Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 08:27:05
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1370.50 | 5898.62 | 5898.62 |
Net Site Energy | 1370.50 | 5898.62 | 5898.62 |
Total Source Energy | 2356.86 | 10143.90 | 10143.90 |
Net Source Energy | 2356.86 | 10143.90 | 10143.90 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 258.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 33.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 21.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 252.09 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 57.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 216.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 37.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 418.26 | 952.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 258.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 33.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 21.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 57.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 216.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 11.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 17.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 258.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 33.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 21.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 15.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 252.09 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 57.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 216.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 37.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 161.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 393.74 | 2044.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1244.66 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1800.19 | 4098.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 161.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 393.74 | 2044.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1244.66 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1800.19 | 4098.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 418.262 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 418.262 | 100.00 |
Total On-Site and Utility Electric Sources | 418.262 | 100.00 |
Total Electricity End Uses | 418.262 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.50 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3536.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 4.6627 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.9536 | 18.52 | 1067.3199 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 7.3082 | 2.48 | 592.0534 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 7.3082 | 2.48 | 592.0534 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 4.6627 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.9536 | 18.52 | 1067.3199 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 7.3082 | 1.24 | 592.0534 | |||||||
Conditioned Total | 232.34 | 7.3082 | 1.24 | 592.0534 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 7.3082 | 2.48 | 592.0534 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-16:10 | 21-DEC-20:10 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 86946.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13616.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1008.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 12287.48 | 18386.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3221.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 12213.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1145.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31280.05 | 117546.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 86946.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 13616.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1008.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 11696.68 | 18386.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 3221.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 12213.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 362.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 588.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 279.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 107.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 69.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 49.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 798.38 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 182.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 235.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 117.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1324.64 | 1032.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1204.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 461.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 298.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 213.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3436.21 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 785.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1012.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 505.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5701.21 | 4442.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1204.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 461.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 298.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 213.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3436.21 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 785.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1012.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 505.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5701.21 | 4442.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 2.04 |
KITCHEN DIRECT AIR | 1.35 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.04 | 2.04 | 2.04 | 2.04 | 2.04 | 2.04 | 1.00 | 1.00 | 2.04 |
PSZ-AC_2:2 | 1.35 | 1.35 | 1.35 | 1.35 | 1.35 | 1.35 | 1.00 | 1.00 | 1.35 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.04 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.35 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 2.04 | 2181.35 |
PSZ-AC_2:2_ADDAQ FAN | 1.35 | 1498.07 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.04 | 2.04 | 2.04 | 1.35 | 33745.32 | 53764.72 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.35 | 1.35 | 1.35 | 0.893030 | 27605.85 | 69534.50 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.04 | 1.02 | 1.36 | 33745.32 | 16872.66 | 0.800660 | 0.800660 |
PSZ-AC_2:2 COOLING COIL | 1.35 | 0.676538 | 0.902053 | 27605.85 | 13802.92 | 0.768300 | 0.768300 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 53764.72 |
PSZ-AC_2:2 HEATING COIL | 69534.50 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 4.663 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 121.450 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.954 | 275.967 | 791.353 | 0.000 | 0.000 | 0.000 | 1077.273 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 541.679 | 4.663 | 6.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 541.679 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1156.323 | 9.954 | 184.325 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1156.323 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 277.500 | 2.389 | 44.235 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 313.300 | 2.697 | 49.942 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.4391 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2452 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2452 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.043 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.002 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.002 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.38584905E-12 | 0.75146531E-15 | -0.12966877E-12 | 0.12247089E-15 |
34 | 6 | 0.32626755E-07 | 0.12794687E-09 | 0.74410738E-08 | -0.15657130E-12 |
35 | 5 | -0.20999199E-03 | 0.10694986E-05 | -0.10771460E-03 | 0.73422529E-08 |
36 | 4 | 0.31512205 | 0.50965885E-03 | 0.10796022 | -0.36842960E-04 |
37 | 3 | -7.7206601 | 0.15495837E-01 | -2.4737779 | 0.31237450E-01 |
38 | 2 | 42.368774 | 0.54174396E-01 | 15.816616 | -0.35002435 |
39 | 1 | -81.692611 | 0.24088120E-01 | -29.635684 | 1.1030598 |
40 | 0 | 46.824332 | 0.47759164E-03 | 16.279740 | |
41 | 7 | -0.17135090E-08 | -0.36864923E-15 | 0.71259317E-14 | -0.97083918E-16 |
42 | 6 | 0.68579659E-05 | 0.47011368E-08 | 0.31862738E-02 | -0.26729135E-04 |
43 | 5 | -0.49396463E-03 | 0.27861516E-05 | -0.22352018 | 0.19543461E-02 |
44 | 4 | 0.11367371E-01 | 0.12683264E-03 | 4.8261412 | -0.45232255E-01 |
45 | 3 | -0.99836882E-01 | 0.10087729E-02 | -38.002184 | 0.39844117 |
46 | 2 | 0.35452054 | 0.16782362E-02 | 116.44652 | -1.4174386 |
47 | 1 | -0.51170991 | 0.51154075E-03 | -143.88527 | 2.0486777 |
48 | 0 | 0.24948649 | 0.12321491E-04 | 60.838472 | |
49 | 7 | -0.17135090E-08 | -0.36864923E-15 | 0.71259317E-14 | -0.97083918E-16 |
50 | 6 | 0.68579659E-05 | 0.47011368E-08 | 0.31862738E-02 | -0.26729135E-04 |
51 | 5 | -0.49396463E-03 | 0.27861516E-05 | -0.22352018 | 0.19543461E-02 |
52 | 4 | 0.11367371E-01 | 0.12683264E-03 | 4.8261412 | -0.45232255E-01 |
53 | 3 | -0.99836882E-01 | 0.10087729E-02 | -38.002184 | 0.39844117 |
54 | 2 | 0.35452054 | 0.16782362E-02 | 116.44652 | -1.4174386 |
55 | 1 | -0.51170991 | 0.51154075E-03 | -143.88527 | 2.0486777 |
56 | 0 | 0.24948649 | 0.12321491E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.362_SHGC_SOUTH_0.379 | 38 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.380 | ||
2 | NONRESWINDOW_U_0.362_SHGC_NORTH_0.379 | 39 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.380 | ||
3 | NONRESWINDOW_U_0.362_SHGC_EAST_0.379 | 40 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.380 | ||
4 | NONRESWINDOW_U_0.362_SHGC_WEST_0.379 | 41 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.380 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.63679E-002 | 0.29270 | 0.50147 | 0.50147 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.63679E-002 | 0.29270 | 0.50147 | 0.50147 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.63679E-002 | 0.29270 | 0.50147 | 0.50147 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.63679E-002 | 0.29270 | 0.50147 | 0.50147 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.053 | 0.3093 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.584 | 5.025E-003 | 6.281E-003 | 5.934 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.4255E-003 |
2 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.8245E-002 |
3 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.1738E-003 |
4 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.5826E-002 |
5 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.0310E-003 |
6 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.9601E-002 |
7 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.6373E-003 |
8 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.6408E-002 |
9 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.8827E-002 |
10 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.9356E-002 |
11 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 9.1374E-002 |
12 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 9.2048E-002 |
13 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 4.8831E-002 |
14 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.8972E-002 |
15 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.7751E-002 |
16 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.7751E-002 |
17 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.8563E-002 |
18 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.4648E-003 |
19 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6216E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.2237E-003 |
21 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.0013E-002 |
22 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.0664E-003 |
23 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6410E-002 |
24 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.6373E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 18733.53735 | 22480.24482 | 1.69880 | 2.03855 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 6059.86520 | 7271.83824 | 0.31767 | 0.41606 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -17.90000 | 9.55238E-004 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 14916.52122 | 17899.82547 | 1.12756 | 1.35308 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32.56800 | 5.47322E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 636.45933 | 763.75120 | 3.02464E-002 | 1.14133 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -17.90000 | 9.55238E-004 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 26286.16 | 2.03855 | 2.03855 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 23660.53 | 0.41606 | 0.41606 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 24915.22 | 1.35308 | 1.35308 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 64906.04 | 1.14133 | 1.14133 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.03855 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.35308 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.03855 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.03855 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.03855 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.03855 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.03855 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.03855 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.35308 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35308 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.35308 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.35308 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.35308 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.35308 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.03855 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.35308 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.03855 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.03855 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2181.35000 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.03855 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.03855 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.03855 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.34545 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.03855 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.01928 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.35903 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33745.32000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16872.66000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33745.32000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 53764.72338 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 53764.72338 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.35308 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.35308 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1498.06992 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.35308 