Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 08:25:23
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1287.70 | 5542.22 | 5542.22 |
Net Site Energy | 1287.70 | 5542.22 | 5542.22 |
Total Source Energy | 2636.10 | 11345.74 | 11345.74 |
Net Source Energy | 2636.10 | 11345.74 | 11345.74 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 22.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 35.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 276.88 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 131.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 192.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 66.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 595.41 | 692.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 22.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 35.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 41.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.75 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 131.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 192.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 17.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 22.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 35.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 41.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 276.88 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 131.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 192.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 66.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 716.13 | 925.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1475.87 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2562.64 | 2979.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 716.13 | 925.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1475.87 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2562.64 | 2979.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 595.411 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 595.411 | 100.00 |
Total On-Site and Utility Electric Sources | 595.411 | 100.00 |
Total Electricity End Uses | 595.411 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3410.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 9.2637 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 11.9458 | 18.52 | 1074.0064 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 10.6047 | 2.48 | 595.3967 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 10.6047 | 2.48 | 595.3967 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 9.2637 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.9458 | 18.52 | 1074.0064 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 10.6047 | 1.24 | 595.3967 | |||||||
Conditioned Total | 232.34 | 10.6047 | 1.24 | 595.3967 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 10.6047 | 2.48 | 595.3967 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-OCT-10:20 | 29-MAR-10:20 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 10559.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15532.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2217.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14428.03 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4762.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 21432.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 4540.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 41480.45 | 58652.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 10559.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 15532.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2217.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 13060.45 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 4762.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 21432.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 3516.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1024.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 24.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 111.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 141.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 130.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 876.87 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 415.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 208.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 209.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1885.67 | 750.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 106.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 480.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 611.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 562.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3774.05 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1787.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 896.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 900.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8115.87 | 3229.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 106.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 480.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 611.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 562.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3774.05 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1787.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 896.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 900.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8115.87 | 3229.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.90 |
KITCHEN DIRECT AIR | 1.29 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.90 | 1.90 | 1.90 | 1.90 | 1.90 | 1.90 | 1.00 | 1.00 | 1.90 |
PSZ-AC_2:2 | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.00 | 1.000000 | 1.29 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.90 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.29 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.90 | 2081.78 |
PSZ-AC_2:2_ADDAQ FAN | 1.29 | 1468.40 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.90 | 1.90 | 1.90 | 1.90 | 35224.32 | 51220.21 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.29 | 1.29 | 1.29 | 1.29 | 27899.78 | 56028.00 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.90 | 0.951016 | 1.90 | 35224.32 | 16827.14 | 35224.32 | 0.800630 | 0.800630 |
PSZ-AC_2:2 COOLING COIL | 1.29 | 0.643972 | 1.29 | 27899.78 | 13463.37 | 27899.78 | 0.745950 | 0.745950 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 51220.21 |
PSZ-AC_2:2 HEATING COIL | 56028.00 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 9.264 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 126.051 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 11.946 | 282.654 | 791.353 | 0.000 | 0.000 | 0.000 | 1085.952 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 1076.175 | 9.264 | 12.293 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1076.175 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1387.759 | 11.946 | 221.217 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1387.759 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 515.917 | 4.441 | 82.240 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 851.667 | 7.331 | 135.761 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.6929 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.209 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.33002231E-12 | 0.10712597E-14 | -0.10720425E-12 | 0.10137879E-15 |
34 | 6 | 0.29661659E-07 | 0.19687232E-09 | 0.67865745E-08 | -0.14052424E-12 |
35 | 5 | -0.19512200E-03 | 0.16741682E-05 | -0.10029371E-03 | 0.67057946E-08 |
36 | 4 | 0.29799499 | 0.81016957E-03 | 0.10178761 | -0.34398158E-04 |
37 | 3 | -7.3821031 | 0.24971312E-01 | -2.3732702 | 0.29576512E-01 |
38 | 2 | 41.252923 | 0.88368331E-01 | 15.405914 | -0.33759269 |
39 | 1 | -80.838295 | 0.39713828E-01 | -29.267905 | 1.0848528 |
40 | 0 | 46.824337 | 0.79570062E-03 | 16.288235 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.6141_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.052 | 0.3089 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 9.529E-002 | 8.202E-004 | 1.025E-003 | 0.969 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 9.529E-002 | 8.202E-004 | 1.004E-003 | 0.969 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 21192.99738 | 25431.59685 | 1.58503 | 1.90203 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 31.30000 | 8.23349E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 3220.46203 | 3864.55444 | 0.13782 | 0.41606 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 3.80000 | 5.05843E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 17213.64192 | 20656.37031 | 1.07329 | 1.28794 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 30.49900 | 8.23222E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.14133 | 00:10:00 | 3.80000 | 5.05843E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 28701.77 | 1.90203 | 1.90203 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 17885.52 | 0.41606 | 0.41606 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 26296.77 | 1.28794 | 1.28794 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 49063.92 | 1.14133 | 1.14133 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.90203 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.28794 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.90203 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.90203 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.90203 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.90203 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.90203 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.90203 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.28794 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.28794 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.28794 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.28794 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.28794 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.28794 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.90203 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.28794 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.90203 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.90203 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2081.78376 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.90203 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.90203 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.90203 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.90203 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.90203 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.95102 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.90203 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 35224.32000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 16827.14011 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 35224.32000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80063 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80063 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35224.32000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 51220.20548 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 51220.20548 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.28794 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.28794 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1468.39687 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.28794 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.28794 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.28794 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.28794 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.28794 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64397 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.28794 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27899.78000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 13463.36774 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 27899.78000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74595 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74595 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27899.78000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 56028.00247 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 56028.00247 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 33842.2 | 10.26 | 10.13 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 26974.1 | 10.49 | 10.35 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | N/A | 3.491 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | N/A | 3.491 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | N/A | 3.491 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 3.9240121460E-002 | 0.1497445205 | Pass | Pass | 0.1253712521 | 0.2451470653 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2451962966 | 0.6655571848 | Pass | Pass | 8.8507840605E-002 | 0.3690341108 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.3081119124 | 0.3454239456 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 674.15 | 114.24 | 741.46 | 35.80 | 487.37 | 2053.03 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 3.491 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.491 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 9.2637 | 116.17 | 1076.18 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 19.58 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.9458 | 116.17 | 1387.76 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 25.25 |
Interior Lighting Total | 10.6047 | 232.34 | 2463.93 | 44.83 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 2625.88 | AstronomicalClock | - | 83.75 | 83.75 | 41.28 | |
Exterior Lighting Total | 2625.88 | 41.28 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 35224.32 | 28201.65 | 7022.67 | 0.80 | 3.50 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27899.78 | 20811.84 | 7087.94 | 0.75 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 33842.2 | 10.26 | 10.13 | ||||
