49588 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 55376.49588 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.25092 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.25092 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1384.97218 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.25092 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.25092 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.25092 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.25092 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.25092 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62546 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.83395 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31063.44000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15531.72000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31063.44000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 80970.58368 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 80970.58368 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 38701.4 | 11.66 | 11.60 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 30174.3 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.524 | 0.486 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | N/A | 2.689 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.524 | 0.486 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | N/A | 2.689 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.524 | 0.486 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | N/A | 2.689 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.524 | 0.486 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.524 | 0.486 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.524 | 0.486 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1192800515 | 0.4829466060 | Pass | Pass | 0.2014836368 | 0.9422676005 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1489501362 | 0.7133825418 | Pass | Pass | 3.3020963666E-002 | 9.6177963882E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.1395103227 | 0.1367912073 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 480.20 | 134.50 | 999.28 | 8.98 | 489.24 | 2112.20 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.486 | 0.524 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.486 | 0.524 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.486 | 0.524 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.486 | 0.524 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.486 | 0.524 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.486 | 0.524 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.689 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.689 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 7.5044 | 116.17 | 871.80 | LightsWired | LTG_SCH_DINING | 91.35 | 168.00 | 65.68 | 0.0000 | Y | 10.75 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.8503 | 116.17 | 1144.32 | LightsWired | LTG_SCH_KITCHEN | 87.05 | 168.00 | 86.54 | 0.0000 | Y | 18.59 |
Interior Lighting Total | 8.6773 | 232.34 | 2016.12 | 29.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.22 | 871.80 | 191.80 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.22 | 871.80 | 191.80 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 216.58 | AstronomicalClock | - | 49.04 | 49.04 | 1.99 | |
EXTERIOR_LIGHTS_B | 1823.66 | AstronomicalClock | - | 83.67 | 73.28 | 25.09 | |
Exterior Lighting Total | 2040.24 | 27.08 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 39843.90 | 27949.70 | 11894.20 | 0.70 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31063.44 | 21777.96 | 9285.48 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 38701.4 | 11.66 | 11.60 | ||||
PSZ-AC_2:2 COOLING COIL | 30174.3 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 55376.50 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 80970.58 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 1.56 | 1211.87 | 778.12 | 1.00 | 0.64 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.61 | 1719.70 | 1070.05 | 1.00 | 1.35 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.25 | 1384.97 | 1107.16 | 1.00 | 1.35 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 17761.59 | 21313.91 | 183.47 | 1.339 | 1.607 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.87 | 0.01089 | 30.30 | 0.01337 | 0.416 | 0.00 |
KITCHEN | 16607.79 | 19929.35 | 171.55 | 1.042 | 1.251 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.01021 | 29.46 | 0.01337 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 7402.73 | 8883.28 | 76.47 | 0.323 | 0.416 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00764 | -16.30 | 0.00092 | 0.416 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.141 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 18.89 | 19.19 | 0.00071 | -16.30 | 0.00092 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.61 | 1.61 | 0.42 | 0.42 | 1.6071 | 1.6071 | 1.6071 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.25 | 1.25 | 1.14 | 1.14 | 1.2509 | 1.2509 | 1.2509 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 39843.900 | 27949.699 | 1.607130 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 19921.95 | 13035.37 | 1.071420 | 25.53 | 19.08 | 0.01152972 | 11.91 | 11.51 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 38.8322 | 23.87 | 0.01088794 | 57.3599 | 17761.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 55376.496 | 55376.496 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | 55376.50 | 55376.50 | 1.607126 | 10.79 | 7.90 | 0.00559840 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 25.8882 | 16.37 | 0.00723119 | 60.9468 | 2694.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 31063.440 | 21777.957 | 1.250920 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 15531.72 | 9470.27 | 0.833947 | 29.16 | 21.31 | 0.01308918 | 11.88 | 11.49 | 0.00850000 | 29.46 | 0.01336548 | 21.59 | 136.8593 | 26.10 | 0.01021176 | 47.1667 | 16607.79 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 80970.584 | 80970.584 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 80970.58 | 80970.58 | 1.250925 | -14.87 | -15.20 | 0.00090649 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 91.2392 | 19.60 | 0.00072320 | 5.0287 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 39843.900 | 27949.699 | 1.607130 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2732 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.607126 | 1.88664545 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 19921.95 | 13035.37 | 1.0000 | 1.25776706 | 1.071420 | 25.53 | 19.08 | 0.01152972 | 55039.7 | 11.91 | 11.51 | 0.00850000 | 33415.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19921.95 | 30.30 | 0.01336696 | 21.83 | 0.41605618 | 38.8322 | 23.87 | 0.01088794 | 23.87 | 0.01088794 | 57.3599 | 17761.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 55376.496 | 55376.496 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.607126 | 1.88664545 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | Sensible | 55376.50 | 55376.50 | 1.0000 | 1.88664545 | 1.607126 | 10.79 | 7.90 | 0.00559840 | 24955.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 55376.50 | -16.30 | 0.00092409 | -16.30 | 0.41605618 | 25.8882 | 20.25 | 0.00723119 | 16.37 | 0.00723119 | 60.9468 | 2694.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31063.440 | 21777.957 | 1.250920 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1029.1721 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.250925 | 1.46849214 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 15531.72 | 9470.27 | 1.0000 | 0.97899110 | 0.833947 | 29.16 | 21.31 | 0.01308918 | 62750.7 | 11.88 | 11.49 | 0.00850000 | 33386.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15531.72 | 29.46 | 0.01336548 | 21.59 | 1.14133354 | 136.8593 | 26.06 | 0.01021176 | 26.10 | 0.01021176 | 47.1667 | 16607.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 80970.584 | 80970.584 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.250925 | 1.46849214 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 80970.58 | 80970.58 | 1.0000 | 1.46849214 | 1.250925 | -14.87 | -15.20 | 0.00090649 | -12701.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 80970.58 | -16.30 | 0.00092409 | -16.30 | 1.14133354 | 91.2392 | 0.00 | 0.00072320 | 19.60 | 0.00072320 | 5.0287 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.61 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.25 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3432.17 | 5615.17 | 2130.00 |
KITCHEN | 4658.67 | 6189.67 | 3858.83 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4738.83 | 6920.67 | 3942.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 95.67 | 16.83 | 0.17 | 0.00 |
KITCHEN | 0.00 | 176.50 | 0.00 | 0.33 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 95.67 | 177.33 | 0.17 | 0.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.803 | 2.766 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 11.950 | 0.041 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.045 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 11.093 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 12435221.47 | 0.00 | 12435221.47 | 7023001.06 | 19458222.53 | 13120747.55 | 1429.10 | 5991.64 | 1339.26 | 483.06 |
KITCHEN | 31278622.59 | 0.00 | 31278622.59 | 174370.05 | 31452992.65 | 35993094.65 | 1418.32 | 5921.10 | 1420.58 | 608.44 |
Total Facility | 43713844.06 | 0.00 | 43713844.06 | 7197371.12 | 50911215.18 | 49113842.20 | 1447.58 | 6215.23 | 1654.65 | 818.68 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4662 | 0.0000 | 0.4662 | 0.2687 | 0.7349 | 0.4161 | 0.00 | 5881.99 | 1305.01 |
KITCHEN | 1.1616 | 0.0000 | 1.1616 | 0.0040 | 1.1656 | 1.1413 | 0.00 | 5815.88 | 1371.12 |
Total Facility | 1.6278 | 0.0000 | 1.6278 | 0.2727 | 1.9005 | 1.5574 | 0.00 | 6102.29 | 1591.42 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 17137694.69 | 0.00 | 17137694.69 | 13120747.55 | 1421.93 | 0.97 | 7337.10 | 483.00 |
PSZ-AC_2:2 | 43105089.87 | 0.00 | 43105089.87 | 35993094.65 | 1377.70 | 1.64 | 7380.66 | 608.44 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6425 | 0.0000 | 0.6425 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.6007 | 0.0000 | 1.6007 | 1.1413 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1287.25 | 395.53 | 5987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 1577.68 | 6217.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.0243 | 0.7840 | 0.5735 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.7180 | 1.5730 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 374 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 519.56 | 5208.00 | 07-FEB-01:10 | 35281.51 | 20-JUL-11:10 |
Electricity:Building | 323.79 | 2948.69 | 01-JAN-01:10 | 19261.27 | 02-JAN-11:10 |
Electricity:Zone:DINING | 81.08 | 392.54 | 01-JAN-01:10 | 4341.96 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 305.93 | 2539.66 | 01-JAN-01:10 | 15745.17 | 02-JAN-11:10 |
InteriorLights:Electricity | 29.34 | 230.86 | 03-JUN-05:00 | 1654.77 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:DINING | 10.75 | 77.60 | 03-JUN-05:00 | 735.19 | 02-JAN-16:50 |
InteriorLights:Electricity:SpaceType:GENERAL | 29.34 | 230.86 | 03-JUN-05:00 | 1654.77 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 29.34 | 230.86 | 03-JUN-05:00 | 1654.77 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 10.75 | 77.60 | 03-JUN-05:00 | 735.19 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 29.34 | 230.86 | 03-JUN-05:00 | 1654.77 | 02-JAN-16:50 |
Electricity:Zone:KITCHEN | 242.71 | 2556.15 | 01-JAN-01:10 | 14919.31 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 18.59 | 153.26 | 01-JAN-01:10 | 919.59 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 18.59 | 153.26 | 01-JAN-01:10 | 919.59 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 276.59 | 2263.87 | 01-JAN-01:10 | 14413.88 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 276.59 | 2263.87 | 01-JAN-01:10 | 14413.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 206.26 | 1993.86 | 01-JAN-01:10 | 10483.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 62.97 | 1035.59 | 09-JAN-23:30 | 4592.33 | 02-JUN-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
Electricity:Plant | 45.11 | 779.94 | 08-FEB-23:10 | 2546.67 | 21-JUL-03:30 |
LowTempRefrigeration:Refrigeration:Electricity | 16.06 | 0.00 | 01-JAN-11:10 | 1470.43 | 21-JUL-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 29.05 | 701.41 | 11-DEC-00:20 | 1076.23 | 14-MAR-12:10 |
ElectricityPurchased:Facility | 519.56 | 5208.00 | 07-FEB-01:10 | 35281.51 | 20-JUL-11:10 |
ElectricityPurchased:Plant | 519.56 | 5208.00 | 07-FEB-01:10 | 35281.51 | 20-JUL-11:10 |
Cogeneration:ElectricityPurchased | 519.56 | 5208.00 | 07-FEB-01:10 | 35281.51 | 20-JUL-11:10 |
General:Cogeneration:ElectricityPurchased | 519.56 | 5208.00 | 07-FEB-01:10 | 35281.51 | 20-JUL-11:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 519.56 | 5208.00 | 07-FEB-01:10 | 35281.51 | 20-JUL-11:10 |
ElectricityNet:Plant | 519.56 | 5208.00 | 07-FEB-01:10 | 35281.51 | 20-JUL-11:10 |