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.35308 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.35308 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.89303 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.35308 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67654 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.90205 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27605.85000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13802.92500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76830 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76830 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27605.85000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 69534.50014 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 69534.50014 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 32253.9 | 11.01 | 10.96 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 26629.0 | 11.47 | 11.41 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_EAST_0.379 | N/A | 2.057 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_SOUTH_0.379 | N/A | 2.057 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_WEST_0.379 | N/A | 2.057 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.245 | 0.231 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.245 | 0.231 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 8.1952226235E-002 | 0.3418461415 | Pass | Pass | 0.2794666531 | 0.9726489657 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1397873788 | 0.5912995911 | Pass | Pass | 4.7028849582E-002 | 0.1792803680 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4423642114 | 0.5243146432 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 560.15 | 109.73 | 891.92 | 12.69 | 450.56 | 2025.05 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.236 | 0.245 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.236 | 0.245 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.362_SHGC_EAST_0.379 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.057 | 0.380 | 0.418 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.362_SHGC_SOUTH_0.379 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.057 | 0.380 | 0.418 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.362_SHGC_WEST_0.379 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.057 | 0.380 | 0.418 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.057 | 0.380 | 0.418 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.057 | 0.380 | 0.418 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 4.6627 | 116.17 | 541.68 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 43.64 | 0.0000 | Y | 4.44 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.9536 | 116.17 | 1156.32 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 80.60 | 0.0000 | Y | 17.50 |
Interior Lighting Total | 7.3082 | 232.34 | 1698.00 | 21.93 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 541.68 | 205.84 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 541.68 | 205.84 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 218.22 | AstronomicalClock | - | 49.26 | 49.26 | 2.02 | |
EXTERIOR_LIGHTS_B | 1154.09 | AstronomicalClock | - | 83.67 | 62.97 | 13.64 | |
Exterior Lighting Total | 1372.31 | 15.66 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33745.32 | 27018.53 | 6726.79 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27605.85 | 21209.57 | 6396.28 | 0.77 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 32253.9 | 11.01 | 10.96 | ||||
PSZ-AC_2:2 COOLING COIL | 26629.0 | 11.47 | 11.41 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 53764.72 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 69534.50 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 2.04 | 2181.35 | 1070.05 | 1.00 | 1.31 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.35 | 1498.07 | 1107.16 | 1.00 | 1.34 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 18733.54 | 22480.24 | 193.51 | 1.699 | 2.039 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.89 | 0.00757 | 33.90 | 0.00548 | 0.416 | 0.00 |
KITCHEN | 14916.52 | 17899.83 | 154.08 | 1.128 | 1.353 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.00884 | 32.57 | 0.00547 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 6059.87 | 7271.84 | 62.60 | 0.318 | 0.416 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 21.11 | 21.11 | 0.00780 | -17.90 | 0.00096 | 0.416 | 0.00 |
KITCHEN | 636.46 | 763.75 | 6.57 | 0.030 | 1.141 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 18.89 | 18.89 | 0.00461 | -17.90 | 0.00096 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.04 | 2.04 | 0.42 | 0.42 | 2.0386 | 2.0386 | 2.0386 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.35 | 1.35 | 1.14 | 1.14 | 1.3531 | 1.3531 | 1.3531 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 33745.320 | 27018.528 | 2.038550 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 16872.66 | 16576.13 | 1.359033 | 25.93 | 13.79 | 0.00714458 | 11.72 | 8.31 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | 30.6141 | 23.89 | 0.00757264 | 33.3673 | 18733.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 53764.723 | 53764.723 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 53764.72 | 53764.72 | 2.038555 | 13.15 | 8.23 | 0.00633405 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 20.4094 | 19.48 | 0.00771334 | 44.4832 | 3463.57 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 27605.850 | 21209.575 | 1.353080 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 13802.92 | 13802.92 | 0.902053 | 31.55 | 14.73 | 0.00600037 | 11.69 | 7.26 | 0.00600037 | 32.57 | 0.00547322 | 14.64 | 126.5262 | 26.10 | 0.00884184 | 34.0797 | 14916.52 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 69534.500 | 69534.500 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 69534.50 | 69534.50 | 1.353076 | -12.32 | -12.37 | 0.00157843 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 84.3510 | 18.71 | 0.00493754 | 30.0176 | 272.25 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33745.320 | 27018.528 | 2.038550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1214 | 1004.8586 | 0.9774 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.038555 | 1.99256014 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 16872.66 | 16576.13 | 1.0000 | 1.32837030 | 1.359033 | 25.93 | 13.79 | 0.00714458 | 44266.4 | 11.72 | 8.31 | 0.00700000 | 29440.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16872.66 | 33.90 | 0.00547527 | 15.07 | 0.41605618 | 30.6141 | 23.88 | 0.00757264 | 23.89 | 0.00757264 | 33.3673 | 18733.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 53764.723 | 53764.723 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.038555 | 1.99256014 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 53764.72 | 53764.72 | 1.0000 | 1.99256014 | 2.038555 | 13.15 | 8.23 | 0.00633405 | 29207.3 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 53764.72 | -17.90 | 0.00095524 | -17.90 | 0.41605618 | 20.4094 | 21.11 | 0.00771334 | 19.48 | 0.00771334 | 44.4832 | 3463.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27605.850 | 21209.575 | 1.353080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1015.9944 | 1004.8586 | 0.9774 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.353076 | 1.32254738 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 13802.92 | 13802.92 | 1.0000 | 0.88170086 | 0.902053 | 31.55 | 14.73 | 0.00600037 | 47058.9 | 11.69 | 7.26 | 0.00600037 | 26878.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13802.92 | 32.57 | 0.00547322 | 14.64 | 1.14133354 | 126.5262 | 26.05 | 0.00884184 | 26.10 | 0.00884184 | 34.0797 | 14916.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 69534.500 | 69534.500 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.353076 | 1.32254738 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 69534.50 | 69534.50 | 1.0000 | 1.32254738 | 1.353076 | -12.32 | -12.37 | 0.00157843 | -8470.2 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 69534.50 | -17.90 | 0.00095524 | -17.90 | 1.14133354 | 84.3510 | 17.74 | 0.00493754 | 18.71 | 0.00493754 | 30.0176 | 272.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.04 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.35 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 2730.50 | 4602.50 | 976.83 |
KITCHEN | 4487.17 | 5975.83 | 3476.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4545.83 | 6683.50 | 3536.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 72.50 | 36.83 | 0.50 | 0.17 |
KITCHEN | 0.00 | 119.50 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 72.50 | 151.67 | 0.50 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 5.209 | 2.742 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 9.475 | 0.030 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.105 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 8.810 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 13496038.31 | 0.00 | 13496038.31 | 6981777.24 | 20477815.55 | 13120747.55 | 1433.23 | 5830.54 | 1496.23 | 392.86 |
KITCHEN | 24633396.33 | 0.00 | 24633396.33 | 134202.88 | 24767599.21 | 35993094.65 | 8663.32 | 93.80 | 2.88 | 467.55 |
Total Facility | 38129434.64 | 0.00 | 38129434.64 | 7115980.12 | 45245414.76 | 49113842.20 | 8664.99 | 5830.64 | 1497.83 | 659.46 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.5082 | 0.0000 | 0.5082 | 0.2676 | 0.7758 | 0.4161 | 0.00 | 5720.20 | 1466.80 |
KITCHEN | 0.9236 | 0.0000 | 0.9236 | 0.0029 | 0.9265 | 1.1413 | 7095.64 | 91.25 | 0.11 |
Total Facility | 1.4318 | 0.0000 | 1.4318 | 0.2705 | 1.7023 | 1.5574 | 7095.64 | 5720.20 | 1466.80 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12894366.58 | 0.00 | 12894366.58 | 13120747.55 | 7278.20 | 11.79 | 1470.01 | 392.79 |
PSZ-AC_2:2 | 23534188.22 | 0.00 | 23534188.22 | 35993094.65 | 8757.23 | 0.10 | 2.67 | 467.55 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.4856 | 0.0000 | 0.4856 | 0.4161 | 5733.63 | 10.92 | 1442.46 |
PSZ-AC_2:2 | 0.8824 | 0.0000 | 0.8824 | 1.1413 | 7186.93 | 0.00 | 0.07 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1127.46 | 626.57 | 5825.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 136.20 | 1021.96 | 6496.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.9647 | 0.6379 | 0.3976 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.8684 | 0.9032 | 0.8803 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 386 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 418.26 | 3008.03 | 24-DEC-01:20 | 31280.05 | 26-JUN-16:10 |
Electricity:Building | 281.97 | 1673.38 | 01-JAN-01:20 | 17939.26 | 02-JAN-11:10 |
Electricity:Zone:DINING | 74.77 | 295.02 | 01-JAN-01:20 | 4037.01 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 274.03 | 1537.10 | 01-JAN-01:20 | 14645.21 | 02-JAN-11:10 |
InteriorLights:Electricity | 21.93 | 50.02 | 01-JAN-01:20 | 1346.16 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:DINING | 4.44 | 23.72 | 31-MAY-05:00 | 444.80 | 02-JAN-16:50 |
InteriorLights:Electricity:SpaceType:GENERAL | 21.93 | 50.02 | 01-JAN-01:20 | 1346.16 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 21.93 | 50.02 | 01-JAN-01:20 | 1346.16 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 4.44 | 23.72 | 31-MAY-05:00 | 444.80 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 21.93 | 50.02 | 01-JAN-01:20 | 1346.16 | 02-JAN-16:50 |
Electricity:Zone:KITCHEN | 207.20 | 1378.36 | 01-JAN-01:20 | 13902.25 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.50 | 25.01 | 01-JAN-01:20 | 901.37 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.50 | 25.01 | 01-JAN-01:20 | 901.37 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 252.09 | 1487.08 | 01-JAN-01:10 | 13637.09 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 252.09 | 1487.08 | 01-JAN-01:10 | 13637.09 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 181.76 | 1217.07 | 01-JAN-01:10 | 9706.84 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 37.10 | 594.45 | 21-DEC-23:30 | 3927.96 | 28-JUL-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 29.15 | 508.67 | 23-DEC-23:20 | 1624.37 | 04-AUG-03:40 |
LowTempRefrigeration:Refrigeration:Electricity | 11.20 | 0.00 | 01-JAN-11:10 | 987.28 | 04-AUG-03:40 |
MedTempRefrigeration:Refrigeration:Electricity | 17.96 | 475.34 | 06-MAR-01:10 | 637.09 | 03-JUN-12:10 |
ElectricityPurchased:Facility | 418.26 | 3008.03 | 24-DEC-01:20 | 31280.05 | 26-JUN-16:10 |
ElectricityPurchased:Plant | 418.26 | 3008.03 | 24-DEC-01:20 | 31280.05 | 26-JUN-16:10 |
Cogeneration:ElectricityPurchased | 418.26 | 3008.03 | 24-DEC-01:20 | 31280.05 | 26-JUN-16:10 |
General:Cogeneration:ElectricityPurchased | 418.26 | 3008.03 | 24-DEC-01:20 | 31280.05 | 26-JUN-16:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 418.26 | 3008.03 | 24-DEC-01:20 | 31280.05 | 26-JUN-16:10 |
ElectricityNet:Plant | 418.26 | 3008.03 | 24-DEC-01:20 | 31280.05 | 26-JUN-16:10 |
Cogeneration:ElectricityNet | 418.26 | 3008.03 | 24-DEC-01:20 | 31280.05 | 26-JUN-16:10 |
General:Cogeneration:ElectricityNet | 418.26 | 3008.03 | 24-DEC-01:20 | 31280.05 | 26-JUN-16:10 |
Electricity:HVAC | 91.48 | 0.00 | 01-JAN-01:10 | 17195.18 | 26-JUN-17:10 |
Fans:Electricity | 57.62 | 0.00 | 01-JAN-01:10 | 3376.10 | 26-JUN-17:10 |
General:Fans:Electricity | 57.62 | 0.00 | 01-JAN-01:10 | 3376.10 | 26-JUN-17:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 33.87 | 0.00 | 01-JAN-00:10 | 13819.09 | 26-JUN-17:10 |
General:Cooling:Electricity | 33.87 | 0.00 | 01-JAN-00:10 | 13819.09 | 26-JUN-17:10 |
ExteriorLights:Electricity | 15.66 | 0.00 | 01-JAN-07:30 | 1372.31 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 15.66 | 0.00 | 01-JAN-07:30 | 1372.31 | 01-JAN-06:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-10:20 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-10:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 952.24 | 2558.65 | 20-APR-02:10 | 117546.60 | 21-DEC-20:10 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 258.14 | 0.00 | 01-JAN-01:10 | 89079.47 | 23-DEC-07:10 |
Heating:NaturalGas | 258.14 | 0.00 | 01-JAN-01:10 | 89079.47 | 23-DEC-07:10 |
General:Heating:NaturalGas | 258.14 | 0.00 | 01-JAN-01:10 | 89079.47 | 23-DEC-07:10 |
NaturalGas:Plant | 216.94 | 720.00 | 01-JAN-09:30 | 27774.97 | 11-FEB-13:40 |
WaterSystems:NaturalGas | 216.94 | 720.00 | 01-JAN-09:30 | 27774.97 | 11-FEB-13:40 |
Water Heater:WaterSystems:NaturalGas | 216.94 | 720.00 | 01-JAN-09:30 | 27774.97 | 11-FEB-13:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 965.18 | 2415.83 | 24-DEC-01:10 | 107920.82 | 21-DEC-20:10 |
EnergyTransfer:Building | 412.82 | 1207.91 | 24-DEC-01:10 | 32089.11 | 16-AUG-11:10 |
EnergyTransfer:Zone:KITCHEN | 308.97 | 1207.91 | 24-DEC-01:10 | 19625.59 | 09-MAY-04:10 |
Refrigeration:EnergyTransfer | 136.07 | 2415.83 | 24-DEC-01:10 | 7834.84 | 16-JUN-03:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.03 | 1207.91 | 24-DEC-01:10 | 3917.42 | 16-JUN-03:30 |
General:Refrigeration:EnergyTransfer | 68.03 | 1207.91 | 24-DEC-01:10 | 3917.42 | 16-JUN-03:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.03 | 1207.91 | 24-DEC-01:10 | 3917.42 | 16-JUN-03:30 |
EnergyTransfer:Plant | 216.17 | 1207.91 | 24-DEC-01:10 | 22563.13 | 18-FEB-14:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.99 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 55.04 | 1059.55 | 06-MAR-01:10 | 2238.70 | 03-JUN-12:10 |
