Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 08:25:25
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2341.82 | 10079.16 | 10079.16 |
Net Site Energy | 2341.82 | 10079.16 | 10079.16 |
Total Source Energy | 3607.40 | 15526.17 | 15526.17 |
Net Source Energy | 3607.40 | 15526.17 | 15526.17 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1090.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 29.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 276.59 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 112.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 260.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 61.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 513.14 | 1828.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1090.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 6.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 29.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 27.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 112.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 260.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 27.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1090.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 6.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 29.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 27.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 276.59 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 112.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 260.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 61.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 245.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 509.37 | 5816.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1453.62 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2208.53 | 7870.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 245.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 509.37 | 5816.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1453.62 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2208.53 | 7870.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 513.136 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 513.136 | 100.00 |
Total On-Site and Utility Electric Sources | 513.136 | 100.00 |
Total Electricity End Uses | 513.136 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4514.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 7.5044 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.8503 | 18.52 | 1074.0064 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.6773 | 2.48 | 595.3967 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.6773 | 2.48 | 595.3967 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 7.5044 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.8503 | 18.52 | 1074.0064 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 8.6773 | 1.24 | 595.3967 | |||||||
Conditioned Total | 232.34 | 8.6773 | 1.24 | 595.3967 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 8.6773 | 2.48 | 595.3967 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-10:20 | 12-JAN-13:20 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 152641.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4467.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1183.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14413.88 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4158.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 33359.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 4547.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28771.23 | 208984.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 152641.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 4467.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1183.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 13046.29 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 4158.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 33359.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 3497.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1049.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1182.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 94.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 86.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 875.96 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 355.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 282.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 193.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1625.10 | 1982.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 5088.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 82.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 372.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3770.11 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1530.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1217.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 833.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6994.41 | 8531.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 5088.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 82.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 372.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3770.11 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1530.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1217.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 833.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6994.41 | 8531.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.48 |
KITCHEN DIRECT AIR | 1.23 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.48 | 1.48 | 1.48 | 1.48 | 1.48 | 1.48 | 1.00 | 1.000000 | 1.48 |
PSZ-AC_2:2 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.00 | 1.00 | 1.23 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.48 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.23 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.48 | 1588.90 |
PSZ-AC_2:2_ADDAQ FAN | 1.23 | 1358.05 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.48 | 1.48 | 1.48 | 1.48 | 27433.75 | 64779.58 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.23 | 1.23 | 1.23 | 1.23 | 22744.02 | 113672.25 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.48 | 0.742443 | 0.989927 | 27433.75 | 13716.88 | 0.800410 | 0.800410 |
PSZ-AC_2:2 COOLING COIL | 1.23 | 0.613304 | 0.817740 | 22744.02 | 11372.01 | 0.800220 | 0.800220 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 64779.58 |
PSZ-AC_2:2 HEATING COIL | 113672.25 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 7.504 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 124.291 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.850 | 282.654 | 791.353 | 0.000 | 0.000 | 0.000 | 1083.857 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 871.800 | 7.504 | 9.958 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 871.800 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1144.319 | 9.850 | 182.411 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1144.319 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 515.917 | 4.441 | 82.240 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 851.667 | 7.331 | 135.761 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.3437 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2452 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2452 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.676 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.002 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.002 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.37952697E-12 | 0.61408557E-15 | -0.13272107E-12 | 0.50758063E-16 |
34 | 6 | 0.33724497E-07 | 0.10093158E-09 | 0.76834149E-08 | -0.16284036E-12 |
35 | 5 | -0.21544664E-03 | 0.83871048E-06 | -0.11042849E-03 | 0.75774699E-08 |
36 | 4 | 0.32132970 | 0.39756193E-03 | 0.11020102 | -0.37736946E-04 |
37 | 3 | -7.8431967 | 0.12030612E-01 | -2.5101688 | 0.31839093E-01 |
38 | 2 | 42.772448 | 0.41882255E-01 | 15.964898 | -0.35452273 |
39 | 1 | -82.001465 | 0.18553051E-01 | -29.768348 | 1.1096424 |
40 | 0 | 46.824330 | 0.36650034E-03 | 16.276759 | |
41 | 7 | -0.17135090E-08 | -0.36864923E-15 | 0.71259317E-14 | -0.97083918E-16 |
42 | 6 | 0.68579659E-05 | 0.47011368E-08 | 0.31862738E-02 | -0.26729135E-04 |
43 | 5 | -0.49396463E-03 | 0.27861516E-05 | -0.22352018 | 0.19543461E-02 |
44 | 4 | 0.11367371E-01 | 0.12683264E-03 | 4.8261412 | -0.45232255E-01 |
45 | 3 | -0.99836882E-01 | 0.10087729E-02 | -38.002184 | 0.39844117 |
46 | 2 | 0.35452054 | 0.16782362E-02 | 116.44652 | -1.4174386 |
47 | 1 | -0.51170991 | 0.51154075E-03 | -143.88527 | 2.0486777 |
48 | 0 | 0.24948649 | 0.12321491E-04 | 60.838472 | |
49 | 7 | -0.17135090E-08 | -0.36864923E-15 | 0.71259317E-14 | -0.97083918E-16 |
50 | 6 | 0.68579659E-05 | 0.47011368E-08 | 0.31862738E-02 | -0.26729135E-04 |
51 | 5 | -0.49396463E-03 | 0.27861516E-05 | -0.22352018 | 0.19543461E-02 |
52 | 4 | 0.11367371E-01 | 0.12683264E-03 | 4.8261412 | -0.45232255E-01 |
53 | 3 | -0.99836882E-01 | 0.10087729E-02 | -38.002184 | 0.39844117 |
54 | 2 | 0.35452054 | 0.16782362E-02 | 116.44652 | -1.4174386 |
55 | 1 | -0.51170991 | 0.51154075E-03 | -143.88527 | 2.0486777 |
56 | 0 | 0.24948649 | 0.12321491E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4116_SHGC_SOUTH_0.45 | 38 | 1 | VerySmooth | 2.339 | 2.339 | 1.000 | 0.451 | ||
2 | NONRESWINDOW_U_0.4116_SHGC_NORTH_0.45 | 39 | 1 | VerySmooth | 2.339 | 2.339 | 1.000 | 0.451 | ||
3 | NONRESWINDOW_U_0.4116_SHGC_EAST_0.45 | 40 | 1 | VerySmooth | 2.339 | 2.339 | 1.000 | 0.451 | ||
4 | NONRESWINDOW_U_0.4116_SHGC_WEST_0.45 | 41 | 1 | VerySmooth | 2.339 | 2.339 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.12284E-002 | 0.36619 | 0.42846 | 0.42846 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12208 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.12284E-002 | 0.36619 | 0.42846 | 0.42846 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12208 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.12284E-002 | 0.36619 | 0.42846 | 0.42846 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12208 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.12284E-002 | 0.36619 | 0.42846 | 0.42846 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12208 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.053 | 0.3093 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.584 | 5.025E-003 | 6.281E-003 | 5.934 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 3.5268E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 3.1537E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 3.5655E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 3.0068E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.4314E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 3.3950E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.7203E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.6668E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.5032E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.9453E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.7014E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.9809E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 5.1203E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.9537E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.7466E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.7478E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.6777E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.7680E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.2965E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.4668E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.7352E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.0034E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.6726E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.7204E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 16544.57007 | 19853.48409 | 1.23740 | 1.48489 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 27.29800 | 7.00699E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 8565.95322 | 10279.14386 | 0.37084 | 0.44501 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -41.90000 | 6.45023E-005 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16400.06376 | 19680.07651 | 1.02217 | 1.22661 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.48200 | 7.00575E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 367.65800 | 441.18960 | 1.44066E-002 | 1.14133 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -41.90000 | 6.45023E-005 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 21331.17 | 1.48489 | 1.48489 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 41245.47 | 0.44501 | 0.44501 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 19948.03 | 1.22661 | 1.22661 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 111347.57 | 1.14133 | 1.14133 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.48489 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.22661 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.48489 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.48489 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.48489 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.48489 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.48489 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.48489 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.22661 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.22661 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.22661 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.22661 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.22661 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.22661 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.48489 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.22661 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.48489 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.48489 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 1588.89783 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.48489 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.48489 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.48489 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.48489 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.48489 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.74244 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.98993 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27433.75000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13716.87500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80041 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80041 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27433.75000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 64779.58483 