Cogeneration:ElectricityNet | 519.56 | 5208.00 | 07-FEB-01:10 | 35281.51 | 20-JUL-11:10 |
General:Cogeneration:ElectricityNet | 519.56 | 5208.00 | 07-FEB-01:10 | 35281.51 | 20-JUL-11:10 |
Electricity:HVAC | 123.59 | 0.00 | 01-JAN-01:10 | 18217.64 | 27-JUN-13:00 |
Fans:Electricity | 93.28 | 0.00 | 01-JAN-01:10 | 3960.11 | 06-FEB-21:00 |
General:Fans:Electricity | 93.28 | 0.00 | 01-JAN-01:10 | 3960.11 | 06-FEB-21:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 30.31 | 0.00 | 01-JAN-00:10 | 14556.67 | 27-JUN-13:00 |
General:Cooling:Electricity | 30.31 | 0.00 | 01-JAN-00:10 | 14556.67 | 27-JUN-13:00 |
ExteriorLights:Electricity | 27.08 | 0.00 | 01-JAN-08:00 | 2040.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 27.08 | 0.00 | 01-JAN-08:00 | 2040.24 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 10-MAY-17:50 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 10-MAY-17:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1137.47 | 2558.65 | 06-FEB-03:40 | 128909.52 | 06-FEB-11:10 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 439.25 | 0.00 | 01-JAN-01:10 | 89657.54 | 06-FEB-20:10 |
Heating:NaturalGas | 439.25 | 0.00 | 01-JAN-01:10 | 89657.54 | 06-FEB-20:10 |
General:Heating:NaturalGas | 439.25 | 0.00 | 01-JAN-01:10 | 89657.54 | 06-FEB-20:10 |
NaturalGas:Plant | 221.06 | 720.00 | 03-JAN-03:10 | 28004.29 | 13-FEB-13:30 |
WaterSystems:NaturalGas | 221.06 | 720.00 | 03-JAN-03:10 | 28004.29 | 13-FEB-13:30 |
Water Heater:WaterSystems:NaturalGas | 221.06 | 720.00 | 03-JAN-03:10 | 28004.29 | 13-FEB-13:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUL-12:40 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUL-12:40 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUL-12:40 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUL-12:40 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUL-12:40 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUL-12:40 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUL-12:40 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUL-12:40 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1156.14 | 2741.04 | 07-FEB-01:10 | 113982.42 | 06-FEB-14:00 |
EnergyTransfer:Building | 459.61 | 1370.52 | 07-FEB-01:10 | 34628.13 | 06-FEB-12:10 |
EnergyTransfer:Zone:KITCHEN | 352.51 | 1370.52 | 07-FEB-01:10 | 22717.39 | 13-JUN-04:10 |
Refrigeration:EnergyTransfer | 144.43 | 2699.61 | 08-FEB-23:10 | 7834.84 | 02-JUN-04:10 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 72.21 | 1349.81 | 08-FEB-23:10 | 3917.42 | 02-JUN-04:10 |
General:Refrigeration:EnergyTransfer | 72.21 | 1349.81 | 08-FEB-23:10 | 3917.42 | 02-JUN-04:10 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 72.21 | 1349.81 | 08-FEB-23:10 | 3917.42 | 02-JUN-04:10 |
EnergyTransfer:Plant | 223.54 | 1349.81 | 10-DEC-23:20 | 23092.16 | 14-MAR-12:40 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 16.29 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 55.92 | 1114.23 | 11-DEC-00:20 | 2238.70 | 14-MAR-12:10 |
EnergyTransfer:Zone:DINING | 107.09 | 0.00 | 01-JAN-01:10 | 19876.33 | 06-FEB-21:00 |
Heating:EnergyTransfer | 48.48 | 0.00 | 01-JAN-00:20 | 19876.33 | 06-FEB-21:00 |
Heating:EnergyTransfer:Zone:DINING | 48.46 | 0.00 | 01-JAN-00:10 | 19876.33 | 06-FEB-21:00 |
General:Heating:EnergyTransfer | 48.48 | 0.00 | 01-JAN-00:20 | 19876.33 | 06-FEB-21:00 |
General:Heating:EnergyTransfer:Zone:DINING | 48.46 | 0.00 | 01-JAN-00:10 | 19876.33 | 06-FEB-21:00 |
Cooling:EnergyTransfer | 338.91 | 0.00 | 01-JAN-01:10 | 27730.65 | 21-JUL-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 58.64 | 0.00 | 01-JAN-01:10 | 13080.68 | 10-AUG-12:00 |
General:Cooling:EnergyTransfer | 338.91 | 0.00 | 01-JAN-01:10 | 27730.65 | 21-JUL-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 58.64 | 0.00 | 01-JAN-01:10 | 13080.68 | 10-AUG-12:00 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:20 | 1084.93 | 12-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:20 | 1084.93 | 12-DEC-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 280.28 | 0.00 | 01-JAN-01:10 | 18846.59 | 13-JUN-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 280.28 | 0.00 | 01-JAN-01:10 | 18846.59 | 13-JUN-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 151.32 | 0.00 | 01-JAN-00:10 | 20674.41 | 12-FEB-14:00 |
PlantLoopHeatingDemand:Plant | 151.32 | 0.00 | 01-JAN-00:10 | 20674.41 | 12-FEB-14:00 |
WaterSystems:PlantLoopHeatingDemand | 151.32 | 0.00 | 01-JAN-00:10 | 20674.41 | 12-FEB-14:00 |
General:WaterSystems:PlantLoopHeatingDemand | 151.32 | 0.00 | 01-JAN-00:10 | 20674.41 | 12-FEB-14:00 |
EnergyTransfer:HVAC | 473.00 | 0.00 | 01-JAN-01:10 | 71726.03 | 06-FEB-20:10 |
HeatingCoils:EnergyTransfer | 351.40 | 0.00 | 01-JAN-01:10 | 71726.03 | 06-FEB-20:10 |
CoolingCoils:EnergyTransfer | 121.60 | 0.00 | 01-JAN-00:10 | 62661.33 | 27-JUN-13:00 |
WaterSystems:EnergyTransfer | 151.32 | 0.00 | 01-JAN-00:10 | 20674.41 | 12-FEB-14:00 |
WaterUse:WaterSystems:EnergyTransfer | 151.32 | 0.00 | 01-JAN-00:10 | 20674.41 | 12-FEB-14:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 48.459 | -58.635 | 0.000 | 0.000 | 72.225 | 10.749 | 52.748 | 21.310 | 0.000 | 1.657 | 0.000 | 0.000 | -16.457 | 0.000 | -106.918 | -25.138 |
KITCHEN | 0.000 | 0.000 | 0.019 | -280.271 | 0.000 | 0.000 | 5.186 | 18.590 | 211.968 | 0.000 | 0.000 | 0.009 | 47.709 | 0.000 | 0.000 | 0.000 | -3.211 | -0.001 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.871 | 10.292 | 0.000 | 0.000 | 0.000 | -13.163 | -0.000 |
Total Facility | 0.000 | 0.000 | 48.478 | -338.906 | 0.000 | 0.000 | 77.411 | 29.339 | 264.717 | 21.310 | 0.000 | 4.537 | 58.001 | 0.000 | -16.457 | 0.000 | -123.292 | -25.138 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 24-MAY-00:21 | 0.00 | 0.00 | 0.00 | -20250.22 | 0.00 | 0.00 | 0.00 | 122.53 | 202.51 | 0.00 | 0.00 | 2.84 | 20050.96 | 0.00 | -128.63 | 0.00 | 0.00 | 0.00 |
KITCHEN | 11-DEC-05:01 | 0.00 | 0.00 | 0.00 | -51030.68 | 0.00 | 0.00 | 20.13 | 204.35 | 5271.43 | 0.00 | 0.00 | 0.00 | 45596.01 | 0.00 | -0.00 | 0.00 | -61.26 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-DEC-00:01 | 0.00 | 0.00 | 0.00 | -58146.81 | 0.00 | 0.00 | 388.31 | 275.79 | 2648.48 | 0.00 | 0.00 | 204.40 | 56983.88 | 0.00 | -2174.60 | 0.00 | -179.44 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 08-FEB-03:01 | 0.00 | 0.00 | 40060.95 | 0.00 | 0.00 | 0.00 | 0.00 | 122.53 | 202.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1383.94 | 0.00 | -911.07 | -38090.98 |
KITCHEN | 12-DEC-05:03 | 0.00 | 0.00 | 10840.59 | 0.00 | 0.00 | 0.00 | 18.04 | 204.35 | 5271.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -172.52 | -16161.90 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-FEB-03:01 | 0.00 | 0.00 | 40060.95 | 0.00 | 0.00 | 0.00 | 0.00 | 275.79 | 2219.64 | 0.00 | 0.00 | 65.31 | 0.00 | 0.00 | -1383.94 | 0.00 | -1923.75 | -39314.01 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.6071 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.6071 | 0.2589 | 1.0000 | Not calculated | 0.4161 | 0.2589 | ||
PSZ-AC_2:2 | 1.2509 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2509 | 0.1209 | 1.0000 | Not calculated | 0.1513 | 0.1209 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.6071 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.6071 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2589 | ||
PSZ-AC_2:2 | 1.2509 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2509 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1209 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6071 | 1.6071 | 1.6071 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2509 | 1.2509 | 1.2509 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.6071 | 1.6071 | 1.6071 | 1.6071 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2509 | 1.2509 | 1.2509 | 1.2509 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6071 | 1.6071 | 1.6071 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2509 | 1.2509 | 1.2509 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.6071 | 1.6071 | 1.6071 | 1.6071 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2509 | 1.2509 | 1.2509 | 1.2509 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 0.33 |
Number of hours not met | 0.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 439.25 | 89657.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 30.31 | 14556.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 29.34 | 1654.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 27.08 | 2040.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 93.28 | 3960.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 221.06 | 28004.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 17.86 | 3516.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 16.06 | 1470.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 29.05 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 339.56 | 519.56 |
Natural Gas | 477.16 | 1137.47 |
Additional | 0.00 | 0.00 |
Total | 816.71 | 1657.03 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 126.28 |
Space Heating | 0.00 |
Space Cooling | 130.45 |
Fans (All) | 401.46 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1190.44 |
Miscellaneous (All) | 2236.19 |
Subtotal | 2236.19 |
Natural Gas [MJ/m2] | |
Space Heating | 1890.52 |
Service Water Heating | 951.43 |
Miscellaneous (All) | 4895.63 |
Subtotal | 4895.63 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.77 |
Space Heating | 26.51 |
Space Cooling | 1.83 |
Fans (All) | 5.63 |
Service Water Heating | 13.34 |
Receptacle Equipment | 45.49 |
Miscellaneous | 5.43 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4763. | 8760. |
LTG_SCH_KITCHEN | 4539. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_SETBACK | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_SETBACK | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8608.00 | 152.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 7217.17 | 478.67 | 482.17 | 510.33 | 71.67 |
Min | 7217.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 478.67 | 482.17 | 510.33 | 71.67 |
Average | 8195.06 | 210.22 | 160.72 | 170.11 | 23.89 |
Sum | 24585.17 | 630.67 | 482.17 | 510.33 | 71.67 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16256.00 | 2.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 2.00 | 0.00 | 0.00 | 0.00 |
Average | 90327.00 | 0.67 | 0.00 | 0.00 | 0.00 |
Sum | 270981.00 | 2.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8149.00 | 611.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6983.67 | 1776.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 7134.83 | 874.33 | 291.33 | 245.17 | 214.33 |
Min | 6983.67 | 611.00 | 0.00 | 0.00 | 0.00 |
Max | 8149.00 | 1776.33 | 291.33 | 245.17 | 214.33 |
Average | 7422.50 | 1087.22 | 97.11 | 81.72 | 71.44 |
Sum | 22267.50 | 3261.67 | 291.33 | 245.17 | 214.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 234851.17 | 19873.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 12670.83 | 3587.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 234851.17 | 19873.83 | 0.00 | 0.00 | 0.00 |
Average | 82507.33 | 7820.33 | 0.00 | 0.00 | 0.00 |
Sum | 247522.00 | 23461.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.597859E+09 | 13725.73 | 24-JAN-00:01 | -11.1 | -12.0 | 0.444694E+10 | 3722.85 | 28-JAN-19:10 | -7.1 | -8.8 |
February | 0.562878E+09 | 15466.15 | 07-FEB-00:01 | -15.0 | -15.8 | 0.402518E+10 | 3722.85 | 04-FEB-19:30 | -15.0 | -15.8 |
March | 0.145802E+10 | 14764.26 | 06-MAR-05:02 | -11.1 | -11.9 | 0.455347E+10 | 4413.13 | 14-MAR-11:00 | 23.90 | 17.56 |
April | 0.227651E+10 | 10129.58 | 16-APR-23:01 | -2.9 | -4.7 | 0.439856E+10 | 4448.12 | 08-APR-18:49 | -2.9 | -4.7 |
May | 0.515951E+10 | 20254.04 | 24-MAY-00:21 | 23.05 | 14.96 | 0.487750E+10 | 4681.21 | 13-MAY-18:49 | 23.05 | 14.96 |
June | 0.903145E+10 | 17400.98 | 17-JUN-01:11 | 19.63 | 16.04 | 0.513956E+10 | 4681.37 | 10-JUN-18:40 | 19.63 | 16.04 |
July | 0.124468E+11 | 18070.48 | 08-JUL-01:22 | 20.25 | 15.31 | 0.538220E+10 | 4681.47 | 08-JUL-18:30 | 24.15 | 18.99 |
August | 0.120901E+11 | 18130.11 | 06-AUG-03:22 | 20.60 | 15.63 | 0.539981E+10 | 4681.63 | 05-AUG-18:00 | 20.60 | 15.63 |
September | 0.847502E+10 | 16188.26 | 09-SEP-00:42 | 20.10 | 16.82 | 0.501490E+10 | 4681.57 | 16-SEP-18:40 | 24.27 | 19.19 |
October | 0.412032E+10 | 8997.61 | 16-OCT-23:01 | -0.1 | -0.7 | 0.464954E+10 | 4583.41 | 21-OCT-18:10 | 16.42 | 12.10 |
November | 0.175042E+10 | 9672.88 | 24-NOV-00:01 | -1.8 | -2.5 | 0.435160E+10 | 4412.86 | 16-NOV-12:50 | -1.8 | -2.5 |
December | 0.666633E+09 | 16013.36 | 11-DEC-00:01 | -16.1 | -16.3 | 0.444543E+10 | 3722.87 | 09-DEC-19:10 | -16.1 | -16.3 |
Annual Sum or Average | 0.586355E+11 | 0.566847E+11 | ||||||||
Minimum of Months | 0.562878E+09 | 8997.61 | -16.1 | -16.3 | 0.402518E+10 | 3722.85 | -16.1 | -16.3 | ||
Maximum of Months | 0.124468E+11 | 20254.04 | 23.05 | 16.82 | 0.539981E+10 | 4681.63 | 24.27 | 19.19 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219347E+11 | 47734.49 | 10-JAN-05:01 | -13.3 | -14.3 | 0.768072E+10 | 5049.27 | 11-JAN-11:00 | 9.40 | 8.22 |
