Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2023-10-16 08:26:45
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2520.96 | 1098.94 | 1098.94 |
Net Site Energy | 2520.96 | 1098.94 | 1098.94 |
Total Source Energy | 7805.93 | 3402.77 | 3402.77 |
Net Source Energy | 7805.93 | 3402.77 | 3402.77 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1175.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 491.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 125.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 447.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 85.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2435.53 | 85.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 1175.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 491.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 125.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 447.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 85.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1175.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 491.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 125.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 447.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 85.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 269.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 707.48 | 37.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1061.70 | 37.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 269.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 707.48 | 37.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1061.70 | 37.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2435.528 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2435.528 | 100.00 |
Total On-Site and Utility Electric Sources | 2435.528 | 100.00 |
Total Electricity End Uses | 2435.528 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4911.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1 COOLING COIL | PSZ-AC:2 COOLING COIL | PSZ-AC:3 COOLING COIL | PSZ-AC:4 COOLING COIL |WindowReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | FRONT_ENTRY UNIT HEATER HEATING COIL | PSZ-AC:1 COOLING COIL | PSZ-AC:2 COOLING COIL | PSZ-AC:3 COOLING COIL | PSZ-AC:4 COOLING COIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATER FAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.95 | 0.00 | 0.00 | 83.95 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.95 | 0.00 | 0.00 | 83.95 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 19.36 |
Skylight-Roof Ratio [%] | 0.84 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 9.0271 | 46.45 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 18.2986 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.06 | 38.06 | 18.2986 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.06 | 38.06 | 18.2986 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 10.9792 | 6.19 | 0.0000 |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.95 | 83.95 | 16.7250 | 7.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.95 | 83.95 | 16.7250 | 7.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BACK_SPACE | 379.89 | Yes | Yes | 1.00 | BACK_SPACE | GENERAL | BACK_SPACE | 9.0271 | 46.45 | 8.0700 | |
CORE_RETAIL | 1600.48 | Yes | Yes | 1.00 | CORE_RETAIL | GENERAL | CORE_RETAIL | 18.2986 | 6.19 | 3.2300 | |
POINT_OF_SALE | 150.81 | Yes | Yes | 1.00 | POINT_OF_SALE | GENERAL | POINT_OF_SALE | 18.2986 | 6.19 | 21.5200 | |
FRONT_RETAIL | 150.81 | Yes | Yes | 1.00 | FRONT_RETAIL | GENERAL | FRONT_RETAIL | 18.2986 | 6.19 | 3.2300 | |
FRONT_ENTRY | 12.00 | Yes | Yes | 1.00 | FRONT_ENTRY | GENERAL | FRONT_ENTRY | 10.9792 | 6.19 | 0.0000 | |
Total | 2293.99 | 16.7250 | 3.62 | 5.2170 | |||||||
Conditioned Total | 2293.99 | 16.7250 | 3.62 | 5.2170 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2293.99 | 2293.99 | 0.00 | 0.00 | 16.7250 | 7.23 | 5.2170 |
Total | 2293.99 | 2293.99 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 13-JUN-14:00 | 06-JAN-12:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 86499.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 34530.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 21358.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4805.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 153159.31 | 4805.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 86499.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 34530.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 21358.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4805.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3722.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1556.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 398.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1417.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 92.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7713.32 | 92.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 678.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 173.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 618.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 40.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3362.40 | 40.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 678.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 173.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 618.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 40.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3362.40 | 40.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 2.44 |
CORE_RETAIL DIRECT AIR | 9.24 |
POINT_OF_SALE DIRECT AIR | 1.41 |
FRONT_RETAIL DIRECT AIR | 1.24 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 0.102068 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER FAN | 0.102068 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | 2365.02 |
PSZ-AC:1 HEATING COIL | 56711.74 |
PSZ-AC:2 HEATING COIL | 213382.56 |
PSZ-AC:3 HEATING COIL | 32879.31 |
PSZ-AC:4 HEATING COIL | 28800.20 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 2.44 | 2.44 | 2.44 | 2.44 | 2.44 | 2.44 | 1.00 | 1.00 | 2.44 |
PSZ-AC:2 | 9.24 | 9.24 | 9.24 | 9.24 | 9.24 | 9.24 | 1.00 | 1.00 | 9.24 |
PSZ-AC:3 | 1.41 | 1.41 | 1.41 | 1.41 | 1.41 | 1.41 | 1.00 | 1.00 | 1.41 |
PSZ-AC:4 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.00 | 1.00 | 1.24 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 2.44 | 0.231581 |
PSZ-AC:2_OA_CONTROLLER | 9.24 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.41 | 0.178122 |
PSZ-AC:4_OA_CONTROLLER | 1.24 | 0.178122 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.44 | 2675.91 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 9.24 | 15666.01 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.41 | 1607.01 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.24 | 1409.86 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 2.44 | 2.44 | 2.44 | 2.44 | 49831.09 | 56711.74 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 9.24 | 9.24 | 9.24 | 9.24 | 222534.99 | 213382.56 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.41 | 1.41 | 1.41 | 1.41 | 30711.53 | 32879.31 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.24 | 1.24 | 1.24 | 1.24 | 27866.92 | 28800.20 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC:1 COOLING COIL | 2.44 | 1.22 | 2.44 | 49831.09 | 24550.94 | 49831.09 | 0.768600 | 0.768600 |
PSZ-AC:2 COOLING COIL | 9.24 | 4.62 | 9.24 | 222534.99 | 112309.77 | 222534.99 | 0.710670 | 0.710670 |
PSZ-AC:3 COOLING COIL | 1.41 | 0.704762 | 1.41 | 30711.53 | 15177.85 | 30711.53 | 0.744320 | 0.744320 |
PSZ-AC:4 COOLING COIL | 1.24 | 0.618299 | 1.24 | 27866.92 | 13778.96 | 27866.92 | 0.732070 | 0.732070 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 65 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 6.69 | 10 | 14 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.74 | 38.06 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.74 | 38.06 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 8.2 | 46.452 | 2.153E-002 | 9.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.097 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 18.299 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 21.529 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 18.299 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 39.819 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 18.299 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 21.529 | No |
5 | FRONT_ENTRY | 12.00 | 1.9 | 6.192 | 0.162 | 10.979 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.979 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 8.2 | 8.2 | 2.153E-002 | 46.452 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 1.9 | 1.9 | 0.162 | 6.192 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | LTG_SCH_BACK | BACK_SPACE | 379.89 | 8.2 | 3429.297 | 9.027 | 419.326 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3429.297 |
2 | CORE_RETAIL_LIGHTS | LTG_SCH_CORE | CORE_RETAIL | 1600.48 | 258.4 | 29286.644 | 18.299 | 113.323 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29286.644 |
3 | POINT_OF_SALE_LIGHTS | LTG_SCH_SALE | POINT_OF_SALE | 150.81 | 24.4 | 2759.616 | 18.299 | 113.323 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2759.616 |
4 | FRONT_RETAIL_LIGHTS | LTG_SCH_FRONT | FRONT_RETAIL | 150.81 | 24.4 | 2759.616 | 18.299 | 113.323 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2759.616 |
5 | FRONT_ENTRY_LIGHTS | LTG_SCH_ENTRY | FRONT_ENTRY | 12.00 | 1.9 | 131.750 | 10.979 | 67.983 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 131.750 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 8.2 | 3065.712 | 8.070 | 374.868 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
21 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
22 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
23 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
24 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
25 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
26 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
27 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
28 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
29 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
30 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
31 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
32 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
33 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 36 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
2 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 37 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19502 | 0.25365 | 0.25365 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.1514 | 11722.8 | 0.727 | 0.1878 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2281.32 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2281.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
31 | SKYLIGHTS_R2C4 | 0 | 2281.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
32 | SKYLIGHTS_R2C1 | 0 | 2281.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
33 | SKYLIGHTS_R2C2 | 0 | 2281.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
34 | SKYLIGHTS_R2C3 | 0 | 2281.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C3 | 0 | 2281.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C1 | 0 | 2281.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2281.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C2 | 0 | 2281.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
39 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
40 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
42 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
43 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
44 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
45 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
46 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
47 | POINT_OF_SALE_ROOF | 0 | 2281.32 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
48 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
49 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
50 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
52 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
54 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | FRONT_RETAIL_ROOF | 0 | 2281.32 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
58 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
59 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
60 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
62 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
63 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
64 | FRONT_ENTRY_ROOF | 0 | 2281.32 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
65 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | CurtainWall | 5.849 | 0.276 | 0.167 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 8.2 | 0.427 | 1.123E-003 | 5.097E-004 | 0.663 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.366 | 2.286E-004 | 1.858E-004 | 0.135 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.195 | 1.290E-003 | 5.713E-004 | 0.761 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.195 | 1.290E-003 | 5.713E-004 | 0.761 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 1.9 | 2.500E-002 | 2.083E-003 | 6.871E-004 | 1.229 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 1.9 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 27751.25367 | 33301.50441 | 2.03738 | 2.44486 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 35.11500 | 1.71580E-002 | 379.89000 | 8.17812 | 0.23158 | 0.00000 |
2 | BACK_SPACE | Heating | 6576.11315 | 7891.33578 | 0.27606 | 0.33127 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 379.89000 | 8.17812 | 0.23158 | 0.00000 |
3 | CORE_RETAIL | Cooling | 104867.77329 | 125841.32794 | 7.69910 | 9.23892 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 34.84583 | 1.71575E-002 | 1600.48290 | 258.43418 | 1.89033 | 0.00000 |
4 | CORE_RETAIL | Heating | 22617.77877 | 27141.33452 | 0.94370 | 1.89033 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 1600.48290 | 258.43418 | 1.89033 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 15996.97001 | 19196.36401 | 1.17460 | 1.40952 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
6 | POINT_OF_SALE | Heating | 3230.85349 | 3877.02419 | 0.13532 | 0.17812 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 14034.38324 | 16841.25989 | 1.03050 | 1.23660 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | 35.20000 | 1.71581E-002 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
8 | FRONT_RETAIL | Heating | 3230.85349 | 3877.02419 | 0.13532 | 0.17812 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41732E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 35.11500 | 1.71580E-002 | 12.00000 | 1.93800 | 1.41732E-002 | 0.00000 |
10 | FRONT_ENTRY | Heating | 1970.90973 | 2365.09167 | 8.50564E-002 | 0.10207 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 20.10000 | 1.47983E-002 | 12.00000 | 1.93800 | 1.41732E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 35950.81 | 2.44486 | 2.44486 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 7876.97 | 0.33127 | 0.33127 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 149149.80 | 9.23892 | 9.23892 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 45496.26 | 1.89033 | 1.89033 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 21336.78 | 1.40952 | 1.40952 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 4287.01 | 0.17812 | 0.17812 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 19018.09 | 1.23660 | 1.23660 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 4287.01 | 0.17812 | 0.17812 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.44486 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.23892 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.40952 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.23660 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.10207 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATER FAN | Design Size Maximum Flow Rate [m3/s] | 0.10207 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER HEATING COIL | Design Size Nominal Capacity [W] | 2365.01808 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.44486 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.44486 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.44486 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.44486 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.44486 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.44486 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 9.23892 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 9.23892 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.23892 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 9.23892 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.23892 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 9.23892 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.40952 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.40952 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.40952 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.40952 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.40952 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.40952 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.23660 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.23660 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.23660 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.23660 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.23660 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.23660 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 2.44486 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 9.23892 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.40952 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.23660 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.44486 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23158 |
46 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.44486 |
47 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2675.91152 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.44486 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.44486 |
50 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.44486 |
51 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.44486 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.44486 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.22243 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.44486 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 49831.09000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 24550.94361 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 49831.09000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76860 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76860 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 49831.09000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 56711.73744 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-AC:1 HEATING COIL | Design Size Nominal Capacity [W] | 56711.73744 |
65 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.23892 |
66 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89033 |
67 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 9.23892 |
68 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 15666.01301 |
69 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 9.23892 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 9.23892 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 9.23892 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 9.23892 |
73 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 9.23892 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 4.61946 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 9.23892 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 222534.99000 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 112309.77185 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 222534.99000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71067 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71067 |
81 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 222534.99000 |
82 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 213382.56451 |
83 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
84 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
85 | Coil:Heating:Fuel | PSZ-AC:2 HEATING COIL | Design Size Nominal Capacity [W] | 213382.56451 |
86 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.40952 |
87 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17812 |
88 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.40952 |
89 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1607.01250 |
90 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.40952 |
91 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.40952 |
92 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.40952 |
93 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.40952 |
94 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.40952 |
95 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.70476 |
96 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.40952 |
97 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30711.53000 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 15177.84877 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30711.53000 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74432 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74432 |
102 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30711.53000 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32879.30722 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
106 | Coil:Heating:Fuel | PSZ-AC:3 HEATING COIL | Design Size Nominal Capacity [W] | 32879.30722 |
107 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.23660 |
108 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17812 |
109 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.23660 |
110 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1409.85740 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.23660 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.23660 |
113 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.23660 |
114 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.23660 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.23660 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61830 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.23660 |
118 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27866.92000 |
119 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 13778.96131 |
120 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 27866.92000 |
121 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73207 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73207 |
123 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27866.92000 |
124 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28800.19925 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
127 | Coil:Heating:Fuel | PSZ-AC:4 HEATING COIL | Design Size Nominal Capacity [W] | 28800.19925 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | 47909.1 | 9.83 | 9.83 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | 215250.6 | 9.85 | 9.85 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | 29602.2 | 10.44 | 10.44 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | 26893.1 | 10.48 | 10.48 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 25 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.233 | 8.233 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.233 | 8.233 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.233 | 8.233 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.233 | 8.233 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.233 | 8.233 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 1581.12 | 1600.48 | 1593.79 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.799 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
32 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.799 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
33 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.799 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
34 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.799 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.799 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.799 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.799 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.799 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
40 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 115.16 | 153.22 | 115.16 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 6.813 | No | 38.06 | 38.06 | 38.06 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 115.16 | 153.22 | 115.16 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 6.813 | No | 38.06 | 38.06 | 38.06 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
56 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
57 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
58 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 6.813 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | |
1 | SKYLIGHT_FRAME_NONRES | Frame | SKYLIGHTS_R2C4 | Window5 Detailed Fenestration | N/A | N/A | 1.58 | 1.58 | * | N/A | N/A | 0.32 | N/A | |||
2 | SKYLIGHT_FRAME_NONRES | Frame | SKYLIGHTS_R2C1 | Window5 Detailed Fenestration | N/A | N/A | 1.58 | 1.58 | * | N/A | N/A | 0.32 | N/A | |||
3 | SKYLIGHT_FRAME_NONRES | Frame | SKYLIGHTS_R2C2 | Window5 Detailed Fenestration | N/A | N/A | 1.58 | 1.58 | * | N/A | N/A | 0.32 | N/A | |||
4 | SKYLIGHT_FRAME_NONRES | Frame | SKYLIGHTS_R2C3 | Window5 Detailed Fenestration | N/A | N/A | 1.58 | 1.58 | * | N/A | N/A | 0.32 | N/A | |||
5 | SKYLIGHT_FRAME_NONRES | Frame | SKYLIGHTS_R1C3 | Window5 Detailed Fenestration | N/A | N/A | 1.58 | 1.58 | * | N/A | N/A | 0.32 | N/A | |||
6 | SKYLIGHT_FRAME_NONRES | Frame | SKYLIGHTS_R1C1 | Window5 Detailed Fenestration | N/A | N/A | 1.58 | 1.58 | * | N/A | N/A | 0.32 | N/A | |||
7 | SKYLIGHT_FRAME_NONRES | Frame | SKYLIGHTS_R1C4 | Window5 Detailed Fenestration | N/A | N/A | 1.58 | 1.58 | * | N/A | N/A | 0.32 | N/A | |||
8 | SKYLIGHT_FRAME_NONRES | Frame | SKYLIGHTS_R1C2 | Window5 Detailed Fenestration | N/A | N/A | 1.58 | 1.58 | * | N/A | N/A | 0.32 | N/A |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 0.1358667126 | 0.2087957740 | Pass | Pass | 0.5484997464 | 1.7811276680 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 0.1039456325 | 0.1562871588 | Pass | Pass | 1.2447723846 | 5.7112373493 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 0.1754676082 | 0.2704262231 | Pass | Pass | 0.3399414593 | 0.7765163487 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 0.1510584637 | 0.2333032951 | Pass | Pass | 0.3453658764 | 0.7967857495 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 7.6828899854E-002 | 9.5590726257E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5591.81 | -87.2 | 0.00 | -1781.5 | 5017.67 | 8740.83 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.227 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.046 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 1600.48 | 1581.12 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 153.22 | 115.16 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.260 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 153.22 | 115.16 | 180.00 | 90.00 | S |