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 64779.58483 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.22661 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.22661 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1358.04878 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.22661 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.22661 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.22661 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.22661 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.22661 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61330 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.81774 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22744.02000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11372.01000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80022 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80022 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22744.02000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 113672.24690 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 113672.24690 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 26354.6 | 11.26 | 11.21 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 21852.8 | 11.27 | 11.21 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.344 | 0.327 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4116_SHGC_EAST_0.45 | N/A | 2.339 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.344 | 0.327 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4116_SHGC_SOUTH_0.45 | N/A | 2.339 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.344 | 0.327 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4116_SHGC_WEST_0.45 | N/A | 2.339 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.245 | 0.231 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.344 | 0.327 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.344 | 0.327 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.344 | 0.327 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.245 | 0.231 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1485633452 | 0.6049070011 | Pass | Pass | 0.1362025865 | 0.3825652921 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1384371849 | 0.6815412736 | Pass | Pass | 5.3747222586E-002 | 0.2226198635 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 5.8322130537E-002 | 4.9331872948E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 294.66 | 224.08 | 1643.22 | 11.82 | 464.48 | 2638.27 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.327 | 0.344 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.327 | 0.344 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.327 | 0.344 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.236 | 0.245 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.327 | 0.344 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.327 | 0.344 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.327 | 0.344 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.236 | 0.245 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.4116_SHGC_EAST_0.45 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.339 | 0.451 | 0.452 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4116_SHGC_SOUTH_0.45 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.339 | 0.451 | 0.452 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.4116_SHGC_WEST_0.45 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.339 | 0.451 | 0.452 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.339 | 0.451 | 0.452 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.339 | 0.451 | 0.452 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 7.5044 | 116.17 | 871.80 | LightsWired | LTG_SCH_DINING | 91.35 | 168.00 | 68.07 | 0.0000 | Y | 11.14 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.8503 | 116.17 | 1144.32 | LightsWired | LTG_SCH_KITCHEN | 87.05 | 168.00 | 86.54 | 0.0000 | Y | 18.59 |
Interior Lighting Total | 8.6773 | 232.34 | 2016.12 | 29.73 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.22 | 871.80 | 191.80 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.22 | 871.80 | 191.80 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 216.58 | AstronomicalClock | - | 51.74 | 51.74 | 2.10 | |
EXTERIOR_LIGHTS_B | 1823.66 | AstronomicalClock | - | 83.06 | 73.66 | 25.22 | |
Exterior Lighting Total | 2040.24 | 27.32 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27433.75 | 21958.25 | 5475.50 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22744.02 | 18200.22 | 4543.80 | 0.80 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 26354.6 | 11.26 | 11.21 | ||||
PSZ-AC_2:2 COOLING COIL | 21852.8 | 11.27 | 11.21 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 64779.58 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 113672.25 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 1.56 | 1211.87 | 778.12 | 1.00 | 0.64 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.48 | 1588.90 | 1070.05 | 1.00 | 1.36 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.23 | 1358.05 | 1107.16 | 1.00 | 1.36 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 16544.57 | 19853.48 | 170.90 | 1.237 | 1.485 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 23.89 | 23.88 | 0.00798 | 27.30 | 0.00701 | 0.416 | 0.00 |
KITCHEN | 16400.06 | 19680.08 | 169.41 | 1.022 | 1.227 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.00868 | 26.48 | 0.00701 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 8565.95 | 10279.14 | 88.48 | 0.371 | 0.445 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00798 | -41.90 | 0.00006 | 0.416 | 0.00 |
KITCHEN | 367.66 | 441.19 | 3.80 | 0.014 | 1.141 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 18.89 | 18.89 | 0.00300 | -41.90 | 0.00006 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.48 | 1.48 | 0.45 | 0.45 | 1.4849 | 1.4849 | 1.4849 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.23 | 1.23 | 1.14 | 1.14 | 1.2266 | 1.2266 | 1.2266 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 27433.750 | 21958.248 | 1.484890 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 13716.88 | 12375.84 | 0.989927 | 24.87 | 15.85 | 0.00770868 | 11.91 | 10.04 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 42.0290 | 23.88 | 0.00798202 | 42.6382 | 16533.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 64779.585 | 64779.585 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 64779.58 | 64779.58 | 1.484886 | 3.38 | 3.38 | 0.00575925 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 28.0194 | 21.11 | 0.00797601 | 50.4208 | 8565.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 22744.020 | 18200.220 | 1.226610 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 11372.01 | 11181.69 | 0.817740 | 26.45 | 15.91 | 0.00712196 | 11.88 | 10.02 | 0.00700000 | 26.48 | 0.00700575 | 15.82 | 139.5717 | 26.10 | 0.00867735 | 40.5700 | 16400.06 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 113672.247 | 113672.247 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 113672.25 | 113672.25 | 1.226607 | -37.80 | -37.80 | 0.00032083 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 93.0480 | 18.83 | 0.00375165 | 27.4911 | 225.82 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27433.750 | 21958.248 | 1.484890 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1701 | 1004.8586 | 1.1854 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.484886 | 1.76024179 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 13716.88 | 12375.84 | 1.0000 | 1.17349797 | 0.989927 | 24.87 | 15.85 | 0.00770868 | 44623.3 | 11.91 | 10.04 | 0.00700000 | 29633.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13716.88 | 27.40 | 0.00700714 | 16.15 | 0.41605618 | 42.0290 | 23.88 | 0.00798202 | 23.88 | 0.00798202 | 42.6382 | 16533.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 64779.585 | 64779.585 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.484886 | 1.76024179 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | Sensible | 64779.58 | 64779.58 | 1.0000 | 1.76024179 | 1.484886 | 3.38 | 3.38 | 0.00575925 | 17832.4 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 64779.58 | -41.90 | 0.00006450 | -41.90 | 0.41605618 | 28.0194 | 21.00 | 0.00797601 | 21.11 | 0.00797601 | 50.4208 | 8565.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22744.020 | 18200.220 | 1.226610 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0794 | 1004.8586 | 1.1854 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.226607 | 1.45406827 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 11372.01 | 11181.69 | 1.0000 | 0.96938113 | 0.817740 | 26.45 | 15.91 | 0.00712196 | 44742.3 | 11.88 | 10.02 | 0.00700000 | 29601.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11372.01 | 26.48 | 0.00700575 | 15.82 | 1.14133354 | 139.5717 | 26.06 | 0.00867735 | 26.10 | 0.00867735 | 40.5700 | 16400.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 113672.247 | 113672.247 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.226607 | 1.45406827 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 113672.25 | 113672.25 | 1.0000 | 1.45406827 | 1.226607 | -37.80 | -37.80 | 0.00032083 | -37200.4 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 113672.25 | -41.90 | 0.00006450 | -41.90 | 1.14133354 | 93.0480 | 17.11 | 0.00375165 | 18.83 | 0.00375165 | 27.4911 | 225.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.48 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.23 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 4174.67 | 5905.50 | 3300.00 |
KITCHEN | 5151.83 | 6284.17 | 4458.17 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5207.83 | 6682.83 | 4514.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 161.83 | 8.67 | 0.17 | 0.00 |
KITCHEN | 0.00 | 123.33 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 161.83 | 124.83 | 0.17 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.873 | 2.852 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 11.815 | 0.019 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.092 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 11.223 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 12543288.68 | 0.00 | 12543288.68 | 7180182.88 | 19723471.56 | 13120747.55 | 1433.91 | 6404.34 | 921.75 | 461.63 |
KITCHEN | 30499691.26 | 0.00 | 30499691.26 | 85214.71 | 30584905.97 | 35993094.65 | 1455.16 | 6668.98 | 635.86 | 488.50 |
Total Facility | 43042979.94 | 0.00 | 43042979.94 | 7265397.59 | 50308377.52 | 49113842.20 | 1458.16 | 6774.10 | 1005.66 | 728.11 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4717 | 0.0000 | 0.4717 | 0.2761 | 0.7478 | 0.4161 | 0.00 | 6267.40 | 919.60 |
KITCHEN | 1.1485 | 0.0000 | 1.1485 | 0.0019 | 1.1504 | 1.1413 | 0.00 | 6556.04 | 630.96 |
Total Facility | 1.6202 | 0.0000 | 1.6202 | 0.2780 | 1.8982 | 1.5574 | 0.00 | 6636.96 | 1000.51 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 17626665.91 | 0.00 | 17626665.91 | 13120747.55 | 1427.21 | 0.51 | 7332.28 | 461.60 |
PSZ-AC_2:2 | 42860188.88 | 0.00 | 42860188.88 | 35993094.65 | 1448.99 | 0.62 | 7310.39 | 488.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6628 | 0.0000 | 0.6628 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.6140 | 0.0000 | 1.6140 | 1.1413 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 765.53 | 482.45 | 6400.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 710.06 | 6965.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.4635 | 0.9482 | 0.5848 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.7181 | 1.6041 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 374 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 513.14 | 4284.54 | 02-JUN-03:00 | 28771.23 | 22-JUL-10:20 |
Electricity:Building | 324.18 | 2894.78 | 20-JUN-03:00 | 19584.75 | 02-JAN-11:10 |
Electricity:Zone:DINING | 81.47 | 338.63 | 20-JUN-03:00 | 4665.44 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 306.32 | 2485.74 | 20-JUN-03:00 | 16068.65 | 02-JAN-11:10 |
InteriorLights:Electricity | 29.73 | 221.88 | 06-MAY-04:30 | 1654.77 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 11.14 | 68.62 | 06-MAY-04:30 | 735.19 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 29.73 | 221.88 | 06-MAY-04:30 | 1654.77 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 29.73 | 221.88 | 06-MAY-04:30 | 1654.77 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 11.14 | 68.62 | 06-MAY-04:30 | 735.19 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 29.73 | 221.88 | 06-MAY-04:30 | 1654.77 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 242.71 | 2556.15 | 01-JAN-01:10 | 14919.31 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 18.59 | 153.26 | 01-JAN-01:10 | 919.59 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 18.59 | 153.26 | 01-JAN-01:10 | 919.59 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 276.59 | 2263.87 | 01-JAN-01:10 | 14413.88 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 276.59 | 2263.87 | 01-JAN-01:10 | 14413.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 206.26 | 1993.86 | 01-JAN-01:10 | 10483.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.15 | 1035.59 | 06-APR-22:30 | 4574.14 | 30-JUN-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
Electricity:Plant | 43.29 | 779.93 | 06-FEB-23:10 | 2536.82 | 25-JUL-04:10 |
LowTempRefrigeration:Refrigeration:Electricity | 15.47 | 0.00 | 01-JAN-11:10 | 1460.59 | 25-JUL-04:10 |
MedTempRefrigeration:Refrigeration:Electricity | 27.82 | 701.41 | 17-JAN-01:10 | 1076.23 | 19-JUN-13:10 |
ElectricityPurchased:Facility | 513.14 | 4284.54 | 02-JUN-03:00 | 28771.23 | 22-JUL-10:20 |
ElectricityPurchased:Plant | 513.14 | 4284.54 | 02-JUN-03:00 | 28771.23 | 22-JUL-10:20 |
Cogeneration:ElectricityPurchased | 513.14 | 4284.54 | 02-JUN-03:00 | 28771.23 | 22-JUL-10:20 |
General:Cogeneration:ElectricityPurchased | 513.14 | 4284.54 | 02-JUN-03:00 | 28771.23 | 22-JUL-10:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 513.14 | 4284.54 | 02-JUN-03:00 | 28771.23 | 22-JUL-10:20 |
ElectricityNet:Plant | 513.14 | 4284.54 | 02-JUN-03:00 | 28771.23 | 22-JUL-10:20 |
Cogeneration:ElectricityNet | 513.14 | 4284.54 | 02-JUN-03:00 | 28771.23 | 22-JUL-10:20 |
General:Cogeneration:ElectricityNet | 513.14 | 4284.54 | 02-JUN-03:00 | 28771.23 | 22-JUL-10:20 |
Electricity:HVAC | 118.35 | 0.00 | 01-JAN-01:10 | 12264.21 | 29-JUL-17:10 |
Fans:Electricity | 112.26 | 0.00 | 01-JAN-01:10 | 4158.82 | 01-JAN-06:20 |
General:Fans:Electricity | 112.26 | 0.00 | 01-JAN-01:10 | 4158.82 | 01-JAN-06:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 6.09 | 0.00 | 01-JAN-00:10 | 8105.39 | 29-JUL-17:10 |
General:Cooling:Electricity | 6.09 | 0.00 | 01-JAN-00:10 | 8105.39 | 29-JUL-17:10 |