PSZ-AC_2:2 COOLING COIL | 26974.1 | 10.49 | 10.35 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 51220.21 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 56028.00 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 1.56 | 1211.87 | 778.12 | 1.00 | 0.64 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.57 | 622.50 | 1.90 | 2081.78 | 1094.51 | 1.00 | 1.29 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.55 | 622.50 | 1.29 | 1468.40 | 1140.11 | 1.00 | 1.31 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 21193.00 | 25431.60 | 218.91 | 1.585 | 1.902 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 23.89 | 23.89 | 0.00913 | 31.30 | 0.00823 | 0.416 | 0.00 |
KITCHEN | 17213.64 | 20656.37 | 177.81 | 1.073 | 1.288 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 26.11 | 26.09 | 0.01006 | 30.50 | 0.00823 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 3220.46 | 3864.55 | 33.27 | 0.138 | 0.416 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 21.11 | 21.11 | 0.00741 | 3.80 | 0.00506 | 0.416 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.141 | 00:10:00 | 15.56 | 28.22 | 0.00479 | 3.80 | 0.00506 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.90 | 1.90 | 0.42 | 0.42 | 1.9020 | 1.9020 | 1.9020 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.29 | 1.29 | 1.14 | 1.14 | 1.2879 | 1.2879 | 1.2879 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 35224.320 | 28201.647 | 1.902030 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 35224.32 | 32735.29 | 1.902030 | 25.51 | 17.08 | 0.00893219 | 11.89 | 11.56 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 21.8743 | 23.89 | 0.00912782 | 48.5054 | 21193.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 51220.205 | 51220.205 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 51220.21 | 51220.21 | 1.902031 | 17.32 | 12.31 | 0.00701447 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 21.8743 | 20.47 | 0.00756214 | 49.6051 | 1834.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 27899.780 | 20811.841 | 1.287940 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 27899.78 | 27899.78 | 1.287940 | 29.99 | 18.19 | 0.00844000 | 11.85 | 11.48 | 0.00844000 | 30.50 | 0.00823222 | 18.19 | 88.6170 | 26.09 | 0.01005756 | 46.7858 | 17213.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 56028.002 | 56028.002 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 56028.00 | 56028.00 | 1.287943 | 3.37 | 3.37 | 0.00502809 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 88.6168 | 28.22 | 0.00479188 | 19.8378 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 35224.320 | 28201.647 | 1.902030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4445 | 1004.8586 | 1.1818 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.902031 | 2.24778006 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 35224.32 | 32735.29 | 1.0000 | 2.24777847 | 1.902030 | 25.51 | 17.08 | 0.00893219 | 48393.1 | 11.89 | 11.56 | 0.00850000 | 33396.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35224.32 | 31.30 | 0.00823349 | 18.45 | 0.41605618 | 21.8743 | 23.89 | 0.00912782 | 23.89 | 0.00912782 | 48.5054 | 21193.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 51220.205 | 51220.205 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.902031 | 2.24778006 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 51220.21 | 51220.21 | 1.0000 | 2.24778006 | 1.902031 | 17.32 | 12.31 | 0.00701447 | 35175.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51220.21 | 3.80 | 0.00505843 | 3.80 | 0.41605618 | 21.8743 | 21.11 | 0.00756214 | 20.47 | 0.00756214 | 49.6051 | 1834.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27899.780 | 20811.841 | 1.287940 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5295 | 1004.8586 | 1.1818 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.287943 | 1.52206389 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | Sensible | 27899.78 | 27899.78 | 1.0000 | 1.52206001 | 1.287940 | 29.99 | 18.19 | 0.00844000 | 51717.2 | 11.85 | 11.48 | 0.00844000 | 33206.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27899.78 | 30.50 | 0.00823222 | 18.19 | 1.14133354 | 88.6170 | 26.06 | 0.01005756 | 26.09 | 0.01005756 | 46.7858 | 17213.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 56028.002 | 56028.002 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.287943 | 1.52206389 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 56028.00 | 56028.00 | 1.0000 | 1.52206389 | 1.287943 | 3.37 | 3.37 | 0.00502809 | 15990.2 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 56028.00 | 3.80 | 0.00505843 | 3.80 | 1.14133354 | 88.6168 | 0.00 | 0.00479188 | 28.22 | 0.00479188 | 19.8378 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.90 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.29 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3418.50 | 3742.33 | 748.67 |
KITCHEN | 5511.00 | 4741.17 | 3394.67 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5511.17 | 6368.33 | 3410.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.17 | 20.33 | 0.00 | 0.00 |
KITCHEN | 0.00 | 326.33 | 0.00 | 1.67 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.17 | 328.67 | 0.00 | 1.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 6.631 | 4.274 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 12.343 | 0.037 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.179 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 11.367 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 16846032.53 | 0.00 | 16846032.53 | 10727480.81 | 27573513.34 | 13120747.55 | 1444.37 | 4549.71 | 2765.92 | 414.73 |
KITCHEN | 32326899.96 | 0.00 | 32326899.96 | 140835.77 | 32467735.72 | 35993094.65 | 1429.66 | 4934.58 | 2395.76 | 1038.64 |
Total Facility | 49172932.49 | 0.00 | 49172932.49 | 10868316.57 | 60041249.06 | 49113842.20 | 1448.14 | 5191.81 | 3039.85 | 1066.37 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.6396 | 0.0000 | 0.6396 | 0.4127 | 1.0524 | 0.4161 | 0.00 | 4448.77 | 2738.23 |
KITCHEN | 1.1864 | 0.0000 | 1.1864 | 0.0036 | 1.1899 | 1.1413 | 0.00 | 4822.29 | 2364.71 |
Total Facility | 1.8260 | 0.0000 | 1.8260 | 0.4163 | 2.2423 | 1.5574 | 0.00 | 5078.01 | 2993.96 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 23527176.11 | 0.00 | 23527176.11 | 13120747.55 | 1443.30 | 0.07 | 7316.63 | 414.71 |
PSZ-AC_2:2 | 45147774.66 | 0.00 | 45147774.66 | 35993094.65 | 1397.36 | 2.16 | 7360.48 | 1038.64 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.8933 | 0.0000 | 0.8933 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.6569 | 0.0000 | 1.6569 | 1.1413 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1557.14 | 1511.91 | 4532.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 2738.84 | 5486.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.8608 | 1.0067 | 0.5812 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.7837 | 1.5940 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 370 |
Defaulted Fields | 263 |
Fields with Defaults | 871 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 595.41 | 6676.60 | 07-JAN-01:10 | 41480.45 | 16-OCT-10:20 |
Electricity:Building | 339.57 | 3046.93 | 01-JAN-01:10 | 20161.68 | 02-JAN-11:10 |
Electricity:Zone:DINING | 90.00 | 432.77 | 01-JAN-01:10 | 4903.08 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 321.71 | 2637.89 | 01-JAN-01:10 | 16645.57 | 02-JAN-11:10 |
InteriorLights:Electricity | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 19.58 | 161.43 | 01-JAN-01:10 | 968.56 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 19.58 | 161.43 | 01-JAN-01:10 | 968.56 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 249.57 | 2614.16 | 01-JAN-01:10 | 15258.60 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 25.25 | 208.16 | 01-JAN-01:10 | 1248.98 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 25.25 | 208.16 | 01-JAN-01:10 | 1248.98 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 276.88 | 2268.30 | 01-JAN-01:10 | 14428.03 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 276.88 | 2268.30 | 01-JAN-01:10 | 14428.03 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 206.46 | 1996.96 | 01-JAN-01:10 | 10493.51 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.33 | 629.37 | 01-JAN-01:10 | 9125.93 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 66.03 | 1036.69 | 23-NOV-23:30 | 4592.33 | 27-JUN-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
Electricity:Plant | 48.17 | 781.03 | 23-NOV-23:30 | 2544.54 | 03-OCT-03:30 |
LowTempRefrigeration:Refrigeration:Electricity | 17.21 | 0.00 | 01-JAN-11:10 | 1468.31 | 03-OCT-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 30.96 | 716.70 | 07-JAN-01:10 | 1076.23 | 13-JAN-14:10 |
ElectricityPurchased:Facility | 595.41 | 6676.60 | 07-JAN-01:10 | 41480.45 | 16-OCT-10:20 |
ElectricityPurchased:Plant | 595.41 | 6676.60 | 07-JAN-01:10 | 41480.45 | 16-OCT-10:20 |
Cogeneration:ElectricityPurchased | 595.41 | 6676.60 | 07-JAN-01:10 | 41480.45 | 16-OCT-10:20 |
General:Cogeneration:ElectricityPurchased | 595.41 | 6676.60 | 07-JAN-01:10 | 41480.45 | 16-OCT-10:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 595.41 | 6676.60 | 07-JAN-01:10 | 41480.45 | 16-OCT-10:20 |
ElectricityNet:Plant | 595.41 | 6676.60 | 07-JAN-01:10 | 41480.45 | 16-OCT-10:20 |
Cogeneration:ElectricityNet | 595.41 | 6676.60 | 07-JAN-01:10 | 41480.45 | 16-OCT-10:20 |
General:Cogeneration:ElectricityNet | 595.41 | 6676.60 | 07-JAN-01:10 | 41480.45 | 16-OCT-10:20 |
Electricity:HVAC | 166.39 | 0.00 | 01-JAN-01:10 | 22629.44 | 16-OCT-11:10 |
Fans:Electricity | 131.12 | 0.00 | 01-JAN-01:10 | 4762.05 | 03-APR-11:30 |
General:Fans:Electricity | 131.12 | 0.00 | 01-JAN-01:10 | 4762.05 | 03-APR-11:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 35.27 | 0.00 | 01-JAN-00:10 | 17867.38 | 16-OCT-11:10 |
General:Cooling:Electricity | 35.27 | 0.00 | 01-JAN-00:10 | 17867.38 | 16-OCT-11:10 |
ExteriorLights:Electricity | 41.28 | 0.00 | 01-JAN-07:00 | 2625.88 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 41.28 | 0.00 | 01-JAN-07:00 | 2625.88 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 11-FEB-16:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 11-FEB-16:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 692.29 | 2560.65 | 12-FEB-01:10 | 58652.88 | 29-MAR-10:20 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 22.91 | 0.00 | 01-JAN-00:10 | 35770.19 | 08-JAN-07:10 |
Heating:NaturalGas | 22.91 | 0.00 | 01-JAN-00:10 | 35770.19 | 08-JAN-07:10 |
General:Heating:NaturalGas | 22.91 | 0.00 | 01-JAN-00:10 | 35770.19 | 08-JAN-07:10 |
NaturalGas:Plant | 192.22 | 722.00 | 06-JAN-04:50 | 25684.74 | 29-JAN-13:20 |
WaterSystems:NaturalGas | 192.22 | 722.00 | 06-JAN-04:50 | 25684.74 | 29-JAN-13:20 |
Water Heater:WaterSystems:NaturalGas | 192.22 | 722.00 | 06-JAN-04:50 | 25684.74 | 29-JAN-13:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 794.72 | 2838.56 | 07-JAN-01:10 | 109755.55 | 29-SEP-13:00 |
EnergyTransfer:Building | 451.28 | 1419.28 | 07-JAN-01:10 | 39191.95 | 16-OCT-11:10 |
EnergyTransfer:Zone:KITCHEN | 378.22 | 1419.28 | 07-JAN-01:10 | 24084.18 | 29-DEC-05:10 |
Refrigeration:EnergyTransfer | 156.34 | 2706.21 | 23-NOV-23:30 | 7834.84 | 31-JAN-04:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 78.17 | 1353.10 | 23-NOV-23:30 | 3917.42 | 31-JAN-04:40 |
General:Refrigeration:EnergyTransfer | 78.17 | 1353.10 | 23-NOV-23:30 | 3917.42 | 31-JAN-04:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 78.17 | 1353.10 | 23-NOV-23:30 | 3917.42 | 31-JAN-04:40 |
EnergyTransfer:Plant | 206.69 | 1353.10 | 23-NOV-23:30 | 19087.13 | 13-FEB-13:50 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 16.51 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 61.66 | 1160.10 | 07-JAN-01:10 | 2238.70 | 13-JAN-14:10 |
EnergyTransfer:Zone:DINING | 73.06 | 0.00 | 01-JAN-01:10 | 21486.67 | 16-OCT-11:10 |
Heating:EnergyTransfer | 3.03 | 0.00 | 01-JAN-00:10 | 8816.29 | 08-JAN-07:10 |
Heating:EnergyTransfer:Zone:DINING | 3.03 | 0.00 | 01-JAN-00:10 | 8816.29 | 08-JAN-07:10 |
General:Heating:EnergyTransfer | 3.03 | 0.00 | 01-JAN-00:10 | 8816.29 | 08-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:DINING | 3.03 | 0.00 | 01-JAN-00:10 | 8816.29 | 08-JAN-07:10 |
Cooling:EnergyTransfer | 370.08 | 0.00 | 01-JAN-01:10 | 35313.32 | 16-OCT-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 70.03 | 0.00 | 01-JAN-01:10 | 21486.67 | 16-OCT-11:10 |
General:Cooling:EnergyTransfer | 370.08 | 0.00 | 01-JAN-01:10 | 35313.32 | 16-OCT-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 70.03 | 0.00 | 01-JAN-01:10 | 21486.67 | 16-OCT-11:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 300.05 | 0.00 | 01-JAN-01:10 | 20258.28 | 29-DEC-05:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 300.05 | 0.00 | 01-JAN-01:10 | 20258.28 | 29-DEC-05:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 128.52 | 0.00 | 01-JAN-00:10 | 16445.28 | 03-FEB-13:50 |
PlantLoopHeatingDemand:Plant | 128.52 | 0.00 | 01-JAN-00:10 | 16445.28 | 03-FEB-13:50 |
WaterSystems:PlantLoopHeatingDemand | 128.52 | 0.00 | 01-JAN-00:10 | 16445.28 | 03-FEB-13:50 |
General:WaterSystems:PlantLoopHeatingDemand | 128.52 | 0.00 | 01-JAN-00:10 | 16445.28 | 03-FEB-13:50 |
EnergyTransfer:HVAC | 136.75 | 0.00 | 01-JAN-00:10 | 57989.73 | 16-OCT-11:10 |
HeatingCoils:EnergyTransfer | 18.33 | 0.00 | 01-JAN-00:10 | 28616.15 | 08-JAN-07:10 |
CoolingCoils:EnergyTransfer | 118.42 | 0.00 | 01-JAN-00:10 | 57989.73 | 16-OCT-11:10 |
WaterSystems:EnergyTransfer | 128.52 | 0.00 | 01-JAN-00:10 | 16445.28 | 03-FEB-13:50 |
WaterUse:WaterSystems:EnergyTransfer | 128.52 | 0.00 | 01-JAN-00:10 | 16445.28 | 03-FEB-13:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 3.031 | -70.026 | 0.000 | 0.000 | 68.877 | 19.580 | 52.814 | 20.364 | 0.000 | 1.437 | 0.000 | 0.000 | -12.866 | 0.000 | -78.227 | -4.983 |
KITCHEN | 0.000 | 0.000 | 0.000 | -300.045 | 0.000 | 0.000 | 4.450 | 25.249 | 212.059 | 0.000 | 0.000 | 0.007 | 59.880 | 0.000 | 0.000 | 0.000 | -1.601 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.948 | 14.855 | 0.000 | 0.000 | 0.000 | -18.803 | -0.000 |
Total Facility | 0.000 | 0.000 | 3.031 | -370.071 | 0.000 | 0.000 | 73.327 | 44.830 | 264.873 | 20.364 | 0.000 | 5.392 | 74.735 | 0.000 | -12.866 | 0.000 | -98.631 | -4.983 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 16-OCT-03:21 | 0.00 | 0.00 | 0.00 | -32175.96 | 0.00 | 0.00 | 0.00 | 161.43 | 508.77 | 0.00 | 0.00 | 0.00 | 32078.32 | 0.00 | -556.72 | 0.00 | -15.83 | 0.00 |