EnergyTransfer:Zone:DINING | 103.85 | 0.00 | 01-JAN-01:10 | 25078.93 | 22-DEC-03:20 |
Heating:EnergyTransfer | 24.26 | 0.00 | 01-JAN-00:10 | 18924.69 | 21-DEC-18:10 |
Heating:EnergyTransfer:Zone:DINING | 24.25 | 0.00 | 01-JAN-00:10 | 18924.69 | 21-DEC-18:10 |
General:Heating:EnergyTransfer | 24.26 | 0.00 | 01-JAN-00:10 | 18924.69 | 21-DEC-18:10 |
General:Heating:EnergyTransfer:Zone:DINING | 24.25 | 0.00 | 01-JAN-00:10 | 18924.69 | 21-DEC-18:10 |
Cooling:EnergyTransfer | 320.53 | 0.00 | 01-JAN-01:10 | 28386.29 | 16-AUG-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 79.60 | 0.00 | 01-JAN-01:10 | 15845.57 | 26-JUN-17:20 |
General:Cooling:EnergyTransfer | 320.53 | 0.00 | 01-JAN-01:10 | 28386.29 | 16-AUG-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 79.60 | 0.00 | 01-JAN-01:10 | 15845.57 | 26-JUN-17:20 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 1487.46 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 1487.46 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 240.92 | 0.00 | 01-JAN-01:10 | 16027.85 | 21-SEP-16:00 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 240.92 | 0.00 | 01-JAN-01:10 | 16027.85 | 21-SEP-16:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 148.14 | 0.00 | 01-JAN-00:10 | 20159.86 | 14-FEB-13:40 |
PlantLoopHeatingDemand:Plant | 148.14 | 0.00 | 01-JAN-00:10 | 20159.86 | 14-FEB-13:40 |
WaterSystems:PlantLoopHeatingDemand | 148.14 | 0.00 | 01-JAN-00:10 | 20159.86 | 14-FEB-13:40 |
General:WaterSystems:PlantLoopHeatingDemand | 148.14 | 0.00 | 01-JAN-00:10 | 20159.86 | 14-FEB-13:40 |
EnergyTransfer:HVAC | 336.19 | 0.00 | 01-JAN-01:10 | 71263.58 | 23-DEC-07:10 |
HeatingCoils:EnergyTransfer | 206.52 | 0.00 | 01-JAN-01:10 | 71263.58 | 23-DEC-07:10 |
CoolingCoils:EnergyTransfer | 129.68 | 0.00 | 01-JAN-00:10 | 47950.79 | 26-JUN-17:10 |
WaterSystems:EnergyTransfer | 148.14 | 0.00 | 01-JAN-00:10 | 20159.86 | 14-FEB-13:40 |
WaterUse:WaterSystems:EnergyTransfer | 148.14 | 0.00 | 01-JAN-00:10 | 20159.86 | 14-FEB-13:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 24.245 | -79.604 | 0.000 | 0.000 | 71.067 | 4.437 | 52.748 | 33.033 | 0.000 | 4.975 | 0.000 | 0.000 | -13.787 | 0.000 | -81.533 | -15.581 |
KITCHEN | 0.000 | 0.000 | 0.012 | -240.914 | 0.000 | 0.000 | 4.979 | 17.495 | 187.472 | 0.000 | 0.000 | 0.030 | 32.917 | 0.000 | 0.000 | 0.000 | -1.990 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.393 | 10.267 | 0.000 | 0.000 | 0.000 | -13.660 | -0.001 |
Total Facility | 0.000 | 0.000 | 24.257 | -320.518 | 0.000 | 0.000 | 76.045 | 21.932 | 240.220 | 33.033 | 0.000 | 8.397 | 43.184 | 0.000 | -13.787 | 0.000 | -97.183 | -15.582 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 17-AUG-02:61 | 0.00 | 0.00 | 0.00 | -28846.33 | 0.00 | 0.00 | 0.00 | 25.01 | 202.51 | 0.00 | 0.00 | 0.00 | 29269.12 | 0.00 | -570.49 | 0.00 | -79.81 | 0.00 |
KITCHEN | 28-SEP-02:61 | 0.00 | 0.00 | 0.00 | -43578.80 | 0.00 | 0.00 | 0.00 | 25.01 | 1240.35 | 0.00 | 0.00 | 0.00 | 42490.32 | 0.00 | -0.00 | 0.00 | -176.89 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-AUG-02:61 | 0.00 | 0.00 | 0.00 | -68582.21 | 0.00 | 0.00 | 0.00 | 50.02 | 1442.86 | 0.00 | 0.00 | 29.74 | 67816.45 | 0.00 | -570.49 | 0.00 | -186.37 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 21-DEC-04:31 | 0.00 | 0.00 | 39633.30 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 506.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2099.89 | 0.00 | -346.21 | -37718.48 |
KITCHEN | 23-DEC-05:02 | 0.00 | 0.00 | 11883.87 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 4488.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -154.18 | -16242.82 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-DEC-04:31 | 0.00 | 0.00 | 39633.30 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 2720.95 | 0.00 | 0.00 | 121.64 | 0.00 | 0.00 | -2099.89 | 0.00 | -710.71 | -39715.31 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0386 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.0386 | 0.2041 | 1.0000 | Not calculated | 0.4161 | 0.2041 | ||
PSZ-AC_2:2 | 1.3531 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.3531 | 0.1118 | 1.0000 | Not calculated | 0.1513 | 0.1118 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0386 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.0386 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2041 | ||
PSZ-AC_2:2 | 1.3531 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.3531 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1118 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0386 | 2.0386 | 2.0386 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3531 | 1.3531 | 1.3531 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0386 | 2.0386 | 2.0386 | 2.0386 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.3531 | 1.3531 | 1.3531 | 1.3531 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0386 | 2.0386 | 2.0386 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3531 | 1.3531 | 1.3531 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0386 | 2.0386 | 2.0386 | 2.0386 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.3531 | 1.3531 | 1.3531 | 1.3531 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.50 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 0.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 258.14 | 89079.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 33.87 | 13819.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 21.93 | 1346.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 15.66 | 1372.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 57.62 | 3376.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 216.94 | 27774.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 11.20 | 987.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 17.96 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 289.19 | 418.26 |
Natural Gas | 477.16 | 952.24 |
Additional | 0.00 | 0.00 |
Total | 766.35 | 1370.50 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 94.40 |
Space Heating | 0.00 |
Space Cooling | 145.75 |
Fans (All) | 247.98 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1085.00 |
Miscellaneous (All) | 1800.19 |
Subtotal | 1800.19 |
Natural Gas [MJ/m2] | |
Space Heating | 1111.05 |
Service Water Heating | 933.70 |
Miscellaneous (All) | 4098.42 |
Subtotal | 4098.42 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.60 |
Space Heating | 18.84 |
Space Cooling | 2.47 |
Fans (All) | 4.20 |
Service Water Heating | 15.83 |
Receptacle Equipment | 53.21 |
Miscellaneous | 3.85 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8411.17 | 348.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 6765.00 | 599.50 | 568.67 | 811.33 | 15.50 |
Min | 6765.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 599.50 | 568.67 | 811.33 | 15.50 |
Average | 7978.72 | 316.11 | 189.56 | 270.44 | 5.17 |
Sum | 23936.17 | 948.33 | 568.67 | 811.33 | 15.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16258.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 90327.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 270983.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8713.50 | 46.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8130.83 | 629.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 7005.17 | 834.17 | 315.50 | 281.17 | 324.00 |
Min | 7005.17 | 46.50 | 0.00 | 0.00 | 0.00 |
Max | 8713.50 | 834.17 | 315.50 | 281.17 | 324.00 |
Average | 7949.83 | 503.28 | 105.17 | 93.72 | 108.00 |
Sum | 23849.50 | 1509.83 | 315.50 | 281.17 | 324.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 253796.50 | 928.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15253.00 | 1005.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 253796.50 | 1005.00 | 0.00 | 0.00 | 0.00 |
Average | 89683.17 | 644.50 | 0.00 | 0.00 | 0.00 |
Sum | 269049.50 | 1933.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:05
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234283E+10 | 17426.29 | 14-JAN-04:49 | -17.0 | -17.0 | 0.451893E+10 | 4413.16 | 20-JAN-12:00 | 21.00 | 6.97 |
February | 0.190348E+10 | 22031.24 | 12-FEB-04:48 | -19.8 | -19.8 | 0.406791E+10 | 4200.74 | 27-FEB-12:00 | 14.00 | 4.76 |
March | 0.333467E+10 | 10201.31 | 05-MAR-00:01 | -9.0 | -9.0 | 0.469044E+10 | 4445.73 | 11-MAR-19:10 | 13.83 | 4.16 |
April | 0.311146E+10 | 9127.38 | 16-APR-23:01 | -6.0 | -6.8 | 0.453568E+10 | 4495.21 | 08-APR-18:10 | -6.0 | -6.8 |
May | 0.676386E+10 | 9798.77 | 17-MAY-12:55 | 29.00 | 11.92 | 0.505556E+10 | 4681.01 | 06-MAY-18:19 | 29.00 | 11.92 |
June | 0.127744E+11 | 27027.09 | 15-JUN-02:61 | 15.42 | 7.63 | 0.526664E+10 | 4681.47 | 17-JUN-18:00 | 23.30 | 16.53 |
July | 0.132536E+11 | 26069.72 | 02-JUL-02:61 | 11.83 | 3.99 | 0.539305E+10 | 4681.12 | 22-JUL-18:00 | 27.00 | 15.92 |
August | 0.134848E+11 | 28855.15 | 17-AUG-02:61 | 14.67 | 6.30 | 0.544401E+10 | 4681.15 | 19-AUG-18:00 | 24.00 | 12.71 |
September | 0.114169E+11 | 27445.41 | 19-SEP-02:61 | 13.62 | 7.17 | 0.514605E+10 | 4681.18 | 02-SEP-18:00 | 13.62 | 7.17 |
October | 0.549225E+10 | 10172.63 | 30-OCT-23:01 | -8.8 | -8.8 | 0.477873E+10 | 4680.69 | 07-OCT-18:10 | -8.8 | -8.8 |
November | 0.328300E+10 | 12251.64 | 30-NOV-03:19 | -14.0 | -14.3 | 0.442336E+10 | 4413.14 | 07-NOV-12:50 | -14.0 | -14.3 |
December | 0.244352E+10 | 27084.45 | 22-DEC-03:11 | -22.7 | -22.7 | 0.452209E+10 | 4413.12 | 01-DEC-12:09 | -22.7 | -22.7 |
Annual Sum or Average | 0.796047E+11 | 0.578424E+11 | ||||||||
Minimum of Months | 0.190348E+10 | 9127.38 | -22.7 | -22.7 | 0.406791E+10 | 4200.74 | -22.7 | -22.7 | ||
Maximum of Months | 0.134848E+11 | 28855.15 | 29.00 | 11.92 | 0.544401E+10 | 4681.47 | 29.00 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198817E+11 | 32928.29 | 05-JAN-05:01 | -17.0 | -17.0 | 0.769915E+10 | 5135.93 | 20-JAN-11:00 | 20.00 | 7.55 |
February | 0.175815E+11 | 34513.64 | 12-FEB-05:01 | -19.8 | -19.8 | 0.694925E+10 | 5116.77 | 18-FEB-11:00 | 18.00 | 6.83 |
March | 0.194692E+11 | 28874.77 | 05-MAR-05:01 | -12.0 | -12.0 | 0.772843E+10 | 5135.93 | 14-MAR-10:30 | 21.00 | 7.05 |
April | 0.192430E+11 | 32138.45 | 21-APR-02:61 | 8.83 | 6.25 | 0.748502E+10 | 5135.93 | 27-APR-10:00 | 18.00 | 8.14 |
May | 0.196434E+11 | 41610.87 | 11-MAY-02:61 | 11.50 | 3.69 | 0.781102E+10 | 5135.96 | 24-MAY-10:00 | 21.00 | 12.14 |
June | 0.202029E+11 | 39953.98 | 09-JUN-02:61 | 8.62 | 4.77 | 0.760557E+10 | 5135.97 | 02-JUN-10:39 | 8.62 | 4.77 |
July | 0.209268E+11 | 39929.71 | 02-JUL-02:61 | 11.83 | 3.99 | 0.785541E+10 | 5135.97 | 28-JUL-10:39 | 19.67 | 16.52 |
August | 0.213473E+11 | 39754.52 | 17-AUG-02:61 | 14.67 | 6.30 | 0.785902E+10 | 5135.97 | 28-AUG-10:39 | 20.67 | 15.18 |
September | 0.208061E+11 | 43611.80 | 28-SEP-02:61 | 11.78 | 4.23 | 0.758978E+10 | 5135.95 | 01-SEP-10:09 | 11.78 | 4.23 |
October | 0.214255E+11 | 40228.02 | 01-OCT-02:61 | 9.10 | 3.41 | 0.775277E+10 | 5135.93 | 05-OCT-10:00 | 17.00 | 8.23 |
November | 0.203705E+11 | 33781.15 | 07-NOV-04:21 | 5.00 | -0.5 | 0.746179E+10 | 5135.93 | 09-NOV-11:00 | 20.00 | 9.32 |
December | 0.200255E+11 | 37152.24 | 22-DEC-05:01 | -21.0 | -21.0 | 0.769998E+10 | 5135.93 | 04-DEC-11:00 | -21.0 | -21.0 |
Annual Sum or Average | 0.240923E+12 | 0.914972E+11 | ||||||||
Minimum of Months | 0.175815E+11 | 28874.77 | -21.0 | -21.0 | 0.694925E+10 | 5116.77 | -21.0 | -21.0 | ||
Maximum of Months | 0.214255E+11 | 43611.80 | 14.67 | 6.30 | 0.785902E+10 | 5135.97 | 21.00 | 16.52 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.50 | -1.8 | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 | -1.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 | -5.3 | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 | -1.1 | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 | 2.10 | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.10 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 | 4.75 | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 | 11.26 | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.26 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 22.27 | 10.91 | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.91 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 | 15.43 | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.43 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 | 10.64 | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.64 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 | 8.03 | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.03 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 | -5.7 | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 2.77 | -0.5 | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 | -0.5 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -5.7 | -5.7 | 0.00 | 0.00 | -5.7 | -5.7 | ||
Maximum of Months | 0.00 | 0.00 | 22.27 | 15.43 | 0.00 | 0.00 | 22.27 | 15.43 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.420591E+10 | 32982.38 | 05-JAN-03:21 | -16.0 |
February | 0.451375E+10 | 39222.88 | 12-FEB-04:31 | -19.7 |
March | 0.292753E+10 | 24083.17 | 19-MAR-04:01 | -8.7 |
April | 0.200525E+10 | 21239.31 | 17-APR-04:01 | -8.0 |
May | 89955793.60 | 8336.58 | 12-MAY-05:20 | 2.00 |
June | 2780479.21 | 5514.23 | 14-JUN-03:00 | 22.20 |
July | 3307778.29 | 6844.40 | 17-JUL-02:30 | 21.00 |
August | 1683762.95 | 7538.90 | 01-AUG-02:04 | 19.45 |
September | 55065462.16 | 3974.95 | 29-SEP-02:03 | 15.22 |
October | 0.170267E+10 | 21788.89 | 30-OCT-04:01 | -10.0 |
November | 0.267724E+10 | 25404.77 | 29-NOV-05:01 | -10.0 |
December | 0.605993E+10 | 39627.28 | 21-DEC-04:31 | -18.3 |
Annual Sum or Average | 0.242451E+11 | |||
Minimum of Months | 1683762.95 | 3974.95 | -19.7 | |
Maximum of Months | 0.605993E+10 | 39627.28 | 22.20 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 960630.07 | 5376.36 | 07-JAN-05:03 | -8.8 |
February | 2736670.71 | 7721.51 | 12-FEB-05:02 | -19.8 |
March | 1289164.61 | 7371.77 | 04-MAR-05:03 | -6.9 |
April | 1022905.90 | 5325.67 | 03-APR-04:03 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 465279.71 | 7754.66 | 30-OCT-04:03 | -10.0 |
November | 1228014.20 | 7223.29 | 02-NOV-04:03 | -9.0 |
December | 3987465.50 | 11899.71 | 23-DEC-05:02 | -21.4 |
Annual Sum or Average | 11690130.71 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 3987465.50 | 11899.71 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.450884E+09 | 444.80 | 02-JAN-16:49 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.382429E+09 | 444.80 | 01-FEB-17:19 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.382214E+09 | 444.80 | 01-MAR-17:49 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.333858E+09 | 444.80 | 01-APR-18:19 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.315186E+09 | 444.80 | 01-MAY-18:49 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.292853E+09 | 444.80 | 01-JUN-19:19 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.302808E+09 | 444.80 | 01-JUL-19:30 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.338835E+09 | 444.80 | 01-AUG-18:00 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.346039E+09 | 444.80 | 01-SEP-18:30 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.400592E+09 | 444.80 | 02-OCT-17:40 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.430425E+09 | 444.80 | 01-NOV-16:00 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.461020E+09 | 444.80 | 01-DEC-16:30 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.443714E+10 | 0.703313E+11 | ||||