ExteriorLights:Electricity | 27.32 | 0.00 | 01-JAN-11:20 | 2040.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 27.32 | 0.00 | 01-JAN-11:20 | 2040.24 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-07:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1828.69 | 2558.65 | 29-JAN-03:40 | 208984.72 | 12-JAN-13:20 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 1090.67 | 0.00 | 01-JAN-01:10 | 163048.89 | 12-JAN-21:00 |
Heating:NaturalGas | 1090.67 | 0.00 | 01-JAN-01:10 | 163048.89 | 12-JAN-21:00 |
General:Heating:NaturalGas | 1090.67 | 0.00 | 01-JAN-01:10 | 163048.89 | 12-JAN-21:00 |
NaturalGas:Plant | 260.85 | 720.00 | 10-JAN-04:30 | 33363.77 | 03-JAN-13:20 |
WaterSystems:NaturalGas | 260.85 | 720.00 | 10-JAN-04:30 | 33363.77 | 03-JAN-13:20 |
Water Heater:WaterSystems:NaturalGas | 260.85 | 720.00 | 10-JAN-04:30 | 33363.77 | 03-JAN-13:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1666.29 | 2739.63 | 12-JAN-01:10 | 194408.17 | 12-JAN-14:00 |
EnergyTransfer:Building | 518.94 | 1369.82 | 12-JAN-01:10 | 53688.06 | 12-JAN-12:10 |
EnergyTransfer:Zone:KITCHEN | 340.16 | 1369.82 | 12-JAN-01:10 | 23803.17 | 16-JUN-04:10 |
Refrigeration:EnergyTransfer | 136.74 | 2699.60 | 06-FEB-23:10 | 7834.84 | 30-JUN-04:10 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.37 | 1349.80 | 06-FEB-23:10 | 3917.42 | 30-JUN-04:10 |
General:Refrigeration:EnergyTransfer | 68.37 | 1349.80 | 06-FEB-23:10 | 3917.42 | 30-JUN-04:10 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.37 | 1349.80 | 06-FEB-23:10 | 3917.42 | 30-JUN-04:10 |
EnergyTransfer:Plant | 251.55 | 1349.81 | 20-FEB-23:10 | 25788.38 | 12-MAY-13:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 16.14 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 52.23 | 1114.23 | 17-JAN-01:10 | 2238.70 | 19-JUN-13:10 |
EnergyTransfer:Zone:DINING | 178.78 | 0.00 | 01-JAN-01:10 | 38001.95 | 12-JAN-20:40 |
Heating:EnergyTransfer | 139.44 | 0.00 | 01-JAN-00:30 | 38001.95 | 12-JAN-20:40 |
Heating:EnergyTransfer:Zone:DINING | 139.34 | 0.00 | 01-JAN-00:10 | 38001.95 | 12-JAN-20:40 |
General:Heating:EnergyTransfer | 139.44 | 0.00 | 01-JAN-00:30 | 38001.95 | 12-JAN-20:40 |
General:Heating:EnergyTransfer:Zone:DINING | 139.34 | 0.00 | 01-JAN-00:10 | 38001.95 | 12-JAN-20:40 |
Cooling:EnergyTransfer | 311.13 | 0.00 | 01-JAN-01:10 | 24544.50 | 25-AUG-04:10 |
Cooling:EnergyTransfer:Zone:DINING | 39.44 | 0.00 | 01-JAN-01:10 | 15093.91 | 27-FEB-04:50 |
General:Cooling:EnergyTransfer | 311.13 | 0.00 | 01-JAN-01:10 | 24544.50 | 25-AUG-04:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 39.44 | 0.00 | 01-JAN-01:10 | 15093.91 | 27-FEB-04:50 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.10 | 0.00 | 01-JAN-00:20 | 2725.79 | 12-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.10 | 0.00 | 01-JAN-00:20 | 2725.79 | 12-JAN-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 271.69 | 0.00 | 01-JAN-01:10 | 19933.19 | 16-JUN-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 271.69 | 0.00 | 01-JAN-01:10 | 19933.19 | 16-JUN-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 183.18 | 0.00 | 01-JAN-00:10 | 23248.45 | 12-MAR-13:00 |
PlantLoopHeatingDemand:Plant | 183.18 | 0.00 | 01-JAN-00:10 | 23248.45 | 12-MAR-13:00 |
WaterSystems:PlantLoopHeatingDemand | 183.18 | 0.00 | 01-JAN-00:10 | 23248.45 | 12-MAR-13:00 |
General:WaterSystems:PlantLoopHeatingDemand | 183.18 | 0.00 | 01-JAN-00:10 | 23248.45 | 12-MAR-13:00 |
EnergyTransfer:HVAC | 895.80 | 0.00 | 01-JAN-01:10 | 130439.11 | 12-JAN-21:00 |
HeatingCoils:EnergyTransfer | 872.54 | 0.00 | 01-JAN-01:10 | 130439.11 | 12-JAN-21:00 |
CoolingCoils:EnergyTransfer | 23.27 | 0.00 | 01-JAN-00:10 | 34130.03 | 29-JUL-17:10 |
WaterSystems:EnergyTransfer | 183.18 | 0.00 | 01-JAN-00:10 | 23248.45 | 12-MAR-13:00 |
WaterUse:WaterSystems:EnergyTransfer | 183.18 | 0.00 | 01-JAN-00:10 | 23248.45 | 12-MAR-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 139.342 | -39.438 | 0.000 | 0.000 | 73.637 | 11.139 | 52.748 | 22.794 | 0.000 | 0.222 | 0.002 | 0.000 | -26.812 | 0.000 | -196.226 | -37.406 |
KITCHEN | 0.000 | 0.000 | 0.100 | -271.681 | 0.000 | 0.000 | 5.523 | 18.590 | 211.968 | 0.000 | 0.000 | 0.000 | 37.653 | 0.000 | 0.000 | 0.000 | -2.154 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.900 | 4.432 | 0.000 | 0.000 | 0.000 | -9.332 | -0.000 |
Total Facility | 0.000 | 0.000 | 139.442 | -311.119 | 0.000 | 0.000 | 79.160 | 29.730 | 264.717 | 22.794 | 0.000 | 5.122 | 42.087 | 0.000 | -26.812 | 0.000 | -207.712 | -37.407 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 12-JAN-04:41 | 0.00 | 0.00 | 0.00 | -33464.93 | 0.00 | 0.00 | 0.00 | 122.53 | 506.27 | 0.00 | 0.00 | 0.00 | 35699.43 | 0.00 | -2779.00 | 0.00 | -84.29 | 0.00 |
KITCHEN | 15-DEC-05:01 | 0.00 | 0.00 | 0.00 | -72497.28 | 0.00 | 0.00 | 18.55 | 204.35 | 5271.43 | 0.00 | 0.00 | 0.00 | 67002.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-DEC-05:01 | -28541.39 | 28541.39 | 28541.39 | -72497.28 | 0.00 | 0.00 | 431.05 | 367.73 | 6491.17 | 0.00 | 0.00 | 476.01 | 38662.25 | 0.00 | -2472.31 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 25-MAR-02:61 | 0.00 | 0.00 | 46485.06 | 0.00 | 0.00 | 0.00 | 0.00 | 122.53 | 202.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1488.73 | 0.00 | -569.73 | -44751.64 |
KITCHEN | 12-JAN-05:02 | 0.00 | 0.00 | 27226.83 | 0.00 | 0.00 | 0.00 | 21.35 | 204.35 | 5271.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -32723.96 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-MAR-02:61 | 0.00 | 0.00 | 46485.06 | 0.00 | 0.00 | 0.00 | 0.00 | 275.79 | 2219.64 | 0.00 | 0.00 | 87.83 | 0.00 | 0.00 | -1488.73 | 0.00 | -1195.95 | -46383.64 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.4849 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.4849 | 0.2802 | 1.0000 | Not calculated | 0.4161 | 0.2802 | ||
PSZ-AC_2:2 | 1.2266 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2266 | 0.1233 | 1.0000 | Not calculated | 0.1513 | 0.1233 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.4849 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.4849 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2802 | ||
PSZ-AC_2:2 | 1.2266 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2266 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1233 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4849 | 1.4849 | 1.4849 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2266 | 1.2266 | 1.2266 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.4849 | 1.4849 | 1.4849 | 1.4849 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2266 | 1.2266 | 1.2266 | 1.2266 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4849 | 1.4849 | 1.4849 | No | 0.4161 | 0.9349 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2266 | 1.2266 | 1.2266 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.4849 | 1.4849 | 1.4849 | 1.4849 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2266 | 1.2266 | 1.2266 | 1.2266 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1090.67 | 163048.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 6.09 | 8105.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 29.73 | 1654.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 27.32 | 2040.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 112.26 | 4158.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 260.85 | 33363.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 17.86 | 3516.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.47 | 1460.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 27.82 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 337.74 | 513.14 |
Natural Gas | 477.16 | 1828.69 |
Additional | 0.00 | 0.00 |
Total | 814.90 | 2341.82 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 127.96 |
Space Heating | 0.00 |
Space Cooling | 26.20 |
Fans (All) | 483.18 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1190.44 |
Miscellaneous (All) | 2208.53 |
Subtotal | 2208.53 |
Natural Gas [MJ/m2] | |
Space Heating | 4694.24 |
Service Water Heating | 1122.71 |
Miscellaneous (All) | 7870.63 |
Subtotal | 7870.63 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.27 |
Space Heating | 46.57 |
Space Cooling | 0.26 |
Fans (All) | 4.79 |
Service Water Heating | 11.14 |
Receptacle Equipment | 32.19 |
Miscellaneous | 3.78 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4763. | 8760. |
LTG_SCH_KITCHEN | 4539. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_SETBACK | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_SETBACK | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8672.17 | 87.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 7875.83 | 480.00 | 332.83 | 71.33 | 0.00 |
Min | 7875.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 480.00 | 332.83 | 71.33 | 0.00 |
Average | 8436.00 | 189.28 | 110.94 | 23.78 | 0.00 |
Sum | 25308.00 | 567.83 | 332.83 | 71.33 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16258.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 90327.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 270983.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8473.67 | 286.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 8008.50 | 616.33 | 109.00 | 24.50 | 1.67 |
Min | 8008.50 | 1.67 | 0.00 | 0.00 | 0.00 |
Max | 8758.33 | 616.33 | 109.00 | 24.50 | 1.67 |
Average | 8413.50 | 301.44 | 36.33 | 8.17 | 0.56 |
Sum | 25240.50 | 904.33 | 109.00 | 24.50 | 1.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 254647.83 | 77.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15566.00 | 692.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254647.83 | 692.00 | 0.00 | 0.00 | 0.00 |
Average | 90071.28 | 256.39 | 0.00 | 0.00 | 0.00 |
Sum | 270213.83 | 769.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:25
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.667267E+09 | 33463.57 | 12-JAN-04:41 | -37.7 | -37.8 | 0.444644E+10 | 3722.80 | 14-JAN-19:10 | -21.8 | -22.0 |
February | 0.639354E+09 | 30223.13 | 27-FEB-04:50 | -35.8 | -35.9 | 0.402507E+10 | 3722.80 | 18-FEB-19:10 | -35.8 | -35.9 |
March | 0.649678E+09 | 20294.33 | 01-MAR-00:01 | -28.9 | -29.2 | 0.449096E+10 | 3722.82 | 18-MAR-18:40 | 2.03 | 0.19 |
April | 0.180120E+10 | 14668.15 | 02-APR-23:01 | -15.8 | -17.1 | 0.434950E+10 | 4164.54 | 22-APR-18:10 | 12.62 | 5.42 |
May | 0.480642E+10 | 7241.48 | 11-MAY-04:01 | 3.48 | 0.36 | 0.485457E+10 | 4680.68 | 13-MAY-18:10 | 18.80 | 8.86 |
June | 0.802280E+10 | 11665.19 | 30-JUN-04:01 | 14.40 | 12.81 | 0.509057E+10 | 4681.01 | 10-JUN-18:00 | 14.40 | 12.81 |
July | 0.957391E+10 | 11886.99 | 25-JUL-04:01 | 14.40 | 13.72 | 0.523900E+10 | 4681.32 | 08-JUL-18:40 | 14.40 | 13.72 |
August | 0.791788E+10 | 10675.03 | 11-AUG-17:05 | 25.60 | 14.63 | 0.514399E+10 | 4681.08 | 26-AUG-18:30 | 20.60 | 13.96 |
September | 0.304600E+10 | 8282.86 | 28-SEP-23:01 | -1.2 | -2.4 | 0.443799E+10 | 4680.87 | 02-SEP-18:30 | -1.2 | -2.4 |
October | 0.973846E+09 | 15103.06 | 26-OCT-23:01 | -16.7 | -17.3 | 0.444864E+10 | 3722.81 | 14-OCT-18:30 | -16.7 | -17.3 |
November | 0.632803E+09 | 20275.88 | 29-NOV-00:01 | -28.8 | -29.0 | 0.430070E+10 | 3722.81 | 04-NOV-18:19 | -28.8 | -29.0 |
December | 0.707191E+09 | 26222.91 | 15-DEC-04:50 | -33.1 | -33.2 | 0.444506E+10 | 3722.80 | 09-DEC-19:40 | -33.1 | -33.2 |
Annual Sum or Average | 0.394383E+11 | 0.552725E+11 | ||||||||
Minimum of Months | 0.632803E+09 | 7241.48 | -37.7 | -37.8 | 0.402507E+10 | 3722.80 | -35.8 | -35.9 | ||
Maximum of Months | 0.957391E+10 | 33463.57 | 25.60 | 14.63 | 0.523900E+10 | 4681.32 | 20.60 | 13.96 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205433E+11 | 71917.55 | 13-JAN-05:01 | -32.9 | -33.0 | 0.768048E+10 | 5036.86 | 18-JAN-11:00 | -10.6 | -10.8 |
February | 0.182291E+11 | 66378.85 | 22-FEB-05:01 | -30.0 | -30.2 | 0.693768E+10 | 5036.86 | 07-FEB-11:00 | -30.0 | -30.2 |
March | 0.210414E+11 | 64131.37 | 01-MAR-05:01 | -28.3 | -28.7 | 0.768296E+10 | 5036.86 | 29-MAR-10:00 | -9.4 | -11.6 |
April | 0.220637E+11 | 55526.94 | 03-APR-04:01 | -21.1 | -21.6 | 0.744080E+10 | 5061.09 | 22-APR-10:00 | 12.80 | 6.00 |
May | 0.236327E+11 | 40949.21 | 23-MAY-03:31 | 8.30 | 5.23 | 0.775237E+10 | 5135.91 | 31-MAY-10:00 | 18.90 | 10.59 |
June | 0.235976E+11 | 46511.44 | 02-JUN-03:41 | 3.40 | 2.48 | 0.757111E+10 | 5135.94 | 30-JUN-10:39 | 21.67 | 16.64 |
July | 0.251609E+11 | 40459.70 | 21-JUL-04:01 | 9.60 | 8.02 | 0.782583E+10 | 5135.95 | 27-JUL-10:00 | 20.00 | 14.43 |
August | 0.258454E+11 | 42144.37 | 11-AUG-04:01 | 11.10 | 6.92 | 0.780466E+10 | 5135.94 | 04-AUG-10:00 | 11.10 | 6.92 |
September | 0.249459E+11 | 36425.07 | 30-SEP-04:01 | -4.0 | -4.5 | 0.746135E+10 | 5074.77 | 19-SEP-10:00 | -4.0 | -4.5 |
October | 0.243103E+11 | 54293.75 | 22-OCT-04:01 | -18.6 | -18.8 | 0.768252E+10 | 5058.44 | 04-OCT-10:00 | -18.6 | -18.8 |
November | 0.213084E+11 | 66427.43 | 28-NOV-05:01 | -27.7 | -27.9 | 0.743259E+10 | 5036.86 | 03-NOV-10:00 | -27.7 | -27.9 |
December | 0.210088E+11 | 72553.67 | 15-DEC-05:01 | -33.2 | -33.3 | 0.768036E+10 | 5036.86 | 19-DEC-11:09 | -15.4 | -15.8 |
Annual Sum or Average | 0.271687E+12 | 0.909527E+11 | ||||||||
Minimum of Months | 0.182291E+11 | 36425.07 | -33.2 | -33.3 | 0.693768E+10 | 5036.86 | -30.0 | -30.2 | ||
Maximum of Months | 0.258454E+11 | 72553.67 | 11.10 | 8.02 | 0.782583E+10 | 5135.95 | 21.67 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -28.9 | -29.2 | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.2 |
April | 0.00 | 0.00 | 01-APR-00:01 | -11.7 | -13.3 | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.3 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.70 | 2.18 | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.18 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 | 8.14 | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.14 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 | 13.77 | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 | 11.83 | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.83 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8.08 | 5.90 | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 1.42 | 0.12 | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.12 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 0.00 | 0.00 | -28.9 | -29.2 | ||
Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.00 | 0.00 | 16.35 | 13.77 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.276624E+11 | 45972.49 | 05-JAN-03:01 | -11.9 |
February | 0.221839E+11 | 46271.47 | 02-FEB-03:01 | -9.1 |
March | 0.174289E+11 | 46487.40 | 25-MAR-02:61 | -10.8 |
April | 0.556661E+10 | 38300.91 | 04-APR-02:61 | -10.6 |
May | 0.422609E+09 | 13996.19 | 28-MAY-02:62 | 0.10 |
June | 647120.60 | 3452.80 | 25-JUN-06:55 | 10.00 |
July | 1403648.29 | 465.21 | 05-JUL-06:10 | 8.30 |
August | 74903479.45 | 4646.20 | 31-AUG-06:10 | -1.5 |
September | 0.172750E+10 | 9169.88 | 18-SEP-05:03 | 1.78 |
October | 0.102945E+11 | 29671.38 | 27-OCT-04:01 | -17.7 |
November | 0.249898E+11 | 42312.55 | 13-NOV-05:01 | -20.2 |
December | 0.289885E+11 | 42541.66 | 27-DEC-05:01 | -19.6 |
Annual Sum or Average | 0.139342E+12 | |||
Minimum of Months | 647120.60 | 465.21 | -20.2 | |