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.260 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.420 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 | |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 12.00 | 12.00 | 180.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 330.83 | 330.83 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_SOUTH_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_SOUTH_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_EAST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
CORE_RETAIL_WALL_SOUTH_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.38 | 24.38 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 330.83 | 330.83 | 0.00 | 90.00 | N |
CORE_RETAIL_WALL_WEST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
POINT_OF_SALE_WALL_EAST_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
POINT_OF_SALE_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 0.00 | 90.00 | N |
POINT_OF_SALE_WALL_EAST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_WEST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
FRONT_RETAIL_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 0.00 | 90.00 | N |
FRONT_RETAIL_WALL_WEST_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
FRONT_ENTRY_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
FRONT_ENTRY_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 24.38 | 24.38 | 0.00 | 90.00 | N |
FRONT_ENTRY_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
BACK_SPACE_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 759.78 | 0.00 | 90.00 | N | ||
CORE_RETAIL_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3200.97 | 0.00 | 90.00 | N | ||
POINT_OF_SALE_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 301.62 | 0.00 | 90.00 | N | ||
FRONT_RETAIL_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 301.62 | 0.00 | 90.00 | N | ||
FRONT_ENTRY_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 24.00 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 0.84 | 1.58 | 0.00 | 2.42 | 2.42 | 5.799 | 0.361 | 0.362 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.167 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 0.84 | 1.58 | 0.00 | 2.42 | 2.42 | 5.799 | 0.361 | 0.362 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.167 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 0.84 | 1.58 | 0.00 | 2.42 | 2.42 | 5.799 | 0.361 | 0.362 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.167 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 0.84 | 1.58 | 0.00 | 2.42 | 2.42 | 5.799 | 0.361 | 0.362 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.167 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 0.84 | 1.58 | 0.00 | 2.42 | 2.42 | 5.799 | 0.361 | 0.362 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.167 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 0.84 | 1.58 | 0.00 | 2.42 | 2.42 | 5.799 | 0.361 | 0.362 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.167 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 0.84 | 1.58 | 0.00 | 2.42 | 2.42 | 5.799 | 0.361 | 0.362 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.167 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 0.84 | 1.58 | 0.00 | 2.42 | 2.42 | 5.799 | 0.361 | 0.362 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.167 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_1.2_SHGC_0.25 | 38.06 | 0.00 | 0.00 | 38.06 | 38.06 | 6.813 | 0.251 | 0.252 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_1.2_SHGC_0.25 | 38.06 | 0.00 | 0.00 | 38.06 | 38.06 | 6.813 | 0.251 | 0.252 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_1.2_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 6.813 | 0.251 | 0.252 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 103.31 | 6.623 | 0.271 | 0.272 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 103.31 | 6.623 | 0.271 | 0.272 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | BACK_SPACE | GENERAL | 9.0271 | 379.89 | 3429.30 | LightsWired | LTG_SCH_BACK | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 43.94 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | CORE_RETAIL | GENERAL | 18.2986 | 1600.48 | 29286.64 | LightsWired | LTG_SCH_CORE | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 375.23 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | POINT_OF_SALE | GENERAL | 18.2986 | 150.81 | 2759.62 | LightsWired | LTG_SCH_SALE | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 35.36 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | FRONT_RETAIL | GENERAL | 18.2986 | 150.81 | 2759.62 | LightsWired | LTG_SCH_FRONT | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 35.36 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | FRONT_ENTRY | GENERAL | 10.9792 | 12.00 | 131.75 | LightsWired | LTG_SCH_ENTRY | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.69 |
Interior Lighting Total | 16.7250 | 2293.99 | 38366.92 | 491.56 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7996.55 | AstronomicalClock | - | 83.83 | 83.83 | 125.84 | |
Exterior Lighting Total | 7996.55 | 125.84 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 49831.09 | 38300.18 | 11530.91 | 0.77 | 3.30 | |||
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 222534.99 | 158148.94 | 64386.05 | 0.71 | 3.23 | |||
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30711.53 | 22859.21 | 7852.32 | 0.74 | 3.50 | |||
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27866.92 | 20400.54 | 7466.38 | 0.73 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1 COOLING COIL | 47909.1 | 9.83 | 9.83 | ||||
PSZ-AC:2 COOLING COIL | 215250.6 | 9.85 | 9.85 | ||||
PSZ-AC:3 COOLING COIL | 29602.2 | 10.44 | 10.44 | ||||
PSZ-AC:4 COOLING COIL | 26893.1 | 10.48 | 10.48 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | Coil:Heating:Fuel | 2365.02 | 0.80 | |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | 56711.74 | 0.80 | |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | 213382.56 | 0.79 | |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | 32879.31 | 0.80 | |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | 28800.20 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATER FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.10 | 9.48 | 92.91 | 1.00 | 12.13 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 2.44 | 2675.91 | 1094.51 | 1.00 | 1.26 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 9.24 | 15666.01 | 1695.65 | 1.00 | 1.14 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.41 | 1607.01 | 1140.11 | 1.00 | 1.29 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.24 | 1409.86 | 1140.11 | 1.00 | 1.31 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 27751.25 | 33301.50 | 87.66 | 2.037 | 2.445 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 23.89 | 23.89 | 0.00901 | 35.12 | 0.01716 | 0.232 | 0.00 |
CORE_RETAIL | 104867.77 | 125841.33 | 78.63 | 7.699 | 9.239 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 23.89 | 23.89 | 0.00915 | 34.85 | 0.01716 | 1.890 | 0.00 |
POINT_OF_SALE | 15996.97 | 19196.36 | 127.29 | 1.175 | 1.410 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 23.89 | 23.89 | 0.00918 | 35.20 | 0.01716 | 0.178 | 0.00 |
FRONT_RETAIL | 14034.38 | 16841.26 | 111.67 | 1.030 | 1.237 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | 23.89 | 23.89 | 0.00927 | 35.20 | 0.01716 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 0.00 | 34.89 | 0.01721 | 35.12 | 0.01716 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 6576.11 | 7891.34 | 20.77 | 0.276 | 0.331 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.01162 | 20.10 | 0.01480 | 0.232 | 0.00 |
CORE_RETAIL | 22617.78 | 27141.33 | 16.96 | 0.944 | 1.890 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00937 | 20.10 | 0.01480 | 1.890 | 0.00 |
POINT_OF_SALE | 3230.85 | 3877.02 | 25.71 | 0.135 | 0.178 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.01155 | 20.10 | 0.01480 | 0.178 | 0.00 |
FRONT_RETAIL | 3230.85 | 3877.02 | 25.71 | 0.135 | 0.178 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.01155 | 20.10 | 0.01480 | 0.178 | 0.00 |
FRONT_ENTRY | 1970.91 | 2365.09 | 197.09 | 0.085 | 0.102 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.12 | 0.01441 | 20.10 | 0.01480 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 2.44 | 2.44 | 0.33 | 0.33 | 2.4449 | 2.4449 | 2.4449 | 1.0000 | 1.0000 |
PSZ-AC:2 | 9.24 | 9.24 | 1.89 | 1.89 | 9.2389 | 9.2389 | 9.2389 | 1.0000 | 1.0000 |
PSZ-AC:3 | 1.41 | 1.41 | 0.18 | 0.18 | 1.4095 | 1.4095 | 1.4095 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.24 | 1.24 | 0.18 | 0.18 | 1.2366 | 1.2366 | 1.2366 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 2365.018 | 2365.018 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 2365.02 | 2365.02 | 0.102068 | 21.12 | 20.13 | 0.01440585 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.12 | 0.01440585 | 91.4677 | 2365.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 49831.090 | 38300.176 | 2.444860 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 49831.09 | 40718.96 | 2.444860 | 25.85 | 18.08 | 0.00977751 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 9.4721 | 23.89 | 0.00900516 | 48.7404 | 27747.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 56711.737 | 56711.737 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 56711.74 | 56711.74 | 2.444859 | 20.82 | 18.13 | 0.01192339 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 9.4721 | 21.11 | 0.01162258 | 74.1569 | 6576.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 222534.990 | 158148.941 | 9.238920 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 222534.99 | 163789.92 | 9.238920 | 27.55 | 19.43 | 0.01078944 | 12.80 | 12.09 | 0.00850000 | 35.06 | 0.01715788 | 25.79 | 20.4605 | 23.89 | 0.00914655 | 49.4960 | 104626.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 213382.565 | 213382.565 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 213382.56 | 213382.56 | 9.238919 | 20.90 | 16.74 | 0.01019446 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 20.4605 | 19.79 | 0.00901019 | 62.6307 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 30711.530 | 22859.206 | 1.409520 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 30711.53 | 23851.74 | 1.409520 | 26.24 | 18.54 | 0.01018660 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 12.6370 | 23.89 | 0.00917817 | 49.6681 | 15996.97 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 32879.307 | 32879.307 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 32879.31 | 32879.31 | 1.409524 | 20.71 | 18.57 | 0.01252620 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 12.6370 | 21.33 | 0.01219754 | 76.7211 | 1101.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 27866.920 | 20400.536 | 1.236600 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | 27866.92 | 21103.05 | 1.236600 | 26.44 | 18.78 | 0.01040495 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 14.4041 | 23.89 | 0.00926852 | 50.1498 | 14034.38 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 28800.199 | 28800.199 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 | 28800.20 | 28800.20 | 1.236598 | 20.74 | 18.56 | 0.01250092 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 14.4042 | 21.41 | 0.01211431 | 75.8354 | 1358.68 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 2365.018 | 2365.018 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FRONT_ENTRY UNIT HEATER FAN | Fan:ConstantVolume | 0.102068 | 0.12284813 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 2365.02 | 2365.02 | 1.0000 | 0.12284813 | 0.102068 | 21.12 | 20.13 | 0.01440585 | 57816.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2365.02 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.12 | 0.01440585 | 21.12 | 0.01440585 | 91.4677 | 2365.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 49831.090 | 38300.176 | 2.444860 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0159 | 1004.8586 | 1.2036 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.444859 | 2.94261993 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | Sensible | 49831.09 | 40718.96 | 1.0000 | 2.94262123 | 2.444860 | 25.85 | 18.08 | 0.00977751 | 50896.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49831.09 | 35.20 | 0.01715815 | 25.83 | 0.23158056 | 9.4721 | 23.89 | 0.00900516 | 23.89 | 0.00900516 | 48.7404 | 27747.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 56711.737 | 56711.737 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.444859 | 2.94261993 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 56711.74 | 56711.74 | 1.0000 | 2.94261993 | 2.444859 | 20.82 | 18.13 | 0.01192339 | 51202.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 56711.74 | 20.10 | 0.01479830 | 20.10 | 0.23158056 | 9.4721 | 20.90 | 0.01162258 | 21.11 | 0.01162258 | 74.1569 | 6576.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 222534.990 | 158148.941 | 9.238920 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8970 | 1004.8586 | 1.2036 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 9.238919 | 11.11991644 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | Sensible | 222534.99 | 163789.92 | 1.0000 | 11.11991775 | 9.238920 | 27.55 | 19.43 | 0.01078944 | 55222.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 222534.99 | 35.06 | 0.01715788 | 25.79 | 1.89032875 | 20.4605 | 23.89 | 0.00914655 | 23.89 | 0.00914655 | 49.4960 | 104626.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 213382.565 | 213382.565 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 9.238919 | 11.11991644 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 213382.56 | 213382.56 | 1.0000 | 11.11991644 | 9.238919 | 20.90 | 16.74 | 0.01019446 | 46896.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 213382.56 | 20.10 | 0.01479830 | 20.10 | 1.89032875 | 20.4605 | 21.11 | 0.00901019 | 19.79 | 0.00901019 | 62.6307 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30711.530 | 22859.206 | 1.409520 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7764 | 1004.8586 | 1.2036 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.409524 | 1.69649628 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | Sensible | 30711.53 | 23851.74 | 1.0000 | 1.69649120 | 1.409520 | 26.24 | 18.54 | 0.01018660 | 52341.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30711.53 | 35.20 | 0.01715815 | 25.83 | 0.17812154 | 12.6370 | 23.89 | 0.00917817 | 23.89 | 0.00917817 | 49.6681 | 15996.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32879.307 | 32879.307 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.409524 | 1.69649628 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | Sensible | 32879.31 | 32879.31 | 1.0000 | 1.69649628 | 1.409524 | 20.71 | 18.57 | 0.01252620 | 52622.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32879.31 | 20.10 | 0.01479830 | 20.10 | 0.17812154 | 12.6370 | 20.80 | 0.01219754 | 21.33 | 0.01219754 | 76.7211 | 1101.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27866.920 | 20400.536 | 1.236600 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1823 | 1004.8586 | 1.2036 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.236598 | 1.48836292 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | Sensible | 27866.92 | 21103.05 | 1.0000 | 1.48836555 | 1.236600 | 26.44 | 18.78 | 0.01040495 | 53102.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27866.92 | 35.20 | 0.01715815 | 25.83 | 0.17812154 | 14.4041 | 23.89 | 0.00926852 | 23.89 | 0.00926852 | 50.1498 | 14034.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28800.199 | 28800.199 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.236598 | 1.48836292 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 | Sensible | 28800.20 | 28800.20 | 1.0000 | 1.48836292 | 1.236598 | 20.74 | 18.56 | 0.01250092 | 52589.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28800.20 | 20.10 | 0.01479830 | 20.10 | 0.17812154 | 14.4042 | 20.85 | 0.01211431 | 21.41 | 0.01211431 | 75.8354 | 1358.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 4908.83 | 87.83 | 87.83 |
CORE_RETAIL | 4912.00 | 1569.00 | 1569.00 |
POINT_OF_SALE | 4913.00 | 259.50 | 259.50 |
FRONT_RETAIL | 4913.00 | 539.50 | 539.50 |
FRONT_ENTRY | 4913.00 | 4911.00 | 4911.00 |
Facility | 4913.00 | 4911.00 | 4911.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 0.00 | 587.17 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 116.50 | 0.00 | 0.00 |
POINT_OF_SALE | 0.00 | 777.17 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 708.50 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 779.50 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 4.07 | 8.18 | 2317.33 | 0.372 | 0.034 | 0.000 | 0.000 |
CORE_RETAIL | 128.48 | 258.43 | 9762.95 | 0.722 | 0.007 | 0.000 | 0.000 |
POINT_OF_SALE | 12.11 | 24.35 | 919.94 | 0.720 | 0.039 | 0.000 | 0.000 |
FRONT_RETAIL | 12.11 | 24.35 | 919.94 | 0.721 | 0.039 | 0.000 | 0.000 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 0.000 | 35.356 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 4.07 | 8.18 | 2317.33 | 0.364 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.48 | 258.43 | 9762.95 | 0.706 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.11 | 24.35 | 919.94 | 0.705 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.11 | 24.35 | 919.94 | 0.705 | 0.000 | 0.000 | 0.000 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 4.07 | 8.18 | 2317.33 | 379.89 | 0.2316 | 0.232 |
CORE_RETAIL | PSZ-AC:2 | 128.48 | 258.43 | 9762.95 | 1600.48 | 1.8903 | 1.890 |
POINT_OF_SALE | PSZ-AC:3 | 12.11 | 24.35 | 919.94 | 150.81 | 0.1781 | 0.178 |
FRONT_RETAIL | PSZ-AC:4 | 12.11 | 24.35 | 919.94 | 150.81 | 0.1781 | 0.178 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 12.00 | 0.014 | ||
Total Facility | 157.72 | 317.25 | 13993.36 | 2293.99 | 2.4782 | 2.492 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BACK_SPACE | 4924672.26 | 0.00 | 4924672.26 | 1096802.01 | 6021474.27 | 7303124.67 | 3413.96 | 5346.04 | 0.00 | 2732.38 |
CORE_RETAIL | 38687417.17 | 0.00 | 38687417.17 | 940483.23 | 39627900.40 | 59613407.55 | 3467.74 | 5292.26 | 0.00 | 2522.68 |
POINT_OF_SALE | 3752006.16 | 0.00 | 3752006.16 | 500204.05 | 4252210.21 | 5617240.89 | 3457.08 | 5302.92 | 0.00 | 2753.40 |
FRONT_RETAIL | 3743019.91 | 0.00 | 3743019.91 | 500204.05 | 4243223.96 | 5617240.89 | 3454.92 | 5305.08 | 0.00 | 2739.03 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 12007028.00 | 12007028.00 | 446965.66 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 51107115.50 | 0.00 | 51107115.50 | 15044721.35 | 66151836.85 | 78597979.65 | 8760.00 | 5359.76 | 0.00 | 2928.60 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BACK_SPACE | 0.2316 | 0.0000 | 0.2316 | 0.0209 | 0.2525 | 0.2316 | 0.00 | 4913.00 | 0.00 |
CORE_RETAIL | 1.8903 | 0.0000 | 1.8903 | 0.0179 | 1.9083 | 1.8903 | 0.00 | 4913.00 | 0.00 |
POINT_OF_SALE | 0.1781 | 0.0000 | 0.1781 | 0.0095 | 0.1877 | 0.1781 | 0.00 | 4913.00 | 0.00 |
FRONT_RETAIL | 0.1781 | 0.0000 | 0.1781 | 0.0095 | 0.1877 | 0.1781 | 0.00 | 4913.00 | 0.00 |
FRONT_ENTRY | 0.0000 | 0.0000 | 0.0000 | 0.6716 | 0.6716 | 0.0142 | 4913.00 | 0.00 | 0.00 |
Total Facility | 2.4782 | 0.0000 | 2.4782 | 0.7295 | 3.2076 | 2.4923 | 4913.00 | 4913.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC:1 | 7134081.55 | 0.00 | 7134081.55 | 7303124.67 | 3314.44 | 4.42 | 5441.15 | 2725.00 |
PSZ-AC:2 | 56044174.05 | 0.00 | 56044174.05 | 59613407.55 | 3417.08 | 4.44 | 5338.48 | 2521.95 |
PSZ-AC:3 | 5435309.50 | 0.00 | 5435309.50 | 5617240.89 | 3354.97 | 5.08 | 5399.95 | 2752.49 |
PSZ-AC:4 | 5422291.66 | 0.00 | 5422291.66 | 5617240.89 | 3357.88 | 6.07 | 5396.04 | 2733.44 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC:1 | 0.3355 | 0.0000 | 0.3355 | 0.2316 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:2 | 2.7384 | 0.0000 | 2.7384 | 1.8903 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:3 | 0.2580 | 0.0000 | 0.2580 | 0.1781 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:4 | 0.2580 | 0.0000 | 0.2580 | 0.1781 | 0.00 | 0.00 | 4913.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC:1 | 0.00 | 7638.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:2 | 0.00 | 7434.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:3 | 0.00 | 7665.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:4 | 0.00 | 7646.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC:1 | 0.0000 | 0.3355 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:2 | 0.0000 | 2.7384 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:3 | 0.0000 | 0.2580 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:4 | 0.0000 | 0.2580 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 11 | 11 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 457 |
Defaulted Fields | 416 |
Fields with Defaults | 1298 |
Autosized Fields | 76 |
Autosizable Fields | 182 |
Autocalculated Fields | 70 |
Autocalculatable Fields | 140 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2435.53 | 3713.52 | 16-JAN-06:20 | 153159.31 | 13-JUN-15:00 |
Electricity:Building | 686.72 | 3713.52 | 01-JAN-00:10 | 45301.27 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 93.93 | 631.32 | 01-JAN-00:10 | 5845.51 | 02-JAN-09:10 |
Electricity:SpaceType:GENERAL | 686.72 | 3713.52 | 01-JAN-00:10 | 45301.27 | 02-JAN-09:10 |
InteriorLights:Electricity | 491.57 | 1918.35 | 01-JAN-00:10 | 34530.23 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 43.94 | 171.46 | 01-JAN-00:10 | 3086.37 | 02-JAN-09:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 491.57 | 1918.35 | 01-JAN-00:10 | 34530.23 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 491.57 | 1918.35 | 01-JAN-00:10 | 34530.23 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:BACK_SPACE | 43.94 | 171.46 | 01-JAN-00:10 | 3086.37 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 491.57 | 1918.35 | 01-JAN-00:10 | 34530.23 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 459.53 | 2239.77 | 01-JAN-00:10 | 31010.58 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 375.23 | 1464.33 | 01-JAN-00:10 | 26357.98 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_RETAIL | 375.23 | 1464.33 | 01-JAN-00:10 | 26357.98 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 88.28 | 624.80 | 01-JAN-00:10 | 5404.54 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 35.36 | 137.98 | 01-JAN-00:10 | 2483.65 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:POINT_OF_SALE | 35.36 | 137.98 | 01-JAN-00:10 | 2483.65 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 43.30 | 211.05 | 01-JAN-00:10 | 2922.06 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 35.36 | 137.98 | 01-JAN-00:10 | 2483.65 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:FRONT_RETAIL | 35.36 | 137.98 | 01-JAN-00:10 | 2483.65 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.69 | 6.59 | 01-JAN-00:10 | 118.58 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.69 | 6.59 | 01-JAN-00:10 | 118.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.69 | 6.59 | 01-JAN-00:10 | 118.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 2435.53 | 3713.52 | 16-JAN-06:20 | 153159.31 | 13-JUN-15:00 |
ElectricityPurchased:Plant | 2435.53 | 3713.52 | 16-JAN-06:20 | 153159.31 | 13-JUN-15:00 |
Cogeneration:ElectricityPurchased | 2435.53 | 3713.52 | 16-JAN-06:20 | 153159.31 | 13-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 2435.53 | 3713.52 | 16-JAN-06:20 | 153159.31 | 13-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2435.53 | 3713.52 | 16-JAN-06:20 | 153159.31 | 13-JUN-15:00 |
ElectricityNet:Plant | 2435.53 | 3713.52 | 16-JAN-06:20 | 153159.31 | 13-JUN-15:00 |
Cogeneration:ElectricityNet | 2435.53 | 3713.52 | 16-JAN-06:20 | 153159.31 | 13-JUN-15:00 |
General:Cogeneration:ElectricityNet | 2435.53 | 3713.52 | 16-JAN-06:20 | 153159.31 | 13-JUN-15:00 |
Electricity:HVAC | 1622.96 | 0.00 | 02-JAN-05:40 | 107858.04 | 13-JUN-15:00 |
Fans:Electricity | 447.67 | 0.00 | 02-JAN-05:40 | 21358.79 | 01-JAN-09:40 |
General:Fans:Electricity | 447.67 | 0.00 | 02-JAN-05:40 | 21358.79 | 01-JAN-09:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1175.30 | 0.00 | 02-JAN-05:40 | 86499.24 | 13-JUN-15:00 |
General:Cooling:Electricity | 1175.30 | 0.00 | 02-JAN-05:40 | 86499.24 | 13-JUN-15:00 |
ExteriorLights:Electricity | 125.84 | 0.00 | 01-JAN-06:20 | 7996.55 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 125.84 | 0.00 | 01-JAN-06:20 | 7996.55 | 01-JAN-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 85.43 | 1862.00 | 24-JAN-08:10 | 4805.79 | 06-JAN-13:00 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 85.43 | 1862.00 | 24-JAN-08:10 | 4805.79 | 06-JAN-13:00 |
WaterSystems:NaturalGas | 85.43 | 1862.00 | 24-JAN-08:10 | 4805.79 | 06-JAN-13:00 |
Water Heater:WaterSystems:NaturalGas | 85.43 | 1862.00 | 24-JAN-08:10 | 4805.79 | 06-JAN-13:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 5568.94 | 0.00 | 02-JAN-05:40 | 395613.62 | 13-JUN-15:00 |
EnergyTransfer:Building | 1726.57 | 0.00 | 02-JAN-05:40 | 124677.02 | 06-MAY-15:00 |
EnergyTransfer:Zone:BACK_SPACE | 325.44 | 0.00 | 01-JAN-00:10 | 26295.09 | 13-JUN-16:00 |
Heating:EnergyTransfer | 0.19 | 0.00 | 01-JAN-00:10 | 9634.47 | 12-OCT-05:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 0.01 | 0.00 | 01-JAN-00:10 | 1825.56 | 20-OCT-05:10 |
General:Heating:EnergyTransfer | 0.19 | 0.00 | 01-JAN-00:10 | 9634.47 | 12-OCT-05:10 |
General:Heating:EnergyTransfer:Zone:BACK_SPACE | 0.01 | 0.00 | 01-JAN-00:10 | 1825.56 | 20-OCT-05:10 |
Cooling:EnergyTransfer | 1726.38 | 0.00 | 02-JAN-05:40 | 124677.02 | 06-MAY-15:00 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 325.42 | 0.00 | 01-JAN-00:10 | 26295.09 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer | 1726.38 | 0.00 | 02-JAN-05:40 | 124677.02 | 06-MAY-15:00 |
General:Cooling:EnergyTransfer:Zone:BACK_SPACE | 325.42 | 0.00 | 01-JAN-00:10 | 26295.09 | 13-JUN-16:00 |
EnergyTransfer:Zone:CORE_RETAIL | 1007.20 | 0.00 | 01-JAN-00:40 | 72703.90 | 06-MAY-15:00 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 0.17 | 0.00 | 01-JAN-00:10 | 9139.09 | 10-OCT-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_RETAIL | 0.17 | 0.00 | 01-JAN-00:10 | 9139.09 | 10-OCT-05:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 1007.03 | 0.00 | 01-JAN-00:40 | 72703.90 | 06-MAY-15:00 |
General:Cooling:EnergyTransfer:Zone:CORE_RETAIL | 1007.03 | 0.00 | 01-JAN-00:40 | 72703.90 | 06-MAY-15:00 |
EnergyTransfer:Zone:POINT_OF_SALE | 214.49 | 0.00 | 01-JAN-00:40 | 16371.51 | 07-DEC-15:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.00 | 0.00 | 01-JAN-00:10 | 797.86 | 19-NOV-08:10 |
General:Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.00 | 0.00 | 01-JAN-00:10 | 797.86 | 19-NOV-08:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 214.48 | 0.00 | 01-JAN-00:40 | 16371.51 | 07-DEC-15:10 |
General:Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 214.48 | 0.00 | 01-JAN-00:40 | 16371.51 | 07-DEC-15:10 |
EnergyTransfer:Zone:FRONT_RETAIL | 179.45 | 0.00 | 01-JAN-00:40 | 14676.25 | 08-DEC-14:30 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.01 | 0.00 | 01-JAN-00:10 | 701.58 | 19-NOV-08:10 |
General:Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.01 | 0.00 | 01-JAN-00:10 | 701.58 | 19-NOV-08:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 179.44 | 0.00 | 01-JAN-00:40 | 14676.25 | 08-DEC-14:30 |
General:Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 179.44 | 0.00 | 01-JAN-00:40 | 14676.25 | 08-DEC-14:30 |
EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 3842.37 | 0.00 | 02-JAN-05:40 | 274313.46 | 13-JUN-15:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 3842.37 | 0.00 | 02-JAN-05:40 | 274313.46 | 13-JUN-15:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 0.013 | -325.417 | 0.000 | 0.000 | 4.889 | 43.937 | 49.992 | 0.000 | 0.000 | 4.525 | 222.232 | 0.000 | 0.000 | 0.000 | -0.171 | -0.000 |
CORE_RETAIL | 0.000 | 0.000 | 0.169 | -1007.022 | 0.000 | 0.000 | 154.488 | 375.227 | 84.300 | 17.611 | 0.000 | 3.934 | 373.387 | 0.000 | -1.952 | 0.000 | -0.142 | -0.001 |
POINT_OF_SALE | 0.000 | 0.000 | 0.005 | -214.481 | 0.000 | 0.000 | 14.557 | 35.357 | 52.923 | 40.974 | 0.000 | 2.050 | 72.253 | 0.000 | -3.555 | 0.000 | -0.084 | -0.000 |
FRONT_RETAIL | 0.000 | 0.000 | 0.005 | -179.439 | 0.000 | 0.000 | 14.557 | 35.357 | 7.943 | 41.100 | 0.000 | 2.061 | 81.809 | 0.000 | -3.313 | 0.000 | -0.081 | -0.000 |
FRONT_ENTRY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.596 | 1.688 | 0.000 | 6.377 | 0.000 | 1.508 | 0.000 | 0.000 | -1.510 | 0.000 | -2.170 | -6.490 |
Total Facility | 0.000 | 0.000 | 0.193 | -1726.358 | 0.000 | 0.000 | 189.087 | 491.565 | 195.158 | 106.063 | 0.000 | 14.078 | 749.682 | 0.000 | -10.330 | 0.000 | -2.648 | -6.492 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 23-FEB-02:23 | 0.00 | 0.00 | 0.00 | -39925.10 | 0.00 | 0.00 | 0.00 | 171.46 | 613.14 | 0.00 | 0.00 | 0.00 | 39140.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 24-FEB-21:07 | 0.00 | 0.00 | 0.00 | -146027.21 | 0.00 | 0.00 | 0.00 | 5857.33 | 1033.91 | 0.00 | 0.00 | 97.08 | 139178.96 | 0.00 | -140.08 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 20-DEC-21:42 | 0.00 | 0.00 | 0.00 | -24631.07 | 0.00 | 0.00 | 0.00 | 551.92 | 649.09 | 0.00 | 0.00 | 0.00 | 24402.39 | 0.00 | -859.53 | 0.00 | -112.80 | 0.00 |
FRONT_RETAIL | 20-DEC-21:42 | 0.00 | 0.00 | 0.00 | -21742.95 | 0.00 | 0.00 | 0.00 | 551.92 | 97.42 | 0.00 | 0.00 | 0.00 | 22032.61 | 0.00 | -830.54 | 0.00 | -108.47 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-FEB-01:42 | 0.00 | 0.00 | 0.00 | -226576.09 | 0.00 | 0.00 | 0.00 | 1918.35 | 2393.56 | 0.00 | 0.00 | 0.00 | 223350.96 | 0.00 | -1086.78 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 01-OCT-07:07 | 0.00 | 0.00 | 3745.70 | 0.00 | 0.00 | 0.00 | 0.00 | 171.46 | 459.86 | 0.00 | 0.00 | 21.33 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4398.35 |
CORE_RETAIL | 28-MAY-07:03 | 0.00 | 0.00 | 26548.59 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.33 | 775.43 | 728.95 | 0.00 | 80.45 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29597.75 |
POINT_OF_SALE | 28-MAY-07:03 | 0.00 | 0.00 | 2804.53 | 0.00 | 0.00 | 0.00 | 0.00 | 137.98 | 486.81 | 1681.64 | 0.00 | 42.74 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5153.70 |
FRONT_RETAIL | 19-NOV-08:07 | 0.00 | 0.00 | 2105.26 | 0.00 | 0.00 | 0.00 | 0.00 | 137.98 | 73.07 | 1934.80 | 0.00 | 7.42 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4258.52 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-MAY-07:03 | -9589.01 | 9589.01 | 31141.69 | -9589.01 | 0.00 | 0.00 | 0.00 | 1918.35 | 1795.17 | 4403.55 | 0.00 | 1024.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -30694.35 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.4449 | 0.0000 | 8.1781 | 1.0000 | Calculated from schedules | 0.2316 | 2.4449 | 0.0947 | 1.0000 | Not calculated | 0.2316 | 0.0947 | ||
PSZ-AC:2 | 9.2389 | 0.0000 | 258.4342 | 1.0000 | Calculated from schedules | 1.8903 | 9.2389 | 0.2046 | 1.0000 | Not calculated | 1.8903 | 0.2046 | ||
PSZ-AC:3 | 1.4095 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.4095 | 0.1264 | 1.0000 | Not calculated | 0.1781 | 0.1264 | ||
PSZ-AC:4 | 1.2366 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.2366 | 0.1440 | 1.0000 | Not calculated | 0.1781 | 0.1440 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.4449 | 0.0000 | 8.1781 | 1.0000 | Calculated from schedules | 0.2316 | 2.4449 | 1.0000 | 1.0000 | Not calculated | 0.2316 | 0.0947 | ||
PSZ-AC:2 | 9.2389 | 0.0000 | 258.4342 | 1.0000 | Calculated from schedules | 1.8903 | 9.2389 | 1.0000 | 1.0000 | Not calculated | 1.8903 | 0.2046 | ||
PSZ-AC:3 | 1.4095 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.4095 | 1.0000 | 1.0000 | Not calculated | 0.1781 | 0.1264 | ||
PSZ-AC:4 | 1.2366 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.2366 | 1.0000 | 1.0000 | Not calculated | 0.1781 | 0.1440 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 8.1781 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8903 | 1.0000 | 1.8903 | 1.000 | 1.8903 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 8.18 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8903 | 1.8903 | 1.8903 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4449 | 2.4449 | 2.4449 | No | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_RETAIL | PSZ-AC:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 9.2389 | 9.2389 | 9.2389 | No | 1.8903 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
POINT_OF_SALE | PSZ-AC:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4095 | 1.4095 | 1.4095 | No | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
FRONT_RETAIL | PSZ-AC:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2366 | 1.2366 | 1.2366 | No | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.4449 | 2.4449 | 2.4449 | 2.4449 | 0.2316 | 1.0000 |
PSZ-AC:2 | 9.2389 | 9.2389 | 9.2389 | 9.2389 | 1.8903 | 1.0000 |
PSZ-AC:3 | 1.4095 | 1.4095 | 1.4095 | 1.4095 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.2366 | 1.2366 | 1.2366 | 1.2366 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4449 | 2.4449 | 2.4449 | No | 0.2316 | 0.6991 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_RETAIL | PSZ-AC:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 9.2389 | 9.2389 | 9.2389 | No | 1.8903 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
POINT_OF_SALE | PSZ-AC:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4095 | 1.4095 | 1.4095 | No | 0.1781 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
FRONT_RETAIL | PSZ-AC:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2366 | 1.2366 | 1.2366 | No | 0.1781 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.4449 | 2.4449 | 2.4449 | 2.4449 | 0.2316 | 1.0000 |
PSZ-AC:2 | 9.2389 | 9.2389 | 9.2389 | 9.2389 | 1.8903 | 1.0000 |
PSZ-AC:3 | 1.4095 | 1.4095 | 1.4095 | 1.4095 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.2366 | 1.2366 | 1.2366 | 1.2366 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 2293.99 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 94.22 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1175.30 | 86499.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 491.57 | 34530.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 125.84 | 7996.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 447.67 | 21358.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 85.43 | 4805.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 2435.53 |
Natural Gas | 0.00 | 85.43 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 2520.96 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 214.28 |
Space Heating | 0.00 |
Space Cooling | 512.34 |
Fans (All) | 195.15 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 1061.70 |
Subtotal | 1061.70 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 37.24 |
Miscellaneous (All) | 37.24 |
Subtotal | 37.24 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.50 |
Space Heating | 0.00 |
Space Cooling | 46.62 |
Fans (All) | 17.76 |
Service Water Heating | 3.39 |
Receptacle Equipment | 7.74 |
Miscellaneous | 4.99 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
LTG_SCH_ENTRY | 3609. | 8760. |
LTG_SCH_CORE | 3609. | 8760. |
LTG_SCH_BACK | 3609. | 8760. |
LTG_SCH_SALE | 3609. | 8760. |
LTG_SCH_FRONT | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | FRONT_ENTRY HEATING SP | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_SETBACK | BACK_SPACE DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_SCH_PSZ_AC_2 | CORE_RETAIL DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BACK_SPACE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 356.00 | 3882.00 | 3991.50 | 530.50 | 0.00 |
Min | 356.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 3882.00 | 3991.50 | 530.50 | 0.00 |
Average | 7079.20 | 776.40 | 798.30 | 106.10 | 0.00 |
Sum | 35396.00 | 3882.00 | 3991.50 | 530.50 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BACK_SPACE | 16872.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 609599.00 | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 56000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 56000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 29.83 | 220.00 | 1288.50 | 381.67 | 0.00 |
Min | 29.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 609599.00 | 220.00 | 1288.50 | 381.67 | 0.00 |
Average | 147700.17 | 44.00 | 257.70 | 76.33 | 0.00 |
Sum | 738500.83 | 220.00 | 1288.50 | 381.67 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BACK_SPACE | 8562.67 | 197.33 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 6992.17 | 1767.83 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 8347.00 | 413.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 7985.33 | 774.67 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 1.83 | 4832.17 | 3481.17 | 444.83 | 0.00 |
Min | 1.83 | 197.33 | 0.00 | 0.00 | 0.00 |
Max | 8562.67 | 4832.17 | 3481.17 | 444.83 | 0.00 |
Average | 6377.80 | 1597.00 | 696.23 | 88.97 | 0.00 |
Sum | 31889.00 | 7985.00 | 3481.17 | 444.83 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BACK_SPACE | 16666.50 | 205.50 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 444707.00 | 164892.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 54516.67 | 1483.33 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 51874.33 | 4125.67 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 516.00 | 1084.17 | 319.83 | 0.00 |
Min | 0.00 | 205.50 | 0.00 | 0.00 | 0.00 |
Max | 444707.00 | 164892.00 | 1084.17 | 319.83 | 0.00 |
Average | 113552.90 | 34244.50 | 216.83 | 63.97 | 0.00 |
Sum | 567764.50 | 171222.50 | 1084.17 | 319.83 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226391E+11 | 38542.58 | 15-JAN-21:42 | 25.08 | 20.20 | 0.291181E+09 | 326.84 | 28-JAN-15:00 | 32.10 | 22.10 |
February | 0.234083E+11 | 39926.12 | 23-FEB-02:23 | 25.60 | 21.95 | 0.265888E+09 | 326.84 | 23-FEB-15:09 | 32.30 | 22.02 |
March | 0.285868E+11 | 37947.34 | 02-MAR-22:23 | 26.00 | 21.11 | 0.304124E+09 | 326.84 | 29-MAR-14:00 | 34.00 | 24.67 |
April | 0.301671E+11 | 37623.56 | 26-APR-22:42 | 27.88 | 23.81 | 0.287504E+09 | 326.80 | 14-APR-14:00 | 27.88 | 23.81 |
May | 0.330373E+11 | 37128.30 | 11-MAY-01:23 | 24.10 | 24.04 | 0.297656E+09 | 326.85 | 04-MAY-14:50 | 24.10 | 24.04 |
June | 0.360664E+11 | 37832.97 | 27-JUN-02:63 | 24.00 | 24.00 | 0.293542E+09 | 326.85 | 24-JUN-12:00 | 24.00 | 24.00 |
July | 0.306876E+11 | 38515.54 | 20-JUL-02:63 | 23.70 | 22.58 | 0.291623E+09 | 326.85 | 14-JUL-14:39 | 23.70 | 22.58 |
August | 0.279755E+11 | 37388.19 | 24-AUG-02:63 | 23.17 | 23.17 | 0.304122E+09 | 326.80 | 05-AUG-10:09 | 23.17 | 23.17 |
September | 0.260765E+11 | 37087.47 | 12-SEP-21:23 | 26.30 | 24.85 | 0.287504E+09 | 326.80 | 16-SEP-10:09 | 29.00 | 26.25 |
October | 0.229414E+11 | 36512.61 | 08-OCT-21:23 | 26.00 | 24.36 | 0.291181E+09 | 326.80 | 11-OCT-14:00 | 24.50 | 24.50 |
November | 0.223095E+11 | 36435.94 | 05-NOV-21:23 | 25.75 | 24.38 | 0.280151E+09 | 326.80 | 18-NOV-12:50 | 33.75 | 25.33 |
December | 0.215263E+11 | 39478.47 | 20-DEC-21:42 | 22.17 | 18.29 | 0.291622E+09 | 326.80 | 30-DEC-11:39 | 31.00 | 25.16 |
Annual Sum or Average | 0.325422E+12 | 0.348610E+10 | ||||||||
Minimum of Months | 0.215263E+11 | 36435.94 | 22.17 | 18.29 | 0.265888E+09 | 326.80 | 23.17 | 22.02 | ||
Maximum of Months | 0.360664E+11 | 39926.12 | 27.88 | 24.85 | 0.304124E+09 | 326.85 | 34.00 | 26.25 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.800115E+11 | 140531.10 | 13-JAN-23:03 | 24.42 | 22.37 | 0.920152E+10 | 10327.18 | 07-JAN-11:09 | 24.42 | 22.37 |
February | 0.781189E+11 | 146043.79 | 24-FEB-21:07 | 27.38 | 21.32 | 0.840219E+10 | 10327.18 | 18-FEB-11:09 | 27.38 | 21.32 |
March | 0.930379E+11 | 144952.94 | 02-MAR-22:23 | 26.00 | 21.11 | 0.961047E+10 | 10327.18 | 25-MAR-10:09 | 31.58 | 24.67 |
April | 0.915505E+11 | 139116.69 | 26-APR-22:42 | 27.88 | 23.81 | 0.908534E+10 | 10327.18 | 14-APR-14:00 | 27.88 | 23.81 |
May | 0.898843E+11 | 127221.57 | 10-MAY-20:08 | 22.17 | 22.17 | 0.940600E+10 | 10327.19 | 12-MAY-14:09 | 31.17 | 25.78 |
June | 0.915243E+11 | 120748.87 | 07-JUN-20:08 | 28.00 | 25.05 | 0.927587E+10 | 10327.18 | 24-JUN-14:39 | 34.00 | 26.71 |
July | 0.840604E+11 | 135106.21 | 30-JUL-20:03 | 29.00 | 23.33 | 0.921546E+10 | 10327.19 | 08-JUL-10:09 | 29.00 | 23.33 |
August | 0.842436E+11 | 125978.50 | 23-AUG-20:08 | 23.00 | 22.40 | 0.961048E+10 | 10327.19 | 04-AUG-14:09 | 23.00 | 22.40 |
September | 0.823985E+11 | 128608.56 | 12-SEP-21:23 | 26.30 | 24.85 | 0.908534E+10 | 10327.19 | 16-SEP-13:39 | 25.13 | 24.29 |
October | 0.778195E+11 | 132994.57 | 08-OCT-21:23 | 26.00 | 24.36 | 0.920152E+10 | 10327.19 | 11-OCT-14:09 | 24.08 | 24.08 |
November | 0.763268E+11 | 134520.17 | 24-NOV-21:08 | 23.38 | 21.12 | 0.885298E+10 | 10327.18 | 27-NOV-15:00 | 27.00 | 23.97 |
December | 0.780555E+11 | 143765.57 | 26-DEC-21:07 | 23.88 | 19.93 | 0.921546E+10 | 10327.19 | 18-DEC-15:00 | 23.88 | 19.93 |
Annual Sum or Average | 0.100703E+13 | 0.110163E+12 | ||||||||
Minimum of Months | 0.763268E+11 | 120748.87 | 22.17 | 19.93 | 0.840219E+10 | 10327.18 | 23.00 | 19.93 | ||
Maximum of Months | 0.930379E+11 | 146043.79 | 29.00 | 25.05 | 0.961048E+10 | 10327.19 | 34.00 | 26.71 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203003E+11 | 24184.60 | 15-JAN-21:42 | 25.08 | 20.20 | 0.867087E+09 | 973.35 | 12-JAN-15:39 | 25.08 | 20.20 |
February | 0.188589E+11 | 24430.62 | 23-FEB-01:42 | 25.87 | 21.85 | 0.791760E+09 | 973.34 | 09-FEB-15:00 | 25.87 | 21.85 |
March | 0.196519E+11 | 22957.14 | 02-MAR-22:23 | 26.00 | 21.11 | 0.905590E+09 | 973.33 | 25-MAR-15:20 | 33.23 | 24.52 |
April | 0.174155E+11 | 21915.65 | 26-APR-22:42 | 27.88 | 23.81 | 0.856091E+09 | 973.11 | 14-APR-14:00 | 27.88 | 23.81 |
May | 0.175706E+11 | 20469.29 | 10-MAY-20:06 | 22.17 | 22.17 | 0.886310E+09 | 973.32 | 05-MAY-14:00 | 22.17 | 22.17 |
June | 0.175111E+11 | 19807.83 | 07-JUN-20:06 | 28.00 | 25.05 | 0.874045E+09 | 973.11 | 24-JUN-15:09 | 32.38 | 26.43 |
July | 0.161490E+11 | 21678.05 | 30-JUL-20:03 | 29.00 | 23.33 | 0.868352E+09 | 973.11 | 08-JUL-10:09 | 29.00 | 23.33 |
August | 0.158551E+11 | 20050.46 | 23-AUG-20:08 | 23.00 | 22.40 | 0.905574E+09 | 973.11 | 04-AUG-14:00 | 23.00 | 22.40 |
September | 0.164581E+11 | 21745.42 | 12-SEP-21:23 | 26.30 | 24.85 | 0.856091E+09 | 973.11 | 16-SEP-13:50 | 25.32 | 24.31 |
October | 0.167165E+11 | 22159.36 | 08-OCT-21:23 | 26.00 | 24.36 | 0.867039E+09 | 973.35 | 28-OCT-13:50 | 31.32 | 26.47 |
November | 0.181681E+11 | 22304.80 | 05-NOV-21:23 | 25.75 | 24.38 | 0.834202E+09 | 973.35 | 18-NOV-15:20 | 30.23 | 25.10 |
December | 0.198294E+11 | 24631.92 | 20-DEC-21:42 | 22.17 | 18.29 | 0.868385E+09 | 973.35 | 30-DEC-15:50 | 30.42 | 25.66 |
Annual Sum or Average | 0.214485E+12 | 0.103805E+11 | ||||||||
Minimum of Months | 0.158551E+11 | 19807.83 | 22.17 | 18.29 | 0.791760E+09 | 973.11 | 22.17 | 20.20 | ||
Maximum of Months | 0.203003E+11 | 24631.92 | 29.00 | 25.05 | 0.905590E+09 | 973.35 | 33.23 | 26.47 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172908E+11 | 21472.04 | 15-JAN-21:42 | 25.08 | 20.20 | 0.867063E+09 | 973.32 | 30-JAN-15:00 | 30.10 | 24.75 |
February | 0.161492E+11 | 21627.69 | 23-FEB-01:42 | 25.87 | 21.85 | 0.791741E+09 | 973.31 | 04-FEB-13:00 | 25.87 | 21.85 |
March | 0.165091E+11 | 20120.31 | 02-MAR-22:23 | 26.00 | 21.11 | 0.905580E+09 | 973.31 | 28-MAR-14:00 | 35.00 | 25.48 |
April | 0.145082E+11 | 19123.72 | 26-APR-22:42 | 27.88 | 23.81 | 0.856091E+09 | 973.11 | 14-APR-14:00 | 27.88 | 23.81 |
May | 0.146424E+11 | 17618.65 | 10-MAY-20:06 | 22.17 | 22.17 | 0.886308E+09 | 973.30 | 06-MAY-14:09 | 22.17 | 22.17 |
June | 0.146899E+11 | 17037.51 | 07-JUN-20:06 | 28.00 | 25.05 | 0.874045E+09 | 973.11 | 24-JUN-14:39 | 34.00 | 26.71 |
July | 0.132484E+11 | 19177.39 | 30-JUL-20:03 | 29.00 | 23.33 | 0.868352E+09 | 973.11 | 08-JUL-10:09 | 29.00 | 23.33 |
August | 0.129046E+11 | 17319.77 | 23-AUG-20:08 | 23.00 | 22.40 | 0.905574E+09 | 973.11 | 04-AUG-14:00 | 23.00 | 22.40 |
September | 0.136388E+11 | 18796.53 | 29-SEP-23:23 | 27.55 | 25.64 | 0.856091E+09 | 973.11 | 16-SEP-15:00 | 27.55 | 25.64 |
October | 0.137357E+11 | 19570.71 | 08-OCT-21:23 | 26.00 | 24.36 | 0.867039E+09 | 973.11 | 11-OCT-14:00 | 24.50 | 24.50 |
November | 0.152916E+11 | 19744.94 | 05-NOV-21:23 | 25.75 | 24.38 | 0.834197E+09 | 973.24 | 18-NOV-13:39 | 32.10 | 25.08 |
December | 0.168334E+11 | 21743.30 | 20-DEC-21:42 | 22.17 | 18.29 | 0.868373E+09 | 973.32 | 30-DEC-14:30 | 31.50 | 25.21 |
Annual Sum or Average | 0.179442E+12 | 0.103805E+11 | ||||||||
Minimum of Months | 0.129046E+11 | 17037.51 | 22.17 | 18.29 | 0.791741E+09 | 973.11 | 22.17 | 21.85 | ||
Maximum of Months | 0.172908E+11 | 21743.30 | 29.00 | 25.64 | 0.905580E+09 | 973.32 | 35.00 | 26.71 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 | 23.60 | 0.114745E+09 | 167.86 | 05-JAN-15:09 | 33.73 | 23.23 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 | 22.46 | 0.110782E+09 | 176.79 | 28-FEB-15:09 | 34.60 | 24.66 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 22.97 | 0.129626E+09 | 185.70 | 21-MAR-14:09 | 35.67 | 23.99 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 | 25.10 | 0.123444E+09 | 179.20 | 01-APR-14:09 | 35.42 | 26.93 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 | 26.40 | 0.126559E+09 | 186.05 | 06-MAY-11:30 | 36.50 | 25.80 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 | 23.91 | 0.125652E+09 | 184.62 | 13-JUN-14:00 | 36.00 | 28.43 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.40 | 24.33 | 0.109367E+09 | 156.71 | 15-JUL-15:00 | 33.20 | 25.63 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 | 24.75 | 0.115277E+09 | 164.07 | 10-AUG-14:09 | 33.50 | 27.78 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.53 | 25.66 | 0.110432E+09 | 164.80 | 06-SEP-14:09 | 33.83 | 26.60 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 | 25.35 | 0.106698E+09 | 156.26 | 04-OCT-14:09 | 32.92 | 26.22 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 | 24.37 | 0.104732E+09 | 169.61 | 18-NOV-13:09 | 33.75 | 25.30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 | 23.43 | 0.111058E+09 | 158.64 | 07-DEC-15:09 | 32.63 | 22.66 |
Annual Sum or Average | 0.00 | 0.138837E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 23.80 | 22.46 | 0.104732E+09 | 156.26 | 32.63 | 22.66 | ||
Maximum of Months | 0.00 | 0.00 | 28.62 | 26.40 | 0.129626E+09 | 186.05 | 36.50 | 28.43 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 506942.17 | 2836.19 | 29-JAN-08:04 | 24.17 |
February | 1677080.34 | 3562.36 | 26-FEB-08:07 | 25.33 |
March | 244810.45 | 662.81 | 04-MAR-06:10 | 24.10 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 724456.03 | 3622.28 | 16-JUL-07:07 | 24.92 |
August | 2318308.61 | 3459.13 | 05-AUG-05:05 | 25.00 |
September | 943178.30 | 1571.96 | 16-SEP-05:10 | 24.00 |
October | 3650279.44 | 3745.25 | 01-OCT-07:07 | 25.50 |
November | 1075266.85 | 3575.48 | 19-NOV-08:07 | 25.50 |
December | 2154135.26 | 3563.65 | 31-DEC-08:05 | 24.67 |
Annual Sum or Average | 13294457.46 | |||
Minimum of Months | 0.00 | 0.00 | 24.00 | |
Maximum of Months | 3650279.44 | 3745.25 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35386092.45 | 17970.07 | 03-JAN-06:05 | 24.67 |
February | 16929853.74 | 19461.03 | 05-FEB-08:07 | 25.33 |
March | 7470555.18 | 16675.87 | 06-MAR-06:05 | 24.03 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 3531779.38 | 26542.31 | 28-MAY-07:03 | 32.25 |
June | 5234912.34 | 15702.16 | 05-JUN-05:05 | 26.00 |
July | 20761299.60 | 18615.45 | 16-JUL-07:07 | 24.92 |
August | 16879602.81 | 15841.62 | 18-AUG-05:05 | 25.83 |
September | 839122.05 | 557.86 | 19-SEP-05:10 | 24.00 |
October | 25161415.85 | 20009.10 | 01-OCT-07:07 | 25.50 |
November | 27278438.75 | 19809.56 | 19-NOV-08:07 | 25.50 |
December | 9562097.50 | 16964.99 | 25-DEC-08:05 | 24.33 |
Annual Sum or Average | 0.169035E+09 | |||
Minimum of Months | 0.00 | 0.00 | 24.00 | |
Maximum of Months | 35386092.45 | 26542.31 | 32.25 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 652208.28 | 1827.34 | 29-JAN-08:04 | 24.17 |
February | 1091555.89 | 2363.58 | 05-FEB-08:07 | 25.33 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 280402.30 | 2804.02 | 28-MAY-07:03 | 32.25 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 421243.47 | 2106.22 | 16-JUL-07:07 | 24.92 |
August | 376874.41 | 766.73 | 21-AUG-05:10 | 24.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.53 |
October | 470975.82 | 2354.88 | 01-OCT-07:07 | 25.50 |
November | 587335.37 | 2393.59 | 19-NOV-08:07 | 25.50 |
December | 1075813.15 | 2350.32 | 03-DEC-08:05 | 24.50 |
Annual Sum or Average | 4956408.71 | |||
Minimum of Months | 0.00 | 0.00 | 24.00 | |
Maximum of Months | 1091555.89 | 2804.02 | 32.25 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 582292.75 | 1596.43 | 29-JAN-08:04 | 24.17 |
February | 955733.34 | 2082.14 | 05-FEB-08:07 | 25.33 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 178828.70 | 1788.29 | 28-MAY-07:03 | 32.25 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 368385.53 | 1841.93 | 16-JUL-07:07 | 24.92 |
August | 445464.72 | 1013.88 | 21-AUG-05:05 | 24.00 |
September | 290721.33 | 484.54 | 16-SEP-05:10 | 24.00 |
October | 1066738.05 | 2064.88 | 01-OCT-07:07 | 25.50 |
November | 546076.18 | 2104.74 | 19-NOV-08:07 | 25.50 |
December | 917673.02 | 1993.72 | 31-DEC-08:05 | 24.67 |
Annual Sum or Average | 5351913.62 | |||
Minimum of Months | 0.00 | 0.00 | 24.00 | |
Maximum of Months | 1066738.05 | 2104.74 | 32.25 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.368451E+10 | 3086.37 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.335241E+10 | 3086.37 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.382401E+10 | 3086.37 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.360796E+10 | 3086.37 | 01-APR-09:09 | 0.410339E+10 | 2759.14 | 01-APR-09:09 |
May | 0.375426E+10 | 3086.37 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.369006E+10 | 3086.37 | 01-JUN-08:09 | 0.416906E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.367216E+10 | 3086.37 | 01-JUL-09:09 | 0.419831E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.382401E+10 | 3086.37 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.360796E+10 | 3086.37 | 01-SEP-08:09 | 0.410229E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.368451E+10 | 3086.37 | 02-OCT-08:09 | 0.421210E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.356290E+10 | 3086.37 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.367216E+10 | 3086.37 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.439369E+11 | 0.499923E+11 | ||||
Minimum of Months | 0.335241E+10 | 3086.37 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.382401E+10 | 3086.37 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314662E+11 | 26357.98 | 02-JAN-09:09 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.286300E+11 | 26357.98 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.326575E+11 | 26357.98 | 01-MAR-09:09 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.308125E+11 | 26357.98 | 01-APR-09:09 | 0.691935E+10 | 4652.60 | 01-APR-09:09 |
May | 0.320618E+11 | 26357.98 | 01-MAY-08:09 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.315136E+11 | 26357.98 | 01-JUN-08:09 | 0.703008E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.313607E+11 | 26357.98 | 01-JUL-09:09 | 0.707940E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.326575E+11 | 26357.98 | 01-AUG-08:09 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.308125E+11 | 26357.98 | 01-SEP-08:09 | 0.691749E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.314662E+11 | 26357.98 | 02-OCT-08:09 | 0.710266E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.304277E+11 | 26357.98 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.313607E+11 | 26357.98 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.375227E+12 | 0.842996E+11 | ||||
Minimum of Months | 0.286300E+11 | 26357.98 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.326575E+11 | 26357.98 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.296499E+10 | 2483.65 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.269775E+10 | 2483.65 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.307725E+10 | 2483.65 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.290339E+10 | 2483.65 | 01-APR-09:09 | 0.434394E+10 | 2920.89 | 01-APR-09:09 |
May | 0.302112E+10 | 2483.65 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.296946E+10 | 2483.65 | 01-JUN-08:09 | 0.441346E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.295505E+10 | 2483.65 | 01-JUL-09:09 | 0.444442E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.307725E+10 | 2483.65 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.290339E+10 | 2483.65 | 01-SEP-08:09 | 0.434278E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.296499E+10 | 2483.65 | 02-OCT-08:09 | 0.445903E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.286713E+10 | 2483.65 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.295505E+10 | 2483.65 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.353568E+11 | 0.529230E+11 | ||||
Minimum of Months | 0.269775E+10 | 2483.65 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.307725E+10 | 2483.65 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.296499E+10 | 2483.65 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.269775E+10 | 2483.65 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.307725E+10 | 2483.65 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.290339E+10 | 2483.65 | 01-APR-09:09 | 0.651995E+09 | 438.40 | 01-APR-09:09 |
May | 0.302112E+10 | 2483.65 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.296946E+10 | 2483.65 | 01-JUN-08:09 | 0.662429E+09 | 438.40 | 01-JUN-08:09 |
July | 0.295505E+10 | 2483.65 | 01-JUL-09:09 | 0.667077E+09 | 438.40 | 01-JUL-09:09 |
August | 0.307725E+10 | 2483.65 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.290339E+10 | 2483.65 | 01-SEP-08:09 | 0.651820E+09 | 438.40 | 01-SEP-08:09 |
October | 0.296499E+10 | 2483.65 | 02-OCT-08:09 | 0.669269E+09 | 438.40 | 02-OCT-08:09 |
November | 0.286713E+10 | 2483.65 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.295505E+10 | 2483.65 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.353568E+11 | 0.794337E+10 | ||||