KITCHEN | 29-DEC-05:01 | 0.00 | 0.00 | 0.00 | -52370.69 | 0.00 | 0.00 | 9.68 | 277.55 | 5273.28 | 0.00 | 0.00 | 0.00 | 46902.88 | 0.00 | -0.00 | 0.00 | -92.70 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-OCT-03:21 | 0.00 | 0.00 | 0.00 | -66807.25 | 0.00 | 0.00 | 0.00 | 369.59 | 3503.73 | 0.00 | 0.00 | 503.72 | 63080.84 | 0.00 | -556.72 | 0.00 | -93.90 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 16-OCT-02:43 | 0.00 | 0.00 | 16888.84 | 0.00 | 0.00 | 0.00 | 0.00 | 161.43 | 203.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -554.71 | 0.00 | -11.41 | -16687.66 |
KITCHEN | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-OCT-02:43 | 0.00 | 0.00 | 16888.84 | 0.00 | 0.00 | 0.00 | 0.00 | 369.59 | 2222.04 | 0.00 | 0.00 | 490.12 | 0.00 | 0.00 | -554.71 | 0.00 | -53.35 | -19362.54 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9020 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.9020 | 0.2187 | 1.0000 | Not calculated | 0.4161 | 0.2187 | ||
PSZ-AC_2:2 | 1.2879 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2879 | 0.1175 | 1.0000 | Not calculated | 0.1513 | 0.1175 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9020 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.9020 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2187 | ||
PSZ-AC_2:2 | 1.2879 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2879 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1175 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9020 | 1.9020 | 1.9020 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2879 | 1.2879 | 1.2879 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9020 | 1.9020 | 1.9020 | 1.9020 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2879 | 1.2879 | 1.2879 | 1.2879 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9020 | 1.9020 | 1.9020 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2879 | 1.2879 | 1.2879 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9020 | 1.9020 | 1.9020 | 1.9020 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2879 | 1.2879 | 1.2879 | 1.2879 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1.67 |
Number of hours not met | 1.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 22.91 | 35770.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 35.27 | 17867.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 44.83 | 2217.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 41.28 | 2625.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.75 | 13060.45 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 131.12 | 4762.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 192.22 | 25684.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 17.86 | 3516.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 17.21 | 1468.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 30.96 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 342.91 | 595.41 |
Natural Gas | 477.16 | 692.29 |
Additional | 0.00 | 0.00 |
Total | 820.07 | 1287.70 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 192.95 |
Space Heating | 0.00 |
Space Cooling | 151.79 |
Fans (All) | 564.34 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1191.68 |
Miscellaneous (All) | 2562.64 |
Subtotal | 2562.64 |
Natural Gas [MJ/m2] | |
Space Heating | 98.61 |
Service Water Heating | 827.29 |
Miscellaneous (All) | 2979.58 |
Subtotal | 2979.58 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 3.48 |
Space Heating | 1.78 |
Space Cooling | 2.74 |
Fans (All) | 10.18 |
Service Water Heating | 14.93 |
Receptacle Equipment | 58.56 |
Miscellaneous | 8.33 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 5084. | 8760. |
LTG_SCH_KITCHEN | 5084. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_SETBACK | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_SETBACK | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8482.50 | 277.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 6000.83 | 793.00 | 730.17 | 1034.83 | 201.17 |
Min | 6000.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 793.00 | 730.17 | 1034.83 | 201.17 |
Average | 7747.78 | 356.83 | 243.39 | 344.94 | 67.06 |
Sum | 23243.33 | 1070.50 | 730.17 | 1034.83 | 201.17 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16255.33 | 2.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 2.67 | 0.00 | 0.00 | 0.00 |
Average | 90326.78 | 0.89 | 0.00 | 0.00 | 0.00 |
Sum | 270980.33 | 2.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8070.67 | 689.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 5591.50 | 3168.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 6036.17 | 1271.17 | 408.83 | 411.17 | 632.67 |
Min | 5591.50 | 689.33 | 0.00 | 0.00 | 0.00 |
Max | 8070.67 | 3168.50 | 408.83 | 411.17 | 632.67 |
Average | 6566.11 | 1709.67 | 136.28 | 137.06 | 210.89 |
Sum | 19698.33 | 5129.00 | 408.83 | 411.17 | 632.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 231727.50 | 22997.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 9333.00 | 6925.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 231727.50 | 22997.50 | 0.00 | 0.00 | 0.00 |
Average | 80353.50 | 9974.17 | 0.00 | 0.00 | 0.00 |
Sum | 241060.50 | 29922.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:23
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Environment
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.395940E+10 | 11292.04 | 18-JAN-12:55 | 26.00 | 14.69 | 0.488709E+10 | 4681.72 | 14-JAN-19:30 | 26.00 | 14.69 |
February | 0.290572E+10 | 9597.02 | 01-FEB-12:05 | 25.67 | 14.54 | 0.432715E+10 | 4414.24 | 21-FEB-12:00 | 21.00 | 13.54 |
March | 0.316105E+10 | 7215.72 | 10-MAR-13:00 | 23.00 | 12.77 | 0.478585E+10 | 4414.14 | 23-MAR-11:50 | 22.00 | 16.49 |
April | 0.495453E+10 | 10963.88 | 26-APR-13:00 | 27.00 | 17.13 | 0.486263E+10 | 4681.79 | 01-APR-18:10 | 27.00 | 17.13 |
May | 0.489800E+10 | 8733.16 | 04-MAY-12:00 | 24.00 | 16.55 | 0.509355E+10 | 4665.76 | 27-MAY-18:10 | 16.50 | 12.42 |
June | 0.629840E+10 | 9013.30 | 29-JUN-11:05 | 24.83 | 19.55 | 0.515692E+10 | 4681.79 | 17-JUN-18:00 | 24.83 | 19.55 |
July | 0.892115E+10 | 12757.26 | 31-JUL-12:00 | 28.00 | 21.19 | 0.538061E+10 | 4681.98 | 29-JUL-18:30 | 28.00 | 21.19 |
August | 0.938918E+10 | 12988.08 | 18-AUG-12:00 | 28.00 | 21.20 | 0.544304E+10 | 4681.83 | 05-AUG-18:10 | 28.00 | 21.20 |
September | 0.773426E+10 | 24850.59 | 30-SEP-01:22 | 24.20 | 13.95 | 0.515808E+10 | 4681.82 | 30-SEP-18:49 | 21.33 | 17.57 |
October | 0.898113E+10 | 32179.41 | 16-OCT-03:21 | 20.00 | 10.00 | 0.529703E+10 | 4681.82 | 14-OCT-18:30 | 20.00 | 10.00 |
November | 0.446238E+10 | 9938.82 | 19-NOV-13:00 | 27.00 | 14.96 | 0.478396E+10 | 4624.90 | 18-NOV-19:10 | 27.00 | 14.96 |
December | 0.436144E+10 | 11702.39 | 19-DEC-13:00 | 26.00 | 11.60 | 0.487799E+10 | 4556.50 | 16-DEC-19:10 | 26.00 | 11.60 |
Annual Sum or Average | 0.700266E+11 | 0.600539E+11 | ||||||||
Minimum of Months | 0.290572E+10 | 7215.72 | 20.00 | 10.00 | 0.432715E+10 | 4414.14 | 16.50 | 10.00 | ||
Maximum of Months | 0.938918E+10 | 32179.41 | 28.00 | 21.20 | 0.544304E+10 | 4681.98 | 28.00 | 21.20 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251459E+11 | 49975.40 | 10-JAN-04:51 | 7.00 | 2.49 | 0.778515E+10 | 5138.46 | 19-JAN-11:00 | 23.00 | 15.75 |
February | 0.225808E+11 | 48817.59 | 04-FEB-04:32 | 8.67 | 2.25 | 0.702849E+10 | 5138.41 | 03-FEB-11:00 | 8.67 | 2.25 |
March | 0.251973E+11 | 39449.81 | 14-MAR-03:31 | 9.00 | 8.62 | 0.777646E+10 | 5138.41 | 22-MAR-10:39 | 21.00 | 16.08 |
April | 0.243741E+11 | 39332.26 | 25-APR-04:01 | 11.83 | 11.38 | 0.756450E+10 | 5138.45 | 28-APR-10:00 | 19.00 | 14.76 |
May | 0.253481E+11 | 39521.75 | 24-MAY-03:21 | 15.00 | 7.56 | 0.782582E+10 | 5138.45 | 19-MAY-10:39 | 15.00 | 7.56 |
June | 0.247921E+11 | 41048.06 | 13-JUN-04:01 | 11.00 | 9.85 | 0.759709E+10 | 5138.44 | 09-JUN-10:00 | 11.00 | 9.85 |
July | 0.261146E+11 | 32324.75 | 08-JUL-04:01 | 16.00 | 14.13 | 0.785572E+10 | 5138.44 | 18-JUL-10:50 | 25.83 | 20.32 |
August | 0.260904E+11 | 32185.77 | 23-AUG-04:01 | 15.75 | 14.07 | 0.786127E+10 | 5138.45 | 17-AUG-10:00 | 15.75 | 14.07 |
September | 0.250092E+11 | 38160.61 | 19-SEP-04:01 | 13.17 | 11.93 | 0.759658E+10 | 5150.43 | 29-SEP-10:00 | 36.00 | 17.91 |
October | 0.257251E+11 | 50189.75 | 27-OCT-04:01 | 9.00 | 3.53 | 0.784702E+10 | 5158.42 | 16-OCT-10:00 | 9.00 | 3.53 |
November | 0.245124E+11 | 42679.52 | 03-NOV-03:31 | 9.33 | 6.72 | 0.755114E+10 | 5138.45 | 09-NOV-11:00 | 19.00 | 14.77 |
December | 0.251594E+11 | 52330.20 | 29-DEC-05:01 | 7.83 | 1.88 | 0.778700E+10 | 5138.45 | 07-DEC-11:50 | 7.83 | 1.88 |
Annual Sum or Average | 0.300049E+12 | 0.920763E+11 | ||||||||
Minimum of Months | 0.225808E+11 | 32185.77 | 7.00 | 1.88 | 0.702849E+10 | 5138.41 | 7.83 | 1.88 | ||
Maximum of Months | 0.261146E+11 | 52330.20 | 16.00 | 14.13 | 0.786127E+10 | 5158.42 | 36.00 | 20.32 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 8.83 | 8.36 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 | 6.62 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.62 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9.63 | 8.61 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 15.20 | 14.50 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 | 12.03 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 | 15.81 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.07 | 17.20 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 | 14.83 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.83 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 | 17.39 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 | 11.07 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.07 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.44 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.44 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.63 | 5.44 | 0.00 | 0.00 | 7.63 | 5.44 | ||
Maximum of Months | 0.00 | 0.00 | 18.42 | 17.39 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.827972E+09 | 8816.29 | 08-JAN-07:10 | 1.83 |
February | 0.455162E+09 | 4537.44 | 26-FEB-21:00 | 8.00 |
March | 0.941983E+09 | 6929.48 | 29-MAR-19:55 | 6.60 |
April | 54463535.16 | 4953.99 | 01-APR-06:10 | 7.67 |
May | 17417524.68 | 2035.89 | 15-MAY-06:43 | 12.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.07 |
September | 6281835.48 | 14202.32 | 30-SEP-02:45 | 24.12 |
October | 10564585.04 | 16888.49 | 16-OCT-02:43 | 20.00 |
November | 0.105136E+09 | 4745.55 | 05-NOV-06:10 | 7.17 |
December | 0.611963E+09 | 5281.84 | 12-DEC-21:00 | 8.00 |
Annual Sum or Average | 0.303094E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.83 | |
Maximum of Months | 0.941983E+09 | 16888.49 | 24.12 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.165449E+10 | 968.56 | 02-JAN-10:09 | 0.598074E+10 | 3934.52 | 01-JAN-11:09 |
February | 0.149855E+10 | 968.56 | 01-FEB-10:09 | 0.540196E+10 | 3934.52 | 01-FEB-11:09 |
March | 0.168084E+10 | 968.56 | 01-MAR-10:09 | 0.598074E+10 | 3934.52 | 01-MAR-11:09 |
April | 0.160761E+10 | 968.56 | 01-APR-16:10 | 0.578781E+10 | 3934.52 | 01-APR-10:09 |
May | 0.166766E+10 | 968.56 | 01-MAY-09:09 | 0.598074E+10 | 3934.52 | 01-MAY-10:09 |
June | 0.162466E+10 | 968.56 | 01-JUN-09:09 | 0.578781E+10 | 3934.52 | 01-JUN-10:09 |
July | 0.165081E+10 | 968.56 | 01-JUL-16:10 | 0.598074E+10 | 3934.52 | 01-JUL-10:09 |
August | 0.168084E+10 | 968.56 | 01-AUG-09:09 | 0.598074E+10 | 3934.52 | 01-AUG-10:09 |
September | 0.160800E+10 | 968.56 | 01-SEP-09:09 | 0.578781E+10 | 3934.52 | 01-SEP-10:09 |
October | 0.165430E+10 | 968.56 | 02-OCT-09:09 | 0.598074E+10 | 3934.52 | 01-OCT-10:09 |
November | 0.160161E+10 | 968.56 | 01-NOV-09:09 | 0.578781E+10 | 3934.52 | 01-NOV-10:09 |
December | 0.165100E+10 | 968.56 | 01-DEC-10:09 | 0.598074E+10 | 3934.52 | 01-DEC-11:09 |
Annual Sum or Average | 0.195804E+11 | 0.704184E+11 | ||||
Minimum of Months | 0.149855E+10 | 968.56 | 0.540196E+10 | 3934.52 | ||
Maximum of Months | 0.168084E+10 | 968.56 | 0.598074E+10 | 3934.52 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.213351E+10 | 1248.98 | 02-JAN-10:09 | 0.175350E+11 | 10493.51 | 01-JAN-11:09 |
February | 0.193243E+10 | 1248.98 | 01-FEB-10:09 | 0.158380E+11 | 10493.51 | 01-FEB-11:09 |
March | 0.216749E+10 | 1248.98 | 01-MAR-10:09 | 0.175350E+11 | 10493.51 | 01-MAR-11:09 |
April | 0.207306E+10 | 1248.98 | 01-APR-16:10 | 0.169693E+11 | 10493.51 | 01-APR-10:09 |
May | 0.215050E+10 | 1248.98 | 01-MAY-09:09 | 0.175350E+11 | 10493.51 | 01-MAY-10:09 |
June | 0.209504E+10 | 1248.98 | 01-JUN-09:09 | 0.169693E+11 | 10493.51 | 01-JUN-10:09 |
July | 0.212877E+10 | 1248.98 | 01-JUL-16:10 | 0.175350E+11 | 10493.51 | 01-JUL-10:09 |
August | 0.216749E+10 | 1248.98 | 01-AUG-09:09 | 0.175350E+11 | 10493.51 | 01-AUG-10:09 |
September | 0.207356E+10 | 1248.98 | 01-SEP-09:09 | 0.169693E+11 | 10493.51 | 01-SEP-10:09 |
October | 0.213326E+10 | 1248.98 | 02-OCT-09:09 | 0.175350E+11 | 10493.51 | 01-OCT-10:09 |
November | 0.206532E+10 | 1248.98 | 01-NOV-09:09 | 0.169693E+11 | 10493.51 | 01-NOV-10:09 |
December | 0.212902E+10 | 1248.98 | 01-DEC-10:09 | 0.175350E+11 | 10493.51 | 01-DEC-11:09 |
Annual Sum or Average | 0.252494E+11 | 0.206460E+12 | ||||
Minimum of Months | 0.193243E+10 | 1248.98 | 0.158380E+11 | 10493.51 | ||
Maximum of Months | 0.216749E+10 | 1248.98 | 0.175350E+11 | 10493.51 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.165449E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29887324.23 | 0.882299E+10 |
February | 0.852256E+10 | 0.149855E+10 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5011945.54 | 0.801514E+10 |
March | 0.954557E+10 | 0.168084E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 687467.70 | 0.930831E+10 |
April | 0.915225E+10 | 0.160761E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29685926.92 | 0.681020E+10 |
May | 0.947560E+10 | 0.166766E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 425092.60 | 0.688433E+10 |
June | 0.922788E+10 | 0.162466E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5312049.39 | 0.521534E+10 |
July | 0.939996E+10 | 0.165081E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166270E+09 | 0.382591E+10 |
August | 0.954557E+10 | 0.168084E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189806E+09 | 0.375086E+10 |
September | 0.915225E+10 | 0.160800E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335887E+09 | 0.496541E+10 |
October | 0.940563E+10 | 0.165430E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620315E+09 | 0.457528E+10 |
November | 0.909363E+10 | 0.160161E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29752129.82 | 0.765028E+10 |