Maximum of Months | 0.289885E+11 | 46487.40 | 10.00 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20007834.71 | 27257.91 | 12-JAN-05:02 | -37.9 |
February | 20884908.37 | 26498.58 | 27-FEB-05:02 | -36.1 |
March | 14136102.45 | 21348.30 | 02-MAR-05:02 | -26.7 |
April | 4404214.77 | 11704.78 | 08-APR-04:03 | -7.3 |
May | 1080480.31 | 15841.38 | 28-MAY-04:05 | 1.78 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 191658.37 | 1483.68 | 17-SEP-04:04 | 2.02 |
October | 4506988.92 | 10366.04 | 29-OCT-04:03 | -11.2 |
November | 15291698.44 | 11678.07 | 04-NOV-04:03 | -7.8 |
December | 19527010.07 | 13759.78 | 06-DEC-05:02 | -28.0 |
Annual Sum or Average | 0.100031E+09 | |||
Minimum of Months | 0.00 | 0.00 | -37.9 | |
Maximum of Months | 20884908.37 | 27257.91 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.115452E+10 | 735.19 | 02-JAN-10:09 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.942477E+09 | 735.19 | 01-FEB-15:20 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.949373E+09 | 735.19 | 01-MAR-17:19 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.801751E+09 | 735.19 | 01-APR-19:40 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.794547E+09 | 735.19 | 01-MAY-20:30 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.743812E+09 | 735.19 | 02-JUN-20:00 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.769991E+09 | 735.19 | 25-JUL-20:00 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.832200E+09 | 735.19 | 02-AUG-20:40 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.876360E+09 | 735.19 | 01-SEP-19:10 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.992444E+09 | 735.19 | 02-OCT-17:19 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.106348E+10 | 735.19 | 01-NOV-09:09 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.121835E+10 | 735.19 | 01-DEC-10:09 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.111393E+11 | 0.703313E+11 | ||||
Minimum of Months | 0.743812E+09 | 735.19 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.121835E+10 | 735.19 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.157083E+10 | 919.59 | 02-JAN-10:09 | 0.175178E+11 | 10483.62 | 01-JAN-11:09 |
February | 0.142278E+10 | 919.59 | 01-FEB-10:09 | 0.158225E+11 | 10483.62 | 01-FEB-11:09 |
March | 0.159585E+10 | 919.59 | 01-MAR-10:09 | 0.175179E+11 | 10483.62 | 01-MAR-11:09 |
April | 0.152633E+10 | 919.59 | 01-APR-16:10 | 0.169527E+11 | 10483.62 | 01-APR-10:09 |
May | 0.158334E+10 | 919.59 | 01-MAY-09:09 | 0.175178E+11 | 10483.62 | 01-MAY-10:09 |
June | 0.154251E+10 | 919.59 | 01-JUN-09:09 | 0.169528E+11 | 10483.62 | 01-JUN-10:09 |
July | 0.156734E+10 | 919.59 | 01-JUL-16:10 | 0.175177E+11 | 10483.62 | 01-JUL-10:09 |
August | 0.159585E+10 | 919.59 | 01-AUG-09:09 | 0.175179E+11 | 10483.62 | 01-AUG-10:09 |
September | 0.152669E+10 | 919.59 | 01-SEP-09:09 | 0.169527E+11 | 10483.62 | 01-SEP-10:09 |
October | 0.157065E+10 | 919.59 | 02-OCT-09:09 | 0.175178E+11 | 10483.62 | 01-OCT-10:09 |
November | 0.152062E+10 | 919.59 | 01-NOV-09:09 | 0.169527E+11 | 10483.62 | 01-NOV-10:09 |
December | 0.156752E+10 | 919.59 | 01-DEC-10:09 | 0.175177E+11 | 10483.62 | 01-DEC-11:09 |
Annual Sum or Average | 0.185903E+11 | 0.206258E+12 | ||||
Minimum of Months | 0.142278E+10 | 919.59 | 0.158225E+11 | 10483.62 | ||
Maximum of Months | 0.159585E+10 | 919.59 | 0.175179E+11 | 10483.62 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.115452E+10 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299284E+11 |
February | 0.852256E+10 | 0.942477E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247832E+11 |
March | 0.954557E+10 | 0.949373E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228780E+11 |
April | 0.915225E+10 | 0.801751E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129884E+11 |
May | 0.947560E+10 | 0.794547E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674631E+10 |
June | 0.922788E+10 | 0.743812E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64730462.98 | 0.384138E+10 |
July | 0.939996E+10 | 0.769991E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138306E+09 | 0.329986E+10 |
August | 0.954557E+10 | 0.832200E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18576697.94 | 0.501987E+10 |
September | 0.915225E+10 | 0.876360E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932396E+10 |
October | 0.940563E+10 | 0.992444E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175453E+11 |
November | 0.909363E+10 | 0.106348E+10 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286006E+11 |
December | 0.939996E+10 | 0.121835E+10 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312706E+11 |
Annual Sum or Average | 0.111326E+12 | 0.111393E+11 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221613E+09 | 0.196226E+12 |
Minimum of Months | 0.852256E+10 | 0.743812E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329986E+10 |
Maximum of Months | 0.954557E+10 | 0.121835E+10 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138306E+09 | 0.312706E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.157083E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233318E+09 |
February | 0.610713E+09 | 0.142278E+10 | 0.120683E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192596E+09 |
March | 0.684021E+09 | 0.159585E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302641E+09 |
April | 0.655836E+09 | 0.152633E+10 | 0.129303E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295805E+09 |
May | 0.679007E+09 | 0.158334E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186137E+09 |
June | 0.661256E+09 | 0.154251E+10 | 0.129304E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 55017.28 | 0.110470E+09 |
July | 0.673587E+09 | 0.156734E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 306446.54 | 81433003.39 |
August | 0.684021E+09 | 0.159585E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107071E+09 |
September | 0.655836E+09 | 0.152669E+10 | 0.129303E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113563E+09 |
October | 0.673993E+09 | 0.157065E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256702E+09 |
November | 0.651635E+09 | 0.152062E+10 | 0.129304E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94192774.36 |
December | 0.673587E+09 | 0.156752E+10 | 0.133613E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180500E+09 |
Annual Sum or Average | 0.797748E+10 | 0.185903E+11 | 0.157319E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 361463.81 | 0.215443E+10 |
Minimum of Months | 0.610713E+09 | 0.142278E+10 | 0.120683E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81433003.39 |
Maximum of Months | 0.684021E+09 | 0.159585E+10 | 0.133614E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 306446.54 | 0.302641E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767167E+09 | 13378412.71 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550127E+09 | 0.181329E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398591E+09 | 0.779168E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277111E+09 | 0.131702E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183529E+09 | 0.158548E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93395679.93 | 0.168276E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112945E+09 | 0.158655E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191485E+09 | 0.122631E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308883E+09 | 0.638183E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366732E+09 | 0.272813E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815986E+09 | 48222862.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834310E+09 | 715600.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490026E+10 | 0.933193E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93395679.93 | 715600.94 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834310E+09 | 0.168276E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 735.19 | 02-JAN-10:09 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 41336.51 | 12-JAN-12:05 |
February | 9454.80 | 04-FEB-19:10 | 735.19 | 01-FEB-15:20 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 35839.55 | 27-FEB-12:05 |
March | 9454.80 | 04-MAR-19:10 | 735.19 | 01-MAR-17:19 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 29494.06 | 01-MAR-21:00 |
April | 9454.80 | 01-APR-18:10 | 735.19 | 01-APR-19:40 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 19621.83 | 01-APR-19:00 |
May | 9454.80 | 06-MAY-18:10 | 735.19 | 01-MAY-20:30 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 10372.22 | 26-MAY-20:00 |
June | 9454.80 | 03-JUN-18:10 | 735.19 | 02-JUN-20:00 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1565.78 | 20-JUN-17:55 | 6196.59 | 24-JUN-19:00 |
July | 9454.80 | 01-JUL-18:10 | 735.19 | 25-JUL-20:00 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2794.94 | 29-JUL-17:03 | 6251.61 | 05-JUL-12:00 |
August | 9454.80 | 05-AUG-18:10 | 735.19 | 02-AUG-20:40 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 962.86 | 11-AUG-17:05 | 8809.83 | 30-AUG-20:00 |
September | 9454.80 | 02-SEP-18:10 | 735.19 | 01-SEP-19:10 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 14981.94 | 30-SEP-18:53 |
October | 9454.80 | 07-OCT-18:10 | 735.19 | 02-OCT-17:19 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 25585.07 | 30-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 735.19 | 01-NOV-09:09 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 33982.97 | 30-NOV-21:00 |
December | 9454.80 | 02-DEC-19:10 | 735.19 | 01-DEC-10:09 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 38104.88 | 15-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 735.19 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6196.59 | |||||
Maximum of Months | 9454.80 | 735.19 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2794.94 | 41336.51 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 919.59 | 02-JAN-10:09 | 7748.81 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1517.91 | 29-JAN-01:10 |
February | 677.52 | 04-FEB-19:10 | 919.59 | 01-FEB-10:09 | 7748.81 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1045.25 | 24-FEB-05:00 |
March | 677.52 | 04-MAR-19:10 | 919.59 | 01-MAR-10:09 | 7748.81 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 805.39 | 25-MAR-04:00 |
April | 677.52 | 01-APR-18:10 | 919.59 | 01-APR-16:10 | 7748.81 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 877.68 | 07-APR-04:00 |
May | 677.52 | 06-MAY-18:10 | 919.59 | 01-MAY-09:09 | 7748.81 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 594.77 | 27-MAY-04:00 |
June | 677.52 | 03-JUN-18:10 | 919.59 | 01-JUN-09:09 | 7748.81 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 11.20 | 30-JUN-15:00 | 619.68 | 25-JUN-04:00 |
July | 677.52 | 01-JUL-18:10 | 919.59 | 01-JUL-16:10 | 7748.81 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 33.20 | 21-JUL-16:00 | 332.08 | 30-JUL-03:20 |
August | 677.52 | 05-AUG-18:10 | 919.59 | 01-AUG-09:09 | 7748.81 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 451.04 | 30-AUG-01:00 |
September | 677.52 | 02-SEP-18:10 | 919.59 | 01-SEP-09:09 | 7748.81 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 325.26 | 30-SEP-02:00 |
October | 677.52 | 07-OCT-18:10 | 919.59 | 02-OCT-09:09 | 7748.81 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 797.33 | 21-OCT-04:00 |
November | 677.52 | 04-NOV-18:10 | 919.59 | 01-NOV-09:09 | 7748.81 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 628.96 | 10-NOV-05:00 |
December | 677.52 | 02-DEC-19:10 | 919.59 | 01-DEC-10:09 | 7748.81 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 639.55 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 919.59 | 7748.81 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 325.26 | ||||||
Maximum of Months | 677.52 | 919.59 | 7748.81 | 7998.14 | 0.00 | 0.00 | 0.00 | 33.20 | 1517.91 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 772.35 | 13-JAN-01:00 | 372.23 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.62 | 17-FEB-04:52 | 955.93 | 27-FEB-13:30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.71 | 27-MAR-07:32 | 1831.81 | 26-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.78 | 01-APR-00:45 | 1855.48 | 27-APR-13:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.78 | 22-MAY-03:30 | 1993.15 | 31-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.88 | 07-JUN-01:00 | 2036.48 | 08-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.15 | 11-JUL-24:00 | 2107.38 | 23-JUL-12:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.75 | 22-AUG-05:10 | 1903.87 | 09-AUG-13:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.07 | 19-SEP-01:55 | 1300.34 | 07-SEP-12:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.48 | 31-OCT-08:00 | 800.29 | 22-OCT-12:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 759.15 | 18-NOV-03:32 | 511.89 | 06-NOV-14:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 802.24 | 23-DEC-01:53 | 125.14 | 27-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.15 | 125.14 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.71 | 2107.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33463.57 | 12-JAN-04:41 | 0.00 | 1225.31 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.29 |
February | 30223.13 | 27-FEB-04:50 | 0.00 | 1225.31 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20294.33 | 01-MAR-00:01 | 5252.67 | 1225.31 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.38 |
April | 14668.15 | 02-APR-23:01 | 5252.67 | 1225.31 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.23 |
May | 7241.48 | 11-MAY-04:01 | 5252.67 | 1034.71 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.56 |
June | 11665.19 | 30-JUN-04:01 | 5252.67 | 914.90 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 |
July | 11886.99 | 25-JUL-04:01 | 5252.67 | 1274.33 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 |
August | 10675.03 | 11-AUG-17:05 | 16808.53 | 823.41 | 6505.25 | 0.00 | 0.00 | 0.00 | 0.00 | 962.86 | 0.00 |
September | 8282.86 | 28-SEP-23:01 | 4202.13 | 980.25 | 3252.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.16 |
October | 15103.06 | 26-OCT-23:01 | 5252.67 | 1225.31 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.04 |
November | 20275.88 | 29-NOV-00:01 | 5252.67 | 1225.31 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26222.91 | 15-DEC-04:50 | 0.00 | 1225.31 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7241.48 | 0.00 | 823.41 | 3252.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33463.57 | 16808.53 | 1274.33 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 962.86 | 148.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 71917.55 | 13-JAN-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 66378.85 | 22-FEB-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 64131.37 | 01-MAR-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 55526.94 | 03-APR-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 107.38 |