February | 0.194672E+11 | 49003.29 | 07-FEB-05:01 | -15.7 | -16.1 | 0.693812E+10 | 5036.86 | 14-FEB-11:00 | -5.6 | -7.2 |
March | 0.223453E+11 | 47284.08 | 07-MAR-05:01 | -13.3 | -13.9 | 0.769953E+10 | 5135.95 | 15-MAR-10:50 | 23.62 | 15.52 |
April | 0.223502E+11 | 34514.67 | 17-APR-04:01 | -3.4 | -5.0 | 0.746002E+10 | 5128.30 | 07-APR-10:00 | -3.4 | -5.0 |
May | 0.230523E+11 | 45234.14 | 23-MAY-03:51 | 7.20 | 5.65 | 0.778095E+10 | 5135.95 | 10-MAY-10:50 | 7.20 | 5.65 |
June | 0.235461E+11 | 43872.87 | 06-JUN-03:31 | 6.87 | 6.67 | 0.758741E+10 | 5137.40 | 27-JUN-10:00 | 28.30 | 22.79 |
July | 0.251471E+11 | 39777.43 | 07-JUL-04:01 | 12.20 | 11.56 | 0.785421E+10 | 5136.98 | 20-JUL-10:00 | 29.40 | 22.73 |
August | 0.255963E+11 | 41542.71 | 04-AUG-04:01 | 12.20 | 10.63 | 0.785414E+10 | 5135.99 | 15-AUG-10:09 | 26.70 | 22.70 |
September | 0.245585E+11 | 44580.42 | 05-SEP-03:31 | 6.87 | 6.34 | 0.757178E+10 | 5135.95 | 25-SEP-10:30 | 22.50 | 18.26 |
October | 0.254707E+11 | 40590.19 | 13-OCT-04:01 | 11.02 | 10.67 | 0.773286E+10 | 5135.93 | 11-OCT-10:00 | 11.02 | 10.67 |
November | 0.239903E+11 | 34798.68 | 24-NOV-05:01 | -3.0 | -3.7 | 0.744859E+10 | 5134.61 | 16-NOV-11:00 | -3.0 | -3.7 |
December | 0.228188E+11 | 51069.58 | 11-DEC-05:01 | -17.5 | -18.0 | 0.768112E+10 | 5093.69 | 01-DEC-11:00 | -17.5 | -18.0 |
Annual Sum or Average | 0.280277E+12 | 0.912894E+11 | ||||||||
Minimum of Months | 0.194672E+11 | 34514.67 | -17.5 | -18.0 | 0.693812E+10 | 5036.86 | -17.5 | -18.0 | ||
Maximum of Months | 0.255963E+11 | 51069.58 | 12.20 | 11.56 | 0.785421E+10 | 5137.40 | 29.40 | 22.79 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124262E+11 | 39711.89 | 12-JAN-03:01 | -5.8 |
February | 0.118693E+11 | 40062.83 | 08-FEB-03:01 | -5.3 |
March | 0.672630E+10 | 37606.13 | 06-MAR-05:01 | -11.1 |
April | 0.241930E+10 | 34055.07 | 16-APR-02:61 | 0.32 |
May | 0.173541E+09 | 5349.21 | 03-MAY-04:01 | 6.60 |
June | 1762042.76 | 2049.29 | 26-JUN-02:04 | 21.10 |
July | 2448626.74 | 4922.42 | 26-JUL-02:30 | 21.15 |
August | 213137.23 | 710.46 | 14-AUG-02:50 | 23.90 |
September | 9030709.44 | 1804.19 | 30-SEP-06:10 | 7.30 |
October | 0.946545E+09 | 10321.85 | 24-OCT-09:20 | 2.97 |
November | 0.296760E+10 | 15680.21 | 24-NOV-03:02 | -2.9 |
December | 0.109169E+11 | 37242.12 | 27-DEC-05:01 | -11.6 |
Annual Sum or Average | 0.484591E+11 | |||
Minimum of Months | 213137.23 | 710.46 | -11.6 | |
Maximum of Months | 0.124262E+11 | 40062.83 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6182143.08 | 9079.60 | 31-JAN-05:03 | -11.7 |
February | 5757643.60 | 10006.22 | 10-FEB-05:03 | -9.1 |
March | 3262934.05 | 9969.19 | 27-MAR-04:03 | -5.7 |
April | 404618.06 | 3249.20 | 16-APR-04:03 | -2.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 14.65 |
October | 36590.91 | 609.85 | 18-OCT-04:04 | 1.70 |
November | 35260.20 | 342.38 | 18-NOV-05:04 | 1.60 |
December | 3588398.68 | 10849.32 | 12-DEC-05:03 | -9.9 |
Annual Sum or Average | 19267588.59 | |||
Minimum of Months | 0.00 | 0.00 | -11.7 | |
Maximum of Months | 6182143.08 | 10849.32 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.980310E+09 | 735.19 | 02-JAN-16:49 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.867149E+09 | 735.19 | 01-FEB-17:19 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.921758E+09 | 735.19 | 01-MAR-17:49 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.852067E+09 | 735.19 | 01-APR-18:30 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.851885E+09 | 735.19 | 01-MAY-19:10 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.818078E+09 | 735.19 | 01-JUN-19:40 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.834806E+09 | 735.19 | 01-JUL-19:40 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.868739E+09 | 735.19 | 01-AUG-19:30 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.869272E+09 | 735.19 | 01-SEP-18:40 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.934041E+09 | 735.19 | 02-OCT-17:40 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.956235E+09 | 735.19 | 01-NOV-16:40 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.994617E+09 | 735.19 | 01-DEC-16:30 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.107490E+11 | 0.703313E+11 | ||||
Minimum of Months | 0.818078E+09 | 735.19 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.994617E+09 | 735.19 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.157083E+10 | 919.59 | 02-JAN-10:09 | 0.175178E+11 | 10483.62 | 01-JAN-11:09 |
February | 0.142278E+10 | 919.59 | 01-FEB-10:09 | 0.158225E+11 | 10483.62 | 01-FEB-11:09 |
March | 0.159585E+10 | 919.59 | 01-MAR-10:09 | 0.175179E+11 | 10483.62 | 01-MAR-11:09 |
April | 0.152633E+10 | 919.59 | 01-APR-16:10 | 0.169527E+11 | 10483.62 | 01-APR-10:09 |
May | 0.158334E+10 | 919.59 | 01-MAY-09:09 | 0.175178E+11 | 10483.62 | 01-MAY-10:09 |
June | 0.154251E+10 | 919.59 | 01-JUN-09:09 | 0.169528E+11 | 10483.62 | 01-JUN-10:09 |
July | 0.156734E+10 | 919.59 | 01-JUL-16:10 | 0.175177E+11 | 10483.62 | 01-JUL-10:09 |
August | 0.159585E+10 | 919.59 | 01-AUG-09:09 | 0.175179E+11 | 10483.62 | 01-AUG-10:09 |
September | 0.152669E+10 | 919.59 | 01-SEP-09:09 | 0.169527E+11 | 10483.62 | 01-SEP-10:09 |
October | 0.157065E+10 | 919.59 | 02-OCT-09:09 | 0.175178E+11 | 10483.62 | 01-OCT-10:09 |
November | 0.152062E+10 | 919.59 | 01-NOV-09:09 | 0.169527E+11 | 10483.62 | 01-NOV-10:09 |
December | 0.156752E+10 | 919.59 | 01-DEC-10:09 | 0.175177E+11 | 10483.62 | 01-DEC-11:09 |
Annual Sum or Average | 0.185903E+11 | 0.206258E+12 | ||||
Minimum of Months | 0.142278E+10 | 919.59 | 0.158225E+11 | 10483.62 | ||
Maximum of Months | 0.159585E+10 | 919.59 | 0.175179E+11 | 10483.62 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.980310E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181495E+11 |
February | 0.852256E+10 | 0.867149E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169450E+11 |
March | 0.954557E+10 | 0.921758E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13089399.67 | 0.132538E+11 |
April | 0.915225E+10 | 0.852067E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890031E+10 |
May | 0.947560E+10 | 0.851885E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8221670.44 | 0.515419E+10 |
June | 0.922788E+10 | 0.818078E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268870E+09 | 0.263794E+10 |
July | 0.939996E+10 | 0.834806E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740339E+09 | 0.103414E+10 |
August | 0.954557E+10 | 0.868739E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582327E+09 | 0.168785E+10 |
September | 0.915225E+10 | 0.869272E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43683467.98 | 0.368820E+10 |
October | 0.940563E+10 | 0.934041E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792460E+10 |
November | 0.909363E+10 | 0.956235E+09 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103430E+11 |
December | 0.939996E+10 | 0.994617E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171996E+11 |
Annual Sum or Average | 0.111326E+12 | 0.107490E+11 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165653E+10 | 0.106918E+12 |
Minimum of Months | 0.852256E+10 | 0.818078E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103414E+10 |
Maximum of Months | 0.954557E+10 | 0.994617E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740339E+09 | 0.181495E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.157083E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517112E+09 |
February | 0.610713E+09 | 0.142278E+10 | 0.120683E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547942E+09 |
March | 0.684021E+09 | 0.159585E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334942E+09 |
April | 0.655836E+09 | 0.152633E+10 | 0.129303E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252866E+09 |
May | 0.679007E+09 | 0.158334E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 3449.17 | 0.153369E+09 |
June | 0.661256E+09 | 0.154251E+10 | 0.129304E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 1377686.18 | 0.111571E+09 |
July | 0.673587E+09 | 0.156734E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 4257357.85 | 63802666.02 |
August | 0.684021E+09 | 0.159585E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 2971723.73 | 75131459.65 |
September | 0.655836E+09 | 0.152669E+10 | 0.129303E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 111471.66 | 0.107723E+09 |
October | 0.673993E+09 | 0.157065E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210662E+09 |
November | 0.651635E+09 | 0.152062E+10 | 0.129304E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293922E+09 |
December | 0.673587E+09 | 0.156752E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541507E+09 |
Annual Sum or Average | 0.797748E+10 | 0.185903E+11 | 0.157319E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 8721688.59 | 0.321055E+10 |
Minimum of Months | 0.610713E+09 | 0.142278E+10 | 0.120683E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63802666.02 |
Maximum of Months | 0.684021E+09 | 0.159585E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 4257357.85 | 0.547942E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268781E+09 | 0.502566E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203321E+09 | 0.721938E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293362E+09 | 0.112900E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209912E+09 | 0.138925E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232507E+09 | 0.162893E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200037E+09 | 0.180386E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196276E+09 | 0.173725E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202954E+09 | 0.148762E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271316E+09 | 0.112445E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273209E+09 | 0.762678E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281456E+09 | 0.435975E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238214E+09 | 0.439763E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287134E+10 | 0.131633E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196276E+09 | 0.435975E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293362E+09 | 0.180386E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 735.19 | 02-JAN-16:49 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 21951.87 | 30-JAN-18:55 |
February | 9454.80 | 04-FEB-19:10 | 735.19 | 01-FEB-17:19 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 23842.55 | 06-FEB-21:00 |
March | 9454.80 | 04-MAR-19:10 | 735.19 | 01-MAR-17:49 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 678.44 | 15-MAR-14:00 | 20681.72 | 06-MAR-21:00 |
April | 9454.80 | 01-APR-18:10 | 735.19 | 01-APR-18:30 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 12607.05 | 16-APR-20:00 |
May | 9454.80 | 06-MAY-18:10 | 735.19 | 01-MAY-19:10 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 667.86 | 10-MAY-14:00 | 7220.20 | 11-MAY-19:00 |
June | 9454.80 | 03-JUN-18:10 | 735.19 | 01-JUN-19:40 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3390.40 | 27-JUN-12:00 | 6626.71 | 13-JUN-12:00 |
July | 9454.80 | 01-JUL-18:10 | 735.19 | 01-JUL-19:40 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3389.20 | 21-JUL-12:00 | 2864.83 | 06-JUL-19:52 |
August | 9454.80 | 05-AUG-18:10 | 735.19 | 01-AUG-19:30 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3385.03 | 10-AUG-12:00 | 5123.57 | 30-AUG-17:55 |
September | 9454.80 | 02-SEP-18:10 | 735.19 | 01-SEP-18:40 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1241.11 | 15-SEP-12:00 | 6090.73 | 28-SEP-17:10 |
October | 9454.80 | 07-OCT-18:10 | 735.19 | 02-OCT-17:40 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 12322.10 | 16-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 735.19 | 01-NOV-16:40 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 14165.19 | 22-NOV-21:00 |
December | 9454.80 | 02-DEC-19:10 | 735.19 | 01-DEC-16:30 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 24203.83 | 11-DEC-20:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 735.19 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2864.83 | |||||
Maximum of Months | 9454.80 | 735.19 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3390.40 | 24203.83 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 919.59 | 02-JAN-10:09 | 7748.81 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1629.81 | 12-JAN-05:00 |
February | 677.52 | 04-FEB-19:10 | 919.59 | 01-FEB-10:09 | 7748.81 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1621.57 | 13-FEB-04:10 |
March | 677.52 | 04-MAR-19:10 | 919.59 | 01-MAR-10:09 | 7748.81 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1059.75 | 02-MAR-05:00 |
April | 677.52 | 01-APR-18:10 | 919.59 | 01-APR-16:10 | 7748.81 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 1021.02 | 16-APR-04:00 |
May | 677.52 | 06-MAY-18:10 | 919.59 | 01-MAY-09:09 | 7748.81 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 14.28 | 24-MAY-00:47 | 363.98 | 30-MAY-03:30 |