Minimum of Months | 0.292853E+09 | 444.80 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.461020E+09 | 444.80 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147778E+10 | 901.37 | 02-JAN-10:09 | 0.154373E+11 | 9706.84 | 01-JAN-11:09 |
February | 0.133867E+10 | 901.37 | 01-FEB-10:09 | 0.139433E+11 | 9706.84 | 01-FEB-11:09 |
March | 0.150331E+10 | 901.37 | 01-MAR-10:09 | 0.154374E+11 | 9706.84 | 01-MAR-11:09 |
April | 0.143598E+10 | 901.37 | 01-APR-16:10 | 0.149393E+11 | 9706.84 | 01-APR-10:09 |
May | 0.149055E+10 | 901.37 | 01-MAY-09:09 | 0.154373E+11 | 9706.84 | 01-MAY-10:09 |
June | 0.145287E+10 | 901.37 | 01-JUN-09:09 | 0.149394E+11 | 9706.84 | 01-JUN-10:09 |
July | 0.147384E+10 | 901.37 | 01-JUL-16:10 | 0.154372E+11 | 9706.84 | 01-JUL-10:09 |
August | 0.150331E+10 | 901.37 | 01-AUG-09:09 | 0.154374E+11 | 9706.84 | 01-AUG-10:09 |
September | 0.143634E+10 | 901.37 | 01-SEP-09:09 | 0.149393E+11 | 9706.84 | 01-SEP-10:09 |
October | 0.147760E+10 | 901.37 | 02-OCT-09:09 | 0.154373E+11 | 9706.84 | 01-OCT-10:09 |
November | 0.143091E+10 | 901.37 | 01-NOV-09:09 | 0.149393E+11 | 9706.84 | 01-NOV-10:09 |
December | 0.147402E+10 | 901.37 | 01-DEC-10:09 | 0.154372E+11 | 9706.84 | 01-DEC-11:09 |
Annual Sum or Average | 0.174952E+11 | 0.181762E+12 | ||||
Minimum of Months | 0.133867E+10 | 901.37 | 0.139433E+11 | 9706.84 | ||
Maximum of Months | 0.150331E+10 | 901.37 | 0.154374E+11 | 9706.84 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.450884E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116166E+11 |
February | 0.852256E+10 | 0.382429E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111411E+11 |
March | 0.954557E+10 | 0.382214E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27518.00 | 0.938066E+10 |
April | 0.915225E+10 | 0.333858E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816283E+10 |
May | 0.947560E+10 | 0.315186E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83149247.28 | 0.421035E+10 |
June | 0.922788E+10 | 0.292853E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148027E+10 | 0.105361E+10 |
July | 0.939996E+10 | 0.302808E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153771E+10 | 0.974762E+09 |
August | 0.954557E+10 | 0.338835E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127632E+10 | 0.126952E+10 |
September | 0.915225E+10 | 0.346039E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585598E+09 | 0.234447E+10 |
October | 0.940563E+10 | 0.400592E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11438871.07 | 0.806605E+10 |
November | 0.909363E+10 | 0.430425E+09 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100361E+11 |
December | 0.939996E+10 | 0.461020E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132769E+11 |
Annual Sum or Average | 0.111326E+12 | 0.443714E+10 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497451E+10 | 0.815330E+11 |
Minimum of Months | 0.852256E+10 | 0.292853E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.974762E+09 |
Maximum of Months | 0.954557E+10 | 0.461020E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153771E+10 | 0.132769E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.147778E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141494E+09 |
February | 0.610713E+09 | 0.133867E+10 | 0.101891E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215431E+09 |
March | 0.684021E+09 | 0.150331E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244119E+09 |
April | 0.655836E+09 | 0.143598E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243530E+09 |
May | 0.679007E+09 | 0.149055E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 246233.95 | 0.150130E+09 |
June | 0.661256E+09 | 0.145287E+10 | 0.109170E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 9922824.03 | 77367928.61 |
July | 0.673587E+09 | 0.147384E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 10492908.40 | 77130927.06 |
August | 0.684021E+09 | 0.150331E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 6752229.10 | 76728406.90 |
September | 0.655836E+09 | 0.143634E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 2569789.64 | 0.108421E+09 |
October | 0.673993E+09 | 0.147760E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 9310.01 | 0.179001E+09 |
November | 0.651635E+09 | 0.143091E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169177E+09 |
December | 0.673587E+09 | 0.147402E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307188E+09 |
Annual Sum or Average | 0.797748E+10 | 0.174952E+11 | 0.132823E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 29993295.12 | 0.198972E+10 |
Minimum of Months | 0.610713E+09 | 0.133867E+10 | 0.101891E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76728406.90 |
Maximum of Months | 0.684021E+09 | 0.150331E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 10492908.40 | 0.307188E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385687E+09 | 0.739807E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310662E+09 | 0.895063E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279747E+09 | 0.115306E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192938E+09 | 0.118877E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193816E+09 | 0.150723E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227615E+09 | 0.165384E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206997E+09 | 0.149020E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233217E+09 | 0.152821E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313627E+09 | 0.116131E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330253E+09 | 0.972648E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327937E+09 | 0.795442E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390267E+09 | 0.574450E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339276E+10 | 0.136600E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192938E+09 | 0.574450E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390267E+09 | 0.165384E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 444.80 | 02-JAN-16:49 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 21584.43 | 05-JAN-19:00 |
February | 9454.80 | 04-FEB-19:10 | 444.80 | 01-FEB-17:19 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 20957.27 | 11-FEB-20:00 |
March | 9454.80 | 04-MAR-19:10 | 444.80 | 01-MAR-17:49 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.86 | 14-MAR-13:00 | 17993.52 | 04-MAR-20:00 |
April | 9454.80 | 01-APR-18:10 | 444.80 | 01-APR-18:19 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 12096.64 | 15-APR-18:53 |
May | 9454.80 | 06-MAY-18:10 | 444.80 | 01-MAY-18:49 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2119.26 | 17-MAY-13:00 | 8121.52 | 11-MAY-19:53 |
June | 9454.80 | 03-JUN-18:10 | 444.80 | 01-JUN-19:19 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6263.83 | 26-JUN-17:03 | 4106.06 | 02-JUN-19:55 |
July | 9454.80 | 01-JUL-18:10 | 444.80 | 01-JUL-19:30 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5539.34 | 17-JUL-11:55 | 3836.71 | 05-JUL-19:54 |
August | 9454.80 | 05-AUG-18:10 | 444.80 | 01-AUG-18:00 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5366.59 | 16-AUG-17:03 | 4328.86 | 22-AUG-19:55 |
September | 9454.80 | 02-SEP-18:10 | 444.80 | 01-SEP-18:30 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2982.03 | 08-SEP-12:55 | 10849.92 | 21-SEP-19:00 |
October | 9454.80 | 07-OCT-18:10 | 444.80 | 02-OCT-17:40 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 876.76 | 11-OCT-13:00 | 15348.88 | 30-OCT-18:00 |
November | 9454.80 | 04-NOV-18:10 | 444.80 | 01-NOV-16:00 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 19319.70 | 29-NOV-21:00 |
December | 9454.80 | 02-DEC-19:10 | 444.80 | 01-DEC-16:30 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 23801.53 | 21-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 444.80 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3836.71 | |||||
Maximum of Months | 9454.80 | 444.80 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6263.83 | 23801.53 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 901.37 | 02-JAN-10:09 | 6972.03 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 556.43 | 13-JAN-05:00 |
February | 677.52 | 04-FEB-19:10 | 901.37 | 01-FEB-10:09 | 6972.03 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 530.80 | 24-FEB-05:00 |
March | 677.52 | 04-MAR-19:10 | 901.37 | 01-MAR-10:09 | 6972.03 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1157.37 | 19-MAR-01:55 |
April | 677.52 | 01-APR-18:10 | 901.37 | 01-APR-16:10 | 6972.03 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 765.05 | 10-APR-04:00 |
May | 677.52 | 06-MAY-18:10 | 901.37 | 01-MAY-09:09 | 6972.03 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 10.16 | 17-MAY-13:00 | 508.02 | 03-MAY-03:00 |
June | 677.52 | 03-JUN-18:10 | 901.37 | 01-JUN-09:09 | 6972.03 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 54.85 | 14-JUN-12:00 | 327.61 | 09-JUN-01:50 |
July | 677.52 | 01-JUL-18:10 | 901.37 | 01-JUL-16:10 | 6972.03 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 48.46 | 16-JUL-12:00 | 335.06 | 03-JUL-03:40 |
August | 677.52 | 05-AUG-18:10 | 901.37 | 01-AUG-09:09 | 6972.03 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 45.08 | 02-AUG-15:23 | 340.65 | 16-AUG-01:30 |
September | 677.52 | 02-SEP-18:10 | 901.37 | 01-SEP-09:09 | 6972.03 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 30.33 | 09-SEP-14:52 | 337.07 | 22-SEP-02:00 |
October | 677.52 | 07-OCT-18:10 | 901.37 | 02-OCT-09:09 | 6972.03 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 2.83 | 11-OCT-14:00 | 491.08 | 29-OCT-04:00 |
November | 677.52 | 04-NOV-18:10 | 901.37 | 01-NOV-09:09 | 6972.03 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 796.61 | 01-NOV-04:00 |
December | 677.52 | 02-DEC-19:10 | 901.37 | 01-DEC-10:09 | 6972.03 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 790.05 | 24-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 901.37 | 6972.03 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 327.61 | ||||||
Maximum of Months | 677.52 | 901.37 | 6972.03 | 7998.14 | 0.00 | 0.00 | 0.00 | 54.85 | 1157.37 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 751.42 | 08-JAN-03:53 | 1659.61 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.41 | 07-FEB-07:55 | 1977.21 | 12-FEB-13:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.37 | 23-MAR-06:53 | 2236.34 | 26-MAR-12:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.51 | 07-APR-03:55 | 2463.66 | 24-APR-12:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.79 | 13-MAY-05:23 | 2308.54 | 09-MAY-12:20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.25 | 06-JUN-22:00 | 2181.54 | 22-JUN-12:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.97 | 01-JUL-05:23 | 2249.94 | 03-JUL-12:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.88 | 15-AUG-03:00 | 2159.14 | 24-AUG-13:20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.04 | 28-SEP-06:42 | 1943.08 | 20-SEP-12:30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.18 | 14-OCT-07:12 | 1939.29 | 04-OCT-13:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.33 | 30-NOV-07:53 | 1817.82 | 12-NOV-12:30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 699.59 | 23-DEC-08:41 | 1495.24 | 21-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.97 | 1495.24 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 751.42 | 2463.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17426.29 | 14-JAN-04:49 | 0.00 | 250.09 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.26 |
February | 22031.24 | 12-FEB-04:48 | 0.00 | 250.09 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.78 |
March | 10201.31 | 05-MAR-00:01 | 5252.67 | 988.46 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 |
April | 9127.38 | 16-APR-23:01 | 5252.67 | 741.34 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.42 |
May | 9798.77 | 17-MAY-12:55 | 14707.47 | 213.50 | 6776.30 | 0.00 | 0.00 | 0.00 | 0.00 | 2119.26 | 0.00 |
June | 27027.09 | 15-JUN-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.51 |
July | 26069.72 | 02-JUL-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.21 |
August | 28855.15 | 17-AUG-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.81 |
September | 27445.41 | 19-SEP-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.24 |
October | 10172.63 | 30-OCT-23:01 | 5252.67 | 741.34 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.78 |
November | 12251.64 | 30-NOV-03:19 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.31 |
December | 27084.45 | 22-DEC-03:11 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9127.38 | 0.00 | 213.50 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28855.15 | 14707.47 | 988.46 | 6776.30 | 0.00 | 0.00 | 0.00 | 0.00 | 2119.26 | 557.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32928.29 | 05-JAN-05:01 | 376.40 | 250.09 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 32.52 |
February | 34513.64 | 12-FEB-05:01 | 0.00 | 225.08 | 28990.33 | 29786.16 | 0.00 | 0.00 | 0.00 | 0.00 | 118.80 |
March | 28874.77 | 05-MAR-05:01 | 0.00 | 250.09 | 32211.48 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 49.29 |
April | 32138.45 | 21-APR-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 64.48 |
May | 41610.87 | 11-MAY-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 150.38 |
June | 39953.98 | 09-JUN-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 242.31 |
July | 39929.71 | 02-JUL-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 157.23 |
August | 39754.52 | 17-AUG-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 106.56 |
September | 43611.80 | 28-SEP-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 176.89 |
October | 40228.02 | 01-OCT-02:61 | 0.00 | 250.09 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 134.54 |
November | 33781.15 | 07-NOV-04:21 | 0.00 | 175.06 | 11807.45 | 9652.92 | 0.00 | 0.00 | 0.00 | 0.00 | 176.43 |
December | 37152.24 | 22-DEC-05:01 | 376.40 | 250.09 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 46.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 28874.77 | 0.00 | 175.06 | 10291.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 32.52 | |
Maximum of Months | 43611.80 | 376.40 | 250.09 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 242.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.50 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.24 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.54 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.55 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.89 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.56 | 0.00 |
July | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.45 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.78 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.15 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.97 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.23 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.37 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.331825E+11 | 21421.11 | 05-JAN-11:09 | 0.105317E+12 | 116535.51 | 05-JAN-13:09 |