May | 40949.21 | 23-MAY-03:31 | 0.00 | 1226.07 | 19708.49 | 11031.91 | 0.00 | 0.00 | 0.00 | 0.00 | 126.83 |
June | 46511.44 | 02-JUN-03:41 | 0.00 | 1379.33 | 22172.05 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 121.78 |
July | 40459.70 | 21-JUL-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 4.29 |
August | 42144.37 | 11-AUG-04:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 67.60 |
September | 36425.07 | 30-SEP-04:01 | 0.00 | 1532.59 | 39979.31 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 58.20 |
October | 54293.75 | 22-OCT-04:01 | 0.00 | 1532.59 | 39979.31 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 101.36 |
November | 66427.43 | 28-NOV-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 72553.67 | 15-DEC-05:01 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36425.07 | 0.00 | 1226.07 | 19708.49 | 11031.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72553.67 | 376.40 | 2043.53 | 40080.91 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 126.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.95 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.59 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.82 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.87 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.64 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.93 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.66 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.91 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.73 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.75 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.97 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 716.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 716.24 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.446208E+11 | 26634.71 | 02-JAN-11:09 | 0.262091E+12 | 208984.72 | 12-JAN-13:20 |
February | 0.395077E+11 | 24291.06 | 09-FEB-11:20 | 0.220463E+12 | 186432.78 | 27-FEB-11:20 |
March | 0.428931E+11 | 24294.80 | 22-MAR-10:20 | 0.205603E+12 | 150585.04 | 01-MAR-08:30 |
April | 0.406068E+11 | 24297.00 | 28-APR-10:20 | 0.122046E+12 | 126448.39 | 03-APR-07:10 |
May | 0.418095E+11 | 24412.29 | 31-MAY-10:09 | 0.735195E+11 | 79592.09 | 27-MAY-10:09 |
June | 0.420644E+11 | 28135.47 | 30-JUN-10:00 | 0.611856E+11 | 54690.24 | 25-JUN-10:20 |
July | 0.450256E+11 | 28771.23 | 22-JUL-10:20 | 0.623262E+11 | 54508.89 | 05-JUL-10:39 |
August | 0.439113E+11 | 26199.42 | 11-AUG-16:10 | 0.645455E+11 | 60534.71 | 31-AUG-06:19 |
September | 0.414305E+11 | 24339.08 | 01-SEP-10:20 | 0.848160E+11 | 88710.87 | 29-SEP-10:09 |
October | 0.433917E+11 | 24313.80 | 02-OCT-10:20 | 0.152528E+12 | 135416.77 | 27-OCT-10:09 |
November | 0.428693E+11 | 24486.64 | 29-NOV-11:09 | 0.248822E+12 | 170872.71 | 28-NOV-11:20 |
December | 0.450053E+11 | 26635.78 | 26-DEC-11:20 | 0.270739E+12 | 194885.53 | 15-DEC-13:20 |
Annual Sum or Average | 0.513136E+12 | 0.182869E+13 | ||||
Minimum of Months | 0.395077E+11 | 24291.06 | 0.611856E+11 | 54508.89 | ||
Maximum of Months | 0.450256E+11 | 28771.23 | 0.270739E+12 | 208984.72 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.272536E+10 | 0.396365E+10 | 0.234911E+11 | 0.00 | 0.944662E+10 | 0.79 | 0.00 | 222667.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236526E+10 | 0.289948E+10 | 0.212178E+11 | 0.00 | 0.851243E+10 | 0.72 | 0.00 | 74719.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.254522E+10 | 0.243959E+10 | 0.234913E+11 | 0.00 | 0.940853E+10 | 0.80 | 0.00 | 180249.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.232808E+10 | 0.161188E+10 | 0.227333E+11 | 0.00 | 0.904619E+10 | 0.77 | 0.00 | 953532.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.237789E+10 | 0.101003E+10 | 0.234912E+11 | 0.00 | 0.955253E+10 | 0.80 | 0.00 | 89803264.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.228632E+10 | 0.532417E+09 | 0.227335E+11 | 0.00 | 0.946926E+10 | 0.77 | 0.00 | 0.164489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.233733E+10 | 0.755634E+09 | 0.234911E+11 | 0.00 | 0.980361E+10 | 0.79 | 0.00 | 0.301894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.242805E+10 | 0.136703E+10 | 0.234913E+11 | 0.00 | 0.976951E+10 | 0.80 | 0.00 | 0.132561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.240305E+10 | 0.203713E+10 | 0.227333E+11 | 0.00 | 0.922613E+10 | 0.77 | 0.00 | 3765196.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.256309E+10 | 0.287783E+10 | 0.234911E+11 | 0.00 | 0.940719E+10 | 0.79 | 0.00 | 1371377.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.258411E+10 | 0.355017E+10 | 0.227334E+11 | 0.00 | 0.916385E+10 | 0.77 | 0.00 | 326795.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.278588E+10 | 0.427458E+10 | 0.234911E+11 | 0.00 | 0.945745E+10 | 0.79 | 0.00 | 146564.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297296E+11 | 0.273194E+11 | 0.276589E+12 | 0.00 | 0.112263E+12 | 9.37 | 0.00 | 0.608628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.228632E+10 | 0.532417E+09 | 0.212178E+11 | 0.00 | 0.851243E+10 | 0.72 | 0.00 | 74719.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.278588E+10 | 0.427458E+10 | 0.234913E+11 | 0.00 | 0.980361E+10 | 0.80 | 0.00 | 0.301894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.198536E+12 | 0.00 | 0.230292E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.163058E+12 | 0.00 | 0.208019E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.142005E+12 | 0.00 | 0.230721E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.605566E+11 | 0.00 | 0.222712E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.101523E+11 | 0.00 | 0.228415E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.630850E+09 | 0.00 | 0.213363E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 0.531516E+09 | 0.00 | 0.212690E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 0.313070E+10 | 0.00 | 0.208891E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.254090E+11 | 0.00 | 0.201885E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.907564E+11 | 0.00 | 0.212463E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.188385E+12 | 0.00 | 0.212181E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.207524E+12 | 0.00 | 0.226895E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.109067E+13 | 0.00 | 0.260853E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.531516E+09 | 0.00 | 0.201885E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.207524E+12 | 0.00 | 0.230721E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1654.77 | 02-JAN-10:09 | 2040.24 | 01-JAN-00:10 | 14413.88 | 01-JAN-11:09 | 0.00 | 4158.82 | 01-JAN-06:19 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 1654.77 | 01-FEB-15:20 | 2040.24 | 01-FEB-00:10 | 14413.88 | 01-FEB-11:09 | 0.00 | 4158.82 | 01-FEB-16:30 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 1654.77 | 01-MAR-17:19 | 2040.24 | 01-MAR-00:10 | 14413.88 | 01-MAR-11:09 | 0.00 | 4158.82 | 02-MAR-14:09 | 0.00 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 1654.77 | 01-APR-19:40 | 2040.24 | 01-APR-05:10 | 14413.88 | 01-APR-10:09 | 0.00 | 4158.82 | 02-APR-04:00 | 0.00 | 01-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 1654.77 | 01-MAY-20:30 | 2040.24 | 01-MAY-21:10 | 14413.88 | 01-MAY-10:09 | 0.00 | 4158.82 | 02-MAY-20:49 | 0.00 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 1654.77 | 02-JUN-20:00 | 2040.24 | 01-JUN-22:49 | 14413.88 | 01-JUN-10:09 | 0.00 | 4158.82 | 01-JUN-04:49 | 0.00 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 1654.77 | 25-JUL-20:00 | 2040.24 | 01-JUL-23:19 | 14413.88 | 01-JUL-10:09 | 0.00 | 4158.82 | 01-JUL-04:19 | 0.00 | 01-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 1654.77 | 02-AUG-20:40 | 2040.24 | 01-AUG-21:00 | 14413.88 | 01-AUG-10:09 | 0.00 | 4158.82 | 02-AUG-04:19 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 1654.77 | 01-SEP-19:10 | 2040.24 | 01-SEP-05:10 | 14413.88 | 01-SEP-10:09 | 0.00 | 4158.82 | 01-SEP-04:49 | 0.00 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 1654.77 | 02-OCT-17:19 | 2040.24 | 01-OCT-05:10 | 14413.88 | 01-OCT-10:09 | 0.00 | 4158.82 | 02-OCT-18:10 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 1654.77 | 01-NOV-09:09 | 2040.24 | 01-NOV-05:10 | 14413.88 | 01-NOV-10:09 | 0.00 | 4158.82 | 02-NOV-08:09 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 1654.77 | 01-DEC-10:09 | 2040.24 | 01-DEC-00:10 | 14413.88 | 01-DEC-11:09 | 0.00 | 4158.82 | 14-DEC-05:00 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1654.77 | 2040.24 | 14413.88 | 0.00 | 4158.82 | 0.00 | 0.00 | ||||||
Maximum of Months | 1654.77 | 2040.24 | 14413.88 | 0.00 | 4158.82 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 69.76 | 24-JAN-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 63.73 | 03-FEB-04:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 101.35 | 17-MAR-03:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 161.42 | 28-APR-03:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2970.41 | 31-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7024.26 | 30-JUN-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8105.39 | 29-JUL-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5853.19 | 11-AUG-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 251.21 | 22-SEP-03:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 161.33 | 10-OCT-03:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84.34 | 17-NOV-04:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 67.80 | 26-DEC-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 63.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8105.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 26634.71 | 02-JAN-11:09 | 1654.77 | 14413.88 | 2040.24 | 0.00 | 4158.82 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24291.06 | 09-FEB-11:20 | 1331.29 | 14413.88 | 0.00 | 0.00 | 4158.82 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24294.80 | 22-MAR-10:20 | 1331.29 | 14413.88 | 0.00 | 0.00 | 4158.82 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24297.00 | 28-APR-10:20 | 1331.29 | 14413.88 | 0.00 | 0.00 | 4158.82 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24412.29 | 31-MAY-10:09 | 1331.29 | 14413.88 | 0.00 | 0.00 | 4158.82 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28135.47 | 30-JUN-10:00 | 1331.29 | 14413.88 | 0.00 | 0.00 | 4158.82 | 0.00 | 0.00 | 5313.83 | 0.00 |
July | 28771.23 | 22-JUL-10:20 | 1183.37 | 14413.88 | 0.00 | 0.00 | 4158.82 | 0.00 | 0.00 | 4467.78 | 0.00 |
August | 26199.42 | 11-AUG-16:10 | 1331.29 | 13064.26 | 0.00 | 0.00 | 4158.82 | 0.00 | 0.00 | 5605.26 | 0.00 |
September | 24339.08 | 01-SEP-10:20 | 1331.29 | 14413.88 | 0.00 | 0.00 | 4158.82 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24313.80 | 02-OCT-10:20 | 1331.29 | 14413.88 | 0.00 | 0.00 | 4158.82 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24486.64 | 29-NOV-11:09 | 1546.95 | 14413.88 | 0.00 | 0.00 | 4158.82 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26635.78 | 26-DEC-11:20 | 1654.77 | 14413.88 | 2040.24 | 0.00 | 4158.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 24291.06 | 1183.37 | 13064.26 | 0.00 | 0.00 | 4158.82 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28771.23 | 1654.77 | 14413.88 | 2040.24 | 0.00 | 4158.82 | 0.00 | 0.00 | 5605.26 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 163048.89 | 12-JAN-20:00 | 0.00 | 33363.77 | 03-JAN-13:20 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 143921.25 | 27-FEB-07:10 | 0.00 | 33360.71 | 17-FEB-13:20 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 125829.80 | 01-MAR-07:10 | 0.00 | 33361.32 | 29-MAR-12:20 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 102258.13 | 03-APR-06:10 | 0.00 | 33361.38 | 03-APR-12:20 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 38467.76 | 27-MAY-06:00 | 0.00 | 33303.62 | 03-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 13423.84 | 02-JUN-04:10 | 0.00 | 29952.16 | 02-JUN-12:30 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 9857.99 | 05-JUL-06:10 | 0.00 | 28419.77 | 01-JUL-12:00 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 39715.00 | 31-AUG-06:10 | 0.00 | 28130.19 | 01-AUG-12:00 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 53505.49 | 30-SEP-06:10 | 0.00 | 28100.12 | 30-SEP-12:00 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 101653.01 | 22-OCT-06:10 | 0.00 | 28351.64 | 31-OCT-12:50 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 133711.89 | 30-NOV-20:00 | 0.00 | 28759.48 | 27-NOV-13:30 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 148987.76 | 15-DEC-12:39 | 0.00 | 33360.59 | 29-DEC-13:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 9857.99 | 0.00 | 28100.12 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 163048.89 | 0.00 | 33363.77 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.17 | 18.98 | 0.17 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
February | 24.50 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
March | 23.83 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
April | 10.00 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 |
May | 0.67 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.51 | 0.00 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.54 | 0.00 | 24.54 |
September | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
October | 10.67 | 19.81 | 0.00 | 19.81 | 0.00 | 19.81 | 0.00 | 19.81 |
November | 31.33 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
December | 31.50 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
Annual Sum or Average | 161.83 | 19.14 | 0.17 | 19.13 | 8.67 | 19.41 | 0.00 | 19.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 | 0.00 | 18.88 |
Maximum of Months | 31.50 | 20.53 | 0.17 | 20.53 | 5.00 | 24.54 | 0.00 | 24.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.81 | 0.00 | 26.81 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.79 | 0.00 | 26.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.80 | 0.00 | 26.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.05 | 0.00 | 27.05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.43 | 0.00 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 28.23 | 0.00 | 28.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 28.39 | 0.00 | 28.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 28.25 | 0.00 | 28.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.26 | 0.00 | 27.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.13 | 0.00 | 27.13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.94 | 0.00 | 26.94 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.81 | 0.00 | 26.81 |
Annual Sum or Average | 0.00 | 0.00 | 123.33 | 27.98 | 0.00 | 27.98 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.79 | 0.00 | 26.79 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 28.39 | 0.00 | 28.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.83 | 610.00 | 20.83 | 610.00 | 20.83 |