June | 677.52 | 03-JUN-18:10 | 919.59 | 01-JUN-09:09 | 7748.81 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 31.93 | 12-JUN-13:10 | 629.87 | 13-JUN-03:20 |
July | 677.52 | 01-JUL-18:10 | 919.59 | 01-JUL-16:10 | 7748.81 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 84.49 | 21-JUL-03:00 | 474.18 | 06-JUL-02:00 |
August | 677.52 | 05-AUG-18:10 | 919.59 | 01-AUG-09:09 | 7748.81 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 36.03 | 13-AUG-13:00 | 278.20 | 27-AUG-03:20 |
September | 677.52 | 02-SEP-18:10 | 919.59 | 01-SEP-09:09 | 7748.81 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 22.79 | 17-SEP-00:25 | 598.22 | 29-SEP-03:50 |
October | 677.52 | 07-OCT-18:10 | 919.59 | 02-OCT-09:09 | 7748.81 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 543.88 | 07-OCT-02:10 |
November | 677.52 | 04-NOV-18:10 | 919.59 | 01-NOV-09:09 | 7748.81 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1060.21 | 17-NOV-04:10 |
December | 677.52 | 02-DEC-19:10 | 919.59 | 01-DEC-10:09 | 7748.81 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1342.41 | 26-DEC-04:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 919.59 | 7748.81 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 278.20 | ||||||
Maximum of Months | 677.52 | 919.59 | 7748.81 | 7998.14 | 0.00 | 0.00 | 0.00 | 84.49 | 1629.81 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.83 | 10-JAN-07:50 | 1518.99 | 30-JAN-13:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.25 | 14-FEB-19:55 | 2107.20 | 08-FEB-13:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.19 | 08-MAR-07:13 | 2372.03 | 07-MAR-13:30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.91 | 07-APR-04:55 | 2715.38 | 06-APR-12:40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540.93 | 27-MAY-05:05 | 2507.95 | 08-MAY-12:20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.73 | 12-JUN-00:01 | 2533.70 | 10-JUN-12:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.56 | 13-JUL-02:00 | 2486.42 | 03-JUL-12:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.07 | 12-AUG-03:00 | 2295.10 | 16-AUG-13:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.93 | 10-SEP-22:30 | 2182.41 | 10-SEP-13:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.56 | 09-OCT-22:55 | 1765.24 | 17-OCT-13:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.24 | 25-NOV-21:00 | 1266.10 | 24-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.86 | 16-DEC-08:00 | 1391.96 | 10-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.07 | 1266.10 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.91 | 2715.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13725.73 | 24-JAN-00:01 | 5252.67 | 1225.31 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.78 |
February | 15466.15 | 07-FEB-00:01 | 5252.67 | 1225.31 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.86 |
March | 14764.26 | 06-MAR-05:02 | 5252.67 | 1633.75 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.60 |
April | 10129.58 | 16-APR-23:01 | 5252.67 | 1225.31 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.02 |
May | 20254.04 | 24-MAY-00:21 | 0.00 | 1225.31 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.84 | 0.00 |
June | 17400.98 | 17-JUN-01:11 | 0.00 | 857.72 | 2835.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.48 |
July | 18070.48 | 08-JUL-01:22 | 0.00 | 735.19 | 2430.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.03 |
August | 18130.11 | 06-AUG-03:22 | 0.00 | 735.19 | 4050.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.11 |
September | 16188.26 | 09-SEP-00:42 | 0.00 | 735.19 | 1620.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.85 |
October | 8997.61 | 16-OCT-23:01 | 5252.67 | 1225.31 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.60 |
November | 9672.88 | 24-NOV-00:01 | 5252.67 | 1225.31 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.13 |
December | 16013.36 | 11-DEC-00:01 | 5252.67 | 1225.31 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8997.61 | 0.00 | 735.19 | 1620.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20254.04 | 5252.67 | 1633.75 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 2.84 | 235.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 47734.49 | 10-JAN-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 118.50 |
February | 49003.29 | 07-FEB-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 277.95 |
March | 47284.08 | 07-MAR-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 89.20 |
April | 34514.67 | 17-APR-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45234.14 | 23-MAY-03:51 | 0.00 | 1226.07 | 19708.49 | 11031.91 | 0.00 | 0.00 | 0.00 | 0.00 | 195.45 |
June | 43872.87 | 06-JUN-03:31 | 0.00 | 1226.07 | 19708.49 | 11031.91 | 0.00 | 0.00 | 0.00 | 0.00 | 214.43 |
July | 39777.43 | 07-JUL-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 26.10 |
August | 41542.71 | 04-AUG-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 38.26 |
September | 44580.42 | 05-SEP-03:31 | 0.00 | 1226.07 | 19708.49 | 11031.91 | 0.00 | 0.00 | 0.00 | 0.00 | 112.50 |
October | 40590.19 | 13-OCT-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 32.90 |
November | 34798.68 | 24-NOV-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 62.14 |
December | 51069.58 | 11-DEC-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 61.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 34514.67 | 0.00 | 1226.07 | 19708.49 | 11031.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51069.58 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 277.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.40 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.22 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.73 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.90 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.76 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.08 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.11 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.50 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.00 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.90 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.81 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.22 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.421395E+11 | 23854.31 | 31-JAN-11:09 | 0.162684E+12 | 118991.59 | 31-JAN-13:50 |
February | 0.378430E+11 | 23948.83 | 06-FEB-11:09 | 0.152266E+12 | 128909.52 | 06-FEB-11:09 |
March | 0.417156E+11 | 26872.30 | 15-MAR-10:00 | 0.124108E+12 | 107035.96 | 06-MAR-13:09 |
April | 0.395567E+11 | 23640.30 | 14-APR-10:09 | 0.865847E+11 | 88915.99 | 16-APR-12:09 |
May | 0.415662E+11 | 25984.67 | 10-MAY-10:00 | 0.644329E+11 | 55026.72 | 11-MAY-12:50 |
June | 0.452634E+11 | 34924.41 | 27-JUN-11:09 | 0.572012E+11 | 51617.23 | 13-JUN-12:20 |
July | 0.530307E+11 | 35281.51 | 20-JUL-11:09 | 0.575289E+11 | 48917.73 | 01-JUL-12:39 |
August | 0.503594E+11 | 34350.08 | 15-AUG-10:20 | 0.573343E+11 | 48496.54 | 02-AUG-12:39 |
September | 0.436254E+11 | 31460.24 | 15-SEP-10:00 | 0.568670E+11 | 50068.52 | 29-SEP-10:39 |
October | 0.418051E+11 | 24420.60 | 22-OCT-10:20 | 0.749006E+11 | 68540.91 | 17-OCT-07:10 |
November | 0.404877E+11 | 23647.07 | 22-NOV-11:09 | 0.917152E+11 | 79696.98 | 24-NOV-11:09 |
December | 0.421703E+11 | 23868.08 | 11-DEC-11:09 | 0.151842E+12 | 119356.38 | 11-DEC-11:09 |
Annual Sum or Average | 0.519563E+12 | 0.113747E+13 | ||||
Minimum of Months | 0.378430E+11 | 23640.30 | 0.568670E+11 | 48496.54 | ||
Maximum of Months | 0.530307E+11 | 35281.51 | 0.162684E+12 | 128909.52 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.255114E+10 | 0.293904E+10 | 0.234911E+11 | 0.00 | 0.813742E+10 | 0.79 | 0.00 | 384678.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228993E+10 | 0.242329E+10 | 0.212178E+11 | 0.00 | 0.737946E+10 | 0.72 | 0.00 | 242646.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251761E+10 | 0.236369E+10 | 0.234913E+11 | 0.00 | 0.791738E+10 | 0.80 | 0.00 | 0.300341E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237839E+10 | 0.196490E+10 | 0.227333E+11 | 0.00 | 0.744440E+10 | 0.77 | 0.00 | 19892828.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.243523E+10 | 0.175909E+10 | 0.234912E+11 | 0.00 | 0.776242E+10 | 0.80 | 0.00 | 0.668844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.236059E+10 | 0.158108E+10 | 0.227335E+11 | 0.00 | 0.764821E+10 | 0.77 | 0.00 | 0.543386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.240215E+10 | 0.167356E+10 | 0.234911E+11 | 0.00 | 0.801251E+10 | 0.79 | 0.00 | 0.116674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.246459E+10 | 0.190341E+10 | 0.234913E+11 | 0.00 | 0.797267E+10 | 0.80 | 0.00 | 0.876671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.239597E+10 | 0.214852E+10 | 0.227333E+11 | 0.00 | 0.762883E+10 | 0.77 | 0.00 | 0.326368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.250469E+10 | 0.255099E+10 | 0.234911E+11 | 0.00 | 0.778569E+10 | 0.79 | 0.00 | 0.174444E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247686E+10 | 0.275570E+10 | 0.227334E+11 | 0.00 | 0.752883E+10 | 0.77 | 0.00 | 12971086.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.256214E+10 | 0.301616E+10 | 0.234911E+11 | 0.00 | 0.805968E+10 | 0.79 | 0.00 | 846425.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293393E+11 | 0.270794E+11 | 0.276589E+12 | 0.00 | 0.932775E+11 | 9.37 | 0.00 | 0.303096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.228993E+10 | 0.158108E+10 | 0.212178E+11 | 0.00 | 0.737946E+10 | 0.72 | 0.00 | 242646.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.256214E+10 | 0.301616E+10 | 0.234913E+11 | 0.00 | 0.813742E+10 | 0.80 | 0.00 | 0.116674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.101627E+12 | 0.00 | 0.205307E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.968868E+11 | 0.00 | 0.187755E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.630178E+11 | 0.00 | 0.205645E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.281927E+11 | 0.00 | 0.191735E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.510277E+10 | 0.00 | 0.188044E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.777915E+09 | 0.00 | 0.172048E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 14999415.69 | 0.00 | 0.169882E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 47455897.85 | 0.00 | 0.167611E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.118744E+10 | 0.00 | 0.164611E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.165755E+11 | 0.00 | 0.177993E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.342858E+11 | 0.00 | 0.182109E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.915326E+11 | 0.00 | 0.197841E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.439249E+12 | 0.00 | 0.221058E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 14999415.69 | 0.00 | 0.164611E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.101627E+12 | 0.00 | 0.205645E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1654.77 | 02-JAN-16:49 | 2040.24 | 01-JAN-00:10 | 14413.88 | 01-JAN-11:09 | 0.00 | 3886.67 | 30-JAN-19:10 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 1654.77 | 01-FEB-17:19 | 2040.24 | 01-FEB-00:10 | 14413.88 | 01-FEB-11:09 | 0.00 | 3960.11 | 06-FEB-20:00 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 1654.77 | 01-MAR-17:49 | 2040.24 | 01-MAR-00:10 | 14413.88 | 01-MAR-11:09 | 0.00 | 3845.79 | 06-MAR-20:00 | 0.00 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 1654.77 | 01-APR-18:30 | 2040.24 | 01-APR-05:10 | 14413.88 | 01-APR-10:09 | 0.00 | 3648.79 | 16-APR-06:00 | 0.00 | 01-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 1654.77 | 01-MAY-19:10 | 2040.24 | 01-MAY-05:10 | 14413.88 | 01-MAY-10:09 | 0.00 | 3509.51 | 01-MAY-06:10 | 0.00 | 10-MAY-17:49 | 0.00 | 01-MAY-00:10 |
June | 1654.77 | 01-JUN-19:40 | 2040.24 | 01-JUN-19:49 | 14413.88 | 01-JUN-10:09 | 0.00 | 3660.97 | 27-JUN-12:00 | 0.00 | 01-JUN-11:39 | 0.00 | 01-JUN-00:10 |
July | 1654.77 | 01-JUL-19:40 | 2040.24 | 01-JUL-19:00 | 14413.88 | 01-JUL-10:09 | 0.00 | 3618.90 | 20-JUL-12:00 | 0.00 | 15-JUL-12:39 | 0.00 | 01-JUL-00:10 |
August | 1654.77 | 01-AUG-19:30 | 2040.24 | 01-AUG-19:40 | 14413.88 | 01-AUG-10:09 | 0.00 | 3631.94 | 10-AUG-11:00 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 1654.77 | 01-SEP-18:40 | 2040.24 | 01-SEP-05:10 | 14413.88 | 01-SEP-10:09 | 0.00 | 3430.40 | 30-SEP-06:10 | 0.00 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 1654.77 | 02-OCT-17:40 | 2040.24 | 01-OCT-05:10 | 14413.88 | 01-OCT-10:09 | 0.00 | 3597.03 | 17-OCT-06:10 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 1654.77 | 01-NOV-16:40 | 2040.24 | 01-NOV-05:10 | 14413.88 | 01-NOV-10:09 | 0.00 | 3632.74 | 22-NOV-20:00 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 1654.77 | 01-DEC-16:30 | 2040.24 | 01-DEC-00:10 | 14413.88 | 01-DEC-11:09 | 0.00 | 3953.87 | 11-DEC-19:00 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1654.77 | 2040.24 | 14413.88 | 0.00 | 3430.40 | 0.00 | 0.00 | ||||||