Minimum of Months | 0.269775E+10 | 2483.65 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.307725E+10 | 2483.65 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.141555E+09 | 118.58 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.128796E+09 | 118.58 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.146915E+09 | 118.58 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.138614E+09 | 118.58 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.144235E+09 | 118.58 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.141768E+09 | 118.58 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.141081E+09 | 118.58 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.146915E+09 | 118.58 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.138614E+09 | 118.58 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.141555E+09 | 118.58 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.136883E+09 | 118.58 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.141081E+09 | 118.58 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.168801E+10 | 0.00 | 0.00 | ||
Minimum of Months | 0.128796E+09 | 118.58 | 0.00 | 0.00 | |
Maximum of Months | 0.146915E+09 | 118.58 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.699524E+09 | 0.368451E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221400E+09 | 52921804.84 |
February | 0.638757E+09 | 0.335241E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299740E+09 | 2807109.43 |
March | 0.730614E+09 | 0.382401E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583882E+09 | 5609378.59 |
April | 0.690691E+09 | 0.360796E+10 | 0.410339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588874E+09 | 219409.78 |
May | 0.715069E+09 | 0.375426E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634927E+09 | 2144748.55 |
June | 0.705176E+09 | 0.369006E+10 | 0.416906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579340E+09 | 4632503.56 |
July | 0.700584E+09 | 0.367216E+10 | 0.419831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317252E+09 | 2495841.84 |
August | 0.730614E+09 | 0.382401E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425192E+09 | 4597780.25 |
September | 0.690691E+09 | 0.360796E+10 | 0.410229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300154E+09 | 2472935.57 |
October | 0.699524E+09 | 0.368451E+10 | 0.421210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235613E+09 | 3739476.63 |
November | 0.673027E+09 | 0.356290E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185577E+09 | 15200062.41 |
December | 0.700584E+09 | 0.367216E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152756E+09 | 74005376.73 |
Annual Sum or Average | 0.837485E+10 | 0.439369E+11 | 0.499923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452471E+10 | 0.170846E+09 |
Minimum of Months | 0.638757E+09 | 0.335241E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152756E+09 | 219409.78 |
Maximum of Months | 0.730614E+09 | 0.382401E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634927E+09 | 74005376.73 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.314662E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191319E+09 | 45055931.77 |
February | 0.201852E+11 | 0.286300E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259475E+09 | 2161581.43 |
March | 0.230879E+11 | 0.326575E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507081E+09 | 4309569.02 |
April | 0.218263E+11 | 0.308125E+11 | 0.691935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511941E+09 | 120064.12 |
May | 0.225967E+11 | 0.320618E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553405E+09 | 1252709.24 |
June | 0.222841E+11 | 0.315136E+11 | 0.703008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507913E+09 | 3118332.63 |
July | 0.221389E+11 | 0.313607E+11 | 0.707940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276446E+09 | 1446355.10 |
August | 0.230879E+11 | 0.326575E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370413E+09 | 3667848.75 |
September | 0.218263E+11 | 0.308125E+11 | 0.691749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260315E+09 | 1915288.18 |
October | 0.221054E+11 | 0.314662E+11 | 0.710266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203737E+09 | 2949384.63 |
November | 0.212681E+11 | 0.304277E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160218E+09 | 12696668.76 |
December | 0.221389E+11 | 0.313607E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131637E+09 | 62930456.72 |
Annual Sum or Average | 0.264651E+12 | 0.375227E+12 | 0.842996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393390E+10 | 0.141624E+09 |
Minimum of Months | 0.201852E+11 | 0.286300E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131637E+09 | 120064.12 |
Maximum of Months | 0.230879E+11 | 0.326575E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553405E+09 | 62930456.72 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.296499E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99155135.05 | 25962017.67 |
February | 0.190200E+10 | 0.269775E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134436E+09 | 1898736.83 |
March | 0.217552E+10 | 0.307725E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262389E+09 | 3091307.41 |
April | 0.205665E+10 | 0.290339E+10 | 0.434394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267115E+09 | 125267.67 |
May | 0.212923E+10 | 0.302112E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289341E+09 | 1023247.46 |
June | 0.209978E+10 | 0.296946E+10 | 0.441346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265061E+09 | 2055710.58 |
July | 0.208610E+10 | 0.295505E+10 | 0.444442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144856E+09 | 1157101.08 |
August | 0.217552E+10 | 0.307725E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193728E+09 | 2160988.98 |
September | 0.205665E+10 | 0.290339E+10 | 0.434278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135898E+09 | 1281339.38 |
October | 0.208295E+10 | 0.296499E+10 | 0.445903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106209E+09 | 2078053.73 |
November | 0.200405E+10 | 0.286713E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83411485.12 | 7734125.40 |
December | 0.208610E+10 | 0.295505E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68852918.66 | 35722558.72 |
Annual Sum or Average | 0.249375E+11 | 0.353568E+11 | 0.529230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205045E+10 | 84290454.92 |
Minimum of Months | 0.190200E+10 | 0.269775E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68852918.66 | 125267.67 |
Maximum of Months | 0.217552E+10 | 0.307725E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289341E+09 | 35722558.72 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.296499E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 99606550.67 | 25302931.56 |
February | 0.190200E+10 | 0.269775E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135057E+09 | 1630626.04 |
March | 0.217552E+10 | 0.307725E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264206E+09 | 2776965.18 |
April | 0.205665E+10 | 0.290339E+10 | 0.651995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268651E+09 | 94179.55 |
May | 0.212923E+10 | 0.302112E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290637E+09 | 887629.20 |
June | 0.209978E+10 | 0.296946E+10 | 0.662429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266349E+09 | 1914065.37 |
July | 0.208610E+10 | 0.295505E+10 | 0.667077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145441E+09 | 1009342.30 |
August | 0.217552E+10 | 0.307725E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194747E+09 | 2052090.12 |
September | 0.205665E+10 | 0.290339E+10 | 0.651820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136541E+09 | 1165178.07 |
October | 0.208295E+10 | 0.296499E+10 | 0.669269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106674E+09 | 1890270.26 |
November | 0.200405E+10 | 0.286713E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83788758.98 | 7389262.19 |
December | 0.208610E+10 | 0.295505E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69008916.13 | 35050045.31 |
Annual Sum or Average | 0.249375E+11 | 0.353568E+11 | 0.794337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206071E+10 | 81162585.17 |
Minimum of Months | 0.190200E+10 | 0.269775E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69008916.13 | 94179.55 |
Maximum of Months | 0.217552E+10 | 0.307725E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290637E+09 | 35050045.31 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.165769E+09 | 0.141555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2445216.70 | 0.384490E+09 |
February | 0.151369E+09 | 0.128796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21851130.09 | 0.208260E+09 |
March | 0.173136E+09 | 0.146915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165001E+09 | 0.101332E+09 |
April | 0.163676E+09 | 0.138614E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279841E+09 | 28838086.12 |
May | 0.169453E+09 | 0.144235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332167E+09 | 65954884.01 |
June | 0.167108E+09 | 0.141768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295531E+09 | 59131829.15 |
July | 0.166020E+09 | 0.141081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109973E+09 | 0.124248E+09 |
August | 0.173136E+09 | 0.146915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172939E+09 | 0.111865E+09 |
September | 0.163676E+09 | 0.138614E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99773962.90 | 0.126151E+09 |
October | 0.165769E+09 | 0.141555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23562013.47 | 0.199117E+09 |
November | 0.159490E+09 | 0.136883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3963895.48 | 0.331900E+09 |
December | 0.166020E+09 | 0.141081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 780412.43 | 0.428340E+09 |
Annual Sum or Average | 0.198462E+10 | 0.168801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150783E+10 | 0.216963E+10 |
Minimum of Months | 0.151369E+09 | 0.128796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 780412.43 | 28838086.12 |
Maximum of Months | 0.173136E+09 | 0.146915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332167E+09 | 0.428340E+09 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 785.10 | 02-JAN-15:09 | 3086.37 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 624.60 | 08-JAN-19:10 | 1382.15 | 07-JAN-05:00 |
February | 785.10 | 01-FEB-15:09 | 3086.37 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 798.05 | 20-FEB-19:45 | 99.30 | 26-FEB-06:40 |
March | 785.10 | 01-MAR-15:09 | 3086.37 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1743.74 | 19-MAR-18:10 | 271.21 | 14-MAR-22:00 |
April | 785.10 | 01-APR-10:09 | 3086.37 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1077.74 | 02-APR-19:00 | 68.00 | 22-APR-02:40 |
May | 785.10 | 01-MAY-14:09 | 3086.37 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1384.40 | 07-MAY-18:10 | 527.90 | 08-MAY-22:00 |
June | 785.10 | 01-JUN-14:09 | 3086.37 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1293.79 | 11-JUN-19:00 | 459.89 | 20-JUN-23:20 |
July | 785.10 | 01-JUL-10:09 | 3086.37 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 711.29 | 25-JUL-20:50 | 305.75 | 19-JUL-20:40 |
August | 785.10 | 01-AUG-14:09 | 3086.37 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1038.44 | 01-AUG-21:00 | 366.24 | 23-AUG-20:05 |
September | 785.10 | 01-SEP-14:09 | 3086.37 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 613.28 | 10-SEP-14:55 | 261.77 | 15-SEP-22:00 |
October | 785.10 | 02-OCT-14:09 | 3086.37 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 883.81 | 08-OCT-18:10 | 179.00 | 23-OCT-04:50 |
November | 785.10 | 01-NOV-14:09 | 3086.37 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 370.68 | 02-NOV-20:10 | 315.33 | 25-NOV-05:05 |
December | 785.10 | 01-DEC-15:09 | 3086.37 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 420.30 | 10-DEC-19:10 | 637.92 | 21-DEC-04:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 785.10 | 3086.37 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 370.68 | 68.00 | |||||
Maximum of Months | 785.10 | 3086.37 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1743.74 | 1382.15 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 26357.98 | 02-JAN-09:09 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 535.38 | 08-JAN-19:10 | 1178.96 | 07-JAN-05:00 |
February | 24809.68 | 01-FEB-15:09 | 26357.98 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 688.55 | 20-FEB-19:08 | 90.63 | 26-FEB-06:55 |
March | 24809.68 | 01-MAR-15:09 | 26357.98 | 01-MAR-09:09 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1495.21 | 19-MAR-18:10 | 206.58 | 03-MAR-05:40 |
April | 24809.68 | 01-APR-10:09 | 26357.98 | 01-APR-09:09 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 934.30 | 02-APR-18:45 | 35.25 | 22-APR-02:40 |
May | 24809.68 | 01-MAY-14:09 | 26357.98 | 01-MAY-08:09 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1192.63 | 07-MAY-18:10 | 328.88 | 08-MAY-22:00 |
June | 24809.68 | 01-JUN-14:09 | 26357.98 | 01-JUN-08:09 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1109.39 | 11-JUN-19:00 | 241.31 | 20-JUN-23:20 |
July | 24809.68 | 01-JUL-10:09 | 26357.98 | 01-JUL-09:09 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 619.52 | 25-JUL-20:45 | 179.99 | 19-JUL-20:40 |
August | 24809.68 | 01-AUG-14:09 | 26357.98 | 01-AUG-08:09 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 890.44 | 01-AUG-21:00 | 269.11 | 19-AUG-23:55 |
September | 24809.68 | 01-SEP-14:09 | 26357.98 | 01-SEP-08:09 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 527.24 | 13-SEP-20:10 | 195.18 | 15-SEP-22:10 |
October | 24809.68 | 02-OCT-14:09 | 26357.98 | 02-OCT-08:09 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 757.44 | 08-OCT-18:10 | 141.97 | 23-OCT-04:40 |
November | 24809.68 | 01-NOV-14:09 | 26357.98 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 325.12 | 02-NOV-21:52 | 257.46 | 25-NOV-05:15 |
December | 24809.68 | 01-DEC-15:09 | 26357.98 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.90 | 10-DEC-19:10 | 545.02 | 21-DEC-04:35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 24809.68 | 26357.98 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 325.12 | 35.25 | |||||
Maximum of Months | 24809.68 | 26357.98 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1495.21 | 1178.96 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2483.65 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 284.85 | 08-JAN-19:10 | 740.89 | 07-JAN-05:00 |
February | 2337.76 | 01-FEB-15:09 | 2483.65 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 363.49 | 20-FEB-19:10 | 66.93 | 24-FEB-01:00 |
March | 2337.76 | 01-MAR-15:09 | 2483.65 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 795.24 | 19-MAR-18:10 | 156.55 | 14-MAR-22:00 |
April | 2337.76 | 01-APR-10:09 | 2483.65 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 491.51 | 02-APR-19:00 | 37.07 | 22-APR-02:40 |
May | 2337.76 | 01-MAY-14:09 | 2483.65 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 631.39 | 07-MAY-18:10 | 255.57 | 08-MAY-22:00 |
June | 2337.76 | 01-JUN-14:09 | 2483.65 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 590.04 | 11-JUN-19:00 | 213.90 | 20-JUN-23:20 |
July | 2337.76 | 01-JUL-10:09 | 2483.65 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 329.09 | 25-JUL-20:45 | 137.76 | 19-JUL-20:40 |
August | 2337.76 | 01-AUG-14:09 | 2483.65 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 473.59 | 01-AUG-21:00 | 179.10 | 23-AUG-20:05 |
September | 2337.76 | 01-SEP-14:09 | 2483.65 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 279.69 | 10-SEP-14:55 | 138.91 | 15-SEP-22:00 |
October | 2337.76 | 02-OCT-14:09 | 2483.65 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 403.03 | 08-OCT-18:10 | 81.72 | 23-OCT-23:20 |
November | 2337.76 | 01-NOV-14:09 | 2483.65 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 169.05 | 02-NOV-20:10 | 149.11 | 25-NOV-05:00 |
December | 2337.76 | 01-DEC-15:09 | 2483.65 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 191.68 | 10-DEC-19:10 | 314.20 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2337.76 | 2483.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 169.05 | 37.07 | |||||
Maximum of Months | 2337.76 | 2483.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 795.24 | 740.89 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2483.65 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 284.85 | 08-JAN-19:10 | 703.38 | 07-JAN-05:00 |
February | 2337.76 | 01-FEB-15:09 | 2483.65 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 363.49 | 20-FEB-19:10 | 58.81 | 24-FEB-01:00 |
March | 2337.76 | 01-MAR-15:09 | 2483.65 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 795.24 | 19-MAR-18:10 | 141.82 | 14-MAR-22:00 |
April | 2337.76 | 01-APR-10:09 | 2483.65 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 491.51 | 02-APR-19:00 | 28.87 | 22-APR-02:40 |
May | 2337.76 | 01-MAY-14:09 | 2483.65 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 631.39 | 07-MAY-18:10 | 230.86 | 08-MAY-22:00 |
June | 2337.76 | 01-JUN-14:09 | 2483.65 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 590.04 | 11-JUN-19:00 | 190.25 | 20-JUN-23:20 |
July | 2337.76 | 01-JUL-10:09 | 2483.65 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 328.52 | 25-JUL-20:45 | 118.84 | 19-JUL-20:40 |
August | 2337.76 | 01-AUG-14:09 | 2483.65 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 473.59 | 01-AUG-21:00 | 164.28 | 23-AUG-20:05 |
September | 2337.76 | 01-SEP-14:09 | 2483.65 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 279.69 | 10-SEP-14:55 | 123.46 | 15-SEP-22:00 |
October | 2337.76 | 02-OCT-14:09 | 2483.65 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 403.04 | 08-OCT-18:10 | 81.04 | 23-OCT-05:00 |
November | 2337.76 | 01-NOV-14:09 | 2483.65 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 169.05 | 02-NOV-20:10 | 144.97 | 25-NOV-05:00 |
December | 2337.76 | 01-DEC-15:09 | 2483.65 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 191.68 | 10-DEC-19:10 | 306.06 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2337.76 | 2483.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 169.05 | 28.87 | |||||
Maximum of Months | 2337.76 | 2483.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 795.24 | 703.38 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 186.05 | 02-JAN-15:09 | 118.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.01 | 11-JAN-08:63 | 1539.69 | 24-JAN-08:61 |
February | 186.05 | 01-FEB-15:09 | 118.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.80 | 26-FEB-12:55 | 1216.36 | 21-FEB-09:53 |
March | 186.05 | 01-MAR-15:09 | 118.58 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2203.01 | 03-MAR-12:02 | 1639.32 | 14-MAR-11:02 |
April | 186.05 | 01-APR-10:09 | 118.58 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1405.53 | 09-APR-11:02 | 1266.47 | 14-APR-15:53 |
May | 186.05 | 01-MAY-14:09 | 118.58 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2389.37 | 05-MAY-11:02 | 1852.43 | 01-MAY-12:52 |
June | 186.05 | 01-JUN-14:09 | 118.58 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1359.48 | 16-JUN-11:02 | 1597.09 | 30-JUN-12:53 |
July | 186.05 | 01-JUL-10:09 | 118.58 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 861.33 | 01-JUL-11:03 | 1567.96 | 03-JUL-12:53 |
August | 186.05 | 01-AUG-14:09 | 118.58 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1894.53 | 16-AUG-11:02 | 1938.60 | 25-AUG-11:02 |
September | 186.05 | 01-SEP-14:09 | 118.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 719.78 | 01-SEP-11:03 | 1703.25 | 15-SEP-16:53 |
October | 186.05 | 02-OCT-14:09 | 118.58 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.43 | 19-OCT-11:05 | 1189.42 | 29-OCT-16:53 |
November | 186.05 | 01-NOV-14:09 | 118.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.04 | 18-NOV-12:55 | 1227.46 | 09-NOV-15:55 |
December | 186.05 | 01-DEC-15:09 | 118.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.35 | 29-DEC-18:55 | 1221.26 | 21-DEC-08:61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 186.05 | 118.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.35 | 1189.42 | ||||
Maximum of Months | 186.05 | 118.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2389.37 | 1938.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 38542.58 | 15-JAN-21:42 | 0.00 | 685.86 | 1839.43 | 0.00 | 0.00 | 0.00 | 0.00 | 104.14 | 0.00 |
February | 39926.12 | 23-FEB-02:23 | 0.00 | 685.86 | 2452.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 37947.34 | 02-MAR-22:23 | 0.00 | 685.86 | 2452.57 | 0.00 | 0.00 | 0.00 | 0.00 | 193.31 | 0.00 |
April | 37623.56 | 26-APR-22:42 | 0.00 | 685.86 | 2452.57 | 0.00 | 0.00 | 0.00 | 0.00 | 281.50 | 0.00 |
May | 37128.30 | 11-MAY-01:23 | 0.00 | 514.39 | 1839.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.04 |
June | 37832.97 | 27-JUN-02:63 | 0.00 | 514.39 | 1839.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 38515.54 | 20-JUL-02:63 | 0.00 | 514.39 | 1839.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 37388.19 | 24-AUG-02:63 | 0.00 | 514.39 | 1839.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 |
September | 37087.47 | 12-SEP-21:23 | 0.00 | 685.86 | 2452.57 | 0.00 | 0.00 | 0.00 | 0.00 | 28.16 | 0.00 |
October | 36512.61 | 08-OCT-21:23 | 0.00 | 685.86 | 1839.43 | 0.00 | 0.00 | 0.00 | 0.00 | 52.76 | 0.00 |
November | 36435.94 | 05-NOV-21:23 | 0.00 | 685.86 | 1839.43 | 0.00 | 0.00 | 0.00 | 0.00 | 48.38 | 0.00 |
December | 39478.47 | 20-DEC-21:42 | 0.00 | 2743.44 | 2452.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 36435.94 | 0.00 | 514.39 | 1839.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39926.12 | 0.00 | 2743.44 | 2452.57 | 0.00 | 0.00 | 0.00 | 0.00 | 281.50 | 196.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 140531.10 | 13-JAN-23:03 | 0.00 | 5857.33 | 4135.65 | 0.00 | 0.00 | 0.00 | 0.00 | 47.32 | 0.00 |
February | 146043.79 | 24-FEB-21:07 | 0.00 | 35143.97 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 97.08 | 0.00 |
March | 144952.94 | 02-MAR-22:23 | 0.00 | 5857.33 | 4135.65 | 0.00 | 0.00 | 0.00 | 0.00 | 203.02 | 0.00 |
April | 139116.69 | 26-APR-22:42 | 0.00 | 5857.33 | 4135.65 | 0.00 | 0.00 | 0.00 | 0.00 | 288.21 | 0.00 |
May | 127221.57 | 10-MAY-20:08 | 0.00 | 29286.64 | 5169.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.87 |
June | 120748.87 | 07-JUN-20:08 | 0.00 | 29286.64 | 5169.56 | 0.00 | 0.00 | 0.00 | 0.00 | 231.39 | 0.00 |
July | 135106.21 | 30-JUL-20:03 | 0.00 | 5857.33 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 426.08 | 0.00 |
August | 125978.50 | 23-AUG-20:08 | 0.00 | 23429.32 | 4135.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.37 |
September | 128608.56 | 12-SEP-21:23 | 0.00 | 5857.33 | 4135.65 | 0.00 | 0.00 | 0.00 | 0.00 | 29.80 | 0.00 |
October | 132994.57 | 08-OCT-21:23 | 0.00 | 5857.33 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 58.14 | 0.00 |
November | 134520.17 | 24-NOV-21:08 | 0.00 | 29286.64 | 5169.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.18 |
December | 143765.57 | 26-DEC-21:07 | 0.00 | 35143.97 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 120748.87 | 0.00 | 5857.33 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 146043.79 | 0.00 | 35143.97 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 426.08 | 168.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24184.60 | 15-JAN-21:42 | 0.00 | 551.92 | 1947.26 | 0.00 | 0.00 | 0.00 | 0.00 | 24.78 | 0.00 |
February | 24430.62 | 23-FEB-01:42 | 0.00 | 551.92 | 2596.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22957.14 | 02-MAR-22:23 | 0.00 | 551.92 | 2596.34 | 0.00 | 0.00 | 0.00 | 0.00 | 78.97 | 0.00 |
April | 21915.65 | 26-APR-22:42 | 0.00 | 551.92 | 2596.34 | 0.00 | 0.00 | 0.00 | 0.00 | 134.29 | 0.00 |
May | 20469.29 | 10-MAY-20:06 | 0.00 | 2759.62 | 3245.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.53 |
June | 19807.83 | 07-JUN-20:06 | 0.00 | 2759.62 | 3245.43 | 0.00 | 0.00 | 0.00 | 0.00 | 121.11 | 0.00 |
July | 21678.05 | 30-JUL-20:03 | 0.00 | 551.92 | 1947.26 | 0.00 | 0.00 | 0.00 | 0.00 | 201.40 | 0.00 |
August | 20050.46 | 23-AUG-20:08 | 0.00 | 2207.69 | 2596.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.94 |
September | 21745.42 | 12-SEP-21:23 | 0.00 | 551.92 | 2596.34 | 0.00 | 0.00 | 0.00 | 0.00 | 12.35 | 0.00 |
October | 22159.36 | 08-OCT-21:23 | 0.00 | 551.92 | 1947.26 | 0.00 | 0.00 | 0.00 | 0.00 | 20.71 | 0.00 |
November | 22304.80 | 05-NOV-21:23 | 0.00 | 551.92 | 1947.26 | 0.00 | 0.00 | 0.00 | 0.00 | 16.87 | 0.00 |
December | 24631.92 | 20-DEC-21:42 | 0.00 | 2207.69 | 2596.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19807.83 | 0.00 | 551.92 | 1947.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24631.92 | 0.00 | 2759.62 | 3245.43 | 0.00 | 0.00 | 0.00 | 0.00 | 201.40 | 112.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21472.04 | 15-JAN-21:42 | 0.00 | 551.92 | 292.27 | 0.00 | 0.00 | 0.00 | 0.00 | 28.12 | 0.00 |
February | 21627.69 | 23-FEB-01:42 | 0.00 | 551.92 | 389.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20120.31 | 02-MAR-22:23 | 0.00 | 551.92 | 389.69 | 0.00 | 0.00 | 0.00 | 0.00 | 85.03 | 0.00 |
April | 19123.72 | 26-APR-22:42 | 0.00 | 551.92 | 389.69 | 0.00 | 0.00 | 0.00 | 0.00 | 139.97 | 0.00 |
May | 17618.65 | 10-MAY-20:06 | 0.00 | 2759.62 | 487.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.60 |
June | 17037.51 | 07-JUN-20:06 | 0.00 | 2759.62 | 487.12 | 0.00 | 0.00 | 0.00 | 0.00 | 123.95 | 0.00 |
July | 19177.39 | 30-JUL-20:03 | 0.00 | 551.92 | 292.27 | 0.00 | 0.00 | 0.00 | 0.00 | 202.13 | 0.00 |
August | 17319.77 | 23-AUG-20:08 | 0.00 | 2207.69 | 389.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.89 |
September | 18796.53 | 29-SEP-23:23 | 0.00 | 551.92 | 292.27 | 0.00 | 0.00 | 0.00 | 0.00 | 70.62 | 0.00 |
October | 19570.71 | 08-OCT-21:23 | 0.00 | 551.92 | 292.27 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | 0.00 |
November | 19744.94 | 05-NOV-21:23 | 0.00 | 551.92 | 292.27 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 | 0.00 |
December | 21743.30 | 20-DEC-21:42 | 0.00 | 2207.69 | 389.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17037.51 | 0.00 | 551.92 | 292.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21743.30 | 0.00 | 2759.62 | 487.12 | 0.00 | 0.00 | 0.00 | 0.00 | 202.13 | 108.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 19.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.77 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 6.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 6.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.08 |
April | 0.00 | 01-APR-00:03 | 0.00 | 19.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 |
May | 0.00 | 01-MAY-00:03 | 0.00 | 19.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 0.00 |
June | 0.00 | 01-JUN-00:03 | 0.00 | 19.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.92 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 13.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.65 |
August | 0.00 | 01-AUG-00:03 | 0.00 | 19.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.03 |
September | 0.00 | 01-SEP-00:03 | 0.00 | 19.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.40 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 6.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 |