February | 0.299182E+11 | 20945.24 | 01-FEB-11:09 | 0.102145E+12 | 103026.80 | 12-FEB-07:10 |
March | 0.328535E+11 | 22239.32 | 14-MAR-10:20 | 0.915271E+11 | 93737.72 | 04-MAR-13:09 |
April | 0.314230E+11 | 21001.84 | 19-APR-10:20 | 0.811925E+11 | 79047.33 | 02-APR-12:50 |
May | 0.337126E+11 | 25645.32 | 17-MAY-10:20 | 0.617557E+11 | 54293.72 | 02-MAY-10:50 |
June | 0.396403E+11 | 31280.05 | 26-JUN-16:10 | 0.560988E+11 | 49287.83 | 01-JUN-12:39 |
July | 0.413922E+11 | 30893.70 | 17-JUL-10:20 | 0.572512E+11 | 48675.05 | 02-JUL-12:30 |
August | 0.406026E+11 | 30857.27 | 16-AUG-11:09 | 0.570556E+11 | 48326.43 | 31-AUG-12:20 |
September | 0.367828E+11 | 27576.57 | 09-SEP-10:00 | 0.564514E+11 | 52082.32 | 22-SEP-10:20 |
October | 0.332477E+11 | 24457.92 | 11-OCT-10:20 | 0.776241E+11 | 89962.06 | 30-OCT-12:50 |
November | 0.320504E+11 | 21852.46 | 09-NOV-11:20 | 0.891694E+11 | 93212.74 | 29-NOV-20:00 |
December | 0.334560E+11 | 21480.47 | 20-DEC-11:09 | 0.116652E+12 | 117546.60 | 21-DEC-20:10 |
Annual Sum or Average | 0.418262E+12 | 0.952240E+12 | ||||
Minimum of Months | 0.299182E+11 | 20945.24 | 0.560988E+11 | 48326.43 | ||
Maximum of Months | 0.413922E+11 | 31280.05 | 0.116652E+12 | 117546.60 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.192866E+10 | 0.170593E+10 | 0.214106E+11 | 0.00 | 0.512013E+10 | 0.79 | 0.00 | 32654894.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172110E+10 | 0.140517E+10 | 0.193386E+11 | 0.00 | 0.476183E+10 | 0.72 | 0.00 | 10753425.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188553E+10 | 0.136422E+10 | 0.214107E+11 | 0.00 | 0.494598E+10 | 0.80 | 0.00 | 0.209836E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176984E+10 | 0.112619E+10 | 0.207199E+11 | 0.00 | 0.468390E+10 | 0.77 | 0.00 | 0.164866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180573E+10 | 0.101730E+10 | 0.214107E+11 | 0.00 | 0.455108E+10 | 0.80 | 0.00 | 0.169423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174572E+10 | 0.917178E+09 | 0.207201E+11 | 0.00 | 0.461492E+10 | 0.77 | 0.00 | 0.838691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.177665E+10 | 0.966854E+09 | 0.214105E+11 | 0.00 | 0.479118E+10 | 0.79 | 0.00 | 0.908277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.184215E+10 | 0.108921E+10 | 0.214107E+11 | 0.00 | 0.475619E+10 | 0.80 | 0.00 | 0.813532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.178238E+10 | 0.123570E+10 | 0.207199E+11 | 0.00 | 0.448845E+10 | 0.77 | 0.00 | 0.534536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187819E+10 | 0.147703E+10 | 0.214106E+11 | 0.00 | 0.478959E+10 | 0.79 | 0.00 | 0.585994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.186133E+10 | 0.160046E+10 | 0.207200E+11 | 0.00 | 0.480287E+10 | 0.77 | 0.00 | 0.147823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193504E+10 | 0.175369E+10 | 0.214105E+11 | 0.00 | 0.531114E+10 | 0.79 | 0.00 | 68531199.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219323E+11 | 0.156589E+11 | 0.252093E+12 | 0.00 | 0.576173E+11 | 9.37 | 0.00 | 0.338650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.172110E+10 | 0.917178E+09 | 0.193386E+11 | 0.00 | 0.448845E+10 | 0.72 | 0.00 | 10753425.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.193504E+10 | 0.175369E+10 | 0.214107E+11 | 0.00 | 0.531114E+10 | 0.80 | 0.00 | 0.908277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.446809E+11 | 0.00 | 0.201101E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.471790E+11 | 0.00 | 0.183623E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.309236E+11 | 0.00 | 0.200778E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.232450E+11 | 0.00 | 0.187291E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.284384E+10 | 0.00 | 0.183861E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 20032519.97 | 0.00 | 0.168604E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 5657347.02 | 0.00 | 0.167198E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 2328567.73 | 0.00 | 0.165276E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.994263E+09 | 0.00 | 0.162387E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.195401E+11 | 0.00 | 0.175583E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.320118E+11 | 0.00 | 0.179391E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.566976E+11 | 0.00 | 0.194288E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.258144E+12 | 0.00 | 0.216938E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 2328567.73 | 0.00 | 0.162387E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.566976E+11 | 0.00 | 0.201101E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1346.16 | 02-JAN-16:49 | 1372.31 | 01-JAN-06:10 | 13637.09 | 01-JAN-11:09 | 0.00 | 3149.99 | 05-JAN-18:00 | 0.00 | 06-JAN-10:20 | 0.00 | 01-JAN-00:10 |
February | 1346.16 | 01-FEB-17:19 | 1372.31 | 01-FEB-06:10 | 13637.09 | 01-FEB-11:09 | 0.00 | 3146.44 | 12-FEB-07:10 | 0.00 | 01-FEB-11:20 | 0.00 | 01-FEB-00:10 |
March | 1346.16 | 01-MAR-17:49 | 1372.31 | 01-MAR-06:10 | 13637.09 | 01-MAR-11:09 | 0.00 | 2988.34 | 19-MAR-06:00 | 0.00 | 05-MAR-08:50 | 0.00 | 01-MAR-00:10 |
April | 1346.16 | 01-APR-18:19 | 1372.31 | 01-APR-05:10 | 13637.09 | 01-APR-10:09 | 0.00 | 2665.50 | 17-APR-06:10 | 0.00 | 13-APR-13:39 | 0.00 | 01-APR-00:10 |
May | 1346.16 | 01-MAY-18:49 | 1372.31 | 01-MAY-18:49 | 13637.09 | 01-MAY-10:09 | 0.00 | 2361.12 | 02-MAY-06:10 | 0.00 | 02-MAY-08:39 | 0.00 | 01-MAY-00:10 |
June | 1346.16 | 01-JUN-19:19 | 1372.31 | 01-JUN-19:19 | 13637.09 | 01-JUN-10:09 | 0.00 | 3376.10 | 26-JUN-17:10 | 0.00 | 13-JUN-06:49 | 0.00 | 01-JUN-00:10 |
July | 1346.16 | 01-JUL-19:30 | 1372.31 | 01-JUL-19:30 | 13637.09 | 01-JUL-10:09 | 0.00 | 3115.86 | 17-JUL-12:00 | 0.00 | 03-JUL-08:30 | 0.00 | 01-JUL-00:10 |
August | 1346.16 | 01-AUG-18:00 | 1372.31 | 01-AUG-19:10 | 13637.09 | 01-AUG-10:09 | 0.00 | 3185.74 | 16-AUG-12:00 | 0.00 | 04-AUG-13:20 | 0.00 | 01-AUG-00:10 |
September | 1346.16 | 01-SEP-18:30 | 1372.31 | 01-SEP-05:10 | 13637.09 | 01-SEP-10:09 | 0.00 | 2484.48 | 09-SEP-12:00 | 0.00 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 1346.16 | 02-OCT-17:40 | 1372.31 | 01-OCT-05:10 | 13637.09 | 01-OCT-10:09 | 0.00 | 2716.44 | 30-OCT-06:10 | 0.00 | 04-OCT-07:49 | 0.00 | 01-OCT-00:10 |
November | 1346.16 | 01-NOV-16:00 | 1372.31 | 01-NOV-05:10 | 13637.09 | 01-NOV-10:09 | 0.00 | 2962.77 | 29-NOV-20:00 | 0.00 | 04-NOV-09:39 | 0.00 | 01-NOV-00:10 |
December | 1346.16 | 01-DEC-16:30 | 1372.31 | 01-DEC-06:10 | 13637.09 | 01-DEC-11:09 | 0.00 | 3277.19 | 21-DEC-18:10 | 0.00 | 21-DEC-11:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1346.16 | 1372.31 | 13637.09 | 0.00 | 2361.12 | 0.00 | 0.00 | ||||||
Maximum of Months | 1346.16 | 1372.31 | 13637.09 | 0.00 | 3376.10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 2405.96 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1443.87 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4521.39 | 14-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3288.21 | 20-APR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6675.01 | 17-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13819.09 | 26-JUN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12435.72 | 17-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12671.63 | 16-AUG-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9516.20 | 09-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5918.26 | 11-OCT-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3527.84 | 07-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2785.46 | 01-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1443.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13819.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 21421.11 | 05-JAN-11:09 | 1008.12 | 13637.09 | 0.00 | 0.00 | 2947.95 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20945.24 | 01-FEB-11:09 | 1008.12 | 13637.09 | 0.00 | 0.00 | 2465.90 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22239.32 | 14-MAR-10:20 | 1008.12 | 13637.09 | 0.00 | 0.00 | 1975.40 | 0.00 | 0.00 | 1718.67 | 0.00 |
April | 21001.84 | 19-APR-10:20 | 1008.12 | 13637.09 | 0.00 | 0.00 | 1975.40 | 0.00 | 0.00 | 484.74 | 0.00 |
May | 25645.32 | 17-MAY-10:20 | 1008.12 | 13637.09 | 0.00 | 0.00 | 1975.40 | 0.00 | 0.00 | 5121.19 | 0.00 |
June | 31280.05 | 26-JUN-16:10 | 1008.12 | 12287.48 | 0.00 | 0.00 | 3221.98 | 0.00 | 0.00 | 13616.77 | 0.00 |
July | 30893.70 | 17-JUL-10:20 | 1008.12 | 13637.09 | 0.00 | 0.00 | 2498.09 | 0.00 | 0.00 | 9846.99 | 0.00 |
August | 30857.27 | 16-AUG-11:09 | 1008.12 | 12737.35 | 0.00 | 0.00 | 3137.36 | 0.00 | 0.00 | 12288.69 | 0.00 |
September | 27576.57 | 09-SEP-10:00 | 896.11 | 13637.09 | 0.00 | 0.00 | 2464.02 | 0.00 | 0.00 | 8901.19 | 0.00 |
October | 24457.92 | 11-OCT-10:20 | 1008.12 | 13637.09 | 0.00 | 0.00 | 1975.40 | 0.00 | 0.00 | 3937.15 | 0.00 |
November | 21852.46 | 09-NOV-11:20 | 1008.12 | 13637.09 | 0.00 | 0.00 | 1975.40 | 0.00 | 0.00 | 1326.96 | 0.00 |
December | 21480.47 | 20-DEC-11:09 | 1008.12 | 13637.09 | 0.00 | 0.00 | 3007.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 20945.24 | 896.11 | 12287.48 | 0.00 | 0.00 | 1975.40 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31280.05 | 1008.12 | 13637.09 | 0.00 | 0.00 | 3221.98 | 0.00 | 0.00 | 13616.77 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 78945.78 | 05-JAN-18:00 | 0.00 | 27747.86 | 31-JAN-13:00 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 82027.36 | 12-FEB-07:10 | 0.00 | 27774.97 | 11-FEB-13:39 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 70156.24 | 19-MAR-06:00 | 0.00 | 27737.02 | 01-MAR-13:00 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 67205.90 | 03-APR-02:49 | 0.00 | 27462.64 | 01-APR-12:50 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 25428.90 | 02-MAY-06:10 | 0.00 | 26964.65 | 01-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 2454.02 | 09-JUN-05:10 | 0.00 | 26304.68 | 01-JUN-12:39 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 2059.26 | 17-JUL-02:30 | 0.00 | 25691.90 | 02-JUL-12:30 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 1904.45 | 01-AUG-02:09 | 0.00 | 25343.28 | 31-AUG-12:20 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 25983.02 | 22-SEP-06:10 | 0.00 | 25740.00 | 30-SEP-12:00 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 67205.90 | 30-OCT-02:09 | 0.00 | 26393.80 | 31-OCT-12:39 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 67205.90 | 02-NOV-02:09 | 0.00 | 27009.09 | 30-NOV-13:00 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 89079.47 | 23-DEC-07:10 | 0.00 | 27495.48 | 31-DEC-13:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 1904.45 | 0.00 | 25343.28 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 89079.47 | 0.00 | 27774.97 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.17 | 19.96 | 0.17 | 19.96 | 0.00 | 19.96 | 0.00 | 19.96 |
February | 18.83 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 |
March | 12.33 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 |
April | 6.83 | 19.83 | 0.00 | 19.83 | 0.00 | 19.83 | 0.00 | 19.83 |
May | 0.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 24.57 | 0.17 | 24.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 24.62 | 0.00 | 24.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 24.66 | 0.00 | 24.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 24.67 | 0.00 | 24.67 |
October | 4.83 | 19.50 | 0.33 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 |
November | 6.67 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
December | 13.50 | 19.74 | 0.00 | 19.74 | 0.00 | 19.74 | 0.00 | 19.74 |
Annual Sum or Average | 72.50 | 19.77 | 0.50 | 19.77 | 36.83 | 21.40 | 0.17 | 21.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.40 | 0.00 | 19.40 |
Maximum of Months | 18.83 | 20.47 | 0.33 | 20.47 | 12.67 | 24.67 | 0.17 | 24.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.99 | 0.00 | 26.99 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.99 | 0.00 | 26.99 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.60 | 0.00 | 27.60 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.40 | 0.00 | 27.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.77 | 0.00 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 29.23 | 0.00 | 29.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 29.44 | 0.00 | 29.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 29.62 | 0.00 | 29.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 29.15 | 0.00 | 29.15 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.61 | 0.00 | 27.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.38 | 0.00 | 27.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.97 | 0.00 | 26.97 |
Annual Sum or Average | 0.00 | 0.00 | 119.50 | 28.86 | 0.00 | 28.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.97 | 0.00 | 26.97 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 29.62 | 0.00 | 29.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 587.67 | 20.98 | 117.50 | 20.81 | 117.50 | 20.69 |
February | 535.83 | 20.94 | 154.67 | 20.80 | 154.67 | 20.70 |
March | 540.50 | 21.08 | 112.00 | 20.92 | 112.00 | 20.80 |
April | 521.83 | 21.16 | 86.83 | 21.02 | 84.83 | 20.90 |
May | 373.50 | 21.67 | 97.67 | 22.02 | 12.50 | 21.96 |
June | 101.17 | 23.25 | 459.17 | 23.77 | 54.50 | 23.77 |
July | 134.67 | 23.53 | 505.33 | 23.82 | 105.17 | 23.82 |
August | 88.33 | 23.27 | 517.00 | 23.80 | 52.50 | 23.80 |
September | 127.50 | 21.95 | 346.33 | 23.35 | 1.50 | 23.33 |
October | 462.50 | 21.20 | 102.17 | 21.33 | 52.17 | 21.21 |
November | 547.17 | 21.05 | 67.67 | 20.90 | 65.33 | 20.77 |
December | 581.83 | 20.98 | 164.17 | 20.83 | 164.17 | 20.74 |
Annual Sum or Average | 4602.50 | 21.29 | 2730.50 | 21.86 | 976.83 | 21.75 |
Minimum of Months | 88.33 | 20.94 | 67.67 | 20.80 | 1.50 | 20.69 |
Maximum of Months | 587.67 | 23.53 | 517.00 | 23.82 | 164.17 | 23.82 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 559.83 | 18.99 | 248.33 | 19.12 | 210.33 | 18.98 |
February | 521.67 | 18.96 | 249.00 | 19.00 | 227.17 | 18.89 |
March | 509.50 | 19.50 | 265.83 | 20.03 | 180.33 | 19.86 |
April | 470.50 | 19.66 | 234.83 | 20.41 | 138.67 | 20.32 |
May | 387.83 | 23.44 | 415.33 | 24.23 | 229.50 | 24.51 |
June | 496.67 | 26.03 | 585.67 | 25.94 | 493.17 | 25.98 |
July | 542.67 | 26.06 | 603.50 | 26.00 | 542.00 | 26.02 |
August | 524.67 | 26.04 | 609.17 | 25.94 | 524.17 | 25.97 |
September | 447.00 | 25.48 | 528.50 | 25.59 | 404.83 | 25.72 |
October | 440.33 | 20.46 | 252.17 | 21.58 | 128.17 | 21.73 |
November | 517.17 | 19.28 | 192.00 | 19.64 | 136.83 | 19.53 |
December | 558.00 | 19.03 | 302.83 | 19.18 | 260.83 | 19.03 |
Annual Sum or Average | 5975.83 | 21.84 | 4487.17 | 22.66 | 3476.00 | 22.87 |
Minimum of Months | 387.83 | 18.96 | 192.00 | 19.00 | 128.17 | 18.89 |
Maximum of Months | 559.83 | 26.06 | 609.17 | 26.00 | 542.00 | 26.02 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 21.08008 | 24.08429 | -0.4071 | 10.06679 |
February | 551.00000 | 21.01852 | 21.64453 | -0.4522 | 10.94841 |
March | 612.00000 | 21.40883 | 22.07247 | -0.3441 | 9.82113 |
April | 590.00000 | 21.47051 | 27.12467 | -0.3049 | 9.28617 |
May | 611.00000 | 22.51262 | 32.15016 | -0.9693 | 28.12059 |
June | 592.00000 | 23.76916 | 36.03342 | -0.4132 | 9.32728 |
July | 609.00000 | 23.82063 | 38.99939 | -0.3765 | 8.61126 |