December | 0.939996E+10 | 0.165100E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24146598.98 | 0.840338E+10 |
Annual Sum or Average | 0.111326E+12 | 0.195804E+11 | 0.704184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143719E+10 | 0.782274E+11 |
Minimum of Months | 0.852256E+10 | 0.149855E+10 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 425092.60 | 0.375086E+10 |
Maximum of Months | 0.954557E+10 | 0.168084E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620315E+09 | 0.930831E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.213351E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166417E+09 |
February | 0.610713E+09 | 0.193243E+10 | 0.120792E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185131E+09 |
March | 0.684021E+09 | 0.216749E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201855E+09 |
April | 0.655836E+09 | 0.207306E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 16901.88 | 0.127639E+09 |
May | 0.679007E+09 | 0.215050E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153632E+09 |
June | 0.661256E+09 | 0.209504E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85606356.37 |
July | 0.673587E+09 | 0.212877E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 326086.90 | 60195023.30 |
August | 0.684021E+09 | 0.216749E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 237745.06 | 82250598.63 |
September | 0.655836E+09 | 0.207356E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 1931380.07 | 77821749.72 |
October | 0.673993E+09 | 0.213326E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 4600101.82 | 0.121454E+09 |
November | 0.651635E+09 | 0.206532E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 13262.27 | 0.162851E+09 |
December | 0.673587E+09 | 0.212902E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175995E+09 |
Annual Sum or Average | 0.797748E+10 | 0.252494E+11 | 0.157461E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 7125478.00 | 0.160085E+10 |
Minimum of Months | 0.610713E+09 | 0.193243E+10 | 0.120792E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60195023.30 |
Maximum of Months | 0.684021E+09 | 0.216749E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 4600101.82 | 0.201855E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470429E+09 | 0.995795E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316266E+09 | 0.101447E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290181E+09 | 0.148818E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282890E+09 | 0.199511E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253979E+09 | 0.203877E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189519E+09 | 0.208400E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239704E+09 | 0.231874E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253533E+09 | 0.212944E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315929E+09 | 0.163858E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395873E+09 | 0.118632E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425155E+09 | 0.101655E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514125E+09 | 0.896719E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394758E+10 | 0.188027E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189519E+09 | 0.896719E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514125E+09 | 0.231874E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 968.56 | 02-JAN-10:09 | 3934.52 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1861.12 | 18-JAN-12:55 | 14333.23 | 02-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 968.56 | 01-FEB-10:09 | 3934.52 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1565.45 | 01-FEB-12:05 | 11294.43 | 21-FEB-21:00 |
March | 9454.80 | 04-MAR-19:10 | 968.56 | 01-MAR-10:09 | 3934.52 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 | 11-MAR-13:25 | 13571.80 | 29-MAR-19:55 |
April | 9454.80 | 01-APR-18:10 | 968.56 | 01-APR-16:10 | 3934.52 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2433.26 | 26-APR-13:00 | 9271.48 | 15-APR-18:52 |
May | 9454.80 | 06-MAY-18:10 | 968.56 | 01-MAY-09:09 | 3934.52 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.48 | 04-MAY-12:00 | 9353.81 | 10-MAY-19:53 |
June | 9454.80 | 03-JUN-18:10 | 968.56 | 01-JUN-09:09 | 3934.52 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 834.64 | 29-JUN-11:05 | 7641.21 | 06-JUN-18:52 |
July | 9454.80 | 01-JUL-18:10 | 968.56 | 01-JUL-16:10 | 3934.52 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3597.75 | 19-JUL-12:00 | 6898.45 | 15-JUL-18:57 |
August | 9454.80 | 05-AUG-18:10 | 968.56 | 01-AUG-09:09 | 3934.52 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3598.78 | 18-AUG-12:00 | 7042.60 | 21-AUG-19:53 |
September | 9454.80 | 02-SEP-18:10 | 968.56 | 01-SEP-09:09 | 3934.52 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10290.68 | 29-SEP-11:05 | 7769.34 | 02-SEP-18:53 |
October | 9454.80 | 07-OCT-18:10 | 968.56 | 02-OCT-09:09 | 3934.52 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11027.45 | 16-OCT-11:03 | 8231.55 | 07-OCT-18:53 |
November | 9454.80 | 04-NOV-18:10 | 968.56 | 01-NOV-09:09 | 3934.52 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1841.81 | 19-NOV-13:00 | 10932.48 | 04-NOV-20:00 |
December | 9454.80 | 02-DEC-19:10 | 968.56 | 01-DEC-10:09 | 3934.52 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1858.96 | 19-DEC-13:00 | 13276.02 | 28-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 968.56 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 | 6898.45 | |||||
Maximum of Months | 9454.80 | 968.56 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 11027.45 | 14333.23 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 1248.98 | 02-JAN-10:09 | 7755.73 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 738.71 | 02-JAN-03:00 |
February | 677.52 | 04-FEB-19:10 | 1248.98 | 01-FEB-10:09 | 7755.73 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 767.11 | 25-FEB-03:10 |
March | 677.52 | 04-MAR-19:10 | 1248.98 | 01-MAR-10:09 | 7755.73 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 666.10 | 29-MAR-02:00 |
April | 677.52 | 01-APR-18:10 | 1248.98 | 01-APR-16:10 | 7755.73 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 5.44 | 26-APR-13:00 | 474.94 | 22-APR-03:30 |
May | 677.52 | 06-MAY-18:10 | 1248.98 | 01-MAY-09:09 | 7755.73 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 530.07 | 26-MAY-04:00 |
June | 677.52 | 03-JUN-18:10 | 1248.98 | 01-JUN-09:09 | 7755.73 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 327.04 | 07-JUN-00:40 |
July | 677.52 | 01-JUL-18:10 | 1248.98 | 01-JUL-16:10 | 7755.73 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 14.33 | 31-JUL-13:00 | 241.11 | 21-JUL-02:00 |
August | 677.52 | 05-AUG-18:10 | 1248.98 | 01-AUG-09:09 | 7755.73 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 11.54 | 17-AUG-14:00 | 240.15 | 29-AUG-03:20 |
September | 677.52 | 02-SEP-18:10 | 1248.98 | 01-SEP-09:09 | 7755.73 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 59.30 | 29-SEP-13:30 | 305.20 | 02-SEP-02:00 |
October | 677.52 | 07-OCT-18:10 | 1248.98 | 02-OCT-09:09 | 7755.73 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 89.17 | 16-OCT-10:23 | 604.97 | 11-OCT-02:00 |
November | 677.52 | 04-NOV-18:10 | 1248.98 | 01-NOV-09:09 | 7755.73 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 5.46 | 19-NOV-13:00 | 730.82 | 23-NOV-04:30 |
December | 677.52 | 02-DEC-19:10 | 1248.98 | 01-DEC-10:09 | 7755.73 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 572.75 | 18-DEC-04:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 1248.98 | 7755.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 240.15 | ||||||
Maximum of Months | 677.52 | 1248.98 | 7755.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 89.17 | 767.11 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.43 | 06-JAN-04:00 | 1876.51 | 30-JAN-11:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 690.96 | 01-FEB-02:22 | 2097.16 | 18-FEB-12:50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 604.96 | 07-MAR-06:00 | 2560.90 | 15-MAR-12:20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.54 | 16-APR-00:53 | 2688.88 | 23-APR-12:30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.00 | 16-MAY-24:00 | 2821.65 | 31-MAY-12:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.17 | 18-JUN-01:51 | 2713.02 | 01-JUN-12:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.40 | 14-JUL-05:25 | 2674.07 | 03-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.44 | 24-AUG-03:51 | 2533.75 | 11-AUG-13:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.71 | 29-SEP-22:50 | 2383.29 | 07-SEP-13:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 802.86 | 16-OCT-06:52 | 2154.85 | 18-OCT-12:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733.18 | 27-NOV-06:53 | 1917.31 | 04-NOV-11:40 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 753.11 | 26-DEC-05:00 | 1772.08 | 02-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.40 | 1772.08 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 802.86 | 2821.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11292.04 | 18-JAN-12:55 | 16808.53 | 1937.12 | 7326.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1861.12 | 0.00 |
February | 9597.02 | 01-FEB-12:05 | 16808.53 | 1937.12 | 7326.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1565.45 | 0.00 |
March | 7215.72 | 10-MAR-13:00 | 8404.27 | 968.56 | 3663.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 794.06 |
April | 10963.88 | 26-APR-13:00 | 7353.73 | 968.56 | 3391.83 | 0.00 | 0.00 | 0.00 | 0.00 | 2433.26 | 0.00 |
May | 8733.16 | 04-MAY-12:00 | 8404.27 | 968.56 | 3663.17 | 0.00 | 0.00 | 0.00 | 0.00 | 97.48 | 0.00 |
June | 9013.30 | 29-JUN-11:05 | 16808.53 | 1937.12 | 7326.35 | 0.00 | 0.00 | 0.00 | 0.00 | 834.64 | 0.00 |
July | 12757.26 | 31-JUL-12:00 | 16808.53 | 1937.12 | 7326.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3584.40 | 0.00 |
August | 12988.08 | 18-AUG-12:00 | 16808.53 | 1937.12 | 7326.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3598.78 | 0.00 |
September | 24850.59 | 30-SEP-01:22 | 0.00 | 807.13 | 2035.10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.46 | 0.00 |
October | 32179.41 | 16-OCT-03:21 | 0.00 | 1129.98 | 4748.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 |
November | 9938.82 | 19-NOV-13:00 | 5252.67 | 753.32 | 3663.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1841.81 | 0.00 |
December | 11702.39 | 19-DEC-13:00 | 8404.27 | 968.56 | 3663.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1858.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7215.72 | 0.00 | 753.32 | 2035.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32179.41 | 16808.53 | 1937.12 | 7326.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3598.78 | 794.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 49975.40 | 10-JAN-04:51 | 0.00 | 1457.15 | 17282.92 | 9652.92 | 0.00 | 0.00 | 0.00 | 0.00 | 353.38 |
February | 48817.59 | 04-FEB-04:32 | 0.00 | 1248.98 | 14813.93 | 8273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 378.31 |
March | 39449.81 | 14-MAR-03:31 | 0.00 | 1665.31 | 19751.91 | 11031.91 | 0.00 | 0.00 | 0.00 | 0.00 | 239.91 |
April | 39332.26 | 25-APR-04:01 | 376.40 | 2775.52 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 |
May | 39521.75 | 24-MAY-03:21 | 0.00 | 1457.15 | 17282.92 | 9652.92 | 0.00 | 0.00 | 0.00 | 0.00 | 227.45 |
June | 41048.06 | 13-JUN-04:01 | 376.40 | 2775.52 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 56.66 |
July | 32324.75 | 08-JUL-04:01 | 0.00 | 1873.47 | 36098.60 | 29786.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32185.77 | 23-AUG-04:01 | 338.76 | 2497.97 | 36098.60 | 29786.16 | 0.00 | 0.00 | 0.00 | 0.00 | 32.59 |
September | 38160.61 | 19-SEP-04:01 | 376.40 | 2775.52 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 42.13 |
October | 50189.75 | 27-OCT-04:01 | 376.40 | 2775.52 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 91.21 |
November | 42679.52 | 03-NOV-03:31 | 0.00 | 1665.31 | 19751.91 | 11031.91 | 0.00 | 0.00 | 0.00 | 0.00 | 208.22 |
December | 52330.20 | 29-DEC-05:01 | 376.40 | 2775.52 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 92.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 32185.77 | 0.00 | 1248.98 | 14813.93 | 8273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52330.20 | 376.40 | 2775.52 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 378.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.59 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.73 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.46 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.72 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.19 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.17 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.11 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.47 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.90 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.68 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.45 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.73 | 24.72 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.487978E+11 | 31896.85 | 14-JAN-11:20 | 0.631810E+11 | 53921.69 | 08-JAN-07:19 |
February | 0.433066E+11 | 31857.72 | 01-FEB-11:00 | 0.553769E+11 | 52853.46 | 25-FEB-13:30 |
March | 0.478479E+11 | 30468.39 | 11-MAR-11:20 | 0.631192E+11 | 58652.88 | 29-MAR-10:20 |
April | 0.472694E+11 | 34068.84 | 26-APR-10:00 | 0.562329E+11 | 48408.16 | 01-APR-12:39 |
May | 0.483417E+11 | 30981.06 | 03-MAY-10:20 | 0.574026E+11 | 48125.46 | 01-MAY-12:00 |
June | 0.491056E+11 | 34695.74 | 29-JUN-10:00 | 0.545914E+11 | 47802.29 | 02-JUN-12:39 |
July | 0.545190E+11 | 36949.98 | 19-JUL-10:20 | 0.561543E+11 | 47560.25 | 03-JUL-12:39 |
August | 0.555483E+11 | 37572.54 | 14-AUG-10:20 | 0.561707E+11 | 47535.62 | 31-AUG-12:50 |
September | 0.508379E+11 | 41073.88 | 29-SEP-10:20 | 0.545092E+11 | 47752.01 | 30-SEP-12:39 |
October | 0.536294E+11 | 41480.45 | 16-OCT-10:20 | 0.568028E+11 | 48048.42 | 30-OCT-12:00 |
November | 0.471781E+11 | 32123.85 | 19-NOV-11:20 | 0.568825E+11 | 48352.13 | 30-NOV-13:39 |
December | 0.490288E+11 | 32494.04 | 19-DEC-11:20 | 0.618616E+11 | 48830.05 | 12-DEC-13:39 |
Annual Sum or Average | 0.595411E+12 | 0.692285E+12 | ||||
Minimum of Months | 0.433066E+11 | 30468.39 | 0.545092E+11 | 47535.62 | ||