Maximum of Months | 1654.77 | 2040.24 | 14413.88 | 0.00 | 3960.11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 182.64 | 17-JAN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 148.32 | 17-FEB-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6118.83 | 14-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2121.88 | 08-APR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6297.49 | 10-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14556.67 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14238.49 | 20-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13179.55 | 10-AUG-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10670.03 | 15-SEP-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4059.87 | 11-OCT-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1471.35 | 27-NOV-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 440.32 | 01-DEC-04:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 148.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14556.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 23854.31 | 31-JAN-11:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3742.14 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23948.83 | 06-FEB-11:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3836.66 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26872.30 | 15-MAR-10:00 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3284.73 | 0.00 | 0.00 | 4939.60 | 0.00 |
April | 23640.30 | 14-APR-10:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3495.08 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25984.67 | 10-MAY-10:00 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3284.73 | 0.00 | 0.00 | 4039.66 | 0.00 |
June | 34924.41 | 27-JUN-11:09 | 1331.29 | 13514.13 | 0.00 | 0.00 | 3522.80 | 0.00 | 0.00 | 13617.37 | 0.00 |
July | 35281.51 | 20-JUL-11:09 | 1331.29 | 13514.13 | 0.00 | 0.00 | 3577.87 | 0.00 | 0.00 | 13917.65 | 0.00 |
August | 34350.08 | 15-AUG-10:20 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3284.73 | 0.00 | 0.00 | 10727.85 | 0.00 |
September | 31460.24 | 15-SEP-10:00 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3284.73 | 0.00 | 0.00 | 9495.51 | 0.00 |
October | 24420.60 | 22-OCT-10:20 | 1035.45 | 14413.88 | 0.00 | 0.00 | 3284.73 | 0.00 | 0.00 | 1178.44 | 0.00 |
November | 23647.07 | 22-NOV-11:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3519.93 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23868.08 | 11-DEC-11:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3754.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 23640.30 | 1035.45 | 13514.13 | 0.00 | 0.00 | 3284.73 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35281.51 | 1331.29 | 14413.88 | 0.00 | 0.00 | 3836.66 | 0.00 | 0.00 | 13917.65 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 79889.73 | 31-JAN-20:10 | 0.00 | 27969.69 | 31-JAN-13:50 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 89657.54 | 06-FEB-20:10 | 0.00 | 28004.29 | 13-FEB-13:30 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 77889.47 | 07-MAR-07:10 | 0.00 | 27974.01 | 01-MAR-13:00 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 52360.37 | 16-APR-06:00 | 0.00 | 27707.80 | 01-APR-12:39 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 30576.42 | 01-MAY-06:10 | 0.00 | 27220.66 | 01-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 13807.21 | 14-JUN-05:10 | 0.00 | 26536.08 | 02-JUN-12:20 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 2986.99 | 26-JUL-02:30 | 0.00 | 25934.58 | 01-JUL-12:39 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 2591.83 | 31-AUG-06:10 | 0.00 | 25513.39 | 02-AUG-12:39 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 15340.46 | 30-SEP-06:10 | 0.00 | 25904.95 | 30-SEP-12:20 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 45460.16 | 17-OCT-06:10 | 0.00 | 26534.39 | 30-OCT-12:20 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 47431.96 | 24-NOV-07:10 | 0.00 | 27196.59 | 30-NOV-13:00 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 89094.55 | 11-DEC-19:00 | 0.00 | 27700.81 | 31-DEC-13:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 2591.83 | 0.00 | 25513.39 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 89657.54 | 0.00 | 28004.29 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.17 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
February | 23.00 | 19.53 | 0.00 | 19.53 | 0.00 | 19.53 | 0.00 | 19.53 |
March | 16.67 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 |
April | 5.83 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
May | 0.50 | 20.52 | 0.00 | 20.52 | 0.17 | 21.51 | 0.00 | 21.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.59 | 0.00 | 24.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.53 | 0.00 | 24.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.53 | 0.00 | 24.53 |
October | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
November | 2.33 | 20.47 | 0.17 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
December | 21.83 | 19.71 | 0.00 | 19.71 | 0.00 | 19.71 | 0.00 | 19.71 |
Annual Sum or Average | 95.67 | 19.65 | 0.17 | 19.66 | 16.83 | 20.39 | 0.00 | 20.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.17 | 20.52 | 0.17 | 20.52 | 8.33 | 24.59 | 0.00 | 24.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.82 | 0.00 | 26.82 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.78 | 0.00 | 26.78 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.58 | 0.00 | 27.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.21 | 0.00 | 27.21 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.65 | 0.00 | 27.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 28.35 | 0.00 | 28.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 28.64 | 0.33 | 28.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.72 | 0.00 | 28.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 28.36 | 0.00 | 28.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.64 | 0.00 | 27.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.26 | 0.00 | 27.26 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 0.00 | 0.00 | 176.50 | 28.20 | 0.33 | 28.20 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.78 | 0.00 | 26.78 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 28.72 | 0.33 | 28.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.84 | 414.00 | 20.79 | 414.00 | 20.77 |
February | 551.00 | 20.84 | 369.33 | 20.79 | 369.33 | 20.77 |
March | 586.83 | 20.92 | 216.67 | 20.87 | 197.17 | 20.79 |
April | 581.00 | 21.10 | 93.83 | 20.93 | 93.83 | 20.81 |
May | 469.00 | 21.52 | 82.00 | 21.68 | 30.17 | 21.62 |
June | 280.83 | 22.65 | 381.50 | 23.33 | 129.33 | 23.40 |
July | 291.67 | 23.62 | 561.83 | 23.79 | 253.17 | 23.81 |
August | 233.17 | 23.22 | 507.67 | 23.66 | 155.00 | 23.70 |
September | 297.33 | 22.17 | 336.17 | 23.05 | 80.50 | 23.13 |
October | 528.67 | 21.15 | 88.50 | 21.30 | 30.33 | 21.18 |
November | 576.67 | 21.00 | 71.00 | 20.86 | 67.50 | 20.73 |
December | 609.00 | 20.85 | 309.67 | 20.77 | 309.67 | 20.73 |
Annual Sum or Average | 5615.17 | 21.38 | 3432.17 | 21.76 | 2130.00 | 21.71 |
Minimum of Months | 233.17 | 20.84 | 71.00 | 20.77 | 30.17 | 20.73 |
Maximum of Months | 610.00 | 23.62 | 561.83 | 23.79 | 414.00 | 23.81 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 18.74 | 476.33 | 18.71 | 476.33 | 18.70 |
February | 551.00 | 18.74 | 418.33 | 18.71 | 418.33 | 18.70 |
March | 586.83 | 19.20 | 350.67 | 19.26 | 335.83 | 19.23 |
April | 522.83 | 19.28 | 195.50 | 19.42 | 154.00 | 19.26 |
May | 374.33 | 21.64 | 310.17 | 22.86 | 122.17 | 23.07 |
June | 454.83 | 25.24 | 508.17 | 25.42 | 394.00 | 25.59 |
July | 556.50 | 26.03 | 599.00 | 25.96 | 552.67 | 26.00 |
August | 504.00 | 25.97 | 591.00 | 25.83 | 495.67 | 25.90 |
September | 411.00 | 24.69 | 468.00 | 25.00 | 318.83 | 25.25 |
October | 470.67 | 19.99 | 210.50 | 20.82 | 101.83 | 20.88 |
November | 540.17 | 19.04 | 172.00 | 19.26 | 130.83 | 19.15 |
December | 607.50 | 18.74 | 359.00 | 18.70 | 358.33 | 18.67 |
Annual Sum or Average | 6189.67 | 21.24 | 4658.67 | 21.83 | 3858.83 | 21.95 |
Minimum of Months | 374.33 | 18.74 | 172.00 | 18.70 | 101.83 | 18.67 |
Maximum of Months | 610.00 | 26.03 | 599.00 | 25.96 | 552.67 | 26.00 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.84319 | 19.92289 | -0.6299 | 14.28255 |
February | 551.00000 | 20.84450 | 20.09441 | -0.6308 | 14.33627 |
March | 612.00000 | 21.03927 | 29.30750 | -0.4599 | 11.40936 |
April | 590.00000 | 21.13562 | 35.25149 | -0.3617 | 9.30315 |
May | 611.00000 | 22.05369 | 41.85025 | -1.1088 | 33.94271 |
June | 592.00000 | 23.26906 | 51.99107 | -0.5284 | 14.19342 |
July | 609.00000 | 23.74486 | 61.08847 | -0.2578 | 7.37750 |
August | 612.00000 | 23.59407 | 55.74015 | -0.3338 | 8.96085 |
September | 590.00000 | 22.95517 | 52.40496 | -0.6020 | 16.52221 |
October | 610.00000 | 21.49219 | 41.14614 | -0.1536 | 7.68983 |
November | 591.00000 | 21.06863 | 33.09205 | -0.3702 | 9.14297 |
December | 609.00000 | 20.85151 | 23.75370 | -0.5777 | 12.93951 |
Annual Sum or Average | 7187.00000 | 21.91455 | 38.91277 | -0.5006 | 13.34688 |
Minimum of Months | 551.00000 | 20.84319 | 19.92289 | -1.1088 | 7.37750 |
Maximum of Months | 612.00000 | 23.74486 | 61.08847 | -0.1536 | 33.94271 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.73726 | 25.62253 | -0.7160 | 16.48264 |
February | 551.00000 | 18.74260 | 26.00349 | -0.7212 | 16.63863 |
March | 612.00000 | 19.37868 | 34.96724 | -0.5081 | 15.06978 |
April | 590.00000 | 19.79748 | 40.95179 | -0.3632 | 11.89164 |
May | 611.00000 | 22.56124 | 42.96479 | -0.6129 | 24.71155 |
June | 592.00000 | 24.92142 | 49.34190 | 0.26855 | 15.21730 |
July | 609.00000 | 25.83018 | 56.38399 | 0.65613 | 16.18782 |
August | 612.00000 | 25.56995 | 52.05577 | 0.54846 | 14.70516 |
September | 590.00000 | 24.32641 | 50.10856 | 0.10839 | 15.67349 |
October | 610.00000 | 20.79697 | 44.64272 | -0.0446 | 11.98811 |
November | 591.00000 | 19.45591 | 38.46391 | -0.4124 | 12.18458 |
December | 609.00000 | 18.75425 | 29.57575 | -0.6699 | 15.21854 |
Annual Sum or Average | 7187.00000 | 21.59085 | 41.00695 | -0.2024 | 15.50796 |
Minimum of Months | 551.00000 | 18.73726 | 25.62253 | -0.7212 | 11.89164 |
Maximum of Months | 612.00000 | 25.83018 | 56.38399 | 0.65613 | 24.71155 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.502596E+09 | 0.141359E+09 | 19.67 | 0.380712E+09 | 0.121885E+09 | 0.00 | 0.64 | 14-MAR-13:00 | 0.00 | 01-MAR-00:01 | 11643.88 | 14-MAR-13:00 | 8766.98 | 15-MAR-12:00 | 3619.66 | 14-MAR-13:00 | 3105.40 | 14-MAR-13:00 | 0.00 | 01-MAR-00:01 |
April | 16016426.40 | 4952093.39 | 4.33 | 13155859.61 | 2860566.79 | 0.00 | 0.18 | 08-APR-12:55 | 0.00 | 01-APR-00:01 | 2792.30 | 08-APR-12:55 | 2284.09 | 08-APR-13:00 | 508.21 | 08-APR-12:55 | 848.62 | 08-APR-12:55 | 0.00 | 01-APR-00:01 |
May | 0.102219E+10 | 0.297801E+09 | 71.36 | 0.823973E+09 | 0.198217E+09 | 0.00 | 1.00 | 24-MAY-00:21 | 0.00 | 01-MAY-00:01 | 39307.88 | 24-MAY-00:21 | 32737.60 | 24-MAY-00:21 | 6570.28 | 24-MAY-00:21 | 9592.17 | 24-MAY-00:21 | 0.00 | 01-MAY-00:01 |
June | 0.909488E+10 | 0.239840E+10 | 293.14 | 0.584152E+10 | 0.325337E+10 | 0.00 | 1.00 | 02-JUN-00:42 | 0.00 | 01-JUN-00:01 | 42691.54 | 18-JUN-00:11 | 26257.55 | 12-JUN-01:33 | 22667.48 | 18-JUN-00:11 | 9823.00 | 18-JUN-00:11 | 0.00 | 01-JUN-00:01 |
July | 0.200286E+11 | 0.511456E+10 | 504.02 | 0.118438E+11 | 0.818483E+10 | 0.00 | 1.00 | 02-JUL-01:22 | 0.00 | 01-JUL-00:01 | 43228.84 | 16-JUL-00:43 | 27047.90 | 08-JUL-01:22 | 25721.26 | 29-JUL-03:22 | 9861.41 | 16-JUL-00:43 | 0.00 | 01-JUL-00:01 |
August | 0.151123E+11 | 0.394696E+10 | 420.95 | 0.100823E+11 | 0.502994E+10 | 0.00 | 1.00 | 05-AUG-00:42 | 0.00 | 01-AUG-00:01 | 43342.35 | 14-AUG-00:43 | 27352.74 | 06-AUG-03:22 | 24506.76 | 14-AUG-00:43 | 9869.69 | 14-AUG-00:43 | 0.00 | 01-AUG-00:01 |
September | 0.532755E+10 | 0.144496E+10 | 224.79 | 0.332181E+10 | 0.200574E+10 | 0.00 | 1.00 | 09-SEP-00:42 | 0.00 | 01-SEP-00:01 | 42364.86 | 16-SEP-00:11 | 26561.46 | 17-SEP-02:62 | 25065.27 | 16-SEP-00:11 | 9800.17 | 16-SEP-00:11 | 0.00 | 01-SEP-00:01 |
October | 0.260995E+09 | 76827096.61 | 22.43 | 0.206947E+09 | 54048406.65 | 0.00 | 0.45 | 11-OCT-13:00 | 0.00 | 01-OCT-00:01 | 7609.99 | 11-OCT-13:00 | 6263.52 | 11-OCT-13:00 | 1977.50 | 23-OCT-01:19 | 2161.61 | 11-OCT-13:00 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.513652E+11 | 0.134258E+11 | 1560.69 | 0.325143E+11 | 0.188509E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.200286E+11 | 0.511456E+10 | 504.02 | 0.118438E+11 | 0.818483E+10 | 0.00 | 1.00 | 0.00 | 43342.35 | 32737.60 | 25721.26 | 9869.69 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 1275607.09 | 384678.17 | 0.47 | 1086818.66 | 188788.43 | 0.00 | 0.20 | 17-JAN-04:10 | 0.00 | 01-JAN-00:01 | 2475.95 | 17-JAN-04:10 | 2208.36 | 17-JAN-04:10 | 267.58 | 17-JAN-04:10 | 730.56 | 17-JAN-04:10 | 0.00 | 01-JAN-00:01 |
February | 796279.12 | 242646.47 | 0.36 | 650533.01 | 145746.12 | 0.00 | 0.09 | 17-FEB-04:27 | 0.00 | 01-FEB-00:01 | 1094.99 | 17-FEB-04:27 | 875.97 | 17-FEB-04:27 | 219.02 | 17-FEB-04:27 | 331.48 | 17-FEB-04:27 | 0.00 | 01-FEB-00:01 |