November | 0.00 | 01-NOV-00:03 | 0.00 | 19.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 6.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 6.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 19.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 18.08 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.192802E+12 | 134277.31 | 04-JAN-13:20 | 0.730585E+10 | 4805.79 | 06-JAN-12:00 |
February | 0.181505E+12 | 139381.89 | 28-FEB-14:00 | 0.660271E+10 | 4804.78 | 02-FEB-12:30 |
March | 0.210799E+12 | 142200.80 | 28-MAR-14:00 | 0.732456E+10 | 4799.81 | 02-MAR-12:00 |
April | 0.210661E+12 | 145830.22 | 01-APR-13:00 | 0.702349E+10 | 4791.09 | 03-APR-11:39 |
May | 0.221802E+12 | 153115.26 | 06-MAY-14:00 | 0.722415E+10 | 4782.57 | 02-MAY-11:30 |
June | 0.219695E+12 | 153159.31 | 13-JUN-14:00 | 0.698840E+10 | 4775.22 | 01-JUN-11:00 |
July | 0.201227E+12 | 138017.47 | 21-JUL-14:00 | 0.716601E+10 | 4771.43 | 31-JUL-11:30 |
August | 0.211786E+12 | 144494.25 | 11-AUG-14:20 | 0.722757E+10 | 4776.33 | 31-AUG-11:09 |
September | 0.202156E+12 | 142570.85 | 30-SEP-11:09 | 0.699474E+10 | 4783.71 | 28-SEP-11:09 |
October | 0.199635E+12 | 138768.34 | 04-OCT-14:09 | 0.723924E+10 | 4793.53 | 31-OCT-11:30 |
November | 0.191109E+12 | 137186.97 | 18-NOV-12:00 | 0.703329E+10 | 4800.86 | 29-NOV-12:50 |
December | 0.192349E+12 | 133819.39 | 30-DEC-13:00 | 0.730117E+10 | 4805.28 | 28-DEC-12:09 |
Annual Sum or Average | 0.243553E+13 | 0.854312E+11 | ||||
Minimum of Months | 0.181505E+12 | 133819.39 | 0.660271E+10 | 4771.43 | ||
Maximum of Months | 0.221802E+12 | 153159.31 | 0.732456E+10 | 4805.79 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.412222E+11 | 0.112080E+11 | 0.164409E+11 | 0.00 | 0.372380E+11 | 0.00 | 0.00 | 0.866930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.375067E+11 | 0.996530E+10 | 0.149157E+11 | 0.00 | 0.340045E+11 | 0.00 | 0.00 | 0.851131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.427830E+11 | 0.106946E+11 | 0.168545E+11 | 0.00 | 0.384622E+11 | 0.00 | 0.00 | 0.102005E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.403658E+11 | 0.101044E+11 | 0.160187E+11 | 0.00 | 0.373927E+11 | 0.00 | 0.00 | 0.106780E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.420026E+11 | 0.102628E+11 | 0.166477E+11 | 0.00 | 0.387371E+11 | 0.00 | 0.00 | 0.114151E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.412843E+11 | 0.981656E+10 | 0.162750E+11 | 0.00 | 0.378858E+11 | 0.00 | 0.00 | 0.114434E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.410841E+11 | 0.102244E+11 | 0.163892E+11 | 0.00 | 0.378115E+11 | 0.00 | 0.00 | 0.957177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.427830E+11 | 0.103539E+11 | 0.168545E+11 | 0.00 | 0.384068E+11 | 0.00 | 0.00 | 0.103388E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.403658E+11 | 0.102772E+11 | 0.160144E+11 | 0.00 | 0.369089E+11 | 0.00 | 0.00 | 0.985900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.412222E+11 | 0.108961E+11 | 0.164431E+11 | 0.00 | 0.374851E+11 | 0.00 | 0.00 | 0.935888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.398617E+11 | 0.107570E+11 | 0.159174E+11 | 0.00 | 0.360856E+11 | 0.00 | 0.00 | 0.884878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.410841E+11 | 0.112799E+11 | 0.163871E+11 | 0.00 | 0.372472E+11 | 0.00 | 0.00 | 0.863508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.491565E+12 | 0.125840E+12 | 0.195158E+12 | 0.00 | 0.447666E+12 | 0.00 | 0.00 | 0.117530E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.375067E+11 | 0.981656E+10 | 0.149157E+11 | 0.00 | 0.340045E+11 | 0.00 | 0.00 | 0.851131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.427830E+11 | 0.112799E+11 | 0.168545E+11 | 0.00 | 0.387371E+11 | 0.00 | 0.00 | 0.114434E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.730585E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.660271E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.732456E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.702349E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.722415E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.698840E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.716601E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.722757E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.699474E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.723924E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.703329E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.730117E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.854312E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.660271E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.732456E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 34530.23 | 02-JAN-09:09 | 7996.55 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 21358.79 | 01-JAN-09:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 34530.23 | 01-FEB-09:09 | 7996.55 | 01-FEB-00:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 21358.79 | 01-FEB-06:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 34530.23 | 01-MAR-09:09 | 7996.55 | 01-MAR-00:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 21358.79 | 01-MAR-06:19 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 34530.23 | 01-APR-09:09 | 7996.55 | 01-APR-00:10 | 10771.04 | 01-APR-09:09 | 0.00 | 21358.79 | 01-APR-05:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 34530.23 | 01-MAY-08:09 | 7996.55 | 01-MAY-00:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 21358.79 | 01-MAY-05:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 34530.23 | 01-JUN-08:09 | 7996.55 | 01-JUN-00:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 21358.79 | 01-JUN-05:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 34530.23 | 01-JUL-09:09 | 7996.55 | 01-JUL-00:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 21358.79 | 01-JUL-06:19 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 34530.23 | 01-AUG-08:09 | 7996.55 | 01-AUG-00:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 21358.79 | 01-AUG-05:19 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 34530.23 | 01-SEP-08:09 | 7996.55 | 01-SEP-00:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 21358.79 | 01-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 34530.23 | 02-OCT-08:09 | 7996.55 | 01-OCT-00:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 21358.79 | 01-OCT-08:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 34530.23 | 01-NOV-08:09 | 7996.55 | 01-NOV-00:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 21358.79 | 01-NOV-06:49 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 34530.23 | 01-DEC-09:09 | 7996.55 | 01-DEC-00:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 21358.79 | 01-DEC-06:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 34530.23 | 7996.55 | 10771.04 | 0.00 | 21358.79 | 0.00 | 0.00 | |||||
Maximum of Months | 34530.23 | 7996.55 | 10771.04 | 0.00 | 21358.79 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 67617.24 | 04-JAN-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 72721.83 | 28-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 75540.74 | 28-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79170.16 | 01-APR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86455.20 | 06-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86499.24 | 13-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 71357.41 | 21-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 77834.18 | 11-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 75910.78 | 30-SEP-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72108.27 | 04-OCT-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 70526.90 | 18-NOV-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 67159.33 | 30-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 67159.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86499.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 134277.31 | 04-JAN-13:20 | 34530.23 | 10771.04 | 0.00 | 0.00 | 21358.79 | 0.00 | 0.00 | 67617.24 | 0.00 |
February | 139381.89 | 28-FEB-14:00 | 34530.23 | 10771.04 | 0.00 | 0.00 | 21358.79 | 0.00 | 0.00 | 72721.83 | 0.00 |
March | 142200.80 | 28-MAR-14:00 | 34530.23 | 10771.04 | 0.00 | 0.00 | 21358.79 | 0.00 | 0.00 | 75540.74 | 0.00 |
April | 145830.22 | 01-APR-13:00 | 34530.23 | 10771.04 | 0.00 | 0.00 | 21358.79 | 0.00 | 0.00 | 79170.16 | 0.00 |
May | 153115.26 | 06-MAY-14:00 | 34530.23 | 10771.04 | 0.00 | 0.00 | 21358.79 | 0.00 | 0.00 | 86455.20 | 0.00 |
June | 153159.31 | 13-JUN-14:00 | 34530.23 | 10771.04 | 0.00 | 0.00 | 21358.79 | 0.00 | 0.00 | 86499.24 | 0.00 |
July | 138017.47 | 21-JUL-14:00 | 34530.23 | 10771.04 | 0.00 | 0.00 | 21358.79 | 0.00 | 0.00 | 71357.41 | 0.00 |
August | 144494.25 | 11-AUG-14:20 | 34530.23 | 10771.04 | 0.00 | 0.00 | 21358.79 | 0.00 | 0.00 | 77834.18 | 0.00 |
September | 142570.85 | 30-SEP-11:09 | 34530.23 | 10771.04 | 0.00 | 0.00 | 21358.79 | 0.00 | 0.00 | 75910.78 | 0.00 |
October | 138768.34 | 04-OCT-14:09 | 34530.23 | 10771.04 | 0.00 | 0.00 | 21358.79 | 0.00 | 0.00 | 72108.27 | 0.00 |
November | 137186.97 | 18-NOV-12:00 | 34530.23 | 10771.04 | 0.00 | 0.00 | 21358.79 | 0.00 | 0.00 | 70526.90 | 0.00 |
December | 133819.39 | 30-DEC-13:00 | 34530.23 | 10771.04 | 0.00 | 0.00 | 21358.79 | 0.00 | 0.00 | 67159.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 133819.39 | 34530.23 | 10771.04 | 0.00 | 0.00 | 21358.79 | 0.00 | 0.00 | 67159.33 | 0.00 | |
Maximum of Months | 153159.31 | 34530.23 | 10771.04 | 0.00 | 0.00 | 21358.79 | 0.00 | 0.00 | 86499.24 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 4805.79 | 06-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 4804.78 | 02-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 4799.81 | 02-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 4791.09 | 03-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4782.57 | 02-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4775.22 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4771.43 | 31-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4776.33 | 31-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 4783.71 | 28-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 4793.53 | 31-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 4800.86 | 29-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 4805.28 | 28-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4771.43 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4805.79 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 32.17 | 24.56 | 0.00 | 24.56 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 | 24.60 | 0.00 | 24.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 24.67 | 0.00 | 24.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 60.17 | 24.76 | 0.00 | 24.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 59.83 | 24.84 | 0.00 | 24.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 63.83 | 24.92 | 0.00 | 24.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 67.50 | 24.72 | 0.00 | 24.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 52.50 | 24.72 | 0.00 | 24.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 53.17 | 24.65 | 0.00 | 24.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 40.00 | 24.59 | 0.00 | 24.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 24.57 | 0.00 | 24.57 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 24.54 | 0.00 | 24.54 |
Annual Sum or Average | 0.00 | 0.00 | 587.17 | 24.71 | 0.00 | 24.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 24.54 | 0.00 | 24.54 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 67.50 | 24.92 | 0.00 | 24.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.47 | 0.00 | 24.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 24.48 | 0.00 | 24.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 24.51 | 0.00 | 24.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 24.51 | 0.00 | 24.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 24.51 | 0.00 | 24.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 24.52 | 0.00 | 24.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 24.49 | 0.00 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 24.50 | 0.00 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 24.50 | 0.00 | 24.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.48 | 0.00 | 24.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.47 | 0.00 | 24.47 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.47 | 0.00 | 24.47 |
Annual Sum or Average | 0.00 | 0.00 | 116.50 | 24.51 | 0.00 | 24.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.47 | 0.00 | 24.47 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 24.52 | 0.00 | 24.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 68.00 | 24.89 | 0.00 | 24.89 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 65.00 | 24.93 | 0.00 | 24.93 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 24.94 | 0.00 | 24.94 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 64.00 | 24.91 | 0.00 | 24.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 65.50 | 24.87 | 0.00 | 24.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 65.33 | 24.89 | 0.00 | 24.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 69.67 | 24.75 | 0.00 | 24.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 24.79 | 0.00 | 24.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 62.50 | 24.82 | 0.00 | 24.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 60.83 | 24.81 | 0.00 | 24.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 62.50 | 24.84 | 0.00 | 24.84 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 67.17 | 24.84 | 0.00 | 24.84 |
Annual Sum or Average | 0.00 | 0.00 | 777.17 | 24.86 | 0.00 | 24.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 24.75 | 0.00 | 24.75 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 69.67 | 24.94 | 0.00 | 24.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 61.83 | 24.79 | 0.00 | 24.79 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 63.17 | 24.81 | 0.00 | 24.81 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 65.67 | 24.81 | 0.00 | 24.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 60.83 | 24.78 | 0.00 | 24.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 59.83 | 24.77 | 0.00 | 24.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 60.67 | 24.79 | 0.00 | 24.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 60.33 | 24.66 | 0.00 | 24.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 50.33 | 24.69 | 0.00 | 24.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 56.50 | 24.72 | 0.00 | 24.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 54.17 | 24.72 | 0.00 | 24.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 56.67 | 24.75 | 0.00 | 24.75 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 58.50 | 24.76 | 0.00 | 24.76 |
Annual Sum or Average | 0.00 | 0.00 | 708.50 | 24.76 | 0.00 | 24.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 50.33 | 24.66 | 0.00 | 24.66 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 65.67 | 24.81 | 0.00 | 24.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 410.67 | 23.89 | 0.00 | 23.89 |
February | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 23.89 |
March | 0.00 | 0.00 | 422.00 | 23.89 | 0.00 | 23.89 |
April | 0.00 | 0.00 | 405.00 | 23.89 | 0.00 | 23.89 |
May | 32.17 | 23.89 | 418.00 | 23.89 | 32.17 | 23.89 |
June | 1.83 | 23.89 | 408.00 | 23.89 | 1.83 | 23.89 |
July | 1.83 | 23.89 | 415.00 | 23.89 | 1.83 | 23.89 |
August | 30.67 | 23.89 | 422.00 | 23.89 | 30.67 | 23.89 |
September | 4.83 | 23.89 | 405.00 | 23.89 | 4.83 | 23.89 |
October | 16.50 | 23.89 | 414.00 | 23.89 | 16.50 | 23.89 |
November | 0.00 | 0.00 | 399.00 | 23.89 | 0.00 | 23.89 |
December | 0.00 | 0.00 | 414.17 | 23.89 | 0.00 | 23.89 |
Annual Sum or Average | 87.83 | 23.89 | 4908.83 | 23.89 | 87.83 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 23.89 |
Maximum of Months | 32.17 | 23.89 | 422.00 | 23.89 | 32.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.50 | 23.89 | 413.17 | 23.89 | 10.50 | 23.89 |
February | 4.50 | 23.89 | 376.00 | 23.89 | 4.50 | 23.89 |
March | 16.33 | 23.89 | 422.00 | 23.89 | 16.33 | 23.89 |
April | 88.83 | 23.89 | 405.00 | 23.89 | 88.83 | 23.89 |
May | 251.67 | 23.89 | 418.00 | 23.89 | 251.67 | 23.89 |
June | 225.17 | 23.89 | 408.00 | 23.89 | 225.17 | 23.89 |
July | 84.50 | 23.89 | 415.00 | 23.89 | 84.50 | 23.89 |
August | 292.17 | 23.89 | 422.00 | 23.89 | 292.17 | 23.89 |
September | 232.17 | 23.89 | 405.00 | 23.89 | 232.17 | 23.89 |
October | 237.33 | 23.89 | 414.00 | 23.89 | 237.33 | 23.89 |
November | 93.33 | 23.89 | 399.00 | 23.89 | 93.33 | 23.89 |
December | 32.50 | 23.89 | 414.83 | 23.89 | 32.50 | 23.89 |
Annual Sum or Average | 1569.00 | 23.89 | 4912.00 | 23.89 | 1569.00 | 23.89 |
Minimum of Months | 4.50 | 23.89 | 376.00 | 23.89 | 4.50 | 23.89 |
Maximum of Months | 292.17 | 23.89 | 422.00 | 23.89 | 292.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 414.00 | 23.89 | 0.00 | 23.89 |
February | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 23.89 |
March | 0.00 | 0.00 | 422.00 | 23.89 | 0.00 | 23.89 |
April | 4.50 | 23.89 | 405.00 | 23.89 | 4.50 | 23.89 |
May | 71.17 | 23.89 | 418.00 | 23.89 | 71.17 | 23.89 |
June | 49.33 | 23.89 | 408.00 | 23.89 | 49.33 | 23.89 |
July | 2.50 | 23.89 | 415.00 | 23.89 | 2.50 | 23.89 |
August | 84.50 | 23.89 | 422.00 | 23.89 | 84.50 | 23.89 |
September | 26.50 | 23.89 | 405.00 | 23.89 | 26.50 | 23.89 |
October | 21.00 | 23.89 | 414.00 | 23.89 | 21.00 | 23.89 |
November | 0.00 | 0.00 | 399.00 | 23.89 | 0.00 | 23.89 |
December | 0.00 | 0.00 | 415.00 | 23.89 | 0.00 | 23.89 |
Annual Sum or Average | 259.50 | 23.89 | 4913.00 | 23.89 | 259.50 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 23.89 |
Maximum of Months | 84.50 | 23.89 | 422.00 | 23.89 | 84.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 23.89 | 414.00 | 23.89 | 1.33 | 23.89 |
February | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 23.89 |
March | 2.50 | 23.89 | 422.00 | 23.89 | 2.50 | 23.89 |
April | 24.67 | 23.89 | 405.00 | 23.89 | 24.67 | 23.89 |
May | 114.17 | 23.89 | 418.00 | 23.89 | 114.17 | 23.89 |
June | 92.50 | 23.89 | 408.00 | 23.89 | 92.50 | 23.89 |
July | 11.00 | 23.89 | 415.00 | 23.89 | 11.00 | 23.89 |
August | 149.00 | 23.89 | 422.00 | 23.89 | 149.00 | 23.89 |
September | 66.67 | 23.89 | 405.00 | 23.89 | 66.67 | 23.89 |
October | 72.00 | 23.89 | 414.00 | 23.89 | 72.00 | 23.89 |
November | 4.17 | 23.89 | 399.00 | 23.89 | 4.17 | 23.89 |
December | 1.50 | 23.89 | 415.00 | 23.89 | 1.50 | 23.89 |
Annual Sum or Average | 539.50 | 23.89 | 4913.00 | 23.89 | 539.50 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 23.89 |
Maximum of Months | 149.00 | 23.89 | 422.00 | 23.89 | 149.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 412.17 | 29.50 | 414.00 | 29.48 | 412.17 | 29.49 |
February | 376.00 | 30.21 | 376.00 | 30.21 | 376.00 | 30.21 |
March | 422.00 | 30.44 | 422.00 | 30.44 | 422.00 | 30.44 |
April | 405.00 | 30.55 | 405.00 | 30.55 | 405.00 | 30.55 |
May | 418.00 | 30.47 | 418.00 | 30.47 | 418.00 | 30.47 |
June | 408.00 | 30.52 | 408.00 | 30.52 | 408.00 | 30.52 |
July | 415.00 | 28.88 | 415.00 | 28.88 | 415.00 | 28.88 |
August | 422.00 | 28.99 | 422.00 | 28.99 | 422.00 | 28.99 |
September | 405.00 | 29.16 | 405.00 | 29.16 | 405.00 | 29.16 |
October | 414.00 | 28.64 | 414.00 | 28.64 | 414.00 | 28.64 |
November | 399.00 | 28.93 | 399.00 | 28.93 | 399.00 | 28.93 |
December | 414.83 | 29.14 | 415.00 | 29.14 | 414.83 | 29.14 |
Annual Sum or Average | 4911.00 | 29.62 | 4913.00 | 29.61 | 4911.00 | 29.61 |
Minimum of Months | 376.00 | 28.64 | 376.00 | 28.64 | 376.00 | 28.64 |
Maximum of Months | 422.00 | 30.55 | 422.00 | 30.55 | 422.00 | 30.55 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.89001 | 52.94331 | 0.58026 | 12.10522 |
February | 376.00000 | 23.89005 | 52.50991 | 0.60506 | 12.73100 |
March | 422.00000 | 23.89004 | 53.51759 | 0.62931 | 13.37129 |
April | 405.00000 | 23.89000 | 55.51960 | 0.66421 | 14.32005 |
May | 418.00000 | 23.89012 | 57.51360 | -0.1283 | 5.51693 |
June | 408.00000 | 23.89026 | 56.22179 | -0.0903 | 5.36024 |
July | 415.00000 | 23.89002 | 54.24398 | -0.1751 | 5.76942 |
August | 422.00000 | 23.89001 | 59.00972 | -0.1782 | 5.83611 |
September | 405.00000 | 23.89001 | 58.01781 | -0.1900 | 5.87124 |
October | 414.00000 | 23.89001 | 58.83872 | 0.61787 | 13.06075 |
November | 399.00000 | 23.89001 | 56.29030 | 0.60666 | 12.76086 |
December | 415.00000 | 23.89000 | 54.37132 | 0.58114 | 12.11993 |
Annual Sum or Average | 4913.00000 | 23.89004 | 55.77142 | 0.29026 | 9.87122 |
Minimum of Months | 376.00000 | 23.89000 | 52.50991 | -0.1900 | 5.36024 |
Maximum of Months | 422.00000 | 23.89026 | 59.00972 | 0.66421 | 14.32005 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.89001 | 57.47846 | 0.62696 | 13.30946 |
February | 376.00000 | 23.89001 | 57.46808 | 0.64581 | 13.82443 |
March | 422.00000 | 23.89001 | 58.24609 | 0.66466 | 14.35199 |
April | 405.00000 | 23.89001 | 61.97502 | 0.69496 | 15.21429 |
May | 418.00000 | 23.89001 | 65.57394 | -0.1291 | 5.45677 |
June | 408.00000 | 23.89001 | 65.32139 | -0.1134 | 5.38602 |
July | 415.00000 | 23.89001 | 61.87397 | -0.1735 | 5.73142 |
August | 422.00000 | 23.89001 | 66.25199 | -0.1493 | 5.60215 |
September | 405.00000 | 23.89001 | 65.17297 | -0.1484 | 5.57423 |
October | 414.00000 | 23.89002 | 65.21980 | 0.66968 | 14.47498 |
November | 399.00000 | 23.89001 | 62.32833 | 0.65575 | 14.08028 |
December | 415.00000 | 23.89001 | 59.32643 | 0.63283 | 13.45702 |
Annual Sum or Average | 4913.00000 | 23.89001 | 62.21584 | 0.31966 | 10.50283 |
Minimum of Months | 376.00000 | 23.89001 | 57.46808 | -0.1735 | 5.38602 |
Maximum of Months | 422.00000 | 23.89002 | 66.25199 | 0.69496 | 15.21429 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.89042 | 51.02810 | 0.74429 | 16.81422 |
February | 376.00000 | 23.89038 | 51.34807 | 0.75478 | 17.13875 |
March | 422.00000 | 23.89015 | 53.37028 | 0.73630 | 16.53717 |
April | 405.00000 | 23.89001 | 57.10709 | 0.73174 | 16.35008 |
May | 418.00000 | 23.89004 | 59.82955 | -0.0604 | 5.26717 |
June | 408.00000 | 23.89001 | 59.66244 | -0.0485 | 5.23116 |
July | 415.00000 | 23.89001 | 56.75918 | -0.1136 | 5.42967 |
August | 422.00000 | 23.89001 | 60.84675 | -0.1017 | 5.43283 |
September | 405.00000 | 23.89001 | 58.94128 | -0.0768 | 5.33745 |
October | 414.00000 | 23.89002 | 58.30817 | 0.71956 | 16.01376 |
November | 399.00000 | 23.89006 | 54.76478 | 0.74052 | 16.66265 |
December | 415.00000 | 23.89028 | 52.17269 | 0.74387 | 16.78912 |
Annual Sum or Average | 4913.00000 | 23.89011 | 56.21416 | 0.39383 | 11.86545 |
Minimum of Months | 376.00000 | 23.89001 | 51.02810 | -0.1136 | 5.23116 |
Maximum of Months | 422.00000 | 23.89042 | 60.84675 | 0.75478 | 17.13875 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.89021 | 51.79799 | 0.72758 | 16.28389 |
February | 376.00000 | 23.89020 | 52.04194 | 0.73810 | 16.60702 |
March | 422.00000 | 23.89007 | 54.42342 | 0.72055 | 16.04734 |
April | 405.00000 | 23.89001 | 58.54315 | 0.72026 | 15.99193 |
May | 418.00000 | 23.89002 | 61.61063 | -0.0785 | 5.30723 |
June | 408.00000 | 23.89001 | 61.30585 | -0.0660 | 5.26569 |
July | 415.00000 | 23.89001 | 58.44928 | -0.1334 | 5.52177 |
August | 422.00000 | 23.89001 | 63.03609 | -0.1174 | 5.48985 |
September | 405.00000 | 23.89001 | 60.75942 | -0.0950 | 5.38955 |
October | 414.00000 | 23.89001 | 60.22673 | 0.70980 | 15.70525 |
November | 399.00000 | 23.89001 | 56.03608 | 0.72699 | 16.23147 |
December | 415.00000 | 23.89018 | 53.09842 | 0.72810 | 16.28849 |
Annual Sum or Average | 4913.00000 | 23.89006 | 57.65279 | 0.37809 | 11.62841 |
Minimum of Months | 376.00000 | 23.89001 | 51.79799 | -0.1334 | 5.26569 |
Maximum of Months | 422.00000 | 23.89021 | 63.03609 | 0.73810 | 16.60702 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 29.46770 | 59.97194 | 1.90156 | 70.15003 |
February | 376.00000 | 30.20556 | 59.04429 | 2.04144 | 75.50471 |
March | 422.00000 | 30.43919 | 60.28328 | 2.03989 | 75.02464 |
April | 405.00000 | 30.54700 | 69.15306 | 2.10749 | 78.10990 |
May | 418.00000 | 30.46642 | 77.22374 | 1.80555 | 63.47379 |
June | 408.00000 | 30.52335 | 77.61368 | 1.84006 | 64.81319 |
July | 415.00000 | 28.87804 | 72.73419 | 1.28516 | 42.18543 |
August | 422.00000 | 28.99359 | 82.85230 | 1.39363 | 47.19642 |
September | 405.00000 | 29.16328 | 80.08967 | 1.46545 | 50.29142 |
October | 414.00000 | 28.64336 | 80.06927 | 1.81576 | 66.31640 |
November | 399.00000 | 28.93145 | 72.86353 | 1.87531 | 69.04684 |
December | 415.00000 | 29.14331 | 64.83023 | 1.87590 | 69.04991 |
Annual Sum or Average | 4913.00000 | 29.61318 | 71.46996 | 1.78467 | 64.14713 |
Minimum of Months | 376.00000 | 28.64336 | 59.04429 | 1.28516 | 42.18543 |
Maximum of Months | 422.00000 | 30.54700 | 82.85230 | 2.10749 | 78.10990 |
Report: DXReportMonthly
For: PSZ-AC:1 COOLING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.379207E+11 | 0.120490E+11 | 637.46 | 0.293844E+11 | 0.853627E+10 | 0.00 | 1.00 | 02-JAN-21:08 | 0.00 | 01-JAN-00:03 | 52434.50 | 09-JAN-21:06 | 42703.85 | 15-JAN-21:42 | 15082.74 | 09-JAN-21:06 | 13902.86 | 08-JAN-19:07 | 0.00 | 01-JAN-00:03 |
February | 0.383555E+11 | 0.122444E+11 | 581.28 | 0.300503E+11 | 0.830521E+10 | 0.00 | 1.00 | 01-FEB-01:42 | 0.00 | 01-FEB-00:12 | 52327.77 | 14-FEB-23:03 | 44287.63 | 23-FEB-02:23 | 14616.74 | 14-FEB-21:06 | 14023.99 | 26-FEB-19:05 | 0.00 | 01-FEB-00:10 |
March | 0.477470E+11 | 0.152083E+11 | 654.16 | 0.365769E+11 | 0.111701E+11 | 0.00 | 1.00 | 01-MAR-01:03 | 0.00 | 01-MAR-00:12 | 52818.52 | 27-MAR-04:43 | 41846.17 | 02-MAR-22:23 | 16725.27 | 26-MAR-06:23 | 14121.64 | 26-MAR-18:05 | 0.00 | 01-MAR-00:10 |
April | 0.521946E+11 | 0.164606E+11 | 638.50 | 0.383438E+11 | 0.138508E+11 | 0.00 | 1.00 | 01-APR-04:43 | 0.00 | 01-APR-00:33 | 53066.24 | 20-APR-22:03 | 41463.62 | 26-APR-22:42 | 17801.54 | 20-APR-20:08 | 14800.33 | 30-APR-18:42 | 0.00 | 01-APR-00:03 |
May | 0.590742E+11 | 0.183182E+11 | 663.22 | 0.415696E+11 | 0.175046E+11 | 0.00 | 1.00 | 01-MAY-20:06 | 0.00 | 01-MAY-00:33 | 53532.61 | 28-MAY-21:23 | 41116.89 | 11-MAY-01:23 | 20289.13 | 28-MAY-21:23 | 14671.32 | 29-MAY-18:06 | 0.00 | 01-MAY-00:03 |
June | 0.622065E+11 | 0.190608E+11 | 645.19 | 0.444474E+11 | 0.177590E+11 | 0.00 | 1.00 | 01-JUN-01:23 | 0.00 | 01-JUN-00:33 | 53489.10 | 10-JUN-02:43 | 42107.94 | 27-JUN-02:43 | 19314.66 | 28-JUN-22:43 | 14508.33 | 11-JUN-18:42 | 0.00 | 01-JUN-00:03 |
July | 0.504339E+11 | 0.155472E+11 | 656.32 | 0.379723E+11 | 0.124617E+11 | 0.00 | 1.00 | 01-JUL-21:08 | 0.00 | 01-JUL-00:10 | 52738.38 | 07-JUL-20:08 | 42922.38 | 16-JUL-05:03 | 15571.43 | 07-JUL-20:08 | 14140.85 | 30-JUL-18:06 | 0.00 | 01-JUL-00:05 |
August | 0.517983E+11 | 0.158476E+11 | 652.20 | 0.354838E+11 | 0.163146E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:07 | 53412.89 | 25-AUG-02:43 | 41460.13 | 24-AUG-02:63 | 18804.74 | 25-AUG-02:43 | 14159.11 | 27-AUG-18:06 | 0.00 | 01-AUG-00:03 |
September | 0.473204E+11 | 0.146135E+11 | 629.16 | 0.332382E+11 | 0.140822E+11 | 0.00 | 1.00 | 01-SEP-00:03 | 0.00 | 01-SEP-00:07 | 52992.63 | 18-SEP-20:08 | 40780.82 | 06-SEP-04:03 | 16890.03 | 18-SEP-20:08 | 14185.23 | 04-SEP-18:06 | 0.00 | 01-SEP-00:03 |
October | 0.429493E+11 | 0.132755E+11 | 637.49 | 0.297974E+11 | 0.131520E+11 | 0.00 | 1.00 | 01-OCT-18:08 | 0.00 | 01-OCT-00:12 | 53013.22 | 27-OCT-20:08 | 40256.05 | 08-OCT-21:23 | 17008.04 | 14-OCT-21:08 | 13852.16 | 08-OCT-18:06 | 0.00 | 01-OCT-00:10 |