Maximum of Months | 0.555483E+11 | 41480.45 | 0.631810E+11 | 58652.88 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.378800E+10 | 0.406801E+10 | 0.235157E+11 | 0.00 | 0.110203E+11 | 0.79 | 0.00 | 0.947530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.343098E+10 | 0.347719E+10 | 0.212400E+11 | 0.00 | 0.998675E+10 | 0.72 | 0.00 | 0.236347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384832E+10 | 0.356384E+10 | 0.235157E+11 | 0.00 | 0.110122E+11 | 0.80 | 0.00 | 0.451110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.368067E+10 | 0.316839E+10 | 0.227571E+11 | 0.00 | 0.107515E+11 | 0.77 | 0.00 | 0.149938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.381816E+10 | 0.302501E+10 | 0.235157E+11 | 0.00 | 0.111236E+11 | 0.80 | 0.00 | 0.123928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.371970E+10 | 0.280444E+10 | 0.227571E+11 | 0.00 | 0.108200E+11 | 0.77 | 0.00 | 0.346464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.377958E+10 | 0.295254E+10 | 0.235157E+11 | 0.00 | 0.112550E+11 | 0.79 | 0.00 | 0.724777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.384832E+10 | 0.316208E+10 | 0.235157E+11 | 0.00 | 0.112687E+11 | 0.80 | 0.00 | 0.795915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.368156E+10 | 0.332909E+10 | 0.227571E+11 | 0.00 | 0.108660E+11 | 0.77 | 0.00 | 0.464758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.378756E+10 | 0.373085E+10 | 0.235157E+11 | 0.00 | 0.112420E+11 | 0.79 | 0.00 | 0.565966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.366693E+10 | 0.386477E+10 | 0.227571E+11 | 0.00 | 0.107322E+11 | 0.77 | 0.00 | 0.813139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.378002E+10 | 0.413734E+10 | 0.235157E+11 | 0.00 | 0.110430E+11 | 0.79 | 0.00 | 0.110124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448298E+11 | 0.412836E+11 | 0.276879E+12 | 0.00 | 0.131121E+12 | 9.37 | 0.00 | 0.352668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.343098E+10 | 0.280444E+10 | 0.212400E+11 | 0.00 | 0.998675E+10 | 0.72 | 0.00 | 0.236347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.384832E+10 | 0.413734E+10 | 0.235157E+11 | 0.00 | 0.112687E+11 | 0.80 | 0.00 | 0.795915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.565711E+10 | 0.00 | 0.169982E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.340144E+10 | 0.00 | 0.153715E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.569227E+10 | 0.00 | 0.169012E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.100859E+10 | 0.00 | 0.160058E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.681642E+09 | 0.00 | 0.161952E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 12193467.72 | 0.00 | 0.153607E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.156286E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.156450E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 16152278.66 | 0.00 | 0.152746E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.186633E+09 | 0.00 | 0.160904E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.171069E+10 | 0.00 | 0.159534E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.454457E+10 | 0.00 | 0.167913E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.229113E+11 | 0.00 | 0.192216E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.00 | 0.00 | 0.152746E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.569227E+10 | 0.00 | 0.169982E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2217.54 | 02-JAN-10:09 | 2625.88 | 01-JAN-00:10 | 14428.03 | 01-JAN-11:09 | 0.00 | 4762.05 | 01-JAN-10:39 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 2217.54 | 01-FEB-10:09 | 2625.88 | 01-FEB-00:10 | 14428.03 | 01-FEB-11:09 | 0.00 | 4762.05 | 01-FEB-06:30 | 0.00 | 11-FEB-16:10 | 0.00 | 01-FEB-00:10 |
March | 2217.54 | 01-MAR-10:09 | 2625.88 | 01-MAR-00:10 | 14428.03 | 01-MAR-11:09 | 0.00 | 4762.05 | 02-MAR-23:00 | 0.00 | 22-MAR-08:09 | 0.00 | 01-MAR-00:10 |
April | 2217.54 | 01-APR-16:10 | 2625.88 | 01-APR-00:10 | 14428.03 | 01-APR-10:09 | 0.00 | 4762.05 | 03-APR-11:30 | 0.00 | 05-APR-17:40 | 0.00 | 01-APR-00:10 |
May | 2217.54 | 01-MAY-09:09 | 2625.88 | 01-MAY-00:10 | 14428.03 | 01-MAY-10:09 | 0.00 | 4762.05 | 08-MAY-06:40 | 0.00 | 06-MAY-08:00 | 0.00 | 01-MAY-00:10 |
June | 2217.54 | 01-JUN-09:09 | 2625.88 | 01-JUN-00:10 | 14428.03 | 01-JUN-10:09 | 0.00 | 4762.05 | 01-JUN-05:10 | 0.00 | 15-JUN-08:30 | 0.00 | 01-JUN-00:10 |
July | 2217.54 | 01-JUL-16:10 | 2625.88 | 01-JUL-00:10 | 14428.03 | 01-JUL-10:09 | 0.00 | 4762.05 | 05-JUL-14:50 | 0.00 | 15-JUL-14:39 | 0.00 | 01-JUL-00:10 |
August | 2217.54 | 01-AUG-09:09 | 2625.88 | 01-AUG-00:10 | 14428.03 | 01-AUG-10:09 | 0.00 | 4762.05 | 21-AUG-16:10 | 0.00 | 05-AUG-14:39 | 0.00 | 01-AUG-00:10 |
September | 2217.54 | 01-SEP-09:09 | 2625.88 | 01-SEP-00:10 | 14428.03 | 01-SEP-10:09 | 0.00 | 4762.05 | 03-SEP-13:20 | 0.00 | 05-SEP-10:20 | 0.00 | 01-SEP-00:10 |
October | 2217.54 | 02-OCT-09:09 | 2625.88 | 01-OCT-00:10 | 14428.03 | 01-OCT-10:09 | 0.00 | 4762.05 | 01-OCT-18:30 | 0.00 | 10-OCT-08:30 | 0.00 | 01-OCT-00:10 |
November | 2217.54 | 01-NOV-09:09 | 2625.88 | 01-NOV-00:10 | 14428.03 | 01-NOV-10:09 | 0.00 | 4762.05 | 01-NOV-06:30 | 0.00 | 01-NOV-10:09 | 0.00 | 01-NOV-00:10 |
December | 2217.54 | 01-DEC-10:09 | 2625.88 | 01-DEC-00:10 | 14428.03 | 01-DEC-11:09 | 0.00 | 4762.05 | 01-DEC-06:30 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2217.54 | 2625.88 | 14428.03 | 0.00 | 4762.05 | 0.00 | 0.00 | ||||||
Maximum of Months | 2217.54 | 2625.88 | 14428.03 | 0.00 | 4762.05 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 8076.05 | 18-JAN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7838.68 | 01-FEB-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6345.65 | 23-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10316.41 | 26-APR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7627.26 | 04-MAY-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10854.50 | 29-JUN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13260.24 | 31-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13774.24 | 14-AUG-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17259.77 | 29-SEP-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17867.38 | 16-OCT-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8247.01 | 19-NOV-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8171.13 | 19-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6345.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17867.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 31896.85 | 14-JAN-11:20 | 1971.15 | 14428.03 | 0.00 | 0.00 | 4762.05 | 0.00 | 0.00 | 6229.44 | 0.00 |
February | 31857.72 | 01-FEB-11:00 | 2217.54 | 14428.03 | 0.00 | 0.00 | 4762.05 | 0.00 | 0.00 | 7555.76 | 0.00 |
March | 30468.39 | 11-MAR-11:20 | 1971.15 | 14428.03 | 0.00 | 0.00 | 4762.05 | 0.00 | 0.00 | 4781.40 | 0.00 |
April | 34068.84 | 26-APR-10:00 | 2217.54 | 14428.03 | 0.00 | 0.00 | 4762.05 | 0.00 | 0.00 | 9747.04 | 0.00 |
May | 30981.06 | 03-MAY-10:20 | 2217.54 | 14428.03 | 0.00 | 0.00 | 4762.05 | 0.00 | 0.00 | 5010.91 | 0.00 |
June | 34695.74 | 29-JUN-10:00 | 2217.54 | 14428.03 | 0.00 | 0.00 | 4762.05 | 0.00 | 0.00 | 10353.30 | 0.00 |
July | 36949.98 | 19-JUL-10:20 | 2217.54 | 14428.03 | 0.00 | 0.00 | 4762.05 | 0.00 | 0.00 | 10950.02 | 0.00 |
August | 37572.54 | 14-AUG-10:20 | 2217.54 | 14428.03 | 0.00 | 0.00 | 4762.05 | 0.00 | 0.00 | 11572.58 | 0.00 |
September | 41073.88 | 29-SEP-10:20 | 2217.54 | 14428.03 | 0.00 | 0.00 | 4762.05 | 0.00 | 0.00 | 15125.11 | 0.00 |
October | 41480.45 | 16-OCT-10:20 | 2217.54 | 14428.03 | 0.00 | 0.00 | 4762.05 | 0.00 | 0.00 | 15532.13 | 0.00 |
November | 32123.85 | 19-NOV-11:20 | 1724.75 | 14428.03 | 0.00 | 0.00 | 4762.05 | 0.00 | 0.00 | 6699.66 | 0.00 |
December | 32494.04 | 19-DEC-11:20 | 2217.54 | 14428.03 | 0.00 | 0.00 | 4762.05 | 0.00 | 0.00 | 6560.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 30468.39 | 1724.75 | 14428.03 | 0.00 | 0.00 | 4762.05 | 0.00 | 0.00 | 4781.40 | 0.00 | |
Maximum of Months | 41480.45 | 2217.54 | 14428.03 | 0.00 | 0.00 | 4762.05 | 0.00 | 0.00 | 15532.13 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 35770.19 | 08-JAN-07:10 | 0.00 | 25684.74 | 29-JAN-13:20 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 16686.73 | 05-FEB-07:10 | 0.00 | 25682.83 | 04-FEB-13:50 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 24118.12 | 30-MAR-06:10 | 0.00 | 25620.93 | 02-MAR-13:39 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 17431.87 | 01-APR-06:10 | 0.00 | 25425.01 | 01-APR-12:39 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 7397.74 | 14-MAY-05:10 | 0.00 | 25142.31 | 01-MAY-12:00 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 1663.04 | 01-JUN-06:10 | 0.00 | 24819.14 | 02-JUN-12:39 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 24577.10 | 03-JUL-12:39 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 24552.47 | 31-AUG-12:50 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 3826.31 | 30-SEP-02:49 | 0.00 | 24768.86 | 30-SEP-12:39 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 7343.20 | 29-OCT-06:10 | 0.00 | 25065.27 | 30-OCT-12:00 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 17035.54 | 05-NOV-06:10 | 0.00 | 25368.98 | 30-NOV-13:39 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 20575.65 | 22-DEC-07:10 | 0.00 | 25590.63 | 31-DEC-13:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 0.00 | 0.00 | 24552.47 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 35770.19 | 0.00 | 25684.74 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.52 | 0.00 | 24.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.46 | 0.00 | 24.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.48 | 0.00 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.47 | 0.00 | 24.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.54 | 0.00 | 24.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 24.53 | 0.00 | 24.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.53 | 0.00 | 20.53 | 20.33 | 24.47 | 0.00 | 24.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.53 | 0.00 | 20.53 | 8.17 | 24.54 | 0.00 | 24.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 27.73 | 0.00 | 27.73 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 27.61 | 0.00 | 27.61 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 27.59 | 0.00 | 27.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 28.03 | 0.00 | 28.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 28.14 | 0.00 | 28.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 28.55 | 0.00 | 28.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.75 | 0.00 | 28.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.77 | 0.00 | 28.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 28.59 | 0.67 | 28.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 28.54 | 1.00 | 28.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 27.89 | 0.00 | 27.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 27.69 | 0.00 | 27.69 |
Annual Sum or Average | 0.00 | 0.00 | 326.33 | 28.21 | 1.67 | 28.20 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 27.59 | 0.00 | 27.59 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 28.77 | 1.00 | 28.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 396.83 | 21.47 | 132.67 | 21.98 | 8.00 | 21.94 |
February | 420.17 | 21.47 | 78.17 | 21.80 | 7.50 | 21.80 |
March | 479.83 | 21.34 | 108.50 | 21.72 | 8.33 | 21.68 |
April | 309.50 | 21.54 | 224.67 | 22.50 | 0.00 | 22.50 |
May | 291.83 | 21.67 | 246.50 | 22.66 | 0.17 | 22.66 |
June | 161.50 | 22.51 | 404.67 | 23.42 | 29.33 | 23.43 |
July | 219.50 | 23.77 | 553.83 | 23.82 | 205.50 | 23.82 |
August | 286.83 | 23.78 | 579.83 | 23.82 | 274.00 | 23.82 |
September | 177.33 | 23.17 | 455.50 | 23.62 | 105.50 | 23.64 |
October | 230.33 | 22.95 | 403.17 | 23.52 | 104.17 | 23.57 |
November | 356.50 | 21.63 | 156.50 | 22.28 | 0.83 | 22.28 |
December | 412.17 | 21.57 | 74.50 | 21.86 | 5.33 | 21.83 |
Annual Sum or Average | 3742.33 | 22.03 | 3418.50 | 22.87 | 748.67 | 22.94 |
Minimum of Months | 161.50 | 21.34 | 74.50 | 21.72 | 0.00 | 21.68 |
Maximum of Months | 479.83 | 23.78 | 579.83 | 23.82 | 274.00 | 23.82 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 353.00 | 21.83 | 344.83 | 23.09 | 130.33 | 23.36 |
February | 286.50 | 21.64 | 296.50 | 22.92 | 78.50 | 23.18 |
March | 372.33 | 21.46 | 301.83 | 22.62 | 103.00 | 22.90 |
April | 366.17 | 24.18 | 429.33 | 24.58 | 241.33 | 24.89 |
May | 374.83 | 24.66 | 480.67 | 24.85 | 282.83 | 25.11 |
June | 401.67 | 25.81 | 570.50 | 25.50 | 393.67 | 25.61 |
July | 514.83 | 25.90 | 608.83 | 25.77 | 514.83 | 25.81 |
August | 538.67 | 25.88 | 612.00 | 25.77 | 538.67 | 25.80 |
September | 427.50 | 25.84 | 581.67 | 25.58 | 422.67 | 25.67 |
October | 456.50 | 25.58 | 553.83 | 25.60 | 417.00 | 25.72 |
November | 307.33 | 23.05 | 391.00 | 23.96 | 151.50 | 24.27 |
December | 341.83 | 21.92 | 340.00 | 23.23 | 120.33 | 23.52 |
Annual Sum or Average | 4741.17 | 24.24 | 5511.00 | 24.69 | 3394.67 | 24.96 |
Minimum of Months | 286.50 | 21.46 | 296.50 | 22.62 | 78.50 | 22.90 |
Maximum of Months | 538.67 | 25.90 | 612.00 | 25.77 | 538.67 | 25.81 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.25693 | 42.10359 | 0.06878 | 7.43907 |
February | 551.00000 | 21.99658 | 45.85424 | 0.01428 | 6.80778 |
March | 612.00000 | 21.84510 | 49.70673 | -0.0032 | 7.05267 |
April | 590.00000 | 22.58618 | 51.93945 | 0.22001 | 7.94568 |
May | 611.00000 | 22.74964 | 50.99191 | -0.7239 | 19.21058 |
June | 592.00000 | 23.39139 | 55.84084 | -0.4572 | 11.03540 |
July | 609.00000 | 23.77594 | 61.00755 | -0.2551 | 6.95341 |
August | 612.00000 | 23.78586 | 63.01029 | -0.2271 | 6.67606 |
September | 590.00000 | 23.55556 | 57.73063 | -0.3495 | 8.97170 |
October | 610.00000 | 23.46833 | 47.92853 | 0.44630 | 10.51683 |
November | 591.00000 | 22.45479 | 43.28744 | 0.14170 | 7.39851 |
December | 609.00000 | 22.26709 | 36.90224 | 0.04342 | 7.00290 |
Annual Sum or Average | 7187.00000 | 22.84973 | 50.54922 | -0.0909 | 8.93696 |
Minimum of Months | 551.00000 | 21.84510 | 36.90224 | -0.7239 | 6.67606 |
Maximum of Months | 612.00000 | 23.78586 | 63.01029 | 0.44630 | 19.21058 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.65745 | 44.11944 | 0.39151 | 15.65823 |
February | 551.00000 | 22.55352 | 47.24965 | 0.38147 | 13.46638 |
March | 612.00000 | 22.21138 | 51.50811 | 0.33062 | 13.67987 |
April | 590.00000 | 23.87943 | 50.89932 | 0.73277 | 21.02241 |