August | 612.00000 | 23.78898 | 37.56926 | -0.3681 | 8.51595 |
September | 590.00000 | 23.44440 | 28.98055 | -0.5396 | 13.55244 |
October | 610.00000 | 21.83136 | 25.13999 | -0.1463 | 8.20260 |
November | 591.00000 | 21.25781 | 25.84455 | -0.3105 | 8.87420 |
December | 609.00000 | 21.10824 | 17.89009 | -0.4411 | 10.88920 |
Annual Sum or Average | 7187.00000 | 22.21645 | 28.16907 | -0.4229 | 11.36745 |
Minimum of Months | 551.00000 | 21.01852 | 17.89009 | -0.9693 | 8.20260 |
Maximum of Months | 612.00000 | 23.82063 | 38.99939 | -0.1463 | 28.12059 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.43103 | 32.12398 | -0.4964 | 13.51851 |
February | 551.00000 | 19.24808 | 29.74962 | -0.5605 | 14.31294 |
March | 612.00000 | 20.38846 | 29.44303 | -0.2924 | 13.48786 |
April | 590.00000 | 20.63028 | 34.18570 | -0.1999 | 13.14651 |
May | 611.00000 | 23.64636 | 35.36813 | -0.2832 | 18.60374 |
June | 592.00000 | 25.81409 | 36.12434 | 0.50534 | 12.17440 |
July | 609.00000 | 25.91296 | 38.26185 | 0.55638 | 12.95561 |
August | 612.00000 | 25.82557 | 37.69041 | 0.53724 | 12.63808 |
September | 590.00000 | 25.17655 | 31.10491 | 0.27742 | 13.56005 |
October | 610.00000 | 21.45307 | 31.33019 | 0.02042 | 13.31403 |
November | 591.00000 | 19.89588 | 33.66962 | -0.3476 | 12.46443 |
December | 609.00000 | 19.50271 | 25.22871 | -0.5081 | 14.25332 |
Annual Sum or Average | 7187.00000 | 22.26248 | 32.87411 | -0.0631 | 13.70684 |
Minimum of Months | 551.00000 | 19.24808 | 25.22871 | -0.5605 | 12.17440 |
Maximum of Months | 612.00000 | 25.91296 | 38.26185 | 0.55638 | 18.60374 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 45171561.26 | 13377057.40 | 7.00 | 45171561.26 | 0.00 | 0.00 | 0.30 | 20-JAN-13:55 | 0.00 | 01-JAN-00:01 | 4160.69 | 20-JAN-13:55 | 4160.69 | 20-JAN-13:55 | 0.00 | 20-JAN-13:55 | 1205.23 | 20-JAN-13:55 | 0.00 | 01-JAN-00:01 |
February | 11118980.19 | 3368913.92 | 2.67 | 11118980.19 | 0.00 | 0.00 | 0.15 | 18-FEB-14:00 | 0.00 | 01-FEB-00:01 | 2005.68 | 18-FEB-14:00 | 2005.68 | 18-FEB-14:00 | 0.00 | 18-FEB-13:30 | 602.58 | 18-FEB-14:00 | 0.00 | 01-FEB-00:01 |
March | 0.320259E+09 | 91925526.81 | 25.69 | 0.320259E+09 | 0.00 | 0.00 | 0.59 | 14-MAR-13:00 | 0.00 | 01-MAR-00:01 | 8813.87 | 14-MAR-13:00 | 8813.87 | 14-MAR-13:00 | 0.00 | 14-MAR-13:00 | 2369.76 | 14-MAR-13:00 | 0.00 | 01-MAR-00:01 |
April | 0.185217E+09 | 55144773.19 | 28.00 | 0.185164E+09 | 53411.96 | 0.00 | 0.38 | 20-APR-13:00 | 0.00 | 01-APR-00:01 | 5399.52 | 20-APR-13:00 | 5399.52 | 20-APR-13:00 | 18.68 | 27-APR-15:40 | 1532.51 | 20-APR-13:00 | 0.00 | 01-APR-00:01 |
May | 0.246578E+10 | 0.686833E+09 | 144.30 | 0.241857E+10 | 47207834.37 | 0.00 | 0.81 | 17-MAY-12:55 | 0.00 | 01-MAY-00:01 | 12762.30 | 17-MAY-12:55 | 12762.30 | 17-MAY-12:55 | 1352.33 | 31-MAY-18:40 | 3234.27 | 17-MAY-12:55 | 0.00 | 01-MAY-00:01 |
June | 0.141054E+11 | 0.375171E+10 | 412.62 | 0.132361E+11 | 0.869272E+09 | 0.00 | 1.00 | 02-JUN-02:61 | 0.00 | 01-JUN-00:01 | 33291.36 | 14-JUN-03:08 | 33291.36 | 14-JUN-02:61 | 17472.07 | 21-JUN-02:61 | 7981.57 | 06-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.152045E+11 | 0.401708E+10 | 442.23 | 0.139927E+11 | 0.121176E+10 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:02 | 33291.36 | 17-JUL-02:15 | 33291.36 | 01-JUL-02:61 | 16487.32 | 20-JUL-02:61 | 7981.57 | 01-JUL-02:61 | 0.00 | 01-JUL-00:02 |
August | 0.139369E+11 | 0.367191E+10 | 419.21 | 0.129965E+11 | 0.940417E+09 | 0.00 | 1.00 | 01-AUG-02:62 | 0.00 | 01-AUG-00:01 | 34360.44 | 04-AUG-02:62 | 33291.36 | 15-AUG-02:61 | 20750.51 | 04-AUG-02:62 | 8053.21 | 04-AUG-02:62 | 0.00 | 01-AUG-00:01 |
September | 0.908752E+10 | 0.242085E+10 | 329.63 | 0.887976E+10 | 0.207764E+09 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 | 33291.36 | 06-SEP-02:61 | 33291.36 | 29-SEP-02:61 | 13473.50 | 01-SEP-02:61 | 7981.57 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 |
October | 0.926381E+09 | 0.259107E+09 | 65.43 | 0.926280E+09 | 100380.65 | 0.00 | 0.76 | 11-OCT-13:00 | 0.00 | 01-OCT-00:01 | 11828.21 | 11-OCT-13:00 | 11828.21 | 11-OCT-13:00 | 465.73 | 08-OCT-03:28 | 3038.84 | 11-OCT-13:00 | 0.00 | 01-OCT-00:01 |
November | 0.220215E+09 | 64225957.93 | 21.80 | 0.220215E+09 | 0.00 | 0.00 | 0.46 | 07-NOV-14:00 | 0.00 | 01-NOV-00:01 | 6635.08 | 07-NOV-14:00 | 6635.08 | 07-NOV-14:00 | 0.00 | 07-NOV-13:55 | 1846.03 | 07-NOV-14:00 | 0.00 | 01-NOV-00:01 |
December | 98211701.12 | 28978041.64 | 11.17 | 98211701.12 | -0.0 | 0.00 | 0.37 | 01-DEC-14:00 | 0.00 | 01-DEC-00:01 | 5228.14 | 01-DEC-14:00 | 5228.14 | 01-DEC-14:00 | 0.00 | 02-DEC-14:55 | 1488.03 | 01-DEC-14:00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.566066E+11 | 0.150645E+11 | 1909.75 | 0.533301E+11 | 0.327657E+10 | 0.00 | ||||||||||||||
Minimum of Months | 11118980.19 | 3368913.92 | 2.67 | 11118980.19 | -0.0 | 0.00 | 0.15 | 0.00 | 2005.68 | 2005.68 | 0.00 | 602.58 | 0.00 | |||||||
Maximum of Months | 0.152045E+11 | 0.401708E+10 | 442.23 | 0.139927E+11 | 0.121176E+10 | 0.00 | 1.00 | 0.00 | 34360.44 | 33291.36 | 20750.51 | 8053.21 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 65492289.33 | 19277836.92 | 11.40 | 64894736.91 | 597552.42 | 0.00 | 0.37 | 20-JAN-14:00 | 0.00 | 01-JAN-00:01 | 4214.33 | 20-JAN-14:00 | 4214.33 | 20-JAN-14:00 | 836.11 | 10-JAN-04:10 | 1200.98 | 20-JAN-14:00 | 0.00 | 01-JAN-00:01 |
February | 24826477.52 | 7384511.84 | 4.17 | 24642861.50 | 183616.02 | 0.00 | 0.26 | 18-FEB-14:00 | 0.00 | 01-FEB-00:01 | 2872.98 | 18-FEB-14:00 | 2872.98 | 18-FEB-14:00 | 791.69 | 28-FEB-04:10 | 841.29 | 18-FEB-14:00 | 0.00 | 01-FEB-00:01 |
March | 0.416068E+09 | 0.117911E+09 | 44.40 | 0.414569E+09 | 1499680.58 | 0.00 | 1.00 | 10-MAR-04:42 | 0.00 | 01-MAR-00:01 | 27234.47 | 15-MAR-02:61 | 26351.45 | 15-MAR-02:61 | 4584.88 | 17-MAR-04:01 | 6529.44 | 15-MAR-02:61 | 0.00 | 01-MAR-00:01 |
April | 0.379416E+09 | 0.109722E+09 | 47.31 | 0.371546E+09 | 7869846.49 | 0.00 | 1.00 | 20-APR-02:61 | 0.00 | 01-APR-00:01 | 20724.97 | 21-APR-02:61 | 13192.40 | 21-APR-02:61 | 7532.57 | 21-APR-02:61 | 4970.01 | 21-APR-02:61 | 0.00 | 01-APR-00:01 |
May | 0.372416E+10 | 0.100740E+10 | 213.14 | 0.353860E+10 | 0.185557E+09 | 0.00 | 1.00 | 05-MAY-02:61 | 0.00 | 01-MAY-00:01 | 27234.47 | 07-MAY-03:22 | 23692.80 | 11-MAY-02:61 | 13701.45 | 22-MAY-02:61 | 6529.44 | 07-MAY-03:22 | 0.00 | 01-MAY-00:01 |
June | 0.180579E+11 | 0.463521E+10 | 468.46 | 0.166780E+11 | 0.137983E+10 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 | 27234.47 | 05-JUN-02:61 | 27234.47 | 07-JUN-02:32 | 16047.62 | 21-JUN-03:02 | 7893.26 | 26-JUN-15:00 | 0.00 | 01-JUN-00:01 |
July | 0.198779E+11 | 0.506569E+10 | 512.12 | 0.179090E+11 | 0.196892E+10 | 0.00 | 1.00 | 01-JUL-02:11 | 0.00 | 01-JUL-00:02 | 27234.47 | 11-JUL-03:16 | 27234.47 | 01-JUL-02:11 | 16048.32 | 20-JUL-03:12 | 7312.88 | 16-JUL-13:00 | 0.00 | 01-JUL-00:02 |
August | 0.175112E+11 | 0.446340E+10 | 477.73 | 0.160780E+11 | 0.143325E+10 | 0.00 | 1.00 | 01-AUG-02:11 | 0.00 | 01-AUG-00:01 | 27671.45 | 04-AUG-02:11 | 27234.47 | 15-AUG-02:52 | 18579.45 | 04-AUG-02:11 | 7339.93 | 16-AUG-14:00 | 0.00 | 01-AUG-00:01 |
September | 0.114029E+11 | 0.292450E+10 | 389.37 | 0.109590E+11 | 0.443947E+09 | 0.00 | 1.00 | 01-SEP-02:11 | 0.00 | 01-SEP-00:01 | 27234.47 | 01-SEP-02:51 | 27234.47 | 30-SEP-03:11 | 15129.73 | 01-SEP-02:11 | 6529.44 | 01-SEP-02:11 | 0.00 | 01-SEP-00:01 |
October | 0.118533E+10 | 0.326886E+09 | 88.73 | 0.116747E+10 | 17864564.41 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:01 | 27234.47 | 06-OCT-02:61 | 22762.02 | 11-OCT-02:61 | 9291.47 | 10-OCT-02:61 | 6529.44 | 06-OCT-02:61 | 0.00 | 01-OCT-00:01 |
November | 0.291822E+09 | 83597011.25 | 27.66 | 0.289265E+09 | 2557303.51 | 0.00 | 1.00 | 07-NOV-04:21 | 0.00 | 01-NOV-00:01 | 27234.47 | 07-NOV-04:21 | 23985.32 | 07-NOV-04:21 | 6061.35 | 10-NOV-05:01 | 6529.44 | 07-NOV-04:21 | 0.00 | 01-NOV-00:01 |
December | 0.135833E+09 | 39553157.58 | 16.71 | 0.135440E+09 | 393037.70 | 0.00 | 0.43 | 02-DEC-15:00 | 0.00 | 01-DEC-00:01 | 5004.45 | 02-DEC-15:00 | 5004.45 | 02-DEC-15:00 | 305.16 | 05-DEC-04:04 | 1403.96 | 02-DEC-15:00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.730729E+11 | 0.188005E+11 | 2301.21 | 0.676304E+11 | 0.544247E+10 | 0.00 | ||||||||||||||
Minimum of Months | 24826477.52 | 7384511.84 | 4.17 | 24642861.50 | 183616.02 | 0.00 | 0.26 | 0.00 | 2872.98 | 2872.98 | 305.16 | 841.29 | 0.00 | |||||||
Maximum of Months | 0.198779E+11 | 0.506569E+10 | 512.12 | 0.179090E+11 | 0.196892E+10 | 0.00 | 1.00 | 0.00 | 27671.45 | 27234.47 | 18579.45 | 7893.26 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.41 | 73.79 | 46.62 | 111.05 | 175.77 | 0.00 | 0.00 | 0.00 |
February | 159.95 | 100.97 | 58.97 | 157.05 | 180.24 | 0.00 | 0.00 | 0.00 |
March | 193.05 | 112.61 | 80.45 | 204.75 | 134.76 | 0.00 | 0.00 | 0.00 |
April | 197.99 | 96.44 | 101.54 | 206.65 | 116.54 | 0.00 | 0.00 | 0.00 |
May | 231.44 | 96.67 | 134.77 | 276.23 | 68.30 | 0.00 | 0.00 | 0.00 |
June | 282.38 | 148.24 | 134.14 | 390.23 | 39.82 | 0.00 | 0.00 | 0.00 |
July | 256.71 | 122.24 | 134.47 | 358.80 | 36.97 | 0.00 | 0.00 | 0.00 |
August | 258.93 | 142.61 | 116.32 | 356.71 | 44.03 | 0.00 | 0.00 | 0.00 |
September | 215.44 | 117.03 | 98.41 | 281.57 | 65.90 | 0.00 | 0.00 | 0.00 |
October | 156.02 | 85.49 | 70.53 | 169.67 | 137.02 | 0.00 | 0.00 | 0.00 |
November | 121.44 | 68.57 | 52.88 | 117.95 | 162.50 | 0.00 | 0.00 | 0.00 |
December | 105.14 | 60.57 | 44.57 | 91.46 | 203.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.70 | 102.05 | 89.64 | 227.17 | 113.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 105.14 | 60.57 | 44.57 | 91.46 | 36.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 282.38 | 148.24 | 134.77 | 390.23 | 203.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 737.08 | 606.33 | 130.75 | 872.71 | 327.98 | 0.00 | 0.00 | 0.00 |
February | 706.99 | 563.66 | 143.33 | 832.70 | 342.21 | 0.00 | 0.00 | 0.00 |
March | 521.25 | 342.95 | 178.30 | 622.24 | 269.21 | 0.00 | 0.00 | 0.00 |
April | 337.60 | 135.75 | 201.85 | 370.23 | 243.32 | 0.00 | 0.00 | 0.00 |
May | 309.37 | 56.71 | 252.67 | 372.56 | 146.80 | 0.00 | 0.00 | 0.00 |
June | 285.23 | 52.13 | 233.10 | 422.81 | 86.07 | 0.00 | 0.00 | 0.00 |
July | 296.92 | 53.17 | 243.75 | 442.59 | 78.37 | 0.00 | 0.00 | 0.00 |
August | 378.04 | 158.03 | 220.01 | 561.38 | 91.56 | 0.00 | 0.00 | 0.00 |
September | 486.39 | 271.40 | 214.99 | 677.51 | 137.37 | 0.00 | 0.00 | 0.00 |
October | 581.57 | 412.64 | 168.93 | 726.28 | 270.12 | 0.00 | 0.00 | 0.00 |
November | 708.57 | 564.83 | 143.74 | 856.61 | 310.28 | 0.00 | 0.00 | 0.00 |
December | 677.58 | 548.42 | 129.16 | 783.03 | 377.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 501.06 | 312.42 | 188.64 | 627.22 | 222.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 285.23 | 52.13 | 129.16 | 370.23 | 78.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 737.08 | 606.33 | 252.67 | 872.71 | 377.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.09 | 81.16 | 46.92 | 125.29 | 178.71 | 0.00 | 0.00 | 0.00 |
February | 154.45 | 95.72 | 58.74 | 150.96 | 181.12 | 0.00 | 0.00 | 0.00 |
March | 180.86 | 99.78 | 81.07 | 188.31 | 136.04 | 0.00 | 0.00 | 0.00 |
April | 170.28 | 72.10 | 98.19 | 171.04 | 118.78 | 0.00 | 0.00 | 0.00 |
May | 208.13 | 73.37 | 134.76 | 247.64 | 71.37 | 0.00 | 0.00 | 0.00 |
June | 254.56 | 122.48 | 132.08 | 355.13 | 42.89 | 0.00 | 0.00 | 0.00 |
July | 207.40 | 75.97 | 131.44 | 291.18 | 39.01 | 0.00 | 0.00 | 0.00 |
August | 216.47 | 106.94 | 109.53 | 297.04 | 45.28 | 0.00 | 0.00 | 0.00 |
September | 191.94 | 92.05 | 99.89 | 251.13 | 68.69 | 0.00 | 0.00 | 0.00 |
October | 161.48 | 92.30 | 69.18 | 178.96 | 137.76 | 0.00 | 0.00 | 0.00 |
November | 132.50 | 80.44 | 52.06 | 132.79 | 162.91 | 0.00 | 0.00 | 0.00 |
December | 107.02 | 63.22 | 43.80 | 94.63 | 203.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 176.15 | 87.86 | 88.30 | 207.24 | 115.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 107.02 | 63.22 | 43.80 | 94.63 | 39.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 254.56 | 122.48 | 134.76 | 355.13 | 203.76 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322500E+09 | 0.197637E+09 | 0.124862E+09 | 0.297432E+09 | 0.470779E+09 |
February | 0.386947E+09 | 0.244278E+09 | 0.142669E+09 | 0.379924E+09 | 0.436025E+09 |
March | 0.517073E+09 | 0.301604E+09 | 0.215470E+09 | 0.548403E+09 | 0.360944E+09 |
April | 0.513181E+09 | 0.249979E+09 | 0.263202E+09 | 0.535633E+09 | 0.302079E+09 |
May | 0.619897E+09 | 0.258933E+09 | 0.360964E+09 | 0.739859E+09 | 0.182931E+09 |
June | 0.731940E+09 | 0.384249E+09 | 0.347692E+09 | 0.101147E+10 | 0.103201E+09 |
July | 0.687571E+09 | 0.327404E+09 | 0.360167E+09 | 0.961000E+09 | 99030439.88 |
August | 0.693510E+09 | 0.381960E+09 | 0.311550E+09 | 0.955401E+09 | 0.117934E+09 |
September | 0.558422E+09 | 0.303350E+09 | 0.255072E+09 | 0.729820E+09 | 0.170801E+09 |
October | 0.417889E+09 | 0.228979E+09 | 0.188910E+09 | 0.454442E+09 | 0.366983E+09 |
November | 0.314780E+09 | 0.177728E+09 | 0.137052E+09 | 0.305718E+09 | 0.421203E+09 |
December | 0.281599E+09 | 0.162221E+09 | 0.119378E+09 | 0.244977E+09 | 0.546019E+09 |
Annual Sum or Average | 0.604531E+10 | 0.321832E+10 | 0.282699E+10 | 0.716408E+10 | 0.357793E+10 |
Minimum of Months | 0.281599E+09 | 0.162221E+09 | 0.119378E+09 | 0.244977E+09 | 99030439.88 |
Maximum of Months | 0.731940E+09 | 0.384249E+09 | 0.360964E+09 | 0.101147E+10 | 0.546019E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197419E+10 | 0.162398E+10 | 0.350207E+09 | 0.233748E+10 | 0.878461E+09 |
February | 0.171036E+10 | 0.136361E+10 | 0.346754E+09 | 0.201446E+10 | 0.827879E+09 |
March | 0.139612E+10 | 0.918566E+09 | 0.477553E+09 | 0.166661E+10 | 0.721045E+09 |
April | 0.875062E+09 | 0.351865E+09 | 0.523197E+09 | 0.959649E+09 | 0.630688E+09 |
May | 0.828629E+09 | 0.151881E+09 | 0.676747E+09 | 0.997862E+09 | 0.393195E+09 |
June | 0.739325E+09 | 0.135127E+09 | 0.604197E+09 | 0.109593E+10 | 0.223081E+09 |
July | 0.795273E+09 | 0.142411E+09 | 0.652862E+09 | 0.118544E+10 | 0.209919E+09 |
August | 0.101254E+10 | 0.423281E+09 | 0.589263E+09 | 0.150361E+10 | 0.245248E+09 |
September | 0.126071E+10 | 0.703469E+09 | 0.557243E+09 | 0.175610E+10 | 0.356059E+09 |
October | 0.155769E+10 | 0.110522E+10 | 0.452475E+09 | 0.194527E+10 | 0.723497E+09 |
November | 0.183661E+10 | 0.146404E+10 | 0.372566E+09 | 0.222034E+10 | 0.804236E+09 |
December | 0.181482E+10 | 0.146889E+10 | 0.345930E+09 | 0.209726E+10 | 0.101053E+10 |
Annual Sum or Average | 0.158013E+11 | 0.985234E+10 | 0.594899E+10 | 0.197800E+11 | 0.702384E+10 |
Minimum of Months | 0.739325E+09 | 0.135127E+09 | 0.345930E+09 | 0.959649E+09 | 0.209919E+09 |
Maximum of Months | 0.197419E+10 | 0.162398E+10 | 0.676747E+09 | 0.233748E+10 | 0.101053E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.343068E+09 | 0.217386E+09 | 0.125682E+09 | 0.335579E+09 | 0.478658E+09 |
February | 0.373657E+09 | 0.231556E+09 | 0.142100E+09 | 0.365192E+09 | 0.438172E+09 |
March | 0.484406E+09 | 0.267257E+09 | 0.217149E+09 | 0.504364E+09 | 0.364377E+09 |
April | 0.441378E+09 | 0.186871E+09 | 0.254506E+09 | 0.443336E+09 | 0.307870E+09 |
May | 0.557459E+09 | 0.196525E+09 | 0.360935E+09 | 0.663272E+09 | 0.191162E+09 |
June | 0.659813E+09 | 0.317461E+09 | 0.342352E+09 | 0.920498E+09 | 0.111172E+09 |