March | 0.608818E+09 | 0.158982E+09 | 21.81 | 0.506092E+09 | 0.102725E+09 | 0.00 | 1.00 | 14-MAR-03:52 | 0.00 | 01-MAR-00:01 | 30645.56 | 14-MAR-03:52 | 21627.52 | 16-MAR-03:22 | 15699.98 | 14-MAR-03:52 | 7347.25 | 14-MAR-03:52 | 0.00 | 01-MAR-00:01 |
April | 50802050.73 | 14940734.92 | 8.74 | 41837103.47 | 8964947.26 | 0.00 | 0.47 | 09-APR-00:15 | 0.00 | 01-APR-00:01 | 6323.75 | 09-APR-00:15 | 4015.95 | 08-APR-00:18 | 2827.09 | 09-APR-00:15 | 1742.99 | 09-APR-00:15 | 0.00 | 01-APR-00:01 |
May | 0.137018E+10 | 0.371042E+09 | 82.10 | 0.114635E+10 | 0.223830E+09 | 0.00 | 1.00 | 11-MAY-03:32 | 0.00 | 01-MAY-00:01 | 30645.56 | 29-MAY-04:01 | 25459.76 | 24-MAY-00:09 | 16241.09 | 11-MAY-03:32 | 7347.25 | 11-MAY-03:32 | 0.00 | 01-MAY-00:01 |
June | 0.125088E+11 | 0.303546E+10 | 321.67 | 0.813879E+10 | 0.437003E+10 | 0.00 | 1.00 | 01-JUN-01:22 | 0.00 | 01-JUN-00:01 | 34049.24 | 27-JUN-11:10 | 20500.24 | 27-JUN-12:23 | 19075.11 | 08-JUN-00:42 | 7721.40 | 27-JUN-12:55 | 0.00 | 01-JUN-00:01 |
July | 0.279292E+11 | 0.655281E+10 | 522.15 | 0.165211E+11 | 0.114080E+11 | 0.00 | 1.00 | 01-JUL-00:42 | 0.00 | 01-JUL-00:01 | 34049.24 | 16-JUL-02:11 | 22529.88 | 21-JUL-13:55 | 21684.64 | 29-JUL-03:45 | 7729.43 | 15-JUL-14:10 | 0.00 | 01-JUL-00:01 |
August | 0.200393E+11 | 0.481974E+10 | 439.03 | 0.136257E+11 | 0.641360E+10 | 0.00 | 1.00 | 01-AUG-00:04 | 0.00 | 01-AUG-00:01 | 34049.24 | 14-AUG-03:35 | 21226.21 | 20-AUG-00:42 | 21386.51 | 14-AUG-03:43 | 7578.64 | 14-AUG-00:03 | 0.00 | 01-AUG-00:01 |
September | 0.732175E+10 | 0.181871E+10 | 233.71 | 0.451446E+10 | 0.280729E+10 | 0.00 | 1.00 | 01-SEP-03:31 | 0.00 | 01-SEP-00:01 | 32914.95 | 16-SEP-00:03 | 20249.08 | 18-SEP-00:42 | 20420.38 | 16-SEP-00:03 | 7498.82 | 16-SEP-00:03 | 0.00 | 01-SEP-00:01 |
October | 0.353290E+09 | 97617324.32 | 26.71 | 0.278444E+09 | 74846077.38 | 0.00 | 1.00 | 01-OCT-03:32 | 0.00 | 01-OCT-00:01 | 30645.56 | 01-OCT-03:32 | 22468.30 | 22-OCT-03:32 | 15365.50 | 01-OCT-03:32 | 7347.25 | 01-OCT-03:32 | 0.00 | 01-OCT-00:01 |
November | 46161111.53 | 12971086.38 | 7.57 | 33686866.66 | 12474244.87 | 0.00 | 1.00 | 05-NOV-03:32 | 0.00 | 01-NOV-00:01 | 30645.56 | 05-NOV-03:32 | 23220.07 | 27-NOV-03:12 | 11727.05 | 05-NOV-03:32 | 7347.25 | 05-NOV-03:32 | 0.00 | 01-NOV-00:01 |
December | 2829046.41 | 846425.90 | 0.93 | 1830649.17 | 998397.25 | 0.00 | 0.27 | 01-DEC-04:08 | 0.00 | 01-DEC-00:01 | 3380.61 | 01-DEC-04:08 | 2026.15 | 01-DEC-04:08 | 1354.46 | 01-DEC-04:08 | 981.23 | 01-DEC-04:08 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.702331E+11 | 0.168838E+11 | 1665.26 | 0.448100E+11 | 0.254231E+11 | 0.00 | ||||||||||||||
Minimum of Months | 796279.12 | 242646.47 | 0.36 | 650533.01 | 145746.12 | 0.00 | 0.09 | 0.00 | 1094.99 | 875.97 | 219.02 | 331.48 | 0.00 | |||||||
Maximum of Months | 0.279292E+11 | 0.655281E+10 | 522.15 | 0.165211E+11 | 0.114080E+11 | 0.00 | 1.00 | 0.00 | 34049.24 | 25459.76 | 21684.64 | 7729.43 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.87 | 22.85 | 48.02 | 22.71 | 264.13 | 0.00 | 0.00 | 0.00 |
February | 103.99 | 31.21 | 72.79 | 41.69 | 248.24 | 0.00 | 0.00 | 0.00 |
March | 149.22 | 62.49 | 86.73 | 112.16 | 170.94 | 0.00 | 0.00 | 0.00 |
April | 197.51 | 87.27 | 110.24 | 185.80 | 115.49 | 0.00 | 0.00 | 0.00 |
May | 221.28 | 97.88 | 123.40 | 244.45 | 74.10 | 0.00 | 0.00 | 0.00 |
June | 247.13 | 109.22 | 137.91 | 302.87 | 51.01 | 0.00 | 0.00 | 0.00 |
July | 237.31 | 104.48 | 132.83 | 313.44 | 35.13 | 0.00 | 0.00 | 0.00 |
August | 214.32 | 89.96 | 124.36 | 274.30 | 48.03 | 0.00 | 0.00 | 0.00 |
September | 178.35 | 79.11 | 99.24 | 203.79 | 77.13 | 0.00 | 0.00 | 0.00 |
October | 121.03 | 50.06 | 70.97 | 104.66 | 122.47 | 0.00 | 0.00 | 0.00 |
November | 68.65 | 22.02 | 46.63 | 38.46 | 167.43 | 0.00 | 0.00 | 0.00 |
December | 55.26 | 11.42 | 43.85 | 11.01 | 261.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 155.64 | 64.15 | 91.49 | 155.23 | 135.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 55.26 | 11.42 | 43.85 | 11.01 | 35.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 247.13 | 109.22 | 137.91 | 313.44 | 264.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 333.07 | 194.42 | 138.65 | 254.38 | 486.32 | 0.00 | 0.00 | 0.00 |
February | 380.29 | 183.37 | 196.92 | 282.59 | 473.19 | 0.00 | 0.00 | 0.00 |
March | 464.16 | 260.81 | 203.35 | 447.94 | 331.72 | 0.00 | 0.00 | 0.00 |
April | 384.40 | 153.61 | 230.79 | 394.83 | 248.39 | 0.00 | 0.00 | 0.00 |
May | 336.38 | 97.70 | 238.68 | 379.22 | 159.73 | 0.00 | 0.00 | 0.00 |
June | 326.86 | 69.26 | 257.60 | 406.80 | 109.76 | 0.00 | 0.00 | 0.00 |
July | 333.67 | 80.96 | 252.71 | 462.81 | 75.09 | 0.00 | 0.00 | 0.00 |
August | 374.60 | 121.45 | 253.14 | 507.58 | 100.58 | 0.00 | 0.00 | 0.00 |
September | 435.55 | 212.14 | 223.40 | 541.84 | 160.18 | 0.00 | 0.00 | 0.00 |
October | 416.75 | 238.06 | 178.70 | 447.36 | 243.50 | 0.00 | 0.00 | 0.00 |
November | 298.47 | 168.50 | 129.97 | 276.14 | 322.35 | 0.00 | 0.00 | 0.00 |
December | 278.51 | 144.14 | 134.37 | 199.17 | 480.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 363.45 | 160.28 | 203.16 | 383.98 | 264.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 278.51 | 69.26 | 129.97 | 199.17 | 75.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 464.16 | 260.81 | 257.60 | 541.84 | 486.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.81 | 14.28 | 46.53 | 13.60 | 276.06 | 0.00 | 0.00 | 0.00 |
February | 98.55 | 25.33 | 73.22 | 35.03 | 257.29 | 0.00 | 0.00 | 0.00 |
March | 154.46 | 66.14 | 88.32 | 118.21 | 174.05 | 0.00 | 0.00 | 0.00 |
April | 189.12 | 77.55 | 111.57 | 176.88 | 120.40 | 0.00 | 0.00 | 0.00 |
May | 223.09 | 100.82 | 122.27 | 246.95 | 77.20 | 0.00 | 0.00 | 0.00 |
June | 269.17 | 126.61 | 142.56 | 332.61 | 53.43 | 0.00 | 0.00 | 0.00 |
July | 240.65 | 105.51 | 135.14 | 318.45 | 37.16 | 0.00 | 0.00 | 0.00 |
August | 217.65 | 92.55 | 125.10 | 281.02 | 49.60 | 0.00 | 0.00 | 0.00 |
September | 170.92 | 73.81 | 97.11 | 194.12 | 79.51 | 0.00 | 0.00 | 0.00 |
October | 110.80 | 39.03 | 71.77 | 92.16 | 126.99 | 0.00 | 0.00 | 0.00 |
November | 65.66 | 18.92 | 46.74 | 35.02 | 170.98 | 0.00 | 0.00 | 0.00 |
December | 56.92 | 12.40 | 44.52 | 12.63 | 265.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 155.07 | 62.93 | 92.15 | 155.38 | 140.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.92 | 12.40 | 44.52 | 12.63 | 37.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 269.17 | 126.61 | 142.56 | 332.61 | 276.06 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189824E+09 | 61209666.54 | 0.128614E+09 | 60832718.09 | 0.707459E+09 |
February | 0.251575E+09 | 75491251.28 | 0.176083E+09 | 0.100855E+09 | 0.600545E+09 |
March | 0.399682E+09 | 0.167384E+09 | 0.232298E+09 | 0.300399E+09 | 0.457834E+09 |
April | 0.511939E+09 | 0.226202E+09 | 0.285737E+09 | 0.481598E+09 | 0.299347E+09 |
May | 0.592674E+09 | 0.262171E+09 | 0.330503E+09 | 0.654737E+09 | 0.198480E+09 |
June | 0.640565E+09 | 0.283098E+09 | 0.357467E+09 | 0.785038E+09 | 0.132216E+09 |
July | 0.635614E+09 | 0.279852E+09 | 0.355763E+09 | 0.839505E+09 | 94087555.77 |
August | 0.574029E+09 | 0.240946E+09 | 0.333084E+09 | 0.734674E+09 | 0.128638E+09 |
September | 0.462283E+09 | 0.205050E+09 | 0.257232E+09 | 0.528232E+09 | 0.199918E+09 |
October | 0.324154E+09 | 0.134078E+09 | 0.190075E+09 | 0.280322E+09 | 0.328020E+09 |
November | 0.177935E+09 | 57079261.23 | 0.120855E+09 | 99681306.85 | 0.433981E+09 |
December | 0.148021E+09 | 30584329.08 | 0.117437E+09 | 29497755.49 | 0.699887E+09 |
Annual Sum or Average | 0.490829E+10 | 0.202315E+10 | 0.288515E+10 | 0.489537E+10 | 0.428041E+10 |
Minimum of Months | 0.148021E+09 | 30584329.08 | 0.117437E+09 | 29497755.49 | 94087555.77 |
Maximum of Months | 0.640565E+09 | 0.283098E+09 | 0.357467E+09 | 0.839505E+09 | 0.707459E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.892101E+09 | 0.520745E+09 | 0.371355E+09 | 0.681318E+09 | 0.130256E+10 |
February | 0.919986E+09 | 0.443609E+09 | 0.476377E+09 | 0.683644E+09 | 0.114475E+10 |
March | 0.124321E+10 | 0.698554E+09 | 0.544661E+09 | 0.119976E+10 | 0.888474E+09 |
April | 0.996366E+09 | 0.398150E+09 | 0.598216E+09 | 0.102341E+10 | 0.643839E+09 |
May | 0.900973E+09 | 0.261680E+09 | 0.639293E+09 | 0.101571E+10 | 0.427827E+09 |
June | 0.847215E+09 | 0.179529E+09 | 0.667687E+09 | 0.105442E+10 | 0.284492E+09 |
July | 0.893698E+09 | 0.216840E+09 | 0.676858E+09 | 0.123960E+10 | 0.201126E+09 |
August | 0.100332E+10 | 0.325302E+09 | 0.678021E+09 | 0.135950E+10 | 0.269385E+09 |
September | 0.112893E+10 | 0.549874E+09 | 0.579060E+09 | 0.140444E+10 | 0.415179E+09 |
October | 0.111623E+10 | 0.637611E+09 | 0.478618E+09 | 0.119822E+10 | 0.652182E+09 |
November | 0.773633E+09 | 0.436741E+09 | 0.336891E+09 | 0.715754E+09 | 0.835522E+09 |
December | 0.745973E+09 | 0.386075E+09 | 0.359898E+09 | 0.533467E+09 | 0.128704E+10 |
Annual Sum or Average | 0.114616E+11 | 0.505471E+10 | 0.640694E+10 | 0.121093E+11 | 0.835238E+10 |
Minimum of Months | 0.745973E+09 | 0.179529E+09 | 0.336891E+09 | 0.533467E+09 | 0.201126E+09 |
Maximum of Months | 0.124321E+10 | 0.698554E+09 | 0.678021E+09 | 0.140444E+10 | 0.130256E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.162865E+09 | 38234335.83 | 0.124631E+09 | 36431337.13 | 0.739401E+09 |
February | 0.238415E+09 | 61274412.09 | 0.177141E+09 | 84738734.93 | 0.622442E+09 |
March | 0.413710E+09 | 0.177141E+09 | 0.236569E+09 | 0.316609E+09 | 0.466163E+09 |
April | 0.490192E+09 | 0.200998E+09 | 0.289194E+09 | 0.458484E+09 | 0.312085E+09 |
May | 0.597535E+09 | 0.270047E+09 | 0.327488E+09 | 0.661438E+09 | 0.206765E+09 |
June | 0.697688E+09 | 0.328163E+09 | 0.369525E+09 | 0.862126E+09 | 0.138485E+09 |
July | 0.644552E+09 | 0.282593E+09 | 0.361959E+09 | 0.852934E+09 | 99522447.72 |
August | 0.582959E+09 | 0.247879E+09 | 0.335080E+09 | 0.752678E+09 | 0.132838E+09 |
September | 0.443036E+09 | 0.191327E+09 | 0.251708E+09 | 0.503149E+09 | 0.206092E+09 |
October | 0.296770E+09 | 0.104539E+09 | 0.192231E+09 | 0.246846E+09 | 0.340142E+09 |
November | 0.170194E+09 | 49043751.53 | 0.121150E+09 | 90780042.45 | 0.443177E+09 |
December | 0.152461E+09 | 33219513.83 | 0.119242E+09 | 33836329.04 | 0.711609E+09 |
Annual Sum or Average | 0.489038E+10 | 0.198446E+10 | 0.290592E+10 | 0.490005E+10 | 0.441872E+10 |
Minimum of Months | 0.152461E+09 | 33219513.83 | 0.119242E+09 | 33836329.04 | 99522447.72 |
Maximum of Months | 0.697688E+09 | 0.328163E+09 | 0.369525E+09 | 0.862126E+09 | 0.739401E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 255.27 | 991.10 | 464.75 | 231.55 | 233.20 | 0.00 | 0.00 |
February | 328.09 | 947.51 | 582.83 | 239.90 | 342.92 | 0.00 | 0.00 |
March | 644.06 | 642.46 | 767.85 | 389.44 | 378.41 | 0.00 | 0.00 |
April | 731.83 | 458.59 | 771.03 | 318.42 | 452.60 | 0.00 | 0.00 |
May | 854.97 | 295.37 | 780.76 | 296.41 | 484.35 | 0.00 | 0.00 |
June | 1030.72 | 202.64 | 843.16 | 305.09 | 538.07 | 0.00 | 0.00 |
July | 1088.46 | 141.14 | 811.63 | 290.95 | 520.68 | 0.00 | 0.00 |
August | 1056.56 | 191.87 | 806.57 | 303.96 | 502.61 | 0.00 | 0.00 |
September | 929.43 | 306.50 | 784.82 | 365.07 | 419.75 | 0.00 | 0.00 |
October | 634.07 | 482.85 | 648.58 | 327.15 | 321.43 | 0.00 | 0.00 |
November | 337.67 | 648.80 | 432.78 | 209.44 | 223.34 | 0.00 | 0.00 |
December | 194.69 | 979.38 | 390.70 | 167.97 | 222.74 | 0.00 | 0.00 |
Annual Sum or Average | 675.74 | 521.85 | 674.16 | 287.36 | 386.80 | 0.00 | 0.00 |
Minimum of Months | 194.69 | 141.14 | 390.70 | 167.97 | 222.74 | 0.00 | 0.00 |
Maximum of Months | 1088.46 | 991.10 | 843.16 | 389.44 | 538.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.683723E+09 | 0.265456E+10 | 0.124479E+10 | 0.620189E+09 | 0.624601E+09 | 0.00 | 0.00 |
February | 0.793720E+09 | 0.229222E+10 | 0.140998E+10 | 0.580374E+09 | 0.829601E+09 | 0.00 | 0.00 |
March | 0.172505E+10 | 0.172075E+10 | 0.205661E+10 | 0.104308E+10 | 0.101353E+10 | 0.00 | 0.00 |
April | 0.189689E+10 | 0.118868E+10 | 0.199850E+10 | 0.825350E+09 | 0.117315E+10 | 0.00 | 0.00 |
May | 0.228994E+10 | 0.791126E+09 | 0.209118E+10 | 0.793898E+09 | 0.129728E+10 | 0.00 | 0.00 |
June | 0.267164E+10 | 0.525245E+09 | 0.218547E+10 | 0.790789E+09 | 0.139468E+10 | 0.00 | 0.00 |
July | 0.291532E+10 | 0.378019E+09 | 0.217386E+10 | 0.779284E+09 | 0.139458E+10 | 0.00 | 0.00 |
August | 0.282989E+10 | 0.513896E+09 | 0.216031E+10 | 0.814127E+09 | 0.134618E+10 | 0.00 | 0.00 |
September | 0.240908E+10 | 0.794449E+09 | 0.203425E+10 | 0.946252E+09 | 0.108800E+10 | 0.00 | 0.00 |
October | 0.169830E+10 | 0.129325E+10 | 0.173715E+10 | 0.876229E+09 | 0.860924E+09 | 0.00 | 0.00 |
November | 0.875234E+09 | 0.168170E+10 | 0.112176E+10 | 0.542864E+09 | 0.578897E+09 | 0.00 | 0.00 |
December | 0.521449E+09 | 0.262318E+10 | 0.104646E+10 | 0.449879E+09 | 0.596577E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.213102E+11 | 0.164571E+11 | 0.212603E+11 | 0.906231E+10 | 0.121980E+11 | 0.00 | 0.00 |
Minimum of Months | 0.521449E+09 | 0.378019E+09 | 0.104646E+10 | 0.449879E+09 | 0.578897E+09 | 0.00 | 0.00 |
Maximum of Months | 0.291532E+10 | 0.265456E+10 | 0.218547E+10 | 0.104308E+10 | 0.139468E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.150308E+11 | -0.142325E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -798335588.0 | 58.99 | 0.00 | 0.00 |