November | 0.398564E+11 | 0.124241E+11 | 615.63 | 0.288387E+11 | 0.110177E+11 | 0.00 | 1.00 | 01-NOV-20:06 | 0.00 | 01-NOV-00:07 | 53048.32 | 11-NOV-19:10 | 40295.67 | 05-NOV-21:23 | 16881.98 | 11-NOV-19:10 | 13970.48 | 19-NOV-19:07 | 0.00 | 01-NOV-00:03 |
December | 0.372808E+11 | 0.117475E+11 | 634.33 | 0.280920E+11 | 0.918872E+10 | 0.00 | 1.00 | 01-DEC-21:08 | 0.00 | 01-DEC-00:13 | 53137.30 | 18-DEC-21:10 | 43034.95 | 20-DEC-21:42 | 16781.25 | 18-DEC-21:10 | 13870.15 | 10-DEC-19:07 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.567138E+12 | 0.176797E+12 | 7644.92 | 0.413795E+12 | 0.153343E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.372808E+11 | 0.117475E+11 | 581.28 | 0.280920E+11 | 0.830521E+10 | 0.00 | 1.00 | 0.00 | 52327.77 | 40256.05 | 14616.74 | 13852.16 | 0.00 | |||||||
Maximum of Months | 0.622065E+11 | 0.190608E+11 | 663.22 | 0.444474E+11 | 0.177590E+11 | 0.00 | 1.00 | 0.00 | 53532.61 | 44287.63 | 20289.13 | 14800.33 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2 COOLING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.180636E+12 | 0.571603E+11 | 622.84 | 0.122970E+12 | 0.576667E+11 | 0.00 | 1.00 | 02-JAN-21:10 | 0.00 | 01-JAN-00:03 | 242616.70 | 09-JAN-21:08 | 165151.21 | 16-JAN-19:08 | 101395.30 | 09-JAN-21:08 | 63917.49 | 08-JAN-19:08 | 0.00 | 01-JAN-00:03 |
February | 0.176705E+12 | 0.562097E+11 | 572.05 | 0.120807E+12 | 0.558977E+11 | 0.00 | 1.00 | 01-FEB-21:08 | 0.00 | 01-FEB-00:12 | 241654.56 | 15-FEB-21:08 | 172895.35 | 24-FEB-21:07 | 97477.53 | 15-FEB-21:08 | 64540.50 | 26-FEB-19:07 | 0.00 | 01-FEB-00:10 |
March | 0.214037E+12 | 0.681738E+11 | 641.91 | 0.144629E+12 | 0.694074E+11 | 0.00 | 1.00 | 01-MAR-01:03 | 0.00 | 01-MAR-00:12 | 241203.05 | 24-MAR-20:08 | 169966.59 | 14-MAR-00:03 | 95391.30 | 24-MAR-20:08 | 64942.48 | 26-MAR-18:07 | 0.00 | 01-MAR-00:10 |
April | 0.230267E+12 | 0.720781E+11 | 618.37 | 0.144172E+12 | 0.860951E+11 | 0.00 | 1.00 | 01-APR-21:08 | 0.00 | 01-APR-00:07 | 245087.47 | 20-APR-20:10 | 166086.08 | 26-APR-22:42 | 109933.19 | 20-APR-20:10 | 67152.70 | 30-APR-18:42 | 0.00 | 01-APR-00:03 |
May | 0.248286E+12 | 0.763955E+11 | 638.32 | 0.144019E+12 | 0.104267E+12 | 0.00 | 1.00 | 01-MAY-20:08 | 0.00 | 01-MAY-00:07 | 248658.15 | 28-MAY-18:10 | 147580.09 | 29-MAY-18:08 | 124009.58 | 28-MAY-18:10 | 67354.09 | 29-MAY-18:08 | 0.00 | 01-MAY-00:03 |
June | 0.249047E+12 | 0.761662E+11 | 622.89 | 0.144160E+12 | 0.104887E+12 | 0.00 | 1.00 | 01-JUN-20:10 | 0.00 | 01-JUN-00:07 | 247979.74 | 03-JUN-21:10 | 147805.66 | 07-JUN-20:08 | 121320.71 | 03-JUN-21:10 | 66453.18 | 11-JUN-18:42 | 0.00 | 01-JUN-00:03 |
July | 0.206966E+12 | 0.639992E+11 | 633.74 | 0.129052E+12 | 0.779135E+11 | 0.00 | 1.00 | 01-JUL-21:10 | 0.00 | 01-JUL-00:05 | 243535.97 | 07-JUL-20:10 | 164792.45 | 30-JUL-20:03 | 105355.81 | 07-JUL-20:10 | 65096.12 | 30-JUL-18:08 | 0.00 | 01-JUL-00:05 |
August | 0.232502E+12 | 0.701766E+11 | 626.09 | 0.131483E+12 | 0.101019E+12 | 0.00 | 1.00 | 01-AUG-20:08 | 0.00 | 01-AUG-00:07 | 246932.27 | 14-AUG-20:08 | 143258.56 | 23-AUG-20:08 | 116448.05 | 14-AUG-20:08 | 65030.13 | 27-AUG-18:08 | 0.00 | 01-AUG-00:03 |
September | 0.219922E+12 | 0.668489E+11 | 610.80 | 0.127800E+12 | 0.921221E+11 | 0.00 | 1.00 | 01-SEP-20:08 | 0.00 | 01-SEP-00:07 | 245414.91 | 18-SEP-20:10 | 154726.09 | 29-SEP-23:23 | 112833.82 | 18-SEP-20:10 | 65080.67 | 13-SEP-20:07 | 0.00 | 01-SEP-00:03 |
October | 0.208735E+12 | 0.634586E+11 | 622.54 | 0.121200E+12 | 0.875352E+11 | 0.00 | 1.00 | 01-OCT-18:10 | 0.00 | 01-OCT-00:12 | 245282.35 | 14-OCT-21:10 | 156369.69 | 08-OCT-21:23 | 111726.86 | 14-OCT-21:10 | 63671.97 | 08-OCT-18:08 | 0.00 | 01-OCT-00:10 |
November | 0.192031E+12 | 0.591207E+11 | 604.01 | 0.117750E+12 | 0.742809E+11 | 0.00 | 1.00 | 01-NOV-20:08 | 0.00 | 01-NOV-00:07 | 244066.79 | 07-NOV-21:08 | 156262.37 | 04-NOV-00:03 | 108583.13 | 11-NOV-19:10 | 64139.53 | 19-NOV-19:08 | 0.00 | 01-NOV-00:03 |
December | 0.183267E+12 | 0.572781E+11 | 621.22 | 0.119879E+12 | 0.633884E+11 | 0.00 | 1.00 | 01-DEC-21:08 | 0.00 | 01-DEC-00:13 | 244646.97 | 10-DEC-19:08 | 162784.73 | 26-DEC-21:07 | 110534.17 | 09-DEC-22:10 | 63627.20 | 10-DEC-19:08 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.254240E+13 | 0.787066E+12 | 7434.80 | 0.156792E+13 | 0.974480E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.176705E+12 | 0.562097E+11 | 572.05 | 0.117750E+12 | 0.558977E+11 | 0.00 | 1.00 | 0.00 | 241203.05 | 143258.56 | 95391.30 | 63627.20 | 0.00 | |||||||
Maximum of Months | 0.249047E+12 | 0.763955E+11 | 641.91 | 0.144629E+12 | 0.104887E+12 | 0.00 | 1.00 | 0.00 | 248658.15 | 172895.35 | 124009.58 | 67354.09 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3 COOLING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.321082E+11 | 0.925199E+10 | 650.07 | 0.247659E+11 | 0.734232E+10 | 0.00 | 1.00 | 02-JAN-21:08 | 0.00 | 01-JAN-00:03 | 32538.41 | 09-JAN-21:06 | 26754.16 | 15-JAN-21:42 | 10139.70 | 09-JAN-21:06 | 8083.11 | 08-JAN-19:05 | 0.00 | 01-JAN-00:03 |
February | 0.302085E+11 | 0.879429E+10 | 588.63 | 0.232797E+11 | 0.692878E+10 | 0.00 | 1.00 | 01-FEB-01:42 | 0.00 | 01-FEB-00:12 | 32373.66 | 14-FEB-21:06 | 27223.99 | 23-FEB-01:42 | 9524.93 | 14-FEB-21:06 | 8159.43 | 26-FEB-19:05 | 0.00 | 01-FEB-00:10 |
March | 0.335156E+11 | 0.986964E+10 | 656.83 | 0.249465E+11 | 0.856908E+10 | 0.00 | 1.00 | 01-MAR-01:03 | 0.00 | 01-MAR-00:12 | 32519.86 | 28-MAR-22:03 | 25644.82 | 02-MAR-22:23 | 9707.99 | 14-MAR-20:06 | 8227.76 | 26-MAR-18:05 | 0.00 | 01-MAR-00:10 |
April | 0.328105E+11 | 0.965847E+10 | 633.79 | 0.227676E+11 | 0.100428E+11 | 0.00 | 1.00 | 01-APR-21:06 | 0.00 | 01-APR-00:33 | 32960.86 | 20-APR-20:08 | 24897.24 | 26-APR-22:42 | 12392.77 | 20-APR-20:08 | 8623.74 | 30-APR-18:42 | 0.00 | 01-APR-00:03 |
May | 0.353373E+11 | 0.102699E+11 | 655.43 | 0.230840E+11 | 0.122534E+11 | 0.00 | 1.00 | 01-MAY-20:06 | 0.00 | 01-MAY-00:33 | 33303.66 | 28-MAY-21:23 | 23465.21 | 14-MAY-19:23 | 13853.63 | 28-MAY-18:08 | 8560.24 | 29-MAY-18:06 | 0.00 | 01-MAY-00:03 |
June | 0.350176E+11 | 0.101309E+11 | 637.56 | 0.228606E+11 | 0.121570E+11 | 0.00 | 1.00 | 01-JUN-20:08 | 0.00 | 01-JUN-00:33 | 33309.89 | 04-JUN-18:08 | 23638.31 | 07-JUN-20:42 | 13357.94 | 28-JUN-20:08 | 8457.70 | 11-JUN-18:42 | 0.00 | 01-JUN-00:03 |
July | 0.296919E+11 | 0.860750E+10 | 647.48 | 0.207462E+11 | 0.894578E+10 | 0.00 | 1.00 | 01-JUL-21:08 | 0.00 | 01-JUL-00:10 | 32704.82 | 15-JUL-21:08 | 24859.18 | 30-JUL-20:03 | 11225.36 | 07-JUL-20:08 | 8251.66 | 30-JUL-18:06 | 0.00 | 01-JUL-00:05 |
August | 0.323575E+11 | 0.923497E+10 | 647.77 | 0.206657E+11 | 0.116918E+11 | 0.00 | 1.00 | 01-AUG-20:06 | 0.00 | 01-AUG-00:07 | 33112.41 | 06-AUG-18:08 | 22670.70 | 27-AUG-18:42 | 12693.04 | 06-AUG-18:08 | 8262.34 | 27-AUG-18:06 | 0.00 | 01-AUG-00:03 |
September | 0.317297E+11 | 0.907748E+10 | 628.64 | 0.211034E+11 | 0.106263E+11 | 0.00 | 1.00 | 01-SEP-20:06 | 0.00 | 01-SEP-00:07 | 32914.35 | 23-SEP-21:08 | 24294.65 | 29-SEP-23:23 | 11458.99 | 23-SEP-21:08 | 8268.41 | 04-SEP-18:06 | 0.00 | 01-SEP-00:03 |
October | 0.315422E+11 | 0.896648E+10 | 645.64 | 0.211847E+11 | 0.103575E+11 | 0.00 | 1.00 | 01-OCT-18:08 | 0.00 | 01-OCT-00:12 | 32938.15 | 25-OCT-20:08 | 24710.32 | 08-OCT-21:23 | 11760.02 | 25-OCT-20:08 | 8070.97 | 15-OCT-18:06 | 0.00 | 01-OCT-00:10 |
November | 0.315377E+11 | 0.897068E+10 | 625.66 | 0.224611E+11 | 0.907657E+10 | 0.00 | 1.00 | 01-NOV-20:06 | 0.00 | 01-NOV-00:07 | 32779.64 | 12-NOV-19:08 | 24914.07 | 19-NOV-23:42 | 11194.68 | 12-NOV-19:08 | 8122.99 | 19-NOV-19:05 | 0.00 | 01-NOV-00:03 |
December | 0.321263E+11 | 0.917065E+10 | 648.35 | 0.241619E+11 | 0.796439E+10 | 0.00 | 1.00 | 01-DEC-21:06 | 0.00 | 01-DEC-00:13 | 32610.41 | 10-DEC-19:42 | 26711.26 | 20-DEC-21:42 | 11256.19 | 09-DEC-22:08 | 8063.31 | 10-DEC-19:05 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.387983E+12 | 0.112003E+12 | 7665.85 | 0.272027E+12 | 0.115956E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.296919E+11 | 0.860750E+10 | 588.63 | 0.206657E+11 | 0.692878E+10 | 0.00 | 1.00 | 0.00 | 32373.66 | 22670.70 | 9524.93 | 8063.31 | 0.00 | |||||||
Maximum of Months | 0.353373E+11 | 0.102699E+11 | 656.83 | 0.249465E+11 | 0.122534E+11 | 0.00 | 1.00 | 0.00 | 33309.89 | 27223.99 | 13853.63 | 8623.74 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4 COOLING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.285534E+11 | 0.823165E+10 | 649.20 | 0.213749E+11 | 0.717852E+10 | 0.00 | 1.00 | 02-JAN-21:08 | 0.00 | 01-JAN-00:03 | 29727.88 | 09-JAN-21:06 | 23645.29 | 15-JAN-21:42 | 10400.61 | 09-JAN-21:06 | 7344.12 | 08-JAN-19:05 | 0.00 | 01-JAN-00:03 |
February | 0.270218E+11 | 0.786469E+10 | 587.91 | 0.202223E+11 | 0.679947E+10 | 0.00 | 1.00 | 01-FEB-01:42 | 0.00 | 01-FEB-00:12 | 29559.37 | 14-FEB-21:42 | 24052.34 | 23-FEB-01:42 | 9738.20 | 14-FEB-21:06 | 7411.49 | 26-FEB-19:05 | 0.00 | 01-FEB-00:10 |
March | 0.297216E+11 | 0.875335E+10 | 656.41 | 0.214055E+11 | 0.831616E+10 | 0.00 | 1.00 | 01-MAR-01:03 | 0.00 | 01-MAR-00:12 | 29639.53 | 27-MAR-20:42 | 22446.79 | 02-MAR-22:23 | 9891.13 | 14-MAR-20:06 | 7473.39 | 26-MAR-18:05 | 0.00 | 01-MAR-00:10 |
April | 0.292065E+11 | 0.858258E+10 | 633.12 | 0.194764E+11 | 0.973012E+10 | 0.00 | 1.00 | 01-APR-21:06 | 0.00 | 01-APR-00:33 | 30174.26 | 20-APR-20:08 | 21784.50 | 26-APR-22:42 | 12540.10 | 20-APR-20:08 | 7830.93 | 30-APR-18:42 | 0.00 | 01-APR-00:03 |
May | 0.316473E+11 | 0.916776E+10 | 655.07 | 0.197688E+11 | 0.118785E+11 | 0.00 | 1.00 | 01-MAY-20:06 | 0.00 | 01-MAY-00:33 | 30409.86 | 28-MAY-18:08 | 20691.19 | 14-MAY-20:03 | 13569.12 | 28-MAY-18:08 | 7773.71 | 29-MAY-18:06 | 0.00 | 01-MAY-00:03 |
June | 0.314890E+11 | 0.907577E+10 | 637.31 | 0.196629E+11 | 0.118261E+11 | 0.00 | 1.00 | 01-JUN-20:08 | 0.00 | 01-JUN-00:33 | 30429.95 | 28-JUN-20:08 | 20415.30 | 07-JUN-20:42 | 13465.92 | 28-JUN-20:08 | 7678.83 | 11-JUN-18:42 | 0.00 | 01-JUN-00:03 |
July | 0.260829E+11 | 0.756379E+10 | 647.21 | 0.174659E+11 | 0.861702E+10 | 0.00 | 1.00 | 01-JUL-21:08 | 0.00 | 01-JUL-00:10 | 29859.00 | 06-JUL-20:08 | 21959.73 | 30-JUL-20:03 | 11420.93 | 07-JUL-20:08 | 7495.46 | 30-JUL-18:06 | 0.00 | 01-JUL-00:05 |
August | 0.285441E+11 | 0.812855E+10 | 643.93 | 0.173265E+11 | 0.112176E+11 | 0.00 | 1.00 | 01-AUG-20:06 | 0.00 | 01-AUG-00:07 | 30250.68 | 06-AUG-18:08 | 19804.71 | 27-AUG-18:42 | 12674.30 | 06-AUG-18:08 | 7504.32 | 27-AUG-18:06 | 0.00 | 01-AUG-00:03 |
September | 0.281933E+11 | 0.805009E+10 | 627.52 | 0.179130E+11 | 0.102803E+11 | 0.00 | 1.00 | 01-SEP-20:06 | 0.00 | 01-SEP-00:07 | 30089.66 | 22-SEP-20:08 | 21267.00 | 29-SEP-23:23 | 11775.91 | 22-SEP-20:08 | 7509.45 | 04-SEP-18:06 | 0.00 | 01-SEP-00:03 |
October | 0.277833E+11 | 0.788812E+10 | 641.69 | 0.178203E+11 | 0.996300E+10 | 0.00 | 1.00 | 01-OCT-18:08 | 0.00 | 01-OCT-00:12 | 30132.20 | 25-OCT-20:08 | 21724.85 | 08-OCT-21:23 | 12047.82 | 25-OCT-20:08 | 7333.50 | 15-OCT-18:06 | 0.00 | 01-OCT-00:10 |
November | 0.280464E+11 | 0.797239E+10 | 624.50 | 0.192178E+11 | 0.882865E+10 | 0.00 | 1.00 | 01-NOV-20:06 | 0.00 | 01-NOV-00:07 | 29960.94 | 30-NOV-21:08 | 21869.78 | 19-NOV-23:42 | 11285.68 | 30-NOV-21:08 | 7381.46 | 19-NOV-19:05 | 0.00 | 01-NOV-00:03 |
December | 0.285604E+11 | 0.815466E+10 | 647.60 | 0.207871E+11 | 0.777328E+10 | 0.00 | 1.00 | 01-DEC-21:06 | 0.00 | 01-DEC-00:13 | 29767.84 | 11-DEC-21:08 | 23411.17 | 20-DEC-21:42 | 11410.41 | 09-DEC-22:08 | 7325.69 | 10-DEC-19:05 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.344850E+12 | 0.994334E+11 | 7651.48 | 0.232441E+12 | 0.112409E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.260829E+11 | 0.756379E+10 | 587.91 | 0.173265E+11 | 0.679947E+10 | 0.00 | 1.00 | 0.00 | 29559.37 | 19804.71 | 9738.20 | 7325.69 | 0.00 | |||||||
Maximum of Months | 0.316473E+11 | 0.916776E+10 | 656.41 | 0.214055E+11 | 0.118785E+11 | 0.00 | 1.00 | 0.00 | 30429.95 | 24052.34 | 13569.12 | 7830.93 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.36 | 13.53 | 14.84 | 62.39 | 12.47 | 0.00 | 0.00 | 0.00 |
February | 32.80 | 17.00 | 15.80 | 72.97 | 12.50 | 0.00 | 0.00 | 0.00 |
March | 37.95 | 22.19 | 15.76 | 84.45 | 9.23 | 0.00 | 0.00 | 0.00 |
April | 38.41 | 21.45 | 16.96 | 86.35 | 5.37 | 0.00 | 0.00 | 0.00 |
May | 32.17 | 13.93 | 18.24 | 74.56 | 4.09 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 17.14 | 17.63 | 79.99 | 3.93 | 0.00 | 0.00 | 0.00 |
July | 29.29 | 9.66 | 19.63 | 66.73 | 6.35 | 0.00 | 0.00 | 0.00 |
August | 32.31 | 13.81 | 18.51 | 68.87 | 5.85 | 0.00 | 0.00 | 0.00 |
September | 29.86 | 11.53 | 18.33 | 67.71 | 5.39 | 0.00 | 0.00 | 0.00 |
October | 27.31 | 9.63 | 17.68 | 58.53 | 6.08 | 0.00 | 0.00 | 0.00 |
November | 26.13 | 9.89 | 16.24 | 57.73 | 8.55 | 0.00 | 0.00 | 0.00 |
December | 26.34 | 11.80 | 14.55 | 58.07 | 13.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.29 | 14.27 | 17.02 | 69.80 | 7.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.13 | 9.63 | 14.55 | 57.73 | 3.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.41 | 22.19 | 19.63 | 86.35 | 13.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.36 | 13.53 | 14.84 | 62.39 | 12.47 | 0.00 | 0.00 | 0.00 |
February | 32.80 | 17.00 | 15.80 | 72.97 | 12.50 | 0.00 | 0.00 | 0.00 |
March | 37.95 | 22.19 | 15.76 | 84.45 | 9.23 | 0.00 | 0.00 | 0.00 |
April | 38.41 | 21.45 | 16.96 | 86.35 | 5.37 | 0.00 | 0.00 | 0.00 |
May | 32.17 | 13.93 | 18.24 | 74.56 | 4.09 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 17.14 | 17.63 | 79.99 | 3.93 | 0.00 | 0.00 | 0.00 |
July | 29.29 | 9.66 | 19.63 | 66.73 | 6.35 | 0.00 | 0.00 | 0.00 |
August | 32.31 | 13.81 | 18.51 | 68.87 | 5.85 | 0.00 | 0.00 | 0.00 |
September | 29.86 | 11.53 | 18.33 | 67.71 | 5.39 | 0.00 | 0.00 | 0.00 |
October | 27.31 | 9.63 | 17.68 | 58.53 | 6.08 | 0.00 | 0.00 | 0.00 |
November | 26.13 | 9.89 | 16.24 | 57.73 | 8.55 | 0.00 | 0.00 | 0.00 |
December | 26.34 | 11.80 | 14.55 | 58.07 | 13.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.29 | 14.27 | 17.02 | 69.80 | 7.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.13 | 9.63 | 14.55 | 57.73 | 3.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.41 | 22.19 | 19.63 | 86.35 | 13.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.36 | 13.53 | 14.84 | 62.39 | 12.47 | 0.00 | 0.00 | 0.00 |
February | 32.80 | 17.00 | 15.80 | 72.97 | 12.50 | 0.00 | 0.00 | 0.00 |
March | 37.95 | 22.19 | 15.76 | 84.45 | 9.23 | 0.00 | 0.00 | 0.00 |
April | 38.41 | 21.45 | 16.96 | 86.35 | 5.37 | 0.00 | 0.00 | 0.00 |
May | 32.17 | 13.93 | 18.24 | 74.56 | 4.09 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 17.14 | 17.63 | 79.99 | 3.93 | 0.00 | 0.00 | 0.00 |
July | 29.29 | 9.66 | 19.63 | 66.73 | 6.35 | 0.00 | 0.00 | 0.00 |
August | 32.31 | 13.81 | 18.51 | 68.87 | 5.85 | 0.00 | 0.00 | 0.00 |
September | 29.86 | 11.53 | 18.33 | 67.71 | 5.39 | 0.00 | 0.00 | 0.00 |
October | 27.31 | 9.63 | 17.68 | 58.53 | 6.08 | 0.00 | 0.00 | 0.00 |
November | 26.13 | 9.89 | 16.24 | 57.73 | 8.55 | 0.00 | 0.00 | 0.00 |
December | 26.34 | 11.80 | 14.55 | 58.07 | 13.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.29 | 14.27 | 17.02 | 69.80 | 7.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.13 | 9.63 | 14.55 | 57.73 | 3.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.41 | 22.19 | 19.63 | 86.35 | 13.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.36 | 13.53 | 14.84 | 62.39 | 12.47 | 0.00 | 0.00 | 0.00 |
February | 32.80 | 17.00 | 15.80 | 72.97 | 12.50 | 0.00 | 0.00 | 0.00 |
March | 37.95 | 22.19 | 15.76 | 84.45 | 9.23 | 0.00 | 0.00 | 0.00 |
April | 38.41 | 21.45 | 16.96 | 86.35 | 5.37 | 0.00 | 0.00 | 0.00 |
May | 32.17 | 13.93 | 18.24 | 74.56 | 4.09 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 17.14 | 17.63 | 79.99 | 3.93 | 0.00 | 0.00 | 0.00 |
July | 29.29 | 9.66 | 19.63 | 66.73 | 6.35 | 0.00 | 0.00 | 0.00 |
August | 32.31 | 13.81 | 18.51 | 68.87 | 5.85 | 0.00 | 0.00 | 0.00 |
September | 29.86 | 11.53 | 18.33 | 67.71 | 5.39 | 0.00 | 0.00 | 0.00 |
October | 27.31 | 9.63 | 17.68 | 58.53 | 6.08 | 0.00 | 0.00 | 0.00 |
November | 26.13 | 9.89 | 16.24 | 57.73 | 8.55 | 0.00 | 0.00 | 0.00 |
December | 26.34 | 11.80 | 14.55 | 58.07 | 13.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.29 | 14.27 | 17.02 | 69.80 | 7.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.13 | 9.63 | 14.55 | 57.73 | 3.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.41 | 22.19 | 19.63 | 86.35 | 13.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.36 | 13.53 | 14.84 | 62.39 | 12.47 | 0.00 | 0.00 | 0.00 |
February | 32.80 | 17.00 | 15.80 | 72.97 | 12.50 | 0.00 | 0.00 | 0.00 |
March | 37.95 | 22.19 | 15.76 | 84.45 | 9.23 | 0.00 | 0.00 | 0.00 |
April | 38.41 | 21.45 | 16.96 | 86.35 | 5.37 | 0.00 | 0.00 | 0.00 |
May | 32.17 | 13.93 | 18.24 | 74.56 | 4.09 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 17.14 | 17.63 | 79.99 | 3.93 | 0.00 | 0.00 | 0.00 |
July | 29.29 | 9.66 | 19.63 | 66.73 | 6.35 | 0.00 | 0.00 | 0.00 |
August | 32.31 | 13.81 | 18.51 | 68.87 | 5.85 | 0.00 | 0.00 | 0.00 |
September | 29.86 | 11.53 | 18.33 | 67.71 | 5.39 | 0.00 | 0.00 | 0.00 |
October | 27.31 | 9.63 | 17.68 | 58.53 | 6.08 | 0.00 | 0.00 | 0.00 |
November | 26.13 | 9.89 | 16.24 | 57.73 | 8.55 | 0.00 | 0.00 | 0.00 |
December | 26.34 | 11.80 | 14.55 | 58.07 | 13.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.29 | 14.27 | 17.02 | 69.80 | 7.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.13 | 9.63 | 14.55 | 57.73 | 3.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.41 | 22.19 | 19.63 | 86.35 | 13.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.36 | 13.53 | 14.84 | 62.39 | 12.47 | 0.00 | 0.00 | 0.00 |
February | 32.80 | 17.00 | 15.80 | 72.97 | 12.50 | 0.00 | 0.00 | 0.00 |
March | 37.95 | 22.19 | 15.76 | 84.45 | 9.23 | 0.00 | 0.00 | 0.00 |
April | 38.41 | 21.45 | 16.96 | 86.35 | 5.37 | 0.00 | 0.00 | 0.00 |
May | 32.17 | 13.93 | 18.24 | 74.56 | 4.09 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 17.14 | 17.63 | 79.99 | 3.93 | 0.00 | 0.00 | 0.00 |
July | 29.29 | 9.66 | 19.63 | 66.73 | 6.35 | 0.00 | 0.00 | 0.00 |
August | 32.31 | 13.81 | 18.51 | 68.87 | 5.85 | 0.00 | 0.00 | 0.00 |
September | 29.86 | 11.53 | 18.33 | 67.71 | 5.39 | 0.00 | 0.00 | 0.00 |
October | 27.31 | 9.63 | 17.68 | 58.53 | 6.08 | 0.00 | 0.00 | 0.00 |
November | 26.13 | 9.89 | 16.24 | 57.73 | 8.55 | 0.00 | 0.00 | 0.00 |
December | 26.34 | 11.80 | 14.55 | 58.07 | 13.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.29 | 14.27 | 17.02 | 69.80 | 7.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.13 | 9.63 | 14.55 | 57.73 | 3.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.41 | 22.19 | 19.63 | 86.35 | 13.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.36 | 13.53 | 14.84 | 62.39 | 12.47 | 0.00 | 0.00 | 0.00 |
February | 32.80 | 17.00 | 15.80 | 72.97 | 12.50 | 0.00 | 0.00 | 0.00 |
March | 37.95 | 22.19 | 15.76 | 84.45 | 9.23 | 0.00 | 0.00 | 0.00 |
April | 38.41 | 21.45 | 16.96 | 86.35 | 5.37 | 0.00 | 0.00 | 0.00 |
May | 32.17 | 13.93 | 18.24 | 74.56 | 4.09 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 17.14 | 17.63 | 79.99 | 3.93 | 0.00 | 0.00 | 0.00 |
July | 29.29 | 9.66 | 19.63 | 66.73 | 6.35 | 0.00 | 0.00 | 0.00 |
August | 32.31 | 13.81 | 18.51 | 68.87 | 5.85 | 0.00 | 0.00 | 0.00 |
September | 29.86 | 11.53 | 18.33 | 67.71 | 5.39 | 0.00 | 0.00 | 0.00 |
October | 27.31 | 9.63 | 17.68 | 58.53 | 6.08 | 0.00 | 0.00 | 0.00 |
November | 26.13 | 9.89 | 16.24 | 57.73 | 8.55 | 0.00 | 0.00 | 0.00 |
December | 26.34 | 11.80 | 14.55 | 58.07 | 13.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.29 | 14.27 | 17.02 | 69.80 | 7.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.13 | 9.63 | 14.55 | 57.73 | 3.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.41 | 22.19 | 19.63 | 86.35 | 13.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.36 | 13.53 | 14.84 | 62.39 | 12.47 | 0.00 | 0.00 | 0.00 |
February | 32.80 | 17.00 | 15.80 | 72.97 | 12.50 | 0.00 | 0.00 | 0.00 |
March | 37.95 | 22.19 | 15.76 | 84.45 | 9.23 | 0.00 | 0.00 | 0.00 |
April | 38.41 | 21.45 | 16.96 | 86.35 | 5.37 | 0.00 | 0.00 | 0.00 |
May | 32.17 | 13.93 | 18.24 | 74.56 | 4.09 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 17.14 | 17.63 | 79.99 | 3.93 | 0.00 | 0.00 | 0.00 |
July | 29.29 | 9.66 | 19.63 | 66.73 | 6.35 | 0.00 | 0.00 | 0.00 |
August | 32.31 | 13.81 | 18.51 | 68.87 | 5.85 | 0.00 | 0.00 | 0.00 |
September | 29.86 | 11.53 | 18.33 | 67.71 | 5.39 | 0.00 | 0.00 | 0.00 |
October | 27.31 | 9.63 | 17.68 | 58.53 | 6.08 | 0.00 | 0.00 | 0.00 |
November | 26.13 | 9.89 | 16.24 | 57.73 | 8.55 | 0.00 | 0.00 | 0.00 |
December | 26.34 | 11.80 | 14.55 | 58.07 | 13.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.29 | 14.27 | 17.02 | 69.80 | 7.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.13 | 9.63 | 14.55 | 57.73 | 3.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.41 | 22.19 | 19.63 | 86.35 | 13.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 563.11 | 241.32 | 321.78 | 1898.39 | 210.71 | 0.00 | 0.00 | 0.00 |
February | 491.19 | 175.21 | 315.99 | 1765.48 | 163.90 | 0.00 | 0.00 | 0.00 |
March | 339.03 | 62.04 | 276.99 | 1327.99 | 109.79 | 0.00 | 0.00 | 0.00 |
April | 238.68 | 0.24 | 238.44 | 1028.42 | 31.72 | 0.00 | 0.00 | 0.00 |
May | 238.71 | 0.00 | 238.71 | 1066.97 | 46.11 | 0.00 | 0.00 | 0.00 |
June | 237.85 | 0.00 | 237.85 | 1052.42 | 48.40 | 0.00 | 0.00 | 0.00 |
July | 245.02 | 0.00 | 245.02 | 945.79 | 96.84 | 0.00 | 0.00 | 0.00 |
August | 238.83 | 0.66 | 238.16 | 867.30 | 73.88 | 0.00 | 0.00 | 0.00 |
September | 268.24 | 12.80 | 255.45 | 1034.30 | 79.40 | 0.00 | 0.00 | 0.00 |
October | 357.69 | 67.29 | 290.40 | 1204.93 | 109.15 | 0.00 | 0.00 | 0.00 |
November | 459.86 | 147.68 | 312.18 | 1563.62 | 143.79 | 0.00 | 0.00 | 0.00 |
December | 558.38 | 241.32 | 317.07 | 1864.17 | 239.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 352.48 | 78.68 | 273.80 | 1299.28 | 112.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 237.85 | 0.00 | 237.85 | 867.30 | 31.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 563.11 | 241.32 | 321.78 | 1898.39 | 239.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 563.11 | 241.32 | 321.78 | 1900.17 | 201.30 | 0.00 | 0.00 | 0.00 |
February | 491.19 | 175.21 | 315.99 | 1767.23 | 154.49 | 0.00 | 0.00 | 0.00 |
March | 339.03 | 62.04 | 276.99 | 1331.24 | 98.77 | 0.00 | 0.00 | 0.00 |
April | 238.68 | 0.24 | 238.44 | 1035.18 | 25.88 | 0.00 | 0.00 | 0.00 |
May | 238.71 | 0.00 | 238.71 | 1074.72 | 41.65 | 0.00 | 0.00 | 0.00 |
June | 237.85 | 0.00 | 237.85 | 1058.26 | 43.71 | 0.00 | 0.00 | 0.00 |
July | 245.02 | 0.00 | 245.02 | 949.00 | 89.90 | 0.00 | 0.00 | 0.00 |
August | 238.83 | 0.66 | 238.16 | 872.13 | 66.19 | 0.00 | 0.00 | 0.00 |
September | 268.24 | 12.80 | 255.45 | 1037.75 | 72.59 | 0.00 | 0.00 | 0.00 |
October | 357.69 | 67.29 | 290.40 | 1210.02 | 100.20 | 0.00 | 0.00 | 0.00 |
November | 459.86 | 147.68 | 312.18 | 1566.34 | 136.14 | 0.00 | 0.00 | 0.00 |
December | 558.38 | 241.32 | 317.07 | 1865.66 | 230.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 352.48 | 78.68 | 273.80 | 1303.29 | 105.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 237.85 | 0.00 | 237.85 | 872.13 | 25.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 563.11 | 241.32 | 321.78 | 1900.17 | 230.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.85 | 49.65 | 66.20 | 322.50 | 74.12 | 0.00 | 0.00 | 0.00 |
February | 101.06 | 36.05 | 65.01 | 288.79 | 66.38 | 0.00 | 0.00 | 0.00 |
March | 69.75 | 12.76 | 56.99 | 200.76 | 52.99 | 0.00 | 0.00 | 0.00 |
April | 49.11 | 0.05 | 49.06 | 139.92 | 29.94 | 7.33 | 0.00 | 0.00 |
May | 49.11 | 0.00 | 49.11 | 143.05 | 30.05 | 179.67 | 0.00 | 0.00 |
June | 48.94 | 0.00 | 48.94 | 141.62 | 32.70 | 96.83 | 0.00 | 0.00 |
July | 50.41 | 0.00 | 50.41 | 141.27 | 38.91 | 15.50 | 0.00 | 0.00 |
August | 49.14 | 0.14 | 49.00 | 124.66 | 34.50 | 66.50 | 0.00 | 0.00 |
September | 55.19 | 2.63 | 52.56 | 155.23 | 37.40 | 54.83 | 0.00 | 0.00 |
October | 73.59 | 13.84 | 59.75 | 193.53 | 44.65 | 72.50 | 0.00 | 0.00 |
November | 94.61 | 30.38 | 64.23 | 261.50 | 55.32 | 13.83 | 0.00 | 0.00 |
December | 114.88 | 49.65 | 65.23 | 318.65 | 78.08 | 33.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.52 | 16.19 | 56.33 | 202.22 | 47.87 | 540.00 | 0.00 | 0.00 |
Minimum of Months | 48.94 | 0.00 | 48.94 | 124.66 | 29.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.85 | 49.65 | 66.20 | 322.50 | 78.08 | 179.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75969466.43 | 36232911.97 | 39736554.46 | 0.167109E+09 | 33407830.12 |
February | 79341614.39 | 41120309.15 | 38221305.24 | 0.176540E+09 | 30250725.27 |
March | 0.101642E+09 | 59432071.08 | 42210401.31 | 0.226189E+09 | 24725952.86 |
April | 99559469.14 | 55607737.42 | 43951731.72 | 0.223826E+09 | 13917388.38 |
May | 86168815.62 | 37302159.69 | 48866655.93 | 0.199702E+09 | 10956570.51 |
June | 90117869.69 | 44429463.46 | 45688406.23 | 0.207341E+09 | 10195575.54 |
July | 78440382.86 | 25872072.91 | 52568309.96 | 0.178730E+09 | 17018194.50 |
August | 86544439.58 | 36977058.15 | 49567381.43 | 0.184458E+09 | 15671884.92 |
September | 77402051.72 | 29891946.65 | 47510105.06 | 0.175501E+09 | 13962614.75 |
October | 73158377.21 | 25794802.98 | 47363574.22 | 0.156775E+09 | 16291326.86 |
November | 67725550.30 | 25626637.69 | 42098912.62 | 0.149632E+09 | 22153413.96 |
December | 70553365.24 | 31592532.52 | 38960832.72 | 0.155523E+09 | 35500364.26 |
Annual Sum or Average | 0.986624E+09 | 0.449880E+09 | 0.536744E+09 | 0.220133E+10 | 0.244052E+09 |
Minimum of Months | 67725550.30 | 25626637.69 | 38221305.24 | 0.149632E+09 | 10195575.54 |
Maximum of Months | 0.101642E+09 | 59432071.08 | 52568309.96 | 0.226189E+09 | 35500364.26 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75969466.43 | 36232911.97 | 39736554.46 | 0.167109E+09 | 33407830.12 |
February | 79341614.39 | 41120309.15 | 38221305.24 | 0.176540E+09 | 30250725.27 |
March | 0.101642E+09 | 59432071.08 | 42210401.31 | 0.226189E+09 | 24725952.86 |
April | 99559469.14 | 55607737.42 | 43951731.72 | 0.223826E+09 | 13917388.38 |
May | 86168815.62 | 37302159.69 | 48866655.93 | 0.199702E+09 | 10956570.51 |
June | 90117869.69 | 44429463.46 | 45688406.23 | 0.207341E+09 | 10195575.54 |
July | 78440382.86 | 25872072.91 | 52568309.96 | 0.178730E+09 | 17018194.50 |
August | 86544439.58 | 36977058.15 | 49567381.43 | 0.184458E+09 | 15671884.92 |
September | 77402051.72 | 29891946.65 | 47510105.06 | 0.175501E+09 | 13962614.75 |
October | 73158377.21 | 25794802.98 | 47363574.22 | 0.156775E+09 | 16291326.86 |
November | 67725550.30 | 25626637.69 | 42098912.62 | 0.149632E+09 | 22153413.96 |
December | 70553365.24 | 31592532.52 | 38960832.72 | 0.155523E+09 | 35500364.26 |
Annual Sum or Average | 0.986624E+09 | 0.449880E+09 | 0.536744E+09 | 0.220133E+10 | 0.244052E+09 |
Minimum of Months | 67725550.30 | 25626637.69 | 38221305.24 | 0.149632E+09 | 10195575.54 |
Maximum of Months | 0.101642E+09 | 59432071.08 | 52568309.96 | 0.226189E+09 | 35500364.26 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75969466.43 | 36232911.97 | 39736554.46 | 0.167109E+09 | 33407830.12 |
February | 79341614.39 | 41120309.15 | 38221305.24 | 0.176540E+09 | 30250725.27 |
March | 0.101642E+09 | 59432071.08 | 42210401.31 | 0.226189E+09 | 24725952.86 |
April | 99559469.14 | 55607737.42 | 43951731.72 | 0.223826E+09 | 13917388.38 |
May | 86168815.62 | 37302159.69 | 48866655.93 | 0.199702E+09 | 10956570.51 |