July | 0.555511E+09 | 0.203473E+09 | 0.352038E+09 | 0.779908E+09 | 0.104485E+09 |
August | 0.579796E+09 | 0.286427E+09 | 0.293369E+09 | 0.795593E+09 | 0.121281E+09 |
September | 0.497521E+09 | 0.238594E+09 | 0.258927E+09 | 0.650924E+09 | 0.178053E+09 |
October | 0.432499E+09 | 0.247205E+09 | 0.185294E+09 | 0.479322E+09 | 0.368974E+09 |
November | 0.343440E+09 | 0.208510E+09 | 0.134930E+09 | 0.344187E+09 | 0.422254E+09 |
December | 0.286653E+09 | 0.169333E+09 | 0.117319E+09 | 0.253458E+09 | 0.545745E+09 |
Annual Sum or Average | 0.555520E+10 | 0.277060E+10 | 0.278460E+10 | 0.653563E+10 | 0.363221E+10 |
Minimum of Months | 0.286653E+09 | 0.169333E+09 | 0.117319E+09 | 0.253458E+09 | 0.104485E+09 |
Maximum of Months | 0.659813E+09 | 0.317461E+09 | 0.360935E+09 | 0.920498E+09 | 0.545745E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1082.76 | 656.16 | 985.57 | 761.28 | 224.29 | 0.00 | 0.00 |
February | 1118.22 | 681.09 | 1021.40 | 760.35 | 261.05 | 0.00 | 0.00 |
March | 999.17 | 523.88 | 895.16 | 555.34 | 339.82 | 0.00 | 0.00 |
April | 731.34 | 462.05 | 705.87 | 304.29 | 401.58 | 0.00 | 0.00 |
May | 883.96 | 274.01 | 748.95 | 226.75 | 522.19 | 0.00 | 0.00 |
June | 1159.95 | 160.55 | 822.18 | 322.85 | 499.32 | 0.00 | 0.00 |
July | 1087.11 | 148.90 | 761.03 | 251.38 | 509.66 | 0.00 | 0.00 |
August | 1210.15 | 175.89 | 853.44 | 407.58 | 445.86 | 0.00 | 0.00 |
September | 1202.22 | 263.98 | 893.77 | 480.48 | 413.29 | 0.00 | 0.00 |
October | 1067.31 | 537.30 | 899.07 | 590.43 | 308.65 | 0.00 | 0.00 |
November | 1091.95 | 620.28 | 962.51 | 713.84 | 248.67 | 0.00 | 0.00 |
December | 942.05 | 757.83 | 889.74 | 672.21 | 217.53 | 0.00 | 0.00 |
Annual Sum or Average | 1047.46 | 437.18 | 868.91 | 502.32 | 366.58 | 0.00 | 0.00 |
Minimum of Months | 731.34 | 148.90 | 705.87 | 226.75 | 217.53 | 0.00 | 0.00 |
Maximum of Months | 1210.15 | 757.83 | 1021.40 | 761.28 | 522.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.290006E+10 | 0.175746E+10 | 0.263976E+10 | 0.203901E+10 | 0.600751E+09 | 0.00 | 0.00 |
February | 0.270519E+10 | 0.164769E+10 | 0.247096E+10 | 0.183944E+10 | 0.631524E+09 | 0.00 | 0.00 |
March | 0.267617E+10 | 0.140316E+10 | 0.239760E+10 | 0.148743E+10 | 0.910171E+09 | 0.00 | 0.00 |
April | 0.189562E+10 | 0.119764E+10 | 0.182962E+10 | 0.788716E+09 | 0.104091E+10 | 0.00 | 0.00 |
May | 0.236761E+10 | 0.733901E+09 | 0.200599E+10 | 0.607339E+09 | 0.139865E+10 | 0.00 | 0.00 |
June | 0.300660E+10 | 0.416155E+09 | 0.213108E+10 | 0.836837E+09 | 0.129424E+10 | 0.00 | 0.00 |
July | 0.291172E+10 | 0.398805E+09 | 0.203836E+10 | 0.673288E+09 | 0.136507E+10 | 0.00 | 0.00 |
August | 0.324126E+10 | 0.471114E+09 | 0.228585E+10 | 0.109167E+10 | 0.119418E+10 | 0.00 | 0.00 |
September | 0.311616E+10 | 0.684233E+09 | 0.231665E+10 | 0.124541E+10 | 0.107124E+10 | 0.00 | 0.00 |
October | 0.285868E+10 | 0.143909E+10 | 0.240808E+10 | 0.158140E+10 | 0.826679E+09 | 0.00 | 0.00 |
November | 0.283033E+10 | 0.160777E+10 | 0.249483E+10 | 0.185028E+10 | 0.644548E+09 | 0.00 | 0.00 |
December | 0.252318E+10 | 0.202978E+10 | 0.238307E+10 | 0.180044E+10 | 0.582628E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.330326E+11 | 0.137868E+11 | 0.274018E+11 | 0.158413E+11 | 0.115606E+11 | 0.00 | 0.00 |
Minimum of Months | 0.189562E+10 | 0.398805E+09 | 0.182962E+10 | 0.607339E+09 | 0.582628E+09 | 0.00 | 0.00 |
Maximum of Months | 0.324126E+10 | 0.202978E+10 | 0.263976E+10 | 0.203901E+10 | 0.139865E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.146899E+11 | -0.139023E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -787593620.5 | 58.99 | 0.00 | 0.00 |
February | 0.134284E+11 | -0.127130E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -715347884.6 | 58.99 | 0.00 | 0.00 |
March | 0.146658E+11 | -0.138960E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -769800405.2 | 58.99 | 0.00 | 0.00 |
April | 0.136239E+11 | -0.128844E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -739557461.9 | 58.99 | 0.00 | 0.00 |
May | 0.132952E+11 | -0.125886E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -706591625.9 | 58.99 | 0.00 | 0.00 |
June | 0.121153E+11 | -0.114722E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -643117605.8 | 58.99 | 0.00 | 0.00 |
July | 0.119481E+11 | -0.112854E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -662672342.7 | 58.99 | 0.00 | 0.00 |
August | 0.117964E+11 | -0.111328E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -663617117.9 | 58.98 | 0.00 | 0.00 |
September | 0.116103E+11 | -0.109559E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -654383100.8 | 58.99 | 0.00 | 0.00 |
October | 0.126297E+11 | -0.118833E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -746437653.6 | 58.99 | 0.00 | 0.00 |
November | 0.129844E+11 | -0.122320E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -752367800.7 | 58.99 | 0.00 | 0.00 |
December | 0.141390E+11 | -0.133524E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -786617512.6 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.156926E+12 | -0.148298E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.862810E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.116103E+11 | -0.139023E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -787593620.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.146899E+11 | -0.109559E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -643117605.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.28 | 0.24 | 01-JAN-07:49 | 7891.31 | 33.05 | 198.83 | 262.00 | 8092.99 | 33.55 | 200.00 | 263.33 |
February | 245.50 | 0.25 | 0.24 | 01-FEB-10:39 | 2935.67 | 25.86 | 109.50 | 265.50 | 3655.34 | 26.68 | 116.83 | 264.67 |
March | 296.17 | 0.25 | 0.24 | 01-MAR-06:49 | 1947.40 | 21.17 | 68.33 | 335.00 | 1957.19 | 21.31 | 76.67 | 332.50 |
April | 296.67 | 0.26 | 0.24 | 03-APR-09:39 | 2074.34 | 18.98 | 25.67 | 354.50 | 2457.91 | 18.90 | 22.33 | 355.67 |
May | 415.33 | 0.26 | 0.24 | 01-MAY-05:40 | 1480.20 | 19.03 | 17.50 | 406.50 | 1637.37 | 19.01 | 24.33 | 408.17 |
June | 421.50 | 0.26 | 0.24 | 01-JUN-05:10 | 1539.93 | 18.52 | 2.33 | 413.00 | 1711.81 | 18.48 | 2.50 | 413.17 |
July | 430.33 | 0.26 | 0.24 | 01-JUL-05:19 | 1477.91 | 18.71 | 9.00 | 413.67 | 1658.53 | 18.64 | 14.00 | 416.17 |
August | 394.50 | 0.27 | 0.24 | 01-AUG-05:49 | 2091.32 | 18.47 | 17.83 | 383.50 | 2465.46 | 18.38 | 12.33 | 380.83 |
September | 354.00 | 0.26 | 0.24 | 01-SEP-05:49 | 1800.06 | 19.08 | 40.50 | 347.00 | 1971.84 | 19.05 | 52.67 | 345.17 |
October | 262.67 | 0.25 | 0.24 | 01-OCT-06:19 | 2798.22 | 22.38 | 92.83 | 305.33 | 2375.80 | 22.04 | 71.00 | 303.67 |
November | 257.67 | 0.27 | 0.24 | 01-NOV-08:39 | 10321.26 | 36.74 | 224.33 | 262.67 | 9302.20 | 34.01 | 185.67 | 262.83 |
December | 251.17 | 0.27 | 0.24 | 01-DEC-07:49 | 7639.46 | 34.44 | 191.00 | 253.67 | 7536.20 | 34.78 | 193.17 | 253.67 |
Annual Sum or Average | 3902.00 | 0.26 | 3272.71 | 22.86 | 997.67 | 4002.33 | 3368.44 | 22.74 | 971.50 | 3999.83 | ||
Minimum of Months | 245.50 | 0.25 | 0.24 | 1477.91 | 18.47 | 2.33 | 253.67 | 1637.37 | 18.38 | 2.50 | 253.67 | |
Maximum of Months | 430.33 | 0.28 | 0.24 | 10321.26 | 36.74 | 224.33 | 413.67 | 9302.20 | 34.78 | 200.00 | 416.17 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.190183E+11 | 53764.72 | 02-JAN-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.205573E+11 | 53764.72 | 01-FEB-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142895E+11 | 53764.72 | 02-MAR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113220E+11 | 53764.72 | 03-APR-02:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181602E+10 | 23048.01 | 03-MAY-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16026015.97 | 5097.01 | 14-JUN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4525877.62 | 6589.64 | 17-JUL-02:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1862854.18 | 7617.80 | 01-AUG-02:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.579184E+09 | 11151.39 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.924304E+10 | 53764.72 | 30-OCT-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145019E+11 | 53764.72 | 02-NOV-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233863E+11 | 53764.72 | 07-DEC-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114736E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1862854.18 | 5097.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.233863E+11 | 53764.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167265E+11 | 39654.17 | 14-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171859E+11 | 49982.50 | 12-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104493E+11 | 35283.34 | 05-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.727404E+10 | 33903.47 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.459055E+09 | 13071.28 | 03-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.216226E+09 | 12389.51 | 22-SEP-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.638901E+10 | 39152.10 | 30-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111075E+11 | 37476.30 | 02-NOV-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219718E+11 | 55784.77 | 23-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.917794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.219718E+11 | 55784.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 45171561.26 | 45171561.26 | 4160.69 | 20-JAN-13:55 | 4160.69 | 0.00 |
February | 0.00 | 0.00 | 11118980.19 | 11118980.19 | 2005.68 | 18-FEB-14:00 | 2005.68 | 0.00 |
March | 0.00 | 0.00 | 0.320259E+09 | 0.320259E+09 | 8813.87 | 14-MAR-13:00 | 8813.87 | 0.00 |
April | 0.00 | 0.00 | 0.185217E+09 | 0.185164E+09 | 5399.52 | 20-APR-13:00 | 5399.52 | 0.00 |
May | 0.00 | 0.00 | 0.246578E+10 | 0.241857E+10 | 12762.30 | 17-MAY-12:55 | 12762.30 | 0.00 |
June | 0.00 | 0.00 | 0.141054E+11 | 0.132361E+11 | 33291.36 | 14-JUN-03:08 | 33291.36 | 0.00 |
July | 0.00 | 0.00 | 0.152045E+11 | 0.139927E+11 | 33291.36 | 17-JUL-02:15 | 33291.36 | 0.00 |
August | 0.00 | 0.00 | 0.139369E+11 | 0.129965E+11 | 34360.44 | 04-AUG-02:62 | 13609.93 | 0.00 |
September | 0.00 | 0.00 | 0.908752E+10 | 0.887976E+10 | 33291.36 | 06-SEP-02:61 | 23890.86 | 0.00 |
October | 0.00 | 0.00 | 0.926381E+09 | 0.926280E+09 | 11828.21 | 11-OCT-13:00 | 11828.21 | 0.00 |
November | 0.00 | 0.00 | 0.220215E+09 | 0.220215E+09 | 6635.08 | 07-NOV-14:00 | 6635.08 | 0.00 |
December | 0.00 | 0.00 | 98211701.12 | 98211701.12 | 5228.14 | 01-DEC-14:00 | 5228.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.566066E+11 | 0.533301E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 11118980.19 | 11118980.19 | 2005.68 | 2005.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.152045E+11 | 0.139927E+11 | 34360.44 | 33291.36 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 65492289.33 | 64894736.91 | 4214.33 | 20-JAN-14:00 | 4214.33 | 0.00 |
February | 0.00 | 0.00 | 24826477.52 | 24642861.50 | 2872.98 | 18-FEB-14:00 | 2872.98 | 0.00 |
March | 0.00 | 0.00 | 0.416068E+09 | 0.414569E+09 | 27234.47 | 15-MAR-02:61 | 26351.45 | 0.00 |
April | 0.00 | 0.00 | 0.379416E+09 | 0.371546E+09 | 20724.97 | 21-APR-02:61 | 13192.40 | 0.00 |
May | 0.00 | 0.00 | 0.372416E+10 | 0.353860E+10 | 27234.47 | 07-MAY-03:22 | 20358.26 | 0.00 |
June | 0.00 | 0.00 | 0.180579E+11 | 0.166780E+11 | 27234.47 | 05-JUN-02:61 | 18892.84 | 0.00 |
July | 0.00 | 0.00 | 0.198779E+11 | 0.179090E+11 | 27234.47 | 11-JUL-03:16 | 22603.13 | 0.00 |
August | 0.00 | 0.00 | 0.175112E+11 | 0.160780E+11 | 27671.45 | 04-AUG-02:11 | 9092.00 | 0.00 |
September | 0.00 | 0.00 | 0.114029E+11 | 0.109590E+11 | 27234.47 | 01-SEP-02:51 | 12264.88 | 0.00 |
October | 0.00 | 0.00 | 0.118533E+10 | 0.116747E+10 | 27234.47 | 06-OCT-02:61 | 21720.14 | 0.00 |
November | 0.00 | 0.00 | 0.291822E+09 | 0.289265E+09 | 27234.47 | 07-NOV-04:21 | 23985.32 | 0.00 |
December | 0.00 | 0.00 | 0.135833E+09 | 0.135440E+09 | 5004.45 | 02-DEC-15:00 | 5004.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.730729E+11 | 0.676304E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 24826477.52 | 24642861.50 | 2872.98 | 2872.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.198779E+11 | 0.179090E+11 | 27671.45 | 26351.45 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5483.44 | 20523.17 | 31-JAN-13:44 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 5548.24 | 20577.95 | 14-FEB-13:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5482.92 | 20496.15 | 01-MAR-13:33 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5262.72 | 19904.77 | 01-APR-12:40 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 4992.33 | 18933.93 | 01-MAY-12:25 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 4719.02 | 17791.67 | 01-JUN-12:30 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 4503.81 | 16849.28 | 01-JUL-12:35 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4449.69 | 16327.80 | 31-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 4517.84 | 16895.01 | 30-SEP-12:45 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4728.16 | 17888.46 | 31-OCT-13:00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 5011.55 | 18995.80 | 30-NOV-13:50 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5276.57 | 19976.67 | 31-DEC-13:37 |
Annual Sum or Average | 0.00 | 4994.82 | ||||
Minimum of Months | 0.00 | 0.00 | 4449.69 | 16327.80 | ||
Maximum of Months | 0.00 | 0.00 | 5548.24 | 20577.95 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.113067E+10 | 0.27 | 503.64 | 01-JAN-00:01 | 0.33 |
February | 0.102022E+10 | 0.27 | 503.64 | 01-FEB-00:01 | 0.33 |
March | 0.114587E+10 | 0.28 | 503.64 | 01-MAR-00:01 | 0.33 |
April | 0.111553E+10 | 0.28 | 503.64 | 01-APR-02:55 | 0.32 |
May | 0.119942E+10 | 0.29 | 503.64 | 01-MAY-04:01 | 0.32 |
June | 0.121200E+10 | 0.30 | 503.64 | 01-JUN-02:61 | 0.32 |
July | 0.126399E+10 | 0.30 | 503.64 | 01-JUL-00:15 | 0.33 |
August | 0.126679E+10 | 0.30 | 503.64 | 01-AUG-00:55 | 0.32 |
September | 0.120309E+10 | 0.30 | 503.64 | 01-SEP-00:19 | 0.33 |
October | 0.117666E+10 | 0.28 | 503.64 | 01-OCT-02:61 | 0.32 |
November | 0.110405E+10 | 0.28 | 503.64 | 01-NOV-04:01 | 0.33 |
December | 0.113288E+10 | 0.27 | 503.64 | 01-DEC-00:01 | 0.33 |
Annual Sum or Average | 0.139712E+11 | 0.29 | |||
Minimum of Months | 0.102022E+10 | 0.27 | 503.64 | 0.32 | |
Maximum of Months | 0.126679E+10 | 0.30 | 503.64 | 0.33 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.243509E+10 | 0.65 | 2181.35 | 02-JAN-03:02 | 1.08 |
February | 0.231103E+10 | 0.67 | 2181.35 | 01-FEB-03:02 | 1.08 |
March | 0.232426E+10 | 0.64 | 2181.35 | 02-MAR-03:02 | 1.08 |
April | 0.217653E+10 | 0.62 | 2181.35 | 03-APR-02:08 | 1.08 |
May | 0.199252E+10 | 0.56 | 1251.15 | 12-MAY-05:20 | 0.82 |
June | 0.191532E+10 | 0.57 | 1465.61 | 26-JUN-17:17 | 0.89 |
July | 0.197949E+10 | 0.57 | 1408.47 | 25-JUL-02:61 | 0.87 |
August | 0.198352E+10 | 0.58 | 1440.51 | 03-AUG-02:61 | 0.88 |
September | 0.191718E+10 | 0.57 | 1343.00 | 03-SEP-02:61 | 0.85 |
October | 0.218407E+10 | 0.59 | 2181.35 | 30-OCT-02:70 | 1.09 |
November | 0.225877E+10 | 0.62 | 2181.35 | 02-NOV-02:70 | 1.09 |
December | 0.255601E+10 | 0.66 | 2181.35 | 07-DEC-03:03 | 1.08 |
Annual Sum or Average | 0.260338E+11 | 0.61 | |||
Minimum of Months | 0.191532E+10 | 0.56 | 1251.15 | 0.82 | |
Maximum of Months | 0.255601E+10 | 0.67 | 2181.35 | 1.09 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.155437E+10 | 0.62 | 1111.82 | 14-JAN-05:03 | 0.98 |