February | 0.137639E+11 | -0.130421E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -721809151.7 | 58.99 | 0.00 | 0.00 |
March | 0.150574E+11 | -0.142717E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -785702625.5 | 58.99 | 0.00 | 0.00 |
April | 0.139827E+11 | -0.132312E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -751490351.6 | 58.99 | 0.00 | 0.00 |
May | 0.136329E+11 | -0.129066E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -726298835.0 | 58.99 | 0.00 | 0.00 |
June | 0.123921E+11 | -0.117290E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -663145289.9 | 58.99 | 0.00 | 0.00 |
July | 0.121682E+11 | -0.114990E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -669194178.5 | 58.99 | 0.00 | 0.00 |
August | 0.119839E+11 | -0.113104E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -673561946.8 | 58.99 | 0.00 | 0.00 |
September | 0.117898E+11 | -0.111170E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -672713795.1 | 58.98 | 0.00 | 0.00 |
October | 0.128248E+11 | -0.120680E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -756780098.5 | 58.99 | 0.00 | 0.00 |
November | 0.132063E+11 | -0.124502E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -756056723.7 | 58.99 | 0.00 | 0.00 |
December | 0.144274E+11 | -0.136306E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -796820608.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.160260E+12 | -0.151488E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.877191E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.117898E+11 | -0.142717E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -798335588.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.150574E+11 | -0.111170E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -663145289.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.57 | 0.56 | 01-JAN-08:39 | 2871.16 | 25.38 | 142.17 | 260.33 | 2853.80 | 25.18 | 142.00 | 261.33 |
February | 262.50 | 0.57 | 0.56 | 01-FEB-08:50 | 4000.43 | 27.24 | 176.67 | 262.67 | 3870.65 | 27.07 | 174.83 | 262.67 |
March | 339.33 | 0.57 | 0.56 | 01-MAR-07:40 | 2250.74 | 18.73 | 42.33 | 338.50 | 2264.50 | 18.82 | 41.50 | 338.50 |
April | 371.17 | 0.57 | 0.56 | 01-APR-06:30 | 1979.65 | 16.08 | 0.00 | 364.50 | 2540.52 | 17.79 | 38.33 | 363.67 |
May | 332.17 | 0.57 | 0.56 | 01-MAY-05:49 | 2701.59 | 16.08 | 0.00 | 410.83 | 2149.40 | 16.09 | 0.00 | 414.17 |
June | 430.67 | 0.57 | 0.56 | 01-JUN-05:40 | 2724.11 | 15.88 | 0.00 | 416.17 | 2245.72 | 15.97 | 0.00 | 417.83 |
July | 439.00 | 0.57 | 0.56 | 01-JUL-05:19 | 2489.72 | 15.95 | 0.00 | 422.17 | 1954.25 | 16.01 | 0.00 | 423.83 |
August | 406.00 | 0.57 | 0.56 | 01-AUG-05:49 | 2562.14 | 16.49 | 1.50 | 400.17 | 2620.74 | 16.51 | 3.50 | 397.00 |
September | 289.17 | 0.57 | 0.56 | 01-SEP-07:40 | 2535.93 | 19.85 | 53.00 | 341.17 | 3148.91 | 20.03 | 58.50 | 344.00 |
October | 314.33 | 0.57 | 0.56 | 01-OCT-06:00 | 5171.02 | 29.33 | 242.50 | 306.83 | 4683.77 | 28.41 | 231.83 | 307.17 |
November | 258.33 | 0.58 | 0.56 | 01-NOV-07:40 | 3043.80 | 27.26 | 182.17 | 249.83 | 3023.55 | 27.16 | 180.83 | 249.00 |
December | 230.67 | 0.57 | 0.56 | 01-DEC-07:00 | 2179.39 | 22.45 | 103.00 | 246.83 | 2177.36 | 22.50 | 103.00 | 248.50 |
Annual Sum or Average | 3928.50 | 0.57 | 2833.86 | 20.11 | 943.33 | 4020.00 | 2730.00 | 20.21 | 974.33 | 4027.67 | ||
Minimum of Months | 230.67 | 0.57 | 0.56 | 1979.65 | 15.88 | 0.00 | 246.83 | 1954.25 | 15.97 | 0.00 | 248.50 | |
Maximum of Months | 439.00 | 0.58 | 0.56 | 5171.02 | 29.33 | 242.50 | 422.17 | 4683.77 | 28.41 | 231.83 | 423.83 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.397915E+11 | 55376.50 | 04-JAN-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.376299E+11 | 55376.50 | 03-FEB-03:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.256179E+11 | 55376.50 | 01-MAR-03:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127973E+11 | 45708.44 | 16-APR-02:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.313807E+10 | 12064.17 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.528390E+09 | 7343.99 | 10-JUN-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11999532.55 | 4779.19 | 26-JUL-02:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 37964718.28 | 2399.22 | 31-AUG-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.808523E+09 | 7818.33 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.824087E+10 | 24116.90 | 17-OCT-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154210E+11 | 33015.77 | 24-NOV-03:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.359672E+11 | 55376.50 | 07-DEC-03:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179991E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11999532.55 | 2399.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.397915E+11 | 55376.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.415102E+11 | 51054.42 | 10-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.398795E+11 | 48012.42 | 06-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.247964E+11 | 49734.39 | 07-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.975692E+10 | 30763.41 | 17-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.944144E+09 | 16497.79 | 01-MAY-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 93942268.68 | 8340.38 | 14-JUN-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141426E+09 | 7136.87 | 30-SEP-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.501957E+10 | 22542.86 | 18-OCT-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120077E+11 | 22804.60 | 25-NOV-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.372589E+11 | 48327.35 | 12-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171409E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.415102E+11 | 51054.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.502596E+09 | 0.380712E+09 | 11643.88 | 14-MAR-13:00 | 8024.22 | 0.00 |
April | 0.00 | 0.00 | 16016426.40 | 13155859.61 | 2792.30 | 08-APR-12:55 | 2284.09 | 0.00 |
May | 0.00 | 0.00 | 0.102219E+10 | 0.823973E+09 | 39307.88 | 24-MAY-00:21 | 32737.60 | 0.00 |
June | 0.00 | 0.00 | 0.909488E+10 | 0.584152E+10 | 42691.54 | 18-JUN-00:11 | 20024.05 | 0.00 |
July | 0.00 | 0.00 | 0.200286E+11 | 0.118438E+11 | 43228.84 | 16-JUL-00:43 | 19759.69 | 0.00 |
August | 0.00 | 0.00 | 0.151123E+11 | 0.100823E+11 | 43342.35 | 14-AUG-00:43 | 18835.58 | 0.00 |
September | 0.00 | 0.00 | 0.532755E+10 | 0.332181E+10 | 42364.86 | 16-SEP-00:11 | 17299.60 | 0.00 |
October | 0.00 | 0.00 | 0.260995E+09 | 0.206947E+09 | 7609.99 | 11-OCT-13:00 | 6263.52 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.513652E+11 | 0.325143E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.200286E+11 | 0.118438E+11 | 43342.35 | 32737.60 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1275607.09 | 1086818.66 | 2475.95 | 17-JAN-04:10 | 2208.36 | 0.00 |
February | 0.00 | 0.00 | 796279.12 | 650533.01 | 1094.99 | 17-FEB-04:27 | 875.97 | 0.00 |
March | 0.00 | 0.00 | 0.608818E+09 | 0.506092E+09 | 30645.56 | 14-MAR-03:52 | 14945.58 | 0.00 |
April | 0.00 | 0.00 | 50802050.73 | 41837103.47 | 6323.75 | 09-APR-00:15 | 3496.66 | 0.00 |
May | 0.00 | 0.00 | 0.137018E+10 | 0.114635E+10 | 30645.56 | 29-MAY-04:01 | 15129.77 | 0.00 |
June | 0.00 | 0.00 | 0.125088E+11 | 0.813879E+10 | 34049.24 | 27-JUN-11:10 | 19106.50 | 0.00 |
July | 0.00 | 0.00 | 0.279292E+11 | 0.165211E+11 | 34049.24 | 16-JUL-02:11 | 13135.68 | 0.00 |
August | 0.00 | 0.00 | 0.200393E+11 | 0.136257E+11 | 34049.24 | 14-AUG-03:35 | 12748.62 | 0.00 |
September | 0.00 | 0.00 | 0.732175E+10 | 0.451446E+10 | 32914.95 | 16-SEP-00:03 | 12494.58 | 0.00 |
October | 0.00 | 0.00 | 0.353290E+09 | 0.278444E+09 | 30645.56 | 01-OCT-03:32 | 15280.06 | 0.00 |
November | 0.00 | 0.00 | 46161111.53 | 33686866.66 | 30645.56 | 05-NOV-03:32 | 18918.51 | 0.00 |
December | 0.00 | 0.00 | 2829046.41 | 1830649.17 | 3380.61 | 01-DEC-04:08 | 2026.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.702331E+11 | 0.448100E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 796279.12 | 650533.01 | 1094.99 | 875.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.279292E+11 | 0.165211E+11 | 34049.24 | 19106.50 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5607.52 | 21033.91 | 31-JAN-13:40 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 5684.77 | 21109.12 | 14-FEB-13:20 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5623.86 | 21040.47 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5396.70 | 20444.57 | 01-APR-12:58 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5111.56 | 19428.93 | 01-MAY-12:28 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 4818.41 | 18212.41 | 01-JUN-12:20 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4583.48 | 17192.09 | 01-JUL-12:32 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4516.79 | 16577.71 | 01-AUG-13:00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 4580.05 | 17139.51 | 30-SEP-12:40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4797.37 | 18180.17 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 5096.71 | 19357.63 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5381.16 | 20420.17 | 31-DEC-13:30 |
Annual Sum or Average | 0.00 | 5096.45 | ||||
Minimum of Months | 0.00 | 0.00 | 4516.79 | 16577.71 | ||
Maximum of Months | 0.00 | 0.00 | 5684.77 | 21109.12 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | -0.0 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271853E+10 | 0.55 | 1211.87 | 01-JAN-00:01 | 0.66 |
February | 0.244883E+10 | 0.55 | 1211.87 | 01-FEB-00:01 | 0.66 |
March | 0.277176E+10 | 0.56 | 1211.87 | 01-MAR-00:01 | 0.66 |
April | 0.271410E+10 | 0.56 | 1211.87 | 01-APR-04:01 | 0.65 |
May | 0.302139E+10 | 0.61 | 1211.87 | 01-MAY-02:50 | 0.65 |
June | 0.299605E+10 | 0.62 | 1211.87 | 01-JUN-00:07 | 0.65 |
July | 0.310325E+10 | 0.62 | 1211.87 | 01-JUL-00:06 | 0.65 |
August | 0.310211E+10 | 0.62 | 1211.87 | 01-AUG-00:04 | 0.65 |
September | 0.299692E+10 | 0.62 | 1211.87 | 01-SEP-00:12 | 0.65 |
October | 0.296288E+10 | 0.59 | 1211.87 | 01-OCT-00:14 | 0.65 |
November | 0.274645E+10 | 0.57 | 1211.87 | 01-NOV-01:25 | 0.65 |
December | 0.272526E+10 | 0.55 | 1211.87 | 01-DEC-00:01 | 0.65 |
Annual Sum or Average | 0.343075E+11 | 0.58 | |||
Minimum of Months | 0.244883E+10 | 0.55 | 1211.87 | 0.65 | |
Maximum of Months | 0.310325E+10 | 0.62 | 1211.87 | 0.66 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.232692E+10 | 0.62 | 1719.70 | 04-JAN-03:10 | 0.91 |
February | 0.213832E+10 | 0.62 | 1719.70 | 03-FEB-03:15 | 0.90 |
March | 0.204142E+10 | 0.57 | 1719.70 | 01-MAR-03:08 | 0.90 |
April | 0.172896E+10 | 0.53 | 1419.46 | 16-APR-02:61 | 0.90 |
May | 0.159434E+10 | 0.47 | 912.67 | 01-MAY-06:03 | 0.65 |
June | 0.151081E+10 | 0.47 | 1066.10 | 27-JUN-13:00 | 0.70 |
July | 0.158946E+10 | 0.49 | 1022.85 | 20-JUL-12:55 | 0.69 |
August | 0.157346E+10 | 0.50 | 1035.09 | 10-AUG-12:00 | 0.69 |
September | 0.151369E+10 | 0.47 | 833.56 | 30-SEP-06:10 | 0.61 |
October | 0.169028E+10 | 0.49 | 1037.73 | 24-OCT-09:20 | 0.70 |
November | 0.177650E+10 | 0.53 | 1078.71 | 18-NOV-05:06 | 0.72 |
December | 0.224179E+10 | 0.61 | 1719.70 | 07-DEC-03:07 | 0.90 |
Annual Sum or Average | 0.217259E+11 | 0.53 | |||
Minimum of Months | 0.151081E+10 | 0.47 | 833.56 | 0.61 | |
Maximum of Months | 0.232692E+10 | 0.62 | 1719.70 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.309197E+10 | 0.78 | 1384.97 | 01-JAN-14:40 | 0.93 |
February | 0.279231E+10 | 0.78 | 1384.97 | 01-FEB-05:09 | 0.93 |
March | 0.310420E+10 | 0.79 | 1384.97 | 01-MAR-00:20 | 0.94 |
April | 0.300134E+10 | 0.80 | 1384.97 | 01-APR-07:17 | 0.93 |
May | 0.314669E+10 | 0.86 | 1384.97 | 01-MAY-04:45 | 0.93 |
June | 0.314134E+10 | 0.87 | 1384.97 | 02-JUN-06:10 | 0.92 |
July | 0.331980E+10 | 0.86 | 1384.97 | 01-JUL-09:23 | 0.92 |
August | 0.329710E+10 | 0.87 | 1384.97 | 01-AUG-09:43 | 0.92 |
September | 0.311823E+10 | 0.87 | 1384.97 | 01-SEP-13:28 | 0.93 |
October | 0.313253E+10 | 0.84 | 1384.97 | 02-OCT-05:10 | 0.93 |
November | 0.300588E+10 | 0.81 | 1384.97 | 01-NOV-04:10 | 0.93 |
December | 0.309264E+10 | 0.78 | 1384.97 | 01-DEC-22:10 | 0.93 |
Annual Sum or Average | 0.372440E+11 | 0.83 | |||
Minimum of Months | 0.279231E+10 | 0.78 | 1384.97 | 0.92 | |