February | 551.00 | 20.84 | 538.33 | 20.83 | 538.33 | 20.83 |
March | 612.00 | 20.84 | 449.67 | 20.80 | 449.67 | 20.78 |
April | 586.83 | 20.95 | 186.17 | 20.81 | 186.17 | 20.73 |
May | 492.00 | 21.46 | 35.33 | 21.37 | 29.00 | 21.27 |
June | 223.17 | 21.82 | 231.17 | 22.87 | 0.67 | 22.87 |
July | 175.50 | 21.77 | 389.67 | 23.21 | 5.33 | 23.21 |
August | 287.50 | 21.54 | 254.50 | 22.61 | 2.50 | 22.59 |
September | 557.50 | 21.14 | 39.83 | 21.03 | 38.33 | 20.93 |
October | 610.00 | 20.87 | 243.00 | 20.77 | 243.00 | 20.71 |
November | 591.00 | 20.84 | 588.00 | 20.83 | 588.00 | 20.83 |
December | 609.00 | 20.83 | 609.00 | 20.83 | 609.00 | 20.83 |
Annual Sum or Average | 5905.50 | 21.03 | 4174.67 | 21.18 | 3300.00 | 21.07 |
Minimum of Months | 175.50 | 20.83 | 35.33 | 20.77 | 0.67 | 20.71 |
Maximum of Months | 612.00 | 21.82 | 610.00 | 23.21 | 610.00 | 23.21 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 18.72 | 609.33 | 18.72 | 609.33 | 18.72 |
February | 551.00 | 18.72 | 539.33 | 18.72 | 539.33 | 18.72 |
March | 612.00 | 18.73 | 557.17 | 18.72 | 557.17 | 18.71 |
April | 587.50 | 18.99 | 336.33 | 18.85 | 336.33 | 18.78 |
May | 427.50 | 20.03 | 200.00 | 20.89 | 80.00 | 20.75 |
June | 352.17 | 24.12 | 426.83 | 24.73 | 228.33 | 25.03 |
July | 416.17 | 24.76 | 491.33 | 25.03 | 326.83 | 25.28 |
August | 405.50 | 23.15 | 393.00 | 24.00 | 220.00 | 24.36 |
September | 512.33 | 19.30 | 111.33 | 19.40 | 73.67 | 19.24 |
October | 610.00 | 18.82 | 307.67 | 18.74 | 307.67 | 18.69 |
November | 591.00 | 18.72 | 586.17 | 18.72 | 586.17 | 18.72 |
December | 609.00 | 18.72 | 593.33 | 18.72 | 593.33 | 18.72 |
Annual Sum or Average | 6284.17 | 19.88 | 5151.83 | 20.17 | 4458.17 | 20.11 |
Minimum of Months | 352.17 | 18.72 | 111.33 | 18.72 | 73.67 | 18.69 |
Maximum of Months | 612.00 | 24.76 | 609.33 | 25.03 | 609.33 | 25.28 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.83449 | 11.20456 | -0.8107 | 19.57280 |
February | 551.00000 | 20.83685 | 12.46208 | -0.7792 | 18.65969 |
March | 612.00000 | 20.83926 | 13.76811 | -0.6723 | 15.57633 |
April | 590.00000 | 20.96223 | 18.97145 | -0.4789 | 11.27230 |
May | 611.00000 | 21.92827 | 27.39957 | -1.1853 | 37.14395 |
June | 592.00000 | 23.07388 | 39.89824 | -0.6569 | 16.84711 |
July | 609.00000 | 23.21846 | 48.22113 | -0.5270 | 13.75380 |
August | 612.00000 | 22.72390 | 44.17536 | -0.7256 | 19.98512 |
September | 590.00000 | 21.27629 | 34.53059 | -1.3766 | 45.11853 |
October | 610.00000 | 20.87304 | 21.84092 | -0.5294 | 11.87074 |
November | 591.00000 | 20.83552 | 10.36456 | -0.7587 | 17.88106 |
December | 609.00000 | 20.83480 | 10.23314 | -0.8118 | 19.59079 |
Annual Sum or Average | 7187.00000 | 21.52556 | 24.50772 | -0.7756 | 20.59820 |
Minimum of Months | 551.00000 | 20.83449 | 10.23314 | -1.3766 | 11.27230 |
Maximum of Months | 612.00000 | 23.21846 | 48.22113 | -0.4789 | 45.11853 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.72376 | 15.67455 | -0.8103 | 19.39348 |
February | 551.00000 | 18.72399 | 17.51838 | -0.8106 | 19.47528 |
March | 612.00000 | 18.72525 | 19.28894 | -0.7759 | 18.34204 |
April | 590.00000 | 19.00879 | 25.12641 | -0.6334 | 14.91687 |
May | 611.00000 | 21.28185 | 31.64905 | -1.0788 | 37.67391 |
June | 592.00000 | 24.05373 | 40.59656 | -0.0899 | 14.06533 |
July | 609.00000 | 24.39325 | 47.41812 | 0.10077 | 14.19745 |
August | 612.00000 | 23.27970 | 45.09213 | -0.2664 | 19.43691 |
September | 590.00000 | 19.80648 | 39.81915 | -1.4500 | 50.12122 |
October | 610.00000 | 18.81994 | 27.31412 | -0.6308 | 14.24728 |
November | 591.00000 | 18.72414 | 14.98743 | -0.7763 | 18.25913 |
December | 609.00000 | 18.72305 | 14.47763 | -0.8048 | 19.19823 |
Annual Sum or Average | 7187.00000 | 20.36920 | 28.31747 | -0.6669 | 21.59726 |
Minimum of Months | 551.00000 | 18.72305 | 14.47763 | -1.4500 | 14.06533 |
Maximum of Months | 612.00000 | 24.39325 | 47.41812 | 0.10077 | 50.12122 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 |
May | 0.153743E+09 | 44530438.60 | 23.75 | 0.153743E+09 | -0.0 | 0.00 | 0.50 | 31-MAY-16:05 | 0.00 | 01-MAY-00:01 | 5890.99 | 31-MAY-16:05 | 5890.99 | 31-MAY-16:05 | 0.00 | 31-MAY-17:13 | 1614.13 | 31-MAY-16:05 | 0.00 | 01-MAY-00:01 |
June | 0.292671E+10 | 0.780567E+09 | 174.78 | 0.285346E+10 | 73250110.63 | 0.00 | 1.00 | 30-JUN-11:32 | 0.00 | 01-JUN-00:01 | 15810.87 | 30-JUN-12:00 | 13202.83 | 20-JUN-17:55 | 3217.69 | 30-JUN-12:00 | 3698.71 | 30-JUN-12:00 | 0.00 | 01-JUN-00:01 |
July | 0.547861E+10 | 0.142709E+10 | 232.68 | 0.525657E+10 | 0.222042E+09 | 0.00 | 1.00 | 21-JUL-16:03 | 0.00 | 01-JUL-00:01 | 17149.89 | 29-JUL-17:10 | 15915.50 | 29-JUL-17:10 | 2658.80 | 29-JUL-19:00 | 4097.03 | 29-JUL-17:10 | 0.00 | 01-JUL-00:01 |
August | 0.231684E+10 | 0.625331E+09 | 136.76 | 0.224876E+10 | 68080719.31 | 0.00 | 0.97 | 11-AUG-17:05 | 0.00 | 01-AUG-00:01 | 13112.65 | 11-AUG-17:05 | 13112.65 | 11-AUG-17:05 | 3065.60 | 13-AUG-00:09 | 3153.92 | 11-AUG-17:05 | 0.00 | 01-AUG-00:01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.108759E+11 | 0.287752E+10 | 567.96 | 0.105125E+11 | 0.363373E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.547861E+10 | 0.142709E+10 | 232.68 | 0.525657E+10 | 0.222042E+09 | 0.00 | 1.00 | 0.00 | 17149.89 | 15915.50 | 3217.69 | 4097.03 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 730650.72 | 222667.98 | 0.49 | 623179.93 | 107470.79 | 0.00 | 0.10 | 17-JAN-04:15 | 0.00 | 01-JAN-00:01 | 890.82 | 17-JAN-04:15 | 672.69 | 17-JAN-04:15 | 218.13 | 17-JAN-04:15 | 269.06 | 17-JAN-04:15 | 0.00 | 01-JAN-00:01 |
February | 246358.00 | 74719.93 | 0.14 | 203570.50 | 42787.50 | 0.00 | 0.11 | 17-FEB-04:47 | 0.00 | 01-FEB-00:01 | 980.67 | 17-FEB-04:47 | 916.90 | 17-FEB-04:47 | 180.70 | 03-FEB-04:15 | 295.52 | 17-FEB-04:47 | 0.00 | 01-FEB-00:01 |
March | 590663.73 | 180249.77 | 0.39 | 500908.11 | 89755.62 | 0.00 | 0.08 | 17-MAR-03:27 | 0.00 | 01-MAR-00:01 | 752.25 | 17-MAR-03:27 | 651.66 | 17-MAR-03:27 | 108.83 | 24-MAR-03:30 | 228.02 | 17-MAR-03:27 | 0.00 | 01-MAR-00:01 |
April | 3174018.42 | 953532.93 | 1.20 | 2543052.61 | 630965.81 | 0.00 | 0.24 | 28-APR-03:08 | 0.00 | 01-APR-00:01 | 2210.01 | 28-APR-03:08 | 1636.30 | 28-APR-03:08 | 573.71 | 28-APR-03:08 | 645.68 | 28-APR-03:08 | 0.00 | 01-APR-00:01 |
May | 0.156436E+09 | 45272825.58 | 29.40 | 0.154270E+09 | 2165959.05 | 0.00 | 1.00 | 23-MAY-03:31 | 0.00 | 01-MAY-00:01 | 22438.04 | 23-MAY-03:31 | 17085.35 | 23-MAY-03:31 | 5352.70 | 23-MAY-03:31 | 5379.50 | 23-MAY-03:31 | 0.00 | 01-MAY-00:01 |
June | 0.331218E+10 | 0.864320E+09 | 197.50 | 0.319871E+10 | 0.113461E+09 | 0.00 | 1.00 | 02-JUN-03:41 | 0.00 | 01-JUN-00:01 | 22438.04 | 27-JUN-03:21 | 20735.16 | 24-JUN-00:42 | 10754.46 | 24-JUN-04:01 | 5379.50 | 02-JUN-03:41 | 0.00 | 01-JUN-00:01 |
July | 0.626364E+10 | 0.159185E+10 | 257.93 | 0.589525E+10 | 0.368393E+09 | 0.00 | 1.00 | 01-JUL-03:21 | 0.00 | 01-JUL-00:01 | 22438.04 | 09-JUL-04:01 | 19862.09 | 13-JUL-00:42 | 12478.74 | 16-JUL-03:22 | 5379.50 | 01-JUL-03:21 | 0.00 | 01-JUL-00:01 |
August | 0.263381E+10 | 0.700276E+09 | 158.44 | 0.243895E+10 | 0.194861E+09 | 0.00 | 1.00 | 01-AUG-00:42 | 0.00 | 01-AUG-00:01 | 22438.04 | 13-AUG-01:22 | 19218.48 | 12-AUG-00:42 | 12125.80 | 13-AUG-00:42 | 5379.50 | 01-AUG-00:42 | 0.00 | 01-AUG-00:01 |
September | 12465511.67 | 3765196.82 | 5.84 | 8410947.97 | 4054563.71 | 0.00 | 0.22 | 26-SEP-03:05 | 0.00 | 01-SEP-00:01 | 2060.36 | 26-SEP-03:05 | 1618.43 | 26-SEP-03:05 | 553.80 | 05-SEP-03:17 | 604.20 | 26-SEP-03:05 | 0.00 | 01-SEP-00:01 |
October | 4557463.83 | 1371377.54 | 2.96 | 3347444.73 | 1210019.10 | 0.00 | 0.24 | 10-OCT-03:08 | 0.00 | 01-OCT-00:01 | 2208.69 | 10-OCT-03:08 | 1426.58 | 10-OCT-03:08 | 782.11 | 10-OCT-03:08 | 645.31 | 10-OCT-03:08 | 0.00 | 01-OCT-00:01 |
November | 1074766.67 | 326795.96 | 0.80 | 967885.81 | 106880.86 | 0.00 | 0.12 | 24-NOV-04:10 | 0.00 | 01-NOV-00:01 | 1044.27 | 24-NOV-04:10 | 893.15 | 24-NOV-04:10 | 151.13 | 24-NOV-04:10 | 314.17 | 24-NOV-04:10 | 0.00 | 01-NOV-00:01 |
December | 484225.07 | 146564.87 | 0.29 | 439817.96 | 44407.11 | 0.00 | 0.12 | 19-DEC-04:29 | 0.00 | 01-DEC-00:01 | 1047.61 | 19-DEC-04:29 | 1001.99 | 19-DEC-04:29 | 136.02 | 26-DEC-04:10 | 315.15 | 19-DEC-04:29 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.123894E+11 | 0.320876E+10 | 655.38 | 0.117042E+11 | 0.685168E+09 | 0.00 | ||||||||||||||
Minimum of Months | 246358.00 | 74719.93 | 0.14 | 203570.50 | 42787.50 | 0.00 | 0.08 | 0.00 | 752.25 | 651.66 | 108.83 | 228.02 | 0.00 | |||||||
Maximum of Months | 0.626364E+10 | 0.159185E+10 | 257.93 | 0.589525E+10 | 0.368393E+09 | 0.00 | 1.00 | 0.00 | 22438.04 | 20735.16 | 12478.74 | 5379.50 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.30 | 3.85 | 8.46 | 0.39 | 444.76 | 0.00 | 0.00 | 0.00 |
February | 68.11 | 32.45 | 35.66 | 27.19 | 372.44 | 0.00 | 0.00 | 0.00 |
March | 194.64 | 98.63 | 96.02 | 148.57 | 274.63 | 0.00 | 0.00 | 0.00 |
April | 267.64 | 135.52 | 132.12 | 232.44 | 146.95 | 0.00 | 0.00 | 0.00 |
May | 388.98 | 219.22 | 169.77 | 418.25 | 69.48 | 0.00 | 0.00 | 0.00 |
June | 357.65 | 166.77 | 190.88 | 397.14 | 35.74 | 0.00 | 0.00 | 0.00 |
July | 339.79 | 164.72 | 175.07 | 388.48 | 41.12 | 0.00 | 0.00 | 0.00 |
August | 269.19 | 131.08 | 138.11 | 290.18 | 65.15 | 0.00 | 0.00 | 0.00 |
September | 166.45 | 72.93 | 93.52 | 145.79 | 123.88 | 0.00 | 0.00 | 0.00 |
October | 87.83 | 35.22 | 52.60 | 53.89 | 241.44 | 0.00 | 0.00 | 0.00 |
November | 18.64 | 6.48 | 12.16 | 0.62 | 435.54 | 0.00 | 0.00 | 0.00 |
December | 2.66 | 0.63 | 2.03 | 0.00 | 476.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 181.85 | 89.35 | 92.50 | 176.26 | 226.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2.66 | 0.63 | 2.03 | 0.00 | 35.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 388.98 | 219.22 | 190.88 | 418.25 | 476.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.89 | 74.54 | 38.36 | 52.09 | 822.88 | 0.00 | 0.00 | 0.00 |
February | 388.11 | 270.35 | 117.76 | 291.81 | 653.84 | 0.00 | 0.00 | 0.00 |
March | 665.37 | 451.33 | 214.04 | 608.56 | 497.23 | 0.00 | 0.00 | 0.00 |
April | 810.39 | 504.11 | 306.28 | 863.18 | 312.42 | 0.00 | 0.00 | 0.00 |
May | 667.36 | 345.34 | 322.02 | 740.84 | 160.78 | 0.00 | 0.00 | 0.00 |
June | 609.20 | 249.11 | 360.09 | 692.62 | 90.72 | 0.00 | 0.00 | 0.00 |
July | 587.09 | 255.21 | 331.87 | 686.78 | 95.90 | 0.00 | 0.00 | 0.00 |
August | 608.53 | 335.24 | 273.30 | 697.29 | 141.90 | 0.00 | 0.00 | 0.00 |
September | 492.42 | 296.71 | 195.71 | 504.21 | 246.48 | 0.00 | 0.00 | 0.00 |
October | 355.11 | 225.61 | 129.50 | 295.00 | 436.65 | 0.00 | 0.00 | 0.00 |
November | 190.71 | 133.39 | 57.32 | 101.86 | 771.29 | 0.00 | 0.00 | 0.00 |
December | 33.88 | 23.93 | 9.95 | 3.60 | 917.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 459.96 | 263.33 | 196.63 | 462.02 | 427.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.88 | 23.93 | 9.95 | 3.60 | 90.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 810.39 | 504.11 | 360.09 | 863.18 | 917.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 6.48 | 1.14 | 5.33 | 0.00 | 451.17 | 0.00 | 0.00 | 0.00 |
February | 38.25 | 13.25 | 25.00 | 4.31 | 387.59 | 0.00 | 0.00 | 0.00 |
March | 114.99 | 49.40 | 65.59 | 55.08 | 286.36 | 0.00 | 0.00 | 0.00 |
April | 273.26 | 141.73 | 131.53 | 248.73 | 156.60 | 0.00 | 0.00 | 0.00 |
May | 265.68 | 121.12 | 144.56 | 261.87 | 74.53 | 0.00 | 0.00 | 0.00 |
June | 291.10 | 124.22 | 166.87 | 313.82 | 41.72 | 0.00 | 0.00 | 0.00 |
July | 243.54 | 92.21 | 151.33 | 264.90 | 45.31 | 0.00 | 0.00 | 0.00 |
August | 200.17 | 84.83 | 115.34 | 202.68 | 68.85 | 0.00 | 0.00 | 0.00 |
September | 121.09 | 50.72 | 70.37 | 91.27 | 128.97 | 0.00 | 0.00 | 0.00 |
October | 47.35 | 14.19 | 33.16 | 13.31 | 254.32 | 0.00 | 0.00 | 0.00 |
November | 18.92 | 6.84 | 12.08 | 0.92 | 433.60 | 0.00 | 0.00 | 0.00 |
December | 1.70 | 0.18 | 1.52 | 0.00 | 477.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 135.56 | 58.44 | 77.12 | 121.91 | 233.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.70 | 0.18 | 1.52 | 0.00 | 41.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 291.10 | 141.73 | 166.87 | 313.82 | 477.69 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 32956552.35 | 10300745.50 | 22655806.86 | 1050410.29 | 0.119125E+10 |
February | 0.164761E+09 | 78502426.20 | 86258605.30 | 65778746.72 | 0.901003E+09 |
March | 0.521325E+09 | 0.264157E+09 | 0.257168E+09 | 0.397940E+09 | 0.735576E+09 |
April | 0.693725E+09 | 0.351279E+09 | 0.342446E+09 | 0.602472E+09 | 0.380892E+09 |
May | 0.104186E+10 | 0.587157E+09 | 0.454700E+09 | 0.112025E+10 | 0.186101E+09 |
June | 0.927020E+09 | 0.432259E+09 | 0.494760E+09 | 0.102939E+10 | 92638794.52 |
July | 0.910095E+09 | 0.441187E+09 | 0.468908E+09 | 0.104050E+10 | 0.110127E+09 |
August | 0.721010E+09 | 0.351091E+09 | 0.369919E+09 | 0.777217E+09 | 0.174494E+09 |
September | 0.431426E+09 | 0.189024E+09 | 0.242402E+09 | 0.377885E+09 | 0.321101E+09 |
October | 0.235233E+09 | 94341145.98 | 0.140892E+09 | 0.144345E+09 | 0.646664E+09 |
November | 48303415.47 | 16790311.22 | 31513104.24 | 1607963.95 | 0.112891E+10 |
December | 7123641.90 | 1684291.69 | 5439350.21 | 0.00 | 0.127693E+10 |
Annual Sum or Average | 0.573484E+10 | 0.281777E+10 | 0.291706E+10 | 0.555843E+10 | 0.714569E+10 |
Minimum of Months | 7123641.90 | 1684291.69 | 5439350.21 | 0.00 | 92638794.52 |
Maximum of Months | 0.104186E+10 | 0.587157E+09 | 0.494760E+09 | 0.112025E+10 | 0.127693E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302370E+09 | 0.199635E+09 | 0.102735E+09 | 0.139524E+09 | 0.220400E+10 |
February | 0.938921E+09 | 0.654026E+09 | 0.284894E+09 | 0.705942E+09 | 0.158177E+10 |
March | 0.178213E+10 | 0.120883E+10 | 0.573298E+09 | 0.162998E+10 | 0.133179E+10 |
April | 0.210053E+10 | 0.130665E+10 | 0.793878E+09 | 0.223737E+10 | 0.809801E+09 |
May | 0.178746E+10 | 0.924956E+09 | 0.862504E+09 | 0.198425E+10 | 0.430631E+09 |
June | 0.157905E+10 | 0.645695E+09 | 0.933356E+09 | 0.179527E+10 | 0.235156E+09 |
July | 0.157245E+10 | 0.683565E+09 | 0.888884E+09 | 0.183947E+10 | 0.256871E+09 |
August | 0.162990E+10 | 0.897900E+09 | 0.731997E+09 | 0.186763E+10 | 0.380068E+09 |
September | 0.127636E+10 | 0.769077E+09 | 0.507284E+09 | 0.130692E+10 | 0.638864E+09 |
October | 0.951130E+09 | 0.604284E+09 | 0.346846E+09 | 0.790136E+09 | 0.116953E+10 |
November | 0.494323E+09 | 0.345760E+09 | 0.148563E+09 | 0.264014E+09 | 0.199919E+10 |
December | 90738074.75 | 64084305.33 | 26653769.41 | 9643587.37 | 0.245642E+10 |
Annual Sum or Average | 0.145054E+11 | 0.830447E+10 | 0.620089E+10 | 0.145702E+11 | 0.134941E+11 |
Minimum of Months | 90738074.75 | 64084305.33 | 26653769.41 | 9643587.37 | 0.235156E+09 |
Maximum of Months | 0.210053E+10 | 0.130665E+10 | 0.933356E+09 | 0.223737E+10 | 0.245642E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 17348358.27 | 3061057.55 | 14287300.71 | 0.00 | 0.120841E+10 |