February | 0.143058E+10 | 0.63 | 1245.33 | 12-FEB-05:02 | 1.03 |
March | 0.147586E+10 | 0.61 | 1055.32 | 05-MAR-05:03 | 0.95 |
April | 0.139184E+10 | 0.60 | 1068.89 | 21-APR-02:61 | 0.95 |
May | 0.135914E+10 | 0.60 | 1498.07 | 17-MAY-02:61 | 1.12 |
June | 0.148760E+10 | 0.65 | 1498.07 | 01-JUN-02:61 | 1.11 |
July | 0.154770E+10 | 0.66 | 1498.07 | 01-JUL-02:11 | 1.12 |
August | 0.150588E+10 | 0.65 | 1498.07 | 01-AUG-02:11 | 1.12 |
September | 0.136818E+10 | 0.63 | 1498.07 | 01-SEP-02:11 | 1.11 |
October | 0.142885E+10 | 0.61 | 1352.60 | 11-OCT-02:61 | 1.07 |
November | 0.144005E+10 | 0.61 | 1083.67 | 02-NOV-04:03 | 0.96 |
December | 0.162224E+10 | 0.64 | 1320.33 | 23-DEC-05:02 | 1.06 |
Annual Sum or Average | 0.176123E+11 | 0.63 | |||
Minimum of Months | 0.135914E+10 | 0.60 | 1055.32 | 0.95 | |
Maximum of Months | 0.162224E+10 | 0.66 | 1498.07 | 1.12 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 49.91 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 51.50 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 51.54 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 51.40 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 50.41 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 52.15 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:02 | 0.00 | 0.00 | 52.94 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:05 | 0.00 | 0.00 | 52.72 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 53.23 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 51.69 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:05 | 0.00 | 0.00 | 52.36 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 51.98 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 49.91 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 53.23 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 37.67 | 37.67 | 5483.44 | 20523.17 | 31-JAN-13:44 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 51.10 | 51.10 | 5548.24 | 20577.95 | 14-FEB-13:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 51.10 | 51.10 | 5482.92 | 20496.15 | 01-MAR-13:33 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.69 | 51.69 | 5262.72 | 19904.77 | 01-APR-12:40 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 38.67 | 38.67 | 4992.33 | 18933.93 | 01-MAY-12:25 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 52.03 | 52.03 | 4719.02 | 17791.67 | 01-JUN-12:30 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 53.03 | 53.03 | 4503.81 | 16849.28 | 01-JUL-12:35 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.68 | 52.68 | 4449.69 | 16327.80 | 31-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 53.06 | 53.06 | 4517.84 | 16895.01 | 30-SEP-12:45 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 40.97 | 40.97 | 4728.16 | 17888.46 | 31-OCT-13:00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.49 | 52.49 | 5011.55 | 18995.80 | 30-NOV-13:50 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 52.28 | 52.28 | 5276.57 | 19976.67 | 31-DEC-13:37 |
Annual Sum or Average | 0.00 | 4994.82 | ||||||
Minimum of Months | 0.00 | 0.00 | 37.67 | 37.67 | 4449.69 | 16327.80 | ||
Maximum of Months | 0.00 | 0.00 | 53.06 | 53.06 | 5548.24 | 20577.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.244847E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.231440E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.241618E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.223167E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.267936E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.566703E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.599656E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.565544E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.433803E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.244318E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.232300E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.258499E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.410983E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.223167E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.599656E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.157365E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.143796E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159377E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.150157E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.236653E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.612280E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.661340E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.596929E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.429268E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.175574E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.152364E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.166180E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.364128E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143796E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.661340E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.243509E+10 | 45171561.26 | 0.190183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231103E+10 | 11118980.19 | 0.205573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232426E+10 | 0.320259E+09 | 0.142895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217653E+10 | 0.185217E+09 | 0.113220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.199252E+10 | 0.246578E+10 | 0.181602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.191532E+10 | 0.140814E+11 | 16026015.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.197949E+10 | 0.151751E+11 | 4525877.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198352E+10 | 0.139073E+11 | 1862854.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191718E+10 | 0.906833E+10 | 0.579184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.218407E+10 | 0.926381E+09 | 0.924304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.225877E+10 | 0.220215E+09 | 0.145019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.255601E+10 | 98211701.12 | 0.233863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260338E+11 | 0.565046E+11 | 0.114736E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.191532E+10 | 11118980.19 | 1862854.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.255601E+10 | 0.151751E+11 | 0.233863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.155437E+10 | 65492289.33 | 0.167265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143058E+10 | 24826477.52 | 0.171859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147586E+10 | 0.415451E+09 | 0.104493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139184E+10 | 0.379416E+09 | 0.727404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135914E+10 | 0.372100E+10 | 0.459055E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148760E+10 | 0.180044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154770E+10 | 0.198061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150588E+10 | 0.174577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136818E+10 | 0.113567E+11 | 0.216226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142885E+10 | 0.118341E+10 | 0.638901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144005E+10 | 0.291028E+09 | 0.111075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162224E+10 | 0.135833E+09 | 0.219718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176123E+11 | 0.728414E+11 | 0.917794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135914E+10 | 24826477.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162224E+10 | 0.198061E+11 | 0.219718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.243509E+10 | 0.00 | 0.00 | 0.00 | 13377057.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231103E+10 | 0.00 | 0.00 | 0.00 | 3368913.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232426E+10 | 0.00 | 0.00 | 0.00 | 91925526.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217653E+10 | 0.00 | 0.00 | 0.00 | 55144773.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.199252E+10 | 0.00 | 0.00 | 0.00 | 0.686833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.191532E+10 | 0.00 | 0.00 | 0.00 | 0.375171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.197949E+10 | 0.00 | 0.00 | 0.00 | 0.401708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198352E+10 | 0.00 | 0.00 | 0.00 | 0.367191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191718E+10 | 0.00 | 0.00 | 0.00 | 0.242085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.218407E+10 | 0.00 | 0.00 | 0.00 | 0.259107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.225877E+10 | 0.00 | 0.00 | 0.00 | 64225957.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.255601E+10 | 0.00 | 0.00 | 0.00 | 28978041.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260338E+11 | 0.00 | 0.00 | 0.00 | 0.150645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.191532E+10 | 0.00 | 0.00 | 0.00 | 3368913.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.255601E+10 | 0.00 | 0.00 | 0.00 | 0.401708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.155437E+10 | 0.00 | 0.00 | 0.00 | 19277836.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143058E+10 | 0.00 | 0.00 | 0.00 | 7384511.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147586E+10 | 0.00 | 0.00 | 0.00 | 0.117911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139184E+10 | 0.00 | 0.00 | 0.00 | 0.109722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135914E+10 | 0.00 | 0.00 | 0.00 | 0.100740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148760E+10 | 0.00 | 0.00 | 0.00 | 0.463521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154770E+10 | 0.00 | 0.00 | 0.00 | 0.506569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150588E+10 | 0.00 | 0.00 | 0.00 | 0.446340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136818E+10 | 0.00 | 0.00 | 0.00 | 0.292450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142885E+10 | 0.00 | 0.00 | 0.00 | 0.326886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144005E+10 | 0.00 | 0.00 | 0.00 | 83597011.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162224E+10 | 0.00 | 0.00 | 0.00 | 39553157.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176123E+11 | 0.00 | 0.00 | 0.00 | 0.188005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135914E+10 | 0.00 | 0.00 | 0.00 | 7384511.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162224E+10 | 0.00 | 0.00 | 0.00 | 0.506569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.644458E+10 | 0.00 | 0.00 | 1432709.47 | 0.00 | 0.151314E+11 | 0.669223E+09 | 0.00 | 3.72 |
February | 0.529843E+10 | 0.00 | 0.00 | 895030.73 | 0.00 | 0.169422E+11 | 0.402091E+09 | 0.00 | 3.68 |
March | 0.594009E+10 | 0.00 | 0.00 | 6025118.44 | 0.00 | 0.118880E+11 | 0.170953E+10 | 0.00 | 3.96 |
April | 0.603765E+10 | 0.00 | 0.00 | 5319088.98 | 0.00 | 0.936106E+10 | 0.180193E+10 | 0.00 | 3.98 |
May | 0.646872E+10 | 10542188.59 | 0.00 | 18251881.23 | 0.00 | 0.672133E+09 | 0.418668E+10 | 0.00 | 4.66 |
June | 0.104436E+10 | 0.905177E+09 | 12331.49 | 35291297.50 | 0.00 | 93730.18 | 0.418233E+10 | 19338.56 | 5.06 |
July | 0.772029E+09 | 0.103723E+10 | 0.00 | 33089574.98 | 0.00 | 349479.50 | 0.418261E+10 | 0.00 | 5.12 |
August | 0.941200E+09 | 0.694202E+09 | 0.00 | 39580152.86 | 0.00 | 919425.29 | 0.512976E+10 | 0.00 | 5.27 |
September | 0.236629E+10 | 0.191673E+09 | 0.00 | 41413132.63 | 0.00 | 0.340803E+09 | 0.575497E+10 | 0.00 | 5.36 |
October | 0.757515E+10 | 0.00 | 0.00 | 12302847.23 | 0.00 | 0.658026E+10 | 0.312617E+10 | 0.00 | 4.20 |
November | 0.736967E+10 | 0.00 | 0.00 | 3573309.87 | 0.00 | 0.113494E+11 | 0.111260E+10 | 0.00 | 3.83 |
December | 0.602089E+10 | 0.00 | 0.00 | 1835245.28 | 0.00 | 0.181355E+11 | 0.758334E+09 | 0.00 | 3.74 |
Annual Sum or Average | 0.562791E+11 | 0.283882E+10 | 12331.49 | 0.199009E+09 | 0.00 | 0.904021E+11 | 0.330162E+11 | 19338.56 | 4.39 |
Minimum of Months | 0.772029E+09 | 0.00 | 0.00 | 895030.73 | 0.00 | 93730.18 | 0.402091E+09 | 0.00 | 3.68 |
Maximum of Months | 0.757515E+10 | 0.103723E+10 | 12331.49 | 41413132.63 | 0.00 | 0.181355E+11 | 0.575497E+10 | 19338.56 | 5.36 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.471916E+11 | 0.00 | 0.00 | 1984260.22 | 0.00 | 11970196.38 | 0.168469E+10 | 0.00 | 8.04 |
February | 0.448685E+11 | 0.00 | 0.00 | 1215366.81 | 424329.53 | 25852096.78 | 0.106023E+10 | 0.00 | 8.06 |
March | 0.370211E+11 | 0.00 | 0.00 | 9708579.02 | 0.00 | 10247167.75 | 0.507523E+10 | 0.00 | 7.91 |
April | 0.328486E+11 | 0.00 | 0.00 | 10758859.40 | 0.00 | 9023374.84 | 0.543322E+10 | 0.00 | 7.83 |
May | 0.148851E+11 | 0.00 | 0.00 | 40013514.55 | 0.00 | 0.00 | 0.147046E+11 | 0.00 | 7.76 |
June | 0.222722E+10 | 0.637828E+09 | 0.00 | 88975785.44 | 0.00 | 0.00 | 0.135710E+11 | 0.00 | 8.25 |
July | 0.162643E+10 | 0.557009E+09 | 0.00 | 91145819.53 | 0.00 | 0.00 | 0.131131E+11 | 0.00 | 8.29 |
August | 0.181773E+10 | 0.456231E+09 | 0.00 | 0.101768E+09 | 0.00 | 0.00 | 0.157366E+11 | 0.00 | 8.23 |
September | 0.538003E+10 | 96821833.87 | 0.00 | 78388788.38 | 0.00 | 0.00 | 0.171715E+11 | 0.00 | 7.97 |
October | 0.304313E+11 | 0.00 | 0.00 | 19412337.86 | 0.00 | 2466895.58 | 0.874249E+10 | 0.00 | 7.82 |
November | 0.396990E+11 | 0.00 | 0.00 | 5347556.22 | 0.00 | 14743019.11 | 0.339901E+10 | 0.00 | 7.91 |
December | 0.525158E+11 | 0.00 | 0.00 | 2496523.76 | 0.00 | 29568296.18 | 0.176946E+10 | 0.00 | 8.12 |
Annual Sum or Average | 0.310512E+12 | 0.174789E+10 | 0.00 | 0.451216E+09 | 424329.53 | 0.103871E+09 | 0.101461E+12 | 0.00 | 8.02 |
Minimum of Months | 0.162643E+10 | 0.00 | 0.00 | 1215366.81 | 0.00 | 0.00 | 0.106023E+10 | 0.00 | 7.76 |
Maximum of Months | 0.525158E+11 | 0.637828E+09 | 0.00 | 0.101768E+09 | 424329.53 | 29568296.18 | 0.171715E+11 | 0.00 | 8.29 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:05
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.278437E+11 | 0.138719E+11 | 0.103398E+12 | 0.202558E+09 | 0.250683E+11 |
February | 0.364876E+11 | 0.136070E+11 | 0.968968E+11 | 0.109121E+09 | 0.243739E+11 |
March | 0.479903E+11 | 0.124065E+11 | 0.911438E+11 | 0.611183E+09 | 0.247953E+11 |
April | 0.516895E+11 | 0.112540E+11 | 0.843303E+11 | 0.668835E+09 | 0.229775E+11 |
May | 0.636818E+11 | 0.744279E+10 | 0.667856E+11 | 0.164041E+10 | 0.307536E+11 |
June | 0.698172E+11 | 0.267573E+10 | 0.348677E+11 | 0.163642E+10 | 0.654174E+11 |
July | 0.646811E+11 | 0.231280E+10 | 0.326037E+11 | 0.166143E+10 | 0.685860E+11 |
August | 0.633884E+11 | 0.295842E+10 | 0.389362E+11 | 0.200513E+10 | 0.653178E+11 |
September | 0.463097E+11 | 0.441322E+10 | 0.508384E+11 | 0.234598E+10 | 0.486248E+11 |
October | 0.365763E+11 | 0.107060E+11 | 0.871642E+11 | 0.113621E+10 | 0.248311E+11 |
November | 0.303076E+11 | 0.123891E+11 | 0.929771E+11 | 0.400628E+09 | 0.228031E+11 |
December | 0.213730E+11 | 0.156927E+11 | 0.111981E+12 | 0.277069E+09 | 0.270077E+11 |
Annual Sum or Average | 0.560147E+12 | 0.109730E+12 | 0.891923E+12 | 0.126950E+11 | 0.450556E+12 |
Minimum of Months | 0.213730E+11 | 0.231280E+10 | 0.326037E+11 | 0.109121E+09 | 0.228031E+11 |
Maximum of Months | 0.698172E+11 | 0.156927E+11 | 0.111981E+12 | 0.234598E+10 | 0.685860E+11 |