May | 611.00000 | 24.19010 | 49.54239 | 0.06083 | 13.33644 |
June | 592.00000 | 25.14621 | 52.38403 | 0.41329 | 12.81733 |
July | 609.00000 | 25.64884 | 56.06815 | 0.63254 | 15.57599 |
August | 612.00000 | 25.67581 | 57.67895 | 0.65166 | 15.94540 |
September | 590.00000 | 25.32747 | 53.77926 | 0.49213 | 13.53683 |
October | 610.00000 | 25.23205 | 45.19736 | 1.03845 | 30.67989 |
November | 591.00000 | 23.39413 | 43.81658 | 0.57212 | 17.25329 |
December | 609.00000 | 22.78757 | 39.31026 | 0.38805 | 14.63082 |
Annual Sum or Average | 7187.00000 | 24.06693 | 49.30617 | 0.50756 | 16.49310 |
Minimum of Months | 551.00000 | 22.21138 | 39.31026 | 0.06083 | 12.81733 |
Maximum of Months | 612.00000 | 25.67581 | 57.67895 | 1.03845 | 30.67989 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.125035E+10 | 0.394621E+09 | 57.80 | 0.117958E+10 | 70769622.58 | 0.00 | 0.48 | 18-JAN-12:55 | 0.00 | 01-JAN-00:03 | 14421.31 | 18-JAN-12:55 | 14421.31 | 18-JAN-12:55 | 2340.60 | 17-JAN-14:00 | 4334.22 | 18-JAN-12:55 | 0.00 | 01-JAN-00:03 |
February | 0.261234E+09 | 83281659.99 | 17.42 | 0.259260E+09 | 1974004.20 | 0.00 | 0.42 | 01-FEB-12:05 | 0.00 | 01-FEB-00:10 | 12561.25 | 01-FEB-12:05 | 12561.25 | 01-FEB-12:05 | 861.28 | 01-FEB-13:30 | 3829.39 | 01-FEB-12:05 | 0.00 | 01-FEB-00:10 |
March | 0.531860E+09 | 0.170186E+09 | 29.91 | 0.463483E+09 | 68377123.72 | 0.00 | 0.32 | 11-MAR-14:00 | 0.00 | 01-MAR-00:03 | 9181.51 | 11-MAR-14:00 | 9181.51 | 11-MAR-14:00 | 2409.11 | 22-MAR-13:00 | 2874.03 | 11-MAR-14:00 | 0.00 | 01-MAR-00:03 |
April | 0.174176E+10 | 0.551628E+09 | 89.68 | 0.144798E+10 | 0.293772E+09 | 0.00 | 0.55 | 26-APR-11:13 | 0.00 | 01-APR-00:01 | 17037.33 | 26-APR-11:13 | 14592.04 | 26-APR-13:00 | 3768.28 | 27-APR-03:57 | 4971.42 | 26-APR-11:13 | 0.00 | 01-APR-00:01 |
May | 0.101793E+10 | 0.327999E+09 | 77.29 | 0.834313E+09 | 0.183617E+09 | 0.00 | 0.43 | 04-MAY-12:00 | 0.00 | 01-MAY-00:01 | 12828.88 | 04-MAY-12:00 | 10863.47 | 04-MAY-12:00 | 3521.49 | 03-MAY-03:57 | 3902.92 | 04-MAY-12:00 | 0.00 | 01-MAY-00:01 |
June | 0.396584E+10 | 0.123737E+10 | 180.48 | 0.285532E+10 | 0.111052E+10 | 0.00 | 0.54 | 29-JUN-11:10 | 0.00 | 01-JUN-00:01 | 17279.53 | 29-JUN-11:10 | 11556.24 | 29-JUN-11:05 | 6021.90 | 30-JUN-00:09 | 4950.05 | 29-JUN-11:10 | 0.00 | 01-JUN-00:01 |
July | 0.976914E+10 | 0.292994E+10 | 299.07 | 0.649137E+10 | 0.327777E+10 | 0.00 | 0.75 | 31-JUL-11:55 | 0.00 | 01-JUL-00:01 | 25489.66 | 31-JUL-11:55 | 16885.63 | 31-JUL-12:00 | 8604.11 | 31-JUL-11:55 | 6849.38 | 31-JUL-11:55 | 0.00 | 01-JUL-00:01 |
August | 0.112253E+11 | 0.333901E+10 | 302.93 | 0.733293E+10 | 0.389237E+10 | 0.00 | 0.75 | 18-AUG-11:55 | 0.00 | 01-AUG-00:01 | 25784.35 | 18-AUG-11:55 | 17115.58 | 18-AUG-12:00 | 8669.10 | 18-AUG-11:55 | 6915.25 | 18-AUG-11:55 | 0.00 | 01-AUG-00:01 |
September | 0.576412E+10 | 0.178350E+10 | 217.68 | 0.441041E+10 | 0.135371E+10 | 0.00 | 1.00 | 22-SEP-00:42 | 0.00 | 01-SEP-00:01 | 37070.15 | 22-SEP-00:42 | 34750.46 | 30-SEP-02:62 | 19827.64 | 22-SEP-00:42 | 9212.89 | 22-SEP-00:42 | 0.00 | 01-SEP-00:01 |
October | 0.753806E+10 | 0.231754E+10 | 254.30 | 0.644596E+10 | 0.109210E+10 | 0.00 | 1.00 | 01-OCT-03:21 | 0.00 | 01-OCT-00:01 | 36616.36 | 05-OCT-00:42 | 34750.46 | 16-OCT-00:09 | 20272.75 | 01-OCT-03:21 | 9403.80 | 16-OCT-11:07 | 0.00 | 01-OCT-00:01 |
November | 0.104233E+10 | 0.329136E+09 | 51.84 | 0.102309E+10 | 19242531.76 | 0.00 | 0.45 | 19-NOV-13:00 | 0.00 | 01-NOV-00:01 | 13567.86 | 19-NOV-13:00 | 13567.86 | 19-NOV-13:00 | 2734.92 | 11-NOV-05:00 | 4104.38 | 19-NOV-13:00 | 0.00 | 01-NOV-00:01 |
December | 0.151634E+10 | 0.481633E+09 | 87.45 | 0.150712E+10 | 9224056.26 | 0.00 | 0.49 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 | 14826.05 | 19-DEC-13:00 | 14826.05 | 19-DEC-13:00 | 1143.42 | 07-DEC-13:55 | 4442.18 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.456243E+11 | 0.139458E+11 | 1665.87 | 0.342508E+11 | 0.113734E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.261234E+09 | 83281659.99 | 17.42 | 0.259260E+09 | 1974004.20 | 0.00 | 0.32 | 0.00 | 9181.51 | 9181.51 | 861.28 | 2874.03 | 0.00 | |||||||
Maximum of Months | 0.112253E+11 | 0.333901E+10 | 302.93 | 0.733293E+10 | 0.389237E+10 | 0.00 | 1.00 | 0.00 | 37070.15 | 34750.46 | 20272.75 | 9403.80 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.179418E+10 | 0.552908E+09 | 86.92 | 0.156899E+10 | 0.225193E+09 | 0.00 | 1.00 | 10-JAN-04:51 | 0.00 | 01-JAN-00:03 | 27524.46 | 15-JAN-04:22 | 27524.46 | 15-JAN-02:22 | 14739.11 | 31-JAN-04:31 | 7164.08 | 10-JAN-04:51 | 0.00 | 01-JAN-00:03 |
February | 0.491685E+09 | 0.153066E+09 | 38.41 | 0.432817E+09 | 58868227.02 | 0.00 | 1.00 | 01-FEB-02:32 | 0.00 | 01-FEB-00:10 | 27524.46 | 01-FEB-02:32 | 27524.46 | 03-FEB-04:31 | 15288.47 | 14-FEB-04:31 | 7164.08 | 01-FEB-02:32 | 0.00 | 01-FEB-00:10 |
March | 0.896071E+09 | 0.280924E+09 | 52.29 | 0.684486E+09 | 0.211586E+09 | 0.00 | 1.00 | 03-MAR-04:11 | 0.00 | 01-MAR-00:03 | 27524.46 | 03-MAR-04:11 | 15676.05 | 27-MAR-03:42 | 14973.45 | 24-MAR-03:31 | 7164.08 | 03-MAR-04:11 | 0.00 | 01-MAR-00:03 |
April | 0.307401E+10 | 0.947752E+09 | 147.92 | 0.231413E+10 | 0.759876E+09 | 0.00 | 1.00 | 04-APR-03:31 | 0.00 | 01-APR-00:01 | 27524.46 | 25-APR-04:01 | 16918.68 | 29-APR-03:21 | 16008.42 | 27-APR-00:42 | 7164.08 | 04-APR-03:31 | 0.00 | 01-APR-00:01 |
May | 0.292377E+10 | 0.911280E+09 | 160.35 | 0.212973E+10 | 0.794036E+09 | 0.00 | 1.00 | 01-MAY-03:21 | 0.00 | 01-MAY-00:01 | 27524.46 | 02-MAY-03:31 | 26287.81 | 24-MAY-03:21 | 15126.82 | 03-MAY-04:01 | 7164.08 | 01-MAY-03:21 | 0.00 | 01-MAY-00:01 |
June | 0.744948E+10 | 0.222726E+10 | 250.76 | 0.493398E+10 | 0.251550E+10 | 0.00 | 1.00 | 02-JUN-03:21 | 0.00 | 01-JUN-00:01 | 27524.46 | 06-JUN-01:22 | 16873.18 | 23-JUN-03:21 | 16540.82 | 28-JUN-02:62 | 7164.08 | 02-JUN-03:21 | 0.00 | 01-JUN-00:01 |
July | 0.151608E+11 | 0.431783E+10 | 360.71 | 0.922043E+10 | 0.594039E+10 | 0.00 | 1.00 | 01-JUL-00:42 | 0.00 | 01-JUL-00:01 | 27760.73 | 23-JUL-00:42 | 19348.10 | 19-JUL-11:00 | 17116.41 | 20-JUL-04:01 | 7181.44 | 23-JUL-00:42 | 0.00 | 01-JUL-00:01 |
August | 0.163856E+11 | 0.462014E+10 | 366.55 | 0.974049E+10 | 0.664507E+10 | 0.00 | 1.00 | 01-AUG-00:42 | 0.00 | 01-AUG-00:01 | 28908.11 | 14-AUG-10:53 | 19410.91 | 14-AUG-11:00 | 17915.07 | 07-AUG-02:42 | 7212.12 | 07-AUG-01:22 | 0.00 | 01-AUG-00:01 |
September | 0.971228E+10 | 0.286408E+10 | 277.71 | 0.664855E+10 | 0.306374E+10 | 0.00 | 1.00 | 01-SEP-00:42 | 0.00 | 01-SEP-00:01 | 29180.06 | 22-SEP-00:03 | 28068.07 | 29-SEP-12:40 | 17099.75 | 22-SEP-01:22 | 8301.60 | 29-SEP-10:55 | 0.00 | 01-SEP-00:01 |
October | 0.113624E+11 | 0.334212E+10 | 322.14 | 0.880601E+10 | 0.255638E+10 | 0.00 | 1.00 | 01-OCT-00:42 | 0.00 | 01-OCT-00:01 | 28803.58 | 05-OCT-00:03 | 27980.48 | 16-OCT-11:00 | 17910.94 | 01-OCT-04:02 | 8493.47 | 16-OCT-10:53 | 0.00 | 01-OCT-00:01 |
November | 0.156221E+10 | 0.484003E+09 | 88.20 | 0.138089E+10 | 0.181322E+09 | 0.00 | 1.00 | 01-NOV-03:21 | 0.00 | 01-NOV-00:01 | 27524.46 | 10-NOV-02:22 | 27524.46 | 28-NOV-02:22 | 16199.10 | 12-NOV-03:02 | 7164.08 | 01-NOV-03:21 | 0.00 | 01-NOV-00:01 |
December | 0.198532E+10 | 0.619608E+09 | 109.09 | 0.192372E+10 | 61594491.47 | 0.00 | 1.00 | 01-DEC-03:52 | 0.00 | 01-DEC-00:10 | 27524.46 | 06-DEC-01:42 | 27524.46 | 06-DEC-02:22 | 14133.02 | 08-DEC-04:31 | 7164.08 | 01-DEC-03:52 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.727978E+11 | 0.213210E+11 | 2261.07 | 0.497842E+11 | 0.230136E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.491685E+09 | 0.153066E+09 | 38.41 | 0.432817E+09 | 58868227.02 | 0.00 | 1.00 | 0.00 | 27524.46 | 15676.05 | 14133.02 | 7164.08 | 0.00 | |||||||
Maximum of Months | 0.163856E+11 | 0.462014E+10 | 366.55 | 0.974049E+10 | 0.664507E+10 | 0.00 | 1.00 | 0.00 | 29180.06 | 28068.07 | 17915.07 | 8493.47 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.27 | 41.34 | 35.93 | 90.24 | 141.65 | 0.00 | 0.00 | 0.00 |
February | 81.48 | 37.33 | 44.15 | 89.38 | 127.66 | 0.00 | 0.00 | 0.00 |
March | 98.93 | 44.06 | 54.88 | 117.05 | 125.93 | 0.00 | 0.00 | 0.00 |
April | 126.50 | 63.43 | 63.08 | 174.16 | 102.54 | 0.00 | 0.00 | 0.00 |
May | 119.39 | 49.81 | 69.58 | 156.18 | 94.00 | 0.00 | 0.00 | 0.00 |
June | 118.67 | 51.49 | 67.18 | 167.36 | 77.19 | 0.00 | 0.00 | 0.00 |
July | 134.45 | 66.80 | 67.64 | 207.55 | 70.37 | 0.00 | 0.00 | 0.00 |
August | 132.76 | 70.50 | 62.26 | 206.96 | 72.66 | 0.00 | 0.00 | 0.00 |
September | 96.69 | 44.31 | 52.38 | 138.94 | 85.29 | 0.00 | 0.00 | 0.00 |
October | 85.58 | 43.98 | 41.60 | 126.51 | 94.62 | 0.00 | 0.00 | 0.00 |
November | 78.04 | 39.66 | 38.38 | 91.07 | 129.54 | 0.00 | 0.00 | 0.00 |
December | 74.47 | 41.40 | 33.08 | 86.50 | 141.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 102.16 | 49.61 | 52.55 | 138.00 | 105.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.47 | 37.33 | 33.08 | 86.50 | 70.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.45 | 70.50 | 69.58 | 207.55 | 141.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 377.35 | 276.65 | 100.71 | 575.66 | 272.46 | 0.00 | 0.00 | 0.00 |
February | 296.95 | 182.87 | 114.08 | 420.18 | 249.09 | 0.00 | 0.00 | 0.00 |
March | 237.26 | 114.83 | 122.42 | 330.17 | 258.51 | 0.00 | 0.00 | 0.00 |
April | 198.94 | 76.52 | 122.42 | 292.65 | 216.96 | 0.00 | 0.00 | 0.00 |
May | 141.43 | 17.88 | 123.56 | 157.22 | 201.63 | 0.00 | 0.00 | 0.00 |
June | 123.94 | 7.80 | 116.14 | 136.16 | 162.10 | 0.00 | 0.00 | 0.00 |
July | 131.47 | 15.28 | 116.19 | 175.75 | 146.23 | 0.00 | 0.00 | 0.00 |
August | 169.20 | 54.06 | 115.15 | 271.88 | 153.01 | 0.00 | 0.00 | 0.00 |
September | 234.86 | 119.41 | 115.45 | 385.61 | 174.23 | 0.00 | 0.00 | 0.00 |
October | 297.76 | 199.10 | 98.67 | 499.25 | 187.51 | 0.00 | 0.00 | 0.00 |
November | 361.35 | 254.98 | 106.37 | 547.98 | 249.22 | 0.00 | 0.00 | 0.00 |
December | 403.06 | 306.61 | 96.45 | 620.44 | 270.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 247.59 | 135.34 | 112.25 | 367.61 | 211.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 123.94 | 7.80 | 96.45 | 136.16 | 146.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.06 | 306.61 | 123.56 | 620.44 | 272.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.55 | 37.12 | 36.44 | 87.10 | 146.10 | 0.00 | 0.00 | 0.00 |
February | 87.69 | 40.47 | 47.22 | 100.75 | 129.53 | 0.00 | 0.00 | 0.00 |
March | 100.50 | 44.44 | 56.06 | 120.55 | 129.09 | 0.00 | 0.00 | 0.00 |
April | 138.54 | 72.11 | 66.43 | 192.25 | 103.89 | 0.00 | 0.00 | 0.00 |
May | 136.10 | 62.84 | 73.26 | 182.15 | 94.61 | 0.00 | 0.00 | 0.00 |
June | 144.17 | 72.05 | 72.12 | 206.35 | 76.12 | 0.00 | 0.00 | 0.00 |
July | 152.62 | 81.64 | 70.98 | 234.04 | 69.22 | 0.00 | 0.00 | 0.00 |
August | 143.18 | 77.57 | 65.61 | 221.67 | 73.73 | 0.00 | 0.00 | 0.00 |
September | 122.59 | 65.57 | 57.02 | 180.83 | 84.94 | 0.00 | 0.00 | 0.00 |
October | 93.74 | 51.17 | 42.57 | 141.73 | 96.30 | 0.00 | 0.00 | 0.00 |
November | 84.70 | 44.31 | 40.39 | 104.83 | 131.41 | 0.00 | 0.00 | 0.00 |
December | 74.83 | 40.15 | 34.68 | 91.50 | 146.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.78 | 57.53 | 55.26 | 155.59 | 106.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.55 | 37.12 | 34.68 | 87.10 | 69.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.62 | 81.64 | 73.26 | 234.04 | 146.15 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206957E+09 | 0.110723E+09 | 96234301.66 | 0.241693E+09 | 0.379398E+09 |
February | 0.197119E+09 | 90304614.47 | 0.106815E+09 | 0.216232E+09 | 0.308830E+09 |
March | 0.264984E+09 | 0.118003E+09 | 0.146980E+09 | 0.313499E+09 | 0.337282E+09 |
April | 0.327896E+09 | 0.164403E+09 | 0.163493E+09 | 0.451433E+09 | 0.265794E+09 |
May | 0.319775E+09 | 0.133412E+09 | 0.186363E+09 | 0.418312E+09 | 0.251768E+09 |
June | 0.307587E+09 | 0.133453E+09 | 0.174134E+09 | 0.433794E+09 | 0.200079E+09 |
July | 0.360102E+09 | 0.178923E+09 | 0.181179E+09 | 0.555889E+09 | 0.188466E+09 |
August | 0.355585E+09 | 0.188834E+09 | 0.166751E+09 | 0.554319E+09 | 0.194613E+09 |
September | 0.250616E+09 | 0.114848E+09 | 0.135768E+09 | 0.360126E+09 | 0.221077E+09 |
October | 0.229212E+09 | 0.117802E+09 | 0.111409E+09 | 0.338856E+09 | 0.253423E+09 |
November | 0.202272E+09 | 0.102786E+09 | 99486186.79 | 0.236055E+09 | 0.335771E+09 |
December | 0.199465E+09 | 0.110876E+09 | 88588718.57 | 0.231675E+09 | 0.380011E+09 |
Annual Sum or Average | 0.322157E+10 | 0.156437E+10 | 0.165720E+10 | 0.435188E+10 | 0.331651E+10 |
Minimum of Months | 0.197119E+09 | 90304614.47 | 88588718.57 | 0.216232E+09 | 0.188466E+09 |
Maximum of Months | 0.360102E+09 | 0.188834E+09 | 0.186363E+09 | 0.555889E+09 | 0.380011E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101070E+10 | 0.740972E+09 | 0.269730E+09 | 0.154186E+10 | 0.729758E+09 |
February | 0.718381E+09 | 0.442395E+09 | 0.275986E+09 | 0.101650E+10 | 0.602597E+09 |
March | 0.635467E+09 | 0.307571E+09 | 0.327896E+09 | 0.884328E+09 | 0.692398E+09 |
April | 0.515653E+09 | 0.198347E+09 | 0.317306E+09 | 0.758537E+09 | 0.562371E+09 |
May | 0.378818E+09 | 47884912.69 | 0.330933E+09 | 0.421106E+09 | 0.540046E+09 |
June | 0.321244E+09 | 20209321.72 | 0.301035E+09 | 0.352936E+09 | 0.420173E+09 |
July | 0.352124E+09 | 40919658.65 | 0.311204E+09 | 0.470730E+09 | 0.391664E+09 |
August | 0.453198E+09 | 0.144787E+09 | 0.308412E+09 | 0.728200E+09 | 0.409824E+09 |
September | 0.608759E+09 | 0.309508E+09 | 0.299252E+09 | 0.999507E+09 | 0.451613E+09 |
October | 0.797533E+09 | 0.533261E+09 | 0.264272E+09 | 0.133720E+10 | 0.502224E+09 |
November | 0.936626E+09 | 0.660916E+09 | 0.275709E+09 | 0.142037E+10 | 0.645990E+09 |
December | 0.107955E+10 | 0.821225E+09 | 0.258327E+09 | 0.166179E+10 | 0.725760E+09 |
Annual Sum or Average | 0.780805E+10 | 0.426799E+10 | 0.354006E+10 | 0.115931E+11 | 0.667442E+10 |
Minimum of Months | 0.321244E+09 | 20209321.72 | 0.258327E+09 | 0.352936E+09 | 0.391664E+09 |
Maximum of Months | 0.107955E+10 | 0.821225E+09 | 0.330933E+09 | 0.166179E+10 | 0.729758E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197008E+09 | 99410172.27 | 97597783.02 | 0.233281E+09 | 0.391313E+09 |
February | 0.212142E+09 | 97913542.20 | 0.114229E+09 | 0.243738E+09 | 0.313362E+09 |
March | 0.269183E+09 | 0.119040E+09 | 0.150144E+09 | 0.322887E+09 | 0.345753E+09 |
April | 0.359101E+09 | 0.186918E+09 | 0.172183E+09 | 0.498306E+09 | 0.269290E+09 |
May | 0.364520E+09 | 0.168304E+09 | 0.196217E+09 | 0.487861E+09 | 0.253417E+09 |