February | 92538973.13 | 32056291.98 | 60482681.15 | 10429356.53 | 0.937659E+09 |
March | 0.307982E+09 | 0.132308E+09 | 0.175674E+09 | 0.147523E+09 | 0.766990E+09 |
April | 0.708292E+09 | 0.367376E+09 | 0.340916E+09 | 0.644700E+09 | 0.405916E+09 |
May | 0.711598E+09 | 0.324411E+09 | 0.387187E+09 | 0.701385E+09 | 0.199634E+09 |
June | 0.754524E+09 | 0.321986E+09 | 0.432538E+09 | 0.813433E+09 | 0.108142E+09 |
July | 0.652299E+09 | 0.246968E+09 | 0.405331E+09 | 0.709497E+09 | 0.121359E+09 |
August | 0.536148E+09 | 0.227218E+09 | 0.308930E+09 | 0.542854E+09 | 0.184405E+09 |
September | 0.313861E+09 | 0.131456E+09 | 0.182405E+09 | 0.236563E+09 | 0.334294E+09 |
October | 0.126834E+09 | 38015693.47 | 88818625.12 | 35658711.32 | 0.681164E+09 |
November | 49040540.71 | 17733514.85 | 31307025.86 | 2385838.20 | 0.112390E+10 |
December | 4552386.95 | 470133.49 | 4082253.46 | 0.00 | 0.127946E+10 |
Annual Sum or Average | 0.427502E+10 | 0.184306E+10 | 0.243196E+10 | 0.384443E+10 | 0.735133E+10 |
Minimum of Months | 4552386.95 | 470133.49 | 4082253.46 | 0.00 | 0.108142E+09 |
Maximum of Months | 0.754524E+09 | 0.367376E+09 | 0.432538E+09 | 0.813433E+09 | 0.127946E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 24.17 | 1690.50 | 131.67 | 79.52 | 52.15 | 0.00 | 0.00 |
February | 245.74 | 1336.30 | 494.47 | 316.05 | 178.42 | 0.00 | 0.00 |
March | 738.10 | 984.11 | 975.00 | 599.35 | 375.65 | 0.00 | 0.00 |
April | 1287.35 | 558.98 | 1351.29 | 781.37 | 569.92 | 0.00 | 0.00 |
May | 1384.19 | 268.03 | 1322.03 | 685.68 | 636.35 | 0.00 | 0.00 |
June | 1380.81 | 145.41 | 1257.95 | 540.10 | 717.85 | 0.00 | 0.00 |
July | 1324.26 | 166.45 | 1170.42 | 512.14 | 658.27 | 0.00 | 0.00 |
August | 1169.70 | 255.44 | 1077.90 | 551.15 | 526.75 | 0.00 | 0.00 |
September | 714.25 | 472.31 | 779.96 | 420.35 | 359.60 | 0.00 | 0.00 |
October | 320.45 | 890.64 | 490.29 | 275.03 | 215.26 | 0.00 | 0.00 |
November | 55.84 | 1592.87 | 228.27 | 146.71 | 81.55 | 0.00 | 0.00 |
December | 0.00 | 1867.97 | 38.24 | 24.73 | 13.51 | 0.00 | 0.00 |
Annual Sum or Average | 722.78 | 850.20 | 777.37 | 411.13 | 366.25 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 145.41 | 38.24 | 24.73 | 13.51 | 0.00 | 0.00 |
Maximum of Months | 1384.19 | 1867.97 | 1351.29 | 781.37 | 717.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 64746269.81 | 0.452784E+10 | 0.352675E+09 | 0.212997E+09 | 0.139678E+09 | 0.00 | 0.00 |
February | 0.594505E+09 | 0.323278E+10 | 0.119622E+10 | 0.764585E+09 | 0.431636E+09 | 0.00 | 0.00 |
March | 0.197693E+10 | 0.263584E+10 | 0.261144E+10 | 0.160530E+10 | 0.100614E+10 | 0.00 | 0.00 |
April | 0.333681E+10 | 0.144888E+10 | 0.350254E+10 | 0.202530E+10 | 0.147724E+10 | 0.00 | 0.00 |
May | 0.370742E+10 | 0.717903E+09 | 0.354092E+10 | 0.183652E+10 | 0.170439E+10 | 0.00 | 0.00 |
June | 0.357906E+10 | 0.376899E+09 | 0.326060E+10 | 0.139994E+10 | 0.186065E+10 | 0.00 | 0.00 |
July | 0.354691E+10 | 0.445808E+09 | 0.313484E+10 | 0.137172E+10 | 0.176312E+10 | 0.00 | 0.00 |
August | 0.313291E+10 | 0.684179E+09 | 0.288706E+10 | 0.147621E+10 | 0.141085E+10 | 0.00 | 0.00 |
September | 0.185135E+10 | 0.122424E+10 | 0.202165E+10 | 0.108956E+10 | 0.932091E+09 | 0.00 | 0.00 |
October | 0.858282E+09 | 0.238550E+10 | 0.131320E+10 | 0.736641E+09 | 0.576556E+09 | 0.00 | 0.00 |
November | 0.144733E+09 | 0.412873E+10 | 0.591666E+09 | 0.380284E+09 | 0.211383E+09 | 0.00 | 0.00 |
December | 0.00 | 0.500317E+10 | 0.102414E+09 | 66238730.52 | 36175373.08 | 0.00 | 0.00 |
Annual Sum or Average | 0.227937E+11 | 0.268118E+11 | 0.245152E+11 | 0.129653E+11 | 0.115499E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.376899E+09 | 0.102414E+09 | 66238730.52 | 36175373.08 | 0.00 | 0.00 |
Maximum of Months | 0.370742E+10 | 0.500317E+10 | 0.354092E+10 | 0.202530E+10 | 0.186065E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.170495E+11 | -0.162504E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -799102486.7 | 58.99 | 0.00 | 0.00 |
February | 0.154005E+11 | -0.146781E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -722445329.8 | 58.99 | 0.00 | 0.00 |
March | 0.170837E+11 | -0.162844E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -799214328.9 | 58.99 | 0.00 | 0.00 |
April | 0.164865E+11 | -0.157202E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -766306961.5 | 58.99 | 0.00 | 0.00 |
May | 0.168959E+11 | -0.161465E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -749442807.3 | 59.00 | 0.00 | 0.00 |
June | 0.157326E+11 | -0.150550E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -677583102.4 | 58.99 | 0.00 | 0.00 |
July | 0.156236E+11 | -0.149293E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -694246326.6 | 58.99 | 0.00 | 0.00 |
August | 0.153193E+11 | -0.146063E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -713026901.1 | 58.99 | 0.00 | 0.00 |
September | 0.148047E+11 | -0.140555E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -749144714.6 | 58.99 | 0.00 | 0.00 |
October | 0.156079E+11 | -0.148147E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -793157746.8 | 58.98 | 0.00 | 0.00 |
November | 0.156374E+11 | -0.148660E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -771333128.1 | 58.99 | 0.00 | 0.00 |
December | 0.167725E+11 | -0.159741E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -798465681.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.192414E+12 | -0.183381E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.903347E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.148047E+11 | -0.162844E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -799214328.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.170837E+11 | -0.140555E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -677583102.4 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.68 | 0.56 | 03-JAN-11:30 | 315.75 | 9.04 | 0.00 | 73.50 | 320.41 | 8.85 | 0.00 | 73.50 |
February | 205.83 | 0.62 | 0.56 | 01-FEB-10:30 | 773.13 | 12.61 | 0.00 | 174.17 | 784.56 | 12.65 | 0.00 | 173.67 |
March | 329.50 | 0.59 | 0.56 | 01-MAR-09:20 | 4470.63 | 27.00 | 199.17 | 303.67 | 4427.41 | 26.76 | 194.50 | 303.67 |
April | 421.83 | 0.58 | 0.56 | 01-APR-06:00 | 6461.93 | 26.61 | 222.17 | 408.33 | 7591.47 | 28.43 | 254.83 | 407.17 |
May | 545.00 | 0.59 | 0.56 | 01-MAY-04:40 | 2338.20 | 16.81 | 52.33 | 498.00 | 2701.22 | 16.96 | 56.17 | 494.50 |
June | 583.50 | 0.59 | 0.56 | 01-JUN-03:20 | 2169.39 | 15.21 | 0.00 | 528.50 | 2379.84 | 16.45 | 48.17 | 524.83 |
July | 562.83 | 0.59 | 0.56 | 01-JUL-03:49 | 2190.86 | 15.78 | 13.33 | 518.17 | 2613.42 | 16.92 | 56.17 | 514.00 |
August | 467.17 | 0.58 | 0.56 | 01-AUG-04:40 | 4397.33 | 23.22 | 192.50 | 441.67 | 4519.36 | 23.07 | 198.67 | 444.00 |
September | 356.33 | 0.59 | 0.56 | 01-SEP-06:19 | 3421.47 | 25.58 | 215.00 | 331.00 | 3393.30 | 25.21 | 195.33 | 330.50 |
October | 265.50 | 0.60 | 0.56 | 01-OCT-07:30 | 852.87 | 13.82 | 0.00 | 241.33 | 882.09 | 13.66 | 0.00 | 240.50 |
November | 135.83 | 0.64 | 0.56 | 01-NOV-09:50 | 419.02 | 10.70 | 0.00 | 122.67 | 419.60 | 10.64 | 0.00 | 123.33 |
December | 71.17 | 0.85 | 0.56 | 04-DEC-10:00 | 105.17 | 4.67 | 0.00 | 8.17 | 105.95 | 4.44 | 0.00 | 8.17 |
Annual Sum or Average | 4053.17 | 0.60 | 2894.02 | 18.76 | 894.50 | 3649.17 | 3160.09 | 19.22 | 1003.83 | 3637.83 | ||
Minimum of Months | 71.17 | 0.58 | 0.56 | 105.17 | 4.67 | 0.00 | 8.17 | 105.95 | 4.44 | 0.00 | 8.17 | |
Maximum of Months | 583.50 | 0.85 | 0.56 | 6461.93 | 27.00 | 222.17 | 528.50 | 7591.47 | 28.43 | 254.83 | 524.83 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.716716E+11 | 64779.58 | 01-JAN-03:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.585571E+11 | 64779.58 | 01-FEB-03:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.512278E+11 | 64779.58 | 01-MAR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.220229E+11 | 64779.58 | 03-APR-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.445122E+10 | 23871.57 | 28-MAY-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.423288E+09 | 7878.15 | 25-JUN-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.371665E+09 | 5303.82 | 05-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147031E+10 | 14323.29 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104481E+11 | 19533.99 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336351E+11 | 64779.58 | 22-OCT-02:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.680985E+11 | 64779.58 | 06-NOV-04:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.749525E+11 | 64779.58 | 01-DEC-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.397330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.371665E+09 | 5303.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.749525E+11 | 64779.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.871569E+11 | 102944.37 | 12-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.718889E+11 | 99763.28 | 27-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.623761E+11 | 83389.61 | 01-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.264224E+11 | 57686.61 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.367060E+10 | 37768.87 | 28-MAY-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 81392378.12 | 14112.77 | 07-JUN-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 53547208.54 | 8145.75 | 06-JUL-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103425E+10 | 22353.56 | 31-AUG-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.987908E+10 | 28687.58 | 30-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.389700E+11 | 53006.08 | 22-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.826095E+11 | 73721.18 | 29-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.910667E+11 | 76645.45 | 15-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.475209E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 53547208.54 | 8145.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.910667E+11 | 102944.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.153743E+09 | 0.153743E+09 | 5890.99 | 31-MAY-16:05 | 5890.99 | 0.00 |
June | 0.00 | 0.00 | 0.292671E+10 | 0.285346E+10 | 15810.87 | 30-JUN-12:00 | 12593.18 | 0.00 |
July | 0.00 | 0.00 | 0.547861E+10 | 0.525657E+10 | 17149.89 | 29-JUL-17:10 | 15915.50 | 0.00 |
August | 0.00 | 0.00 | 0.231684E+10 | 0.224876E+10 | 13112.65 | 11-AUG-17:05 | 13112.65 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.108759E+11 | 0.105125E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.547861E+10 | 0.525657E+10 | 17149.89 | 15915.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 730650.72 | 623179.93 | 890.82 | 17-JAN-04:15 | 672.69 | 0.00 |
February | 0.00 | 0.00 | 246358.00 | 203570.50 | 980.67 | 17-FEB-04:47 | 916.90 | 0.00 |
March | 0.00 | 0.00 | 590663.73 | 500908.11 | 752.25 | 17-MAR-03:27 | 651.66 | 0.00 |
April | 0.00 | 0.00 | 3174018.42 | 2543052.61 | 2210.01 | 28-APR-03:08 | 1636.30 | 0.00 |
May | 0.00 | 0.00 | 0.156436E+09 | 0.154270E+09 | 22438.04 | 23-MAY-03:31 | 17085.35 | 0.00 |
June | 0.00 | 0.00 | 0.331218E+10 | 0.319871E+10 | 22438.04 | 27-JUN-03:21 | 13896.39 | 0.00 |
July | 0.00 | 0.00 | 0.626364E+10 | 0.589525E+10 | 22438.04 | 09-JUL-04:01 | 11495.01 | 0.00 |
August | 0.00 | 0.00 | 0.263381E+10 | 0.243895E+10 | 22438.04 | 13-AUG-01:22 | 10344.81 | 0.00 |
September | 0.00 | 0.00 | 12465511.67 | 8410947.97 | 2060.36 | 26-SEP-03:05 | 1618.43 | 0.00 |
October | 0.00 | 0.00 | 4557463.83 | 3347444.73 | 2208.69 | 10-OCT-03:08 | 1426.58 | 0.00 |
November | 0.00 | 0.00 | 1074766.67 | 967885.81 | 1044.27 | 24-NOV-04:10 | 893.15 | 0.00 |
December | 0.00 | 0.00 | 484225.07 | 439817.96 | 1047.61 | 19-DEC-04:29 | 1001.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.123894E+11 | 0.117042E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 246358.00 | 203570.50 | 752.25 | 651.66 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.626364E+10 | 0.589525E+10 | 22438.04 | 17085.35 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 6366.97 | 23784.70 | 03-JAN-13:15 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6366.85 | 23784.22 | 22-FEB-13:17 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 6381.07 | 23784.86 | 19-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6363.57 | 23785.72 | 04-APR-12:38 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6327.93 | 23785.58 | 02-MAY-12:38 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 6106.27 | 23162.07 | 01-JUN-12:40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 5867.01 | 22208.25 | 01-JUL-12:50 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 5749.13 | 21474.89 | 01-AUG-12:30 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5715.99 | 21341.48 | 30-SEP-12:35 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 5825.54 | 21971.10 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6032.25 | 22878.95 | 30-NOV-13:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 6261.44 | 23782.63 | 31-DEC-13:30 |
Annual Sum or Average | 0.00 | 6112.24 | ||||
Minimum of Months | 0.00 | 0.00 | 5715.99 | 21341.48 | ||
Maximum of Months | 0.00 | 0.00 | 6381.07 | 23785.72 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271744E+10 | 0.54 | 1211.87 | 01-JAN-00:01 | 0.65 |
February | 0.245200E+10 | 0.54 | 1211.87 | 01-FEB-00:01 | 0.65 |
March | 0.271581E+10 | 0.54 | 1211.87 | 01-MAR-00:01 | 0.65 |
April | 0.265061E+10 | 0.55 | 1211.87 | 01-APR-04:01 | 0.65 |
May | 0.294902E+10 | 0.59 | 1211.87 | 01-MAY-03:35 | 0.65 |
June | 0.299541E+10 | 0.61 | 1211.87 | 01-JUN-00:12 | 0.65 |
July | 0.309507E+10 | 0.61 | 1211.87 | 01-JUL-00:07 | 0.64 |
August | 0.308187E+10 | 0.61 | 1211.87 | 01-AUG-00:06 | 0.65 |
September | 0.283984E+10 | 0.58 | 1211.87 | 01-SEP-01:20 | 0.65 |
October | 0.278307E+10 | 0.56 | 1211.87 | 01-OCT-03:15 | 0.65 |
November | 0.264033E+10 | 0.55 | 1211.87 | 01-NOV-04:01 | 0.65 |
December | 0.271971E+10 | 0.55 | 1211.87 | 01-DEC-00:01 | 0.65 |
Annual Sum or Average | 0.336402E+11 | 0.57 | |||
Minimum of Months | 0.245200E+10 | 0.54 | 1211.87 | 0.64 | |
Maximum of Months | 0.309507E+10 | 0.61 | 1211.87 | 0.65 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.369760E+10 | 0.79 | 1588.90 | 01-JAN-06:20 | 0.90 |
February | 0.332233E+10 | 0.79 | 1588.90 | 01-FEB-16:30 | 0.90 |
March | 0.366120E+10 | 0.79 | 1588.90 | 01-MAR-00:04 | 0.90 |
April | 0.346028E+10 | 0.78 | 1588.90 | 01-APR-18:20 | 0.90 |
May | 0.354756E+10 | 0.75 | 1588.90 | 03-MAY-12:25 | 0.89 |
June | 0.344264E+10 | 0.77 | 1588.90 | 07-JUN-15:45 | 0.89 |
July | 0.356618E+10 | 0.79 | 1588.90 | 04-JUL-08:30 | 0.88 |
August | 0.356168E+10 | 0.78 | 1588.90 | 04-AUG-11:30 | 0.88 |
September | 0.343335E+10 | 0.75 | 1588.90 | 01-SEP-04:50 | 0.89 |
October | 0.358832E+10 | 0.78 | 1588.90 | 04-OCT-10:45 | 0.89 |
November | 0.358927E+10 | 0.79 | 1588.90 | 02-NOV-08:70 | 0.89 |
December | 0.370619E+10 | 0.79 | 1588.90 | 01-DEC-05:03 | 0.90 |
Annual Sum or Average | 0.425766E+11 | 0.78 | |||
Minimum of Months | 0.332233E+10 | 0.75 | 1588.90 | 0.88 | |