Maximum of Months | 0.331980E+10 | 0.87 | 1384.97 | 0.94 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 49.73 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 51.16 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 51.09 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 51.40 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:05 | 0.00 | 0.00 | 49.12 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 51.96 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:03 | 0.00 | 0.00 | 52.22 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 53.00 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 53.08 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 51.47 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 52.28 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 51.66 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 49.12 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 53.08 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 37.13 | 37.13 | 5607.52 | 21033.91 | 31-JAN-13:40 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 51.50 | 51.50 | 5684.77 | 21109.12 | 14-FEB-13:20 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 51.25 | 51.25 | 5623.86 | 21040.47 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.58 | 51.58 | 5396.70 | 20444.57 | 01-APR-12:58 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 38.17 | 38.17 | 5111.56 | 19428.93 | 01-MAY-12:28 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 52.03 | 52.03 | 4818.41 | 18212.41 | 01-JUN-12:20 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 52.47 | 52.47 | 4583.48 | 17192.09 | 01-JUL-12:32 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.77 | 52.77 | 4516.79 | 16577.71 | 01-AUG-13:00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.91 | 52.91 | 4580.05 | 17139.51 | 30-SEP-12:40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 40.72 | 40.72 | 4797.37 | 18180.17 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.26 | 52.26 | 5096.71 | 19357.63 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 51.78 | 51.78 | 5381.16 | 20420.17 | 31-DEC-13:30 |
Annual Sum or Average | 0.00 | 5096.45 | ||||||
Minimum of Months | 0.00 | 0.00 | 37.13 | 37.13 | 4516.79 | 16577.71 | ||
Maximum of Months | 0.00 | 0.00 | 52.91 | 52.91 | 5684.77 | 21109.12 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.232692E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.213832E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.218278E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.173391E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.189214E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.390921E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.670401E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.552042E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.295865E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.176711E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.177650E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.224179E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.351518E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.173391E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.670401E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.309235E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.279255E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.326318E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.301628E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.351773E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.617680E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.987261E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.811684E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.493694E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.323015E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.301885E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.309348E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.541278E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.279255E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.987261E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.232692E+10 | 0.00 | 0.397915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.213832E+10 | 0.00 | 0.376299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204142E+10 | 0.502596E+09 | 0.256179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172896E+10 | 16016426.40 | 0.127973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159434E+10 | 0.102139E+10 | 0.313807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151081E+10 | 0.905493E+10 | 0.528390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158946E+10 | 0.198998E+11 | 11999532.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157346E+10 | 0.150168E+11 | 37964718.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151369E+10 | 0.528836E+10 | 0.808523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169028E+10 | 0.260995E+09 | 0.824087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177650E+10 | 0.00 | 0.154210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224179E+10 | 0.00 | 0.359672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217259E+11 | 0.510608E+11 | 0.179991E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151081E+10 | 0.00 | 11999532.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.232692E+10 | 0.198998E+11 | 0.397915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.309197E+10 | 1275607.09 | 0.415102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.279231E+10 | 796279.12 | 0.398795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.310420E+10 | 0.608818E+09 | 0.247964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.300134E+10 | 50802050.73 | 0.975692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.314669E+10 | 0.137018E+10 | 0.944144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.314134E+10 | 0.125088E+11 | 93942268.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.331980E+10 | 0.279292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.329710E+10 | 0.200393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.311823E+10 | 0.732175E+10 | 0.141426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.313253E+10 | 0.353290E+09 | 0.501957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.300588E+10 | 46161111.53 | 0.120077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.309264E+10 | 2829046.41 | 0.372589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.372440E+11 | 0.702331E+11 | 0.171409E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.279231E+10 | 796279.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.331980E+10 | 0.279292E+11 | 0.415102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.232692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.213832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204142E+10 | 0.00 | 0.00 | 0.00 | 0.141359E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172896E+10 | 0.00 | 0.00 | 0.00 | 4952093.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159434E+10 | 0.00 | 0.00 | 0.00 | 0.297801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151081E+10 | 0.00 | 0.00 | 0.00 | 0.239840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158946E+10 | 0.00 | 0.00 | 0.00 | 0.511456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157346E+10 | 0.00 | 0.00 | 0.00 | 0.394696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151369E+10 | 0.00 | 0.00 | 0.00 | 0.144496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169028E+10 | 0.00 | 0.00 | 0.00 | 76827096.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217259E+11 | 0.00 | 0.00 | 0.00 | 0.134258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.232692E+10 | 0.00 | 0.00 | 0.00 | 0.511456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.309197E+10 | 0.00 | 0.00 | 0.00 | 384678.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.279231E+10 | 0.00 | 0.00 | 0.00 | 242646.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.310420E+10 | 0.00 | 0.00 | 0.00 | 0.158982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.300134E+10 | 0.00 | 0.00 | 0.00 | 14940734.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.314669E+10 | 0.00 | 0.00 | 0.00 | 0.371042E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.314134E+10 | 0.00 | 0.00 | 0.00 | 0.303546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.331980E+10 | 0.00 | 0.00 | 0.00 | 0.655281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.329710E+10 | 0.00 | 0.00 | 0.00 | 0.481974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.311823E+10 | 0.00 | 0.00 | 0.00 | 0.181871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.313253E+10 | 0.00 | 0.00 | 0.00 | 97617324.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.300588E+10 | 0.00 | 0.00 | 0.00 | 12971086.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.309264E+10 | 0.00 | 0.00 | 0.00 | 846425.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.372440E+11 | 0.00 | 0.00 | 0.00 | 0.168838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.279231E+10 | 0.00 | 0.00 | 0.00 | 242646.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.331980E+10 | 0.00 | 0.00 | 0.00 | 0.655281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.144011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313959E+11 | 0.00 | 0.00 | 3.62 |
February | 0.129091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294741E+11 | 0.00 | 0.00 | 3.63 |
March | 0.323663E+10 | 6972732.16 | 0.00 | 1418767.77 | 0.00 | 0.211459E+11 | 0.208647E+09 | 0.00 | 3.63 |
April | 0.606123E+10 | 0.00 | 0.00 | 520688.13 | 0.00 | 0.104818E+11 | 0.414869E+09 | 0.00 | 3.63 |
May | 0.775411E+10 | 24592726.72 | 0.00 | 7252722.56 | 0.00 | 0.148736E+10 | 0.253944E+10 | 0.00 | 3.93 |
June | 0.323591E+10 | 0.102874E+10 | 0.00 | 18494847.34 | 1458028.24 | 27759205.17 | 0.426260E+10 | 975.63 | 4.66 |
July | 0.816361E+09 | 0.318305E+10 | 676715.10 | 17431180.83 | 596151.20 | 0.00 | 0.284324E+10 | 8495.07 | 5.06 |
August | 0.162435E+10 | 0.175511E+10 | 101988.93 | 23984852.04 | 0.00 | 0.00 | 0.405629E+10 | 699.47 | 4.89 |
September | 0.473126E+10 | 0.280135E+09 | 0.00 | 18983350.43 | 0.00 | 0.127427E+09 | 0.481710E+10 | 0.00 | 4.70 |
October | 0.887768E+10 | 0.00 | 0.00 | 3394322.60 | 0.00 | 0.520485E+10 | 0.158715E+10 | 0.00 | 3.73 |
November | 0.554805E+10 | 0.00 | 0.00 | 314842.85 | 0.00 | 0.126603E+11 | 0.327811E+09 | 0.00 | 3.60 |
December | 0.155645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289581E+11 | 0.00 | 0.00 | 3.63 |
Annual Sum or Average | 0.461730E+11 | 0.627861E+10 | 778704.02 | 91795574.56 | 2054179.44 | 0.140963E+12 | 0.210571E+11 | 10170.18 | 4.06 |
Minimum of Months | 0.816361E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 |
Maximum of Months | 0.887768E+10 | 0.318305E+10 | 676715.10 | 23984852.04 | 1458028.24 | 0.313959E+11 | 0.481710E+10 | 8495.07 | 5.06 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.755607E+11 | 0.00 | 0.00 | 134079.04 | 0.00 | 50414681.92 | 62164243.45 | 0.00 | 9.64 |
February | 0.704782E+11 | 0.00 | 0.00 | 57496.29 | 0.00 | 49611889.47 | 36096549.76 | 0.00 | 9.65 |
March | 0.570655E+11 | 0.00 | 0.00 | 4562081.35 | 0.00 | 26297749.34 | 0.193278E+10 | 0.00 | 9.70 |
April | 0.410812E+11 | 0.00 | 0.00 | 2909181.18 | 0.00 | 9087569.56 | 0.309837E+10 | 0.00 | 9.79 |
May | 0.211981E+11 | 199187.32 | 0.00 | 24569749.83 | 0.00 | 0.00 | 0.144363E+11 | 0.00 | 10.14 |
June | 0.700805E+10 | 0.103163E+10 | 0.00 | 62217530.37 | 0.00 | 0.00 | 0.177382E+11 | 0.00 | 10.89 |
July | 0.170414E+10 | 0.396014E+10 | 0.00 | 69228069.37 | 0.00 | 0.00 | 0.120849E+11 | 0.00 | 11.38 |
August | 0.239132E+10 | 0.164078E+10 | 0.00 | 79008804.04 | 0.00 | 0.00 | 0.174942E+11 | 0.00 | 11.16 |
September | 0.953346E+10 | 0.139156E+09 | 0.00 | 55043175.76 | 0.00 | 0.00 | 0.201269E+11 | 0.00 | 10.71 |
October | 0.336018E+11 | 0.00 | 0.00 | 12007053.68 | 0.00 | 1970173.74 | 0.858418E+10 | 0.00 | 9.92 |
November | 0.443123E+11 | 0.00 | 0.00 | 2977739.45 | 0.00 | 1877641.62 | 0.308618E+10 | 0.00 | 9.78 |
December | 0.717580E+11 | 0.00 | 0.00 | 247801.23 | 0.00 | 35038825.92 | 0.175142E+09 | 0.00 | 9.69 |
Annual Sum or Average | 0.435693E+12 | 0.677189E+10 | 0.00 | 0.312963E+09 | 0.00 | 0.174299E+09 | 0.988554E+11 | 0.00 | 10.21 |
Minimum of Months | 0.170414E+10 | 0.00 | 0.00 | 57496.29 | 0.00 | 0.00 | 36096549.76 | 0.00 | 9.64 |
Maximum of Months | 0.755607E+11 | 0.396014E+10 | 0.00 | 79008804.04 | 0.00 | 50414681.92 | 0.201269E+11 | 0.00 | 11.38 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.135486E+11 | 0.208765E+11 | 0.138960E+12 | 0.00 | 0.350613E+11 |
February | 0.246945E+11 | 0.198025E+11 | 0.129040E+12 | 0.00 | 0.339176E+11 |
March | 0.403388E+11 | 0.163121E+11 | 0.110167E+12 | 0.110216E+09 | 0.329494E+11 |
April | 0.507225E+11 | 0.121983E+11 | 0.851167E+11 | 96479414.35 | 0.258713E+11 |
May | 0.645003E+11 | 0.856786E+10 | 0.711184E+11 | 0.885311E+09 | 0.285487E+11 |
June | 0.716276E+11 | 0.470750E+10 | 0.454570E+11 | 0.193246E+10 | 0.541178E+11 |
July | 0.669895E+11 | 0.780198E+09 | 0.188224E+11 | 0.139305E+10 | 0.887904E+11 |
August | 0.565884E+11 | 0.253011E+10 | 0.343635E+11 | 0.191239E+10 | 0.721598E+11 |
September | 0.415383E+11 | 0.564227E+10 | 0.573735E+11 | 0.214197E+10 | 0.409481E+11 |
October | 0.259922E+11 | 0.105075E+11 | 0.838903E+11 | 0.449561E+09 | 0.229394E+11 |
November | 0.117506E+11 | 0.126680E+11 | 0.921632E+11 | 54377648.50 | 0.215718E+11 |
December | 0.119111E+11 | 0.199082E+11 | 0.132809E+12 | 0.00 | 0.323651E+11 |
Annual Sum or Average | 0.480202E+12 | 0.134501E+12 | 0.999280E+12 | 0.897581E+10 | 0.489241E+12 |
Minimum of Months | 0.117506E+11 | 0.780198E+09 | 0.188224E+11 | 0.00 | 0.215718E+11 |
Maximum of Months | 0.716276E+11 | 0.208765E+11 | 0.138960E+12 | 0.214197E+10 | 0.887904E+11 |