June | 0.373690E+09 | 0.186762E+09 | 0.186928E+09 | 0.534866E+09 | 0.197295E+09 |
July | 0.408773E+09 | 0.218657E+09 | 0.190116E+09 | 0.626853E+09 | 0.185405E+09 |
August | 0.383501E+09 | 0.207770E+09 | 0.175731E+09 | 0.593719E+09 | 0.197483E+09 |
September | 0.317759E+09 | 0.169969E+09 | 0.147790E+09 | 0.468718E+09 | 0.220170E+09 |
October | 0.251077E+09 | 0.137062E+09 | 0.114015E+09 | 0.379601E+09 | 0.257927E+09 |
November | 0.219551E+09 | 0.114860E+09 | 0.104691E+09 | 0.271708E+09 | 0.340605E+09 |
December | 0.200430E+09 | 0.107549E+09 | 92881183.59 | 0.245084E+09 | 0.391449E+09 |
Annual Sum or Average | 0.355674E+10 | 0.181421E+10 | 0.174252E+10 | 0.490662E+10 | 0.336347E+10 |
Minimum of Months | 0.197008E+09 | 97913542.20 | 92881183.59 | 0.233281E+09 | 0.185405E+09 |
Maximum of Months | 0.408773E+09 | 0.218657E+09 | 0.196217E+09 | 0.626853E+09 | 0.391449E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 736.56 | 543.78 | 528.18 | 355.10 | 173.07 | 0.00 | 0.00 |
February | 597.20 | 493.17 | 466.12 | 260.67 | 205.45 | 0.00 | 0.00 |
March | 549.58 | 495.33 | 436.69 | 203.34 | 233.36 | 0.00 | 0.00 |
April | 638.81 | 403.15 | 463.99 | 212.06 | 251.92 | 0.00 | 0.00 |
May | 474.26 | 368.96 | 396.92 | 130.53 | 266.39 | 0.00 | 0.00 |
June | 493.17 | 298.70 | 386.78 | 131.34 | 255.44 | 0.00 | 0.00 |
July | 603.02 | 271.50 | 418.53 | 163.72 | 254.82 | 0.00 | 0.00 |
August | 687.61 | 286.51 | 445.15 | 202.13 | 243.02 | 0.00 | 0.00 |
September | 694.28 | 333.36 | 454.14 | 229.29 | 224.85 | 0.00 | 0.00 |
October | 758.00 | 368.93 | 477.08 | 294.25 | 182.83 | 0.00 | 0.00 |
November | 729.23 | 495.53 | 524.09 | 338.95 | 185.14 | 0.00 | 0.00 |
December | 781.37 | 541.93 | 552.36 | 388.16 | 164.20 | 0.00 | 0.00 |
Annual Sum or Average | 645.72 | 407.99 | 462.53 | 242.47 | 220.06 | 0.00 | 0.00 |
Minimum of Months | 474.26 | 271.50 | 386.78 | 130.53 | 164.20 | 0.00 | 0.00 |
Maximum of Months | 781.37 | 543.78 | 552.36 | 388.16 | 266.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.197281E+10 | 0.145645E+10 | 0.141467E+10 | 0.951104E+09 | 0.463562E+09 | 0.00 | 0.00 |
February | 0.144475E+10 | 0.119307E+10 | 0.112764E+10 | 0.630613E+09 | 0.497029E+09 | 0.00 | 0.00 |
March | 0.147198E+10 | 0.132670E+10 | 0.116963E+10 | 0.544613E+09 | 0.625020E+09 | 0.00 | 0.00 |
April | 0.165579E+10 | 0.104497E+10 | 0.120265E+10 | 0.549668E+09 | 0.652981E+09 | 0.00 | 0.00 |
May | 0.127026E+10 | 0.988217E+09 | 0.106311E+10 | 0.349601E+09 | 0.713512E+09 | 0.00 | 0.00 |
June | 0.127829E+10 | 0.774239E+09 | 0.100252E+10 | 0.340424E+09 | 0.662097E+09 | 0.00 | 0.00 |
July | 0.161513E+10 | 0.727191E+09 | 0.112100E+10 | 0.438500E+09 | 0.682500E+09 | 0.00 | 0.00 |
August | 0.184170E+10 | 0.767386E+09 | 0.119228E+10 | 0.541390E+09 | 0.650894E+09 | 0.00 | 0.00 |
September | 0.179956E+10 | 0.864070E+09 | 0.117713E+10 | 0.594324E+09 | 0.582810E+09 | 0.00 | 0.00 |
October | 0.203023E+10 | 0.988148E+09 | 0.127782E+10 | 0.788126E+09 | 0.489695E+09 | 0.00 | 0.00 |
November | 0.189018E+10 | 0.128441E+10 | 0.135845E+10 | 0.878563E+09 | 0.479886E+09 | 0.00 | 0.00 |
December | 0.209283E+10 | 0.145151E+10 | 0.147945E+10 | 0.103965E+10 | 0.439796E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.203635E+11 | 0.128664E+11 | 0.145864E+11 | 0.764658E+10 | 0.693978E+10 | 0.00 | 0.00 |
Minimum of Months | 0.127026E+10 | 0.727191E+09 | 0.100252E+10 | 0.340424E+09 | 0.439796E+09 | 0.00 | 0.00 |
Maximum of Months | 0.209283E+10 | 0.145645E+10 | 0.147945E+10 | 0.103965E+10 | 0.713512E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.121731E+11 | -0.114485E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -724531059.9 | 58.99 | 0.00 | 0.00 |
February | 0.110082E+11 | -0.103523E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -655895241.4 | 58.99 | 0.00 | 0.00 |
March | 0.120920E+11 | -0.113599E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -732078211.9 | 58.99 | 0.00 | 0.00 |
April | 0.114181E+11 | -0.107377E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -680427564.5 | 58.98 | 0.00 | 0.00 |
May | 0.115247E+11 | -0.108269E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -697804617.5 | 58.99 | 0.00 | 0.00 |
June | 0.108963E+11 | -0.102374E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -658907138.6 | 58.99 | 0.00 | 0.00 |
July | 0.110635E+11 | -0.103915E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -671997359.2 | 58.99 | 0.00 | 0.00 |
August | 0.110795E+11 | -0.104082E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -671396624.0 | 58.99 | 0.00 | 0.00 |
September | 0.108287E+11 | -0.101728E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -655923403.7 | 58.99 | 0.00 | 0.00 |
October | 0.114354E+11 | -0.107557E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -679653113.3 | 58.98 | 0.00 | 0.00 |
November | 0.113801E+11 | -0.106916E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -688510818.8 | 58.99 | 0.00 | 0.00 |
December | 0.120035E+11 | -0.112809E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -722543300.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.136903E+12 | -0.128663E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.823967E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.108287E+11 | -0.114485E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -732078211.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.121731E+11 | -0.101728E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -655895241.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 293.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 338.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 393.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 381.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 328.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 300.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 297.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4065.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.348662E+10 | 16315.84 | 08-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.241669E+10 | 9374.95 | 05-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.381733E+10 | 20785.06 | 30-MAR-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.772811E+09 | 9565.45 | 01-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.531154E+09 | 4759.57 | 14-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9754774.18 | 1330.56 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12921822.93 | 12244.20 | 30-SEP-02:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148718E+09 | 16771.13 | 16-OCT-02:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127022E+10 | 9613.95 | 05-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.302150E+10 | 10432.58 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.381733E+10 | 20785.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103907E+10 | 17493.68 | 08-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.304462E+09 | 13611.98 | 05-FEB-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.736487E+09 | 14538.11 | 30-MAR-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34063657.63 | 6289.44 | 01-APR-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14159089.35 | 8708.36 | 14-MAY-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 587979.65 | 2817.60 | 30-OCT-04:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98334520.56 | 8623.90 | 18-NOV-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.614153E+09 | 13580.77 | 21-DEC-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103907E+10 | 17493.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.125035E+10 | 0.117958E+10 | 14421.31 | 18-JAN-12:55 | 14421.31 | 0.00 |
February | 0.00 | 0.00 | 0.261234E+09 | 0.259260E+09 | 12561.25 | 01-FEB-12:05 | 12561.25 | 0.00 |
March | 0.00 | 0.00 | 0.531860E+09 | 0.463483E+09 | 9181.51 | 11-MAR-14:00 | 9181.51 | 0.00 |
April | 0.00 | 0.00 | 0.174176E+10 | 0.144798E+10 | 17037.33 | 26-APR-11:13 | 13489.49 | 0.00 |
May | 0.00 | 0.00 | 0.101793E+10 | 0.834313E+09 | 12828.88 | 04-MAY-12:00 | 10863.47 | 0.00 |
June | 0.00 | 0.00 | 0.396584E+10 | 0.285532E+10 | 17279.53 | 29-JUN-11:10 | 11554.25 | 0.00 |
July | 0.00 | 0.00 | 0.976914E+10 | 0.649137E+10 | 25489.66 | 31-JUL-11:55 | 16885.55 | 0.00 |
August | 0.00 | 0.00 | 0.112253E+11 | 0.733293E+10 | 25784.35 | 18-AUG-11:55 | 17115.25 | 0.00 |
September | 0.00 | 0.00 | 0.576412E+10 | 0.441041E+10 | 37070.15 | 22-SEP-00:42 | 17242.51 | 0.00 |
October | 0.00 | 0.00 | 0.753806E+10 | 0.644596E+10 | 36616.36 | 05-OCT-00:42 | 18808.49 | 0.00 |
November | 0.00 | 0.00 | 0.104233E+10 | 0.102309E+10 | 13567.86 | 19-NOV-13:00 | 13567.86 | 0.00 |
December | 0.00 | 0.00 | 0.151634E+10 | 0.150712E+10 | 14826.05 | 19-DEC-13:00 | 14826.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.456243E+11 | 0.342508E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.261234E+09 | 0.259260E+09 | 9181.51 | 9181.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.112253E+11 | 0.733293E+10 | 37070.15 | 18808.49 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.179418E+10 | 0.156899E+10 | 27524.46 | 15-JAN-04:22 | 27524.46 | 0.00 |
February | 0.00 | 0.00 | 0.491685E+09 | 0.432817E+09 | 27524.46 | 01-FEB-02:32 | 25075.97 | 0.00 |
March | 0.00 | 0.00 | 0.896071E+09 | 0.684486E+09 | 27524.46 | 03-MAR-04:11 | 15562.54 | 0.00 |
April | 0.00 | 0.00 | 0.307401E+10 | 0.231413E+10 | 27524.46 | 25-APR-04:01 | 13727.92 | 0.00 |
May | 0.00 | 0.00 | 0.292377E+10 | 0.212973E+10 | 27524.46 | 02-MAY-03:31 | 14299.48 | 0.00 |
June | 0.00 | 0.00 | 0.744948E+10 | 0.493398E+10 | 27524.46 | 06-JUN-01:22 | 14657.19 | 0.00 |
July | 0.00 | 0.00 | 0.151608E+11 | 0.922043E+10 | 27760.73 | 23-JUL-00:42 | 11399.85 | 0.00 |
August | 0.00 | 0.00 | 0.163856E+11 | 0.974049E+10 | 28908.11 | 14-AUG-10:53 | 19404.50 | 0.00 |
September | 0.00 | 0.00 | 0.971228E+10 | 0.664855E+10 | 29180.06 | 22-SEP-00:03 | 12196.67 | 0.00 |
October | 0.00 | 0.00 | 0.113624E+11 | 0.880601E+10 | 28803.58 | 05-OCT-00:03 | 13277.59 | 0.00 |
November | 0.00 | 0.00 | 0.156221E+10 | 0.138089E+10 | 27524.46 | 10-NOV-02:22 | 12949.05 | 0.00 |
December | 0.00 | 0.00 | 0.198532E+10 | 0.192372E+10 | 27524.46 | 06-DEC-01:42 | 27524.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.727978E+11 | 0.497842E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.491685E+09 | 0.432817E+09 | 27524.46 | 11399.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.163856E+11 | 0.974049E+10 | 29180.06 | 27524.46 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4566.07 | 16800.23 | 31-JAN-13:25 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 4570.98 | 16800.87 | 02-FEB-13:25 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 4535.11 | 16717.51 | 01-MAR-14:00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4433.58 | 16437.12 | 01-APR-13:00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 4334.93 | 16049.15 | 01-MAY-12:30 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 4243.06 | 15638.49 | 01-JUN-12:40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4170.18 | 15336.20 | 01-JUL-12:40 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4179.95 | 15291.52 | 31-AUG-12:20 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 4216.10 | 15561.58 | 30-SEP-13:00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4307.38 | 15959.93 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4417.34 | 16359.55 | 30-NOV-14:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4502.42 | 16673.20 | 31-DEC-13:15 |
Annual Sum or Average | 0.00 | 4371.96 | ||||
Minimum of Months | 0.00 | 0.00 | 4170.18 | 15291.52 | ||
Maximum of Months | 0.00 | 0.00 | 4570.98 | 16800.87 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.303749E+10 | 0.60 | 1211.87 | 01-JAN-00:03 | 0.65 |
February | 0.277311E+10 | 0.61 | 1211.87 | 01-FEB-00:10 | 0.64 |
March | 0.303567E+10 | 0.60 | 1211.87 | 01-MAR-00:03 | 0.65 |
April | 0.299793E+10 | 0.61 | 1211.87 | 01-APR-01:10 | 0.65 |
May | 0.310155E+10 | 0.62 | 1211.87 | 01-MAY-00:07 | 0.64 |
June | 0.299764E+10 | 0.61 | 1211.87 | 01-JUN-00:12 | 0.64 |
July | 0.310089E+10 | 0.61 | 1211.87 | 01-JUL-00:06 | 0.64 |
August | 0.310162E+10 | 0.61 | 1211.87 | 01-AUG-00:04 | 0.64 |
September | 0.299921E+10 | 0.61 | 1211.87 | 01-SEP-00:06 | 0.64 |
October | 0.310113E+10 | 0.62 | 1211.87 | 01-OCT-00:04 | 0.64 |
November | 0.298901E+10 | 0.61 | 1211.87 | 01-NOV-00:07 | 0.65 |
December | 0.305540E+10 | 0.61 | 1211.87 | 01-DEC-00:10 | 0.65 |
Annual Sum or Average | 0.362906E+11 | 0.61 | |||
Minimum of Months | 0.277311E+10 | 0.60 | 1211.87 | 0.64 | |
Maximum of Months | 0.310162E+10 | 0.62 | 1211.87 | 0.65 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.464681E+10 | 0.76 | 2081.78 | 01-JAN-05:18 | 0.91 |
February | 0.419688E+10 | 0.76 | 2081.78 | 01-FEB-06:30 | 0.91 |
March | 0.464803E+10 | 0.76 | 2081.78 | 01-MAR-05:06 | 0.91 |
April | 0.449745E+10 | 0.76 | 2081.78 | 01-APR-04:30 | 0.91 |
May | 0.464820E+10 | 0.76 | 2081.78 | 01-MAY-11:07 | 0.91 |
June | 0.450945E+10 | 0.79 | 2081.78 | 01-JUN-05:10 | 0.91 |
July | 0.469024E+10 | 0.85 | 2081.78 | 01-JUL-08:58 | 0.90 |
August | 0.469623E+10 | 0.85 | 2081.78 | 01-AUG-09:48 | 0.91 |
September | 0.453137E+10 | 0.83 | 2081.78 | 01-SEP-09:32 | 0.91 |
October | 0.469195E+10 | 0.81 | 2081.78 | 01-OCT-11:40 | 0.90 |
November | 0.449713E+10 | 0.76 | 2081.78 | 01-NOV-06:30 | 0.91 |
December | 0.464716E+10 | 0.76 | 2081.78 | 01-DEC-05:08 | 0.91 |
Annual Sum or Average | 0.549009E+11 | 0.79 | |||
Minimum of Months | 0.419688E+10 | 0.76 | 2081.78 | 0.90 | |
Maximum of Months | 0.469623E+10 | 0.85 | 2081.78 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.333597E+10 | 0.88 | 1468.40 | 07-JAN-23:50 | 0.95 |
February | 0.301676E+10 | 0.89 | 1468.40 | 03-FEB-11:45 | 0.96 |
March | 0.332853E+10 | 0.88 | 1468.40 | 08-MAR-07:27 | 0.95 |
April | 0.325608E+10 | 0.90 | 1468.40 | 03-APR-11:30 | 0.95 |
May | 0.337390E+10 | 0.90 | 1468.40 | 02-MAY-14:57 | 0.94 |
June | 0.331288E+10 | 0.89 | 1468.40 | 03-JUN-12:30 | 0.95 |
July | 0.346388E+10 | 0.89 | 1468.40 | 06-JUL-17:27 | 0.94 |
August | 0.347089E+10 | 0.89 | 1468.40 | 11-AUG-09:05 | 0.94 |
September | 0.333545E+10 | 0.89 | 1468.40 | 01-SEP-15:53 | 0.94 |
October | 0.344896E+10 | 0.89 | 1468.40 | 04-OCT-06:50 | 0.94 |
November | 0.324602E+10 | 0.89 | 1468.40 | 09-NOV-12:35 | 0.94 |
December | 0.334041E+10 | 0.89 | 1468.40 | 16-DEC-10:55 | 0.95 |
Annual Sum or Average | 0.399297E+11 | 0.89 | |||