Maximum of Months | 0.370619E+10 | 0.79 | 1588.90 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.303158E+10 | 0.78 | 1358.05 | 07-JAN-09:30 | 0.93 |
February | 0.273810E+10 | 0.78 | 1358.05 | 10-FEB-13:00 | 0.93 |
March | 0.303153E+10 | 0.78 | 1358.05 | 03-MAR-14:40 | 0.93 |
April | 0.293530E+10 | 0.78 | 1358.05 | 02-APR-10:47 | 0.93 |
May | 0.305595E+10 | 0.83 | 1358.05 | 01-MAY-07:50 | 0.92 |
June | 0.303121E+10 | 0.87 | 1358.05 | 01-JUN-04:50 | 0.92 |
July | 0.314235E+10 | 0.87 | 1358.05 | 09-JUL-17:30 | 0.92 |
August | 0.312596E+10 | 0.86 | 1358.05 | 22-AUG-04:10 | 0.92 |
September | 0.295293E+10 | 0.83 | 1358.05 | 03-SEP-04:50 | 0.92 |
October | 0.303581E+10 | 0.79 | 1358.05 | 02-OCT-18:10 | 0.92 |
November | 0.293425E+10 | 0.78 | 1358.05 | 04-NOV-10:45 | 0.93 |
December | 0.303156E+10 | 0.78 | 1358.05 | 19-DEC-16:50 | 0.93 |
Annual Sum or Average | 0.360465E+11 | 0.81 | |||
Minimum of Months | 0.273810E+10 | 0.78 | 1358.05 | 0.92 | |
Maximum of Months | 0.314235E+10 | 0.87 | 1358.05 | 0.93 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 48.30 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 50.21 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 50.29 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 49.85 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:03 | 0.00 | 0.00 | 45.67 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:05 | 0.00 | 0.00 | 49.96 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:10 | 0.00 | 0.00 | 50.71 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:05 | 0.00 | 0.00 | 50.58 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 51.06 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 49.37 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 51.00 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 50.52 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 45.67 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 51.06 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 33.62 | 33.62 | 6366.97 | 23784.70 | 03-JAN-13:15 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 49.97 | 49.97 | 6366.85 | 23784.22 | 22-FEB-13:17 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 49.87 | 49.87 | 6381.07 | 23784.86 | 19-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:01 | 49.87 | 49.87 | 6363.57 | 23785.72 | 04-APR-12:38 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 33.71 | 33.71 | 6327.93 | 23785.58 | 02-MAY-12:38 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 49.90 | 49.90 | 6106.27 | 23162.07 | 01-JUN-12:40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 50.86 | 50.86 | 5867.01 | 22208.25 | 01-JUL-12:50 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 50.74 | 50.74 | 5749.13 | 21474.89 | 01-AUG-12:30 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 50.98 | 50.98 | 5715.99 | 21341.48 | 30-SEP-12:35 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 36.14 | 36.14 | 5825.54 | 21971.10 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 50.60 | 50.60 | 6032.25 | 22878.95 | 30-NOV-13:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 50.36 | 50.36 | 6261.44 | 23782.63 | 31-DEC-13:30 |
Annual Sum or Average | 0.00 | 6112.24 | ||||||
Minimum of Months | 0.00 | 0.00 | 33.62 | 33.62 | 5715.99 | 21341.48 | ||
Maximum of Months | 0.00 | 0.00 | 50.98 | 50.98 | 6381.07 | 23785.72 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.369760E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.332233E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.366120E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.346028E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.359209E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.422320E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.499328E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.418701E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.343335E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.358832E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.358927E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.370619E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.454541E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.332233E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.499328E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.303181E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.273818E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.303171E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.293626E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.310122E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.389554E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.473420E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.382624E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.295670E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.303718E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.293457E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.303170E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.392553E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.273818E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.473420E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.369760E+10 | 0.00 | 0.716716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.332233E+10 | 0.00 | 0.585571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366120E+10 | 0.00 | 0.512278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.346028E+10 | 0.00 | 0.220229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.354756E+10 | 0.153743E+09 | 0.445122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.344264E+10 | 0.292671E+10 | 0.423288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.356618E+10 | 0.547861E+10 | 0.371665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.356168E+10 | 0.231684E+10 | 0.147031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.343335E+10 | 0.00 | 0.104481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.358832E+10 | 0.00 | 0.336351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.358927E+10 | 0.00 | 0.680985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.370619E+10 | 0.00 | 0.749525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.425766E+11 | 0.108759E+11 | 0.397330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.332233E+10 | 0.00 | 0.371665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.370619E+10 | 0.547861E+10 | 0.749525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.303158E+10 | 730650.72 | 0.871569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.273810E+10 | 246358.00 | 0.718889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.303153E+10 | 590663.73 | 0.623761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.293530E+10 | 3174018.42 | 0.264224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.305595E+10 | 0.156436E+09 | 0.367060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.303121E+10 | 0.331218E+10 | 81392378.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.314235E+10 | 0.626364E+10 | 53547208.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.312596E+10 | 0.263381E+10 | 0.103425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.295293E+10 | 12465511.67 | 0.987908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.303581E+10 | 4557463.83 | 0.389700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.293425E+10 | 1074766.67 | 0.826095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303156E+10 | 484225.07 | 0.910667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360465E+11 | 0.123894E+11 | 0.475209E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.273810E+10 | 246358.00 | 53547208.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.314235E+10 | 0.626364E+10 | 0.910667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.369760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.332233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.346028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.354756E+10 | 0.00 | 0.00 | 0.00 | 44530438.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.344264E+10 | 0.00 | 0.00 | 0.00 | 0.780567E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.356618E+10 | 0.00 | 0.00 | 0.00 | 0.142709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.356168E+10 | 0.00 | 0.00 | 0.00 | 0.625331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.343335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.358832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.358927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.370619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.425766E+11 | 0.00 | 0.00 | 0.00 | 0.287752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.332233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.370619E+10 | 0.00 | 0.00 | 0.00 | 0.142709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.303158E+10 | 0.00 | 0.00 | 0.00 | 222667.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.273810E+10 | 0.00 | 0.00 | 0.00 | 74719.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.303153E+10 | 0.00 | 0.00 | 0.00 | 180249.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.293530E+10 | 0.00 | 0.00 | 0.00 | 953532.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.305595E+10 | 0.00 | 0.00 | 0.00 | 45272825.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.303121E+10 | 0.00 | 0.00 | 0.00 | 0.864320E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.314235E+10 | 0.00 | 0.00 | 0.00 | 0.159185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.312596E+10 | 0.00 | 0.00 | 0.00 | 0.700276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.295293E+10 | 0.00 | 0.00 | 0.00 | 3765196.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.303581E+10 | 0.00 | 0.00 | 0.00 | 1371377.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.293425E+10 | 0.00 | 0.00 | 0.00 | 326795.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303156E+10 | 0.00 | 0.00 | 0.00 | 146564.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360465E+11 | 0.00 | 0.00 | 0.00 | 0.320876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.273810E+10 | 0.00 | 0.00 | 0.00 | 74719.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.314235E+10 | 0.00 | 0.00 | 0.00 | 0.159185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.185454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490644E+11 | 0.00 | 0.00 | 3.69 |
February | 0.160532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410328E+11 | 0.00 | 0.00 | 3.65 |
March | 0.180701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388853E+11 | 0.00 | 0.00 | 3.64 |
April | 0.593036E+10 | 0.00 | 0.00 | 85752.43 | 0.00 | 0.181742E+11 | 0.170047E+09 | 0.00 | 3.62 |
May | 0.909096E+10 | 0.00 | 0.00 | 5411484.76 | 0.00 | 0.272806E+10 | 0.342832E+10 | 0.00 | 4.07 |
June | 0.483266E+10 | 3192681.85 | 0.00 | 20341007.27 | 0.00 | 7756883.37 | 0.760118E+10 | 0.00 | 5.45 |
July | 0.422289E+10 | 33164584.75 | 0.00 | 26850962.84 | 0.00 | 30695546.61 | 0.745057E+10 | 0.00 | 5.53 |
August | 0.667914E+10 | 0.00 | 0.00 | 17220864.45 | 0.00 | 0.599494E+09 | 0.675515E+10 | 0.00 | 5.07 |
September | 0.899670E+10 | 0.00 | 0.00 | 703734.79 | 0.00 | 0.805825E+10 | 0.827722E+09 | 0.00 | 3.60 |
October | 0.364662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268727E+11 | 0.00 | 0.00 | 3.61 |
November | 0.187538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479238E+11 | 0.00 | 0.00 | 3.66 |
December | 0.199454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509188E+11 | 0.00 | 0.00 | 3.67 |
Annual Sum or Average | 0.525361E+11 | 36357266.61 | 0.00 | 70613806.54 | 0.00 | 0.284296E+12 | 0.262330E+11 | 0.00 | 4.11 |
Minimum of Months | 0.160532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7756883.37 | 0.00 | 0.00 | 3.60 |
Maximum of Months | 0.909096E+10 | 33164584.75 | 0.00 | 26850962.84 | 0.00 | 0.509188E+11 | 0.760118E+10 | 0.00 | 5.53 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119343E+12 | 0.00 | 0.00 | 120003.05 | 0.00 | 0.143668E+09 | 53599504.92 | 0.00 | 9.79 |
February | 0.100991E+12 | 0.00 | 0.00 | 73436.12 | 0.00 | 0.133791E+09 | 46052850.64 | 0.00 | 9.68 |
March | 0.958966E+11 | 0.00 | 0.00 | 98150.35 | 0.00 | 0.109162E+09 | 53039580.21 | 0.00 | 9.68 |
April | 0.606312E+11 | 0.00 | 0.00 | 399445.61 | 0.00 | 36537617.16 | 0.525224E+09 | 0.00 | 9.76 |
May | 0.305673E+11 | 0.00 | 0.00 | 11696669.36 | 0.00 | 7492277.59 | 0.965944E+10 | 0.00 | 9.93 |
June | 0.113032E+11 | 0.00 | 0.00 | 46174631.06 | 0.00 | 0.00 | 0.214436E+11 | 0.00 | 10.50 |
July | 0.102206E+11 | 2779774.55 | 0.00 | 57018912.01 | 0.00 | 0.00 | 0.210404E+11 | 0.00 | 10.63 |
August | 0.168184E+11 | 0.00 | 0.00 | 39776014.42 | 0.00 | 0.00 | 0.198010E+11 | 0.00 | 10.35 |
September | 0.424225E+11 | 0.00 | 0.00 | 2842722.63 | 0.00 | 5226480.01 | 0.375881E+10 | 0.00 | 9.85 |
October | 0.745807E+11 | 0.00 | 0.00 | 622395.05 | 0.00 | 35967205.20 | 0.388400E+09 | 0.00 | 9.76 |
November | 0.115406E+12 | 0.00 | 0.00 | 302515.06 | 0.00 | 0.124135E+09 | 0.129278E+09 | 0.00 | 9.73 |
December | 0.123525E+12 | 0.00 | 0.00 | 248899.77 | 0.00 | 0.156746E+09 | 79312573.31 | 0.00 | 9.74 |
Annual Sum or Average | 0.801705E+12 | 2779774.55 | 0.00 | 0.159374E+09 | 0.00 | 0.752724E+09 | 0.769781E+11 | 0.00 | 9.95 |
Minimum of Months | 0.102206E+11 | 0.00 | 0.00 | 73436.12 | 0.00 | 0.00 | 46052850.64 | 0.00 | 9.68 |
Maximum of Months | 0.123525E+12 | 2779774.55 | 0.00 | 57018912.01 | 0.00 | 0.156746E+09 | 0.214436E+11 | 0.00 | 10.63 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:25
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.719610E+10 | 0.312620E+11 | 0.216475E+12 | 0.00 | 0.535893E+11 |
February | 0.126439E+10 | 0.262962E+11 | 0.183459E+12 | 0.00 | 0.477253E+11 |
March | 0.224519E+11 | 0.255118E+11 | 0.175165E+12 | 0.00 | 0.467720E+11 |
April | 0.460836E+11 | 0.161893E+11 | 0.114488E+12 | 21214.35 | 0.314477E+11 |
May | 0.604571E+11 | 0.102662E+11 | 0.820727E+11 | 0.114206E+10 | 0.239595E+11 |
June | 0.631791E+11 | 0.710964E+10 | 0.652496E+11 | 0.379807E+10 | 0.312217E+11 |
July | 0.571406E+11 | 0.628687E+10 | 0.629386E+11 | 0.368199E+10 | 0.394342E+11 |
August | 0.416781E+11 | 0.782494E+10 | 0.736475E+11 | 0.315836E+10 | 0.296606E+11 |
September | 0.176466E+11 | 0.115430E+11 | 0.936768E+11 | 43087113.48 | 0.218998E+11 |
October | 0.461545E+10 | 0.195703E+11 | 0.141396E+12 | 76015.62 | 0.319181E+11 |
November | -0.380740E+10 | 0.297281E+11 | 0.210283E+12 | 0.00 | 0.515488E+11 |
December | -0.885091E+10 | 0.324963E+11 | 0.224370E+12 | 0.00 | 0.553016E+11 |
Annual Sum or Average | 0.294662E+12 | 0.224085E+12 | 0.164322E+13 | 0.118237E+11 | 0.464479E+12 |
Minimum of Months | -0.885091E+10 | 0.628687E+10 | 0.629386E+11 | 0.00 | 0.218998E+11 |
Maximum of Months | 0.631791E+11 | 0.324963E+11 | 0.224370E+12 | 0.379807E+10 | 0.553016E+11 |