June | 90117869.69 | 44429463.46 | 45688406.23 | 0.207341E+09 | 10195575.54 |
July | 78440382.86 | 25872072.91 | 52568309.96 | 0.178730E+09 | 17018194.50 |
August | 86544439.58 | 36977058.15 | 49567381.43 | 0.184458E+09 | 15671884.92 |
September | 77402051.72 | 29891946.65 | 47510105.06 | 0.175501E+09 | 13962614.75 |
October | 73158377.21 | 25794802.98 | 47363574.22 | 0.156775E+09 | 16291326.86 |
November | 67725550.30 | 25626637.69 | 42098912.62 | 0.149632E+09 | 22153413.96 |
December | 70553365.24 | 31592532.52 | 38960832.72 | 0.155523E+09 | 35500364.26 |
Annual Sum or Average | 0.986624E+09 | 0.449880E+09 | 0.536744E+09 | 0.220133E+10 | 0.244052E+09 |
Minimum of Months | 67725550.30 | 25626637.69 | 38221305.24 | 0.149632E+09 | 10195575.54 |
Maximum of Months | 0.101642E+09 | 59432071.08 | 52568309.96 | 0.226189E+09 | 35500364.26 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75969466.43 | 36232911.97 | 39736554.46 | 0.167109E+09 | 33407830.12 |
February | 79341614.39 | 41120309.15 | 38221305.24 | 0.176540E+09 | 30250725.27 |
March | 0.101642E+09 | 59432071.08 | 42210401.31 | 0.226189E+09 | 24725952.86 |
April | 99559469.14 | 55607737.42 | 43951731.72 | 0.223826E+09 | 13917388.38 |
May | 86168815.62 | 37302159.69 | 48866655.93 | 0.199702E+09 | 10956570.51 |
June | 90117869.69 | 44429463.46 | 45688406.23 | 0.207341E+09 | 10195575.54 |
July | 78440382.86 | 25872072.91 | 52568309.96 | 0.178730E+09 | 17018194.50 |
August | 86544439.58 | 36977058.15 | 49567381.43 | 0.184458E+09 | 15671884.92 |
September | 77402051.72 | 29891946.65 | 47510105.06 | 0.175501E+09 | 13962614.75 |
October | 73158377.21 | 25794802.98 | 47363574.22 | 0.156775E+09 | 16291326.86 |
November | 67725550.30 | 25626637.69 | 42098912.62 | 0.149632E+09 | 22153413.96 |
December | 70553365.24 | 31592532.52 | 38960832.72 | 0.155523E+09 | 35500364.26 |
Annual Sum or Average | 0.986624E+09 | 0.449880E+09 | 0.536744E+09 | 0.220133E+10 | 0.244052E+09 |
Minimum of Months | 67725550.30 | 25626637.69 | 38221305.24 | 0.149632E+09 | 10195575.54 |
Maximum of Months | 0.101642E+09 | 59432071.08 | 52568309.96 | 0.226189E+09 | 35500364.26 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75969466.43 | 36232911.97 | 39736554.46 | 0.167109E+09 | 33407830.12 |
February | 79341614.39 | 41120309.15 | 38221305.24 | 0.176540E+09 | 30250725.27 |
March | 0.101642E+09 | 59432071.08 | 42210401.31 | 0.226189E+09 | 24725952.86 |
April | 99559469.14 | 55607737.42 | 43951731.72 | 0.223826E+09 | 13917388.38 |
May | 86168815.62 | 37302159.69 | 48866655.93 | 0.199702E+09 | 10956570.51 |
June | 90117869.69 | 44429463.46 | 45688406.23 | 0.207341E+09 | 10195575.54 |
July | 78440382.86 | 25872072.91 | 52568309.96 | 0.178730E+09 | 17018194.50 |
August | 86544439.58 | 36977058.15 | 49567381.43 | 0.184458E+09 | 15671884.92 |
September | 77402051.72 | 29891946.65 | 47510105.06 | 0.175501E+09 | 13962614.75 |
October | 73158377.21 | 25794802.98 | 47363574.22 | 0.156775E+09 | 16291326.86 |
November | 67725550.30 | 25626637.69 | 42098912.62 | 0.149632E+09 | 22153413.96 |
December | 70553365.24 | 31592532.52 | 38960832.72 | 0.155523E+09 | 35500364.26 |
Annual Sum or Average | 0.986624E+09 | 0.449880E+09 | 0.536744E+09 | 0.220133E+10 | 0.244052E+09 |
Minimum of Months | 67725550.30 | 25626637.69 | 38221305.24 | 0.149632E+09 | 10195575.54 |
Maximum of Months | 0.101642E+09 | 59432071.08 | 52568309.96 | 0.226189E+09 | 35500364.26 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75969466.43 | 36232911.97 | 39736554.46 | 0.167109E+09 | 33407830.12 |
February | 79341614.39 | 41120309.15 | 38221305.24 | 0.176540E+09 | 30250725.27 |
March | 0.101642E+09 | 59432071.08 | 42210401.31 | 0.226189E+09 | 24725952.86 |
April | 99559469.14 | 55607737.42 | 43951731.72 | 0.223826E+09 | 13917388.38 |
May | 86168815.62 | 37302159.69 | 48866655.93 | 0.199702E+09 | 10956570.51 |
June | 90117869.69 | 44429463.46 | 45688406.23 | 0.207341E+09 | 10195575.54 |
July | 78440382.86 | 25872072.91 | 52568309.96 | 0.178730E+09 | 17018194.50 |
August | 86544439.58 | 36977058.15 | 49567381.43 | 0.184458E+09 | 15671884.92 |
September | 77402051.72 | 29891946.65 | 47510105.06 | 0.175501E+09 | 13962614.75 |
October | 73158377.21 | 25794802.98 | 47363574.22 | 0.156775E+09 | 16291326.86 |
November | 67725550.30 | 25626637.69 | 42098912.62 | 0.149632E+09 | 22153413.96 |
December | 70553365.24 | 31592532.52 | 38960832.72 | 0.155523E+09 | 35500364.26 |
Annual Sum or Average | 0.986624E+09 | 0.449880E+09 | 0.536744E+09 | 0.220133E+10 | 0.244052E+09 |
Minimum of Months | 67725550.30 | 25626637.69 | 38221305.24 | 0.149632E+09 | 10195575.54 |
Maximum of Months | 0.101642E+09 | 59432071.08 | 52568309.96 | 0.226189E+09 | 35500364.26 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75969466.43 | 36232911.97 | 39736554.46 | 0.167109E+09 | 33407830.12 |
February | 79341614.39 | 41120309.15 | 38221305.24 | 0.176540E+09 | 30250725.27 |
March | 0.101642E+09 | 59432071.08 | 42210401.31 | 0.226189E+09 | 24725952.86 |
April | 99559469.14 | 55607737.42 | 43951731.72 | 0.223826E+09 | 13917388.38 |
May | 86168815.62 | 37302159.69 | 48866655.93 | 0.199702E+09 | 10956570.51 |
June | 90117869.69 | 44429463.46 | 45688406.23 | 0.207341E+09 | 10195575.54 |
July | 78440382.86 | 25872072.91 | 52568309.96 | 0.178730E+09 | 17018194.50 |
August | 86544439.58 | 36977058.15 | 49567381.43 | 0.184458E+09 | 15671884.92 |
September | 77402051.72 | 29891946.65 | 47510105.06 | 0.175501E+09 | 13962614.75 |
October | 73158377.21 | 25794802.98 | 47363574.22 | 0.156775E+09 | 16291326.86 |
November | 67725550.30 | 25626637.69 | 42098912.62 | 0.149632E+09 | 22153413.96 |
December | 70553365.24 | 31592532.52 | 38960832.72 | 0.155523E+09 | 35500364.26 |
Annual Sum or Average | 0.986624E+09 | 0.449880E+09 | 0.536744E+09 | 0.220133E+10 | 0.244052E+09 |
Minimum of Months | 67725550.30 | 25626637.69 | 38221305.24 | 0.149632E+09 | 10195575.54 |
Maximum of Months | 0.101642E+09 | 59432071.08 | 52568309.96 | 0.226189E+09 | 35500364.26 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75969466.43 | 36232911.97 | 39736554.46 | 0.167109E+09 | 33407830.12 |
February | 79341614.39 | 41120309.15 | 38221305.24 | 0.176540E+09 | 30250725.27 |
March | 0.101642E+09 | 59432071.08 | 42210401.31 | 0.226189E+09 | 24725952.86 |
April | 99559469.14 | 55607737.42 | 43951731.72 | 0.223826E+09 | 13917388.38 |
May | 86168815.62 | 37302159.69 | 48866655.93 | 0.199702E+09 | 10956570.51 |
June | 90117869.69 | 44429463.46 | 45688406.23 | 0.207341E+09 | 10195575.54 |
July | 78440382.86 | 25872072.91 | 52568309.96 | 0.178730E+09 | 17018194.50 |
August | 86544439.58 | 36977058.15 | 49567381.43 | 0.184458E+09 | 15671884.92 |
September | 77402051.72 | 29891946.65 | 47510105.06 | 0.175501E+09 | 13962614.75 |
October | 73158377.21 | 25794802.98 | 47363574.22 | 0.156775E+09 | 16291326.86 |
November | 67725550.30 | 25626637.69 | 42098912.62 | 0.149632E+09 | 22153413.96 |
December | 70553365.24 | 31592532.52 | 38960832.72 | 0.155523E+09 | 35500364.26 |
Annual Sum or Average | 0.986624E+09 | 0.449880E+09 | 0.536744E+09 | 0.220133E+10 | 0.244052E+09 |
Minimum of Months | 67725550.30 | 25626637.69 | 38221305.24 | 0.149632E+09 | 10195575.54 |
Maximum of Months | 0.101642E+09 | 59432071.08 | 52568309.96 | 0.226189E+09 | 35500364.26 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150822E+10 | 0.646363E+09 | 0.861861E+09 | 0.508464E+10 | 0.564372E+09 |
February | 0.118830E+10 | 0.423856E+09 | 0.764439E+09 | 0.427105E+10 | 0.396511E+09 |
March | 0.908059E+09 | 0.166160E+09 | 0.741899E+09 | 0.355689E+10 | 0.294052E+09 |
April | 0.618665E+09 | 622845.10 | 0.618043E+09 | 0.266568E+10 | 82211736.27 |
May | 0.639367E+09 | 0.00 | 0.639367E+09 | 0.285776E+10 | 0.123488E+09 |
June | 0.616515E+09 | 0.00 | 0.616515E+09 | 0.272786E+10 | 0.125451E+09 |
July | 0.656273E+09 | 0.00 | 0.656273E+09 | 0.253319E+10 | 0.259368E+09 |
August | 0.639670E+09 | 1770623.90 | 0.637899E+09 | 0.232298E+10 | 0.197887E+09 |
September | 0.695290E+09 | 33168957.91 | 0.662121E+09 | 0.268090E+10 | 0.205799E+09 |
October | 0.958025E+09 | 0.180219E+09 | 0.777806E+09 | 0.322728E+10 | 0.292353E+09 |
November | 0.119196E+10 | 0.382774E+09 | 0.809183E+09 | 0.405290E+10 | 0.372703E+09 |
December | 0.149558E+10 | 0.646347E+09 | 0.849229E+09 | 0.499300E+10 | 0.640328E+09 |
Annual Sum or Average | 0.111159E+11 | 0.248128E+10 | 0.863463E+10 | 0.409741E+11 | 0.355452E+10 |
Minimum of Months | 0.616515E+09 | 0.00 | 0.616515E+09 | 0.232298E+10 | 82211736.27 |
Maximum of Months | 0.150822E+10 | 0.646363E+09 | 0.861861E+09 | 0.508464E+10 | 0.640328E+09 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150822E+10 | 0.646363E+09 | 0.861861E+09 | 0.508942E+10 | 0.539166E+09 |
February | 0.118830E+10 | 0.423856E+09 | 0.764439E+09 | 0.427529E+10 | 0.373731E+09 |
March | 0.908059E+09 | 0.166160E+09 | 0.741899E+09 | 0.356558E+10 | 0.264555E+09 |
April | 0.618665E+09 | 622845.10 | 0.618043E+09 | 0.268319E+10 | 67089165.51 |
May | 0.639367E+09 | 0.00 | 0.639367E+09 | 0.287854E+10 | 0.111560E+09 |
June | 0.616515E+09 | 0.00 | 0.616515E+09 | 0.274301E+10 | 0.113284E+09 |
July | 0.656273E+09 | 0.00 | 0.656273E+09 | 0.254180E+10 | 0.240788E+09 |
August | 0.639670E+09 | 1770623.90 | 0.637899E+09 | 0.233591E+10 | 0.177292E+09 |
September | 0.695290E+09 | 33168957.91 | 0.662121E+09 | 0.268985E+10 | 0.188156E+09 |
October | 0.958025E+09 | 0.180219E+09 | 0.777806E+09 | 0.324093E+10 | 0.268377E+09 |
November | 0.119196E+10 | 0.382774E+09 | 0.809183E+09 | 0.405997E+10 | 0.352864E+09 |
December | 0.149558E+10 | 0.646347E+09 | 0.849229E+09 | 0.499699E+10 | 0.616499E+09 |
Annual Sum or Average | 0.111159E+11 | 0.248128E+10 | 0.863463E+10 | 0.411005E+11 | 0.331336E+10 |
Minimum of Months | 0.616515E+09 | 0.00 | 0.616515E+09 | 0.233591E+10 | 67089165.51 |
Maximum of Months | 0.150822E+10 | 0.646363E+09 | 0.861861E+09 | 0.508942E+10 | 0.616499E+09 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.310298E+09 | 0.132981E+09 | 0.177317E+09 | 0.863776E+09 | 0.198533E+09 |
February | 0.244476E+09 | 87203086.32 | 0.157273E+09 | 0.698630E+09 | 0.160580E+09 |
March | 0.186821E+09 | 34185410.24 | 0.152636E+09 | 0.537705E+09 | 0.141924E+09 |
April | 0.127282E+09 | 128142.59 | 0.127154E+09 | 0.362672E+09 | 77596263.50 |
May | 0.131541E+09 | 0.00 | 0.131541E+09 | 0.383148E+09 | 80473978.64 |
June | 0.126840E+09 | 0.00 | 0.126840E+09 | 0.367077E+09 | 84765740.45 |
July | 0.135019E+09 | 0.00 | 0.135019E+09 | 0.378366E+09 | 0.104226E+09 |
August | 0.131603E+09 | 364283.72 | 0.131239E+09 | 0.333891E+09 | 92402624.51 |
September | 0.143047E+09 | 6824098.16 | 0.136223E+09 | 0.402362E+09 | 96946274.88 |
October | 0.197101E+09 | 37077754.33 | 0.160023E+09 | 0.518359E+09 | 0.119586E+09 |
November | 0.245230E+09 | 78750983.49 | 0.166479E+09 | 0.677812E+09 | 0.143400E+09 |
December | 0.307695E+09 | 0.132978E+09 | 0.174718E+09 | 0.853479E+09 | 0.209134E+09 |
Annual Sum or Average | 0.228695E+10 | 0.510493E+09 | 0.177646E+10 | 0.637727E+10 | 0.150957E+10 |
Minimum of Months | 0.126840E+09 | 0.00 | 0.126840E+09 | 0.333891E+09 | 77596263.50 |
Maximum of Months | 0.310298E+09 | 0.132981E+09 | 0.177317E+09 | 0.863776E+09 | 0.209134E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 499.13 | 99.78 | 226.91 | 108.22 | 118.69 | 0.00 | 0.00 |
February | 583.80 | 100.04 | 262.37 | 135.98 | 126.39 | 0.00 | 0.00 |
March | 675.59 | 73.85 | 303.59 | 177.52 | 126.08 | 0.00 | 0.00 |
April | 690.82 | 42.95 | 307.28 | 171.63 | 135.65 | 0.00 | 0.00 |
May | 596.48 | 32.73 | 257.37 | 111.42 | 145.96 | 0.00 | 0.00 |
June | 639.94 | 31.47 | 278.14 | 137.13 | 141.01 | 0.00 | 0.00 |
July | 533.84 | 50.83 | 234.29 | 77.28 | 157.01 | 0.00 | 0.00 |
August | 550.95 | 46.81 | 258.50 | 110.45 | 148.05 | 0.00 | 0.00 |
September | 541.67 | 43.09 | 238.90 | 92.26 | 146.64 | 0.00 | 0.00 |
October | 468.27 | 48.66 | 218.51 | 77.05 | 141.47 | 0.00 | 0.00 |
November | 461.83 | 68.37 | 209.03 | 79.09 | 129.93 | 0.00 | 0.00 |
December | 464.52 | 106.03 | 210.73 | 94.36 | 116.37 | 0.00 | 0.00 |
Annual Sum or Average | 558.43 | 61.91 | 250.29 | 114.12 | 136.16 | 0.00 | 0.00 |
Minimum of Months | 461.83 | 31.47 | 209.03 | 77.05 | 116.37 | 0.00 | 0.00 |
Maximum of Months | 690.82 | 106.03 | 307.28 | 177.52 | 157.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1898.39 | 210.71 | 563.11 | 241.32 | 321.78 | 0.00 | 0.00 |
February | 1765.48 | 163.90 | 491.19 | 175.21 | 315.99 | 0.00 | 0.00 |
March | 1327.99 | 109.79 | 339.03 | 62.04 | 276.99 | 0.00 | 0.00 |
April | 1028.42 | 31.72 | 238.68 | 0.24 | 238.44 | 0.00 | 0.00 |
May | 1066.97 | 46.11 | 238.71 | 0.00 | 238.71 | 0.00 | 0.00 |
June | 1052.42 | 48.40 | 237.85 | 0.00 | 237.85 | 0.00 | 0.00 |
July | 945.79 | 96.84 | 245.02 | 0.00 | 245.02 | 0.00 | 0.00 |
August | 867.30 | 73.88 | 238.83 | 0.66 | 238.16 | 0.00 | 0.00 |
September | 1034.30 | 79.40 | 268.24 | 12.80 | 255.45 | 0.00 | 0.00 |
October | 1204.93 | 109.15 | 357.69 | 67.29 | 290.40 | 0.00 | 0.00 |
November | 1563.62 | 143.79 | 459.86 | 147.68 | 312.18 | 0.00 | 0.00 |
December | 1864.17 | 239.07 | 558.38 | 241.32 | 317.07 | 0.00 | 0.00 |
Annual Sum or Average | 1299.28 | 112.71 | 352.48 | 78.68 | 273.80 | 0.00 | 0.00 |
Minimum of Months | 867.30 | 31.72 | 237.85 | 0.00 | 237.85 | 0.00 | 0.00 |
Maximum of Months | 1898.39 | 239.07 | 563.11 | 241.32 | 321.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1900.17 | 201.30 | 563.11 | 241.32 | 321.78 | 0.00 | 0.00 |
February | 1767.23 | 154.49 | 491.19 | 175.21 | 315.99 | 0.00 | 0.00 |
March | 1331.24 | 98.77 | 339.03 | 62.04 | 276.99 | 0.00 | 0.00 |
April | 1035.18 | 25.88 | 238.68 | 0.24 | 238.44 | 0.00 | 0.00 |
May | 1074.72 | 41.65 | 238.71 | 0.00 | 238.71 | 0.00 | 0.00 |
June | 1058.26 | 43.71 | 237.85 | 0.00 | 237.85 | 0.00 | 0.00 |
July | 949.00 | 89.90 | 245.02 | 0.00 | 245.02 | 0.00 | 0.00 |
August | 872.13 | 66.19 | 238.83 | 0.66 | 238.16 | 0.00 | 0.00 |
September | 1037.75 | 72.59 | 268.24 | 12.80 | 255.45 | 0.00 | 0.00 |
October | 1210.02 | 100.20 | 357.69 | 67.29 | 290.40 | 0.00 | 0.00 |
November | 1566.34 | 136.14 | 459.86 | 147.68 | 312.18 | 0.00 | 0.00 |
December | 1865.66 | 230.17 | 558.38 | 241.32 | 317.07 | 0.00 | 0.00 |
Annual Sum or Average | 1303.29 | 105.07 | 352.48 | 78.68 | 273.80 | 0.00 | 0.00 |
Minimum of Months | 872.13 | 25.88 | 237.85 | 0.00 | 237.85 | 0.00 | 0.00 |
Maximum of Months | 1900.17 | 230.17 | 563.11 | 241.32 | 321.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 322.50 | 74.12 | 115.85 | 49.65 | 66.20 | 0.00 | 0.00 |
February | 288.79 | 66.38 | 101.06 | 36.05 | 65.01 | 0.00 | 0.00 |
March | 200.76 | 52.99 | 69.75 | 12.76 | 56.99 | 0.00 | 0.00 |
April | 139.92 | 29.94 | 49.11 | 0.05 | 49.06 | 0.00 | 0.00 |
May | 143.05 | 30.05 | 49.11 | 0.00 | 49.11 | 0.00 | 0.00 |
June | 141.62 | 32.70 | 48.94 | 0.00 | 48.94 | 0.00 | 0.00 |
July | 141.27 | 38.91 | 50.41 | 0.00 | 50.41 | 0.00 | 0.00 |
August | 124.66 | 34.50 | 49.14 | 0.14 | 49.00 | 0.00 | 0.00 |
September | 155.23 | 37.40 | 55.19 | 2.63 | 52.56 | 0.00 | 0.00 |
October | 193.53 | 44.65 | 73.59 | 13.84 | 59.75 | 0.00 | 0.00 |
November | 261.50 | 55.32 | 94.61 | 30.38 | 64.23 | 0.00 | 0.00 |
December | 318.65 | 78.08 | 114.88 | 49.65 | 65.23 | 0.00 | 0.00 |
Annual Sum or Average | 202.22 | 47.87 | 72.52 | 16.19 | 56.33 | 0.00 | 0.00 |
Minimum of Months | 124.66 | 29.94 | 48.94 | 0.00 | 48.94 | 0.00 | 0.00 |
Maximum of Months | 322.50 | 78.08 | 115.85 | 49.65 | 66.20 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133687E+10 | 0.267263E+09 | 0.607756E+09 | 0.289863E+09 | 0.317892E+09 | 0.00 | 0.00 |
February | 0.141232E+10 | 0.242006E+09 | 0.634733E+09 | 0.328962E+09 | 0.305770E+09 | 0.00 | 0.00 |
March | 0.180951E+10 | 0.197808E+09 | 0.813140E+09 | 0.475457E+09 | 0.337683E+09 | 0.00 | 0.00 |
April | 0.179061E+10 | 0.111339E+09 | 0.796476E+09 | 0.444862E+09 | 0.351614E+09 | 0.00 | 0.00 |
May | 0.159762E+10 | 87652564.06 | 0.689351E+09 | 0.298417E+09 | 0.390933E+09 | 0.00 | 0.00 |
June | 0.165873E+10 | 81564604.33 | 0.720943E+09 | 0.355436E+09 | 0.365507E+09 | 0.00 | 0.00 |
July | 0.142984E+10 | 0.136146E+09 | 0.627523E+09 | 0.206977E+09 | 0.420546E+09 | 0.00 | 0.00 |
August | 0.147566E+10 | 0.125375E+09 | 0.692356E+09 | 0.295816E+09 | 0.396539E+09 | 0.00 | 0.00 |
September | 0.140401E+10 | 0.111701E+09 | 0.619216E+09 | 0.239136E+09 | 0.380081E+09 | 0.00 | 0.00 |
October | 0.125420E+10 | 0.130331E+09 | 0.585267E+09 | 0.206358E+09 | 0.378909E+09 | 0.00 | 0.00 |
November | 0.119706E+10 | 0.177227E+09 | 0.541804E+09 | 0.205013E+09 | 0.336791E+09 | 0.00 | 0.00 |
December | 0.124418E+10 | 0.284003E+09 | 0.564427E+09 | 0.252740E+09 | 0.311687E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.176106E+11 | 0.195241E+10 | 0.789299E+10 | 0.359904E+10 | 0.429395E+10 | 0.00 | 0.00 |
Minimum of Months | 0.119706E+10 | 81564604.33 | 0.541804E+09 | 0.205013E+09 | 0.305770E+09 | 0.00 | 0.00 |
Maximum of Months | 0.180951E+10 | 0.284003E+09 | 0.813140E+09 | 0.475457E+09 | 0.420546E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.508464E+10 | 0.564372E+09 | 0.150822E+10 | 0.646363E+09 | 0.861861E+09 | 0.00 | 0.00 |
February | 0.427105E+10 | 0.396511E+09 | 0.118830E+10 | 0.423856E+09 | 0.764439E+09 | 0.00 | 0.00 |
March | 0.355689E+10 | 0.294052E+09 | 0.908059E+09 | 0.166160E+09 | 0.741899E+09 | 0.00 | 0.00 |
April | 0.266568E+10 | 82211736.27 | 0.618665E+09 | 622845.10 | 0.618043E+09 | 0.00 | 0.00 |
May | 0.285776E+10 | 0.123488E+09 | 0.639367E+09 | 0.00 | 0.639367E+09 | 0.00 | 0.00 |
June | 0.272786E+10 | 0.125451E+09 | 0.616515E+09 | 0.00 | 0.616515E+09 | 0.00 | 0.00 |
July | 0.253319E+10 | 0.259368E+09 | 0.656273E+09 | 0.00 | 0.656273E+09 | 0.00 | 0.00 |
August | 0.232298E+10 | 0.197887E+09 | 0.639670E+09 | 1770623.90 | 0.637899E+09 | 0.00 | 0.00 |
September | 0.268090E+10 | 0.205799E+09 | 0.695290E+09 | 33168957.91 | 0.662121E+09 | 0.00 | 0.00 |
October | 0.322728E+10 | 0.292353E+09 | 0.958025E+09 | 0.180219E+09 | 0.777806E+09 | 0.00 | 0.00 |
November | 0.405290E+10 | 0.372703E+09 | 0.119196E+10 | 0.382774E+09 | 0.809183E+09 | 0.00 | 0.00 |
December | 0.499300E+10 | 0.640328E+09 | 0.149558E+10 | 0.646347E+09 | 0.849229E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.409741E+11 | 0.355452E+10 | 0.111159E+11 | 0.248128E+10 | 0.863463E+10 | 0.00 | 0.00 |
Minimum of Months | 0.232298E+10 | 82211736.27 | 0.616515E+09 | 0.00 | 0.616515E+09 | 0.00 | 0.00 |
Maximum of Months | 0.508464E+10 | 0.640328E+09 | 0.150822E+10 | 0.646363E+09 | 0.861861E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.508942E+10 | 0.539166E+09 | 0.150822E+10 | 0.646363E+09 | 0.861861E+09 | 0.00 | 0.00 |
February | 0.427529E+10 | 0.373731E+09 | 0.118830E+10 | 0.423856E+09 | 0.764439E+09 | 0.00 | 0.00 |
March | 0.356558E+10 | 0.264555E+09 | 0.908059E+09 | 0.166160E+09 | 0.741899E+09 | 0.00 | 0.00 |
April | 0.268319E+10 | 67089165.51 | 0.618665E+09 | 622845.10 | 0.618043E+09 | 0.00 | 0.00 |
May | 0.287854E+10 | 0.111560E+09 | 0.639367E+09 | 0.00 | 0.639367E+09 | 0.00 | 0.00 |
June | 0.274301E+10 | 0.113284E+09 | 0.616515E+09 | 0.00 | 0.616515E+09 | 0.00 | 0.00 |
July | 0.254180E+10 | 0.240788E+09 | 0.656273E+09 | 0.00 | 0.656273E+09 | 0.00 | 0.00 |
August | 0.233591E+10 | 0.177292E+09 | 0.639670E+09 | 1770623.90 | 0.637899E+09 | 0.00 | 0.00 |
September | 0.268985E+10 | 0.188156E+09 | 0.695290E+09 | 33168957.91 | 0.662121E+09 | 0.00 | 0.00 |
October | 0.324093E+10 | 0.268377E+09 | 0.958025E+09 | 0.180219E+09 | 0.777806E+09 | 0.00 | 0.00 |
November | 0.405997E+10 | 0.352864E+09 | 0.119196E+10 | 0.382774E+09 | 0.809183E+09 | 0.00 | 0.00 |
December | 0.499699E+10 | 0.616499E+09 | 0.149558E+10 | 0.646347E+09 | 0.849229E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.411005E+11 | 0.331336E+10 | 0.111159E+11 | 0.248128E+10 | 0.863463E+10 | 0.00 | 0.00 |
Minimum of Months | 0.233591E+10 | 67089165.51 | 0.616515E+09 | 0.00 | 0.616515E+09 | 0.00 | 0.00 |
Maximum of Months | 0.508942E+10 | 0.616499E+09 | 0.150822E+10 | 0.646363E+09 | 0.861861E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.863776E+09 | 0.198533E+09 | 0.310298E+09 | 0.132981E+09 | 0.177317E+09 | 0.00 | 0.00 |
February | 0.698630E+09 | 0.160580E+09 | 0.244476E+09 | 87203086.32 | 0.157273E+09 | 0.00 | 0.00 |
March | 0.537705E+09 | 0.141924E+09 | 0.186821E+09 | 34185410.24 | 0.152636E+09 | 0.00 | 0.00 |
April | 0.362672E+09 | 77596263.50 | 0.127282E+09 | 128142.59 | 0.127154E+09 | 0.00 | 0.00 |
May | 0.383148E+09 | 80473978.64 | 0.131541E+09 | 0.00 | 0.131541E+09 | 0.00 | 0.00 |
June | 0.367077E+09 | 84765740.45 | 0.126840E+09 | 0.00 | 0.126840E+09 | 0.00 | 0.00 |
July | 0.378366E+09 | 0.104226E+09 | 0.135019E+09 | 0.00 | 0.135019E+09 | 0.00 | 0.00 |
August | 0.333891E+09 | 92402624.51 | 0.131603E+09 | 364283.72 | 0.131239E+09 | 0.00 | 0.00 |
September | 0.402362E+09 | 96946274.88 | 0.143047E+09 | 6824098.16 | 0.136223E+09 | 0.00 | 0.00 |
October | 0.518359E+09 | 0.119586E+09 | 0.197101E+09 | 37077754.33 | 0.160023E+09 | 0.00 | 0.00 |
November | 0.677812E+09 | 0.143400E+09 | 0.245230E+09 | 78750983.49 | 0.166479E+09 | 0.00 | 0.00 |
December | 0.853479E+09 | 0.209134E+09 | 0.307695E+09 | 0.132978E+09 | 0.174718E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.637727E+10 | 0.150957E+10 | 0.228695E+10 | 0.510493E+09 | 0.177646E+10 | 0.00 | 0.00 |
Minimum of Months | 0.333891E+09 | 77596263.50 | 0.126840E+09 | 0.00 | 0.126840E+09 | 0.00 | 0.00 |
Maximum of Months | 0.863776E+09 | 0.209134E+09 | 0.310298E+09 | 0.132981E+09 | 0.177317E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.190169E+10 | -0.138734E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -514340426.0 | 58.99 | 0.00 | 0.00 |
February | 0.171975E+10 | -0.125525E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -464499596.2 | 58.99 | 0.00 | 0.00 |
March | 0.191598E+10 | -0.140188E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -514105376.0 | 58.99 | 0.00 | 0.00 |
April | 0.180139E+10 | -0.130407E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -497326804.5 | 58.99 | 0.00 | 0.00 |
May | 0.183410E+10 | -0.132031E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -513788891.8 | 58.99 | 0.00 | 0.00 |
June | 0.177217E+10 | -0.127513E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -497042323.9 | 58.99 | 0.00 | 0.00 |
July | 0.178649E+10 | -0.127250E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -513985105.5 | 58.99 | 0.00 | 0.00 |
August | 0.183685E+10 | -0.132281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -514045961.6 | 58.99 | 0.00 | 0.00 |
September | 0.177755E+10 | -0.128001E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -497535534.8 | 58.99 | 0.00 | 0.00 |
October | 0.184652E+10 | -0.133229E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -514229510.5 | 58.99 | 0.00 | 0.00 |
November | 0.180888E+10 | -0.131114E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -497738532.6 | 58.99 | 0.00 | 0.00 |
December | 0.189694E+10 | -0.138260E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -514339623.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.218983E+11 | -0.158453E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.605298E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.171975E+10 | -0.140188E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -514340426.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.191598E+10 | -0.125525E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -464499596.2 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 350.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 361.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 376.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 370.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 357.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 356.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 349.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4292.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1 HEATING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2 HEATING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3 HEATING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4 HEATING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER HEATING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1 COOLING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.379207E+11 | 0.293844E+11 | 52434.50 | 09-JAN-21:06 | 37351.76 | 0.00 |
February | 0.00 | 0.00 | 0.383555E+11 | 0.300503E+11 | 52327.77 | 14-FEB-23:03 | 38448.45 | 0.00 |
March | 0.00 | 0.00 | 0.477470E+11 | 0.365769E+11 | 52818.52 | 27-MAR-04:43 | 36517.29 | 0.00 |
April | 0.00 | 0.00 | 0.521946E+11 | 0.383438E+11 | 53066.24 | 20-APR-22:03 | 35306.55 | 0.00 |
May | 0.00 | 0.00 | 0.590742E+11 | 0.415696E+11 | 53532.61 | 28-MAY-21:23 | 33243.47 | 0.00 |
June | 0.00 | 0.00 | 0.622065E+11 | 0.444474E+11 | 53489.10 | 10-JUN-02:43 | 35220.01 | 0.00 |
July | 0.00 | 0.00 | 0.504339E+11 | 0.379723E+11 | 52738.38 | 07-JUL-20:08 | 37166.95 | 0.00 |
August | 0.00 | 0.00 | 0.517983E+11 | 0.354838E+11 | 53412.89 | 25-AUG-02:43 | 34608.15 | 0.00 |
September | 0.00 | 0.00 | 0.473204E+11 | 0.332382E+11 | 52992.63 | 18-SEP-20:08 | 36102.60 | 0.00 |
October | 0.00 | 0.00 | 0.429493E+11 | 0.297974E+11 | 53013.22 | 27-OCT-20:08 | 36034.66 | 0.00 |
November | 0.00 | 0.00 | 0.398564E+11 | 0.288387E+11 | 53048.32 | 11-NOV-19:10 | 36166.33 | 0.00 |
December | 0.00 | 0.00 | 0.372808E+11 | 0.280920E+11 | 53137.30 | 18-DEC-21:10 | 36356.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.567138E+12 | 0.413795E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.372808E+11 | 0.280920E+11 | 52327.77 | 33243.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.622065E+11 | 0.444474E+11 | 53532.61 | 38448.45 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2 COOLING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.180636E+12 | 0.122970E+12 | 242616.70 | 09-JAN-21:08 | 141221.40 | 0.00 |
February | 0.00 | 0.00 | 0.176705E+12 | 0.120807E+12 | 241654.56 | 15-FEB-21:08 | 144177.03 | 0.00 |
March | 0.00 | 0.00 | 0.214037E+12 | 0.144629E+12 | 241203.05 | 24-MAR-20:08 | 145811.74 | 0.00 |
April | 0.00 | 0.00 | 0.230267E+12 | 0.144172E+12 | 245087.47 | 20-APR-20:10 | 135154.29 | 0.00 |
May | 0.00 | 0.00 | 0.248286E+12 | 0.144019E+12 | 248658.15 | 28-MAY-18:10 | 124648.57 | 0.00 |
June | 0.00 | 0.00 | 0.249047E+12 | 0.144160E+12 | 247979.74 | 03-JUN-21:10 | 126659.03 | 0.00 |
July | 0.00 | 0.00 | 0.206966E+12 | 0.129052E+12 | 243535.97 | 07-JUL-20:10 | 138180.15 | 0.00 |
August | 0.00 | 0.00 | 0.232502E+12 | 0.131483E+12 | 246932.27 | 14-AUG-20:08 | 130484.22 | 0.00 |
September | 0.00 | 0.00 | 0.219922E+12 | 0.127800E+12 | 245414.91 | 18-SEP-20:10 | 132581.10 | 0.00 |
October | 0.00 | 0.00 | 0.208735E+12 | 0.121200E+12 | 245282.35 | 14-OCT-21:10 | 133555.48 | 0.00 |
November | 0.00 | 0.00 | 0.192031E+12 | 0.117750E+12 | 244066.79 | 07-NOV-21:08 | 137572.62 | 0.00 |
December | 0.00 | 0.00 | 0.183267E+12 | 0.119879E+12 | 244646.97 | 10-DEC-19:08 | 136210.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.254240E+13 | 0.156792E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.176705E+12 | 0.117750E+12 | 241203.05 | 124648.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.249047E+12 | 0.144629E+12 | 248658.15 | 145811.74 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3 COOLING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.321082E+11 | 0.247659E+11 | 32538.41 | 09-JAN-21:06 | 22398.70 | 0.00 |