Minimum of Months | 0.301676E+10 | 0.88 | 1468.40 | 0.94 | |
Maximum of Months | 0.347089E+10 | 0.90 | 1468.40 | 0.96 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 51.59 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 52.48 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 52.45 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:05 | 0.00 | 0.00 | 52.84 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 51.63 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 53.02 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:03 | 0.00 | 0.00 | 53.32 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 52.99 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 53.51 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 51.86 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 52.73 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 52.78 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 51.59 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 53.51 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 41.19 | 41.19 | 4566.07 | 16800.23 | 31-JAN-13:25 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 52.93 | 52.93 | 4570.98 | 16800.87 | 02-FEB-13:25 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 52.84 | 52.84 | 4535.11 | 16717.51 | 01-MAR-14:00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 52.75 | 52.75 | 4433.58 | 16437.12 | 01-APR-13:00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 41.87 | 41.87 | 4334.93 | 16049.15 | 01-MAY-12:30 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 53.36 | 53.36 | 4243.06 | 15638.49 | 01-JUN-12:40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 52.89 | 52.89 | 4170.18 | 15336.20 | 01-JUL-12:40 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 53.27 | 53.27 | 4179.95 | 15291.52 | 31-AUG-12:20 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 53.66 | 53.66 | 4216.10 | 15561.58 | 30-SEP-13:00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 42.42 | 42.42 | 4307.38 | 15959.93 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 53.09 | 53.09 | 4417.34 | 16359.55 | 30-NOV-14:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 52.62 | 52.62 | 4502.42 | 16673.20 | 31-DEC-13:15 |
Annual Sum or Average | 0.00 | 4371.96 | ||||||
Minimum of Months | 0.00 | 0.00 | 41.19 | 41.19 | 4170.18 | 15291.52 | ||
Maximum of Months | 0.00 | 0.00 | 53.66 | 53.66 | 4570.98 | 16800.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.504143E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.428016E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.481822E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.504908E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.497620E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.574683E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.762017E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.803524E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.631487E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.700949E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.482627E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.512879E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.688467E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.428016E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.803524E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.388888E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.316982E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.360946E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.420383E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.428519E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.554014E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.778171E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.809103E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.619953E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.679108E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.373002E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.396001E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.612507E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.316982E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.809103E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.464681E+10 | 0.125035E+10 | 0.348662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.419688E+10 | 0.261234E+09 | 0.241669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.464803E+10 | 0.531860E+09 | 0.381733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.449745E+10 | 0.174176E+10 | 0.772811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.464820E+10 | 0.101793E+10 | 0.531154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.450945E+10 | 0.396584E+10 | 9754774.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.469024E+10 | 0.976914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.469623E+10 | 0.112253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453137E+10 | 0.576412E+10 | 12921822.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.469195E+10 | 0.753806E+10 | 0.148718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.449713E+10 | 0.104233E+10 | 0.127022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.464716E+10 | 0.151634E+10 | 0.302150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.549009E+11 | 0.456243E+11 | 0.154877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.419688E+10 | 0.261234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.469623E+10 | 0.112253E+11 | 0.381733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.333597E+10 | 0.179418E+10 | 0.103907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.301676E+10 | 0.491685E+09 | 0.304462E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.332853E+10 | 0.896071E+09 | 0.736487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.325608E+10 | 0.307401E+10 | 34063657.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.337390E+10 | 0.292377E+10 | 14159089.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.331288E+10 | 0.744948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.346388E+10 | 0.151608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.347089E+10 | 0.163856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.333545E+10 | 0.971228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.344896E+10 | 0.113624E+11 | 587979.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324602E+10 | 0.156221E+10 | 98334520.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334041E+10 | 0.198532E+10 | 0.614153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.399297E+11 | 0.727978E+11 | 0.284132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.301676E+10 | 0.491685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.347089E+10 | 0.163856E+11 | 0.103907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.464681E+10 | 0.00 | 0.00 | 0.00 | 0.394621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.419688E+10 | 0.00 | 0.00 | 0.00 | 83281659.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.464803E+10 | 0.00 | 0.00 | 0.00 | 0.170186E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.449745E+10 | 0.00 | 0.00 | 0.00 | 0.551628E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.464820E+10 | 0.00 | 0.00 | 0.00 | 0.327999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.450945E+10 | 0.00 | 0.00 | 0.00 | 0.123737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.469024E+10 | 0.00 | 0.00 | 0.00 | 0.292994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.469623E+10 | 0.00 | 0.00 | 0.00 | 0.333901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453137E+10 | 0.00 | 0.00 | 0.00 | 0.178350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.469195E+10 | 0.00 | 0.00 | 0.00 | 0.231754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.449713E+10 | 0.00 | 0.00 | 0.00 | 0.329136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.464716E+10 | 0.00 | 0.00 | 0.00 | 0.481633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.549009E+11 | 0.00 | 0.00 | 0.00 | 0.139458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.419688E+10 | 0.00 | 0.00 | 0.00 | 83281659.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.469623E+10 | 0.00 | 0.00 | 0.00 | 0.333901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.333597E+10 | 0.00 | 0.00 | 0.00 | 0.552908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.301676E+10 | 0.00 | 0.00 | 0.00 | 0.153066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.332853E+10 | 0.00 | 0.00 | 0.00 | 0.280924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.325608E+10 | 0.00 | 0.00 | 0.00 | 0.947752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.337390E+10 | 0.00 | 0.00 | 0.00 | 0.911280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.331288E+10 | 0.00 | 0.00 | 0.00 | 0.222726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.346388E+10 | 0.00 | 0.00 | 0.00 | 0.431783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.347089E+10 | 0.00 | 0.00 | 0.00 | 0.462014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.333545E+10 | 0.00 | 0.00 | 0.00 | 0.286408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.344896E+10 | 0.00 | 0.00 | 0.00 | 0.334212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324602E+10 | 0.00 | 0.00 | 0.00 | 0.484003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334041E+10 | 0.00 | 0.00 | 0.00 | 0.619608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.399297E+11 | 0.00 | 0.00 | 0.00 | 0.213210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.301676E+10 | 0.00 | 0.00 | 0.00 | 0.153066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.347089E+10 | 0.00 | 0.00 | 0.00 | 0.462014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.582193E+10 | 316713.83 | 0.00 | 9411224.31 | 0.00 | 0.357107E+10 | 0.328522E+10 | 0.00 | 4.39 |
February | 0.649837E+10 | 0.00 | 0.00 | 4439076.40 | 0.00 | 0.240336E+10 | 0.216632E+10 | 0.00 | 4.01 |
March | 0.697309E+10 | 0.00 | 0.00 | 5602133.20 | 0.00 | 0.367390E+10 | 0.201951E+10 | 0.00 | 4.17 |
April | 0.629794E+10 | 10057998.62 | 0.00 | 13865637.46 | 0.00 | 0.429005E+09 | 0.456868E+10 | 0.00 | 5.21 |
May | 0.619902E+10 | 19129.78 | 0.00 | 13915428.54 | 0.00 | 0.235995E+09 | 0.556966E+10 | 0.00 | 5.32 |
June | 0.394008E+10 | 24267475.01 | 0.00 | 22723366.21 | 0.00 | 0.00 | 0.634752E+10 | 0.00 | 6.49 |
July | 0.124618E+10 | 0.538360E+09 | 0.00 | 31172696.38 | 0.00 | 0.00 | 0.767291E+10 | 0.00 | 7.06 |
August | 0.104745E+10 | 0.656837E+09 | 0.00 | 31793639.25 | 0.00 | 0.00 | 0.720967E+10 | 0.00 | 7.04 |
September | 0.269948E+10 | 0.252582E+09 | 704931.02 | 27530754.74 | 0.00 | 0.00 | 0.756130E+10 | 42937.90 | 6.69 |
October | 0.294275E+10 | 0.478593E+09 | 0.00 | 25657643.43 | 0.00 | 63128908.14 | 0.733443E+10 | 0.00 | 6.68 |
November | 0.704711E+10 | 2786682.02 | 0.00 | 10715836.18 | 0.00 | 0.790802E+09 | 0.387503E+10 | 0.00 | 4.52 |
December | 0.630764E+10 | 20036.02 | 0.00 | 11407077.15 | 0.00 | 0.289121E+10 | 0.338707E+10 | 0.00 | 4.76 |
Annual Sum or Average | 0.570210E+11 | 0.196384E+10 | 704931.02 | 0.208235E+09 | 0.00 | 0.140585E+11 | 0.609973E+11 | 42937.90 | 5.54 |
Minimum of Months | 0.104745E+10 | 0.00 | 0.00 | 4439076.40 | 0.00 | 0.00 | 0.201951E+10 | 0.00 | 4.01 |
Maximum of Months | 0.704711E+10 | 0.656837E+09 | 704931.02 | 31793639.25 | 0.00 | 0.367390E+10 | 0.767291E+10 | 42937.90 | 7.06 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.218362E+11 | 0.00 | 0.00 | 31146640.85 | 0.00 | 0.00 | 0.158852E+11 | 0.00 | 10.16 |
February | 0.193611E+11 | 0.00 | 0.00 | 21027008.48 | 0.00 | 0.00 | 0.149466E+11 | 0.00 | 10.14 |
March | 0.239790E+11 | 0.00 | 0.00 | 23255995.95 | 0.00 | 0.00 | 0.140290E+11 | 0.00 | 10.11 |
April | 0.136515E+11 | 0.00 | 0.00 | 53387225.61 | 0.00 | 0.00 | 0.205721E+11 | 0.00 | 10.49 |
May | 0.121725E+11 | 0.00 | 0.00 | 60046423.32 | 0.00 | 0.00 | 0.237524E+11 | 0.00 | 10.58 |
June | 0.437838E+10 | 0.00 | 0.00 | 85611463.03 | 0.00 | 0.00 | 0.257417E+11 | 0.00 | 11.00 |
July | 0.157754E+10 | 0.298939E+09 | 0.00 | 0.106059E+09 | 0.00 | 0.00 | 0.226096E+11 | 0.00 | 11.34 |
August | 0.885049E+09 | 0.370047E+09 | 0.00 | 0.107189E+09 | 0.00 | 0.00 | 0.219352E+11 | 0.00 | 11.39 |
September | 0.280537E+10 | 0.197718E+09 | 0.00 | 90778263.45 | 0.00 | 0.00 | 0.253193E+11 | 0.00 | 11.13 |
October | 0.418697E+10 | 0.255257E+09 | 0.00 | 87599304.07 | 0.00 | 0.00 | 0.239011E+11 | 0.00 | 11.11 |
November | 0.144622E+11 | 0.00 | 0.00 | 39883933.89 | 0.00 | 0.00 | 0.215960E+11 | 0.00 | 10.28 |
December | 0.199050E+11 | 0.00 | 0.00 | 33863810.62 | 0.00 | 0.00 | 0.173938E+11 | 0.00 | 10.22 |
Annual Sum or Average | 0.139201E+12 | 0.112196E+10 | 0.00 | 0.739848E+09 | 0.00 | 0.00 | 0.247682E+12 | 0.00 | 10.67 |
Minimum of Months | 0.885049E+09 | 0.00 | 0.00 | 21027008.48 | 0.00 | 0.00 | 0.140290E+11 | 0.00 | 10.11 |
Maximum of Months | 0.239790E+11 | 0.370047E+09 | 0.00 | 0.107189E+09 | 0.00 | 0.00 | 0.257417E+11 | 0.00 | 11.39 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:23
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.317105E+11 | 0.117045E+11 | 0.745795E+11 | 0.159018E+10 | 0.295755E+11 |
February | 0.385056E+11 | 0.109972E+11 | 0.678617E+11 | 0.886899E+09 | 0.236289E+11 |
March | 0.536395E+11 | 0.129431E+11 | 0.755516E+11 | 0.112236E+10 | 0.284587E+11 |
April | 0.728220E+11 | 0.105386E+11 | 0.659497E+11 | 0.297148E+10 | 0.356949E+11 |
May | 0.765687E+11 | 0.109324E+11 | 0.684251E+11 | 0.364297E+10 | 0.350414E+11 |
June | 0.766907E+11 | 0.887001E+10 | 0.556389E+11 | 0.423930E+10 | 0.440012E+11 |
July | 0.831942E+11 | 0.644008E+10 | 0.442473E+11 | 0.426663E+10 | 0.636575E+11 |
August | 0.766207E+11 | 0.596484E+10 | 0.416618E+11 | 0.379748E+10 | 0.667574E+11 |
September | 0.589625E+11 | 0.751521E+10 | 0.514592E+11 | 0.443891E+10 | 0.494296E+11 |
October | 0.415983E+11 | 0.663632E+10 | 0.517204E+11 | 0.471579E+10 | 0.531435E+11 |
November | 0.348990E+11 | 0.105418E+11 | 0.706968E+11 | 0.198420E+10 | 0.283010E+11 |
December | 0.289413E+11 | 0.111567E+11 | 0.736659E+11 | 0.214505E+10 | 0.296831E+11 |
Annual Sum or Average | 0.674153E+12 | 0.114241E+12 | 0.741458E+12 | 0.358012E+11 | 0.487373E+12 |
Minimum of Months | 0.289413E+11 | 0.596484E+10 | 0.416618E+11 | 0.886899E+09 | 0.236289E+11 |
Maximum of Months | 0.831942E+11 | 0.129431E+11 | 0.755516E+11 | 0.471579E+10 | 0.667574E+11 |