February | 0.00 | 0.00 | 0.302085E+11 | 0.232797E+11 | 32373.66 | 14-FEB-21:06 | 22848.73 | 0.00 |
March | 0.00 | 0.00 | 0.335156E+11 | 0.249465E+11 | 32519.86 | 28-MAR-22:03 | 23130.99 | 0.00 |
April | 0.00 | 0.00 | 0.328105E+11 | 0.227676E+11 | 32960.86 | 20-APR-20:08 | 20568.09 | 0.00 |
May | 0.00 | 0.00 | 0.353373E+11 | 0.230840E+11 | 33303.66 | 28-MAY-21:23 | 19566.55 | 0.00 |
June | 0.00 | 0.00 | 0.350176E+11 | 0.228606E+11 | 33309.89 | 04-JUN-18:08 | 19998.66 | 0.00 |
July | 0.00 | 0.00 | 0.296919E+11 | 0.207462E+11 | 32704.82 | 15-JUL-21:08 | 22156.95 | 0.00 |
August | 0.00 | 0.00 | 0.323575E+11 | 0.206657E+11 | 33112.41 | 06-AUG-18:08 | 20419.37 | 0.00 |
September | 0.00 | 0.00 | 0.317297E+11 | 0.211034E+11 | 32914.35 | 23-SEP-21:08 | 21455.36 | 0.00 |
October | 0.00 | 0.00 | 0.315422E+11 | 0.211847E+11 | 32938.15 | 25-OCT-20:08 | 21178.13 | 0.00 |
November | 0.00 | 0.00 | 0.315377E+11 | 0.224611E+11 | 32779.64 | 12-NOV-19:08 | 21584.97 | 0.00 |
December | 0.00 | 0.00 | 0.321263E+11 | 0.241619E+11 | 32610.41 | 10-DEC-19:42 | 23052.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.387983E+12 | 0.272027E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.296919E+11 | 0.206657E+11 | 32373.66 | 19566.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.353373E+11 | 0.249465E+11 | 33309.89 | 23130.99 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4 COOLING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.285534E+11 | 0.213749E+11 | 29727.88 | 09-JAN-21:06 | 19327.27 | 0.00 |
February | 0.00 | 0.00 | 0.270218E+11 | 0.202223E+11 | 29559.37 | 14-FEB-21:42 | 20398.96 | 0.00 |
March | 0.00 | 0.00 | 0.297216E+11 | 0.214055E+11 | 29639.53 | 27-MAR-20:42 | 20199.63 | 0.00 |
April | 0.00 | 0.00 | 0.292065E+11 | 0.194764E+11 | 30174.26 | 20-APR-20:08 | 17634.17 | 0.00 |
May | 0.00 | 0.00 | 0.316473E+11 | 0.197688E+11 | 30409.86 | 28-MAY-18:08 | 16840.74 | 0.00 |
June | 0.00 | 0.00 | 0.314890E+11 | 0.196629E+11 | 30429.95 | 28-JUN-20:08 | 16964.02 | 0.00 |
July | 0.00 | 0.00 | 0.260829E+11 | 0.174659E+11 | 29859.00 | 06-JUL-20:08 | 19080.30 | 0.00 |
August | 0.00 | 0.00 | 0.285441E+11 | 0.173265E+11 | 30250.68 | 06-AUG-18:08 | 17576.38 | 0.00 |
September | 0.00 | 0.00 | 0.281933E+11 | 0.179130E+11 | 30089.66 | 22-SEP-20:08 | 18313.75 | 0.00 |
October | 0.00 | 0.00 | 0.277833E+11 | 0.178203E+11 | 30132.20 | 25-OCT-20:08 | 18084.38 | 0.00 |
November | 0.00 | 0.00 | 0.280464E+11 | 0.192178E+11 | 29960.94 | 30-NOV-21:08 | 18675.26 | 0.00 |
December | 0.00 | 0.00 | 0.285604E+11 | 0.207871E+11 | 29767.84 | 11-DEC-21:08 | 19325.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.344850E+12 | 0.232441E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.260829E+11 | 0.173265E+11 | 29559.37 | 16840.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.316473E+11 | 0.214055E+11 | 30429.95 | 20398.96 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATER FAN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.473291E+10 | 0.82 | 2675.91 | 01-JAN-08:40 | 0.89 |
February | 0.435505E+10 | 0.83 | 2675.91 | 01-FEB-07:30 | 0.89 |
March | 0.496359E+10 | 0.84 | 2675.91 | 01-MAR-06:50 | 0.89 |
April | 0.487305E+10 | 0.84 | 2675.91 | 01-APR-05:50 | 0.89 |
May | 0.511241E+10 | 0.84 | 2675.91 | 01-MAY-06:40 | 0.88 |
June | 0.504538E+10 | 0.84 | 2675.91 | 01-JUN-05:10 | 0.89 |
July | 0.496907E+10 | 0.84 | 2675.91 | 01-JUL-05:50 | 0.88 |
August | 0.500221E+10 | 0.83 | 2675.91 | 01-AUG-08:70 | 0.88 |
September | 0.476295E+10 | 0.83 | 2675.91 | 01-SEP-06:20 | 0.88 |
October | 0.479274E+10 | 0.81 | 2675.91 | 01-OCT-07:50 | 0.89 |
November | 0.459533E+10 | 0.82 | 2675.91 | 01-NOV-10:20 | 0.89 |
December | 0.471208E+10 | 0.81 | 2675.91 | 01-DEC-08:40 | 0.89 |
Annual Sum or Average | 0.579168E+11 | 0.83 | |||
Minimum of Months | 0.435505E+10 | 0.81 | 2675.91 | 0.88 | |
Maximum of Months | 0.511241E+10 | 0.84 | 2675.91 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.270609E+11 | 1.24 | 15666.01 | 01-JAN-09:40 | 1.37 |
February | 0.246846E+11 | 1.26 | 15666.01 | 01-FEB-06:10 | 1.38 |
March | 0.279235E+11 | 1.27 | 15666.01 | 01-MAR-07:00 | 1.37 |
April | 0.271521E+11 | 1.26 | 15666.01 | 01-APR-11:07 | 1.37 |
May | 0.280621E+11 | 1.26 | 15666.01 | 01-MAY-11:20 | 1.37 |
June | 0.274187E+11 | 1.27 | 15666.01 | 01-JUN-05:30 | 1.37 |
July | 0.274434E+11 | 1.26 | 15666.01 | 01-JUL-06:20 | 1.37 |
August | 0.279164E+11 | 1.23 | 15666.01 | 02-AUG-06:50 | 1.37 |
September | 0.268445E+11 | 1.25 | 15666.01 | 01-SEP-06:10 | 1.37 |
October | 0.272870E+11 | 1.23 | 15666.01 | 02-OCT-05:30 | 1.37 |
November | 0.262475E+11 | 1.24 | 15666.01 | 01-NOV-08:40 | 1.37 |
December | 0.271028E+11 | 1.23 | 15666.01 | 01-DEC-08:62 | 1.37 |
Annual Sum or Average | 0.325143E+12 | 1.25 | |||
Minimum of Months | 0.246846E+11 | 1.23 | 15666.01 | 1.37 | |
Maximum of Months | 0.280621E+11 | 1.27 | 15666.01 | 1.38 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.290397E+10 | 0.87 | 1607.01 | 02-JAN-06:20 | 0.92 |
February | 0.264724E+10 | 0.87 | 1607.01 | 25-FEB-08:40 | 0.93 |
March | 0.297490E+10 | 0.88 | 1607.01 | 03-MAR-08:00 | 0.93 |
April | 0.286387E+10 | 0.87 | 1607.01 | 01-APR-05:20 | 0.92 |
May | 0.296507E+10 | 0.87 | 1607.01 | 01-MAY-11:08 | 0.92 |
June | 0.288941E+10 | 0.88 | 1607.01 | 01-JUN-05:30 | 0.92 |
July | 0.287982E+10 | 0.87 | 1607.01 | 11-JUL-08:00 | 0.92 |
August | 0.292881E+10 | 0.86 | 1607.01 | 01-AUG-14:00 | 0.92 |
September | 0.282700E+10 | 0.87 | 1607.01 | 01-SEP-05:50 | 0.92 |
October | 0.288500E+10 | 0.86 | 1607.01 | 02-OCT-07:00 | 0.92 |
November | 0.279624E+10 | 0.86 | 1607.01 | 01-NOV-06:10 | 0.92 |
December | 0.289772E+10 | 0.87 | 1607.01 | 01-DEC-06:20 | 0.93 |
Annual Sum or Average | 0.344591E+11 | 0.87 | |||
Minimum of Months | 0.264724E+10 | 0.86 | 1607.01 | 0.92 | |
Maximum of Months | 0.297490E+10 | 0.88 | 1607.01 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.254030E+10 | 0.87 | 1409.86 | 02-JAN-09:50 | 0.92 |
February | 0.231761E+10 | 0.87 | 1409.86 | 01-FEB-08:03 | 0.93 |
March | 0.260025E+10 | 0.87 | 1409.86 | 01-MAR-19:50 | 0.92 |
April | 0.250373E+10 | 0.87 | 1409.86 | 02-APR-08:20 | 0.92 |
May | 0.259755E+10 | 0.87 | 1409.86 | 04-MAY-14:00 | 0.92 |
June | 0.253230E+10 | 0.87 | 1409.86 | 01-JUN-05:20 | 0.92 |
July | 0.251921E+10 | 0.87 | 1409.86 | 02-JUL-07:50 | 0.92 |
August | 0.255939E+10 | 0.85 | 1409.86 | 01-AUG-06:20 | 0.92 |
September | 0.247446E+10 | 0.86 | 1409.86 | 08-SEP-07:40 | 0.92 |
October | 0.252040E+10 | 0.86 | 1409.86 | 02-OCT-08:15 | 0.92 |
November | 0.244653E+10 | 0.86 | 1409.86 | 01-NOV-18:40 | 0.92 |
December | 0.253463E+10 | 0.87 | 1409.86 | 02-DEC-20:00 | 0.92 |
Annual Sum or Average | 0.301464E+11 | 0.87 | |||
Minimum of Months | 0.231761E+10 | 0.85 | 1409.86 | 0.92 | |
Maximum of Months | 0.260025E+10 | 0.87 | 1409.86 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.167819E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.165995E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.201719E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.213337E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.234306E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.241062E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.205163E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.208498E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.193765E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.180683E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.170194E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.164596E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.234714E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.164596E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.241062E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.842212E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.808943E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.960972E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.992302E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.104458E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.103585E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.914426E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.980931E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.936934E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.907456E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.853681E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.843809E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.111221E+13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.808943E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.104458E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.121560E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.114415E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.128445E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.125223E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.132350E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.130203E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.114873E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.121638E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.119045E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.118515E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.117669E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.120684E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.146462E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.114415E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.132350E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.107719E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.101823E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.113536E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.110863E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.117653E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.116081E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.100830E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.106879E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.105245E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.104085E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.104189E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.106893E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.129580E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.100830E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.117653E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.473291E+10 | 0.379207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.435505E+10 | 0.383555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.496359E+10 | 0.477470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.487305E+10 | 0.521946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.511241E+10 | 0.590742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.504538E+10 | 0.622065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.496907E+10 | 0.504339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.500221E+10 | 0.517983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.476295E+10 | 0.473204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.479274E+10 | 0.429493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.459533E+10 | 0.398564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.471208E+10 | 0.372808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.579168E+11 | 0.567138E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.435505E+10 | 0.372808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511241E+10 | 0.622065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.270609E+11 | 0.180636E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246846E+11 | 0.176705E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.279235E+11 | 0.214037E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.271521E+11 | 0.230267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.280621E+11 | 0.248286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.274187E+11 | 0.249047E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.274434E+11 | 0.206966E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.279164E+11 | 0.232502E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.268445E+11 | 0.219922E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.272870E+11 | 0.208735E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262475E+11 | 0.192031E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271028E+11 | 0.183267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.325143E+12 | 0.254240E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.246846E+11 | 0.176705E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.280621E+11 | 0.249047E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.290397E+10 | 0.321082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264724E+10 | 0.302085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.297490E+10 | 0.335156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.286387E+10 | 0.328105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.296507E+10 | 0.353373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.288941E+10 | 0.350176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.287982E+10 | 0.296919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.292881E+10 | 0.323575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.282700E+10 | 0.317297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288500E+10 | 0.315422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279624E+10 | 0.315377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.289772E+10 | 0.321263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344591E+11 | 0.387983E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.264724E+10 | 0.296919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.297490E+10 | 0.353373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.254030E+10 | 0.285534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231761E+10 | 0.270218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.260025E+10 | 0.297216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.250373E+10 | 0.292065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.259755E+10 | 0.316473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.253230E+10 | 0.314890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.251921E+10 | 0.260829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.255939E+10 | 0.285441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.247446E+10 | 0.281933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.252040E+10 | 0.277833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.244653E+10 | 0.280464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253463E+10 | 0.285604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301464E+11 | 0.344850E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.231761E+10 | 0.260829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.260025E+10 | 0.316473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.473291E+10 | 0.00 | 0.00 | 0.00 | 0.120490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.435505E+10 | 0.00 | 0.00 | 0.00 | 0.122444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.496359E+10 | 0.00 | 0.00 | 0.00 | 0.152083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.487305E+10 | 0.00 | 0.00 | 0.00 | 0.164606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.511241E+10 | 0.00 | 0.00 | 0.00 | 0.183182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.504538E+10 | 0.00 | 0.00 | 0.00 | 0.190608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.496907E+10 | 0.00 | 0.00 | 0.00 | 0.155472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.500221E+10 | 0.00 | 0.00 | 0.00 | 0.158476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.476295E+10 | 0.00 | 0.00 | 0.00 | 0.146135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.479274E+10 | 0.00 | 0.00 | 0.00 | 0.132755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.459533E+10 | 0.00 | 0.00 | 0.00 | 0.124241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.471208E+10 | 0.00 | 0.00 | 0.00 | 0.117475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.579168E+11 | 0.00 | 0.00 | 0.00 | 0.176797E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.435505E+10 | 0.00 | 0.00 | 0.00 | 0.117475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511241E+10 | 0.00 | 0.00 | 0.00 | 0.190608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.270609E+11 | 0.00 | 0.00 | 0.00 | 0.571603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246846E+11 | 0.00 | 0.00 | 0.00 | 0.562097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.279235E+11 | 0.00 | 0.00 | 0.00 | 0.681738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.271521E+11 | 0.00 | 0.00 | 0.00 | 0.720781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.280621E+11 | 0.00 | 0.00 | 0.00 | 0.763955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.274187E+11 | 0.00 | 0.00 | 0.00 | 0.761662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.274434E+11 | 0.00 | 0.00 | 0.00 | 0.639992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.279164E+11 | 0.00 | 0.00 | 0.00 | 0.701766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.268445E+11 | 0.00 | 0.00 | 0.00 | 0.668489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.272870E+11 | 0.00 | 0.00 | 0.00 | 0.634586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262475E+11 | 0.00 | 0.00 | 0.00 | 0.591207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271028E+11 | 0.00 | 0.00 | 0.00 | 0.572781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.325143E+12 | 0.00 | 0.00 | 0.00 | 0.787066E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.246846E+11 | 0.00 | 0.00 | 0.00 | 0.562097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.280621E+11 | 0.00 | 0.00 | 0.00 | 0.763955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.290397E+10 | 0.00 | 0.00 | 0.00 | 0.925199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264724E+10 | 0.00 | 0.00 | 0.00 | 0.879429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.297490E+10 | 0.00 | 0.00 | 0.00 | 0.986964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.286387E+10 | 0.00 | 0.00 | 0.00 | 0.965847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.296507E+10 | 0.00 | 0.00 | 0.00 | 0.102699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.288941E+10 | 0.00 | 0.00 | 0.00 | 0.101309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.287982E+10 | 0.00 | 0.00 | 0.00 | 0.860750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.292881E+10 | 0.00 | 0.00 | 0.00 | 0.923497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.282700E+10 | 0.00 | 0.00 | 0.00 | 0.907748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288500E+10 | 0.00 | 0.00 | 0.00 | 0.896648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279624E+10 | 0.00 | 0.00 | 0.00 | 0.897068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.289772E+10 | 0.00 | 0.00 | 0.00 | 0.917065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344591E+11 | 0.00 | 0.00 | 0.00 | 0.112003E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.264724E+10 | 0.00 | 0.00 | 0.00 | 0.860750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.297490E+10 | 0.00 | 0.00 | 0.00 | 0.102699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.254030E+10 | 0.00 | 0.00 | 0.00 | 0.823165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231761E+10 | 0.00 | 0.00 | 0.00 | 0.786469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.260025E+10 | 0.00 | 0.00 | 0.00 | 0.875335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.250373E+10 | 0.00 | 0.00 | 0.00 | 0.858258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.259755E+10 | 0.00 | 0.00 | 0.00 | 0.916776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.253230E+10 | 0.00 | 0.00 | 0.00 | 0.907577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.251921E+10 | 0.00 | 0.00 | 0.00 | 0.756379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.255939E+10 | 0.00 | 0.00 | 0.00 | 0.812855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.247446E+10 | 0.00 | 0.00 | 0.00 | 0.805009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.252040E+10 | 0.00 | 0.00 | 0.00 | 0.788812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.244653E+10 | 0.00 | 0.00 | 0.00 | 0.797239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253463E+10 | 0.00 | 0.00 | 0.00 | 0.815466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301464E+11 | 0.00 | 0.00 | 0.00 | 0.994334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.231761E+10 | 0.00 | 0.00 | 0.00 | 0.756379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.260025E+10 | 0.00 | 0.00 | 0.00 | 0.916776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.885745E+10 | 0.00 | 0.00 | 1523849.96 | 0.00 | 0.00 | 0.00 | 0.24 |
February | 0.00 | 0.910805E+10 | 0.00 | 18702.24 | 2654363.60 | 0.00 | 3614.17 | 0.00 | 0.25 |
March | 0.00 | 0.112472E+11 | 0.00 | 0.00 | 1822267.11 | 0.00 | 0.00 | 0.00 | 0.25 |
April | 0.00 | 0.141663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
May | 0.00 | 0.171269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.174524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.127086E+11 | 0.00 | 0.00 | 1468561.78 | 0.00 | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.154007E+11 | 0.00 | 0.00 | 4898214.51 | 0.00 | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.142295E+11 | 0.00 | 0.00 | 3056410.27 | 0.00 | 0.00 | 0.00 | 0.25 |
October | 0.00 | 0.130628E+11 | 0.00 | 0.00 | 9648543.92 | 0.00 | 0.00 | 0.00 | 0.24 |
November | 0.00 | 0.112153E+11 | 0.00 | 0.00 | 2596614.18 | 0.00 | 0.00 | 0.00 | 0.24 |
December | 0.00 | 0.950603E+10 | 0.00 | 827.27 | 3661763.96 | 0.00 | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.00 | 0.154081E+12 | 0.00 | 19529.51 | 31330589.28 | 0.00 | 3614.17 | 0.00 | 0.25 |
Minimum of Months | 0.00 | 0.885745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.00 | 0.174524E+11 | 0.00 | 18702.24 | 9648543.92 | 0.00 | 3614.17 | 0.00 | 0.27 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.635933E+11 | 0.00 | 245962.23 | 0.255607E+09 | 0.00 | 3139342.54 | 0.00 | 0.46 |
February | 0.00 | 0.650831E+11 | 0.00 | 0.00 | 0.120151E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
March | 0.00 | 0.816981E+11 | 0.00 | 0.00 | 62373209.56 | 0.00 | 0.00 | 0.00 | 0.47 |
April | 0.00 | 0.100787E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
May | 0.00 | 0.118670E+12 | 0.00 | 0.00 | 61240890.55 | 0.00 | 0.00 | 0.00 | 0.48 |
June | 0.00 | 0.118788E+12 | 0.00 | 0.00 | 56697302.49 | 0.00 | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.853723E+11 | 0.00 | 0.00 | 0.293031E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.108809E+12 | 0.00 | 0.00 | 0.193335E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.100700E+12 | 0.00 | 0.00 | 0.106797E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.935230E+11 | 0.00 | 0.00 | 0.278390E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
November | 0.00 | 0.800893E+11 | 0.00 | 0.00 | 0.120328E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
December | 0.00 | 0.684352E+11 | 0.00 | 24323.39 | 0.116198E+09 | 0.00 | 308481.83 | 0.00 | 0.46 |
Annual Sum or Average | 0.00 | 0.108555E+13 | 0.00 | 270285.62 | 0.166415E+10 | 0.00 | 3447824.37 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.635933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.00 | 0.118788E+12 | 0.00 | 245962.23 | 0.293031E+09 | 0.00 | 3139342.54 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.728798E+10 | 0.00 | 0.00 | 2034565.77 | 0.00 | 0.00 | 0.00 | 0.48 |
February | 0.00 | 0.728392E+10 | 0.00 | 0.00 | 2169046.74 | 0.00 | 0.00 | 0.00 | 0.48 |
March | 0.00 | 0.869336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
April | 0.00 | 0.104458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
May | 0.00 | 0.123697E+11 | 0.00 | 0.00 | 860619.05 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.123053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.905827E+10 | 0.00 | 0.00 | 1136069.47 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.112848E+11 | 0.00 | 0.00 | 2703357.07 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.106931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.101826E+11 | 0.00 | 0.00 | 1172192.59 | 0.00 | 0.00 | 0.00 | 0.47 |
November | 0.00 | 0.899927E+10 | 0.00 | 0.00 | 2175803.35 | 0.00 | 0.00 | 0.00 | 0.47 |
December | 0.00 | 0.786184E+10 | 0.00 | 0.00 | 2102505.46 | 0.00 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.00 | 0.116466E+12 | 0.00 | 0.00 | 14354159.50 | 0.00 | 0.00 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.728392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.00 | 0.123697E+11 | 0.00 | 0.00 | 2703357.07 | 0.00 | 0.00 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.714609E+10 | 0.00 | 0.00 | 2033168.81 | 0.00 | 0.00 | 0.00 | 0.47 |
February | 0.00 | 0.717173E+10 | 0.00 | 0.00 | 2178456.79 | 0.00 | 0.00 | 0.00 | 0.48 |
March | 0.00 | 0.848248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
April | 0.00 | 0.101741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
May | 0.00 | 0.120478E+11 | 0.00 | 0.00 | 851978.61 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.120191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.875706E+10 | 0.00 | 0.00 | 1142431.71 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.108719E+11 | 0.00 | 0.00 | 2508496.63 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.103761E+11 | 0.00 | 0.00 | 2340855.11 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.982035E+10 | 0.00 | 0.00 | 6636187.36 | 0.00 | 0.00 | 0.00 | 0.47 |
November | 0.00 | 0.877698E+10 | 0.00 | 0.00 | 2158052.34 | 0.00 | 0.00 | 0.00 | 0.47 |
December | 0.00 | 0.769300E+10 | 0.00 | 0.00 | 2083006.46 | 0.00 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.00 | 0.113337E+12 | 0.00 | 0.00 | 21932633.82 | 0.00 | 0.00 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.714609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.00 | 0.120478E+11 | 0.00 | 0.00 | 6636187.36 | 0.00 | 0.00 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.394019E+12 | -0.431550E+10 | 0.00 | -0.106698E+12 | 0.365912E+12 |
February | 0.399227E+12 | -0.436486E+10 | 0.00 | -0.107451E+12 | 0.357404E+12 |
March | 0.539035E+12 | -0.961809E+10 | 0.00 | -0.131834E+12 | 0.427026E+12 |
April | 0.545094E+12 | -0.970699E+10 | 0.00 | -0.163039E+12 | 0.451258E+12 |
May | 0.521114E+12 | -0.119861E+11 | 0.00 | -0.192697E+12 | 0.488496E+12 |
June | 0.533207E+12 | -0.113199E+11 | 0.00 | -0.189586E+12 | 0.492194E+12 |
July | 0.436104E+12 | -0.559266E+10 | 0.00 | -0.142337E+12 | 0.408892E+12 |
August | 0.564778E+12 | -0.100086E+11 | 0.00 | -0.177034E+12 | 0.448590E+12 |
September | 0.441057E+12 | -0.638903E+10 | 0.00 | -0.165209E+12 | 0.425755E+12 |
October | 0.471634E+12 | -0.586697E+10 | 0.00 | -0.156763E+12 | 0.404599E+12 |
November | 0.379227E+12 | -0.442468E+10 | 0.00 | -0.134201E+12 | 0.379959E+12 |
December | 0.367314E+12 | -0.359899E+10 | 0.00 | -0.114595E+12 | 0.367585E+12 |
Annual Sum or Average | 0.559181E+13 | -0.871924E+11 | 0.00 | -0.178145E+13 | 0.501767E+13 |
Minimum of Months | 0.367314E+12 | -0.119861E+11 | 0.00 | -0.192697E+12 | 0.357404E+12 |
Maximum of Months | 0.564778E+12 | -0.359899E+10 | 0.00 | -0.106698E+12 | 0.492194E+12 |